Upload
emmeline-goodman
View
219
Download
3
Tags:
Embed Size (px)
Citation preview
Micro Design
System Capacity
**100
*(1 )r
gR
ET TGross Application F
EU L
dayplantgalf
SSFF rpg
dgp //**
623.0)/(
100( )11.6 ( / )
( )ft tapeQ gpm
Application Rate in hrLateral spacing in
( ) ( )
( )
453 ( )in ac
hr
D ASystem Q gpm
T
( ) ( )
( )
453 ( )in ac
hr
D ASystem Q gpm
T
D = gross application for what ever time period ( hrs, day or days)T= hours in time period used to decide “D” (max 22hrs/day)A= Acres irrigated
**100
*(1 )r
gR
ET TGross Application F
EU L
Wetted Area vs Area
Irrigated area vs. wetted areaET rates are computed and published
assuming that the depth comes from the whole area, not just the canopy area or the wetted area. ET rate, expressed as depth per unit of time, is largely governed by the amount of energy available to convert liquid water into vapor (i.e. ET), and therefore does not depend upon the tree size (once the canopy exceeds 65% of the surface area), or the wetted area (as long as there is sufficient root mass to absorb the required water).
Crop Water Needs Example Calculate capacity required for a proposed 1 ac. Micro
irrigation system on Vegetables. Using drip tape with a flow of 0.45 gpm/100’ and 12” emitter spacing, 200 ft rows, 5 ft row spacing, and 10 zones of 0.1 ac each. Design EU of 90%
Q = 453*DA TD = .2” / system
efficiencyA = AreaT = 22 hrs
Crop Water Needs Example Answer
Q = 453*DA T
= 453 x (.2”/.9) x 1 ac22 hrs
= 4.5 gpm
Each field will have a capacity of 4.5 gpm.◦ 200 ft rows with a 0.45 gpm/100’ drip tape
flow will give you 0.9 gpm per row.◦ At 5 ft row spacing, 1 ac will have
approximately 10 zones, each of these zones will have 5 rows, 200 ft long.
◦ 5 rows times 0.9 gpm/row is 4.5 gpm per field.
Minimum water requirement is 4.5 gpm for 1 ac, we only need to run 1 field at a time to meet the crop water demand.
Hours of irrigation per day to apply .2”(1 zone of 0.1 ac each)
T = 453*DA Q
= 453 x (.2”/.9) x 0.1 ac4.5 gpm
= 2 hrs and 15 minutes
WELL
10:1
5 a
.m.
zon
e 2
8:0
0 a
.m.
zon
e 1
2:4
5 p
.m.
zon
e 4
5:1
5 p
.m.
zon
e 5
7:3
0 p
.m.
zon
e 6
12:3
0 p
.m.
zon
e 3
9:4
5 p
.m.
zon
e 7
12:0
0 a
.m.
zon
e 8
2:1
5 a
.m.
zon
e 9
4:3
0 a
.m.
zon
e 1
0
Adjust flow rate or set time
If Ta is greater than 22 hr/day (even for a single-station system), increase the emitter discharge
If the increased discharge exceeds the recommended range or requires too much pressure, either larger emitters or more emitters per plant are required.
Practice problem – Set time and Qs
Pressure flow relationship (Pa)
1
xa
a
qP
K
Where:
qa= average emitter flow rate (gph)
Pa = average pressure (psi)
x = emitter exponentK = flow constant
EU is related to Friction loss
x
a
n
a
n
x
a
n
a
n
q
q
P
P
P
P
q
q
1
Emission Uniformity
1 1.27 100
1 1.27 100
n
a
x
n
a
qCVEU
qn
or
PCV
Pn
Lateral Line DesignImportant lateral characteristics
◦Flow rate◦Location and spacing of manifolds◦Inlet pressure◦Pressure difference
Design objectiveLimit the pressure differential to
maintain the desired EU and flow variation
The pressure differential is affected by◦Lateral length and diameter
Economics longer and Larger
◦Manifold location◦slope
Four Cases
Effects of slope
Allowable pressure loss (subunit)
This applies to both the lateral and subunit. Most of the friction loss occurs in the first 40% of the lateral or manifold
nas PPP 5.2 Ranges from 2 to 3 but generally considered to be 2.5
DPs =allowable pressure loss for subunit
Pa = average emitter pressure
Pn = minimum emitter pressure
Example
Given: CV=0.03, 3 emitters per plant, qa = .43gph Pa=15 psi, EU=92, x=0.57
Find: qn, Pn, and P
Solution
1 1 1
.57
0.031 1.27 100 92 1 1.27 100
0.433
92 0.430.404
.031 1.27 100
3
0.404 15 13.474
0.43
2.5 2.5 15 13.47 3
n n
a
n
x xn n n
n aa a a
a n
q qCVEU
qe
q
P q qP P
P q q
P P P
.83psi
Practice problem - allowable loss
Start with average lateral
Flow rate
Where:l = Length of lateral, ft. (m).Se = spacing of emitters on the lateral, ft. (m).ne = number of emitters along the lateral.qa = average emitter flow rate, gph (L/h)
6060aea
el
qnq
S
lq
Determine optimum lateral lengthEU SlopeBased on friction loss
◦ limited to ½ the allowable pressure difference (ΔPs)
HydraulicsLimited lateral losses to 0.5DPs
Equation for estimating◦Darcy-Weisbach (best)◦Hazen-Williams◦Watters-Keller (easiest, used in NRCS
manuals)
LDC
QFhf 87.4
852.1
5.10
C factor Pipe diameter (in)
130 ≤ 1
140 < 3
150 ≥ 3
130 Lay flat
Hazen-Williams equation
hf =friction loss (ft)
F = multiple outlet factor
Q = flow rate (gpm)
C = friction coefficient
D = inside diameter of the pipe (in)
L = pipe length (ft)
Watters-Keller equation
75.4
75.1
D
QKFLh f
hf = friction loss (ft)
K = constant (.00133 for pipe < 5” .00100 for > 5”)
F = multiple outlet factor
L = pipe length (ft)
Q = flow rate (gpm)
D = inside pipe diameter (in)
Multiple outlet factorChristiansen's equation for computing
the reduction coefficient (F) for pipes with multiple, equally spaced outlets where the first outlet is Sl from the mainline is:
F = Reduction factorN= number of outletsM= exponent depends on which friction equation is used
Multiple outlet factors
Number of outlets
FNumber of
outlets
F
1.851 1.752 1.851 1.752
12345678
1.000.640.540.490.460.440.430.42
1.000.650.550.500.470.450.440.43
910-1112-1516-2021-3031-70>70
0.410.400.390.380.370.360.36
0.420.410.400.390.380.370.36
Adjust length for barb and other minor losses
86.1711.0 ie DBf
OrOr use
equation
Where Fe= equivalent length of lateral, ft)K = 0.711 for English units)B = Barb diameter, inD = Lateral diameter, in
Adjusted length
e
ee
S
fSLL
L’ = adjusted lateral length (ft)
L = lateral length (ft)
Se = emitter spacing (ft)
fe = barb loss (ft)
Barb lossMore companies are giving a Kd
factor now days
2
2f e d ft f f e
Vh K h h eh
g
Example
Given: lateral 1 diameter 0.50”, qave=1.5gpm,
Barb diameter 0.10” lateral 2 diameter 0.50”,
qave=1.5gpm, kd=.10
Both laterals are 300’ long and emitter spacing is 4 ft
Find: equivalent length for lateral 1 and htotal for lateral 2
Solution
1.86
1.75
4.75
0.711*.1 .5 0.258
4 .258300 319.4
4
1.519.4 .36 0.00133 0.51
.5
ef
L
hf ft
fth
fth
gV
fpsV
et
e
h
675.75*009.0
009.009.0*1.0
09.02
45.2
45.20.5
1.5409.0
2
2
Lateral 1 Lateral 2
Procedure
Step 1 - Select a length calculate the friction loss
Step 2 – adjust length to achieve desired pressure difference ( 0.5DHs)
75.2
a
bab L
Lhfhf
36.0
af
bfab h
hLL
Practice problem Lateral length
Step 3 - adjust length to fit geometric conditions
Step 4 - Calculate final friction loss
Step 5 – Find inlet pressure
Step 6 – Find minimum pressure
Next step is to determine Δh
Paired Lateral
Single Lateral – ◦ Slope conditions
S > 0
S = 0
◦ Slope Conditions S < 0 and –S > friction slope
75.211 zhzEh f
fhEh
fhElh
fhElh )(
Last condition
57.157.057.1
36.00.1
ff
ff
ff h
EFh
h
EFEorh
h
E
h
Eh
S < 0 and –S < Friction slope
Which ever is greater
Inlet pressureEstimate with the following equation
Single Lateral
Paired Lateral
Better to use computer program
30.433
4 2f
l a
h ElP h
3.753.750.75 1 2 1 0.4332l a fp
EP h h z z z
Find minimum lateral pressure
Where S > 0 or S=0
Where S < 0 and –S < Friction slope
Where S < 0 and –S > friction slope
n lP P P
n lP P
n lP P P
Calculate final EU
1 1.27 100
1 1.27 100
n
a
x
n
a
qCVEU
qn
or
PCV
Pn
Practice problem pressure difference and EU
Block HydraulicsAvg lateral inlet pressure
Becomes the avg outlet pressure for manifold
Manifold hydraulics
Allowable manifold lossAllowable pressure loss – lateral
lossesCalculate losses using Hazen-
Williams etc.Find minimum and maximum
outlet pressures for manifold use this to calculate maximum and minimum lateral flow rate
Calculate block EU and flow variation
Block EU
Flow variation
𝑞𝑣𝑎𝑟=𝑞𝑚𝑎𝑥−𝑞𝑚𝑖𝑛
𝑞𝑚𝑎𝑥