16
MINI-SPLIT SYSTEMS MS7C/MS7H Lennox ® 7 Series Single Zone - R-410A Bulletin No. 210612 October 2012 Supersedes June 2012 SEER up to 22.00 0.75 to 2.5 Tons Cooling Capacity - 9,000 to 28,000 Btuh Heat Pump Heating Capacity - 9,500 to 28,400 Btuh MODEL NUMBER IDENTIFICATION MS 7 - CO - 12 P 1 A Major Revision Series Type MS = Mini-Split Nominal Cooling Capacity 09 = 0.75 tons 12 = 1 tons 18 = 1.5 tons 24 = 2 tons 30 = 2.5 tons Minor Revision Voltage L = 115V-1phase-60hz P = 208/230V-1phase-60hz OUTDOOR UNITS Unit Type CO = Air Conditioner Outdoor Unit HO = Heat Pump Outdoor Unit INDOOR UNITS MS7-CO Air Conditioner Outdoor Unit MS7-HO Heat Pump Outdoor Unit MS7-CI Air Conditioner Indoor Unit MS7-HI Heat Pump Indoor Unit MS 7 - CI - 12 P 1 A Major Revision Series Type MS = Mini-Split Nominal Cooling Capacity 09 = 0.75 tons 12 = 1 tons 18 = 1.5 tons 24 = 2 tons 30 = 2.5 tons Minor Revision Voltage L = 115V-1phase-60hz P = 208/230V-1phase-60hz Unit Type CI = Air Conditioner Indoor Unit HI = Heat Pump Indoor Unit Number of Zones 1 = One Zone Number of Zones 1 = One Zone Wireless Remote Control (furnished) PRODUCT SPECIFICATIONS

MINI-SPLIT SYSTEMS MS7C/MS7H · MS7C/MS7H - Mini-Split Systems / Page 5 WIRELESS REMOTE CONTROL (FURNISHED) Complete remote control of system. Maximum operating range is 25 ft. FAN

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Page 1: MINI-SPLIT SYSTEMS MS7C/MS7H · MS7C/MS7H - Mini-Split Systems / Page 5 WIRELESS REMOTE CONTROL (FURNISHED) Complete remote control of system. Maximum operating range is 25 ft. FAN

M I N I - S P L I T S Y S T E M S

MS7C/MS7HLennox® 7 Series

Single Zone - R-410A Bulletin No. 210612

October 2012Supersedes June 2012

SEER up to 22.000.75 to 2.5 Tons

Cooling Capacity - 9,000 to 28,000 BtuhHeat Pump Heating Capacity - 9,500 to 28,400 Btuh

MODEL NUMBER IDENTIFICATION

MS 7 - CO - 12 P 1 A

Major Revision

Series Type MS = Mini-Split

Nominal Cooling Capacity 09 = 0.75 tons 12 = 1 tons 18 = 1.5 tons 24 = 2 tons 30 = 2.5 tons

Minor Revision

VoltageL = 115V-1phase-60hz P = 208/230V-1phase-60hz

OUTDOOR UNITS

Unit Type CO = Air Conditioner Outdoor Unit

HO = Heat Pump Outdoor Unit

INDOOR UNITS

MS7-CO Air Conditioner Outdoor Unit MS7-HO Heat Pump Outdoor Unit

MS7-CI Air Conditioner Indoor Unit MS7-HI Heat Pump Indoor Unit

MS 7 - CI - 12 P 1 A

Major Revision

Series Type MS = Mini-Split

Nominal Cooling Capacity 09 = 0.75 tons 12 = 1 tons 18 = 1.5 tons 24 = 2 tons 30 = 2.5 tons

Minor Revision

VoltageL = 115V-1phase-60hz P = 208/230V-1phase-60hz

Unit Type CI = Air Conditioner Indoor Unit

HI = Heat Pump Indoor Unit

Number of Zones 1 = One Zone

Number of Zones 1 = One Zone

Wireless Remote Control

(furnished)

P R O D U C T S P E C I F I C AT I O N S

Page 2: MINI-SPLIT SYSTEMS MS7C/MS7H · MS7C/MS7H - Mini-Split Systems / Page 5 WIRELESS REMOTE CONTROL (FURNISHED) Complete remote control of system. Maximum operating range is 25 ft. FAN

MS7C/MS7H - Mini-Split Systems / Page 2

FEATURES - OUTDOOR UNITS

EQUIPMENT Warranty

Compressor - limited warranty for five years in residential installations and one year in non-residential installations.All other covered components - five years in residential installations and one year in non-residential installations.Refer to Lennox Equipment Limited Warranty certificate included with unit for specific details.

APPLICATIONSSEER up to 22.00.HSPF (Heat Pumps) up to 10.20.0.5 through 2.5 ton.Single phase power supply (115V and 208/230V).Outdoor unit sound levels as low as 63 dB.Ductless mini-split systems provide a wide range of capacities and applications and provide an alternative when a ducted system is impractical or cost prohibitive. See AHRI System Matches.Units shipped completely factory assembled, internally piped, and wired.Installer must set outdoor unit, hang indoor unit, connect refrigerant lines, and make electrical connections to complete job

APPROVALSAHRI Certified to AHRI Standard 210/240-2008.Tested in the Lennox Research Laboratory environmental test room.Rated according to U.S. Department of Energy (DOE) test procedures.Indoor and outdoor units and components within bonded for grounding to meet safety standards for servicing required by UL and CEC.Units are UL and ULC listed.Energy Star® certified units are designed to use less energy, help save money on utility bills, and help protect the environment. Many Lennox home comfort systems meet Energy Star requirements when used with matching components.

REFRIGERATION SYSTEM

R-410A RefrigerantNon-chlorine, ozone friendly, R-410A.Unit pre-charged with refrigerant.Outdoor CoilAluminum fins fitted to copper tubes.Wire grille guard provided.Outdoor FanDirect drive fan moves large air volumes uniformly through entire condenser coil for high refrigerant cooling capacity.Fan guard provided.Refrigerant Line Connections, Service ValveFlare connection lines are located on side of unit cabinet.Fully serviceable brass service valve prevents corrosion and provide access to refrigerant system. Shut-off valve on can be fully shut off while 2-way service valve (with service port) may be front seated to manage refrigerant charge while servicing system.NOTE - Special Male Flare Adaptor is required to check operating pressures. See Optional Accessories table.

COMPRESSOR

Variable Frequency Rotary CompressorTwin rotary compressor features high efficiency operation.Balanced for reduced vibration and quiet operation.Brushless DC motor uses powerful Neodymium magnets, which are approximately 15-20 times stronger than ferrite magnets used in conventional AC compressors.Compressor Crankcase Heater (MS7-HO-30P Heat Pump Models only)Protects against refrigerant migration that can occur during low ambient operation.

ContentsDimensions - Indoor Units .........................................13Dimensions - Outdoor Units........................................12Electrical Data...............................................................8Features - Indoor Units .................................................4Features - Outdoor Units ..............................................2Indoor Unit Air Throw Data .........................................11Installation Clearances ...............................................13Model Number Identification .........................................1Optional Accessories ..................................................10Sound Data - Indoor ...................................................11Sound Data - Outdoor.................................................11Specifications - Air Conditioner Systems ......................8Specifications - Heat Pump Systems............................9System Matches - Air Conditioners.............................11System Matches - Heat Pumps ..................................11System Optimal Operating Ranges ............................10

Page 3: MINI-SPLIT SYSTEMS MS7C/MS7H · MS7C/MS7H - Mini-Split Systems / Page 5 WIRELESS REMOTE CONTROL (FURNISHED) Complete remote control of system. Maximum operating range is 25 ft. FAN

MS7C/MS7H - Mini-Split Systems / Page 3

FEATURES - OUTDOOR UNITS

CONTROLS

DC Inverter ControlProvides continuous operation, while adjusting capacity according to room temperature.The accurate sensing of cooling or heating loads prevents frequent changes in capacity and ensures efficient, economical operation.Outdoor Unit MicroprocessorElectronic expansion valve control (all models except MS7-HO-30P).Automatic compressor timed-off protection (3 minutes).Automatic fan delay in heating mode (heat pump models) after coil is warm.Temperature sensor.LEDs on control (09-24 models) or two-digit character display (30 model) display error codes and assist in troubleshooting.Communication port to indoor unit.4-way valve control (heat pump models).Electronic Expansion ValveFurnished on all models except MS7-HO-30P. MS7-HO-30P uses a capillary system.Compressor Overcurrent ProtectionOvercurrent protection can result due to any of the following:• The ambient temperature is too high• Locked rotor on the compressor• Outdoor air is blocked or restrictedCondenser High Temperature ProtectionCondenser high temperature can occur due to any of the following conditions:• High outdoor ambient• Outdoor fan blocked• Outdoor coil blockedThe outdoor coil thermistor continuously monitors the temperature and communicates with the microprocessor.Depending on the temperature measured, the compressor will be allowed to increase the frequency if needed to meet the load or is forced to run at the current or reduced frequency. If the temperature gets excessively high the compressor will be de-energized as shown below:When the outdoor coil temperature drops to 124ºF, the unit will resume normal operationsNOTE - In heating mode (heat pump models) the indoor fan is de-energized 60 seconds after the compressor is de-energized.

High Pressure Discharge Temperature ProtectionThe compressor discharge temperature can be high due to any of the following:• Low refrigerant charge• Blocked capillaryThe compressor discharge line thermistor continuously monitors the temperature and communicates with the microprocessor.Depending on the temperature measured, the compressor will be allowed to increase the frequency to meet the load or is forced to run at the current or reduced frequency. If the temperature gets excessively high, the compressor will be de-energized. When the compressor discharge temperature drops below 194ºF, the unit will resume normal operations.Intelligent Power Module (IPM) ProtectionProtects the unit from any of the following conditions:• Loss of cooling to the heat sink• High ambient temperature• Low voltageLow Voltage ProtectionIf the incoming voltage is below the minimum allowed, E5 will be displayed on the front panel of the indoor unit.Terminal StripFurnished for easy wiring connections.Defrost Control (Heat Pump Models)Defrost cycle is automatically enabled if there is a build-up of frost on the outdoor coil. Outdoor fan and indoor blower operation is terminated during the defrost cycle.H1 is displayed on the indoor unit panel on the front cover during a defrost cycle.Reversing Valve (Heat Pump Models)4-way interchange reversing valve effects a rapid change in direction of refrigerant flow resulting in quick changeover from cooling to heating and vice versa.Valve operates on pressure differential between outdoor unit and indoor unit of the system.

CABINET

Constructed of heavy gauge steel.Tabs on unit base allow secure mounting to slab.Condensate drain outlets furnished on unit base (heat pump models only). Drain must be field furnished.Access cover for power and control wiring connections.Access cover for service valves (-18, -24 and -30 models only).

Page 4: MINI-SPLIT SYSTEMS MS7C/MS7H · MS7C/MS7H - Mini-Split Systems / Page 5 WIRELESS REMOTE CONTROL (FURNISHED) Complete remote control of system. Maximum operating range is 25 ft. FAN

MS7C/MS7H - Mini-Split Systems / Page 4

FEATURES - INDOOR UNITS

CABINET (CONTINUED)

High impact plastic cabinet.Unit Display Panel (on Indoor Unit)• Heat Indicator• Cool Indicator• Temperature/Error Code• Power/Run• Dehumidify Mode• Infrared Signal Receptor (for wireless remote control)Unit display can be turned off using the wireless remote control.Wall Mounting PlateFurnished for easy wall mounting of the indoor unit. See dimension drawing.Air Deflection LouversHorizontal Louvers default to the cooling or heating position when the unit is operating.Horizontal louvers can be set to a preset oscillating range or fixed position by pushing the “LOUVER SETTING” button ( ) on the wireless remote control.Four oscillating settings and five fixed position settings. Full oscillating is the default setting when button pushed.Vertical louvers can be manually adjusted to direct the airflow for optimal comfort.Easy filter access.

INDOOR COIL

Copper tubes fitted to aluminum fins.High efficiency wraparound design.Condensate drain line furnished.Drain line can be located on left side, right side, left rear, right rear (recommended) or bottom of unit.

BLOWER

Dual cross flow centrifugal blower.Aerodynamic spiralled blades for increased airflow and reduced sound levels.Turbo FunctionUnit runs at maximum speed to cool or heat the area quickly.Cold Blow Prevention (Heat Pump Models)Prevents cold air from blowing into a conditioned space during heating mode if the following occurs:• If coil temperature is less than 106°F and indoor air

temperature is less than 75°F there is a three-minute time delay before blower runs at low speed for five minutes.

• If coil temperature is equal to or more than 106°F and room temperature is equal to or more than 75°F blower runs at low speed for five minutes.

FILTER

Cleanable filter furnished as standard.

CONTROLS

Indoor Unit MicroprocessorContains all necessary components to control system.Terminal StripFurnished for easy wiring connections.Indoor Coil Freeze ProtectionWhen the unit is operating in the COOL or DEHUMIDIFICATION MODE, the indoor coil may freeze due to any of the following:• Low system charge• Reduced indoor airflow• Restricted refrigerant flow• Low ambient temperature (outdoor)• Low load (indoor)The indoor coil thermistor monitors the coil temperature continuously. Any time the coil temperature drops below 30°F, the compressor and the outdoor fan (30 seconds later) will be switched off until the coil temperature rises above 43°F and the compressor was off for a minimum of 3 minutes.Auto Button OperationIf the wireless remote control is lost, damaged, or the batteries are exhausted, the AUTO button located inside the front cover on the indoor unit can be used to run the unit.Auto Settings:• Cooling Mode (setpoint 77°F)• Heating Mode (setpoint 68°F)• Fan Only Mode (runs continuously)• Fan Speed (Auto)• Oscillate (On)

Page 5: MINI-SPLIT SYSTEMS MS7C/MS7H · MS7C/MS7H - Mini-Split Systems / Page 5 WIRELESS REMOTE CONTROL (FURNISHED) Complete remote control of system. Maximum operating range is 25 ft. FAN

MS7C/MS7H - Mini-Split Systems / Page 5

WIRELESS REMOTE CONTROL (FURNISHED)

Complete remote control of system. Maximum operating range is 25 ft.

FAN AUTOOPER

ON OFFHOUR

ON OFF MODE

FAN

CLOCK TIMER ON

TURBO

TEMPX-FAN TIMER OFF

SLEEP LIGHT

°F

°C

88:8888

• ON/OFF - Turns system on and off. Also overrides SLEEP function.

• MODE - Select system operation modes (AUTO/COOL/DEHUMIDIFICATION/FAN/HEAT). Default setting is AUTO. HEAT only available on heat pump models.

• +/- (Plus/Minus) Buttons - Increase or decrease temperature in one degree increments.NOTE - Temperature cannot be adjusted in AUTO mode.

• FAN - Select fan speed (AUTO/LOW/MEDIUM/HIGH). Default setting is AUTO. Fan speed is displayed at the top of the control display. Note - Not adjustable during Dehumidification mode.

• LOUVER SETTING - Sets the angle of the horizontal louvers. Four oscillating settings and five fixed position settings. Full oscillating is the default setting when button is first pushed.

OFF

• CLOCK (24 Hour) - Set time on display. + and - buttons adjust time up or down.

• TEMP - Set temperature and display current indoor ambient temperature or outdoor ambient temperature.

FEATURES - INDOOR UNITS

TIMER ON / TIMER OFFTIMER ON (to start the unit at a preset time) and TIMER OFF (to stop the unit at a preset time) can be used separately or together. The clock on the wireless remote control must be set before using this function.Pressing the + (plus) or – (minus) buttons sets time in one-minute increments. Press continuously for ten-minute increments.Press TIMER ON or TIMER OFF again to cancel setting.X-FANOperates the indoor blower in COOL or DEHUMIDIFICATION mode for ten minutes to dry the indoor unit when unit is not operating.Not available in AUTO, FAN or HEAT mode.SLEEPUsed to conserve energy.Cool ModeAfter one hour of operation setpoint will be increased by 2°F.After two hours setpoint will be increased by another 2°F and fan will operate on low speed.Canceled by pushing the “SLEEP” button again.Heat Mode (Heat Pump Models Only)After one hour of operation setpoint will be decreased by 2°F.After two hours setpoint will be decreased by another 2°F and fan will operate on low speed.Canceled by pushing the “SLEEP” button again.Note - SLEEP function is only available when the unit is in COOL or HEAT mode.

TURBOTurns on blower to the maximum speed setting.Canceled when switching modes or changing blower speeds.LIGHTTurns the LCD display backlight on or off.Additional FeaturesPressing the + (plus) and – (minus) buttons simultaneously locks or unlocks the keypad to prevent tampering.Fahrenheit or Celsius temperature display. When system is off press MODE and - (minus) buttons simultaneously to switch between Fahrenheit and CelsiusOperates on two AAA 1.5V batteries (furnished).

OPTIONS

Wireless Remote Control HolderHolder can be mounted on a wall for easy access. Mounting screws furnished.

Page 6: MINI-SPLIT SYSTEMS MS7C/MS7H · MS7C/MS7H - Mini-Split Systems / Page 5 WIRELESS REMOTE CONTROL (FURNISHED) Complete remote control of system. Maximum operating range is 25 ft. FAN

MS7C/MS7H - Mini-Split Systems / Page 6

OPTIONAL ACCESSORIES - ORDER SEPARATELY

OUTDOOR UNITS

Condenser PadProvides permanent foundation for outdoor units.One-piece lightweight structural foam and molded from high-density polyethylene (HDPE), which makes them lightweight and easy to carry and install. The textured finish provides a non-skid surface so that the outdoor unit sits securely in one place. UV stable.DisconnectsPositive unit disconnect. Single door enclosure. Fused and non-fused models available.Fuses30 and 60 amp fuses available.Indoor/Outdoor Wiring Cable (09 through 24 models only)14-gauge, 4-conductor wire. THHN (Thermoplastic High Heat-resistant Nylon-coated) wire. Suitable for wet or dry locations. Rated up to 600V.Refrigerant Line SetsRefrigerant lines are shipped refrigeration clean. Lines are cleaned, dried, pressurized and sealed at factory.Wall BracketsHeavy duty 1/8 in. thick steel brackets for supporting outdoor units. Mount at any height to allow for easy maintenance under units. Pre-punched holes for easy installation. Powder coated gray finish. Load rating 600 lbs. per pair.WhipsHeavy duty electrical whips are available in 8 and 10 gauge sizes. 6 ft. lengths. Weatherproof metal conduit.Universal Mini-Split Installation Kit

Kit includes two-valve service manifold, premium 5 ft. hoses with ball valve, clutch type flaring tool, 6-in-1 metric torque wrench, imperial/metric hex tool, valve core tool, brass adaptors and brass caps, tool bag.

INDOOR UNITS

Condensate Mini-Split Drain LineConstructed of flexible reinforced polypropylene,160 ft. roll.Condensate PumpsQuietly and efficiently removes condensate.Designed to be installed above a false ceiling, behind wall-mounted evaporators or in plastic conduit.ETL listed.

SpeediChannel™ System

SpeediChannel™ is a channel system used to cover system line sets. The two-part system has a base and a cover. The base is fastened to a wall or ceiling with plastic clips (SpeediClip™) that snap into a channel already molded into the base. The cover fits on top of the base. SpeediChannel is manufactured from rigid PVC, which is UL rated and resistant to UV light. The system is a natural color that closely matches typical mini-split outdoor units. However, it can be painted as desired to match any wall color.

WallPenetration

Cover

SpeediChannel™ 90° FlatBend

SpeediChannel™

UnionCoupling

SpeediChannel™

Duct End

OutdoorUnit

Typical Application

Page 7: MINI-SPLIT SYSTEMS MS7C/MS7H · MS7C/MS7H - Mini-Split Systems / Page 5 WIRELESS REMOTE CONTROL (FURNISHED) Complete remote control of system. Maximum operating range is 25 ft. FAN

MS7C/MS7H - Mini-Split Systems / Page 7

OPTIONAL ACCESSORIES - ORDER SEPARATELY

SpeediChannel™ System (CONTINUED)

SpeediChannelTM Starter Kit The starter kit includes (1) Coupling, (1) Wall Penetration, (1) Inside Elbow, (1) Long Radius Flat Bend, (10) SpeediclipsTM, (10) 11 in. Cable Ties, and (1) SpeediChannel Instruction Booklet.Duct End Duct Ends are used to terminate a run of SpeediChannel™ to a small opening just large enough for the line set and condensate drain line to pass through. Flat Wall EscutcheonFlat Wall Escutcheons are used to cover a rough opening in a soffit, wall, or ceiling penetration. One side of the escutcheon

is flat to allow for a SpeediChannel™ to run along a wall and to penetrate through an adjacent wall or ceiling. This is the most common type of wall penetration. Furnished in two parts, the escutcheon easily snaps onto the SpeediChannel™.

Flex JointA Flex Joint is an accordion-style piece of SpeediChannel™. The flex joint can be extremely flexible when routing a SpeediChannel™ system around an obstacle. Each joint is 20 in. long and can be combined together for longer flex runs. The flex joint does not require the use of a union coupling. The flex joint slides tightly inside the SpeediChannel™ system. T-JointT-Joints are used for creating a tee connection between three pieces of SpeediChannel™. Each tee is individually packed and furnished with stainless steel screws.

Union CouplingUnion Couplings are used for joining two pieces of SpeediChannel™. Each coupling is individually packed and furnished with stainless steel screws.

Wall Penetration CoverWall penetration covers are used to transition from the SpeediChannel™ system to a through wall penetration. Wall covers are designed to allow for easy installation, even after the line set has been installed. A hooking and fastening arrangement allows for quick installation. Each wall cover is individually packed, and furnished with stainless steel screws to attach the wall cover to the base. Three screws are necessary to fasten the wall cover to the wall construction, regardless of the type of installed system. 45° and 90° Flat Bend Elbows45º Flat Bends are used to route the SpeediChannel™ around obstacles. Each bend is individually packed and furnished with stainless steel screws.

90° Inside Elbow90º Inside Elbows are used to route the SpeediChannel™ around an inside corner. Each elbow is individually packed and furnished with stainless steel screws.

Mount Block White Qty. (2) 14 in. and (2) 36 in.Mount Blocks are used as mounting bases when outdoor units must be bolted down. End caps (for aesthetics) come furnished with mounting bolts. Maximum load capacity is 900 pounds per mounting block. Installation temperatures range from -4ºF to 140ºF. Mount blocks fit all mini-split outdoor units with a sliding rail feature.

90°45°

Page 8: MINI-SPLIT SYSTEMS MS7C/MS7H · MS7C/MS7H - Mini-Split Systems / Page 5 WIRELESS REMOTE CONTROL (FURNISHED) Complete remote control of system. Maximum operating range is 25 ft. FAN

MS7C/MS7H - Mini-Split Systems / Page 8

SPECIFICATIONS - AIR CONDITIONER SYSTEMSOUTDOOR UNIT

Nominal Tonnage 0.75 0.75 1 1 1.5 2Outdoor Unit Model No. MS7-CO-09L MS7-CO-09P MS7-CO-12L MS7-CO-12P MS7-CO-18P MS7-CO-24P

Cooling Capacity (Btuh)

High 10,600 10,600 14,000 14,000 22,350 25,000Standard 9,000 9,000 12,000 12,000 18,000 21,500

Low 4,435 4,435 4,500 4,500 6,000 9,600Connections (in.)

Small line o.d. - flare 1/4 1/4 1/4 1/4 1/4 1/4Large line o.d. - flare 3/8 3/8 3/8 3/8 1/2 5/8

1 Refrigerant (R-410A) furnished 2 lbs. 6 oz. 2 lbs. 6 oz. 2 lbs. 9 oz. 2 lbs. 9 oz. 3 lbs. 2 oz. 3 lbs. 10 oz.Outdoor Coil

Net face area - sq. ft. 3.95 3.95 4.08 4.08 5.94 7.77Tube diameter - mm 7 7 9 9 7 7

Number of rows 2 2 2 2 2 2Fins per inch 18 18 18 18 18 18

Outdoor Fan Motor

Diameter - in. 15-5/8 15-5/8 15-5/8 15-5/8 20 22No. of blades 3 3 3 3 3 3

Cfm 1120 1120 1120 1120 1885 2470Rpm 900/650 900/650 900/680 900/680 690/500 780/500

Watts 40 40 40 40 60 90Shipping Data - lbs. Outdoor Unit 91 91 97 97 121 132ELECTRICAL DATA

Line voltage data - 60 hz - 1ph 115V 208/230V 115V 208/230V 208/230V 208/230V1 Maximum overcurrent protection (amps) 25 15 25 15 25 25

2 Minimum circuit ampacity 15 6.1 15 6.1 14 14Compressor Locked rotor amps 33 33 33 33 41 41

Rated load amps 4.6 4.6 4.6 4.6 8.4 8.4Compressor Inverter Frequency (hz)

High 70 70 80 80 - - - - - -Standard 41 41 57 57 - - - - - -

Low 15 15 15 15 - - - - - -Compressor Power Input (W)

3 High 1050 1050 1450 1450 - - - - - -3 Standard 640 640 980 980 1640 1640

Low 180 180 120 120 - - - - - -Outdoor Fan Motor

Rated load amps 0.17 0.17 0.17 0.17 0.62 0.90Output (W) 40 40 40 40 60 90

Rated Amps High 16.8 6.5 17.0 7.0 - - - - - -Standard 7.0 3.2 11.0 5.2 12 12

MATCHING INDOOR UNITIndoor Unit Model No. MS7-CI-09L MS7-CI-09P MS7-CI-12L MS7-CI-12P MS7-CI-18P MS7-CI-24P

Connections (in.)

Small line o.d. - flare 1/4 1/4 1/4 1/4 1/4 1/4Large line o.d. - flare 3/8 3/8 3/8 3/8 1/2 5/8

Indoor Blower Air Volume (cfm)

Turbo 330 330 300 300 500 560High 295 295 275 275 460 470

Medium 255 255 255 255 380 410Low 220 220 215 215 325 355

Indoor Blower RPM

Turbo 1260 1260 1260 1260 1350 1400High 1050 1050 1070 1070 1200 1150

Medium 920 920 900 900 1050 1100Low 730 730 730 730 900 850

Indoor Coil

Net face area - sq. ft. 1.85 1.85 1.85 1.85 2.34 2.82Tube diameter - mm 7 7 7 7 7 7

Number of rows 2 2 2 2 2 2Fins per inch 18 18 18 18 18 18

Indoor Blower

Diameter x Length 3.6 x 25.4 3.6 x 25.4 3.6 x 25.4 3.6 x 25.4 3.9 x 28 3.9 x 30Type Cross flow Cross flow Cross flow Cross flow Cross flow Cross flow

Shipping Data - lbs. Indoor Unit 31 31 31 31 31 46ELECTRICAL DATA

Line voltage data - 60 hz - 1ph 115V 208/230V 115V 208/230V 208/230V 208/230VRated Load Amps 0.38 0.20 0.38 0.20 0.25 0.45

Output (W) 20 20 20 20 20 35NOTE - Extremes of operating range are plus 10% and minus 5% of line voltage. 1 HACR type circuit breaker or fuse. 2 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. 3 Rated Input

Page 9: MINI-SPLIT SYSTEMS MS7C/MS7H · MS7C/MS7H - Mini-Split Systems / Page 5 WIRELESS REMOTE CONTROL (FURNISHED) Complete remote control of system. Maximum operating range is 25 ft. FAN

MS7C/MS7H - Mini-Split Systems / Page 9

SPECIFICATIONS - HEAT PUMP SYSTEMSOUTDOOR UNIT

Nominal Tonnage 0.75 0.75 1 1 1.5 2 2.5Outdoor Unit Model No. MS7-HO-09L MS7-HO-09P MS7-HO-12L MS7-HO-12P MS7-HO-18P MS7-HO-24P MS7-HO-30P

Cooling Capacity (Btuh)

High 10,600 10,600 14,000 14,000 22,350 25,000 30,000Standard 9,000 9,000 12,000 12,000 18,000 21,500 28,000

Low 4,435 4435 4,500 4,500 6,000 9,600 9,500Heating Capacity (Btuh)

High 11,100 11,100 14,500 14,500 25,000 26,000 33,000Standard 9,500 9,500 13,000 13,000 25,000 26,000 28,500

Low 3,200 3,200 3,250 3,250 4,100 4,300 10,000Connections (in.)

Small line o.d. - flare 1/4 1/4 1/4 1/4 1/4 1/4 1/4Large line o.d. - flare 3/8 3/8 3/8 3/8 1/2 5/8 5/8

1 Refrigerant (R-410A) furnished 2 lbs. 6 oz. 2 lbs. 6 oz. 2 lbs. 9 oz. 2 lbs. 9 oz. 3 lbs. 2 oz. 3 lbs. 10 oz. 5 lbs. 7 oz.Outdoor Coil

Net face area - sq. ft. 3.95 3.95 4.08 4.08 5.94 7.77 7.66Tube diameter - mm 7 7 9 9 7 7 9

Number of rows 2 2 2 2 2 2 2Fins per inch 18 18 18 18 18 18 18

Outdoor Fan Motor

Diameter - in. 15-5/8 15-5/8 15-5/8 15-5/8 20 22 21-3/4No. of blades 3 3 3 3 3 3 3

Cfm 1120 1120 1120 1120 1885 2470 2355Rpm - Cooling (Heating) 900/650 (900) 900/650 (900) 900/680 (900) 900/680 (900) 690/500 780/500 830/830

Watts 40 40 40 40 60 90 90Shipping Data - lbs. Outdoor Unit 110 110 119 119 148 161 163ELECTRICAL DATA

Line voltage data - 60 hz - 1ph 115V 208/230V 115V 208/230V 208/230V 208/230V 208/230V1 Max. overcurrent protection (amps) 25 15 25 15 25 25 25

2 Minimum circuit ampacity 15 6.1 15 6.1 14 14 13Compressor Locked rotor amps 33 33 33 33 41 41 45

Rated load amps 4.6 4.6 4.6 4.6 8.4 8.4 9.7Compressor Inverter Frequency (hz) (Heating/Cooling)

High 70/63 70/63 80/75 80/75 - - - - - - - - -Standard 41/44 41/44 57/65 57/65 - - - - - - - - -

Low 15/15 15/15 15/15 15/15 - - - - - - - - -Compressor Power Input (W) (Cooling/Heating)

3 High 1050/1100 1050/1100 1450/1500 1450/1500 - - - - - - 3450/35003 Standard 660/700 660/700 1000/1200 980/1200 1640 1640 2780/2870

Low 180/220 180/220 120/220 120/220 - - - - - - 550/700Outdoor Fan Motor

Rated load amps 0.17 0.17 0.17 0.17 0.62 0.90 0.45Output (W) 40 40 40 40 60 90 120

Rated Amps (Cooling/Heating)

High 16.8/17.0 6.5/6.8 17.0/18.2 7.0/7.5 - - - - - - - - -Standard 7.0/7.5 3.2/3.5 11.0/12.5 5.2/6.0 12/12.6 12/12.5 17/17

MATCHING INDOOR UNITIndoor Unit Model No. MS7-HI-09L MS7-HI-09P MS7-HI-12L MS7-HI-12P MS7-HI-18P MS7-HI-24P MS7-HI-30P

Connections (in.)

Small line o.d. - flare 1/4 1/4 1/4 1/4 1/4 1/4 1/4Large line o.d. - flare 3/8 3/8 3/8 3/8 1/2 5/8 5/8

Indoor Blower Air Volume (cfm)

Turbo 330 330 300 300 500 560 - - -High 295 295 275 275 460 470 735

Medium 255 255 255 255 380 410 675Low 220 220 215 215 325 355 645

Indoor Blower RPM (Heating/Cooling)

Turbo 1260/1320 1260/1320 1260/1280 1260/1280 1350/1420 1400/1400 - - -High 1050/1200 1050/1200 1070/1050 1070/1050 1200/1250 1150/1150 1400/1400

Medium 920/1100 920/1100 900/980 900/980 1050/1150 1100/1100 1300/1300Low 730/950 730/950 730/920 730/920 900/1050 850/900 1200/1200

Indoor Coil

Net face area - sq. ft. 1.85 1.85 1.85 1.85 2.34 2.82 4.41Tube diameter - mm 7 7 7 7 7 7 7

Number of rows 2 2 2 2 2 2 2Fins per inch 18 18 18 18 18 18 18

Indoor Blower

Diameter x Length 3.6 x 25.4 3.6 x 25.4 3.6 x 25.4 3.6 x 25.4 3.9 x 28 3.9 x 30 4.25 x 20.5Type Cross flow Cross flow Cross flow Cross flow Cross flow Cross flow Cross flow

Shipping Data - lbs. Indoor Unit 37 37 37 37 46 56 60ELECTRICAL DATA

Line voltage data - 60 hz - 1ph 115V 208/230V 115V 208/230V 208/230V 208/230V 208/230VRated Load Amps 0.38 0.20 0.38 0.20 0.25 0.45 0.40

Output (W) 20 20 20 20 20 35 40NOTE - Extremes of operating range are plus 10% and minus 5% of line voltage. 1 HACR type circuit breaker or fuse. 2 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. 3 Rated Input

Page 10: MINI-SPLIT SYSTEMS MS7C/MS7H · MS7C/MS7H - Mini-Split Systems / Page 5 WIRELESS REMOTE CONTROL (FURNISHED) Complete remote control of system. Maximum operating range is 25 ft. FAN

MS7C/MS7H - Mini-Split Systems / Page 10

OPTIONAL ACCESSORIES - ORDER SEPARATELY

Description Catalog No.

Size09 12 18 24 30

OUTDOOR UNITCondenser Pad (18 x 36 x 2) 48X92 • • • • •Disconnects 30 amp, fused, 1 ph 27P37 • • • • •

60 amp, non-fused, 1 ph 27P39 • • • • •Fuses 30A 83P75 • • • • •

60A 83P77 • • • • •Line Sets 1/4 in. x 3/8 in. x 50 ft. X0258 • •

1/4 in. x 1/2 in. x 25 ft. 90X52 •1/4 in. x 1/2 in. x 50 ft. X0259 •1/4 in. x 5/8 in. x 25 ft. 90X51 • •1/4 in. x 5/8 in. x 50 ft. X0260 • •

Male Flare Adaptor 5/16 in. quick connect x 1/4 in. MF Y0576 • • • • •Wall Brackets 30 inch Y5020 • •

36 inch Y5021 • • •Whips 10 Gauge - 1/2 in. x 6 ft. 29P54 • • • • •

8 Gauge - 3/4 in. x 6 ft. 27P44 • • • • •INDOOR UNIT

Condensate Pumps

Aspen Mini Orange - 3.7 US gallons per hour, 26 ft. lift - 115V X8250 • • • • •Aspen Mini Orange - 3.7 US gallons per hour, 26 ft. lift - 230V X8251 • • • • •

ClearVue Mini™ - 7.9 US gallons per hour, 35 ft. lift - 120/240V Y5170 • • • • •Condensate Mini-Split Drain Line - 5/8 in. I.D. 160 ft. Y3401 • • • • •Indoor/Outdoor Wiring Cable - 14 Gauge, 4 conductor wire, THHN, 250 ft. Y2067 • • • •Wireless Remote Control Holder Y5070 • • • • •

INSTALLATION KITUniversal Mini-Split Installation Kit Y3247 • • • • •

SPEEDICHANNEL™ SYSTEMSpeediChannel™ Starter Kit - 4 in. Y3387 • • • • •SpeediChannel - 4 in. x 6-1/2 ft. Y3388 • • • • •Union Coupling - 4 in. Y3389 • • • • •90° Flat Bend Elbow - 4 in. Y3390 • • • • •90° Inside Elbow - 4 in. Y3391 • • • • •45° Flat Bend Elbow - 4 in. Y3392 • • • • •Flex Joint - 4 in. Y3393 • • • • •T-Joint - 4 in. Y3394 • • • • •Duct End - 4 in. Y3395 • • • • •Flat Wall Escutcheon - 4 in. Y3396 • • • • •Wall Penetration Cover - 4 in. Y3399 • • • • •Mount Block (White) Qty, 2 - 14 in. Y3397 • • • • •Mount Block (White) Qty, 2 - 36 in. Y3398 • • • • •

SYSTEM OPTIMAL OPERATING RANGES

Unit Type System Size

Outdoor Temperature Optimal Operating Ranges

Indoor Temperature Optimal Operating Ranges

Cooling Heating Cooling HeatingAir Conditioner 09 to 24 41°F to 115°F - - - 64ºF to 90ºF - - -

Heat Pump09 to 24 41°F to 115°F 5ºF to 86ºF 64ºF to 90ºF 50ºF to 86ºF

30 64ºF to 109ºF 19ºF to 75ºF 64ºF to 90ºF 50ºF to 86ºFNOTES:18 and 24 Models Only - If the outdoor temperature is above 50ºF, the system will operate in the cooling mode if the room temperature is 61ºF or above. If the outdoor

temperature is below 50ºF, the system will not operate unless the room temperature is 77ºF or above.See MS7 Unit Information Manual for system performance outside of the optimal operating ranges shown.

Page 11: MINI-SPLIT SYSTEMS MS7C/MS7H · MS7C/MS7H - Mini-Split Systems / Page 5 WIRELESS REMOTE CONTROL (FURNISHED) Complete remote control of system. Maximum operating range is 25 ft. FAN

MS7C/MS7H - Mini-Split Systems / Page 11

SYSTEM MATCHES - AIR CONDITIONERSNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.org

Outdoor Model Capacity SEER EER Indoor Model AHRI Reference

MS7-CO-09L 9,000 22.00 14.20 MS7-CI-09L 4733645MS7-CO-09P 9,000 22.00 14.20 MS7-CI-09P 4733646MS7-CO-12L 12,000 20.00 12.50 MS7-CI-12L 4733647MS7-CO-12P 12,000 20.00 12.50 MS7-CI-12P 4733648MS7-CO-18P 18,000 18.00 12.00 MS7-CI-18P 4733649MS7-CO-24P 22,000 18.00 12.00 MS7-CI-24P 4733650

NOTES: Ratings are AHRI certified to AHRI Standard 210/240; 95°F outdoor air temperature, 80°F db / 67°F wb entering evaporator air.

SYSTEM MATCHES - HEAT PUMPSNOTE - For the latest up-to-date system matches please visit the AHRI web site at http://www.ahridirectory.org

Outdoor Model Capacity SEER EERHeat Capacity HSPF

Region IV Indoor Model AHRIReferenceHigh Low

MS7-HO-09L 9,000 22.00 14.20 9,500 5,400 9.80 MS7-HI-09L 4733651MS7-HO-09P 9,000 22.00 14.20 9,500 5,400 9.80 MS7-HI-09P 4733653MS7-HO-12L 12,000 20.00 12.50 13,000 7,500 9.60 MS7-HI-12L 4733652MS7-HO-12P 12,000 20.00 12.50 13,000 7,500 9.60 MS7-HI-12P 4733654MS7-HO-18P 18,000 18.00 12.00 25,000 16,300 10.20 MS7-HI-18P 4733655MS7-HO-24P 21,000 18.00 12.00 26,000 16,000 10.20 MS7-HI-24P 4733656MS7-HO-30P 28,000 16.00 10.05 28,400 17,000 8.20 MS7-HI-30P 4733657

NOTES: Ratings are AHRI certified to AHRI Standard 210/240; • Cooling Ratings - 95°F outdoor air temperature and 80 °F db/67° F wb entering indoor coil air. • High Temperature Heating Ratings - 47° F db/43° F wb outdoor air temperature and 70 °F db entering indoor coil air. • Low Temperature Heating Ratings - 17 °F db/15° F wb outdoor air temperature and 70 °F db entering indoor coil air. To convert HSPF from Region IV to Region V - Divide by 1.15.

SOUND DATA - INDOOR

Unit Type Indoor Unit Model No.

Sound Rating Number (dBA)Low Medium High

Pressure Power Pressure PowerPressure Power

Air Conditioner

MS7-CI-09L 26 36 30 40 34 44MS7-CI-09P 26 36 30 40 34 44MS7-CI-12L 26 36 32 42 36 46MS7-CI-12P 26 36 32 42 36 46MS7-CI-18P 35 45 40 50 44 54MS7-CI-24P 35 45 40 50 44 54

Heat Pump

MS7-HI-09L 26 36 30 40 34 44MS7-HI-09P 26 36 30 40 34 44MS7-HI-12L 26 36 32 42 36 46MS7-HI-12P 26 36 32 42 36 46MS7-HI-18P 35 45 40 50 44 54MS7-HI-24P 35 45 40 50 44 54MS7-HI-30P 48 58 50 60 52 62

INDOOR UNIT AIR THROW DATA

Indoor UnitEffective Throw - ft.

09 12 18 24 30Low Speed 18 19 25 23 N/AMedium Speed 20 21 30 27 N/AHigh Speed 23 25 32 30 N/ATurbo Speed N/A N/A 35 37 N/A

SOUND DATA - OUTDOOR

Unit Type Outdoor Unit Model No.

Sound Rating Number (dBA)

Pressure Power

Air Conditioner

MS7-CI-09L 53 63MS7-CO-09P 53 63MS7-CO-12L 55 65MS7-CO-12P 55 65MS7-CO-18P 54 64MS7-CO-24P 56 66

Heat Pump

MS7-HO-09L 53 63MS7-HO-09P 53 63MS7-HO-12L 55 65MS7-HO-12P 55 65MS7-HO-18P 54 64MS7-HO-24P 56 66MS7-HO-30P 58 68

Page 12: MINI-SPLIT SYSTEMS MS7C/MS7H · MS7C/MS7H - Mini-Split Systems / Page 5 WIRELESS REMOTE CONTROL (FURNISHED) Complete remote control of system. Maximum operating range is 25 ft. FAN

MS7C/MS7H - Mini-Split Systems / Page 12

DIMENSIONS - INCHES (MM) OUTDOOR UNITS

Model No.A B C D E F G

in. mm in. mm in. mm in. mm in. mm in. mm in. mm-09 21 533 30 762 12-5/8 320 10-1/8 257 11-1/4 286 21-1/4 540 33-3/8 848-12 21 533 30 762 12-5/8 320 10-1/8 257 11-1/4 286 21-1/4 540 33-3/8 848-18 27-1/2 701 35 890 13-3/8 340 13-3/8 340 14-1/2 368 22 560 37-1/2 955-24 31-1/8 790 36-1/4 920 16-7/8 427 14-1/2 370 15-3/4 399 24 610 39-3/8 1000-30 31-1/8 790 36-1/4 920 16-7/8 427 14-1/2 370 15-1/2 395 24 610 38-1/2 980

A

C

F

D B

G

E

Front View

Bottom View

Side View

ElectricalConnectionsCover

Refrigerant LineConnections(cover furnished on-18-24 models only)

Page 13: MINI-SPLIT SYSTEMS MS7C/MS7H · MS7C/MS7H - Mini-Split Systems / Page 5 WIRELESS REMOTE CONTROL (FURNISHED) Complete remote control of system. Maximum operating range is 25 ft. FAN

MS7C/MS7H - Mini-Split Systems / Page 13

INSTALLATION CLEARANCES - INCHES (MM)OUTDOOR UNITS In. mm

Left Side 12 305

Right Side 12 305

Front 48 1219

Rear 12 305

Top 24 510

INDOOR UNITS In. mm

Left Side 6 152

Right Side 6 152

Top 6 152

Bottom 72 1829

NOTES:If outdoor unit is mounted on a flat rooftop allow a minimum of 4 in. (102 mm) above the roof surface.Locate the unit above a load bearing wall or area of the roof that can adequately support the unit. Consult local codes for rooftop applications.

DIMENSIONS - INCHES (MM) INDOOR UNITS

B

A

C

D E F

Front ViewSide View

Wall Mounting Plate Detail

NOTE - 30 model has three supports

Model No.A B C D E F

in. mm in. mm in. mm in. mm in. mm in. mm-09 10-7/8 275 33 838 7 180 5-3/8 135 21-3/8 542 6-5/8 169-12 10-7/8 275 33 838 7 180 5-3/8 135 21-3/8 542 6-5/8 169-18 12 305 37 940 8 203 4-5/8 118 27-3/8 694 5-7/8 148-24 12-3/8 315 39-3/4 1008 8-1/2 218 8-1/2 215 27 685 7-1/2 190-30 12-7/8 326 53 1350 10 253 10 253 29-3/8 746 13-7/8 351

Page 14: MINI-SPLIT SYSTEMS MS7C/MS7H · MS7C/MS7H - Mini-Split Systems / Page 5 WIRELESS REMOTE CONTROL (FURNISHED) Complete remote control of system. Maximum operating range is 25 ft. FAN
Page 15: MINI-SPLIT SYSTEMS MS7C/MS7H · MS7C/MS7H - Mini-Split Systems / Page 5 WIRELESS REMOTE CONTROL (FURNISHED) Complete remote control of system. Maximum operating range is 25 ft. FAN
Page 16: MINI-SPLIT SYSTEMS MS7C/MS7H · MS7C/MS7H - Mini-Split Systems / Page 5 WIRELESS REMOTE CONTROL (FURNISHED) Complete remote control of system. Maximum operating range is 25 ft. FAN

NOTE - Due to Lennox’ ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency. ©2012 Lennox Industries, Inc.

Visit us at www.lennox.com

For the latest technical information, www.lennoxdavenet.com

Contact us at 1-800-4-LENNOX

REVISIONS

Sections Description of Change

Optional Accessories Updated Condensate Pump usage.