  • ElectricalNotes&Articles

    SharingAbstracts,NotesonvariousElectricalEngineeringTopics.

    MinimumAcceptableSpecificationofC.T&P.TforMetering

    APRIL1,2011 4COMMENTS(HTTPS://ELECTRICALNOTES.WORDPRESS.COM/2011/04/01/MINIMUMACCEPTABLESPECIFICATIONOFCTFORMETERING/#COMMENTS)

    Min.AcceptableSpecificationofCurrentTransformerforMetering:

    Sr.No

    Particulars 11kV 33kV 132kV 220kV

    1 HighestSystemVoltage(kVrms)

    12 36 145 245

    2 CTratio. 20001000/11 800400/11 400/11 800/11

    1600800/11 600300/11

    1200600/11 400200/11

    800400/11 300150/11

    600300/11 10050/11

    400200/11

    300150/11

    15075/11

    3 Numberofmeteringcores

    TwoNos TwoNos TwoNos TwoNos

    4 Ratedcontinuousthermalcurrent.

    120%ofratedprimarycurrent

    120%ofratedprimarycurrent

    120%ofratedprimarycurrent

    120%ofratedprimarycurrent

    5 Ratedshorttimethermalcurrentofprimaryfor1sec.(kA)

    25 25 31.5 40

    6 CTcharacteristics:a)Ratedprimarycurrent(Amps.)

    20001000 800400 400 800

    1600800 600300

    1200600 400200

    800400 300150

    600300 10050

    400200

    300150

    15075

    (b)RatedSecondarycurrent(Amps.)

    1 1 1 1

    (c)Classofaccuracy. 0.2 0.2 0.2 0.2

  • (d)Max.instrumentsecurityfactor

    5 5 5 5

    (e)Ratedburden(VA). 30 30 30 40

    7 IStowhichCTconforms.

    8 IStowhichinsulatingoilconforms.

    Min.AcceptableSpecificationofVoltageTransformerforMetering:

    Sr.No

    Particulars 245kVCVTs

    145kVCVTs

    1 HighestSystemVoltage(kV)

    245kV 145kV

    2 RatedCapacitance(pF) 4400pfwithtolerance+10%and5%

    3 Forlowvoltageterminaloverentirecarrierfrequencyrange.

    (a)Straycapacitance Shallnotexceed200pf

    (b)Strayconductance Shallnotexceed20us

    4 (a)Highfrequencycapacitanceforentirecarrierfrequencyrange

    within80%to150%ofratedcapacitance

    (b)Equivalentseriesresistanceovertheentirefrequencyrange.

    lessthan40Ohms

    5 No.ofsecondarywindingsforpotentialdevice.

    Two Two

    6 Transformationratio:

    (i)WindingI 20kV\/3/110\/3V

    (ii)WindingII 20kV\/3/110\/3V

    7 Ratedsecondaryburden

    (i)WindingI(VA) 50VA 50VA

    (ii)WindingII(VA) 50VA 50VA

    8 AccuracyClass:

    (i)WindingI(VA) 0.2formetering

    (ii)WindingII(VA) 0.2formetering

    9 VoltagefactorforwindingIVoltagefactorforwindingII

    1.2Cont.&1.5for30secs.1.2Cont.&1.5for30secs.

    10 IStowhichCVTsconform.

    IS3156withlatestamendment

    11 IStowhichInsulatingOilconform.

    IS335withlatestamendment

  • MinimumAcceptableSpecificationofSinglePhasePTforMetering:

    Sr.No Particulars 33kV 11kV

    1 HighestSystemVoltage(kVrms) 36 12

    2 Transformationratio. 33kV/V3/110/V3

    11kV/110V

    3 Numberofwindings. Two Two

    4 Ratedoutput/burden(VA)perwinding/phase.

    50 50

    5 Accuracyclass.(At10to100%ofVAburden)

    0.2 0.2

    6 Ratedvoltagefactorandduration.

    1.2continuous&1.5for30secs.

    7 IStowhichPTconforms. 3156withlatestamendment

    FILEDUNDERUNCATEGORIZED

    AboutJignesh.ParmarJigneshParmarhascompletedM.Tech(PowerSystemControl),B.E(Electrical)fromGujaratUniversity.Hehasmorethan13yearsexperienceinPowerTransmissionPowerDistributionElectricalenergytheftdetectionElectricalMaintenanceElectricalProjects(PlanningDesigningcoordinationExecution).HeisPresentlyassociatewithoneoftheleadingbusinessgroupasaDeputyManageratAhmedabad,India.HeisFreelancerProgrammerofAdvanceExcelanddesignusefulExcelSheetsofElectricalEngineeringasperIS,NEC,IEC,IEEEcodes.HeistechnicalAuthorforElectricalMirrorandElectricalIndiaMagazines.HeisTechnicalBloggerandFamiliarwithEnglish,Hindi,Gujarati,Frenchlanguages.HewantstoSharehisexperience&knowledgeandhelptechnicalenthusiaststofindsuitablesolutionsandupdatingthemselvesonvariousEngineeringTopics.

    4ResponsestoMinimumAcceptableSpecificationofC.T&P.TforMetering

    waqasahmedsays:April2,2011at5:18amdearsir!!

    yourpostareveryinformative..irequestyoutopleaseguideusonrealytestingfordifferentschemesofcableandOHTLprotection..pleaseshareusyourpracticalknowledge..Regards

    YouMayLike

    1.

    About these ads (https://wordpress.com/about-these-ads/)

  • WaqasAhmed

    Replyrajivpandeysays:May10,2011at4:26amItisreallyinformative.Pleaseguidemeaboutthefollowing:Wehaveanewsteelplantcomingupinthestateofwestbengal.Theplantisstillininstallation&commissioningstage.Wehaveerectedone220KVlinefromsupplyingutilitytothe220/33KVMainreceivingstationoftheplant.theCTratiointhelineis400/1,0.2Class.Weneedabout1.5MVAatpresenttokeeptheMRSchargedandforcommissioningoffewoftheequipment.However,supplyingutilityhastoldusthattheywillnotbeabletosupplylessthan5MVAinthe220KVline,assupplyoflessthan5MVAmaycauseerrorinmetering.Kindlyguideuswhetherthestandofsupplyingutilityiscorrectornotwithreasoning.

    Regards,

    Rajiv

    Replyrcsays:July30,2011at12:05pmVerygood.keepitup

    Replyparijatsays:December16,2014at5:46pminmaharastraitisrequiredtoputcheckmeterontheconsumersideforhighMDcosumer.pleasecouldutellmeitspossibletoconnectwithsamecoreofctorPTorwehavetoinsatallseparatemeteringtemple

    Reply

    CreateafreewebsiteorblogatWordPress.com.

    TheEnterpriseTheme.

    Follow

    FollowElectricalNotes&Articles

    BuildawebsitewithWordPress.com