40
User manual MGE™ Galaxy™ PW 20 - 200 kVA

MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

Embed Size (px)

Citation preview

Page 1: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

E-51028230XT/BG - 1

User manual

MGE™ Galaxy™ PW20 - 200 kVA

Page 2: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

2 - E-51028230XT/BG

Page 3: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

E-51028230XT/BG - 3

Contents

IntroductionGeneral characteristics of MGE™ Galaxy™ PW UPSs ......................................... 5System description .................................................................................................. 6Different types of MGE™ Galaxy™ PW systems ................................................... 7Isolation and protection devices .............................................................................. 7Operation in on-line mode ....................................................................................... 8Operation in "eco" mode ......................................................................................... 10Operation with an engine generator set .................................................................. 11Inverter shutdown or overload ................................................................................ 12Output voltage quality and continuity ...................................................................... 12

Description of MGE™ Galaxy™ PW cubiclesUPS cubicle............................................................................................................. 13Battery cubicle ........................................................................................................ 14

Control panelGeneral ................................................................................................................... 14Presentation ............................................................................................................ 15

Start-upSystem start-up ....................................................................................................... 17Start-up of a module ............................................................................................... 18

ShutdownShutdown of the inverter ......................................................................................... 19Shutdown of a rectifier/charger ............................................................................... 19

Control-panel displayGeneral organisation ............................................................................................... 20Display of messages ............................................................................................... 20Measurement system .............................................................................................. 24Voltage measurementsi .......................................................................................... 24Current measurements ........................................................................................... 24Power and frequency measurements ..................................................................... 24Battery measurements ............................................................................................ 25Selections and settings ........................................................................................... 25

AlarmsGeneral ................................................................................................................... 28Maintenance bypass ............................................................................................... 28

Environment informationSignal reception ...................................................................................................... 29Signal transmission ................................................................................................. 29

Logging and time-stampingPresentation of event time-stamping by MGE™ Galaxy™ PW .............................. 30Utilisation via the MGE™ Galaxy™ PW display ..................................................... 30Utilisation via Teleservice ....................................................................................... 33

MaintenanceMaintenance configuration ...................................................................................... 34Battery maintenance ............................................................................................... 37Visual check ............................................................................................................ 37Functional check ..................................................................................................... 37Training center ........................................................................................................ 38

OptionsIsolating and voltage matching transformer for the normal and bypass ACSource and the load ................................................................................................ 39Harmonics filter and power factor improvement ..................................................... 39Safety of life and property ....................................................................................... 39Empty cubicles ........................................................................................................ 40Electrical supervision .............................................................................................. 40

Page 4: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

4 - E-51028230XT/BG

All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available tocompetitors of APC by Schneider Electric.

To take into account evolving standards and technology, equipment may be modified without notice. Indications concerningtechnical characteristics and dimensions are not binding unless confirmed by APC by Schneider Electric.

This document may be copied only with the written consent of APC by Schneider Electric. Authorised copies must be marked"MGE™ Galaxy™ PW User Manual, N° 51028230XT".

Page 5: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

E-51028230XT/BG - 5

Introduction

General characteristics of MGE™ Galaxy™ PW UPSs

UPS power rating in kVA 20 30 40 50 60 80 100 120 160 200Normal AC inputnumber of conductors 3 phasesrated voltage and tolerances 380 V or 400 V or 415 V ± 10% (adjustable to ± 15%)rated frequency and tolerances 50 Hz or 60 Hz / ± 10%THDI with THM filter < 4%power factor with THM filter up to 0,96Bypass AC inputnumber of conductors 3 phases + neutralrated voltage and tolerances 380 V or 400 V or 415 V / ± 10%rated frequency and tolerances 50 Hz or 60 Hz / ± 10%Loadnumber of conductors 3 phases + neutralPh/Ph voltages 380 V or 400 V or 415 V (according to setting)Ph/N voltages 220 V or 230 V or 240 V (according to setting)voltage fluctuations ± 0,5%adjustable frequency and tolerances(on battery power) 50 Hz or 60 Hz ± 0,05 Hzsynchronisation with bypass ± 0,5 Hz (adjustable from ± 0,25 Hz to ± 2 Hz)voltage variation for 0 to 100% load step change ± 2% ((with battery)permissible overloads 150% for 1 minute, 125% for 10 minutesIsc Ph/Ph (% of I rated) 4.2 2.8 2.1 2.5 2.1 3.1 2.5 2.1 2.6 2.1Isc Ph/N (% of I rated) 6.6 4.4 3.3 4 3.3 5 4 3.3 4 3.3THDU Ph/Ph and Ph/N for linear load < 1,5% Ph/Ph, < 2% Ph/NTHDU Ph/Ph and Ph/N for non-linear load < 2% Ph/Ph, < 3% Ph/N (at 80% of Pn) (1)Batterystandard battery type gas-recombination sealed lead-acid batteryUPS characteristicsactive power (kW) 16 24 32 40 48 64 80 96 128 160efficiency at 50% load (%) 87.5 90.5 91.5 92.5 93 91 91.5 92 93 93.2(values ± 1%)efficiency at 100% load (%) 91.5 92 91.5 93 92 92.5 92 91.5 92.8 92.5(values ± 1%)heat losses (2) in KW 1.5 2.1 3.4 3.6 4.7 6.2 8.1 10.1 12.2 14.8

in cal./s 360 504 816 864 984 1488 1950 2420 2930 3550storage temperature range -25 °C to +70 °Coperating temperature range 0 °C to 35 °C (40 °C for 8 hours)relative humidity 95% maximummaximum operating altitude without derating < 1000 metersnoise level (dBA) 58 58 58 60 60 62 64 65 67 68dimensions (mm) width 715 1015 1215

depth 825height 1400 or 1900 ± 10 1900 ± 10

weight (kg) (3) 450 450 450 490 490 800 800 800 1200 1200recommended upstream earth-fault protection 1 Astandards design IEC 146

product ENV 50091safety IEC 950, ENV 50091protection IEC 521 (cubicles 1400 mm high = IP 21, cubicles 1900 mm high = IP 20)electromagnetic compatibility IEC 62040, ENV 50091

(1): As per standards ENV 50091-3 / IEC 62040-3.(2): The losses indicated are those produced at full rated load with the battery float charging. They must be taken into account when sizing the ventilation system.(3): Not including any built-in options, such as harmonic filters or a bypass AC-source isolation transformer.

Page 6: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

6 - E-51028230XT/BG

System description(see figure 1)

◗ a rectifier/charger module (A)converts 3-phase AC power from thenormal AC source supply (1) into DCpower for the normal inverter input andfloat charges or recharges the battery;◗ a battery unit (D) provides backuppower for the inverter in the event of avoltage drop or a normal AC sourcefailure;◗ an inverter module (B) converts theDC power supplied by the rectifier/charger module or the battery unit into3-phase AC power for the load;◗ a static bypass module (C) ensuresthe instantaneous transfer of the load tothe bypass AC source input in theevent of an inverter shutdown (initiatedby the user or by a protective device) ora sudden overload;◗ a maintenance bypass isolates theUPS for maintenance and transfers theload to bypass AC source input withoutinterrupting the supply of power. Themaintenance bypass is made up ofthree manual switches (Q3BP, Q4Sand Q5N).

Note◗ the normal AC input and the bypassAC input have different functions and,depending on the installation, may beprotected differently upstream and/orcome from different sources.◗ frequency converters are availablewithout backup batteries;◗ the static bypass line and themaintenance bypass line do not exist ininstallations where the load frequencyand the bypass AC source frequencyare different (for example in frequencyconverters);◗ when increased power is required,several MGE™ Galaxy™ PW unitsmay be connected in parallel. In thisconfiguration, an "isolation" function isadded for the UPS system as a wholefor maintenance purposes, withoutinterrupting the supply of power to theload.

Introduction (cont.)

The system may also include :◗ an isolating transformer on bypassAC input;◗ a passive harmonic filter (FAH) onthe normal AC input;◗ an active harmonic conditioner on thenormal AC input;◗ different remote control, indicationand display systems.

Schematic diagram of the MGE™ Galaxy™ PW system

Fig. 1

maintenance bypass:Q3BP

inverter (B):DC to ACpower

isolation:Q4S

isolation andprotection:FUS Q5N

rectifier/charger (A):AC to DCpower

QF1: isolationand protection

normalAC input

load

battery (D):backup power

static bypass (C):

bypassAC input

Q1 FUE :isolationand protection

(1)

(2)

Page 7: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

E-51028230XT/BG - 7

Different types ofMGE™ Galaxy™ PWsystems

Frequency converterwithout battery backuppower

Parallel UPS system

Fig. 2

Single-UPS unit

Fig. 3

Frequency converter withbattery backup power

Fig. 4

See figure 5 showing two parallel-connected (redundant) UPS units.A static bypass (C) does not exist inparallel-connected frequency-converter

configurations.When increased power is required (twoto four parallel units), an externalbypass must be added (see figure 6).

Isolation and protectiondevices

(See figure 1 on previous page):◗ Q1 (switch):◗◗ isolation of the rectifier/charger (A)from the normal AC source (1);◗◗ rectifier/charger (A) start-up;◗ QF1 (circuit breaker):◗◗ battery (D) protection and isolation;◗ Q5N (switch):◗◗ isolation of the UPS (B) from theload;◗ Q4S (switch):◗ ◗ isolation of the static bypass (C) fromthe bypass AC source (2);◗ Q3BP (switch):◗◗ bypass switch for maintenance;◗ FUE (fuses):◗◗ protection of the rectifier/charger (A)from the normal AC source;◗ FUS (fuses):◗◗ protection of the inverter (B) from theload.

Note:◗ switch Q3BP does not exist onparallel UPS systems constituted toincrease available power;◗ the "Q3BP" and "Q4S" switches donot exist on frequency converters;◗ circuit breaker QF1 does not exist oninstallations without batteries.

External bypass for parallelUPSs and the hot-swapoptionSee figure 6.◗ Q5N (switch): isolation of theinverters of all the parallel UPSsystems from the load;◗ Q4S (switch): isolation of the staticbypasses (C) on each parallel unitfrom the bypass AC source (2);◗ Q3BP (switch): bypass switch formaintenance.

1

2

A B

CD

1

A B

D

1

A B

Fig. 6

2

1

Q3BP

Q4S

Galaxy 1

Galaxy 22

1Galaxy 32

1Galaxy 42

2

Q5N1

Fig. 5

1

D2

BA

1

D2

BA

C

C

Introduction (cont.)

Page 8: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

8 - E-51028230XT/BG

Introduction (cont.)

Operation in on-linemode

Normal operationNormal AC source power is available(see figure 7).◗ lights 1 , 4 and 5 shine green onthe control panel;◗ the power necessary for the load isprovided by the normal AC source (1)through the rectifier/charger (A) and theinverter (B);◗ the rectifier/charger (A) also suppliesthe power to float charge and rechargethe battery if any.The rectifier/charger output voltage(DC) is regulated to supply:◗◗ the float-charging or the rechargingvoltage for vented lead-acid or Ni/Cdbatteries,◗ ◗ a single charge voltage for sealedlead-acid batteries.

The voltages depend on the number ofbattery cells and the batterymanufacturer. Factory set, they mayalso be adjusted by after-sales supporttechnicians.An electronic board continuouslymeasures the battery temperature andautomatically adjusts the voltages.

Note:In parallel MGE™ Galaxy™ PWsystems, the power drawn by the loadis equally shared between the different

units.Operation with the normalAC source downSee figure 8.In the event of a normal AC sourcefailure or voltage outside specifiedtolerances of ±10% in amplitude (±15%optionally), the rectifier/charger (A)stops and the battery (D) supplies thenecessary backup power to the load viathe inverter (B). The battery, float-connected between the rectifier/chargerand the inverter, discharges during thisoperating mode.Lights 2 , 4 and 5 shine green.The user is warned of battery operationby the slow beeping of the buzzer 6(see figure 19) and the message"LOAD PROTECTED, BATTERYDISCHARGING", followed by theremaining backup time and the percentload.This information is also available viavolt-free changeover contacts forremote control devices.

Note:In the event of a normal AC sourcefailure, frequency converters without abattery shut down and the load is no

longer supplied.Battery timeThe available battery time during anormal AC source outage depends onthe:◗ rated capacity of the battery;◗ power consumed by the load;◗ temperature of the battery;◗ age of the battery.The specified battery time correspondsto a minimum duration at full rated load.The actual backup time can thereforebe greater if the system operates belowits full rated load during the normal ACsource outage. Operation on batterypower can be extended beyond thespecified time by reducing the loadpower consumption (by disconnectingnon-critical loads).A "low battery" warning signal is sentvia volt-free changeover contacts forremote control devices when thebattery voltage reaches a level slightlyabove the minimum level. This signalwarns the user of the imminent end ofbattery power. On the device itself, thebuzzer beeps rapidly.The message "LOW-BATTERYSHUTDOWN WARNING" is displayed,followed by the remaining backup timeand the percent load. Light 2 turns redand flashes.Battery power stops when the voltagesupplied by the battery reaches theminimum threshold (335 V). Thisresults in inverter shutdown andtransfer of the load without interruptionto the bypass AC source. Light 2shines red (not flashing). The message"LOAD NOT PROTECTED, ON-LINEMODE" is displayed and the buzzersounds continuously.If the bypass AC source also fails, theload is no longer supplied. The inverterautomatically shuts down when thetime on battery power exceeds threetimes the specified backup time.

Note:The "low battery shutdown" warningsignal can be sent with an adjustabletime delay prior to the effective end ofbattery power.Fig. 7

1

2

A B

CD

2

1

4 51

Fig. 8

2

1

4 52

1

2

A B

CD

Page 9: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

E-51028230XT/BG - 9

Operation with the normalAC source restoredSee figure 9.When normal AC source power (1) isrestored or its voltage returns to withinspecified tolerances, the systemautomatically returns to its normaloperating mode described above (onthe condition it did not reach the end ofbattery power). If the end of batterypower was reached (with the resultinginverter shutdown), the rectifier/charger(A) restarts automatically, but theinverter (B) must be restarted manually.The rectifier/charger recharges thebattery (D) which was dischargedduring the mains outage. During batterycharging, light 2 flashes green.The message "BATTERY CHARGING"is displayed, together with the value ofthe recharging current and batteryvoltage.

The battery charge cycle takes place intwo steps (see figure 10):◗ step 1: the battery is recharged at aconstant current limited to 0.1C10 (i.e.1/10th of the battery capacity specifiedfor a 10 hour discharge). The DCvoltage increases with the batterycharge until the charge level isreached;◗ step 2: the battery is recharged atconstant voltage equal to the chargelevel (maximum value 463 V).The charging current graduallydecreases until reaching a specifiedlow value (floating current).For vented lead-acid batteries, therectifier/charger supplies the chargingvoltage for 0 to 255 hours (parameterdefined by the after-sales supportdepartment) and then the floatingvoltage. For sealed lead-acid batteries,the charging and floating voltages arethe same.

Note 1:If the normal AC source failure isshorter than 0 to 255 seconds (defaultvalue = 30 seconds) (parameterdefined by after-sales supportdepartment), the charger automaticallysupplies the floating voltage given thelow battery discharge.

Note 2:In frequency converters without batterypower, the return of normal AC sourcepower results in the automatic restart ofthe rectifier/charger and the inverter.

Fig. 9

1

2

A B

CD

2

1

4 521

U/I

currentlimiting

0,1 C10

constant voltagedecreasing current

voltage

current

t

U charge/floating(sealed batteries)

U "floating"(vented batteries)

Fig. 10

Battery charge cycle

Introduction (cont.)

Page 10: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

10 - E-51028230XT/BG

Introduction (cont.)

Operation with bypass ACsource restored◗ no battery discharge (see figure 11).When bypass AC source power supply(2) is restored or returns to withinspecified tolerances, the load istransferred back to the static bypass(C), without an interruption in thesupply of power.

Note: this operating mode does notdepend on the status of the normal ACsource, which may be within or outsidethe specified tolerances.◗ after battery discharge (see figure12).Operation of the rectifier/charger (A)with the battery (D) is identical to thatpresented in the section on on-linemode operation above.

Forced transfer and returntransfer◗ forced transfer. When the load issupplied via the static bypass (C), itmay be transferred to the inverter (B)by pressing pushbutton 20 (see figure19 in the "control panel" section).The message "FORCED TRANSFERTO INVERTER REQUESTED, POWERTO LOAD MAY BE INTERRUPTED" isdisplayed. Confirmation by pressingpushbutton 12 is required to effectivelyforce transfer. The message "LOADFORCED TO INVERTER, ECO MODE"is displayed. Whatever the status of thebypass AC source, a return to normaloperation in "ECO" mode is possibleonly through a forced return transfer tothe static bypass (C).◗ forced disconnection: as the load issupplied by the inverter (B), it can betransferred to the bypass AC source(M2) via the static bypass (C) bypressing the pushbutton 20 . Themessage "FORCED TRANSFER TOM2 REQUESTED, POWER TO LOADMAY BE INTERRUPTED" is thendisplayed. Confirmation by pressingpushbutton 12 is required fordisconnection.

Note:There are two possibilities: the bypassAC source is within tolerances oroutside tolerances. In the first case, theUPS in "ECO" mode returns to normaloperation.In the second case, the transfer willtake place with a power cut to the loadif the bypass AC source is present, orthe load will cease to be supplied if it isabsent. In both cases, the display reads"LOAD NOT PROTECTED, ECOMODE".

Caution:Return to normal operation of theinstallation in the "ECO" mode ispossible only after the bypass ACsource has returned to within specifiedtolerances.

Operation in "ECO"mode

Normal operationSee figure 11.The power required by the load issupplied by the bypass AC source (2),via the static bypass (C). The rectifier/charger (A) supplies the power requiredto float charge and recharge the battery(D).Lights 1 , 3 and 5 shine green andlight 4 flashes green. The message"LOAD PROTECTED, ECO MODE" isdisplayed.

Operation with the bypassAC source outsidetolerancesWhatever the status of the normal ACsource, operation of the rectifier/charger (A) with the battery (D) isidentical to that presented in the sectionon on-line mode operation above.When bypass AC source (2)characteristics are outside tolerances(voltage: ±10%; frequency as perpersonalisation; phase sync withinverter ±3°), the load is supplied viathe inverter (B).From then on, the minimum operatingtime on the inverter (B) is 2 minuteseven if the bypass AC source returns towithin specified tolerances. Refer tofigure 7 in the general appendix if thenormal AC source is present, and tofigure 8 if it is absent. After this 2minute period, the load is immediatelytransferred to the bypass AC sourcewhen the latter returns to withinspecified tolerances.

Note:The maximum transfer time of the loadfrom the static bypass (C) to theinverter (B) is 15 ms.

Fig. 12

1

2

A B

CD

2

1

3 51 4

Fig. 11

1

2

A B

CD

5

2

1

41 3

Page 11: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

E-51028230XT/BG - 11

Parallel UPSs withredundancy◗ the shutdown of one UPS unit is ofno consequence for the load. Theothers each take up an equal amount ofload power and the load continues tobe supplied normally;Unit shutdown results in the followingon the control panel:◗◗ lights 4 and 5 go off,◗◗ activation of the buzzer (continuousbeep),◗◗ the message "LOAD NOTPROTECTED, PARALLEL ON-LINEMODE" is displayed;◗ in the event of an overload, thesystem only loses its redundancy aslong as the overload is less than thetotal rated power of the functioningunits. If the overload is greater, theoperating mode is that previouslydescribed for systems withoutredundancy.

Frequency converters◗ in the event of a shutdown, the loadis no longer supplied with power;◗ in the event of a major transientoverload (greater than 1.65 In), theinverter will current limit to 165% oftheir rated current for 1 second beforestopping;◗ in the event of a smaller butprolonged overload, the inverterrespects the same overload curve asthe single inverter and shuts down;◗ in all three of the above cases,inverter shutdown results in thefollowing:◗◗ lights 4 and 5 go off,◗ ◗ activation of the buzzer (continuousbeep),◗◗ the message "LOAD NOTPROTECTED, ON-LINE MODE" isdisplayed.

Inverter shutdown oroverload

See figure 13 for devices orinstallations operating in on-line modewith a bypass AC source.

If the conditions are not satisfied, theinverter will current limit to 165% of itsrated current for 1 second beforestopping;◗ in the event of a small but extendedoverload (i.e. a continuous level ofpower exceeding the full rated load),the inverter will continue to supplypower for a period depending on themagnitude of the overload (10 minutesfor a 125% overload, 1 minute for a150% overload). See the overloadcurve in figure 14;◗ in all three of the above cases,inverter shutdown and supply of theload via the bypass AC source resultsin the following on the control panel:◗◗ light 4 goes off,◗ ◗ activation of the buzzer (continuousbeep),◗ ◗ light 3 shines green,◗ ◗ the message "LOAD NOTPROTECTED, ON-LINE MODE" isdisplayed.

Parallel UPSs withoutredundancyThe shutdown of one inverter results inoverload on the other inverters inoperation. Two cases may then arise:◗ if the overload on each remaininginverter is > than 1.65 ln, the load isimmediately transferred to the bypassAC source;◗ if the overload is less than 1.65 ln,the remaining inverters support theoverload (see curve in figure 14), andthe load is transferred to the bypass ACsource;◗ after this transfer:◗◗ the light 4 goes off,◗ ◗ the buzzer is activated and soundscontinuously,◗ ◗ the light 3 goes on and turns green,◗◗ the message "LOAD NOTPROTECTED, PARALLEL ON-LINEMODE" is displayed.

Single-UPS unit (on-line or"ECO" mode)◗ in the event of a UPS shutdown(initiated by the user or by an internalprotective device), the load isautomatically transferred to the bypassAC source. If transfer conditions aresatisfied, transfer takes place instantly,without interruption to the load;Note: transfer conditions are notsatisfied when bypass AC sourcecharacteristics are outside tolerances(voltage: ±10%; frequency as perpersonalisation; phase sync withinverter ±3°);◗ in the event of a major transientoverload (greater than 1.65 In),immediate transfer takes place asabove, without interruption to the load.The return to the inverter is automaticwhen the overload disappears if thenumber of possible returns has notbeen reached (0 to 255, programmableby personalisation). If this number hasbeen reached, the load continues to besupplied by the bypass AC source. Thisoperating mode allows start-up of loaddevices causing high inrush currents.This system requires satisfied transferconditions.

Fig. 13

2

1

1

2

A B

CD

3 5

Fig. 14

I

1 2 3 4 5 6 7 8 9 10 (min)

1,5 In

1,35 In

1,25 In

1,15 In

1,10 In

1,05 In

Int30 120

Introduction (cont.)

Page 12: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

12 - E-51028230XT/BG

Operation with anengine generator set

See figure 15 below.If a stand-by generator is included inthe installation, it is generally startedautomatically in the event of a normalAC source failure and connected to themain low voltage switchboard. It isdisconnected when normal AC sourcepower is restored.With such a system, the requiredbattery time may be reduced to the timenecessary for starting and bringing online the stand-by generator. The battery(D) supplies power to the inverter (B)during the transfers:◗ normal AC source to the generator;◗ generator to the normal AC source.The transfer sequences describedabove (normal AC source ➜ battery,battery ➜ generator, generator ➜battery, and battery ➜ normal ACsource) are fully automatic. They in noway affect the load and require nomanual operation by the user.

Note:To avoid load surges on the generator,the rectifier/charger is started with a 10second maximum current consumptionwalk-in (lasting 3 to 10 seconds,depending on the percent load).To avoid overloading an undersizedengine generator set, it is possible toset a maximum power level drawn bythe normal AC input. Any additionalpower required is supplied by thebattery. This modification can be madeon site by an APC by SchneiderElectric technician.

Fig. 15

Example of an installation with an engine generator set

Introduction (cont.)

Output voltage qualityand continuity

The output voltage is stable inamplitude and frequency and is free ofinterruptions or transients outsidespecified tolerances, irrespective ofnormal AC source or load disturbances(outages, load step changes, etc.).

Steady state voltageregulationFor stable or slowly varying loadconditions, the inverter output voltage isregulated to within ±0.5% in amplitude.The frequency of the output voltage cantheoretically be regulated to within0.1% of the rated value, however theoutput frequency range may beintentionally extended to a maximum of±2 Hz so that the inverter can remainsynchronised with the bypass ACsource and its inherent frequencyfluctuations, thus enabling transfer ofthe load to the bypass line at any time.

Note:The output frequency range can bepersonalised and if necessary modifiedon the customer site by a qualified APCby Schneider Electric supporttechnician from ±0.25 Hz to ±2 Hz in0.25 HZ steps.When the bypass AC source voltagemoves outside this frequency range,the inverter is desynchronised andoperates in "free running" mode, withthe output frequency regulated to ahigh level of accuracy by a quartzoscillator.

When the bypass AC source frequencyreturns to within the specifiedtolerances, the inverter is gradually re-synchronised to the bypass line at arate of 0.5 Hz to 2 Hz/s (as per thevalue personalised by the after-salessupport department), thus avoidingexposing the load to sudden frequencyvariations.

Transient voltageregulationThe inverter output voltage is notnotably affected by instantaneousmajor variations in load characteristics.This is made possible by the PWM(Pulse Width Modulation) choppingtechnique and the microprocessor-based regulation system that instantlycompensates for any variation. Inparticular, the inverter output voltageremains within +/- 2% of the ratedvoltage for load step changes of 0 to100% or of 100 to 0%.

���������

����

�����

�������������

��������� �����������������

Page 13: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

E-51028230XT/BG - 13

UPS cubicle

The rated outputs forMGE™ Galaxy™ PW UPSs (orfrequency converters) are 20, 30, 40,50, 60, 80, 100, 120 , 160 and 200kVA.See figure 16 for the layout of thevarious cubicle components.

Legend for figure 16:1 - rectifier/charger module,2 - inverter module,3 - static-bypass module,4 - cage for electronic control boards,5 - rectifier/charger input fuses "FUE",6 - inverter output fuses "FUS",7 - normal AC input switch Q1,8 - bypass AC input switch Q4S (singleor redundant parallel UPSs),9 - maintenance bypass switch Q3BP(single or redundant parallel UPSs),10 - output switch Q5N,11 - display board,12 - Media Contacts 11 remoteindications board.

Description of MGE™ Galaxy™ PW cubicles

Fig. 16

20 - 30 - 40 - 50 - 60 kVA

80 - 100 - 120 kVA

160 - 200 kVA

11

12

1 2 2 2 3

3

4

7 8 9 10

5 6

7 8 9 10

3

22 2

1 4

11

12

11

12

41

2 3

5 6

7 8 9 10

5 6

Page 14: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

14 - E-51028230XT/BG

Control panel

Battery cubicle

Figure 17 shows an example ofcomponent layout in a battery cubicleor a battery circuit-breaker enclosure.

Legend for figure 17:1 - battery isolation and protectioncircuit breaker QF1,2 - battery cells.

Fig. 17

General

The control panel onMGE™ Galaxy™ PW UPSs comprisesthe basic controls and indicationsrequired to check the general status ofthe system (see figure 19).

Located in the upper right part of thecubicle front, the control panel isdesigned to provide an easy and rapidoverview of system status (see figure19 on next page).Interpretation of symbols is very simpleand requires no particular training.The information concerns only thecubicle on which the panel is located.The panel indicates:◗ normal operation (load protected);◗ operation with load on battery power;◗ abnormal situations (operatingproblem);◗ dangerous situations (load notprotected).

Note:The information on the bypass ACsource provided below does notconcern frequency converters.Information on batteries does notconcern frequency converters withoutbatteries.

Fig. 18

2

2

2

2

1

1

Page 15: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

E-51028230XT/BG - 15

"Inverter" light 4◗ light off: inverter OFF;◗ light flashing green: inverter starting,inverter ON but not connected to theload;◗ light shines green: normal inverteroperation;◗ light shines red: inverter fault, thestored alarm indicates one or several ofthe following faults:◗ ◗ inverter shutdown due to inverteroutput voltage outside specifiedtolerances,◗◗ protection fuse at the inverter output(FUS) blown,◗◗ abnormally high inverter-outputtransformer temperature,◗◗ abnormally high inverter temperature,◗◗ output-voltage fault (amplitude orphase) (parallel UPSs),◗ ◗ fault, non-calibration or non-personalisation of the electronic controlboard for the inverter,◗◗ fault on the electronic power-supplyboard.

"Load" light 5◗ light off: load not supplied;◗ light shines green: load supplied viathe inverter or the bypass AC source(via the static bypass).

Presentation

See figure 19.

"Rectifier/charger" light 1◗ light off: rectifier/charger OFF;◗ light shines green: rectifier/chargerON;◗ light shines red: rectifier/charger fault,the stored alarm indicates one orseveral of the following faults:◗ ◗ input switch Q1 open,◗ ◗ protection fuse at the rectifier/chargerinput (FUE) blown,◗ ◗ abnormally high internal rectifier/charger temperature,◗◗ abnormally high battery chargecurrent,◗ ◗ abnormally high battery voltage,◗ ◗ fault, non-calibration or non-personalisation of the electronic controlboard for the rectifier/charger,◗◗ fault on the electronic power-supplyboard.

"Battery light" 2◗ light off: battery float charging;◗ light flashing green: batteryrecharging;◗ light shines green: load on batterypower;◗ light flashing red: low-batteryshutdown warning;◗ light shines red: battery at end ofbackup time and circuit breaker QF1open, or battery fault.

"Static-bypass" light 3◗ light off: bypass AC source withinspecified tolerances and static bypassopen;◗ light shines green: static bypassclosed;◗ light shines red: the stored alarmindicates one or several of the followingfaults:◗ ◗ bypass AC source voltage orfrequency outside specified tolerances,◗◗ static-bypass fault,◗ ◗ abnormally high internal static-bypass temperature,◗◗ static-bypass ventilation fault,◗◗ power-supply fault for the static-bypass control function,◗ ◗ fault on the electronic boardcontrolling the transfer function,◗ ◗ non-calibration or non-personalisation of the electronic controlboard for the inverter,◗◗ fault on the electronic power-supplyboard,◗◗ fault on monitoring the "inverterready" response channels (parallelUPS system).

Buzzer 6The buzzer sounds in the followingsituations:◗ load supplied by the bypass ACsource;◗ load on battery;◗ operating problems.It sounds slowly and discontinuously fora minor problem or when the inverter ison battery power.When the alarm "LOW BATTERYSHUTDOWN" is activated, the buzzersounds more rapidly. Finally, if theinverter shuts down, the beep is loudand continuous. The buzzer may bereset by pressing a button. If the buzzeris reset, a higher level alarm will set itoff again.

"Full-shutdown" button 7Pressing this button shuts down theentire UPS (shutdown of the inverterand rectifier/charger, opening of thebattery circuit breaker and activation ofa relay contact on the Media Contacts11 board).

"Inverter ON" button 8This button is used to start the inverterlocally.

"Inverter OFF" button 9This button turns the inverter off locally.

1

2

V A W.Hz

fault

19

18

9

8

7643 521

23

2220 21

17

10 11 12 13 14 1515 16

Fig. 19

Control panel (cont.)

Page 16: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

16 - E-51028230XT/BG

Keys 10 and 11These keys are used to selectcommands in the main menu andaccess the secondary messages.

Key 12This key is used to validate the user’schoice.

Key 13This key is used to access the mainmenu: display language, display-contrast setting, sound level of thebuzzer, lamp test, date and timesettings, inverse-video and event log.

"V" key 14This key is used to access voltagemeasurements:◗ normal AC source phase-to-phasevoltages;◗ bypass AC source phase-to-phaseand phase-to-neutral voltages;◗ load phase-to-phase and phase-to-neutral voltages.

"A" key 15This key is used to access currentmeasurements:◗ normal AC source, bypass AC sourceand load currents;◗ percent load;◗ load crest factor.

"W.Hz" key 16This key is used to access othermeasurements:◗ normal AC source, bypass AC sourceand inverter frequencies;◗ level of active and apparent powerdrawn by the load;◗ load power factor;◗ inverter load level (percent).

"Anomaly" indicator light 17This indicator light indicates thepresence of anomalies.

Control panel (cont.)

key 18This key is used to access the primarymessages.

"Battery" key 19This key is used to access batterymeasurements:◗ battery voltage (or the DC voltage onfrequency converters without a battery);◗ battery current (charge or discharge);◗ battery temperature;◗ available battery backup time;◗ inverter load level (percent).

"Forced-transfer" key 20This key is used to voluntarily transferthe load to the inverter or from theinverter to the static bypass (returntransfer). Transfer and return transferare carried out only followingconfirmation requested by the systemdisplay and a warning as to the risk ofan interruption in the supply of power tothe load.

"Alarm reset" key 21This key is used to reset stored alarms.The system accepts resetting onlywhen alarms have been cleared.

"Buzzer reset" key 22This key is used to stop the buzzer.However, new alarms set the buzzer offagain.

Display 23The display continuously indicates thesystem operating status.

Page 17: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

E-51028230XT/BG - 17

Parallel UPS unit forincreased outputSee figure 21.Proceed in the following order:◗ check that all load devices are off orthat the load is disconnected;◗ close the upstream switch supplyingnormal AC source power (on the LVswitchboard);◗ close the normal AC input switchesQ1 on the UPS units. The systempowers up:◗◗ the rectifier/chargers automaticallystart,◗◗ the green "rectifier/charger" lights 1in the control panels go on,◗◗ lights 2 turn red;◗ close the battery circuit breakersQF1;◗◗ lights 2 go off;◗ close Mains 2 input switch Q4S in theexternal bypass unit:◗◗ green lights 3 and 5 on the controlpanels go on;◗ close output switches Q5N for theinverters and in the external bypassunit;◗ open maintenance bypass switchQ3BP in the external bypass unit;◗ press the "inverter on" button 8 oneach control panel:◗◗ the green "inverter" lights 4 flash;◗ when a sufficient number of invertersare ready, the inverter-outputcontactors close:◗◗ the green "inverter" lights 4 shinepermanently green;◗◗ the "static-bypass" lights 3 go off.

Start-up

System start-up

Single-UPS unit orredundant parallel UPS orUPS in "ECO" modeSee figure 20.Proceed in the following order:◗ close the upstream switchessupplying normal and bypass ACsource power (on the LV switchboard);◗ close normal AC input switch Q1.The system powers up:◗◗ the rectifier/charger automaticallystarts,◗◗ green light 1 on the control panelgoes on,◗◗ light 2 turns red;◗ close bypass AC input switch Q4S:◗◗ green lights 3 and 5 on the controlpanel go on;◗ close inverter output switch Q5N;◗ close battery circuit breaker QF1;◗◗ light 2 goes off;◗ open maintenance bypass switchQ3BP;◗ press the "inverter on" button 8 onthe control panel:◗◗ the green "inverter" light 4 flashes,◗◗ the inverter starts, then, if the bypassAC source transfer conditions aresatisfied, the load is transferred to theinverter if the on-line mode is selected,or the load remains on the staticbypass if the "ECO" mode is selected,◗◗ the green "static-bypass" light 3goes off,◗◗ the green "inverter" light 4 shinesfor on-line mode or flashes for "ECO"mode.

Single-converter unit orredundant parallelconverter unitSee figure 21.Proceed in the following order:◗ close the upstream switch supplyingnormal AC source power (on the LVswitchboard);◗ close normal AC input switch Q1.The system powers up:◗◗ the rectifier/charger automaticallystarts,◗◗ green light 1 on the control panelgoes on;◗ close battery circuit breaker QF1;◗ close inverter output switch Q5N;◗ press the "inverter on" button 8 onthe control panel:◗◗ the green "inverter" light 4 flashes,◗ ◗ the inverter starts up, then connects.The load is then supplied by theinverter,◗◗ the green light 4 shinespermanently, and light 5 turns green.

Note:Each time a device is switched on, alamp test is run: all the lights turnorange for roughly 1 second. Themessage "autotest OK" is displayeduntil the first primary message is sent.

Fig. 20 Fig. 21

Q5NQ1 Q4S

QF1

0 I

3

1

2

10

10 10 1010

10 10

Q3BP10

1010 1010

101010 10

5

4

6

20 - 200 kVA

3

1

2

10

10 10

10

4

20 - 200 kVA

Q5NQ1

Q5NQ1

QF1

0 I

Page 18: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

18 - E-51028230XT/BG

Start-up of a module

Start-up of a rectifier/charger◗ rectifier/charger start-up is automaticwhen the normal AC input switch Q1 isclosed:◗ ◗ the green "rectifier/charger" light 1on the control panel goes on;◗ close battery circuit breaker QF1.

Start-up of an inverterWhen the rectifier/charger is on:◗ press the "inverter ON" button 8 onthe control panel;◗ ◗ the green "inverter" light 4 flashes.

Single-UPS unit◗ the inverter starts, then, if the bypassAC source transfer conditions aresatisfied, the load is transferred to theinverter if the on-line mode is selected,or the load remains on the staticbypass if the "ECO" mode is selected.For on-line mode:◗ ◗ the green "inverter" light 4 remainson,◗ ◗ the "static-bypass" light 3 goes off.◗ For "ECO" mode:◗ ◗ the green "inverter" light 4 flashes,◗ ◗ the "static-bypass" light 3 remainson.

Parallel UPS unit◗ the inverter starts and awaits the startof the other inverters;◗ when they are all on or enough havebeen started to supply the rated loadpower, the output switch for eachrunning inverter closes and the load issupplied with power:◗◗ the green "static-bypass" light 3goes off,◗◗ the green "inverter" light 4 on thecontrol panels of the running invertersgoes on.

Single-converter unit◗ the inverter starts up, then connects.The load is then supplied by theinverter:◗◗ the green lights 4 and 5 go on.

Parallel-converter unit◗ the inverter starts and awaits the startof the other inverters;◗ when they are all on or enough havebeen started to supply the rated loadpower, the output switch for eachrunning inverter closes and the load issupplied with power:◗ ◗ the green lights 4 and 5 on thecontrol panels of the running invertersgo on.

Start-up (cont.)

Page 19: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

E-51028230XT/BG - 19

Shutdown of a rectifier/charger

Except in frequency converters withouta battery, it is recommended not to stopthe rectifier/charger because thebattery will no longer be charged.Except in the case of a test of theinverter on battery power, the rectifier/charger should be shutdown after theinverter to avoid unnecessary batterydischarge.Proceed in the following order:◗ open battery circuit breaker QF1;◗ open normal AC input switch Q1:◗ ◗ the rectifier/charger shuts down,◗ ◗ the green "rectifier/charger" light 1goes off.

Note:In a frequency converter without abattery, rectifier/charger shutdownautomatically results in invertershutdown.

Shutdown of theinverter

◗ press the "inverter OFF" button 9 onthe control panel for three seconds (seefigure 19).

Single-UPS unit◗ the green "inverter" light 4 on thecontrol panel goes off;◗ the green "static-bypass" light 3goes on;◗ the inverter stops;◗ if bypass AC source (Mains 2)transfer conditions are satisfied, theinverter shuts down and the load istransferred to the bypass AC source;◗ if bypass AC source (Mains 2)transfer conditions are not satisfied, theinverter does not shut down. Themessage "MAINS 2 OUTSIDETOLERANCES, TRANSFERDISABLED" is displayed.

UPS in "ECO" mode◗ the green "inverter" light 4 on thecontrol panel goes off;◗ if the load was on the static bypass,nothing is changed;◗ if the load was on the inverter:◗ ◗ the green "static-bypass" light 3goes on,◗◗ if bypass AC source (Mains 2)transfer conditions are satisfied, theinverter shuts down and the load istransferred to the bypass AC source,◗ ◗ if bypass AC source (Mains 2)transfer conditions are not satisfied, theinverter does not shut down. Themessage " MAINS 2 OUTSIDETOLERANCES, TRANSFERDISABLED" is displayed.

Shutdown

Single-converter unit◗ the green lights 4 and 5 on thecontrol panel go off;◗ the inverter stops.

Parallel UPS unit◗ if the system is redundant, i.e. theother parallel-connected inverters cansupply the load on their own, theinverter shuts down and the green"inverter" light 4 goes off.The load is not affected in that the otherinverters continue to supply it normally;◗ if the system is not redundant, theother inverters go to overload status.If overload conditions are overrun, theload is transferred to the bypass ACsource:◗ ◗ the green lights 3 turn green,◗ ◗ the green "inverter" light 4 goes off.

Parallel-converter unit◗ the redundant system means that theother parallel inverters can supply theload unassisted. The inverter shutsdown and the green "inverter" light 4goes off. The load is not affected in thatthe other inverters continue to supply itnormally;

Page 20: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

20 - E-51028230XT/BG

Display of messages

In addition to keypad operations, thegraphical display brings up a windowgiving the overall device status. Themessage displayed is then said to beprimary (see list in the paragraphbelow). A primary message can beused to access the measuring tablesusing keys 14 , 15 , 16 and 19 onthe keypad (see figure 21 in the generalappendix). The configuration screenscan be accessed by pressing key 13 .A flashing arrow appears at the end ofa primary message if there is a problemor an alarm; secondary messages canbe accessed by pressing key 10 onthe keypad (see the list of secondarymessages). The presence of anothermessage is indicated by the arrows and at the end of the secondarymessage. They can be accessed bypressing keys 10 and 11 on thekeypad.The return to the primary message isautomatic after a 2 minute time delay orby pressing key 18 on the keypad.

Control-panel display

General organisation

The display is structured aroundprimary and secondary messages,measuring tables and setting screens.As a rule, the message displayed onthe screen is always a primary one.The secondary messages, if any, areaccessed by pressing keys 10 and11 (see figure 19).The presence of secondary messagesis indicated by the arrow at the endof the primary message. Return to theprimary messages is automatic if thekeypad is not used for 2 minutes, ordirect by pressing key 18 (see figure19). The display screen lights up whena key is pressed, and goes off if no keyis pressed for 5 minutes.

Note:Most functions may be directlyaccessed. For example, when voltagemeasurements are currently displayed,it is possible to directly access currentmeasurements by pressing the "A"button.

Display of alarms

Fig. 22

(ALARM MESSAGE N° 2)

(LAST ALARM MESSAGE)

primary message

main screen

(ALARM MESSAGE N° 1)

1

2

V A W.Hz

fault

19

18

9

8

7643 521

23

2220 21

17

10 11 12 13 14 1515 16

Fig. 19

Page 21: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

E-51028230XT/BG - 21

LOAD PROTECTEDBATTERY DISCHARGINGRemaining battery time (min) = XX% kW used = XXX

The load is supplied by the inverter, butthe normal AC source is down oroutside tolerances and power issupplied by the battery.This message indicates the remainingbattery time in minutes prior to invertershutdown and the percent load. Thebattery time calculation takes intoaccount:◗ the percentage of full rated loadpower currently being drawn;◗ the type of battery;◗ battery temperature;◗ battery age.The buzzer sounds slowly anddiscontinuously.

LOAD PROTECTED,LOW-BATTERY SHUTDOWNWARNING,Remaining battery time (min) = XX% kW used = XXX

This message replaces the preceding ifthe power outage persists and thewarning level has been reached.The user is warned that the battery isabout to shut down.The buzzer sounds rapidly anddiscontinuously.

List of primary messages

LOAD PROTECTEDON-LINE MODE

This is the normal display when thereare no alarms or problems and the loadis correctly supplied by the inverter, inon-line mode.

LOAD PROTECTEDPARALLEL ON-LINE MODE

This is the normal display when thereare no alarms or problems and the loadis correctly supplied by the inverter in aparallel UPS system, in on-line mode.

LOAD NOT PROTECTEDON-LINE MODE

This display indicates that the load isnot supplied by the inverter, or thatthere is no battery backup. The arrow indicates the presence of one or moreproblems specified in secondarymessages.The buzzer sounds continuously.

LOAD NOT PROTECTEDPARALLEL ON-LINE MODE

Situation identical to that in theprevious screen, but for parallel UPSsystems.

LOAD PROTECTEDECO MODE

This is the normal display when thereare no problems: the load is suppliedby the inverter or the bypass ACsource, and battery backup is available.

LOAD NOT PROTECTEDECO MODE

This display indicates that the load issupplied but has no battery backup.The arrow indicates the presence ofone or more problems specified insecondary messages.The buzzer sounds continuously.

LOAD FORCED TO INVERTERECO MODE

The load has been transferred to theinverter following a specific request bythe user.

Control-panel display (cont.)

Page 22: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

22 - E-51028230XT/BG

MAINS 1 OUTSIDE TOLERANCES,CHECK MAINS 1

The normal AC source (M1) frequencyor voltage is outside specified tolerancesand the rectifier/charger has shut down.The inverter is on battery power.

MAINS 1 INPUT SWITCH Q1IS OPEN

The normal AC input (M1) switch Q1 isopen. It must be closed for rectifier/charger start-up. The buzzer soundsslowly and discontinuously.

INTERNAL UPS FAULT,LOAD TRANSFER FAULT,CALL MAINTENANCE

A fault has occurred in the static switchthat transfers the load between theinverter and the bypass AC source(M2). Servicing by the after-salessupport department is required. Thebuzzer sounds continuously.

OVERLOADRATED CURRENT PER PHASE =XXX ACHECK LOAD LEVEL

This display informs the user that loadcurrent is greater than rated current,and gives the value. The buzzersounds continuously.

UPS SHUTDOWN DUE TO ANOVERLOAD,CHECK LOAD LEVEL

This message follows the precedingwhen the overload persists. The UPShas shut down and the buzzer soundscontinuously.

Control-panel display (cont.)

List of secondarymessages

LOAD ON MAINS 2

The load has been transferred to thebypass AC source (M2) and is nolonger protected (only in on-line mode).The buzzer sounds continuously.

MAINS 2 OUTSIDE TOLERANCESTRANSFER DISABLEDCHECK MAINS 2

The bypass AC source (M2) frequencyor voltage is outside tolerances and theinverter is unable to synchronise.Transfer of the load from the inverter tothe bypass AC source (M2) or vice-versa will result in an interruption of thesupply of power to the load. The buzzersounds slowly and discontinuously.

BATTERY OVERTEMPERATURE,CHECK VENTILATION

The battery temperature is outsidetolerances. The buzzer sounds slowlyand discontinuously.

BATTERY ROOM VENTILATIONFAULT,CHECK VENTILATION

A fault requiring servicing has occurredin the battery room ventilation system.The rectifier/charger shuts down after a30-second time delay.The user must take steps to re-establish correct operation of theventilation system.If a harmonic filter is present in theinstallation, this message also signalsan abnormally high temperature in thefilter inductor.The buzzer sounds slowly anddiscontinuously.

INVERTER NOT IN PHASE WITHMAINS 2.TRANSFER DISABLED,CHECK MAINS 2

The phase difference between theinverter and the bypass AC source(M2) is outside tolerances. Transfer ofthe load between the inverter and thebypass AC source (M2) will result in aninterruption in the supply of power tothe load.For parallel UPSs, this message shouldbe interpreted as meaning the phasedifference between the inverter for whichthe message is displayed and the otherinverters is outside tolerances.

UPS SHUTDOWNBY AN EXTERNAL COMMAND

The inverter has received a commandto shut down. The command is in theform of a signal from received theremote-indications relay board whichhas been set for this function.

FREQUENCY CHANGEBY AN EXTERNAL COMMAND

The inverter has received a commandto change its output frequency (50 Hzor 60 Hz). This command is noteffective unless the inverter has firstbeen shut down. The frequency ischanged when the inverter is startedagain.

MAINS 2 INPUT SWITCH Q4S ISOPEN

The bypass AC source (M2) inputswitch Q4S is open, i.e. backup powerfor the load via the bypass AC source(M2) is not available.

INVERTER OUTPUT SWITCH Q5NIS OPEN

Inverter output switch Q5N is open, i.e.the load cannot be supplied via theinverter.

Page 23: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

E-51028230XT/BG - 23

THE NUMBER OF UPS READY ISINSUFFICIENT,LOAD TRANSFER IN STAND BY

This message may be displayed in non-redundant, parallel UPS systems,when the number of ready inverters innot sufficient to supply the load.

INVERTER NOT CONNECTED

This message may be displayed inparallel UPS systems, when theinverter is not connected to the load.

PARALLEL UPS,FORCED TRANSFER INHIBITED

This message is displayed when forcedconnection is requested on a parallelUPS system for a power extension.

INTERNAL UPS FAULT,SELF-TEST FAULT

Communication between the systemand the display is faulty. The buzzersounds slowly and discontinuously.

FORCED TRANSFER TO M2REQUESTED,POWER TO LOAD MAY BEINTERRUPTEDCONFIRM YOUR REQUEST WITHKEY

This message is displayed followingpressing of the "forced-transfer" key20, when the load is supplied via theinverter.

UPS SUPPLIED BY A GENERATORSET

This message informs the user that theUPS has received the order to limit thecurrent drawn by the rectifier/charger.It is displayed when the correspondingsignal is transmitted by the remoteindications board which must beconfigured for this function.

THE BATTERY C.B. QF1 IS OPEN,CHECK THE INSTALLATION

Battery circuit breaker QF1 is open.The load is no longer protectedbecause battery power is no longeravailable in the event of a normal ACsource outage. The buzzer soundscontinuously.

LOW BATTERY SHUTDOWN

The inverter has shut down at the endof battery power. The buzzer soundscontinuously.

INTERNAL UPS FAULT,INVERTER FAULT,CALL MAINTENANCE

A fault has occurred in the inverter.Servicing by the after-sales supportdepartment is required. The buzzersounds continuously.

INTERNAL UPS FAULT,CHARGER FAULT,CALL MAINTENANCE

A fault has occurred in the rectifier/charger. Servicing by the after-salessupport department is required.The buzzer sounds slowly anddiscontinuously.

FORCED TRANSFER TO INVERTERREQUESTED, POWER TO LOADMAY BE INTERRUPTED,CONFIRM YOUR REQUEST WITHKEY

The requested transfer to the invertermay provoke an interruption in thesupply of power to the load if Mains 2characteristics are not within thespecified tolerances.

BYPASS SWITCH Q3BPIS CLOSED

Maintenance bypass switch Q3BP isclosed. The system is in maintenanceconfiguration and the load is suppliedby the bypass AC source.

STATIC SWITCH (M2) OFFDUE TO AN OVERLOAD

The load is no longer supplied by thebypass AC source (M2), due to anextended overload. The buzzer soundscontinuously.

BATTERY CHARGINGI BAT. = XXX A U BAT. = XXX V

The battery is currently beingrecharged.

BATTERY AT END OF SERVICELIFECALL MAINTENANCE

The battery is nearing the end of itsestimated service life. This informationis based on average service-lifecalculations since its initial installation.The buzzer sounds slowly anddiscontinuously.

EMERGENCY OFF OR FULLSHUTDOWN

This message is displayed when eitherthe external emergency-off pushbuttonor the full-shutdown button 7 on thecontrol panel are pressed. The result is:◗ shutdown of the inverter;◗ shutdown of the rectifier/charger;◗ opening of the battery circuit breaker;◗ activation of a relay contact on theremote-indications relay board.To fully de-energise the installation,these functions must also open theexternal, upstream circuit breakers onthe normal and bypass AC supply lines.The buzzer sounds continuously.

Control-panel display (cont.)

Page 24: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

24 - E-51028230XT/BG

◗ bypass AC source 2◗ ◗ phase-to-neutral voltage,◗ ◗ phase-to-phase voltages,◗ ◗ frequency,◗ ◗ currents of the three phases;

◗ battery 3◗ ◗ voltage;◗ ◗ charge or discharge current;◗ ◗ remaining battery time (for the UPSunit concerned);◗ ◗ battery temperature;

◗ inverter output 4◗ ◗ frequency;

Control-panel display (cont.)

Measurement system

The display 23 may be used to read anumber of input and outputmeasurements made at different pointsin the system. See, in the Appendix,figure 23.

◗ normal AC source 1◗◗ phase-to-phase voltages,◗ ◗ currents of the three phases,◗◗ frequency;

◗ total load 6◗ ◗ phase-to-neutral voltage,◗ ◗ phase-to-phase voltages,◗ ◗ currents of the three phases,◗◗ frequency,◗◗ active and apparent power.

Note:Frequency converters without batteriesare not concerned by the batterymeasurements. The displayed batteryvoltage corresponds to the DC voltageat the rectifier/charger output.Bypass AC source 2 measurementsare not displayed on frequencyconverters

Voltage measurements

These measurements may beaccessed by pressing the "V" key 14 .The following data is displayed.

Note:M1: normal AC sourceM2: bypass AC source

RMS M1 M2 LOAD RMS M2 LOAD

U12 ---- ---- ---- V1 ---- ----

U23 ---- ---- ---- V2 ---- ----

U31 ---- ---- ---- V3 ---- ----

Current measurements

These measurements may beaccessed by pressing the "A" key 15 .The following data is displayed.

Note:CF: crest factor

RMS M1 M2 LOAD FC-LOAD I-LOAD/I-NOM

I1 ---- ---- ---- -.-- ---- %

I2 ---- ---- ---- -.-- ---- %

I3 ---- ---- ---- -.-- ---- %

LOAD KW KVA PL/PN = --- % FREQ.HZ

P1 ---- ---- M1 --.-

P2 ---- ---- M2 --.-

P3 ---- ---- FP.LOAD = -.- INV --.-

Fig. 23

1

2

Q1 Q5N

QF1

U - V - I - F

U - I - F U - I F U - V - I - F - P

A B

C

D

Q4S

6431

2

Power and frequencymeasurements

These measurements may beaccessed by pressing the "W.HZ" key16 . The following data is displayed.

Note:PF: power factor

Page 25: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

E-51028230XT/BG - 25

Selections and settings

These selections and settings may beaccessed by pressing the "contrast"key 13 . The following menu isdisplayed.

Battery measurements

These measurements may beaccessed by pressing the "battery" key19 . The following data is displayed.

BATTERY

U = ---- V REMAINING TIME = ---- MIN

I = ---- A PL / PN = ---- %

T° = ---- °C

CHOOSE LANGUAGE DATE AND TIME

CONTRAST SETUP INVERSE VIDEO

BUZZER SETUP PAST EVENTS

LAMP TEST BATTERY TEST

◗ Selecting the language:FRENCH SPANISH

ENGLISH DUTCH

GERMAN SWEDISH

ITALIAN PORTUGUESE

◗ Adjusting the display contrast:DISPLAY CONTRAST SETUP

CHOOSE WITH KEYS OR

VALIDATE WITH KEY

BUZZER VOLUME SETUP

CHOOSE WITH KEYS OR

VALIDATE WITH KEY

◗ Adjusting the buzzer volume:

◗ Lamp test:When this function is selected, all thelights shine orange for three seconds.

◗ Set date and time:Use the "▲▼" keys to enter the dataand confirm using the " " key.

DATE AND TIME SETUP

YEAR ---- MONTH --

DAY -- HOURS --

MINUTES -- SECONDS --

Control-panel display (cont.)

Page 26: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

26 - E-51028230XT/BG

Control-panel display (cont.)

◗ Inverse video:When this function is selected, the textand background colours are reversed(white text on black or black text onwhite).

◗ Past events:See section "logging and time-stamping".

◗ Battery test:◗ ◗ the screen opposite is displayedwhen a battery test is requested. Itindicates the battery charge status andthe remaining service life. A manual orautomatic test may be requested,

CHARGE LEVEL = -- %

REMAINING SERVICE LIFE = -- MONTH

◗ MANUAL TEST press key

◗ AUTO TEST press key

TESTING BATTERY

U BATTERY = --- V

BATTERY TEST RESULT OK

◗◗ the screen opposite is displayedduring a battery test, whether manualor automatic,

◗◗ the screen opposite is displayedfollowing a positive, manual batterytest,

BATTERY TEST RESULT NOT OK◗ ◗ the screen opposite is displayedfollowing a negative, manual batterytest,

TIME SINCE LAST TEST

WEEK -- DAY -- HOUR --

LAST BATTERY TEST RESULT OK

NEW PARAMETERS YES = NO =

◗ ◗ the screen opposite is displayedfollowing a positive, automatic batterytest. It indicates the time since the lasttest and provides access to testsettings,

TIME SINCE LAST TEST

WEEK -- DAY -- HOUR --

LAST BATTERY TEST RESULT NOT OK

NEW PARAMETERS YES = NO =

◗◗ the screen opposite is displayedfollowing a negative, automatic battery

◗◗ the screen opposite is displayed whenthe user requests access to theautomatic test settings. It is possible tomodify the interval between twoautomatic tests,

SELECT TIME OF NEXT TEST WITH KEYS ,

CHANGE UNITS WITH

WEEK -- DAY -- HOUR --

confirm with key

Page 27: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

E-51028230XT/BG - 27

TEST INTERRUPTED

CHECK PRESENCE OF THE BATTERY

CHECK ALARMS

◗◗ the screen opposite is displayedwhen the battery test cannot becompleted.

Control-panel display (cont.)

Page 28: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

28 - E-51028230XT/BG

General

The autodiagnostic system considersany system status other than normal asa problem.Before taking any action, note downthe messages displayed on the controlpanel.Certain problems may prevent thecontrol panel from functioning.In this case, it is stronglyrecommended to call the APC bySchneider Electric after-salessupport department.◗ If the load is still correctly suppliedwith power, it has probably beentransferred to the bypass AC source(static bypass) and is therefore nolonger protected (if the system is in on-line mode);◗ if the load is no longer supplied withpower, transfer it manually to themaintenance bypass (see sectionbelow).

Alarms

Maintenance bypass

This operation is possible only if thesystem includes a bypass AC source.It results in the load being directlysupplied by the bypass AC source viamaintenance bypass switch Q3BP, thusensuring a higher level of security in theevent of a malfunction.Switching procedures are explained ondrawings next to each switch in theUPS cubicle and the external bypassunit. See section "maintenanceconfiguration".

Page 29: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

E-51028230XT/BG - 29

◗ signal to open battery circuitbreaker(s) QF1 in the event the"emergency off" button is pressed or toavoid an excessive battery discharge(lasting more than three times the ratedbackup time plus two hours);◗ full-shutdown contact (volt-freechangeover contact) used to tripswitching devices in the event of anemergency shutdown or a full shutdown(button 7 ).◗ "general alarm" information (volt-free changeover contact) whichincludes:◗ ◗ internal faults,◗ ◗ information on temperatures outsidetolerances in the battery room(optional),◗ ◗ overload information (> In),◗◗ static-switch ventilation and power-supply faults.

Note:◗ The maximum breaking capacity ofthe changeover contacts is 5A at 250V;◗ information on the battery is notsupplied to frequency converterswithout a battery.

Environment information

Terminals XR2, XR3, XR4 and XR5 onthe "Media Contacts 11" board of eachtype of unit can be used to receivesignals from the operating environmentand to transmit signals concerning theoperating status of the UPS (see figure16 for the position of the board, item12).

Signal reception

The signals should be provided by volt-free contacts.◗ emergency off:An NC contact causes shutdown of theinverter and the rectifier/charger,opening of the battery circuit breakerand activation of a relay contact on the"Media Contacts 11" board;◗ battery room ventilation fault:An NO contact causes shutdown of therectifier/charger;◗ battery circuit breaker QF1 closed:An NO contact prevents inverter start-up if the circuit breaker is open;◗ battery temperature:A PC-board, placed near the battery,supplies information on the batterytemperature, thus enabling the rectifier/charger to regulate the battery voltage;◗ "auxiliary" signals:Depending on the selected settings,these signals may be used to provoke:◗◗ forced shutdown of the inverter(whatever the status of the bypass ACsource),◗◗ protected shutdown of the inverter(load transfer to the bypass ACsource),◗◗ a change in the inverter outputfrequency (50 Hz or 60 Hz).◗ ◗ limiting of the current drawn by therectifier/charger (programmable value)when supplied by an engine generatorset with an insufficient power rating.The additional power required by theinverter is supplied by the battery whichdischarges,◗ ◗ limiting of the battery charge current(programmable value) if the normal ACsource is replaced by an enginegenerator set with an insufficient powerrating.

Signal transmission

◗ an auxiliary 24 V power supply,isolated and backed up, is used tosupply:◗◗ the undervoltage release of thebattery circuit breaker(s) QF1,◗◗ the board that measures thetemperature in the battery room;◗ "low battery" warning signal (volt-free changeover contact) indicating thatbattery time is about to run out. Thewarning threshold may bepersonalised;◗ "load on UPS" signal (volt-freechangeover contact) indicating that theload is supplied by the inverter. For asingle-UPS unit, one volt-freechangeover contact may be used toindicate that the load is supplied by thebypass AC source;◗ "load on battery power" signal(volt-free changeover contact)indicating that the inverter is suppliedby the battery in the following cases:◗◗ normal AC source outage or voltagedrop,◗ ◗ rectifier/charger shutdown,◗◗ rectifier/charger current limiting.This signal, which may be used toinitiate process saving and shutdownprocedures, is time-delayed 30seconds to avoid unnecessaryoperations following micro-breaks;◗ "maintenance position" signal(volt-free changeover contact)indicating that:◗◗ maintenance bypass switch Q3BP isclosed,◗ ◗ bypass AC source input switch Q4Sis open,◗ ◗ inverter output switch Q5N is open,◗◗ battery circuit breaker QF1 is open;

Page 30: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

30 - E-51028230XT/BG

Logging and time-stamping

Presentation of eventtime-stamping byMGE™ Galaxy™ PW

Time-stamping of events byMGE™ Galaxy™ PW makes itpossible to:◗ log the events;◗ consult the last 500 events thatoccurred on the MGE™ Galaxy™ PWUPS;

◗ consult general statistical data onUPS operation;◗ consult measurement records for anumber of physical values concerningsystem operation.The time-stamping information may beaccessed via the MGE™ Galaxy™ PWkeypad and display (standardequipment). This information may alsobe forwarded for the Teleservicefunction using the JBUS RS232/485communications board.

Utilisation via theMGE™ Galaxy™ PWdisplay

Main menu

The time and date can be set for theUPS via the main menu on the display(see below), using the DATE ANDTIME command. The time-stampinginformation, statistics andmeasurement records are alsoavailable via the same menu, using thePAST EVENTS command.Simply select the desired commandwith the ">" sign that can be movedusing the and keys. Theselected command can be confirmed

DATE AND TIME SETUP

>YEAR 1997 MONTH 9

DAY 8 HOURS 8

MINUTES 11 SECONDS 42

and keys to scroll up and downthrough the screens.For time-stamped events, the displaybegins with the last event logged.To access older events, press the key. If during consultation, you wish toreview more recent events, press the

key.

Setting the date and timefor the UPSWhen the DATE AND TIME commandis selected, the screen presentedopposite is displayed:◗ the current values are automaticallydisplayed;◗ you can modify any of the displayedvalues;◗ position the ">" sign opposite thevalue to be modified. Then press the

key;◗ use the and keys to modifythe value;◗ the key increments the value byone;◗ the key decrements the value byone;◗ the selected value can be confirmedby pressing the key. A secondvalue may then be selected formodification, again using the and

keys;◗ modifications are made andconfirmed value by value;◗ press the key at any time to exitthe DATE AND TIME function.

by pressing the key.General instructions forusing most screensYou can display the desired informationand enter commands using the , and keys.Press the key to exit the time-stamping consultation mode and returnto the main menu. If no commands areentered for five minutes, the systemautomatically returns to the normaldisplay mode.You can scroll through the screensdisplaying information. Press the

Page 31: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

E-51028230XT/BG - 31

DATE AND TIME SETUP

>YEAR 1997 MONTH 9

DAY 8 HOURS 8

MINUTES 11 SECONDS 42

02/09/1997 07:25:03 Appearance:

MAINS 1 INPUT SWITCH Q1 IS OPEN

Example:

Note: numerical values are never indicated in screens for time-stamped events.For example:

03/09/1997 15:30:23 Disappearance:

OVERLOAD

RATED CURRENT PER PHASE = _ _ _ A

CHECK LOAD LEVEL

Consulting statisticsSee the screen opposite.◗ total backup time (h): this is thetotal time of operation on battery powersince initial startup of the UPS. It isexpressed in hours;◗ total time on static switch (h):this is the total time of operation on thestatic switch since initial startup of theUPS. It is expressed in hours;◗ total time on UPS (d): this is thetotal time that the load has beensupplied by the UPS since initialstartup. It is expressed in days;

FIGURES SINCE COMMISSIONING

total backup time (h): 0

total time on static switch (h): 0

total time on UPS (d): 3627

total time with Tbatt >25°C (h): 1

FIGURES SINCE RESET

last reset: 05/09/1997

elapsed backup time (min): 0

That is the only means to leave thefunction.If no modifications to values areconfirmed, exiting the functioncorresponds to cancelling the request.

Consulting logged (time-stamped) eventsWhen the PAST EVENTS command isselected, the system displays a screenindicating the last event logged. Logscreens are very similar to thosedisplayed for current events. However,log screens include a line indicating thecorresponding date and time with themention "Appearance of" or"Disappearance of", followed by thestandard text for the event (seeexample opposite). Consult the usermanual for indications on the meaningof events.The complete log may comprise up to500 events. If over 500 events haveoccurred, only the last 500 may beconsulted:◗ press the key to display the eventthat occurred just before the displayedevent. If the displayed event is theoldest in the list, the display is notmodified;◗ press the key to display the eventthat occurred just after the displayedevent. If the displayed event is the mostrecent in the list, the display is notmodified.

Logging and time-stamping (cont.)

Page 32: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

32 - E-51028230XT/BG

Logging and time-stamping (cont.)

◗ total time with Tbatt > 25° C (h):this is the total time of operation withthe battery temperature greater than25° C since initial startup of the UPS.It is expressed in hours;◗ last reset: this is the date that theinformation was last set to zero by theTeleservice function;◗ elapsed backup time (min): this isthe total time of operation on batterypower since the last reset. It isexpressed in minutes.◗ nb of backups: this is the number oftimes the load was supplied by the UPSfrom battery power since the last reset;◗ nb of backups < 1 min: this is thenumber of times the load was suppliedby the UPS from battery power for lessthan one minute, since the last reset;◗ 1 min < nb of backups < 3 min: thisis the number of times the load wassupplied by the UPS from batterypower for more than one minute andless than three minutes, since the lastreset;

Use the and keys to shift between the beginning and the end of the display.

FIGURES SINCE RESET

nb of backups: 0

nb of backups < 1 min: 0

1 min < nb of backups < 3 min: 0

nb of backups > 3 min: 0

nb of overloads < 5 s: 0

nb of overloads > 5 s: 0

nb of times TBatt. > 25°C: 0

◗ nb of backups > 3 min: this is thenumber of times the load was suppliedby the UPS from battery power formore than three minutes, since the lastreset;◗ nb of overloads < 5 s: this is thenumber of times the UPS wasoverloaded (output current greater thanIn) for less than five seconds, since thelast reset;

PARAMETER NAME (units) T=30 days

last read: 05/09/1997

M(t+29T)|M(t+23T)|M(t+17T)|M(t+11T)|M(t+05T)| | | |

M(t+28T)|M(t+22T)|M(t+16T)|M(t+10T)|M(t+04T)| | | |

M(t+27T)|M(t+21T)|M(t+15T)|M(t+09T)|M(t+03T)| | | |

M(t+26T)|M(t+20T)|M(t+14T)|M(t+08T)|M(t+02T)| | | |

M(t+25T)|M(t+19T)|M(t+13T)|M(t+07T)| M(t+T)| | | |

M(t+24T)|M(t+18T)|M(t+12T)|M(t+06T)| M(t)

◗ nb of overloads > 5 s: this is thenumber of times the UPS wasoverloaded (output current greater thanIn) for more than five seconds, sincethe last reset;◗ nb of times TBatt. > 25° C: this isthe number of times the batterytemperature was measured at over25° C, since the last reset.

Consulting recordedmeasurements

Recorded measurements are presentedin the same manner (see opposite):◗ the lists indicate the last 30measurements recorded for the givenparameter. The chronological order ofthe measurements is indicated in thefigure opposite;◗ the most recent measurement ispresented first, in the upper left-handcorner of the list. The followingmeasurement is listed just below, andso on until the 30th value listed in thebottom right-hand corner of the list;◗ the period T between two successivemeasurements is 30 days.The displayed measurements areinstantaneous values.Note: when this screen is selected,approximately ten seconds are requiredto call up and display the information.If the number of measurements isgreater than 30, only the last 30 (themost recent) are displayed.

Page 33: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

E-51028230XT/BG - 33

BACKUP (min) T=30 days

last read: 05/09/1997

120 | 0 | 0 | 0 | 0115 | 0 | 0 | 0 | 0110 | 0 | 0 | 0 | 0105 | 0 | 0 | 0 | 00 | 0 | 0 | 0 | 00 | 0 | 0 | 0 | 0

OUTPUT LOAD LEVEL(%) T=30 days

last read: 05/09/1997

63 | 0 | 0 | 0 | 052 | 0 | 0 | 0 | 063 | 0 | 0 | 0 | 063 | 0 | 0 | 0 | 00 | 0 | 0 | 0 | 00 | 0 | 0 | 0 | 0

Utilisation viaTeleservice

When the optional JBUS RS232/485communications board is installed, thetime-stamped information can be sentto the Teleservice centre.The centre can remotely consult thesame information and carry out thesame modifications as the user locallyon the display. Note that only theTeleservice centre can reset thecounters for the statistical data.

BATTERY CAPACITY (Ah) T=30 days

last read: 05/09/1997

97 | 0 | 0 | 0 | 096 | 0 | 0 | 0 | 095 | 0 | 0 | 0 | 094 | 0 | 0 | 0 | 00 | 0 | 0 | 0 | 00 | 0 | 0 | 0 | 0

The backup time is the valuecalculated by the UPS microprocessoron the basis of measurements carriedout on the battery. It is expressed inminutes. The calculation uses thepercent load and the battery chargestatus at the time of the measurement.

The load level is the ratio between thepower supplied by the UPS to the loadat the time of the measurement and therated output of the UPS. It is expressedas a percentage.

The battery capacity is the valuemeasured by the UPS microprocessor.It is expressed in Ampere-hours.This value changes over timedepending on the parameters of thebattery itself and its environment.This measurement is used to checkthat the battery is capable of supplyingthe rated power in the event of a mainsoutage.

Logging and time-stamping (cont.)

Page 34: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

34 - E-51028230XT/BG

Maintenance

Maintenanceconfiguration

Single-UPS unit or UPS in"ECO" modeSee figure 24. During maintenance, theUPS must be isolated from the normaland bypass AC source, the battery andthe load.◗ UPS isolationProceed in the following order (seefigure 25):◗ ◗ shut down the inverter (press the"inverter OFF" button 9 for threeseconds),◗◗ close bypass switch Q3BP,◗◗ open isolating switches Q5N, Q4S,QF1 and Q1.The UPS is powered down once thecapacitors have discharged (a fewminutes);◗ start-upFollowing servicing, proceed in thefollowing order (see figure 26):◗◗ close switch Q1, then afterapproximately ten seconds, switchesQF1, Q5N and Q4S,◗◗ open bypass switch Q3BP,◗ ◗ start the inverter (press the "inverterON" button 8 ).

Caution◗ work should be carried out inaccordance with applicable safetyregulations;◗ to avoid interrupting the load, thevarious switching operations must becarried out in the correct order.Operations are explained in diagramsplaced next to the switches;◗ the system cubicle is only partiallypowered down. The load is stillsupplied via the bypass AC source andswitch Q3BP.

Fig. 24

Fig. 25

Q1 Q5N

QF1

Q3BP

Q4S

A B

CD

1

2

1010 1010

10 10

1010

101010

Q5NQ1 Q4S

3

1

2

10

Q3BP

1010

1010

5

4

6

QF1

0 I

Fig. 26

OFFOFF10

10

101010 10

Q5NQ1 Q4S

3

1

2

Q3BP

1010

5

4

6

10 1010 10

OFF

10

QF1

0 I

Page 35: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

E-51028230XT/BG - 35

Redundant, parallel UPSSee figures 27 and 28 in the Appendix.During maintenance, a UPS unit mustbe isolated from the normal AC source,its battery and the output circuits of theother UPS units.◗ isolate one UPS (see figure 27)Proceed in the following order (seefigure 25 without Q3BP):◗◗ shut down the inverter (press the"inverter OFF" button 9 for threeseconds),◗◗ open isolating switches Q5N, Q4S,QF1 and Q1.The UPS unit is powered down oncethe capacitors have discharged (a fewminutes);◗ start-upFollowing servicing, proceed in thefollowing order (see figure 26 withoutQ3BP):◗◗ close switch Q1, then afterapproximately ten seconds, switchesQF1, Q5N and Q4S,◗◗ start the inverter (press the "inverterON" button 8 ).

Note: if the load is still suppliedby an inverter, the Q3BP switch onthe unit undergoing maintenancemust not be closed.

To fully isolate the installation, proceedas indicated below:◗ isolate all UPSs (see figure 28)Proceed in the following order (seefigure 25):◗◗ shut down the inverters (press the"inverter OFF" buttons 9 for threeseconds),◗ ◗ close the Q3BP switches used tobypass the units (no units havepriority),◗◗ open isolating switches Q5N, Q4S,QF1 and Q1.The UPS units are powered down oncethe capacitors have discharged (a fewminutes).◗ start-upFollowing servicing, proceed in thefollowing order (see figure 26):◗◗ close switches Q1, then afterapproximately ten seconds, switchesQF1, Q5N and Q4S,◗◗ open the Q3BP switches,◗◗ start the inverters (press the "inverterON" buttons 8 ).

Fig. 27 Fig. 28

1

D

2

BA

Q3BP

Q1 Q5N

Q4S

QF1

C

1

D

2

BA

Q3BP

Q1 Q5N

Q4S

QF1

C

1

D

2

BA

Q3BP

Q1 Q5N

Q4

QF1

C

1

D

2

BA

Q3BP

Q1 Q5N

Q4S

QF1

C

Maintenance (cont.)

Page 36: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

36 - E-51028230XT/BG

��

��

��

���

��

��

��

��

��

��

��

��

� � � ��� �� ��

���

���

���

���

���

���

����� ���

�!�

" #

�������������

������������������

� � � ��

���������������������������

��

��

��

��

����� �����

��

��

��

��

� � � �

�� ��

�� �� ��

���

���

���

���

���

���

����� ���

�!�

" #

�������������

������������������

� � � ��

�� ������������������������

��

��

��

��

��

��

��

��

��

��

��

� �

��

��

Parallel UPS for increasedoutputSee figure 29.◗ isolate all UPSsProceed in the following order (seefigure 30):◗◗ shut down the inverters (press the"inverter OFF" buttons 9 for threeseconds),◗ ◗ close switch Q3BP and openswitches Q5N and Q4S in the parallel-connection unit,◗ ◗ open switches Q1, QF1 and Q5N onthe UPS units.◗ start-upFollowing servicing, proceed in thefollowing order (see figure 31):◗◗ close switches Q5N on the UPSunits,◗◗ close switch Q4S, then switch Q5N,in the parallel-connection unit,◗◗ open switch Q3BP in the parallel-connection unit,◗◗ close switches Q1 and QF1 on theUPS units,◗◗ start the inverters (press the "inverterON" buttons 8 ).

Note:We recommend that you call on theafter-sales support department to carryout these operations.Note that for parallel UPSs forincreased output, the entire installationmust be bypassed because it is notpossible to isolate just one UPS unit.

Maintenance (cont.)

Fig. 29

Fig. 30

Fig. 31

2

1

Q3BP

Q4S

Galaxy 1

Galaxy 22

1Galaxy 32

1Galaxy 42

Q5N1

2

Q1

QF1

Q5N

Q4S

Page 37: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

E-51028230XT/BG - 37

Battery maintenance

Consult the instructions supplied by thebattery manufacturer. Below are a fewgeneral indications:◗ sealed lead-acid batteries: thesebatteries require no maintenance, butcheck the terminals of each cell fromtime to time and clean if necessary;◗ vented lead-acid batteries:◗◗ check the electrolyte level regularlyand add water if necessary,◗◗ check the voltage of each cell todetermine if it is necessary to equalisethe battery,◗◗ check the terminals of each cell andclean if necessary.

Caution:Battery maintenance is undertaken withthe system powered up. Operationsmust be carried out in accordance withapplicable safety regulations byqualified personnel using insulatedtools, gloves and safety goggles.Batteries contain dangeroussubstances that will harm theenvironment if thrown away. If youchange the batteries yourself, call onqualified organisations for batteryrecovery and recycling.

Visual check

◗ Power down the system prior to anymaintenance operations.Note: in redundant, parallel UPSsystems and frequency converters, thecheck may be carried out successivelyon each UPS unit without interruptingthe load. In other configurations, theload must be supplied via themaintenance bypass (see"maintenance bypass" in the "Alarm"section);◗ clean the system regularly,particularly the air inlet and outlet grills.Check that the air circulates freely inthe cubicles. Use a vacuum cleaner ifnecessary;◗ check that nothing hinders theventilation at the top and at the back ofthe system;◗ check that all the fans operatecorrectly.

Functional check

◗ Check that lights 1 , 2 and 3 onthe control panel are not red, to avoidan interruption in the supply of power tothe load due to incorrect transferconditions or a battery problem;◗ press the "inverter OFF" button andcheck that the buzzer and control panellights function correctly (see the sectionon operating modes in the introduction);◗ press the "inverter ON" button andcheck again that the control panel lightsfunction correctly;◗ run a transfer to battery test. With theinverter on, open input switch Q1. Theorange "battery" light on the controlpanel should light. After two minutes onbattery power, close input switch Q1.The rectifier/charger shouldautomatically restart and the orange"battery" light on the control panelshould go off;◗ in parallel systems, run these testson each UPS unit.

Pb Pb

Maintenance (cont.)

Page 38: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

38 - E-51028230XT/BG

Maintenance (cont.)

Training center

Training centersSchneider Critical Power & cooling services50 Hz :

France Training Centre140, Avenue Jean KuntzmannInnovallée38334 - St Ismier CedexFrance

Tel: +33 (0)4 76 18 34 14Fax: +33 (0)4 76 18 45 21

Singapore Training Centre10 Ang MO Kio Street 65, #03-06/10Techpoint BuildingSingapore 569059Singapore

Tel: +65 6389 6792

China Training CentreNo. 999, Shen Fu RoadMin Hang DistrictShanghai 201108P.R. China

Tel: +86 21 3407 3365Fax: +86 21 3407 4526

Internet : Http://powerlearning.apc.comOn-line catalogue and registration.

To allow you to useAPC by Schneider Electric products effectively and carry out basic maintenance, we offer a complete range oftechnical training courses in English and French.

Training centerSchneider Critical Power & cooling services50-60 Hz :

United States Training Centre132 Fairgrounds RoadWest Kingston - RI02892U.S.A

Tel: +1 877 800 4272

Page 39: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

E-51028230XT/BG - 39

Harmonics filter andpower factorimprovement

This option, placed on the normal ACinput upstream of the UPS in the 1.9meter high UPS cubicle for UPSs up to120 kVA and in an auxiliary cubicle forhigher ratings, reduces the reinjectionof harmonic currents into the normalAC source. Harmonic reinjection,produced by the rectifier/charger,increases distortion on the normal ACsource. The amount of the increasedepends on the source impedance.The reduction in distortion reduces therisk of disturbing other sensitive loadsconnected to the mains. The filter canalso increase the power factorupstream of the inverter.Three types of filter are available:◗ uncompensated filter for theadvantages listed above;◗ compensated filter for theadvantages listed above and to limit thecapacitive current absorbed by the filter(additional inductance), in the event theUPS is supplied by an engine generatorset;◗ active harmonic conditioner, the mosteffective solution because it providesthe harmonics drawn, thus allowing thenormal AC source to supply a perfectlysinusoidal current. The conditioner maybe installed in an auxiliary cubicle orwall-mounted.

Isolating and voltagematching transformerfor the normal andbypass AC source andthe load

This transformer, placed in the 1.9meter high UPS cubicle up to 60 kVAand in an auxiliary cubicle for highervalues, may be used to match thebypass AC voltage to that of theinverter, to create galvanic insulationbetween the load and the Ac sources orto create the appropriate systemearthing arrangement.

Options

Safety of life andproperty

◗ backfeed protection. This option,installed upstream of the static bypass,is used to mechanically disconnect thebypass AC source when the systemhas shifted to battery power or whenthe bypass AC source has failed. Thissystem is intended to enhance thesafety of life and property.

Page 40: MGE™ Galaxy™ PW - - APC USA · 4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to

40 - E-51028230XT/BG

Empty cubicles

Cubicles may be supplied empty, thusenabling users to make up their ownauxiliary cubicles (battery cubicles orother) or panels and meet the particulardemands of each installation. In thisway, the entire electrical installation willhave a uniform appearance.The following cubicles are available:◗ battery cubicles, 815 and 1015 mmwide, 1.4 and 1.9 meters high;◗ auxiliary cubicles, 815 mm wide, 1.4and 1.9 meters high.

Electrical supervision

"Teleservice""Teleservice" is a contract offeringcontinuous remote supervision andmaintenance of UPS systems via amodem. Real-time communication isestablished with our "Teleservice"centre for communication of all alarmsand events occurring in the installation.

GTC boardThis electronic board provides useraccess to the J-Bus communicationsprotocol. Using the data and addresstables provided, the user can customisehis installation.

GTC + softwareThe user has access to the J-Busprotocol and, in addition, the associatedsoftware acquires system parameters(measurements, status conditions) andtransforms them into diagrams, alarmmessages and tables. With the click ofa mouse, the user can locally orremotely supervise the UPS system(comprising one or many UPS units).

Management of computernetworks

Integrated SNMP agentThis electronic board, installed in theUPS system, enables direct connectionto all Ethernet networks using TCP/IP.The UPSs may then be supervised viathe computer network. Furthermore,they can be used to close system fileswithout having to add an externalSNMP agent.This board is fully compatible with"Solution PacTM" software.

0080C8ABAA01

The RJ45 connector of thecommunications option deliversinformation using the SNMP protocol.The sticker located on the boardindicates the UPS MAC address.

◗ your MAC address is written in thefollowing way : 0080C8 ZZ XX YY ;◗ your default IP address is 168.8.xx.yy(xx and yy aredecimal values of XX and YY).

For example, MAC address 00 80 C8AB AA 01 is related to IP address168.8.170.1.

Please refer to the "userman.doc"user manual contained in thedirectory "emb/galaxy/snmp/release3.xx" of the Solution-Pac CD-ROM in order to discover themanagement capabilities of your SNMPMGE™ Galaxy™ PW UPS.Please contact your salesrepresentative for more detailedinformation.

Two-channel network boardThis electronic board comprises twoports, each of which may be user set,either for the U-Talk protocol or as arelay contact.U-Talk is the protocol required toestablish contact with thecommunications software.Relay contacts may be used for specificnetwork applications (IBM AS400,Novell, etc.).

Options (cont.)