MEDIUM VOLTAGE ELECTRICAL SYSTEMS ELECTRICAL SYSTEMS for DATA CENTERS for DATA CENTERS Michael Mosman, PE Chief Technical Officer Chief Technical Officer CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED © CCG Facilities Integration Incorporated 15 September 2012

MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS

Embed Size (px)

Citation preview

Page 1: MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS

MEDIUM VOLTAGE ELECTRICAL SYSTEMSELECTRICAL SYSTEMS

for DATA CENTERSfor DATA CENTERS

Michael Mosman, PEChief Technical OfficerChief Technical Officer

CCG Facilities Integration Incorporated FACILITIES INTEGRATION

INCORPORATED

© CCG Facilities Integration Incorporated 15 September 2012

Page 2: MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS

INTRODUCTION

CCG Facilities Integration Incorporated:CCG Facilities Integration Incorporated:• Headquartered in Baltimore, MD since 1992.• An Engineering/Architecture firm specialized

in high-reliability facilities.• Engineer and Program Manager for hundreds

of data centers from 1 to 72 Megawatts.• Programmed facilities both within the USA

and internationally.• Developed or employed several electrical

system innovations for critical facilities,

MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS Page 2

including Isolated-Parallel UPS.

Page 3: MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS

AN OBSERVATION

The first choice for service andThe first choice for service and distribution voltage is 480 volts. Why? Traditional, safe design. Specs are already written around 480 V.p y UPS equipment is readily available at 480 V. Data centers are relatively compact for their Data centers are relatively compact for their

high power density, therefore don’t often require long runs at Medium Voltage forrequire long runs at Medium Voltage for voltage drop reasons like campus-wide electrical distribution systems

MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS Page 3

electrical distribution systems.

Page 4: MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS

TYPICAL COMMERCIAL DESIGN Utility service commonlyUTILITY Utility service, commonly

Medium Voltage. Pad-mounted step-down

UTILITYSERVICE

SERVICE Pad mounted step down service Transformer with LV underground secondary feeder.GDE

SERVICE TRANSFORMER

Main Switchboard with service main breaker.

MAIN SWB

Optional backup Diesel Engine-Generator and transfer devices.

ESSENTIALLOAD

UPS

Optional UPS system to carry critical loads through switching t f

CRITICALLOAD

MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS Page 4

transfers.

Page 5: MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS

LARGE LOW VOLTAGE DATA CENTERLarge Low Voltage electrical systems are certainlyLarge Low Voltage electrical systems are certainly possible, as in this 36 MW critical load data center.

32 UPS SYSTEMSSYSTEMS @ 600V, 1.33 MW

TWO UTILITY SERVICES

@ 35 kV, 30 MW

32 DIESEL ENGINE 16 SERVICE TRANSFORMERS

MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS Page 5

32 DIESEL ENGINE-GENERATORS @ 2.25 MW

16 SERVICE TRANSFORMERS @ 600 V, 5 MVA

Page 6: MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS

MEDIUM VOLTAGE APPLICATION

Where are Medium Voltage distributionWhere are Medium Voltage distribution systems typically considered? In campus distribution where service runs

are quite long. At Engine-Generator Switchgear when

they are paralleled in massive numbers y pfor capacity. In high-rise buildings where shaft space isIn high rise buildings where shaft space is

a premium. NEVER in a computer room

MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS Page 6

NEVER in a computer room.

Page 7: MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS

MEDIUM VOLTAGE APPLICATION

What are the perceptions of MediumWhat are the perceptions of Medium Voltage switchgear when compared to Low Voltage switchboards? More expensive.

Low Voltage switchboards? Less reliable.

More dangerous. Harder to maintain

Not as flexible. Needs more space Harder to maintain.

However, recent advancements in the

Needs more space.

However, recent advancements in the technology of certain Medium Voltage equipment are changing the realityMEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS Page 7

equipment are changing the reality…

Page 8: MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS

LINEAR ACTUATED MV BREAKERS Relatively new on market Relatively new on market. Have the “look and feel” of

Low Voltage breakers.g Can have integral trip units. Can be found in 5kV, 15kV

and 25kV Class. Fast tripping, typically 50ms. Far fewer moving parts. Endurance tests indicate

they may operate up tothey may operate up to 100,000 times without failure of breaker operating

MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS Page 8

p gmechanisms.

Page 9: MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS

FRONT ACCESSIBLE SWITCHGEAR New enclosure architectureNew enclosure architecture

requires ⅔ the space of traditional MV switchgear,

ll i f i i leven allowing for minimal space behind switchgear.

Flexibility nearly equal to LV Flexibility nearly equal to LV switchboards.

Can be built with arc containment enclosures that vent explosive gas out the top or to the building

1.5’

5’FRONT ACCESS3.5’

top or to the building exterior.

Less costly than traditional

5

5’

FRONT ACCESSMV SWITCHGEAR

TRADITIONALMV SWITCHGEAR 8’

6’

MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS Page 9

Less costly than traditional switchgear.

6

Page 10: MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS

UPGRADED DISTRIBUTION TRANSFORMERS New class of liquid-cooledNew class of liquid cooled

transformers incorporated into unit substations.

High flash point, biodegradable fluid (FR3®) safe for indoor applicationsafe for indoor application.

High BIL (150 kV) suitable for vacuum breaker control without snubbers.

Internal, fluid-immersed i d i hiprotection and switching.

High efficiency, 99% or better

MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS Page 10

better.Photos courtesy of Cooper Power Systems

Page 11: MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS

TYPICAL LV & MV SYSTEMSUTILITY

SERVICEUTILITY

SERVICE

GDE

SERVICE

SERVICE TRANSFORMER GDE

SERVICE

SERVICE TRANSFORMER

MAIN SWBD MAIN SWGR

DISTRIBUTION TRANSFORMERS

ESSENTIALLOAD

UPS

CRITICALESSENTIAL

LOAD

UPS

(IN UNIT SUBSTATIONS)

LOADLOAD

CRITICALLOAD

TYPICAL 480 VOLT SYSTEM TYPICAL 4I60 VOLT SYSTEMTYPICAL 480 VOLT SYSTEM2500 kVA SERVICE TRANSFORMERSECONDARY: 277/480 V, 3-PH, 4-W

2000 kW, 480 V STANDBY E-G

TYPICAL 4I60 VOLT SYSTEM2500 kVA SERVICE TRANSFORMER

SECONDARY: 4160 V, 3-PH, 3-W2000 kW STANDBY E-G

MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS Page 11

4000 AMP SWITCHBOARDw/ 4000 A INSULATED CASE MAIN

1200 AMP SWITCHGEARw/ 600 A VACUUM BREAKER MAIN

Page 12: MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS

COST COMPARISON #1 - FEEDERSThe greatest cost difference between systemsThe greatest cost difference between systems is in the feeders. Both of these service entrance ductbanks are rated 2500 kVA.

VS

4160 VOLT 3-PHASE 3-WIRE480 VOLT 3-PHASE 4-WIRE

VS

4160 VOLT, 3-PHASE, 3-WIRE500 AMP, 75’ LONG

(3) 500kCM 5kV XLPE in 5” PVC75’ of 5” PVC

480 VOLT, 3-PHASE, 4-WIRE4000 AMP, 75’ LONG

(8) SETS: (4) 750kCM XHHW in 4” PVC600’ of 4” PVC

180’ of 500kCM CU SHIELDED CABLE2 CU YD of CONCRETE(6) 5 kV TERMINATIONS

$9 000*

2720’ of 750kCM CU WIRE6 CU YD of CONCRETE

(64) 600 V TERMINATIONS$67 000*

MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS Page 12

$9,000$67,000* INCL. LABOR, MATERIAL, O&P (YOUR MILEAGE MAY VARY)

Page 13: MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS

COST COMPARISON #2 - SYSTEMSTYPICAL 480 VOLT SYSTEM TYPICAL 4I60 VOLT SYSTEMVS

ENGINE-GENERATOR:2000 kVA, 4160 V

$700k

ENGINE-GENERATOR:2000 kVA, 480 V

$650k

TYPICAL 480 VOLT SYSTEM TYPICAL 4I60 VOLT SYSTEMVS

$700kSWITCHGEAR LINEUP:

1200 A, 4160 V, w/ MAIN BKR,EG BKR & (2) FDR BKRS

$650kSWITCHBOARD:

4000 A, 480 V, w/ MAIN BKR,EG BKR & (2) FDR BKRS

$250kMAJOR FEEDERS:

75’ 500 A MAIN FDR, 100’ 500 A EG FDR &

$350kMAJOR FEEDERS:

75’ 4000 A MAIN FDR, 100’ 3000 A EG FDR, 100 500 A EG FDR &

150’ of LOAD FDRS @ 250 A$50k

DISTR. TRANSFORMERS:1500 kVA 480 V

100 3000 A EG FDR,100’ 1200 A LOAD FDR &50’ 2000 A LOAD FDR

$200kDISTR TRANSFORMERS 1500 kVA 480 V

1000 kVA 480 V$100k

_____________

$1 100k

DISTR. TRANSFORMERS:NONE

_____________

$1 200k

MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS Page 13

$1,100k$1,200k

Page 14: MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS

COST COMPARISON #3 – LARGE SYSTEMSLarge systems allow transformer consolidation.

35 kV OUTDOOR SWITCHGEAR

UTILITY SERVICE35 kV, 15 MVA

UTILITY SERVICE35 kV, 15 MVA

15 MVAVS

Large systems allow transformer consolidation.

4160 V OUTDOOR SWITCHGEAR

35 kV OUTDOOR SWITCHGEAR

(6) 2500 kVA

15 MVAVS

MAIN SWGR

MAIN SWGR

MAIN SWGR

MAIN SWGR

MAIN SWGR

MAIN SWGR

MAIN SWBD

MAIN SWBD

MAIN SWBD

MAIN SWBD

MAIN SWBD

MAIN SWBD4160 V

(TYPICAL)

(1) 35 kV SWGR, 1200 A: $450k(6) 35 kV FDRs, 200 A, 150’: $80k

$

(1) 15 MVA TRANSF, 4160V: $250k(1) 5 kV SWGR, 3000 A: $550k(1) 3000 100 $20

MAIN SWGR MAIN SWGR MAIN SWGRMAIN SWBD MAIN SWBD MAIN SWBD (TYPICAL)

(6) 2500 kVA TRANSF, 480V: $400k(6) 480 V FDRs, 4000 A, 75’: $400k(6) TYPICAL 480 V SWBD &

DISTRIBUTION SYSTEM: $7 200k

(1) 5 kV FDR, 3000 A, 100’: $20k(6) 5 kV FDR’S, 500 A, 150’: $120k(6) TYPICAL 4160V SWGR &

DISTRIBUTION SYSTEM: $6 600k

MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS Page 14

DISTRIBUTION SYSTEM: $7,200kTOTAL $8,530k

DISTRIBUTION SYSTEM: $6,600kTOTAL $7,540k

Page 15: MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS

MEDIUM VOLTAGE ADVANTAGEBesides the cost advantage there are

Greater safety – lower arc flash

Besides the cost advantage, there are other reasons to consider MV systems:

Greater safety lower arc flash. Smaller footprint – new compact switchgear. Higher reliability longer lasting breakers Higher reliability – longer lasting breakers,

cooler running ductbanks. Lower maintenance simpler breakers Lower maintenance – simpler breakers,

fewer terminations. Greater flexibility choice of secondary Greater flexibility – choice of secondary

voltages, longer feeders without huge cost. Greener building less copper PVC steel

MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS Page 15

Greener building – less copper, PVC, steel.

Page 16: MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS

ARC FLASH SAFETY

Counterintuitive to common belief MVCounterintuitive to common belief, MV systems can have far less arc flash than equivalent power LV systems: Currents are lower in MV systems.equivalent power LV systems:

The new MV linear breakers are faster than LV breakers of equal power rating. Arc currents in MV systems are typically

closer to available fault levels than in LV t B k t i f t li blsystems. Breakers trip faster, more reliably.

Faster tripping + lower currents produce far l

MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS Page 16

less arc energy.

Page 17: MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS

ARC FLASH STUDYMAXIMUM ARCING FAULT CASE #1 (LV) CASE #2 (MV)Utility Characteristics 34.5kV, 750MVA, X/R = 8 34.5kV, 750MVA, X/R = 8

Primary Protection Vacuum fault interrupter, 400 A

Vacuum fault interrupter, 400 A

Service Transformer 2500 kVA 2500 kVA

Secondary Voltage 480 volt, 3-ph, 4-wire, grounded

4160 volt, 3-ph, 3-wire, grounded

Service Entrance Feeder 75' (8) 750kCM/ph, 600V XHHW in PVC

75' (1) 750kCM/ph, 5kV XLPE in PVC

Main Breaker(w/ integral long time & Insulated Case 4000A Solenoid-Actuated (w/ integral long time &short time electronic trip)

Insulated Case, 4000A Vacuum Bottle, 600A

Max Bolted 3-ph Fault Current 53.52 kA 6.41 kAMax Arcing Fault Current at Bus 25.47 kA 6.27 kAMax Arcing Fault Current at Bus 25.47 kA 6.27 kANormal Mode Arcing Time 0.4 seconds 0.4 seconds

Arc Flash Boundary Distance 180 inches 128 inches

Incident Energy 23 1 cal/cm² 4 1 cal/cm²

MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS Page 17

Incident Energy 23.1 cal/cm 4.1 cal/cm

PPE Category 3 1

Page 18: MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS

ARC FLASH STUDYLIMITED ARCING FAULT CASE #3 (LV) CASE #4 (MV)LIMITED ARCING FAULT CASE #3 (LV) CASE #4 (MV)

85% of Maximum Arcing Fault Current 21.65 kA 5.33 kA

A i Ti (@ 85% f lt) 1 0 d 0 4 dArcing Time (@ 85% fault) 1.0 seconds 0.4 seconds

Arc Flash Boundary Distance(@ 85% fault) 297 inches 107 inches

Incident Energy (@ 85% fault) 48.5 cal/cm² 3.5 cal/cm²

PPE Category (@ 85% fault) Dangerous 1

MAINTENANCE MODE CASE #5 (LV) CASE #6 (MV)MAINTENANCE MODE CASE #5 (LV) CASE #6 (MV)

Maintenance Mode Arcing Time (max. fault) 0.06 seconds 0.06 seconds

A Fl h B d Di tArc Flash Boundary Distance (maint. mode) 50 inches 18 inches

Incident Energy (maint. mode) 3.5 cal/cm² 0.6 cal/cm²

MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS Page 18

PPE Category (maint. mode) 1 0

Page 19: MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS

SWITCHGEAR FOOTPRINT

1.5’

5’FRONT ACCESSMV SWITCHGEAR

METAL-CLAD

3.5’

TYPICAL

3.5’

6’5’

METAL-CLADMV SWITCHGEAR 8’

TYPICALLV SWITCHGEAR

6

5’ 6’5’

F t ibl M di V ltFront accessible Medium Voltage switchgear is smaller than both t diti l t l l d it h ANDtraditional metal-clad switchgear AND Low Voltage switchboards of equivalent

MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS Page 19

power.

Page 20: MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS

DUCTBANK INTEGRITY

MUTUAL HEATING

NO MUTUAL HEATING

Multiple underground LV ductbanks close together (common in large facilities) can

NO MUTUAL HEATING

together (common in large facilities) can be destroyed by mutual heating.MV ductbanks are far less susceptible

MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS Page 20

MV ductbanks are far less susceptible.

Page 21: MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS

BREAKER EVALUATION600 volt breaker endurance testing switchboard w/four brands of insulated-case breakers, 9/2005.

5 kV b k5 kV breaker endurance testing switchgear lineup w/two metal-clad b k d tbreakers and two linear-actuator breakers, 2/2007.

MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS Page 21

Photos courtesy of Power Distribution Systems.

Page 22: MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS

BREAKER RELIABILITY

VS

600 VOLT INSULATED CASE BREAKERSQUARE D MASTERPACT NW

MV MAG-ACTUATED VACUUM BREAKERABB VM-1

Endurance test results: The best 480 V breaker performed nearly

25 000 i b f f il25,000 operations before failure. The best 4160 V breaker went over 70,000

ti b f t ti t dMEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS Page 22

operations before testing was stopped.

Page 23: MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS

MAINTAINABILITY

Linear actuator type Linear actuator type breakers have fewer parts, simpler construction than

YES

pmolded case LV breakers.

Medium Voltage switchgear have fewer bus connections and wire terminations than LVterminations than LV switchboards.

MV switchgear have lessMV switchgear have less heat related issues than LV switchboards.

NO

MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS Page 23

Page 24: MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS

FLEXIBILITY

4160 VOLT4160 VOLT MAINS & EG’s

230/400 V. UNIT SUBSTATION

600 V. UNIT SUBSTATION

Providing separate transformation for essential

MECHANICAL PLANT UPS SYSTEMS

Providing separate transformation for essential loads and critical loads allows the secondary voltage to be tailored to load requirements.g q

Medium Voltage main and generator feeders allow the distance to load to grow without huge increase

MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS Page 24

in cost and losses.

Page 25: MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS

SUSTAINABLE CONSTRUCTION?

MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS Page 25

Page 26: MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS

GREEN IDEAS

Eliminate 80% of the PVC and copper Eliminate 80% of the PVC and copper content in data center electrical distribution.R d t f h t l b 60% Reduce transformer heat losses by 60%, and major feeder losses by a factor of 50. Make electrical equipment rooms 25%

smaller and require less building structure. Bring total critical power losses between

utility grid and computer rack under 5% by:y g p y Developing 4160 volt UPS systems and, Using 4160 – 230/400 volt PDU’s in the

MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS Page 26

gcomputer room.

Page 27: MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS

THE TRULY GREEN DATA CENTERUTILITY SERVICE (GRID)

GDE

SERVICE TRANSFORMER WITH 4160V SECONDARY & 99%+ EFFICIENCY

STANDBY EG w/ 4160V ALTERNATOR

MAIN SWGR

4160V MAIN SERVICE SWITCHGEAR WITH FAST LINEAR BREAKERS AND LOW ARC FLASH4160-600V UNIT

UPS

SUBSTATION w/ 99%+ EFFICIENT TRANSFORMER FOR MECHANICAL

4160V UPS SYSTEM w/ 99% EFFICIENT ECONOMY MODE

ESSENTIALLOAD

600 VOLT

EQUIPMENT 4160-400/230V PDU’sw/ 98%+ EFFICIENT TRANSFORMERS

600 VOLT

CRITICALLOAD

400/230 VOLT

MECHANICAL PLANT USING FREE-AIR COOLING, HOT-AISLE CONTAINMENT AND OTHER

400/230V DISTRIBUTION TORACKS w/ 99%+ EFFICIENT BUSWAYS AND TAPS

MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS Page 27

400/230 VOLTCONTAINMENT AND OTHER ENERGY REDUCTION METHODS CRIT PWR LOSS = 5% MAX GRID TO RACK

Page 28: MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS

COMMENTS OR QUESTIONS?

If you have any comments or questions about this presentation please contact

Mi h l M PEMichael Mosman, PE [email protected]

or visit our websiteor visit our website www.ccgfacilities.com

FACILITIES INTEGRATIONINCORPORATED

MEDIUM VOLTAGE ELECTRICAL SYSTEMS FOR DATA CENTERS Page 28