Model 505 Flow Computer

Operation Manual

Application LM01

Single Tank Level Monitorfor

Analog Level Sensors

18 May 2007

Page 2: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Model 505 Flow Computer - Operation Manual

The instructions given herein cover the general description, installation, operation and maintenance of the subject equipment. Contrec Pty. Ltd. reserves the right, without prior notice, to make engineering refinements that may not be reflected in this manual.

Should any questions arise which cannot be answered specifically by this manual, they should be directed to Contrec Pty Ltd for further detailed information and technical assistance.

Contrec Pty. Ltd. will not accept any liability for either direct or consequential damages resulting from the use or misapplication of the contents of this manual.

Part of the software embedded in this product is eCos - Embedded Configurable Operating System, a trademark of Red Hat. Portions created by Red Hat are Copyright © 1998, 1999, 2000 Red Hat, Inc. (http://www.redhat.com). All rights reserved

The software in this product was in part provided by Red Hat and any express or implied warranties, including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose are disclaimed. In no event shall the author be liable for any direct, indirect, incidental, special, exemplary, or consequential damages (including, but not limited to, procurement of substitute goods or services; loss of use, data, or profits; or business interruption) however caused and on any theory of liability, whether in contract, strict liability, or tort (including negligence or otherwise) arising in any way out of the use of this software, even if advised of the possibility of such damage.

Contrec Pty Ltd22 Hall Street Hawthorn East, Melbourne 3123 AUSTRALIA

Tel: +61 3 9804 4200 Fax: +61 3 9822 8329Email: [email protected]

Contrec - USA, LLC916 Belcher Drive Pelham AL 35124 USATel: (205) 685 3000 Fax: (205) 685 3001

Email: [email protected]

Contrec Europe LimitedPO Box 436 Sowerby Bridge, West Yorkshire HX6 3YA, UK

Tel: +44 1422 829 940 Fax: +44 1422 829 941Email: [email protected]

Website: www.contrec.com.au

Publication No: 505-LM01-OM - 18 May 2007

Page 3: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

505 LM01 - 18 May 2007 iii

Safety NoticeThe information in this safety notice is for the prevention of injury to personnel and

damage to the instrument.

The manufacturer assumes no liability for injury or damage caused by misuse of the instrument or for modifications made to the instrument.

Qualified Personnel

The instrument must be installed, operated and serviced by persons who have been properly trained and authorised. Personnel must read and understand this manual prior to installation and operation of the instrument.

Static Hazard

The 500 series flow computer uses high speed CMOS circuitry which is sensitive to static damage. The user should observe accepted safety practices for handling electronic devices, especially during servicing. Once the unit is installed, grounded and interconnected, the chances of static damage are greatly reduced.

Voltage Hazard

Before connecting power to the instrument, ensure that the supply voltage for the AC or DC input is suitable. The AC voltage rating is as stated on the serial number plate. Personnel should take all due care to avoid electric shock.

Welding Hazard

Do not perform electric welding in close proximity to the instrument or its interconnecting cables. If welding in these areas must be performed, disconnect all cables from the instrument. Failure to do so may result in damage to the unit.

Moisture Hazard

To avoid electrical faults and corrosion of the instrument, do not allow moisture to remain in contact with the instrument.

505 LM01 - 18 May 2007

Page 4: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

iv 505 LM01 - 18 May 2007

Page 5: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

v

1 IntroductionOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Displayed Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Main Menu Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Retransmission & Control Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Relay Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Software Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Limitations of Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

2 SpecificationsGeneral . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

3 InstallationPanel Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Electrical Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Rear Panel Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Terminal Designations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Analog Input Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Logic Input Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104-20mA Output Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Logic Output Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Control Relays (Alarms) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11RC Network for Interference Suppression . . . . . . . . . . . . . . . . . . . . . . 12

Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12RS-232 Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Infra-red Port (Display Panel Option) . . . . . . . . . . . . . . . . . . . . . . . . 13RS-485 Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Earthing and Shielding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

4 OperationNormal Operation Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Default Variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Status Lamps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Front Panel Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Main Menu Items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Data Logs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Model Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Alarms Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Contents

505 LM01 - 18 May 2007

Page 6: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

vi 505 LM01 - 18 May 2007

Operation of Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

5 Instrument CalibrationIntroduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Calibration View Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Calibration Set Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Changing the Instrument Settings . . . . . . . . . . . . . . . . . . . . . . . . . . 25Calibration Menu Tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Instrument Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Units of Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36Time Settings and Data Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . 38General Setup Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40Test Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

System Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43Warning Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43Alarm Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

6 CommunicationsOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

Hardware Interconnection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45Protocols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47Modbus RTU Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

List of Data Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49Printer Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

Types of Printouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54Printer Data Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

Appendix A Model NumbersProduct Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59Custom Version Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60Application Information Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

Appendix B Units of MeasurementAvailable Units of Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62

Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

Page 7: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

vii505 LM01 - 18 May 2007

List of Figures

1 Typical Application Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Rear Panel Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 Externally Powered Current Loop . . . . . . . . . . . . . . . . . . . . . . . . . . 94 Internally Powered Current Loop . . . . . . . . . . . . . . . . . . . . . . . . . . 95 Logic Input Connection Diagram . . . . . . . . . . . . . . . . . . . . . . . . . 106 Output 4-20mA Connection Diagram . . . . . . . . . . . . . . . . . . . . . . . 107 Output Logic Connection Diagram . . . . . . . . . . . . . . . . . . . . . . . . 118 Relay Connection Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119 RS-485 Interface Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

10 Logged Data Display Methods . . . . . . . . . . . . . . . . . . . . . . . . . . 1811 Calibration Menu Tree Sheet 1 . . . . . . . . . . . . . . . . . . . . . . . . . . 2612 Calibration Menu Tree Sheet 2 . . . . . . . . . . . . . . . . . . . . . . . . . . 2713 RS-232 Cable Connections to a Computer . . . . . . . . . . . . . . . . . . . . 4614 RS-485 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

Page 8: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

viii 505 LM01 - 18 May 2007

Page 9: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

1

Chapter 1Introduction

Features• 20 point level to volume strapping table• Level control output• Accepts level and pressure (product head) sensors• Density correction available for pressure level sensors• Provides volume to mass conversion via density value• Freely assignable alarms for high or low levels• Allows for non-linear correction• Selection of second language and user tags• RTC logging with up to 100 entries at user-specified scheduled times• Infra-red communications port on front panel• 4-20mA retransmission• Selectable protocols on serial ports including Modbus RTU and Printer

output• Front panel adjustment of 8-24V DC output voltage• Backlit display• LCD backup

OverviewThe 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range of level sensors, including pressure transmitters, ultrasonic sensors and capacitance probes.

The level monitor provides a 20 point strapping table and product density for level to volume and volume to mass conversions. The instrument can display Volume, Percentage Full and Mass as well as Level. Relay alarms are freely assignable as high or low alarms and an open collector output is provided for programmable level control.

505 LM01 - 18 May 2007

Page 10: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Introduction

2 505 LM01 - 18 May 2007

A sub-menu gives full details of alarm status and can offer direct access to change the alarm setpoints. The instrument also has density correction available for pressure level sensors to cater for a deviation in product density.

Calculations

The following equations identify the derivation of some of the displayed variables. If your interest is more in the operation of the instrument, you can skip this section and allow the instrument to take care of the calculations.

Calculations are based on the analog input signal representing the product level in the tank.

level = (Lmax-Lmin) × A + Lmin

volume = (Vmax - Vmin) × A* + Vmin

mass = volume × density

where:A = normalised input signal with

density correction.A* = A for linear tanks.A* = f(A) for non-linear tanks.f(A) = level to volume normalised

strapping table.

Displayed Information

The front panel display shows the current values of the input variables and the results of the calculations.

The instrument can be supplied with a real-time clock for data logging of up to 100 entries of the variables as displayed on the main menu.

Page 11: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Introduction

505 LM01 - 18 May 2007 3

Main Menu Variables

Refer to Available Units of Measurement on page 62 for the list of available units.

Communications

There are three communication ports available as follows:

• RS-232 port (standard) • RS-485 port (standard)• Infra-red port (on front panel - display panel option)

The ports are available for remote data reading, printouts and for initial application loading of the instrument.

Retransmission & Control Outputs

The instrument can re-transmit any main menu variable. The digital output can be used as logic levels for control outputs. If the instrument has the advanced option, it outputs rates as a 4-20mA signal.

Relay Outputs

The relay alarms can be assigned to any of the main menu variables of a rate type. The alarms can be fully configured including hysteresis. Two relays are standard.

Software Configuration

The instrument can be further tailored to suit specific application needs including units of measurement, custom tags, second language or access levels. A distributor can configure these requirements before delivery.

Instrument parameters including units of measurement can be programmed in the field, according to the user access levels assigned to parameters by the distributor.

Main MenuVariables

DefaultUnits

VariableType

Product Volume m3 Rate

Product Level m Rate

Volume Full % % Rate

Product Mass kg Rate

Page 12: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Introduction

4 505 LM01 - 18 May 2007

All set-up parameters and logged data are stored in non-volatile memory with at least 30 years retention.

Figure 1 Typical Application Diagram

Limitations of Use

Density Correction for Pressure Level Sensors

Density correction has been provided for use with pressure level sensors to cater for a deviation in the product density. This correction is only used in the calculations when the minimum and maximum points for the level input have been programmed in a conventional manner. That is, the level corresponding to the 20mA point is greater than the level for the 4mA point.

Approvals

This instrument conforms to the EMC-Directive of the Council of European Communities 89/336/EEC and the following standards:

• Generic Emission Standard EN 50081-1 Residential, Commercial & Light Industry Environment.

• Generic Emission Standard EN 50081-2 Industrial Environment.• Generic Immunity Standard EN 50082-1 Residential, Commercial &

Light Industry Environment.• Generic Immunity Standard EN 50082-2 Industrial Environment.

In order to comply with these standards, the wiring instructions in Chapter 3 - Installation must be followed.

LevelTransmitter

Analog Input

L

Page 13: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

5

Chapter 2Specifications

General Inputs

Outputs

Operating EnvironmentTemperature 0°C to +60°C (conformal coating)

+5°C to +40°C (no coating)Humidity 0 to 95% non condensing (conformal

coating)5% to 85% non condensing (no coating)

Power Supply 95...135 V AC or 190...260 V AC or 12...28 V DC

Consumption Typically 6WProtection Sealed to IP65 (Nema 4X) when panel

mountedDimensions 147mm (5.8") width

74mm (2.9") height167mm (6.6") depth

DisplayType LCD with 7-digit numeric display and

11-character alphanumeric display (backlit option)

Digits 15.5mm (0.6") highCharacters 6mm (0.24") high LCD Backup Last data visible for 15min after power

down (optional)Update Rate 0.3 second

Non-volatile MemoryRetention > 30 yearsData Stored Setup, Totals and Logs

ApprovalsInterference complianceEnclosure ATEX, FM, CSA and SAA approved

enclosures available for hazardous areas

Real Time Clock (Optional)Battery Type 3 volts Lithium button cell (CR2032)Battery Life 5 years (typical)

4-20mA InputOvercurrent 100mA absolute maximum ratingImpedance 250 ohms (to common signal ground)Accuracy 0.1% typical full scale (20°C)

0.2% (full temperature range)Non-linearity Up to 20 correction points (flow inputs)

Remote Key InputSignal Type CMOS, TTL, open collector, reed switchConfiguration One input set as one of front five keys

Relay OutputNo. of Outputs 2 relaysVoltage 250 volts AC, 30 volts DC maximumCurrent 3A maximum

Communication PortsPorts RS-232 port

RS-485 port Infra-red port (optional)

Baud Rate 2400 to 19200 baudParity Odd, even or noneStop Bits 1 or 2Protocols Modbus RTU, Printer

Transducer SupplyVoltage 8 to 24 volts DC, programmableCurrent 70mA @ 24V, 120mA @ 12V maximumProtection Power limited output

Digital OutputSignal Type Open collector, non-isolatedSwitching 200mA, 30 volts DC maximumSaturation 0.8 volts maximum

505 LM01 - 18 May 2007

Page 14: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Specifications

6 505 LM01 - 18 May 2007

Important: Specifications are subject to change without notice.

4-20mA Output (Optional)Supply 24 volts DC internal, non-isolated Resolution 0.05% full scaleAccuracy 0.05% full scale (20°C)

0.1% (full temperature range, typical)

Page 15: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

7

Chapter 3Installation

Panel MountingThe instrument should be located in an area with a clean, dry atmosphere that is also relatively free of shock and vibration.

The standard mounting procedure is panel mounting in a cutout that is 139mm wide by 67mm high. Two side clips secure the unit into the panel.

Figure 2 shows the panel mounting requirements for the 500 Series Instrument.

500 Series Instrument Panel Mounting

145mm

Side View22mm

70mm

67mm

139mm

25mm

66m

m

Min. 189mm

Panel Cut-out

Front Panel

74m

m

Mounting Clip

138mm

147mm

Rear ConnectorsTop View RS232

Port

505 LM01 - 18 May 2007

Page 16: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Installation

8 505 LM01 - 18 May 2007

Electrical Connection

Rear Panel Connections

Figure 2 shows the connections on the rear panel of the instrument.

Figure 2 Rear Panel Connections

Terminal Designations

RS232 Port

CAUTIONMAINS

E N AAC MAINS

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

RS485 RS232 Io SG Li Dout Ii SG Fi Vo G Vi SH RELAYS+ - G Tx Rx C + - + 1+ 2+ + - + + - + E R1 RC R2

Terminal Label Designation Comment1

RS485+ RS485 (+)

2 - RS485 (-)3 G Comms ground4

RS232Tx RS232 data out

Same RS232 port as DB9 connector5 Rx RS232 data in

6 C CTS (Clear to send)7 Io + 4-20mA output Advanced option8 SG - Signal Ground 0V9 Li + Logic input10

D OUT1+ Open collector o/p 1 Control output

Not used11 2+ Open collector o/p 212 Ii + 4-20mA input Level input13 SG - Signal Ground 0V14 Fi + Frequency input Not used15 Vo + 8-24 volts DC output 70mA power limited16 G - DC Ground 17 Vi + DC power input DC power in 12-28V18 SH E Shield terminal19

RELAYSR1 Relay 1

20 RC Relay Common21 R2 Relay 2E

AC MAINS

E Mains ground AC power in 95-135V or 190-260VN N Mains neutral

A A Mains active RS232 port 9-pin serial port

Page 17: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Installation

505 LM01 - 18 May 2007 9

Inputs

Analog Input Connections

The analog input (Ii) can accept current signals from 4 to 20mA.

CAUTIONApplying levels of input current above the absolute maximum

rating (100mA) may cause permanent damage to the input circuitry.

4-20mA Inputs

For an externally powered current loop, connect the transmitter to the input terminals as shown in Figure 3.

Figure 3 Externally Powered Current Loop

Connect internally powered current loop as shown in Figure 4.

Figure 4 Internally Powered Current Loop

Logic Input Connection

These input(s) are designed to be connected to open collector signals or a voltage free contact switch. A minimum activation time of 300ms is required to guarantee reading of an input.

+ -Transmitter

AnalogInput(Ii)

12

13

15

12

+

- AnalogInput

Vo +8...24V DC

(Ii)

Transmitter

Page 18: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Installation

10 505 LM01 - 18 May 2007

Remote Key Input

A remote push-button key can be connected to the Logic Input as shown below. Refer to REMOTE KEY on page 33 to define the function of the key.

Figure 5 Logic Input Connection Diagram

OutputsThe basic instrument has two digital logic outputs (in this application only DOUT1 is used). The advanced option also provides a 4-20mA output port.

4-20mA Output Connection

Figure 6 shows the connections for a 4-20mA output.

Maximum Load Resistance = 900 ohms

Figure 6 Output 4-20mA Connection Diagram

Logic Output Connection

Figure 7 shows a connection example for a logic control output. Output channel 1 uses terminals 10 (+) and 8 (-). Output channel 2 uses terminals 11 (+) and 8 (-).

Signal Ground8

Logic Input(Li)9

18

+

-

Load

Shield

505

4-20mAOutput

(Io)

7

8

Internal supply

Page 19: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Installation

505 LM01 - 18 May 2007 11

Figure 7 Output Logic Connection Diagram

Control Relays (Alarms)The standard instrument has two alarm relays, which can be used to drive external devices such as external relays, lamps, and audible alarms. The operation of alarm relay(s) can be set to various modes as described in Alarms on page 34.

There is also an equipment failure alarm option. This alarm can have normally closed (open) contacts which open (close) when the instrument displays any error message as listed in Error Messages on page 43, or if there is a loss of power to the instrument.

The output characteristics of the relays are:

Note: Solid state relays use AC voltage only.

Figure 8 Relay Connection Diagram

+

-

External LoadResistor 10K

Vo +8...24V DC 15

Logic Input

OpenCollectorOutput

Pulse Output(DOUT)

Shield18

500

Maximum Voltage 30 volts DC or 250 volts ACMaximum Current 3A

SupplyAlarm

Relay 1

Relay 2

AlarmR2

R1

RCRelay Common

MOV

MOV

500

Page 20: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Installation

12 505 LM01 - 18 May 2007

RC Network for Interference Suppression

When driving highly inductive loads with the relay outputs, it is recommended to use RC suppression networks (often called “Snubbers”) for the following reasons:

• To limit the amount of electrical noise caused by arcing across the contacts, which may, in extreme cases, cause the microprocessor to act erratically.

• To protect the relay contacts against premature wear through pitting.

RC suppression networks consist of a capacitor and series resistor and are commonly available in the electrical industry. The values of R and C are dependent entirely on the load. However, if the user is unsure of the type of snubber to use, values of 0.25µF and 100Ω will usually suffice. Note that only mains-approved RC suppression networks should be used.

The basic principle of the operation is that the capacitor prevents a series of sparks arcing across the contact as the contact breaks. The series resistor limits the current through the contact when the contact first makes.

CommunicationsThe communication protocols are described in Communications on page 45.

RS-232 Port

The standard RS-232 port uses terminals 4, 5 and 6 on the rear panel.

The extra RS-232 port 9-pin DB female connector has the following pinout:

Pin 1 Not used

Pin 2 Transmit (TxD)

Pin 3 Receive (RxD)

Pin 4 Not used

Pin 5 Ground

Pin 6 Not used

Pin 7 Handshake line (CTS)

Pin 8 RTS Out

Pin 9 Not used

1 2 3 4 5

6 7 8 9

Page 21: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Installation

505 LM01 - 18 May 2007 13

Note: The instrument does not require a null-modem cable for connection to a personal computer. Refer to Hardware Interconnection on page 45 for cable termination requirements.

Infra-red Port (Display Panel Option)

The infra-red port is located at the front panel, directly below the row of status indicators. The main function of this port is for retrieving current or logged data with a PC that has an infra-red port.

RS-485 Port

Up to 32 units can be connected to a common RS-485 bus. Each unit has a unique address that the host computer uses to identify each instrument.

Figure 9 shows the connection of several instruments to a computer using the RS-485 port.

Figure 9 RS-485 Interface Connections

Earthing and Shielding

It is a good practice to use shielded cable for all signal connections to the instrument. Care must be taken to separate signal cables from power cables to minimize interference.

Overall earth should be connected at the instrument end only. This connection should be as short as possible and connected to the earthing point on the rear terminal at pin 18.

Twisted Pair

Load120 ohms

Gnd Gnd

HostComputer

CommsGnd

+

-

+ - + -

Instrument Instrument1 2 3 1 2 3

Page 22: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Installation

14 505 LM01 - 18 May 2007

Page 23: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

15

Chapter 4Operation

Normal Operation ModeIn normal operation mode, you press the buttons on the front panel to display the values recorded and calculated by the instrument. There are four categories of information that the instrument can display:

• Level variables• Contents variables• Alarm setpoints• Instrument settings

Default Variable

In some applications, a particular variable is of more interest than others, and for this reason a default variable can be assigned during instrument calibration. The default is used in the following way:

• The default variable determines what the display returns to if the display timeout option is enabled and no buttons are pressed for the selected period (usually 30 seconds). It also determines what is displayed on power up.

Status Lamps

The status lamps illuminate to show the following conditions:

Run An instrument operation is in progress.Set The instrument is in Calibrate Set mode.Alarm The instrument has an error, as indicated on the display panel.Cal The instrument is in Calibrate View mode.

Front Panel Keys

For most actions with the front panel keys, you can hold a key to scroll through the values or options, instead of repeatedly pressing the key.

Press the key to display the current tank level. If there is more than one level variable, press or hold the key to display the other level variables in turn.

RunSetAlarmCal

LEVEL LEVEL

LEVEL

505 LM01 - 18 May 2007

Page 24: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Operation

16 505 LM01 - 18 May 2007

Press the key to display the current tank contents. When a contents variable is displayed, press or hold the key to display the other contents variables in turn.

Use the key to clear and acknowledge relay alarms or to initiate a printout if the printer option has been selected. The printout is activated with a single press and gives two beeps while the Clear Alarms Key parameter in calibration can be enabled or disabled during instrument calibration and functions as follows:

• DISABLE - The user cannot clear or acknowledge any relay alarms.• ENABLE - Holding the key for two seconds will acknowledge

and clear all active relays, while individual alarm relays can be cleared in the Alarms Menu with a single press of the clear key.

Press the key to step or scroll through the main menu items.

Press the key, while viewing any main menu variable, to enter the alarms menu. For full details see Alarms Menu on page 19.

Main Menu Items

The main menu in this instrument consists of the following items. The key is used to step or scroll through the list.

CONTENTS CONTENTS

CONTENTS

CLEAR CLEAR

CLEAR

DISPLAY DISPLAY

ALARMS ALARMS

DISPLAY

↓ Description Options

VOLUME Product volume Press the key to enter the Alarms menuLEVEL Product level Press the key to enter the Alarms menu% FULL Volume full percentage Press the key to enter the Alarms menuMASS Product mass Press the key to enter the Alarms menuREPORT PRINT Only shown if print

option is selectedHold the key to print log report as defined in the TM/LOG section of calibration.

LOGGED DATA Only shown if real-time clock option is installed

Hold the key to display data logs as described in Data Logs on page 17.

MODEL INFO Hold the key to display the Model information as described in Model Information on page 19.

CAL MENU Hold the key to enter Calibration View mode as described in Calibration View Mode on page 23.

DISPLAY

ALARMS

ALARMS

ALARMS

ALARMS

SET

SET

SET

SET

Page 25: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Operation

505 LM01 - 18 May 2007 17

Data Logs

The instrument will log the main-menu variables if real-time clock option is installed. The logs are at fixed intervals which can be programmed to a combination of hours, days, weeks, months and years. The instrument can store a total of 100 log entries.

If the number of log entries exceeds the programmed number for a particular time interval, the oldest log entry is overwritten by the newest one for that time interval.

The log entries are recorded at the following times:

View Data Logs

Use the following procedure to view the data that has been logged by the instrument:

1. Press the key to scroll through the menu to the LOGGED DATA prompt.

2. Hold the key.

The system displays the hourly log. The timebase and number of the log are shown, for example LH-001.

3. While holding the key use the key to print the data for the displayed log if the printer option has been selected.

The following example shows the hourly log number 006 at 15:00 (3:00 pm) on 16 January 2002. The day and month alternate with the year in the bottom right hand corner.

HOUR 00 minutes each hourDAY 00 hours and 00 minutes each dayWEEK 00 hours and 00 minutes each MondayMONTH 00 hours and 00 minutes on the first day of the monthYEAR 00 hours and 00 minutes on the first day of the year.

DISPLAY

SET

DISPLAY CLEAR

15-00LH-006 16/01

15-00LH-006 2002

Page 26: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Operation

18 505 LM01 - 18 May 2007

Figure 10 shows how to display the logged data.

Figure 10 Logged Data Display Methods

LY-nnnLM-nnnLW-nnnLD-nnnLH-nnn

LY-002LM-002LW-002LD-002LH-002YEARLY-001

MONTHLM-001

WEEKLW-001

DAYLD-001

……

HOURLH-001

Press at any time to exit from the Data LogsSET

Hold to show the values for a log entry

DISPLAY

Press to select the time base

Press to select the log number

Hold and press to display the main menu variables

DISPLAYVariable 2

Variable 1Error code

Page 27: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Operation

505 LM01 - 18 May 2007 19

Model Information

The model information items display the hardware, software and application versions of the instrument. This information is mainly for service personnel.

Press at any time to exit from the Model information.

Alarms MenuThe alarms menu allows information about individual alarms to be viewed. If multiple alarms are active at one time it can allow the alarms to be individually acknowledged.

On entering the alarms menu with the key the Cal indicator will illuminate and the first item, ALARM 1, will be displayed.

Press the key to step or scroll around through the other alarms in the order of the alarm number. The instrument will exit the alarms menu whenever the or keys are pressed or a timeout of 30 seconds, with no key presses, expires.

↓ Description

-1--F-505 MODEL

The hardware model code. Refer to Product Codes on page 59 for more information.

-LLM01 INPUT

The Application number and the assignment of the inputs. Refer to Application Information Code on page 60 for more information.

0101.002LM01 VERS

The version of software loaded into the instrument.

026357CUSTOM VERS

The Customer version code for this installation. Refer to Custom Version Codes on page 60 for more information.

123456ABC123 S/N

The instrument serial number and unit tag. The serial number is on the top line and unit tag is on the bottom left. Both items are entered when the instrument applicaton software is initially loaded. If the unit tag is not used the default tag, UNIT, will be used.

16-15EDITED 27/08

2002

The time and date when the calibration of the instrument was last edited. The format of the time and date is the same as for the data logs. This example shows 16:15 (4:15pm) on the 27th August 2002.

This function is available only if the instrument has the real time clock option.

DISPLAY

SET

ALARMS

DISPLAY DISPLAY

LEVEL CONTENTS

Page 28: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Operation

20 505 LM01 - 18 May 2007

An alarm menu item consists of the alarm number, type, assignment and setpoint as shown in the following example:

The Alarm led indicates the status of the alarm being viewed.Led flashing = Alarm ACTIVELed solid = Alarm ACKNOWLEDGEDLed off = Alarm IDLE.

If the alarm being viewed has been assigned as an Equipment Alarm (AL-NC) it will be displayed in the following form. An Equipment Alarm relay can not be cleared and pressing the key will have no effect.

The exception status code is the same as that used for communications. For a full list see Instrument Exception Status on page 51.

Changing Alarm SetpointsAn alarm setpoint can only be edited if the Direct Edit Access parameter was enabled during instrument calibration. Hold the key, the display of the setpoint will change from view mode to edit mode after two seconds. Once in edit mode the Set indicator will illuminate and the setpoint values are changed in exactly the same way as in calibration set mode. Press the

key again to exit edit mode and return to the alarm item.

Operation of Alarms

The alarms can be freely assigned to any of the main menu variables as high or low alarms and can also be assigned to be an equipment alarm.

When a high or low alarm condition is detected the relay will activate, the Alarm led will flash and the message for that alarm will be scrolled across the display. The alarm will remain active until the alarm condition is no longer true at which point it is automatically cleared and the relay will deactivate, the led will turn off and the message will stop being displayed.

100.000LEVEL/HI-NO ALRM1

Alternating assigned variable and alarm type

Alarm number

Alarm setpoint

CLEAR

ES 00 AL-NC ALRM1

Instrument exception status

Alarm number

Alarm type

SET

SET

SET

Page 29: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Operation

505 LM01 - 18 May 2007 21

When Clear Alarms Key is enabled the alarm can be acknowledged and the relay cleared from the main menu by pressing the key for two seconds. This will acknowledge all active alarms, the instrument will sound three beeps, the relays will be deactivated, the Alarm led will go from a flashing to solid state and the relevant alarm message will continue to scroll. When the alarm condition is no longer present the led will turn off, the message will stop being displayed and the alarm will be re-armed to activate when the condition is detected again.

If there are multiple alarms present at the same time only the highest priority alarm message will be displayed in the main menu (relays operate regardless of priority). The alarms menu can be used to view the status of all alarms and acknowledge them individually with a short press of the key (or, like above, acknowledge all active alarms by holding the key for two seconds). Any acknowledged alarm takes a lower priority than a non-acknowledged alarm. Hence the priority list of alarms on this instrument is as follows:

Alarm 1 Active Highest priorityAlarm 2 Active Alarm led flashing, Relay activated

Alarm 1 Acknowledged Alarm led solid, Relay deactivatedAlarm 2 Acknowledged Lowest priority

The key indication that the alarm being scrolled on the display is acknowledged or not is the status of the Alarm led.

CLEAR

CLEAR

CLEAR

Page 30: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Operation

22 505 LM01 - 18 May 2007

Page 31: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

23

Chapter 5Instrument Calibration

IntroductionYou can view or change the settings of the instrument according to the access level for each parameter as set by the manufacturer. There are four levels of access to the parameters as follows:

• Not visible - you cannot display or edit the parameter.• Display Only - you can display the parameter, but you cannot change the

setting.• Programmable - you can change the setting of the parameter in

Calibration Set mode.• Password protected - you can change the setting of the parameter in

Calibration Set mode only if you enter the correct password.

Note: When you enter Calibration Set mode, the instrument requests you to enter a password. Any value will allow to change the settings of the “programmable” parameters, but the correct password must be entered to change the password-protected parameters.

Calibration View ModeUse the following procedure to view the calibration settings of the instrument:

1. Press to scroll to the CAL MENU prompt.

2. Hold the key.

The instrument beeps once, illuminates the Cal indicator and shows CAL on the display panel. • Press to scroll through the flashing menu headings. • Press to scroll through submenu items.• Press to return to the main calibration menu.

3. To exit from the Calibration View mode, press to scroll to the END option and press .

The instrument returns to Normal Operation mode.

DISPLAY

SET

RunSetAlarmCal

SET

DISPLAY

SET

505 LM01 - 18 May 2007

Page 32: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Instrument Calibration

24 505 LM01 - 18 May 2007

Calibration Set ModeIn Calibration Set mode, you can change the settings of the “programmable” parameters. You must enter the system password to change the setting of the “password-protected” parameters.

Use the following procedure to enter Calibration Set mode:

1. Press to scroll to the CAL MENU prompt.

2. Hold the key.

The instrument beeps once, illuminates the Cal indicator and shows CAL on the display panel.

3. Press to select any flashing menu heading except END.

4. Hold for two seconds.

The instrument requests a password.

5. Press or to change the value of the current digit. To select the next digit, press .

6. Press to accept the password.• The instrument makes two beeps for a correct password entry and

enables you to change the “programmable” and “password-protected” parameters.

• The instrument makes one beep for an incorrect password entry and enables you to change only the “programmable” parameters.

The instrument illuminates both the Cal and Set indicators.

7. Edit the instrument parameters as required. The programmable values are indicated by the flashing display.• To change a numerical value, press to increase a value, or press

to decrease a value. Press a key momentarily to change the value one number at a time. Hold a key to scroll through the numbers. To proceed to next digit, press .

• To change an option setting, press or to scroll through the options.

8. Press to accept the currently displayed value and proceed to the next parameter. You can press to return to the main calibration menu.

9. To exit from Calibrate Set mode, press to scroll through the main calibration menu to END, then press . Otherwise, from any menu, you can press and hold for two seconds.

The instrument makes two beeps and cancels the Cal and Set indicators.

DISPLAY

SET

RunSetAlarmCal

SET

SET

RunSetAlarmCal

SET

DISPLAY

SET

SETRunSetAlarmCal

Page 33: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Instrument Calibration

505 LM01 - 18 May 2007 25

Changing the Instrument Settings

In Calibration Set mode, the display flashes the item that can be changed. For option settings, the display flashes the complete option. For a numeric parameter, the display flashes one digit at a time, you can change the value of the flashing digit as required, then move the flashing cursor to change another digit.

Note: When you change the setting of a parameter, the instrument records the result as soon as you move to another parameter, or exit from the Calibration Set mode.

Changing Option Settings

When you display an option that can be changed, the entire option flashes on the display, such as the choices of ODD, EVEN or NONE for the communications parity bit checking. Press or to change the option. You can “scroll” through the options in either direction to make a selection as shown below.

Changing Numeric Settings

The display flashes the digit that can be changed.

Press to select the digit that you wish to change.

Press or to increase or decrease the value of the selected digit.

Changing the Decimal Point

To change the position of the decimal point, press to move the flashing selection until the decimal point flashes. Press or to move the decimal point to the right or left as required.

Units of Measurement

The calibration of some parameters is based on the units that are defined for the relevant variables. These units of measurement can been viewed in the UNITS menu in calibration below.

ODD EVEN NONE

ODD NONE EVEN

6789.123

Page 34: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Instrument Calibration

26 505 LM01 - 18 May 2007

Calibration Menu Tree

Figure 11 and Figure 12 show the keys for moving around the calibration menu tree in Calibration View or Set mode.

Figure 11 Calibration Menu Tree Sheet 1

PressSET

ALRM1

TYPE

POINT

HYST

selection

Press

INP-n

OUT-n

AINPLEVEL

PT-MIN

PT-MAX

CUTOFF

CONV

NO-PTS

INP-01

OUT-01

FILTER

LINEARNON-LIN

VOLUME

PT-MIN

PT-MAX

REMOTE KEY

ALRM2

TYPE

POINT

HYST

selection

INPUTS ALARMS

Continued on next page PARAMS

SENSOR TYPE

D-CAL value

D-PROD value

DIRECT ACCES

ALARMS CLEAR

DOUT1

selection

PT-ON

PT-OFF

selection

A-OUT

PT-MAX

PT-MIN

OUTPUTUNITS

View/Edit units of measurement

Page 35: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Instrument Calibration

505 LM01 - 18 May 2007 27

Figure 12 Calibration Menu Tree Sheet 2

PressSET

The shaded boxes indicate advanced options

Press

AINP

LINP1

SUPPLY

A-OUT

PROCESSON

OFF

REL/ALRMPROCESS

OPENCLOSED

DOUT1

A-OUT PROCESSHI

LO

COMMS TM/LOG SETUP TEST

From previous page

DEFAULT VAR

SUPPLY VOLT

T-OUT MODE

T-OUT SEC

DISPL TAGS

BACK-L T-OUT

DATE FORM

CLOCK YEAR

CLOCK M-DAY

CLOCK H-MIN

HOUR LOGS

DAY LOGS

WEEK LOGS

MONTH LOGS

YEAR LOGS

RESET LOGS

REPORT TYPE

PRN TYPE

END

Exit from calibration mode

Press at any point to return to the main calibration menu.

Press at any I/O assignment position to move to the next I/O assignment in the submenu (eg pressing on ALRM1 will move you to ALRM2)

DISPLAY

RTU ADDR

FLASH PORT

RS485

PROTOC

BAUD

PARITY

S-BITS

BAUD

PARITY

S-BITS

RS232

PROTOC

BAUD

PARITY

S-BITS

INFRA

PROTOC

RTU DATA

Page 36: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Instrument Calibration

28 505 LM01 - 18 May 2007

Instrument Settings

Units of Measurement

The Units menu allows the units to be viewed and edited if necessary without the reloading of new application software. Any change in units will result in a full reset to initially downloaded settings. Therefore, any required changes to units of measurement should be made before changing any other settings.

Parameters

↓ → UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST END

ITEM n unit The units for main menu or calibration items can be viewed by pressing the key.

The units of measurement are password protected. To edit the units the correct password must be entered on entry to EDIT mode.

Press or to select the required units. Refer to Available Units of Measurement on page 62 for the list of available units.

ACCEPT UNITS The Accept Units prompt will only appear if one or more of the units have been changed.

IMPORTANT: Accepting the change of units will initiate a master reset. All calibration parameters will revert to their default value (i.e. those values included in the downloaded instrument software). All totals and any logged information will be cleared.

Press or to select YES, then press the key. The instrument makes three beeps to confirm the reset command.

The message -RESET- PLEASE WAIT will be displayed as the instrument exits calibration mode and completes a full re-boot sequence.

SET

SET

SET

↓ → UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST END

SENSOR TYPE Select the type of sensor being used. A pressure sensor (measuring product head) or a level sensor can be selected.

Press or to select LEVEL or PRESSUR.

D-CAL unit The calibration density is the density of the product at the time of the tank calibration. This parameter is required only when a pressure sensor is selected.

SET

Page 37: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Instrument Calibration

505 LM01 - 18 May 2007 29

Inputs

D-PROD unit The product density is used to provide the product mass based on the calculated volume of product.

DIRECT ACCES If the alarm setpoint direct access is enabled then the operator is able to enter edit mode for the setpoint directly from the alarm menu by holding the key while viewing the setpoint. If disabled the setpoint can only be changed from within calibration set mode. Select the direct access mode as required.

Press or to select ENABLE or DISABLE.

ALARMS CLEAR If the “clear alarms key” is enabled then the operator is able to acknowledge and deactivate the relay of an active alarm by pressing the

key.

Holding the clear key for two seconds will acknowledge and clear all active relays, while individual alarm relays can be cleared in the Alarms Menu with a single press of the clear key.

Press or to select ENABLE or DISABLE.

↓ → UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST ENDSET

SET

CLEAR

↓ → UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST END

Analog InputINPUT

LEVEL AINP

For this application, the 4-20mA Analog Input is assigned to level.

PT-MIN LEVEL

PT-MAXEnter the value of the level (in the defined engineering units) that corresponds to the minimum input signal.

Enter the value of the level (in the defined engineering units) that corresponds to the maximum input signal.

For example, if the source signal is 4mA at a minimum level of 2m, enter 2 as the minimum point. If the source signal is 20mA at a maximum level of 5m, enter 5 as the maximum point.

If the sensor is inverted the value entered for the minimum point will be greater than the value entered for the maximum point

SET

Page 38: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Instrument Calibration

30 505 LM01 - 18 May 2007

CUTOFF AINP The Cut-off is the lowest value that the instrument reads from the input sensor. The cut-off setting is the percentage of the span of the input values.

All inputs at or below the cut-off value are considered negligible to the instrument and are ignored. In this case, the instrument uses the minimum value (set at PT-MIN).

FILTER AINP Input fluctuations caused by pulsating signal tend to create distortion in the input readings of the level. The instrument has a digital filter that averages out these fluctuations.

As a guide to the degree of filtering to use, the following table shows the response time (in seconds) to reach 90% and 99% of a step change in input.

The value A is the filter constant that the user can set.

Filter setting A Seconds to reach 90% of full swing

Seconds to reach 99% of full swing

0 0 0

2 2 4

4 4 8

6 5 10

10 8 15

15 12 23

20 14 27

25 18 34

35 25 48

45 32 62

60 42 82

75 52 102

90 62 122

99 68 134

The input filter range is from 0 to 99. A setting of 0 (zero) means that there is no filtering.

↓ → UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST ENDSET

Page 39: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Instrument Calibration

505 LM01 - 18 May 2007 31

PT-MIN VOL

PT-MAXEnter the value of the tank volume (in the defined engineering units) that corresponds to the level minimum input signal (volume at 4mA).

Enter the value of the tank volume (in the defined engineering units) that corresponds to the level maximum input signal (volume at 20mA). The maximum point is the same as the base value (set at the minimum point) plus the span value.

For example, if the source signal is 4mA at a minimum volume of 10m3, enter 10 as the minimum point. If the source signal is 20mA at a maximum volume of 100m3, enter 100 as the maximum point.

CONV VOL The instrument can be programmed to correct for the non-linearities in irregular shaped tanks. These tanks have a non-linear relationship between the level and volume of liquid which can be corrected with a normalised strapping table.

Tank volume conversion type can be selected as follows:

• LINEAR level to volume relationship, strapping table not required.• NON-LINEAR level to volume relationship, normalised strapping

table used for level to volume conversion.

Use or to select LINEAR or NON-LINEAR.NO-PTS VOL This parameter is available for viewing and editing only when the

conversion type is set to Non-linear.

Enter the number of conversion points required for the normalised level to volume tank strapping table.

Press or to select a number between 1 and 20 for the number of conversion points.

↓ → UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST ENDSET

Page 40: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Instrument Calibration

32 505 LM01 - 18 May 2007

INP-01 TABLE

toINP-n

This parameter is available for viewing and editing only when the conversion type is set to Non-linear.

Enter the normalised input value for the conversion point.

Data on tank non-linearity is usually supplied be the tank manufacturer, in the form of strapping tables. If this data is not available, the user will need to determine the relationship between level and volume. This can be done mathematically by equations, or experimentally, by conducting physical measurements. In either case, the data must be entered as normalised values.

The instrument uses linear interpolation between the correction points. An input and an output value are entered for each correction point. The values are normalised between the minimum point (0.0) and the maximum point (1.0). Only the points between 0 and 1 are required to be entered and should be entered in ascending order.

You can press the key to skip the non-linear points and go to the next item.

↓ → UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST ENDSET

DISPLAY

Page 41: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Instrument Calibration

505 LM01 - 18 May 2007 33

Example.A spherical tank has a diameter of 10m. The level at the minimum input signal (PT-MIN) is 0.5m and the level at the maximum input signal (PT-MAX) is 10.0m. The corresponding minimum and maximum volume points have been calculated as PT-MIN = 3.796m3 and PT-MAX = 523.599m3. The following 15 point relationship has been determined:

Correction Points Example

Level Input(m)

Volume Output(m3)

min 0.500 0.000 3.796 0.0001 1.094 0.063 17.421 0.0262 1.688 0.125 39.699 0.0693 2.281 0.188 69.314 0.1264 2.875 0.250 104.951 0.1955 3.469 0.313 145.295 0.2726 4.063 0.375 189.031 0.3567 4.656 0.438 234.844 0.4448 5.250 0.500 281.418 0.5349 5.844 0.563 327.438 0.62310 6.438 0.625 371.590 0.70811 7.031 0.688 412.557 0.78612 7.625 0.750 449.025 0.85713 8.219 0.813 479.678 0.91614 8.813 0.875 503.202 0.96115 9.406 0.938 518.280 0.990max 10.000 1.000 523.599 1.000

OUT-01 TABLE

toOUT-n

This parameter is available for viewing and editing only when the correction type is set to Non-linear.

Enter the normalised output value for the correction point.REMOTE KEY You can assign the remote key input to duplicate any one of the key

switches on the front panel.

Press or to select NO-1 through NO-5 as the key on the front panel (from left to right) that is set as the remote key input. Select NONE to disable the remote key function.

↓ → UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST ENDSET

Page 42: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Instrument Calibration

34 505 LM01 - 18 May 2007

Outputs

Alarms

Thealarm relay(s) can be assigned to rate variables such as level, or set as an equipment failure alarm.

↓ → UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST END

LOGIC DOUT1 You can assign any of the main menu variables to the logic control output. It can be used to control the amount of product in a tank by activating a pump or valve for refilling the tank.

Press or to select the variable that is required as an output.

PT-ON DOUT1

PT-OFF DOUT1The digital output control ON point determines the value at which the output is activated. The control OFF point determines the value at which the output is deactivated.

The control ON point should be lower than the control OFF point.

For example, if the “% FULL” variable is assigned to the control output and it is desired to keep the product in the tank between 30 and 70% full, the PT-ON should be set to 30.0 and the PT-OFF should be set to 70.0.

If the product level falls below 30% FULL the output will activate and will remain ON until the product reaches 70% FULL. At which point the output will deactivate and remain OFF until the product once again falls below 30%.

4-20 A-OUT You can assign any of the “rate” main menu variables to the 4-20mA output.

Press or to select the variable that is required as an output.

PT-MIN A-OUT

PT-MAX A-OUTThe output minimum value corresponds to the 4mA point and the output maximum value corresponds to the 20mA point.

Setting the output range differently from the input range enables the instrument to amplify the input signal. You can drive a chart recorder that “zooms in” on a specified range of values instead of displaying the full operating range of the transducer.

For example, if the minimum point is set to 30% and the maximum point is set to 100%, the 4 to 20mA range would reflect the product level range of 30 to 100%. At level above the maximum and below the minimum points, the output remains at 20mA and 4mA respectively.

SET

Page 43: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Instrument Calibration

505 LM01 - 18 May 2007 35

The alarm switches “on” whenever an alarm condition exists. The alarm switches “off” when the alarm condition no longer exists. For further details, refer to Operation of Alarms on page 20.

Equipment Failure Alarm

Any alarm relay can be assigned as an equipment failure alarm. This alarm setting can have normally closed (open) contacts that open (close) when the instrument displays any error message as listed in Error Messages on page 43, or if there is a loss of power to the instrument.

↓ → UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST END

RELAY ALRMn Select a rate variable to assign to the alarm relay.

Note: If the alarm type is set to “equipment alarm”, this relay assignment setting is ignored.

Press or to select the variable that is required as an alarm.

TYPE ALRMn The options available for alarm types are as follows:

• HI-NO — High Alarm, Normally Open contacts• HI-NC — High Alarm, Normally Closed contacts • LO-NO — Low Alarm, Normally Open contacts • LO-NC — Low Alarm, Normally Closed contacts • BD-NO — Band Alarm, Normally Open contacts• BD-NC — Band Alarm, Normally Closed contacts• AL-NO — Equipment Alarm, Normally Open contacts• AL-NC — Equipment Alarm, Normally Closed contacts

Press or to select the type of alarm required.

SET

Page 44: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Instrument Calibration

36 505 LM01 - 18 May 2007

Communications

The instrument has three communication ports:

• RS-232 Port - Three terminals on the rear of the instrument. There is also an optional 9-pin female connector on the rear panel of the instrument.

• Infra-red Port - (Display panel option only) Located on the front panel, below the status indicators.

• RS-485 Port - Terminals on the rear panel.

POINT ALRMn The Alarm Setpoint is available for viewing and editing for any alarm type except ‘equipment alarms’.

The Alarm Setpoint is the value (in engineering units of assigned variable) at which the alarm condition occurs and therefore the alarm is on.

Each alarm is completely independent, e.g. a High alarm does NOT need to have a higher setpoint than the a Low alarm.

HYST ALRMn The Alarm Hysteresis is available for viewing and editing for any alarm type except ‘equipment alarms’.

Alarm hysteresis loops occur when the alarm toggles continuously on and off when the process variable is close to the setpoint.

For a high alarm, the alarm activates when the value of the variable rises above the alarm setpoint and deactivates when the value falls below the alarm setpoint minus the amount of the hysteresis setting (if any).

For a low alarm, the alarm activates when the value of the variable falls below the alarm setpoint and deactivates when the value rises above the alarm setpoint plus the amount of the hysteresis setting (if any).

For a band alarm, the alarm activates whenever the value of the variable is outside the setpoint plus or minus the amount of the hysteresis.

For example, with a high alarm setpoint of 200, and a hysteresis setting of zero, a value oscillating between 197 and 202 will cause the alarm to toggle on at 200 and toggle off below 200. However, if the hysteresis is set to 5, the value of the variable must fall below 195 to cancel the alarm. The alarm will reactivate only when the value again rises above 200.

↓ → UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST ENDSET

Page 45: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Instrument Calibration

505 LM01 - 18 May 2007 37

↓ → UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST END

PROTOC RS232

RS485

INFRA

The Communications Protocols can be assigned to the communication ports as follows (a protocol cannot be assigned to more than one port at a time):

• RTU - Modbus RTU available for all ports• PRN - Printer Protocol available for RS232 and RS485• NONE - If a port is not being used, set the protocol to NONE.

Printer Protocol (PRN) is only available if the option with Real Time Clock is installed.

For the selected port, press or to select the desired protocol.

BAUD RS232

RS485

INFRA

The Baud setting is the speed of the communication port in data bits per second.

The baud rate of the instrument must match the baud rate of the communication device that the instrument is connected to.

Use or to select 2400, 4800, 9600 or 19200 baud.

PARITY RS232

RS485

INFRA

The Parity bit helps to detect data corruption that might occur during transmission.

The parity bit setting of the instrument must match the parity bit setting of the communication device that the instrument is connected to.

Press or to select EVEN, ODD, or NONE.

S-BITS RS232

RS485

INFRA

The Stop bit indicates the end of a transmission. Stop bits can be 1 or 2 bit periods in length. The stop bit setting of the instrument must match the stop bit setting of the communication device that the instrument is connected to.

Press or to select 1 or 2 stop bits.

RTU DATA The Modbus RTU data format for the 2-register (4-byte) values can be set as either floating point or long integer values.

Use or to select FLOAT or INTEGER.

SET

Page 46: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Instrument Calibration

38 505 LM01 - 18 May 2007

Time Settings and Data Logging

Instrument Clock

Note: The real-time clock is part of the advanced option package.

The instrument has a real-time clock for recording logged events. The clock displays the time and the date. The date format can be set to European format (day/month/year) or American format (month/day/year). The time clock uses the 24-hour format.

The clock will continue to operate for up to 5 years (typically) on the internal battery if there is no power connected to the instrument. Therefore, after an interruption to the power supply, the instrument recommences normal operation although there will be no data recorded during the period without a power supply.

Note: If there is an interruption to the power supply and the battery has failed, the instrument displays an error message when the power supply is restored. In this case, you should set the current time and date so that the instrument continues to log data at the correct times.

Data Logging

The instrument can store up to 100 log entries of the main-menu variables. These logs can all be for one time interval, or shared with other timescales. For example, you can specify 40 hourly logs, 30 daily logs, 15 weekly logs, 10 monthly logs and 5 yearly logs.

The log parameters (below) for each timebase also determine the number of records to be included in a report print out if the printing option is used.

RTU ADDR The Modbus RTU protocol address must be in the range of 1 to 247. When multiple instruments (slaves) are connected to one communication device (master), each assigned address must be unique.

Note: The master device uses the RTU address 0 (zero) for broadcasting to all connected slave units.

FLASH PORT The Flash Driver Port assignment defines the communication port for downloading software into the instrument.

The default setting of this assignment is the RS-232 port.

Press or to select RS-232, RS-485, or INFRA.

↓ → UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST ENDSET

Page 47: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Instrument Calibration

505 LM01 - 18 May 2007 39

↓ → UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST END

DATE FORM Clock Date Format

The European date format is: dd/mm/yyyy or (Day-Month).

The American date format is: mm/dd/yyyy or (Month-Day).

Press or to select DAY-M or M-DAY

CLOCK YEAR The Clock Year defines the current year for the real-time clock.

CLOCK M-DAY The Clock M-DAY setting defines the current month and date for the real-time clock. This parameter is programmed in Month-Day format for both European and American date formats.

CLOCK H-MIN The Clock H-MIN setting is the current time in hours and minutes for the real-time clock.

HOUR LOGS Set the number of Hourly Logs to be recorded and to appear on the printed log report.

The hourly log entry occurs at 00 minutes each hour.

DAY LOGS Set the number of Daily Logs to be recorded and to appear on the printed log report.

The daily log entry occurs at 00 hours and 00 minutes each day.

WEEK LOGS Set the number of Weekly Logs to be recorded and to appear on the printed log report.

The weekly log entry occurs at 00 hours and 00 minutes each Monday.

MONTH LOGS Set the number of Monthly Logs to be recorded and to appear on the printed log report.

The monthly log entry occurs at 00 hours and 00 minutes on the first day of the month.

YEAR LOGS Set the number of Yearly Logs to be recorded and to appear on the printed log report.

The yearly log entry occurs at 00 hours and 00 minutes on the first day of the year.

SET

Page 48: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Instrument Calibration

40 505 LM01 - 18 May 2007

General Setup Parameters

RESET LOGS Reset the logged data. You may need to reset (clear) the logged data if you change the time/log settings.

Press or to select YES, then press the key. The instrument makes three beeps to confirm the reset command.

REPORT TYPE The Printer Protocol Report Type determines the nature of the printout from the REPORT PRINT - HOLD.SET prompt in the main menu. The following report types available in this instrument are:

• REP-01 Hourly Logs Report• REP-02 Daily Logs Report• REP-03 Weekly Logs Report• REP-04 Monthly Logs Report• REP-05 Yearly Logs Report• REP-06 Previous Day’s 24 Hour Report (0Hr – 23Hr, minimum

48 hourly logs required)

Press or to select Report Type.

PRN TYPE The Printer Protocol Printer Type allows the nature of the printer being used to be specified. The following printer types available in this instrument are:

• PRN-01 Generic computer printer• PRN-02 Generic roll printer (prints first line first)• PRN-03 Slip printer TM295

Press or to select Printer Type.

↓ → UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST ENDSET

SET

↓ → UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST END

DEFAULT VAR Select the main menu variable to display on power up or when the display timeout period has elapsed if it is enabled.

Press or to select the default variable display.

SUPPLY VOLT The instrument provides a power-limited supply for external transducers.

Press or to set the transducer supply voltage between 8 and 24 volts DC as required.

SET

Page 49: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Instrument Calibration

505 LM01 - 18 May 2007 41

Test Menu

The Test menu enables you to view the inputs and outputs to and from the instrument.

T-OUT MODE If the Display Timeout mode is enabled, and there is no user activity for the defined timeout period, the display panel returns to the default display.

This function is useful for the following reasons:

• to return the display to a preferred variable after the user has finished reading other information,

• to cancel the calibration mode and return to the default display if the user does not exit from the calibration mode for any reason.

Press or to select the display timeout function as follows:

• DISABLE - Timeout is completely disabled.• EN DISP - Timeout is enabled during Normal mode and Calibration

View mode.• EN EDIT - Timeout is enabled during Calibration Set mode.• EN ALL - Timeout is enabled for all modes.

T-OUT SEC The Display Timeout period defines the delay for the Display Timeout mode if it is enabled.

The display timeout period can be from 10 to 99 seconds.

DISPL TAGS The Display Tags option determines whether the instrument displays the default display tags or the user-defined tags. The display tag setting also defines whether the instrument displays the default error and warning messages, or the user-defined messages.

Note: The user-defined tags can be entered into the instrument only by the manufacturer or the distributor.

Press or to select the Display Tags option as follows:

• DEFAULT - the instrument displays the default (English) tags• USER - the instrument displays the user-defined tags.

BACK-L T-OUT If the backlight timeout is enabled, and there is no user activity (any keys pressed) for a period of 10 seconds, the display backlight switches off to save power. The backlight switches on when a key is pressed. Select the backlight timeout mode as required.

Press or to select ENABLE or DISABLE.

↓ → UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST ENDSET

Page 50: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Instrument Calibration

42 505 LM01 - 18 May 2007

In Calibration Set mode, (by entering the system password) you can control the outputs and the alarms as described in the table below.

System MessagesThe instrument displays messages for defined events and fault conditions.

The manufacturer or distributor can enter user-defined text for the messages. This user-defined text is displayed, instead of the default (English) messages, when the Display Tags option in the Setup menu is set to USER.

↓ → UNITS PARAMS INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST END

AINP mA The current of the signal input to AINP is displayed in milliamps.

LINPn STATE You can view the state of the logic input. If the input is an open contact or inactive it will display HI. If the input is a closed contact or active it will display LO.

DOUTn STATE You can control the state of the outputs. Press the or keys to set the output state as follows:

• PROCESS - the output depends on the current values of the inputs and the calculations that the instrument performs.

• ON - the output is activated. • OFF - the output is deactivated.

A-OUT STATE You can control the state of the outputs. Press the or keys to set the output state as follows:

• PROCESS - the output depends on the current values of the inputs and the calculations that the instrument performs.

• HI - the output is set to 20mA.• LO - the output is set to 4mA.

ALRMn STATE

orREL-n

You can control the state of the relays (alarms). Press the or keys to set the selected relay as follows:

• PROCESS - the relay operates according to the current values of the inputs and the relay settings as programmed.

• OPEN - the relay output contacts are set to “open”.• CLOSED - the relay output contacts are set to “closed”.

SUPPLY V You can display the actual DC output supply voltage, which may help with troubleshooting.

If the actual supply voltage is lower than the preset value (refer to General Setup Parameters on page 40) it may indicate that the output is overloaded.

SET

Page 51: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Instrument Calibration

505 LM01 - 18 May 2007 43

Error Messages

The system displays error messages as described in the following table:

Warning Messages

The system displays warning messages as described in the following table:

Error Messages Description

CPU Card Failure There are failed components on the CPU card and technical support is required.

Power Supply is Low The input and/or output power supply voltage is too low, ensure that:(a) input power supply voltage is within the specified range(b) output power supply is not overloaded.

New/Failed Battery - Set Time

The real-time clock has lost the correct time because the battery has failed, or there is a new battery. Set the current time and date (in the TM/LOG menu) to clear the error message and to continue data logging at the correct times.

Note: The instrument can continue operating with a failed battery, but the correct time will be lost if there are interruptions to the power supply.

Analog Input Signal Failure

The level sensor (analog input) has failed.

It is not possible to override this error condition. The instrument cannot operate without a level input.

Warning Messages Description

Value Has Been Set to Default

You have entered an invalid value for a parameter. Therefore, the instrument has set the default value.

Over Total Limit - Maximum Set

You have exceeded the maximum number of logging entries for the combined time bases. The instrument has set the current log setting to the remaining maximum number.

Already Assigned to Other Port

You have tried to assign a particular protocol type to more than one serial communication port. The instrument has set the protocol to NONE.

Page 52: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Instrument Calibration

44 505 LM01 - 18 May 2007

Alarm Messages

The instrument displays alarm messages as described in the following table:

Alarm Messages Description

Alarm 1 is Active The alarm condition, as defined for relay alarm 1 in the ALARMS section of calibration, is present.

Alarm 2 is Active The alarm condition, as defined for relay alarm 2 in the ALARMS section of calibration, is present.

Page 53: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

45

Chapter 6Communications

OverviewThis chapter describes the communications between the instrument and another communicating device such as a computer or a printer. You should have relevant information about the devices to which the instrument will be connected. Some connection examples are included in this manual, however, the operation and connection of other devices is outside the scope of this manual.

Hardware Interconnection

The instrument has three communication ports:

• RS-232 port on the rear panel (plus extra DB9 female connector) • RS-485 port on the rear panel • Infra-red port on the front panel (display panel option only)

The appropriate interface and protocols are selected during calibration.

RS-232 Port

The RS-232 port provides communication between the instrument and one other device such as a host computer or a printer.

Note: A printer must have a serial port to be able to be directly connected to the flow computer. It is not possible to communicate directly with a printer via a parallel port.

Computers use either a DB9 or a DB25 connector, and the connections to each type are shown in Figure 13.

505 LM01 - 18 May 2007

Page 54: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Communications

46 505 LM01 - 18 May 2007

Figure 13 RS-232 Cable Connections to a Computer

Note: The instrument requires a cable with straight-through connections. Do not use a null modem cable for RS-232 connection to a computer.

RS-485 Port

The RS-485 port enables communication with multiple devices. Each device has a unique address so that the “master” device can communicate with specific “slave” devices.

On RS-485 links, an external terminating resistor must be connected at the furthest end of the cable. When multiple instruments are connected, they should be “daisy chained” in a multidrop configuration as shown in Figure 14. Up to 32 units can be connected to the interface at a maximum distance of 1200 metres.

Figure 14 RS-485 Connections

Infra-red Port

The infra-red port is located on the front panel of the instrument. The infra-red port uses the Infra-red Developers Association (IrDA) physical layer format of signal encoding and decoding.

4

5

3

6

TerminalStrip

Instrument

2

3

5

7

8

TxD

RxD

GND

CTS

RTS

DB9

Computer/Printer

3

2

7

4

5

RxD

TxD

GND

RTS

CTS

DB25

2

3

5

7

8

DB9

Common

Optional

Optional

Twisted Pair

Load120 ohms

Gnd Gnd

HostComputer

CommsGnd

+

-

+ - + -

Instrument Instrument1 2 3 1 2 3

Page 55: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Communications

505 LM01 - 18 May 2007 47

The nature of the infra-red port requires the communicating device to be located close to the front of the instrument. Therefore, its main use would probably be for reloading the instrument application software, or occasional collection of data, rather than continuous communications.

ProtocolsThe communications protocols can be assigned to the communication ports on the instrument as follows:

• RTU - Modbus RTU available for all ports• PRN - Printer Protocol available for RS232 and RS485• NONE - If a port is not being used, set the protocol to NONE.

Note: The Printer Protocol is only available if the option with Real Time Clock is installed. Also a protocol cannot be assigned to more than one port at a time as described in Communications on page 36.

• Modbus RTU - Modbus RTU is an industry-standard protocol which allows the instrument to be easily connected to computers running supervisory software systems.

• Printer - In the Printer protocol there is a selection of printer types. Please refer to the Printer Protocol on page 53 for full details.

Modbus RTU Protocol Modbus RTU (remote terminal unit) is an industry standard protocol that allows the instrument to be easily interfaced to other communication devices.

The instrument implements the Modbus protocol as detailed in the Modicon Modbus Protocol Reference Guide PI-MBUS-300 Rev J (June 1996).

Message Format

In RTU mode, messages start with a silent interval of at least 3.5 character times. The first field transmitted is the device address. Following the last transmitted character, a similar interval of at least 3.5 character times marks the end of the message. A new message can begin after this interval. The entire message frame must be transmitted as a continuous stream. A typical message frame is shown below:

Except for broadcast messages, when a master device sends a query to a slave device, it expects a normal response. One of four possible events can occur from the master’s query:

Address Function Data CRC Check1 byte 1 byte n bytes 2 bytes

Page 56: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Communications

48 505 LM01 - 18 May 2007

• If the slave device receives the query without a communication error, and can handle the query normally, it returns a normal response.

• If the slave does not receive the query due to a communication error, no response is returned. The master program has to process a timeout condition for the query.

• If the slave receives the query, but detects a communications error (parity or CRC), no response is returned. The master program has to process a timeout condition for the query.

• If the slave receives the query without a communication error, but cannot handle it (for example, if the request is to read a nonexistent register), the slave will return an exception response informing the master of the nature of the error.

Instrument Address

The address of the instrument is programmable in the range from 1 to 247. Some addresses are reserved according to PI-MBUS-300 and have a special meaning:

• 0 = Broadcast, no response required from slave devices• 248 to 255 Reserved

Function Codes

The instrument accepts the following function codes:

Code Name Description03 Read data register(s) Obtain the content of one or more 2-byte

data registers.06 Preset data register Preset one 2-byte data register.07 Read status register Obtain the content of 1-byte status register.16 Preset data register(s) Preset one or more 2-byte data registers.

Page 57: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Communications

505 LM01 - 18 May 2007 49

Exception Response

The instrument forms an exception response by adding 80H to the function code and using an exception code as the 1-byte data field in the returned frame. Implemented exception codes are as follows:

List of Data Registers

The following list describes the addresses and meaning of the data registers in the instrument. The data values are expressed in the engineering units that were selected for the variables when the instrument settings were configured. The “Data Type” for the 2-register (4-byte) data values can be set in programming mode as Floating Point or Long Integer as described in Communications on page 36.

The registers are grouped in blocks that relate to a particular function of the instrument.

Note: Conventional numbering of registers often starts from 1, therefore be aware that “register 1” in this case has “address 0” and so on.

Current and Logged Process Data

This block of registers is available for the retrieval of current or logged process data with its matching time and date information.

Code Name Description01 Illegal function The function code is not a legal action for

the slave.02 Illegal data address The data address is not a legal address for

the slave.03 Illegal data value The data value is not a legal value for the

slave.05 Acknowledge The slave has accepted the request and is

processing it, but a long duration of time will be required to do so.

06 Slave device busy The slave is engaged in processing a long duration program command. The master should re-transmit the message later when the slave is free.

Page 58: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Communications

50 505 LM01 - 18 May 2007

Use the log timebase and log number to retrieve the logged information from the appropriate register. If a particular log number does not exist, or the instrument does not have the optional real-time clock, the time and date stamp and associated variables are set to zero.

Note: The Floating Point variable is represented in IEEE-754 Floating Point 4-byte format and requires two 2-byte data registers:

Register Name Comments Read Only or Read/Write

Type

1 Product Volume

Process Variables

R DT*

3 Product Level R DT5 Volume Full Percentage R DT7 Product Mass R DT9 Reserved R DT11 Reserved R DT13 Reserved R DT15 Reserved R DT17 Reserved R DT19 Reserved R DT21 Reserved R DT23 Reserved R DT25 Reserved R DT27 Reserved R DT29 Reserved R DT31 Year

Current Date/Time orLogged Date/Time Stamp

(see register 38 Log Number).Only current Date/Time can be edited

R/W I†

32 Month R/W I33 Date R/W I34 Hour R/W I35 Minute R/W I36 Second R I37 Log Type 00 - hourly or log records

01 - daily02 - weekly03 - monthly04 - yearly05 - last edit of calibration

R/W I

38 Log Number If set to 0, current variables and Date/Time are retrieved

R/W I

39 Clear Data 01 - clear logs02 - clear accumulated totals03 - clear non accumulated totals

W I

40 Reserved

* DT = Data Type of 2-register (4 byte) values can be set as Floating Point or Long Integer values† I = Integer (2 bytes) (Holding Registers)

IEEE-754 Modicon Registers1st byte low byte (register X)2nd byte high byte (register X)

Page 59: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Communications

505 LM01 - 18 May 2007 51

This means that two data registers must be read or written to obtain, or preset, one data value.

Instrument Exception Status

This register is available to verify the status of the instrument.

Instrument Configuration, Control and I/O

This block of registers is available in some applications to give access to important information in the instrument.

3rd byte low byte (register X+1)4th byte high byte (register X+1)

IEEE-754 Modicon Registers

Register Name Comments Read Only or Read/Write

Type

41 Exception Status

00 = no error 01 = analog input 1 failure02 = analog input 2 failure03 = analog input 3 failure04 = analog input 4 failure05 = invalid calibration parameter 06 = invalid reference parameter07 = invalid property08 to 09 reserved 10 = process parameters out of range11 = input is over limit12 = flow error detected20 = system failure21 = power supply is low22 = new or failed clock battery23 to 29 reserved 30 = alarm 1 active31 = alarm 2 active32 = alarm 3 active33 = alarm 4 active

R I*

* I = Integer (2 bytes) (Holding Registers)

Register Name Comments Read Only or Read/Write

Type

42 Reserved43 Reserved44 Reserved45 Relay State 0 to 15 Binary representation of relay status.

0 = open; 1 = closed.

B0 = relay 1 (LSB)B1 = relay 2

R I*

Page 60: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Communications

52 505 LM01 - 18 May 2007

46 Relay Control 0 to 15 Binary representation of relay control. 0 = open; 1 = close.

B0 = relay 1 (LSB)B1 = relay 2

R/W I

47 Relay Control Source

0 to 15 Binary representation of relay control source.0 = Local (controlled by instrument operation) 1 = RTU (controlled by Modbus register 46).

B0 = relay 1 (LSB)B1 = relay 2

R/W I

48 to 50 Reserved51 to 99 Reserved101 Analog Input The input is configured for 4-20mA.

The value will be read in Amperes.R DT†

* I = Integer (2 bytes) (Holding Registers)† DT = Data Type of 2-register (4 byte) values can be set as Floating Point or Long Integer values

Register Name Comments Read Only or Read/Write

Type

Page 61: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Communications

505 LM01 - 18 May 2007 53

Printer Protocol A printer protocol is available in the 500 Series. It provides the ability to print out live data, individual logged data and to do some report-style printing of logged data. The method of printing these and the format of the printouts is described below.

Note: Printer output is only available if the Real Time Clock option is fitted.

The selection of Printer Protocol can be made for the Communications Protocol options for the RS232 or RS485 port. A list of log report types and printer types available at the end of the TM-LOG calibration menu.

Report Types

The list of report types is as follows:

• REP-01 Hourly Logs Report• REP-02 Daily Logs Report• REP-03 Weekly Logs Report• REP-04 Monthly Logs Report• REP-05 Yearly Logs Report• REP-06 Previous Day Hourly Logs (0Hr – 23Hr, minimum 48

hourly logs required)

The number of logs printed in each report are determined by the values programmed for each timebase in the TM-LOG menu.

Printer Types

The list of available printers is as follows:

• PRN-01 Generic computer printer• PRN-02 Generic roll printer (printing first line first)• PRN-03 Slip Printer TM295

Customizing a Printout

A customized printout can be provided which can have up to 4 header lines and 3 footer lines. It is also possible to include or exclude each main menu items on the printout. If any customizing of the printout is required discuss this with the distributor.

Page 62: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Communications

54 505 LM01 - 18 May 2007

Types of Printouts

Live Data

The CLEAR key, when in main menu, is shared as the PRINT key if the printer protocol has been selected. A printout will be initiated whenever this key is pressed. If printing is not required, do not select printer protocol.

The format of this printout will be:

Custom Header Line 1Custom Header Line 2Custom Header Line 3Custom Header Line 4

Current Docket No.

Instrument Serial No. & Tag

Current Date & Time & StatusVariable unit valueVariable unit valueetc.

Custom Footer Line 1Custom Footer Line 2Custom Footer Line 3------------------------------------------- <separation line>

(Note that blank header and footer lines are not printed).

Docket Number

The docket number that appears on the live data printout indicates the print number. This number is cleared when the accumulated totals are reset.

Instrument Serial Number and Unit Tag

The instrument serial number and unit tag is the same as the information shown in the Model Info menu. For more details refer to Model Information on page 19.

Individual Log Data

When in the Log Menu and while holding the DISPLAY key to view the data of the log of interest the RESET key can be pressed to initiate a printout of that log entry. The printout will have the time and date stamp corresponding to when the log was taken. After the print has been initiated there will be the opportunity to scroll to view another log entry and print again.

Page 63: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Communications

505 LM01 - 18 May 2007 55

Custom Header Lines

Instrument Serial No. & Tag

Log Date & Time & StatusVariable unit valueVariable unit valueetc.

Custom Footer Lines -------------------------------------------- <separation line>

Log Report Printing

As there is the likelihood that the reports can be of a considerable length it is strongly recommended that only the 80 Column printer with Z fold (tractor feed) paper be used. This is just as much for the memory storage of printer as it is for the reliable paper supply.

There is a HOLD.SET REPORT PRINT prompt under the main menu with the ability to print the pre-selected type of report. Pressing and holding the SET key for two seconds will initiate the printout. Any of the Log Reports will have the following format:

Custom Header Lines

Title of Report <internally set, indicates report type>

Current Date & TimeInstrument Serial No. & Tag

-------------------------------------------- <separation line>Log No. Date & Time & StatusVariable unit valueVariable unit valueetc.

-------------------------------------------- <separation line>Log No. Date & Time & StatusVariable unit valueVariable unit valueetc.

-------------------------------------------- <separation line>Log No. Date & Time & StatusVariable unit valueVariable unit value

ETC

Page 64: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Communications

56 505 LM01 - 18 May 2007

Custom Footer Lines -------------------------------------------- <separation line>

Reports such as “All Hourly Logs” will print in the historical order, and for those logs that have no data (e.g. unit was powered off at the time) the print will show “Data not available”. i.e.

Log No. Date & Time & StatusVariable unit valueVariable unit valueetc.

-------------------------------------------- <separation line>Log No. Data Not Available

-------------------------------------------- <separation line>Log No. Date & Time & StatusVariable unit valueVariable unit valueetc.

If the unit is programmed for 0 logs for a particular time base then the report for that time base will only consist of the header and ID information and a “Data Not Available” message. Likewise for the 0Hr to 23Hr report to print the complete report there must be a minimum of 48 hourly logs programmed otherwise “Data Not Available” will be printed for the missing logs.

Custom Header Lines

Title of Report

Current Date & TimeInstrument Serial No. & Tag

Data Not Available

Custom Footer Lines -------------------------------------------- <separation line>

Printer Data Control

Some printers have limited data buffers and are therefore unable to collect all the print data being transmitted. The 500 Series has the capability of software handshaking. The Xon/Xoff characters can be used by any of the printer types to control the flow of data to ensure that data is not lost.

Some printers will also transmit an Xoff character in response to other events such as printer being off-line, print head not engaged or power being removed. The specific behaviour of the printer being used should be noted.

Page 65: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Communications

505 LM01 - 18 May 2007 57

Error Messages

There are two printer error messages that can be displayed.

PAPER OUT

This message is related to the Printer Type PRN-03 TM295 Slip printer. It is standard procedure with this printer to check for paper status before printing. If a print is attempted but there is no paper the PAPER OUT message will be scrolled. The instrument will continue to poll the printer for paper and if paper is detected before a communications timeout expires the print will commence.

COMMS TIMEOUT

This message is relevant for all printer types and will be activated for the following conditions.

1. If the flow of data is stopped due to software or hardware handshaking and is not allowed to resume before the communications timeout.

2. If Printer Type is PRN-03 Slip printer and a paper status is requested but no response is received within the timeout period.

3. Paper Out has been detected for Printer Type PRN-03 but no paper is inserted within the timeout period.

When a communications timeout error has been activated the message COMMS TIMEOUT will be scrolled once, the request to print will be cleared and the instrument will return to its normal mode.

Page 66: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

Communications

58 505 LM01 - 18 May 2007

Page 67: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

59

Appendix AModel Numbers

Product Codes

Note: Example full product part number is 505.112EFC-LM01 (This is the number used for placing orders).

Model Supplementary Code Description505 . - LM01

Enclosure

1 Panel mount enclosure2 Field mount enclosure (not yet available)

3/5 Explosion proof Ex410 with metric glands (5 specifies heater version)

4/6 Explosion proof Ex410 with NPT glands(6 specifies heater version)

Output Options0 Basic - RS232 and RS485 serial ports, 2 relays, 2

pulse outputs, rear key input

1 Advanced - also includes 4-20mA o/p and Real-time clock for printer output and logging (100 logs)

Extra Options 2 9-way DB connector for RS232 serial port

Power SupplyE For 220/240VACA For 110/120VACD For DC power only 12-28VDC

Display Panel OptionsS Standard (no backlight, LCD backup or Infra-Red

comms port)

F Fully optioned (with backlight, LCD backup and Infra-Red comms port)

PCB ProtectionC

Conformal coating - required for maximum environmental operating range. Recommended to avoid damage from moisture and corrosion.

N None - suitable for IEC standard 654-1 Climatic Conditions up to Class B2 (Heated and/or cooled enclosed locations)

Application Pack Number LM01 Defines the application software to be loaded into the instrument

For example: Model No. 505.112EFCDisplayed on the 500 Series as:(only h/w that affects the operation is represented)

-1--F-

505 MODEL

505 LM01 - 18 May 2007

Page 68: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

60 505 LM01 - 18 May 2007

Custom Version Codes

Application Information CodeThe Application Information code is an aid for users and service personnel to determine the type of inputs that are used in a particular application. The Application Information code is displayed on the instrument as shown below.

Code Description

Origin Code

Identifies Distributor

00 Factory Default Application

01 Contrec Pty. Ltd. Melbourne Australia

02 Contrec Pty. Ltd. Sydney Australia

03 Contrec Europe Ltd. West Yorkshire UK

04 Contrec - USA, LLC. Pelham AL 35124 USA

05 Flowquip Ltd. Halifax UK

06

etc.

User Language

0 English (Default)1 German2 Dutch3 French4 Spanish5etc.

Distributor’s Code000

Distributor’s own choice. Possibly a code that identifies the customer and the application.…

999

For example: 02 3 157Displayed on the 500 Series as:

023157

CUSTOM VERS

F-FC01 APPL

Assignment type

Application number

Page 69: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

505 LM01 - 18 May 2007 61

The Application number identifies the application as in the following examples:

• BC01 - single channel batch controller for frequency flow input.• FC01 - single channel flow computer for frequency flow input

The Input Assignment type indicates the physical input that is assigned to each input on the instrument. The code is made up from two characters as follows:

The codes are as follows:

• - - not used in this application• A - indicates an analog flow input such as for volume or mass• F - indicates a frequency flow input such as for volume or mass• L - indicates a level input• d - indicates a density input• t - indicates a temperature input.

For example, FL is an instrument with FINP (frequency input) assigned to a flow input, AINP (analog input) assigned to a level input.

FINP AINPX X

Page 70: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

62 505 LM01 - 18 May 2007

Appendix BUnits of Measurement

Available Units of MeasurementThe following is a list of the available units of measurement used across the range of 500 Series applications.

Units Type Available units of measurement

Volume m3, Km3, Ltr, Gal, KGal, MGal, ft3, kft3, Mft3, bbl

Volume Flowrate m3/s, m3/min, m3/h, m3/D, L/s, L/min, L/h, Gal/s, Gal/min, Gal/h, KGal/D, MGal/D, ft3/s, ft3/min, ft3/h, Mft3/D, bbl/s, bbl/min, bbl/h, bbl/D

Volume K-Factor P/m3, P/Ltr, P/Gal, P/ft3, P/bbl

Mass kg, g, Ton, lb, Klb

Mass Flowrate kg/s, kg/min, kg/h, g/s, g/min, g/h, Ton/min, Ton/h, Ton/D, lb/s, lb/min, lb/h, Klb/min, Klb/h, Klb/D

Mass K-Factor P/kg, P/g, P/Ton, P/lb, P/Klb

Energy kJ, MJ, GJ, kWh, MWh, kBTU, Ton.h, therm, cal, kcal, Mcal

Power kJ/h, MJ/h, GJ/h, kW, MW, kBT/M, kBT/h, Ton, therm/min, therm/h, kcal/h, Mcal/h

Energy K-Factor P/kJ, P/kWh, P/kBTU, P/Ton.h, P/therm, P/kcal

Temperature Deg K, Deg C, Deg F, Deg R

Pressure Pa, kg/m2, kg/cm2, kPa, MPa, mbar, bar, psi, Atm, inH2O, mmH2O

Density kg/m3, kg/Ltr, lb/ft3, SG60F

Specific Volume m3/kg, L/kg, ft3/lb

Specific Enthalpy kJ/kg, BT/lb, cal/g, cal/kg, kcal/kg, Mcal/kg

Reynolds Number E+0, E+3, E+6 (scaling for unitless variable)

Length (Level) m, mm, cm, INCH, FOOT

Velocity m/s, m/M, m/h,ft/s, ft/M, ft/h

Length K-Factor P/m, P/cm, P/INCH, P/FOOT

Area m2, ft2

Ratio %

Page 71: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

63

Numerics4-20mA

input 9output 10

Aalarm

connection 11equipment failure 35hysteresis 36relays 34setpoint 36

alarmsmenu 19messages 44setpoints 20

ALARMS key 16alarms menu 35application code 60approvals 4

Bback panel 8battery

failed 43life 38new 43

baud rate 37

Ccalibration

menu 26set mode 24view mode 23

CLEAR key 16clock

battery 38date format 39real-time 38

codesapplication information 60customer version 60exception 51product number 59

communicationconnections 12protocols 47

communications 3, 45menu 36

connectionsalarm 11communication 45communications 12electrical 8input 9output 10

control modes 20customer version codes 60customizing a printout 53

Ddaily logging 39data log

viewing 17data logging

daily 39hourly 39monthly 39weekly 39yearly 39

date format 39default variable 15display

specifications 5timeout mode 41timeout time 41

DISPLAY key 16, 19display-only parameter 23

Eearthing 13

Index

505 LM01 - 18 May 2007

Page 72: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

64 505 LM01 - 18 May 2007

electrical connections 8equipment failure alarm 35error messages 43exception codes 51

Ffeatures 1flash driver port assignment 38format, date 39front panel

infra-red port 13keys 15lamps 15

Ggeneral specifications 5

Hhardware connections 45hourly logging 39hysteresis, alarm 36

Iinfra-red port 13, 36, 46input

4-20mA 9connections 9specifications 5

inputs menu 29installation 7instrument

settings 28interconnections, communication 45interference suppression 12

Kkey

ALARMS 16CLEAR 16DISPLAY 16, 19LEVEL 15RESET 16TOTAL 16

keys, front panel 15

Llamps, status 15LEVEL key 15

logged data 17viewing 17

loggingdaily 39hourly 39monthly 39weekly 39yearly 39

Mmain menu items 16menu

alarms 35calibration 26comms 36inputs 29outputs 34params 28setup 40test 41tm/log 38units 28

messagesalarms 44error 43system 42warning 43

Modbus data format 37Modbus RTU protocol 47mode

display timeout 41normal operation 15process control 20set calibration 24view calibration 23

model numbers 59monthly logging 39mounting 7

Nnormal mode 15number

model 59serial 19

Ooperation, control modes 20operation, normal mode 15

Page 73: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

505 LM01 - 18 May 2007 65

outputconnections 10

4-20mA 10pulse 10

specifications 5outputs menu 34

Ppanel

lamps 15mounting 7rear 8

parameterdisplay-only 23not visible 23password-protected 23programmable 23

parameters menu 28parity bits 37password-protected parameter 23port

assignment, flash driver 38flash driver assignment 38infra-red 13, 36, 46RS-232 12, 36, 45RS-485 13, 36, 46

power supply interruption 38printer

data control 56error messages 57protocol 53report types 53

printer types 53printouts

individual logs 54live data 54log report 55types 54

product number codes 59programmable parameters 23protocol

communication 47Modbus RTU 47printer 53

pulse output 10

Rreal-time clock 38rear panel 8

relay outputs 3relays, alarm 34remote key input 33RESET key 16RS-232 port 12, 36, 45RS-485 port 13, 36, 46RTU protocol 47

Sserial number 19setpoint, alarm 36setpoints

alarms 20settings

instrument 28setup menu 40shielding 13snubber 12specifications 5standards 4status lamps 15stop bits 37suppression, interference 12system

errors 43messages 42warnings 43

Tterminal designations 8test menu 41timeout

mode 41time 41

tm/log menu 38TOTAL key 16

Uunit tag 19units

menu 28

Vvariable, default 15version, customer 60view data logs 17

Wwarnings 43

Page 74: Model 505 Flow Computer - Contrec · The 505 LM01 application monitors and measures the level of product in a single tank. The instrument uses the 4-20mA signal from a wide range

66 505 LM01 - 18 May 2007

weekly logging 39

Yyearly logging 39