1 © NOKIA Metro BTS_Solutions.PPT / 20-05-2005 / Krishna Company Confidential
METRO BTS SITE SOLUTIONS ON TOWER• Infra Requirements for 222 TRX Configuration on 50m Tower
50m Telecom Tower with Platform, Cable Tray & Climbing Ladder. Foundation for Installation of IP43 Power Cabinet at bottom of Tower. Out Door type ACDB within 10m from IP43 Power Cabinet; preferably to be
installed on the same IP43 Foundation OR Special arrangement for ACDB (MCBs)to be made inside IP43 Cabinet.
Diesel Generator suitable to take a load up to 1200W. (2.5KVA would be sufficient)
3m Pole – 3nos for GSM Antennae; 2nos for Metro BTS. 0.3 & 0.6m Microwave dishes can be mounted on the Metro BTS Pole. For 1.2m
& above; separate poles have to be provided. Lightning Protection on Tower. Grounding for the site.
2 © NOKIA Metro BTS_Solutions.PPT / 20-05-2005 / Krishna Company Confidential
METRO BTS SITE SOLUTIONS ON TOWER
B
D
E
F
A
51 2 3 4 6 7 8
A
E
F
B
C
D
51 2 3 4 6 7 8
Power supply
GSM ANTNNA
RG223 CABLE
METRO BTS
LIGHTNING ARRESTER
M/W ANTENNA
J UMPER CABLE
DETAIL OF - X
IP 43 CABINET FOUNDATION
IP 43 CABINET HOUSING UPS, BATTERY & KRONE
M/W ANTENNA
LIGHTNING ARRESTER
METRO BTS
J UMPER CABLE
PVC CONDUIT
RG223 CABLE
GSM ANTENNAE
CABLE TRAY METRO BTS
J UMPER CABLE
X POL ANTENNA
M/W ANTENNA
TOWARDS M/W
FXCRRI
SYNC CABLE
TRX 1TRX 2 TRX 4
TRX 3 TRX 5TRX 6
SECTOR 1 SECTOR 2 SECTOR 3
PVC CONDUIT
PVC CONDUIT
X
(222) METRO SITE SOLUTION ON TOWER
ELEVATION
5000
0
SYNC CABLE
CABLE TRAY
FXCRRI
SYNC CABLE
3 © NOKIA Metro BTS_Solutions.PPT / 20-05-2005 / Krishna Company Confidential
METRO BTS SITE SOLUTIONS ON TOWER• TI Requirements for 222 TRX Configuration on 50m Tower
Standard Metro BTS- 2 no with total 6 TRX & 2 Transmission interface (preferably RRI) .
Flexi hopper & Installation materials – As per transmission design. X-Polar GSM Antennae – 3 no. BTS installation materials as per Link below
(222)Inst.Materials
4 © NOKIA Metro BTS_Solutions.PPT / 20-05-2005 / Krishna Company Confidential
METRO BTS SITE SOLUTIONS ON TOWER• Infra Requirements for 333/444 TRX Configuration on 50m Tower
Infra requirements are the same as 222 configuration except in the no of poles/mounts.
Special type of Pole mounts have to be designed capable of taking 2 poles per sector.
Pole Mounts – 3nos (Special type for mounting 2 poles per mount) for 6 GSM Antennae.
3 extra poles for Metro BTS. 0.3 & 0.6m Microwave dishes can be mounted on the Metro BTS Pole. For 1.2m
& above; separate poles have to be provided.
5 © NOKIA Metro BTS_Solutions.PPT / 20-05-2005 / Krishna Company Confidential
METRO BTS SITE SOLUTIONS ON TOWER
8764321 5
A
F
E
D
B
8764321 5
D
C
B
F
E
APOWER
CABLE TRAY
SECTOR 3
TRX 7TRX 8TRX6
TRX 5 TRX 9TRX 10 TRX 12
TRX11
M/W ANTENNA
METRO BTS
GSM ANTENNA
J UMPER CABLE
RG223 CABLE
SYNC CABLE
DETAIL OF - X
5000
0
FXCRRI
GSM ANTENNA
RG223 CABLE
PVC CONDUIT
J UMPER CABLE
METRO BTS 3 NOS
LIGHTNING ARRESTER
M/W ANTENNA
TRX 1TRX 2 TRX 4
TRX 3
SECTOR 1 SECTOR 2
PVC CONDUIT
X
(444) METRO SITE SOLUTION ON TOWER
ELEVATION
SYNC CABLE
SYNC CABLE
IP 43 CABINET FOUNDATION
IP 43 CABINET HOUSING UPS, BATTERY & KRONE
M/W ANTENNA
LIGHTNING ARRESTER
METRO BTS
J UMPER CABLE
PVC CONDUIT
RG223 CABLE
GSM ANTNNA
CABLE TRAY
6 © NOKIA Metro BTS_Solutions.PPT / 20-05-2005 / Krishna Company Confidential
METRO BTS SITE SOLUTIONS ON TOWER• TI Requirements for 333/444 TRX Configuration on 50m Tower
Standard Metro BTS- 3 no with total 9 or 12 TRX & 3 Transmission interface (preferably RRI) .
Flexi hopper & Installation materials – As per transmission design. X-Polar GSM Antennae – 6 no (2 per sector). BTS installation materials as per Link below
(444)Inst.materials