Medium Vtg Substation Breakers

Embed Size (px)

Citation preview

  • 7/30/2019 Medium Vtg Substation Breakers

    1/4

    Medium Voltage

    Substation Circuit

    BreakersPowersubType EVR

    Vacuum Circuit Breaker

    EVR Breaker Model 0 EVR Breaker Model 1

  • 7/30/2019 Medium Vtg Substation Breakers

    2/4

    EVR Breaker - Model 1

    EVR Breaker - Model 0

    Breaker Legend, EVR - Model # 0 and 1

    1 - High Voltage Compartment (HV)

    2 - Low Voltage (Relay) Compartment (LV)

    3 - Adjustable Legs

    4 - Cable Termination Bushing

    5 - Current Transformers

    6 - Vacuum Interrupter Bottle

    7 - Mechanism

    8 - Auxiliary Switch

    9 - Control Mounting Panel

    10 - Removable Filter Vent Covers

    11 - Hinged Removable Door w/Padlockable Handles (HV

    12 - Hinged Removable Door w/Padlockable Handles (LV

    13 - Hinged Removable Door Fastened to Assembly

    14 - Rear Access Panel Fastened to Assembly (HV)

    15 - Vented Rear Access Panel Fastened to Assembly (L

    16 - Galvanized Base Channel

    Square D Services Medium Voltage Substation Circuit Breakers

    For over 100 years, Square D products rom Schneider Electric have been

    setting standards in quality or the electric industry and serving utilities with

    highly reliable products. By combining the latest developments in circuit

    breaker technology with world-renowned quality, the Powersub Type EVR

    Vacuum Substation Circuit Breakers rom Square D Services are the mostadvanced medium voltage circuit breakers available.

    Compliance to ANSI StandardsDesigned and tested to comply with or exceed ANSI and

    IEEE standards or outdoor circuit breakers.

    ISO 9001 CertifcationDesigned and manuactured in a acility that is Quality Systems

    Certifed by Underwriters Laboratories, Inc. to ISO 9001.

    Benefts

    High-speed operation

    Interrupting time o 3 cycles or less

    Long lieHermetically sealed interrupters protect contacts rom

    corroding elements and contamination.

    Ease o maintenanceInterrupter assemblies and contact wear indicators accessible via a

    bolted panel.

    ReliabilityA minimum o moving parts on the motor-driven, spring-charged

    Type RI mechanism.

    Durability

    Robust design tested to the highest IBC-2000 seismic standard.Other seismic standards may be evaluated upon request.

    FlexibilityStandard adjustable heights in 3 increments.

    Component CommonalityUtilizes Type RI operating mechanism / coils / motor, which are

    commonly used among many Square D medium voltage circuit breakers.

    Standard Features

    Window or viewing status indicators and operation counter.

    Ground pads located on both sides o breaker. A #4 cable connects

    rom the roo and HV/LV compartment to the ground pads to insure a

    solidly grounded enclosure. Painted adjustable legs with galvanized base channels.

    All external hardware is stainless steel.

    Optimized relay panel (32 5/8 W x 33 7/8 H) or instrumentation

    (model 1 only).

    12 pole auxiliary switch (6 a & 6 b contacts), latch check switch

    and emergency cutout switch standard.

    All outer doors latch open at approximately 120 degrees.

    Type RI mechanism with integral manual charging handle.

    Advanced Technology for Leading Reliability

    2

  • 7/30/2019 Medium Vtg Substation Breakers

    3/4

    3

    Powersub Type EVR Vacuum Circuit Breaker

    Powersub Type EVR Medium Voltage Substation Circuit Breaker

    Additional Features and Ratings

    15.5kV, 1200A, 25kA, 110kV BIL. 10,000 operations at load current. Breaker element is a modular design or ease

    o replacement.

    Total height adjustability o 24. Double bent roo gives greater phase to phase

    clearance while maintaining a small ootprint.

    One pad-lockable handle on each outer door. Hinged doors utilized on common access areas.

    The EVR is available with or without a relaycompartment. Model 0 does not have a relaycompartment, and is intended or applicationsin which the relay will be mounted remotely.Model 1 includes a relay compartment, and canbe provided with the relay o your choice.

    EVR Vacuum Circuit Breaker Ratings

    Substation CircuitBreaker Catalog

    Number

    VoltageMax.

    kV rms

    ShortCircuit

    CurrentkA rms

    RatedContinuous

    Current

    Max.Symmetrical

    InterruptingCapabilitykA rms

    LowFrequency

    WithstandkV rms

    Full WaveLightning

    ImpulseWithstandkV Crest

    2u secImpulse

    WithstandkV Crest

    RatedPermissible

    TrippingDelayY Seconds

    3 SecondCurrent

    CarryingCapabilitykA rms

    Close &Latching

    CapabilitykA Peak

    EVR 1 06 11 12

    15.5

    12.5

    600

    12.5

    50 110 142 2

    12.5 32EVR 1 08 11 12 800

    EVR 1 12 11 12 1200

    EVR 1 06 11 16

    16

    600

    16 16 43EVR 1 08 11 16 800

    EVR 1 12 11 16 1200

    EVR 1 06 11 20

    20

    600

    20 20 54EVR 1 08 11 20 800

    EVR 1 12 11 20 1200

    EVR 1 06 11 25

    25

    600

    25 25 68EVR 1 08 11 25 800

    EVR 1 12 11 25 1200

    Type

    Voltage Class Model

    Interrupting Rating

    BIL Rating

    Continuous Current Rating

    Square D Catalog Numbering Scheme (example)

    Catalog Number EVR 1 12 11 16 0

    Type Voltage Class Continous

    Current Rating

    BIL Rating Interrupting Rating Model

    EVR 1 = 15.5 kV 06 = 600 A

    08 = 800 A

    12 = 1200 A

    11 = 110 kV 12 = 12.5 kA

    16 = 16 kA

    20 = 20 kA

    25 = 25 kA

    0 = No relay compartment

    1 = With relay compartment

    Table 1: Catalog Numbering Scheme

  • 7/30/2019 Medium Vtg Substation Breakers

    4/4

    1910BR0901

    9870 Crescent Park DriveWest Chester, OH 45069Tel: 513-777-4445Fax: 513-755-5028

    Schneider Electric North American Operating Division

    8-09

    This document has beenprinted on recycled paper.

    Dimensions 15kV, 110 kV BIL Type EVR

    EVR (no relay compartment model 0) Notes:

    Approx. weight: 1850 lbs.

    All external hardware isstainless steel.

    All dimensions are in

    inches unless otherwisespecifed.

    Adjustable leg has rangeo 24 inches.

    Cross brace must beinstalled duringinstallation.

    All dimensions are typical.

    Diagrams are notor construction.

    EVR (with relay compartment model 1) Notes:

    Control panel with accessterminal blocks ismounted on right wall olow voltage compartment.

    Approx. weight: 2000 lbs.

    All external hardware isstainless steel.

    All dimensions are ininches unless otherwisespecifed.

    Adjustable leg has rangeo 24 inches.

    All dimensions are typical.

    Diagrams are notor construction.

    Why Choose Square D Services?

    Square D Services rom Schneider Electricoers a broad range o service solutions

    to support any manuacturers electricaldistribution equipment. Whether the solutionis reurbishment, replacement, maintenanceor recommendations to optimize your existingsystem, our nationwide network o qualifedexperts oers a complete service package.

    For more inormation call 888-SQUARED or visitus online at www.SquareD-Services.com.

    Breaker rear

    Control conduit

    entrance (3 x 8),customer installscutouts in coverplates as needed

    Control conduitentrance (3 x 8),customer installs

    cutouts in coverplates as needed

    Breaker ront oundation plan

    Breaker rear

    Control conduit

    entrance (8 x 14),customer installscutouts in cover

    plates as needed

    Control conduitentrance (8 x 14)Customer installcutouts in cover

    plates as needed

    Breaker ront oundation plan