Upload
shrikant-kajale
View
218
Download
0
Embed Size (px)
Citation preview
7/30/2019 Medium Vtg Substation Breakers
1/4
Medium Voltage
Substation Circuit
BreakersPowersubType EVR
Vacuum Circuit Breaker
EVR Breaker Model 0 EVR Breaker Model 1
7/30/2019 Medium Vtg Substation Breakers
2/4
EVR Breaker - Model 1
EVR Breaker - Model 0
Breaker Legend, EVR - Model # 0 and 1
1 - High Voltage Compartment (HV)
2 - Low Voltage (Relay) Compartment (LV)
3 - Adjustable Legs
4 - Cable Termination Bushing
5 - Current Transformers
6 - Vacuum Interrupter Bottle
7 - Mechanism
8 - Auxiliary Switch
9 - Control Mounting Panel
10 - Removable Filter Vent Covers
11 - Hinged Removable Door w/Padlockable Handles (HV
12 - Hinged Removable Door w/Padlockable Handles (LV
13 - Hinged Removable Door Fastened to Assembly
14 - Rear Access Panel Fastened to Assembly (HV)
15 - Vented Rear Access Panel Fastened to Assembly (L
16 - Galvanized Base Channel
Square D Services Medium Voltage Substation Circuit Breakers
For over 100 years, Square D products rom Schneider Electric have been
setting standards in quality or the electric industry and serving utilities with
highly reliable products. By combining the latest developments in circuit
breaker technology with world-renowned quality, the Powersub Type EVR
Vacuum Substation Circuit Breakers rom Square D Services are the mostadvanced medium voltage circuit breakers available.
Compliance to ANSI StandardsDesigned and tested to comply with or exceed ANSI and
IEEE standards or outdoor circuit breakers.
ISO 9001 CertifcationDesigned and manuactured in a acility that is Quality Systems
Certifed by Underwriters Laboratories, Inc. to ISO 9001.
Benefts
High-speed operation
Interrupting time o 3 cycles or less
Long lieHermetically sealed interrupters protect contacts rom
corroding elements and contamination.
Ease o maintenanceInterrupter assemblies and contact wear indicators accessible via a
bolted panel.
ReliabilityA minimum o moving parts on the motor-driven, spring-charged
Type RI mechanism.
Durability
Robust design tested to the highest IBC-2000 seismic standard.Other seismic standards may be evaluated upon request.
FlexibilityStandard adjustable heights in 3 increments.
Component CommonalityUtilizes Type RI operating mechanism / coils / motor, which are
commonly used among many Square D medium voltage circuit breakers.
Standard Features
Window or viewing status indicators and operation counter.
Ground pads located on both sides o breaker. A #4 cable connects
rom the roo and HV/LV compartment to the ground pads to insure a
solidly grounded enclosure. Painted adjustable legs with galvanized base channels.
All external hardware is stainless steel.
Optimized relay panel (32 5/8 W x 33 7/8 H) or instrumentation
(model 1 only).
12 pole auxiliary switch (6 a & 6 b contacts), latch check switch
and emergency cutout switch standard.
All outer doors latch open at approximately 120 degrees.
Type RI mechanism with integral manual charging handle.
Advanced Technology for Leading Reliability
2
7/30/2019 Medium Vtg Substation Breakers
3/4
3
Powersub Type EVR Vacuum Circuit Breaker
Powersub Type EVR Medium Voltage Substation Circuit Breaker
Additional Features and Ratings
15.5kV, 1200A, 25kA, 110kV BIL. 10,000 operations at load current. Breaker element is a modular design or ease
o replacement.
Total height adjustability o 24. Double bent roo gives greater phase to phase
clearance while maintaining a small ootprint.
One pad-lockable handle on each outer door. Hinged doors utilized on common access areas.
The EVR is available with or without a relaycompartment. Model 0 does not have a relaycompartment, and is intended or applicationsin which the relay will be mounted remotely.Model 1 includes a relay compartment, and canbe provided with the relay o your choice.
EVR Vacuum Circuit Breaker Ratings
Substation CircuitBreaker Catalog
Number
VoltageMax.
kV rms
ShortCircuit
CurrentkA rms
RatedContinuous
Current
Max.Symmetrical
InterruptingCapabilitykA rms
LowFrequency
WithstandkV rms
Full WaveLightning
ImpulseWithstandkV Crest
2u secImpulse
WithstandkV Crest
RatedPermissible
TrippingDelayY Seconds
3 SecondCurrent
CarryingCapabilitykA rms
Close &Latching
CapabilitykA Peak
EVR 1 06 11 12
15.5
12.5
600
12.5
50 110 142 2
12.5 32EVR 1 08 11 12 800
EVR 1 12 11 12 1200
EVR 1 06 11 16
16
600
16 16 43EVR 1 08 11 16 800
EVR 1 12 11 16 1200
EVR 1 06 11 20
20
600
20 20 54EVR 1 08 11 20 800
EVR 1 12 11 20 1200
EVR 1 06 11 25
25
600
25 25 68EVR 1 08 11 25 800
EVR 1 12 11 25 1200
Type
Voltage Class Model
Interrupting Rating
BIL Rating
Continuous Current Rating
Square D Catalog Numbering Scheme (example)
Catalog Number EVR 1 12 11 16 0
Type Voltage Class Continous
Current Rating
BIL Rating Interrupting Rating Model
EVR 1 = 15.5 kV 06 = 600 A
08 = 800 A
12 = 1200 A
11 = 110 kV 12 = 12.5 kA
16 = 16 kA
20 = 20 kA
25 = 25 kA
0 = No relay compartment
1 = With relay compartment
Table 1: Catalog Numbering Scheme
7/30/2019 Medium Vtg Substation Breakers
4/4
1910BR0901
9870 Crescent Park DriveWest Chester, OH 45069Tel: 513-777-4445Fax: 513-755-5028
Schneider Electric North American Operating Division
8-09
This document has beenprinted on recycled paper.
Dimensions 15kV, 110 kV BIL Type EVR
EVR (no relay compartment model 0) Notes:
Approx. weight: 1850 lbs.
All external hardware isstainless steel.
All dimensions are in
inches unless otherwisespecifed.
Adjustable leg has rangeo 24 inches.
Cross brace must beinstalled duringinstallation.
All dimensions are typical.
Diagrams are notor construction.
EVR (with relay compartment model 1) Notes:
Control panel with accessterminal blocks ismounted on right wall olow voltage compartment.
Approx. weight: 2000 lbs.
All external hardware isstainless steel.
All dimensions are ininches unless otherwisespecifed.
Adjustable leg has rangeo 24 inches.
All dimensions are typical.
Diagrams are notor construction.
Why Choose Square D Services?
Square D Services rom Schneider Electricoers a broad range o service solutions
to support any manuacturers electricaldistribution equipment. Whether the solutionis reurbishment, replacement, maintenanceor recommendations to optimize your existingsystem, our nationwide network o qualifedexperts oers a complete service package.
For more inormation call 888-SQUARED or visitus online at www.SquareD-Services.com.
Breaker rear
Control conduit
entrance (3 x 8),customer installscutouts in coverplates as needed
Control conduitentrance (3 x 8),customer installs
cutouts in coverplates as needed
Breaker ront oundation plan
Breaker rear
Control conduit
entrance (8 x 14),customer installscutouts in cover
plates as needed
Control conduitentrance (8 x 14)Customer installcutouts in cover
plates as needed
Breaker ront oundation plan