Form: 155.32-EG2.EN.UL (320)

Supersedes: 155.32-EG2.EN.UL (1118)

Engineering Guide

Issue Date: 2020-03-12

Model YHAU-CGN/H Double Effect DirectFired Chiller-Heater

Page 2: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater
Page 3: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

ContentsContentsNomenclature................................................................................................................................. 5

Approvals......................................................................................................................................... 6

Introduction.................................................................................................................................... 7

How it works................................................................................................................................... 8

Evaporator............................................................................................................................................ 8

Absorber............................................................................................................................................... 9

Two-step evaporator – absorber....................................................................................................... 9

Plate type heat exchangers.............................................................................................................. 10

Parallel flow........................................................................................................................................ 11

High temperature generator (HTG)................................................................................................ 11

Low temperature generator (LTG).................................................................................................. 11

Condenser.......................................................................................................................................... 12

Equipment Overview.................................................................................................................... 13

General................................................................................................................................................ 13

Construction....................................................................................................................................... 13

Waterboxes........................................................................................................................................ 13

Tube materials................................................................................................................................... 13

Automatic crystallization prevention system................................................................................. 14

Pumps................................................................................................................................................. 14

Automatic purging system............................................................................................................... 15

Lithium bromide and refrigerant.................................................................................................... 15

Dry shipment...................................................................................................................................... 15

Linkless type gas burner.................................................................................................................. 15

Control panel...................................................................................................................................... 15

YHAU control center.......................................................................................................................... 16

Main screen........................................................................................................................................ 16

Data screen........................................................................................................................................ 17

Failure/alarm screen......................................................................................................................... 17

Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater i

Page 4: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Setting screen.................................................................................................................................... 18

Options and Accessories............................................................................................................. 19

Application Data........................................................................................................................... 21

Location.............................................................................................................................................. 21

Water circuits..................................................................................................................................... 21

Sound and vibration considerations............................................................................................... 22

Thermal insulation............................................................................................................................ 22

Electrical data..................................................................................................................................... 22

Natural gas inlet pressure................................................................................................................ 22

Typical operational range................................................................................................................. 23

Weights.......................................................................................................................................... 24

Physical Data................................................................................................................................. 25

Load Points for EX and EXW Units - High Efficiency................................................................. 26

Load Points for EX and EXW Units - Standard Efficiency......................................................... 27

Split Shipment - High Efficiency - CGN...................................................................................... 29

Split Shipment - High Efficiency - CGH...................................................................................... 30

Split Shipment - Standard Efficiency - CGN............................................................................... 31

Split Shipment - Standard Efficiency - CGH............................................................................... 32

Electrical Data - CG/AN................................................................................................................ 34

Electrical Data - CG/AH................................................................................................................ 35

Nozzle Arrangements.................................................................................................................. 36

Sound Data.................................................................................................................................... 38

Process and Instrumentation..................................................................................................... 39

Cooling only (evaporator)................................................................................................................ 39

Heating only (evaporator)................................................................................................................ 40

Residential hot water (auxiliary heat exchanger)......................................................................... 41

Simultaneous heating and residential hot water only.................................................................. 42

Simultaneous cooling and residential hot water........................................................................... 43

Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heaterii

Page 5: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Guide Specifications..................................................................................................................... 47

General................................................................................................................................................ 47

Base unit includes:............................................................................................................................ 47

Base unit does not include:.............................................................................................................. 48

Construction....................................................................................................................................... 48

Tube materials................................................................................................................................... 49

Waterboxes........................................................................................................................................ 49

Automatic decrystallization system................................................................................................. 49

Pumps................................................................................................................................................. 49

Fully automatic purging system...................................................................................................... 49

Lithium bromide and refrigerant.................................................................................................... 49

Dry shipment...................................................................................................................................... 50

Linkless type gas burner.................................................................................................................. 50

Control panel...................................................................................................................................... 50

Main screen........................................................................................................................................ 50

Data screen........................................................................................................................................ 52

Failure / alarm screen....................................................................................................................... 54

Setting screen.................................................................................................................................... 55

iiiModel YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Page 6: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater
Page 7: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Nomenclature

5Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Page 8: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Approvals• GB/T 18362-2008 Direct Fired Lithium Bromide Absorption Water Chiller-Heater

• UL 1995 2011 Ed.4 + R:03Oct2014 Standard for Safety Heating and Cooling Equipment

• UL 508A Industrial Control Panel

• NFPA70 National Electrical Code

• NFPA79 Electrical Standard for Industry Machine

Images contained in this document may represent the standard product with available options.

Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater6

Page 9: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

IntroductionThe YORK YHAU-CGN/H double-effect direct fired absorption chiller-heater represents the world'smost efficient commercially available absorption technology. The unique two step design requiresa remarkably low fuel input rate. With today’s energy and environmental considerations, the YHAU-CGN/H absorption chiller-heater is the ideal choice for a wide range of commercial applications, aswell as areas with low fuel costs or high electric costs.YHAU-CGN/H absorption chiller-heaters are equipped with sophisticated PLC based controls,making the chiller-heater the smartest and most efficient absorption chiller-heater on today’smarket.Each YHAU-CGN/H double-effect direct fired chiller-heater is functionally tested at the factorybefore shipping.With its high efficiency, proven reliability, and the guaranteed quality of a standard performancetest, these units are the ideal choice for today’s demanding applications.

7Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Page 10: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

How it worksThe YHAU-CGN/H direct fired absorption chiller-heater uses water as the refrigerant and lithiumbromide (LiBr) as the absorbent. It is the strong affinity that these two substances have for oneanother that makes the chiller cycle work. The vapor pressure of the LiBr solution is lower thanthe vapor pressure of the refrigerant. The vapor pressure of the LiBr solution is directly relatedto the amount of refrigerant (water) present in the solution with the LiBr salt and the solutiontemperature. The entire absorption process occurs in almost a complete vacuum.

Figure 1: Direct fired absorption cycle

EvaporatorLiquid refrigerant enters the evaporator and is distributed over the top of the tube bundle. As therefrigerant droplets cover the outside surface of the tubes, the heat from the returning chilledwater passing through the tubes causes the refrigerant to flash from a liquid to a vapor. Thetemperature at which this happens depends on the evaporator shell pressure, which is dictatedby the absorber section of the chiller-heater. The refrigerant vapor passes through the mist

Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater8

Page 11: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

eliminators and into the absorber section of the chiller-heater. As the liquid refrigerant passesdown through the bundle of evaporator tubes, more and more of the refrigerant vaporizes. Therefrigerant remaining in a liquid state at the bottom drains into the refrigerant tank and is pumpedback up the top of the tube bundle where the process is repeated.

AbsorberConcentrated LiBr solution enters the absorber section of the chiller-heater and is sprayed overthe absorber tube bundle. Because the vapor pressure of the concentrated solution is very low, therefrigerant (water) vapor from the evaporator flows into the absorber and is absorbed into the LiBrsolution. This mass transfer process lowers the concentration of the LiBr solution as the refrigerant(water) is absorbed into the solution. This dilution process generates heat and, if not cooled, wouldeventually stop as the solution temperature would rise with a corresponding rise in vapor pressure.This would be similar to closing the vanes or slowing down a centrifugal compressor on a chiller-heater where the load was constant. The water flowing inside the absorber tube bundle comesfrom the cooling tower and serves to cool the LiBr solution as it flows down over the tube bundle.This allows the absorption process to continue and the solution becomes more diluted as it absorbsmore refrigerant vapors. When the LiBr solution reaches the bottom of the absorber section, it hasbecome too diluted and drains into the suction of the solution pump where it is re-concentrated.The following section describes the highly unique 2-step evaporator-absorber design of the YHAU-CGN/H direct fired absorption chiller-heater.

Two-step evaporator – absorberThe evaporator and the absorber are split into two sections. This design, similar to a series-counter-flow chiller arrangement along with the parallel flow cycle, facilitates lower LiBr solutionconcentrations. This reduces pressure, the potential for corrosion, and the risk of crystallization andimproves efficiency in conjunction with other advanced components described later in this section.The two evaporators are in series with respect to the chilled water flow through the tubes. In otherwords, the chilled water flows through the lower evaporator tubes first and then to the upperevaporator tubes. Each evaporator operates at a slightly different temperature and pressure.The refrigerant in the lower evaporator boils at a slightly higher temperature than in the upperevaporator, consequently cooling the chilled water in two steps.The two absorber sections are split also, with the strong solution first entering the top of theuppermost absorber and flowing down through the top absorber bundle. It then flows into the topof the lower absorber section. The strong solution entering the upper absorber takes advantageof its lower vapor pressure allowing the upper evaporator to operate at a lower pressure andtemperature.When the LiBr solution enters the lower absorber section it is somewhat diluted from therefrigerant vapor that boiled off in the upper evaporator. At this lower concentration the solutionvapor pressure would normally not be sufficient to provide an evaporator pressure low enough tosatisfy the leaving chilled water design. However, the lower evaporator is the first step of the chilledwater cooling cycle, and the dilute solution’s vapor pressure is adequate to maintain the requiredtemperature and pressure in the lower evaporator.The cooling water enters the lower absorber section first, keeping the vapor pressure of the weakersolution as low as possible.Both the refrigerant (water) and LiBr dispersion system are gravity fed and made of stainless steel.

9Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Page 12: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Plate type heat exchangersThe dilute (weak) LiBr solution leaving the absorber section is pumped through various platetype heat exchangers (such as the low temperature heat exchanger, refrigerant condensate heatexchanger, and high temperature heat exchanger) before it enters the high temperature generatorand low temperature generator sections. These plate type heat exchangers provide cycle efficiencyby preheating the dilute solution. Preheating the dilute solution reduces the consumption of thedriving heat source in the high temperature generator section. The concentrated solution flows outof the generators and back through the various heat exchangers.

The relatively high temperature solution streams from the two generators are used to preheat theweak solution stream leaving the absorber.

Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater10

Page 13: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Parallel flowThe unique parallel flow divides the solution between the low temperature generator and the hightemperature generator sections into two parallel, balanced paths. The result is a safer and moreefficient operation at a much lower pressure than conventional series-flow designs. The varioussolution-to-solution plate type heat exchangers optimize efficiency by enabling effective heattransfer between the diluted (weak) and the concentrated LiBr solutions.

High temperature generator (HTG)YHAU’s high temperature generator section has the unique water tube design where the dilute LiBrsolution coming from the high temperature heat exchanger is inside the tubes, and the productsof combustion (exhaust gas from burning of natural gas), is on the shell side. The hot refrigerantvapor boiled off is sent to the low temperature generator. This leaves behind a strong solution thatis returned through the high temperature heat exchanger.The water tube design is efficient and compact with a lower pressure drop as compared tothe conventional smoke tube type design where the exhaust gas is inside the tubes while theLiBrsolution is on the shell side. Being more efficient, the exhaust gas leaving temperature is lowerthan the smoke tube design.The water tube design also benefits from less volume of LiBr solution and hence faster startuptime. It does not require any ceramic refractory compared to the conventional design. Thisimproves reliability.

Low temperature generator (LTG)The hot refrigerant vapor from the high temperature generator heats up the dilute solution comingin from the low temperature heat exchanger. This vapor then condenses into hot refrigerant liquidand is sent to the condenser through the refrigerant condensate heat exchanger. The additionalvapor produced in the LTG by heating up the dilute solution is sent to the condenser.The LTG is of a falling film design, ensuring superior heat transfer and enhanced life by eliminatingwear and tear at the tube supports.

11Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Page 14: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

CondenserThe cooling water from the absorber section enters into the condenser section. This helps tocondenser the refrigerant vapors produced in the LTG and the condensed refrigerant from therefrigerant condensate heat exchanger. The liquid refrigerant is then sent back to the evaporatorsection through a U-pipe (liquid seal).This completes the cooling cycle.

Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater12

Page 15: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Equipment OverviewGeneralThe YHAU-CGN/H direct fired absorption chiller-heaters are factory-packaged including theevaporator, condenser, low temperature generator, high temperature generator, absorber, pumps,automatic purging system, control center, interconnecting unit piping, burner, and wiring.The initial charge of refrigerant and LiBr solution is supplied for each chiller-heater. Actual shippingprocedures depends on a number of project-specific details.Johnson Controls factory-trained, field service representatives supervise or perform the initial start-up and provide concurrent operator instructions.

ConstructionThe chiller-heater consists of a low temperature generator, high temperature generator, solutionheat exchangers, absorber, condenser, and an evaporator. To minimize the risk of corrosion, theevaporator dispersion tray and the absorber dispersion tray are stainless steel. Each dispersiontray has two step construction and any foreign material is removed from the LiBr solution or therefrigerant at the first stage tray. This avoids any degradation of dispersion performance due toclogging.The evaporator, absorber, condenser, low temperature generator, and high temperature generatorare a shell and tube design. A shell-side rupture disc is furnished and set to blow at 12.0 psig, +/- 2.0psi.The evaporator cycle and the absorber cycle consists of two-step (upper stage and lower stage).This technology makes absorber solution concentration weak, extending machine life. Furthermore,this technology makes the generator solution temperature lower than an ordinary absorber.The plate-type solution heat exchangers are equipped to preheat the diluted solution and achievehigher efficiency.

WaterboxesWaterboxes are removable to facilitate tube cleaning and replacement. All absorber and condenserwaterboxes for CGN/H360EXH/S models or larger are marine type. Water circuit tubing isreplaceable from either end of the absorption unit. All waterboxes and associated water circuitnozzles and tube bundles are designed for 150 psig and water tested to 188 psig. Vent and drainconnections are provided on each waterbox. All the water connections are equipped with ANSIflanges. Mating flanges are not included. The inside of the waterboxes and waterbox covers iscoated with an epoxy resin paint.

Tube materialsEvaporator tubes are Low Residual Phosphorus Deoxidized Copper (C1201), finned type, with a wallthickness before finning of 0.024 in. The absorber, condenser and low temperature generator tubesare bare type and made of 0.024 in. Wall stainless steel (sus436ltb). High temperature generatortubes are carbon steel.

13Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Page 16: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Figure 2: Unit components

Item Components Item ComponentsA Cooling water outlet G Cooling water intletB Condenser H Chilled / hot water inletC Low temperature generator I Burner control panelD High temperature generator J EvaporatorE Burner K Chilled / hot water outletF Solution pump L Absorber

Automatic crystallization prevention systemThe YHAU-CGN/H chiller-heater is built with an anti-crystallization system. The absorber and theevaporator are located side by side in the same shell and separated by an eliminator. When theconcentration of LiBr in the chiller-heater goes up, the water level at the evaporator increases andautomatically spills over to the absorber. This causes the concentration rate of the solution at theabsorber to go down.

PumpsSolution and refrigerant pumps are hermetically sealed, self-lubricating, totally enclosed, factory-mounted, wired, and tested. Motor windings are not exposed to LiBr or water. The suction anddischarge connections for each pump is fully welded to the unit piping to minimize the opportunityfor leaks. Pumps are designed to operate for a total of 60,000 hours. Components in the pumpssuch as bearings and sealing gaskets are to be replaced every 20,000 hours.

Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater14

Page 17: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Automatic purging systemThe chiller-heater is equipped with a purging system to remove non-condensable gases from theunit during operation. Non-condensables are collected by an eductor and accumulated in thepurge tank. The chiller-heater can dictate the pressure increase in the purge tank and automaticallyremove the non-condensable gas through the operation of an electric vacuum pump.The purge pump is a oil rotary double stage design, and is furnished complete with a motor and allrequired accessories. The purge pump is shipped mounted on the chiller-heater and the connectinghose is factory installed. The purge pump oil is charged at the factory.

Lithium bromide and refrigerantLiBr contains a lithium molybdate corrosion inhibitor to minimize the rate of ferrous metalcorrosion on both the solution and refrigerant sides of the unit. The solution and deionizedrefrigerant water are in the barrels and shipped with the chiller. They are changed at the fieldduring commissioning.

Dry shipmentThe solution and refrigerant water are kept in the barrels and shipped with the chiller. They arecharged at the field during the commissioning. The chiller is charged with N2 to 4.4 psig during thedelivery.

Linkless type gas burnerThe gas burner and the train is designed and built according to UL standards and codes. Capacitycontrol for gas burner is a proportional control. A linkless type gas burner facilitates ideal air-fuelratio and high combustion efficiency throughout its capacity control range. The air-fuel ratio canbe adjusted through the touch panel screen on the control panel; simply enter the required valveopening value, with no mechanical adjustment required.The gas burner must include the main and pilot gas shut off valve, the main and pilot gas governor,the high and low gas pressure switch, the low air pressure switch, a flame detector, a gas pressuregauge, and a gas strainer.

Control panelEach unit is furnished complete with a factory mounted and pre-wired control system. The controlpanel enclosure is equipped with a hinged access door with lock and key. The protection rating ofthe control panel is equivalent to IP42. All temperature sensors and other control devices necessaryto sense unit operating parameters are factory mounted and wired to panel. The control panelincludes a touch panel showing all system parameters in various languages with numeric data inimperial or metric units.The operating program is stored in nonvolatile memory (SRAM) to eliminate chiller-heater failuredue to AC power failure.Capacity Control - The control panel automatically controls the input gas flow rate to maintainthe programmed leaving chilled water setpoint for cooling loads. Capacity control range understandard condition is 20% to 100%. The input (gas) flow rate is manually adjustable from the controlpanel to any setting between minimum and maximum when automatic operation is not required.

15Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Page 18: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

YHAU control centerThe YHAU-CGN/H Control Center, furnished as standard on each chiller-heater, provides theultimate in efficiency, monitoring, data recording, chiller-heater protection, and operating ease. Thecontrol center is a factory-mounted, wired and tested state-of-the-art microprocessor based controlsystem for LiBr absorption chiller-heaters. The panel is configured with a color display with keysthat are integrated into the display. These are redefined with one keystroke based on the screendisplayed at that time. This revolutionary development makes chiller-heater operation quicker andeasier than ever before. A single button reveals a wide array of information on a large, full-colorillustration of the appropriate component. This makes information easier to interpret. This is allmounted in the middle of a keypad interface and installed in a locked enclosure.The LCD allows an animated graphic display of the chiller-heater, chiller-heater sub-systems andsystem parameters; this allows the presentation of several operating parameters at once. Inaddition, the operator can view a graphical representation of the historical operation of the chiller-heater and the present operation. A status bar is displayed at all times on all screens.Data is displayed in imperial or metric units plus keypad entry of setpoints to 0.1 increments.Security access is provided to prevent unauthorized changes to setpoints. This is accomplished withthree different levels of access and passwords for each level. There are certain screens, displayedvalues, programmable setpoints and manual controls not shown that are for servicing the chiller-heater. The following listing describes the various system screens and subscreens, and whatinformation they provide.

Main screenThe Main Screen displays equipment status (chiller-heater start/stop, operating, pumps ON/OFF,purge pump ON/OFF, and chilled/hot, and cooling water pumps ON/OFF). Also displayed is theoperating status of the various modes of chiller-heater operation.

Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater16

Page 19: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Data screenThe Data Screen displays values showing temperatures, operating hours, operating frequency, datatrends and a history of failures, alarms, and time based temperature trends.

Failure/alarm screenThis screen displays failure indications (time-outs, operation interlock, overcooled refrigerant, overand under temperatures, and problems with the unit's pumps) and system alarms.

17Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Page 20: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Setting screenThis screen displays control parameters (setting method, remote setting base and differential),valve operation (control valve mode auto/manual, pump operation, forced dilution, and purgemode auto/manual), language (Japanese, English, or Chinese) and date and time parameters.

Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater18

Page 21: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Options and AccessoriesOptional Tubes – Copper (C1200), CuNi(90/10), SUS436L, SUS316L, SUS304 and titanium optionsfor absorber-condenser, and evaporator tubing is available, however, the chiller-heater rating maychange with this option. Certified selection is issued by Johnson Controls' engineering department.Price additions for nonstandard tube materials and wall thickness is provided on a job specificbasis.Wet Shipment - The solution and refrigerant are charged at the factory and used for chillertesting. They are discharged and shipped in barrels with the chiller and charged again duringcommissioning. The chiller is charged with N2 to 4.4 psig on delivery.Long Term Storage - The solution and refrigerant water are stored in the barrels and shipped withthe chiller. The shell side of chiller is charged with N2 to 4.4 psig and the pressure gauge is marked.The tube side and water box are sealed and the pressure gauge is installed. The tube side of thechiller is then charged with the N2 to 2.9 psig and the pressure gauge is marked. The drying agentis then placed into the control panelCold Surface Insulation – Elastomeric foam insulation on cold surfaces is applied at the factory asan option.Isolation Pads – Four pads of 0.39 in. thick NBR isolation material are provided as an option.Pump Isolation Valves: An isolation valve for the solution pump and the refrigerant pump isavailable as an option.Chilled/Hot Water Pressure 300 psig – A chilled/hot water pressure 300 psig option is availablewith marine type waterbox.Cooling Water Pressure 300 psig – A cooling water pressure 300 psig option is available withmarine type waterbox.Cooling Water Pressure Differential Switch – The chilled/hot water pressure differential switch isincluded in the base unit. Pressure differential switches for the condenser water are provided as anoption when it is required.IP54 (Indoor Use) – Protection rating for control panel, electrical component and pumps isequivalent to IP54. Water-resistant flexible conduit is used for chiller-heater wiring. If the plantroom can get below 50°F, you must have the cold ambient option.Factory Performance Test Option Not 3rd Party Witnessed – Provides a full load performancetest and a signed report of capacity and performance.

Note: Full load single point test. Additional part load points or special testing requirements areaddressed by marketing on a project specific basis

Customer Witness Factory Test Option – Facilitates a customer witnessed factory performancetest of a given chiller-heater at design full load conditions. The time of the test is dictated by themanufacturing schedule and is confirmed by the factory.Solution Pump Variable Frequency (Inverter) – This frequency control unit for the solutioncirculation pump and solution spray pumps is available as an option. This unit controls thefrequency of solution pumps to improve part load efficiency of chiller-heater depending on hightemperature pressure, temperature, and concentration.Remote Interface Option – This option facilitates the use of 0-10 V remote signals to limit fuelusage.Junction Box for Separate Installation of Control Panel – A junction box is furnished when thecontrol panel is to be installed at a remote location away from the unit.CO Sensor - This option adds a carbon monoxide sensor to the chiller-heater.Natural Gas Inlet Pressure -The maximum acceptable pressure at the inlet of the gas train is 4.4psig. If the value is more than this, an optional high pressure gas train is required.

19Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Page 22: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Split Shipment – For tight rigging jobs, it is possible to ship the unit in two pieces – the uppersection (evaporator, absorber, condenser, low temperature generator, and high temperaturegenerator) and the lower section (solution heat exchangers and base frame). The solution andrefrigerant is shipped in barrels, along with the chiller, and is charged at the job site by JohnsonControls.High temperature hot water for heating - This design has one auxiliary heat exchanger toproduce the hot water when the heating mode is selected. This hot water is heated to more than140°F (60°C). The maximum temperature is 185°F (85°C). The pressure differential switch is optionalfor hot water.Simultaneous operation - This is equipped with an auxiliary hot water heat exchanger and itprovides both chilled water and hot water simultaneously. The unit operation during simultaneousoperation is initiated and controlled by the chilling load. This is similiar to the normal chillingoperation, with the difference being that during simultaneous operation, some of the vapourgenerated in the HTG is used to make hot water. As the unit operation is controlled by the chillingload, the amount of available heating capacity varies as the chilling load varies. The three-way valvecontrols the hot water outlet temperature. The three-way valve and the sensor are installed on theclient's hot water system. When the unit is in 'heating only' mode, and not simultaneous mode, thehot water three-way control valve must be in the open position to ensure full flow through the hotwater heat exchanger. The hot water controller then modulates the burner to meet load variations.

Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater20

Page 23: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Application DataThe following discussion is a guide in the application and installation of YHAU-CGN/H direct firedchiller-heaters to ensure the reliable, trouble free life that this equipment was designed for. Whilethis guide is directed towards normal water chilling applications, your local  Johnson Controls salesrepresentative can provide complete recommendations on other types of applications.

LocationYHAU-CGN/H units make relatively little noise or vibration when compared to a centrifugal orscrew chiller. The chiller-heater can be generally located at any level in a building where theconstruction supports the total system operating weight. The unit site must be a floor, mountingpad or foundation that is level and capable of supporting the operating weight of the YHAU-CGN/H chiller-heater. The YHAU-CGN/H unit operates properly and produce maximum output, if it isinstalled level within 1/1000 of the unit length in the lengthwise direction and 1/1000 of unit widthin the widthwise direction only.The system location must provide sufficient space around the unit to facilitate tube removal, ifrequired. If a door or other large opening is conveniently located opposite one end of the system,the tubes can be extracted and replaced through these openings. Allow sufficient clearance on theremaining sides of the unit for necessary access and maintenance. Do not put flammable materialsnear the unit.Absorption chiller-heaters are not suitable for outdoor installation. The machine room must beenclosed, with adequate lighting, and correctly ventilated to keep its temperature no higher than104°F, and no lower than 50°F .

Water circuitsFlow rate – For normal fluid chilling duty, evaporator and absorber/condenser flow rates of up to10.9 ft/s are facilitated in the heat exchanger tubes. Under variable chilled and hot fluid and coolingfluid flow conditions, special attention needs to be paid to the rate of change of the flow rate withtime and the minimum/maximum velocities through the tubes. Applications involving chilled andcooling fluid flow rates that vary by more than +10% from design require special consideration on acase by case basis.Water quality – The practical and economical application of liquid chiller-heaters requires thatthe quality of the water supply for the evaporator and the absorber/condenser be analyzed by awater treatment specialist. Water quality can affect the performance of any chiller-heater throughcorrosion, deposits of heat-resistant scale, sedimentation, or organic growth. These impact chiller-heater performance, and increase operating and maintenance costs. Normally, performance can bemaintained by corrective water treatment and periodic cleaning of tubes. If water conditions thatcannot be corrected by proper water treatment exist, it is necessary to provide a larger allowancefor fouling, or specify special material of construction.General water piping – All chilled/hot water and cooling water piping must be designed andinstalled in accordance with accepted piping practice. Chilled/hot water and cooling water pumpsmust be located to discharge through the YHAU-CGN/H unit to assure positive pressure andflow through the unit. Piping must include offsets to provide flexibility and must be arranged toprevent drainage of water from the evaporator, absorber, and condenser when the pumps are shutdown. Piping must be adequately supported and braced independent of the chiller-heater to avoidimposing strain on chiller-heater components. Hangers must faciliate the alignment of the pipe.Isolators in the piping and in the hangers are required to achieve sound and vibration control.Convenience considerations – With consideration given to facilitating the performance of routinemaintenance work, some or all of the following steps can be taken by the customer:

• Evaporator, absorber, and condenser waterboxes are equipped with plugged vent and drainconnections.

• If required vent and drain valves can be installed with or without piping to an open drain.

21Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Page 24: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

• Pressure gauges with stopcocks and stop valves, can be installed in the inlets and outlet of thecooling, chilled/hot water lines as close as possible to the chiller-heater.

• An overhead monorail or beam can be used to facilitate servicing.

Connections – The standard YHAU-CGN/H unit is designed for 150 psig design working pressureand water tested to 188 psig in both the chilled/hot and cooling water circuits. The connections(water nozzles) to these circuits are furnished in accordance with ANSI flanges. Piping must bearranged for ease of disassembly at the unit for performance of such routine maintenance as tubecleaning. All water piping must be thoroughly cleaned of all dirt and debris before final connectionsare made to the YHAU-CGN/H machine.Chilled and hot water – The chilled/hot water circuit uses a differential pressure switch asstandard. It is factory mounted in the water nozzle connection and wired to the chiller-heatercontrol panel. A water strainer with a 10 mesh must be field-installed in the chilled and hot waterinlet line as close as possible to the chiller-heater. If located close enough to the chiller-heater, thechilled/hot water pump can be protected by the same strainer. The flow switch and strainer ensurechilled and hot water flow during unit operation. The loss or severe reduction of water flow couldseriously impair the YHAU-CGN/H unit performance or even result in tube freeze-up.Cooling water – Like the chilled/hot water circuit, the cooling water circuit requires a means ofproving flow. Low flow protection is provided by an optional differential pressure switch mountedin the water nozzle connection and wired to the chiller-heater control panel.The YHAU-CGN/H chiller-heater is engineered for maximum efficiency at both design and partload operation by taking advantage of the colder cooling tower water temperatures, whichnaturally occur in the winter months. In its standard configuration, YHAU-CGN/H absorbers cantolerate entering cooling water temperatures as low as 68°F. Because the unit flow rates must bemaintained, the suggested method of tower water temperature control is a three way mixing valve.

Sound and vibration considerationsAs the YHAU-CGN/H unit generates relatively little vibration when compared to a centrifugal orscrew chiller-heater, vibration eliminating mounts are not usually required. However, when themachine is installed where even mild noise is a problem, mounts or pads must be used. The use ofanchoring bolts on the machine legs is suggested. See Sound Data.

Thermal insulationYHAU-CGN/H units require thermal insulation (by others) on both the hot and cold surfaces inorder to achieve maximum efficiency and prevent sweating.

Electrical dataTotal kW includes power requirements for the system solution and refrigerant pumps. All modelshave one solution pump, one solution spray pump and one refrigerant pump. See Electrical Data -CG/AN.

Natural gas inlet pressureThe maximum acceptable pressure at the inlet of the gas train is 4.4 psig. If the value is more thanthis, a special gas train is required.

Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater22

Page 25: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Typical operational rangeThe numbers shown in the following table are the ranges for each parameter. Not all combinationsare possible. Check with your Johnson Controls Service Center to see if your temperaturedifferential is possible.

Parameter Allowable rangesChilled Water In 44.6°F to 77°FChilled Water Out 39.2°F to 60.8°FCooling Water In 68°F to 98.6°FCooling Water Out 77°F to 107.6°F

120 RT to 300 RT: 0.3 psig to 36.2 psigNatural Gas Inlet Pressure

360 RT to 1600 RT: 1.5 psig to 36.2 psig

23Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Page 26: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

WeightsTable 1: Standard efficiency

Weights - CGN Weights - CGHYHAU Maximum

shipping lb (ton)Operating lb (ton)

Emergency (filledwith water) lb (ton)

Maximumshipping lb (ton)

Operating lb (ton)Emergency (filled

with water) lb (ton)

120EXS 14,330 (6.5) 17,857 (8.1) 25,133 (11.4)

150EXS 14,330 (6.5) 17,857 (8.1) 25,133 (11.4)

180EXS 17,196 (7.8) 21,385 (9.7) 30,644 (13.9)

240EXS 19,401 (8.8) 24,471 (11.1) 36,156 (16.4)

300EXS 21,826 (9.9) 27,999 (12.7) 42,329 (19.2)

360EXS 22,574 (11.6) 32,849 (14.9) 55,556 (25.2)

400EXS 22,574 (11.6) 32,849 (14.9) 55,556 (25.2)

450EXS 26,455 (12) 35,715 (16.2) 57,541 (26.1) 28,881 (13.1) 38,140 (17.3) 61,068 (27.7)500EXS 30,644 (13.9) 40,345 (18.3) 63,273 (28.7) 32,408 (14.7) 42,108 (19.1) 66,139 (30)560EXS 33,951 (15.4) 44,974 (20.4) 72,312 (32.8) 35,715 (16.2) 46,738 (21.2) 75,619 (34.3)600EXS 37,699 (17.1) 50,265 (22.8) 80,028 (36.3) 38,360 (17.4) 50,927 (23.1) 82,012 (37.2)700EXS 41,667 (18.9) 55,556 (25.2) 89,728 (40.7) 42,329 (19.2) 56,218 (25.5) 92,153 (41.8)800EXS 45,636 (20.7) 61,289 (27.8) 102,294 (46.4) 52,470 (23.8) 68,123 (30.9) 107,806 (48.9)

900EXWS 53,572 (24.3) 70,548 (32) 107,806 (48.9) 56,879 (25.8) 73,855 (33.5) 113,097 (51.3)1000EXWS 62,832 (28.5) 82,673 (37.5) 123,679 (56.1) 66,359 (30.1) 86,201 (39.1) 129,191 (58.6)1100EXWS 67,021 (30.4) 89,067 (40.4) 132,498 (60.1) 72,753 (33) 94,799 (43) 140,434 (63.7)

1200EXW3S 70,768 (32.1) 95,681 (43.4) 154,103 (69.9) 76,500 (34.7) 101,413 (46) 162,701 (73.8)1300EXW3S 77,603 (35.2) 103,838 (47.1) 166,229 (75.4) 85,098 (38.6) 111,333 (50.5) 176,811 (80.2)1400EXW3S 82,673 (37.5) 109,790 (49.8) 175,929 (79.8) 90,169 (40.9) 117,286 (53.2) 186,732 (84.7)1500EXW3S 95,019 (43.1) 121,695 (55.2) 192,023 (87.1) 97,665 (44.3) 125,223 (56.8) 199,077 (90.3)1600EXW3S 97,885 (44.4) 125,002 (56.7) 199,298 (90.4) 100,531 (45.6) 128,529 (58.3) 206,573 (93.7)

Table 2: High efficiencyWeights - CGN Weights - CGH

YHAU Maximumshipping lb (ton)

Operating lb (ton)Emergency (filled

with water) lb (ton)Maximum

shipping lb (ton)Operating lb (ton)

Emergency (filledwith water) lb (ton)

120EXH 15,432 (7) 18,960 (8.6) 26,235 (11.9)

150EXH 15,432 (7) 18,960 (8.6) 26,235 (11.9)

180EXH 18,078 (8.2) 22,487 (10.2) 31,747 (14.4)

240EXH 20,062 (9.1) 25,574 (11.6) 37,258 (16.9)

300EXH 22,928 (10.4) 29,101 (13.2) 43,431 (19.7)

360EXH 26,445 (12.0) 34,392 (15.6) 57,100 (25.9)

400EXH 26,445 (12.0) 34,392 (15.6) 57,100 (25.9)

450EXH 27,778 (12.6) 37,258 (16.9) 59,084 (26.8) 30,203 (13.7) 39,683 (18) 62,611 (28.4)500EXH 31,526 (14.3) 42,108 (19.1) 65,036 (29.5) 33,290 (15.1) 43,872 (19.9) 67,902 (30.8)560EXH 35,494 (16.1) 46,958 (21.3) 74,296 (33.7) 37,258 (16.9) 48,722 (22.1) 77,603 (35.2)600EXH 37,478 (17.0) 52,470 (23.8) 82,232 (37.3) 40,565 (18.4) 53,131 (24.1) 84,437 (38.3)700EXH 43,211 (19.6) 58,202 (26.4) 92,374 (41.9) 43,872 (19.9) 58,863 (26.7) 94,799 (43)800EXH 47,840 (21.7) 64,375 (29.2) 102,294 (46.4) 54,675 (24.8) 71,209 (32.3) 110,893 (50.3)

900EXWH 55,556 (25.2) 74,075 (33.6) 111,333 (50.5) 58,863 (26.7) 77,382 (35.1) 116,625 (52.9)1000EXWH 65,698 (29.8) 87,083 (39.5) 128,089 (58.1) 69,225 (31.4) 90,610 (41.1) 133,600 (60.6)1100EXWH 68,343 (31) 93,476 (42.4) 136,907 (62.1) 74,075 (33.6) 99,208 (45) 144,844 (65.7)

1200EXW3H 73,855 (33.5) 100,090 (45.4) 158,512 (71.9) 79,587 (36.1) 105,822 (48) 167,110 (75.8)1300EXW3H 80,469 (36.5) 108,247 (49.1) 170,638 (77.4) 87,964 (39.9) 115,743 (52.5) 181,220 (82.2)1400EXW3H 85,098 (38.6) 114,199 (51.8) 180,338 (81.8) 96,562 (43.8) 121,695 (55.2) 191,141 (86.7)1500EXW3H 98,988 (44.9) 125,663 (57) 195,991 (88.9) 101,633 (46.1) 129,191 (58.6) 203,046 (92.1)1600EXW3H 101,854 (46.2) 128,970 (58.5) 203,266 (92.2) 104,499 (47.4) 132,498 (60.1) 210,541 (95.5)

Note: Data contained in table are approximates.

Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater24

Page 27: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Physical DataTable 3: Physical data (with exhaust gas temperature approximately (428°F (220°C))

Outline dimension Holding volume

YHAU-CGNExhaust

gas volumeft3/ h (m3/h)

Lengthft (m)

Widthft (m)

Heightft (m)

Tube extractingspaceft (m)

Hot insulationarea

ft2 (m2)

Cold insulationarea

ft2 (m2)Chilled/hot water

ft3 (m3)

Coolingwater

ft3 (m3)120EX(H/S) 46.79 (1.33) 10.5 (3.2) 7.22 (2.2) 8.2 (2.5) 6.56 (2) 182.99 (17) 86.11 (8) 7.42 (0.21) 11.3 (0.32)150EX(H/S) 46.79 (1.33) 10.5 (3.2) 7.22 (2.2) 8.2 (2.5) 6.56 (2) 182.99 (17) 86.11 (8) 7.42 (0.21) 11.3 (0.32)180EX(H/S) 60.28 (1.71) 11.81 (3.6) 7.22 (2.2) 8.2 (2.5) 8.37 (2.55) 193.75 (18) 107.64 (10) 8.83 (0.25) 13.42 (0.38)240EX(H/S) 72.89 (2.06) 14.11 (4.3) 7.22 (2.2) 8.2 (2.5) 10.5 (3.2) 236.81 (22) 129.17 (12) 10.59 (0.3) 15.89 (0.45)300EX(H/S) 93.58 (2.65) 15.42 (4.7) 7.22 (2.2) 8.2 (2.5) 13.12 (4) 279.86 (26) 150.69 (14) 12.71 (0.36) 19.07 (0.54)360EX(H/S) 120.81 (3.42) 19.46 (5.93) 7.41 (2.26) 8.2 (2.5) 16.4 (5) 355.21 (33) 150.69 (14) 16.24 (0.46) 28.6 (0.81)400EX(H/S) 120.81 (3.42) 19.46 (5.93) 7.41 (2.26) 8.2 (2.5) 16.4 (5) 355.21 (33) 150.69 (14) 16.24 (0.46) 28.6 (0.81)450EX(H/S) 120.81 (3.42) 16.7 (5.09) 7.28 (2.22) 10.18 (3.1) 13.12 (4) 355.21 (33) 150.69 (14) 19.42 (0.55) 41.32 (1.17)500EX(H/S) 120.81 (3.42) 18.34 (5.59) 7.84 (2.39) 10.18 (3.1) 14.76 (4.5) 387.5 (36) 172.22 (16) 21.19 (0.6) 44.14 (1.25)560EX(H/S) 150.97 (4.28) 19.98 (6.09) 7.84 (2.39) 10.18 (3.1) 16.4 (5) 419.79 (39) 182.99 (17) 22.95 (0.65) 49.09 (1.39)600EX(H/S) 181.2 (5.13) 21.62 (6.59) 8.27 (2.52) 10.18 (3.1) 18.04 (5.5) 430.56 (40) 204.51 (19) 25.07 (0.71) 52.27 (1.48)700EX(H/S) 181.2 (5.13) 24.25 (7.39) 8.73 (2.66) 10.18 (3.1) 20.67 (6.3) 441.32 (41) 215.28 (20) 27.9 (0.79) 56.86 (1.61)800EX(H/S) 211.89 (6) 26.54 (8.09) 8.89 (2.71) 10.18 (3.1) 22.97 (7) 495.14 (46) 247.57 (23) 31.08 (0.88) 66.39 (1.88)

900EXW(H/S) 252.22 (7.14) 22.31 (6.8) 10.16 (3.1) 10.33 (3.15) 18.7 (5.7) 570.49 (53) 279.86 (26) 34.96 (0.99) 72.04 (2.04)1000EXW(H/S) 252.22 (7.14) 24.43 (7.45) 10.16 (3.1) 10.33 (3.15) 20.67 (6.3) 602.78 (56) 376.74 (35) 49.44 (1.4) 94.29 (2.67)1100EXW(H/S) 304.73 (8.63) 26.56 (8.1) 10.16 (3.1) 10.33 (3.15) 22.97 (7) 678.13 (63) 409.03 (38) 53.68 (1.52) 105.94 (3)

1200EXW3(H/S) 304.73 (8.63) 26.89 (8.2) 10.5 (3.2) 10.83 (3.3) 22.97 (7) 721.18 (67) 462.85 (43) 59.33 (1.68) 115.83 (3.28)1300EXW3(H/S) 352.09 (9.97) 28.53 (8.7) 10.5 (3.2) 10.83 (3.3) 24.61 (7.5) 828.82 (77) 495.14 (46) 63.57 (1.8) 120.07 (3.4)1400EXW3(H/S) 352.09 (9.97) 30.17 (9.2) 10.5 (3.2) 10.83 (3.3) 26.25 (8) 871.88 (81) 516.67 (48) 66.74 (1.89) 125.37 (3.55)1500EXW3(H/S) 401.77 (11.38) 31.98 (9.75) 11.81 (3.6) 10.33 (3.46) 27.89 (8.5) 979.52 (91) 548.96 (51) 70.28 (1.99) 130.66 (3.7)1600EXW3(H/S) 401.77 (11.38) 33.62 (10.25) 11.81 (3.6) 10.33 (3.46) 29.53 (9) 1022.57 (95) 570.49 (53) 73.45 (2.08) 135.96 (3.85)

Table 4: Physical data (with exhaust gas temperature approximately (428°F (220°C))Outline dimension Holding volume

YHAU - CGHExhaust

gas volumeft3/h (m3/h)

Lengthft (m)

Widthft (m)

Heightft (m)

Tube extractingspaceft (m)

Hot insulationarea

ft2 (m2)

Cold insulationarea

ft2 (m2)Chilled/hot water

ft3 (m3)

Coolingwater

ft3 (m3)

120EX(H/S)

150EX(H/S)

180EX(H/S)

240EX(H/S)

300EX(H/S)

360EX(H/S)

400EX(H/S)

450EX(H/S) 150.97 (4.28) 16.7 (5.09) 9.45 (2.88) 10.18 (3.1) 13.12 (4) 387.5 (36) 150.69 (14) 19.42 (0.55) 41.32 (1.17)500EX(H/S) 181.2 (5.13) 18.34 (5.59) 9.78 (2.98) 10.18 (3.1) 14.76 (4.5) 430.56 (40) 172.22 (16) 21.19 (0.6) 41.32 (1.25)560EX(H/S) 181.2 (5.13) 181.2 (6.09) 9.78 (2.98) 10.18 (3.1) 16.4 (5) 462.85 (43) 182.99 (17) 22.95 (0.65) 49.09 (1.39)600EX(H/S) 211.89 (6) 21.62 (6.59) 9.78 (2.98) 10.18 (3.1) 18.04 (5.5) 462.85 (43) 204.51 (19) 25.07 (0.71) 52.27 (1.48)700EX(H/S) 252.22 (7.14) 24.25 (7.39) 9.78 (2.98) 10.18 (3.1) 20.67 (6.3) 473.61 (44) 215.28 (20) 27.9 (0.79) 56.86 (1.61)800EX(H/S) 252.22 (7.14) 26.54 (8.09) 10.73 (3.27) 10.18 (3.1) 22.97 (7) 559.72 (52) 247.57 (23) 31.08 (0.88) 66.39 (1.88)

900EXW(H/S) 304.73 (8.63) 22.31 (6.8) 10.73 (3.27) 10.33 (3.15) 18.7 (5.7) 635.07 (59) 279.86 (26) 34.96 (0.99) 72.04 (2.04)1000EXW(H/S) 304.73 (8.63) 24.43 (7.45) 10.83 (3.3) 10.33 (3.15) 20.67 (6.3) 667.36 (62) 376.74 (35) 49.44 (1.4) 94.29 (2.67)1100EXW(H/S) 352.09 (9.97) 26.56 (8.1) 10.83 (3.3) 10.33 (3.15) 22.97 (7) 742.71 (69) 409.03 (38) 53.68 (1.52) 105.94 (3)

1200EXW3(H/S) 352.09 (9.97) 26.89 (8.2) 10.83 (3.3) 10.83 (3.3) 22.97 (7) 785.77 (73) 462.85 (43) 59.33 (1.68) 115.83 (3.28)1300EXW3(H/S) 401.77 (11.38) 28.53 (8.7) 11.81 (3.6) 11.65 (3.55) 24.61 (7.5) 904.17 (84) 495.14 (46) 63.57 (1.8) 120.07 (3.4)1400EXW3(H/S) 401.77 (11.38) 30.17 (9.2) 11.81 (3.6) 11.65 (3.55) 26.25 (8) 947.22 (88) 516.67 (48) 66.74 (1.89) 125.37 (3.55)1500EXW3(H/S) 446.41 (12.64) 31.98 (9.75) 11.81 (3.6) 11.65 (3.55) 27.89 (8.5) 1033.34 (96) 548.96 (51) 70.28 (1.99) 130.66 (3.7)

1600EXW3(H/S) 446.41 (12.64)33.62

(10.25)11.81 (3.6) 11.65 (3.55) 29.53 (9) 1076.39 (100) 570.49 (53) 73.45 (2.08) 135.96 (3.85)

25Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Page 28: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Load Points for EX and EXW Units - High EfficiencyTable 5: Load points for high efficiency

YHAU-CGNLoad point 1

lb (ton)Load point 2

lb (ton)Load point 3

lb (ton)Load point 4

lb (ton)120EXH 5,247 (2.38) 4,299 (1.95) 6,460 (2.93) 3,285 (1.49)150EXH 5,247 (2.38) 4,299 (1.95) 6,460 (2.93) 3,285 (1.49)180EXH 6,305 (2.86) 5,004 (2.27) 7,518 (3.41) 3,990 (1.81)240EXH 6,504 (2.95) 5,820 (2.64) 8,730 (3.96) 4,409 (2)300EXH 8,179 (3.71) 6,592 (2.99) 9,877 (4.48) 5,049 (2.29)360EXH 10,009 (4.54) 7,738 (3.51) 11,618 (5.27) 6,019 (2.73)400EXH 10,009 (4.54) 7,738 (3.51) 11,618 (5.27) 6,019 (2.73)450EXH 12,236 (5.55) 8,841 (4.01) 13,250 (6.01) 7,033 (3.19)500EXH 13,536 (6.14) 8,730 (3.96) 13,117 (5.95) 8,818 (4)560EXH 15,498 (7.03) 10,362 (4.7) 15,565 (7.06) 9,127 (4.14)600EXH 16,645 (7.55) 10,759 (4.88) 16,116 (7.31) 10,494 (4.76)700EXH 17,902 (8.12) 12,059 (5.47) 18,078 (8.2) 11,486 (5.21)800EXH 22,355 (10.14) 13,977 (6.34) 20,966 (9.51) 14,506 (6.58)

900EXWH 24,692 (11.2) 14,506 (6.58) 21,760 (9.87) 16,446 (7.46)1000EXWH 28,660 (13) 17,218 (7.81) 25,794 (11.7) 19,026 (8.63)1100EXWH 30,424 (13.8) 19,952 (9.05) 29,983 (13.6) 19,731 (8.95)

1200EXW3H 29,983 (13.6) 21,980 (9.97) 33,069 (15) 20,349 (9.23)1300EXW3H 32,849 (14.9) 22,708 (10.3) 34,172 (15.5) 23,589 (10.7)1400EXW3H 34,613 (15.7) 24,030 (10.9) 35,935 (16.3) 24,692 (11.2)1500EXW3H 36,817 (16.7) 24,030 (10.9) 36,156 (16.4) 27,558 (12.5)1600EXW3H 37,919 (17.2) 23,369 (10.6) 35,053 (15.9) 29,762 (13.5)

Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater26

Page 29: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Load Points for EX and EXW Units - StandardEfficiencyTable 6: Load points for high efficiency

YHAU-CGHLoad point 1

lb (ton)Load point 2

lb (ton)Load point 3

lb (ton)Load point 4

lb (ton)

120EXH

150EXH

180EXH

240EXH

300EXH

360EXH

400EXH

450EXH 28,660 (13) 17,218 (7.81) 25,794 (11.7) 19,026 (8.63)500EXH 30,424 (13.8) 19,952 (9.05) 29,983 (13.6) 19,731 (8.95)560EXH 29,983 (13.6) 21,980 (9.97) 33,069 (15) 20,349 (9.23)600EXH 32,849 (14.9) 22,708 (10.3) 34,172 (15.5) 23,589 (10.7)700EXH 34,613 (15.7) 24,030 (10.9) 35,935 (16.3) 24,692 (11.2)800EXH 36,817 (16.7) 24,030 (10.9) 36,156 (16.4) 27,558 (12.5)

900EXWH 37,919 (17.2) 23,369 (10.6) 35,053 (15.9) 29,762 (13.5)1000EXWH 28,660 (13) 17,218 (7.81) 25,794 (11.7) 19,026 (8.63)1100EXWH 30,424 (13.8) 19,952 (9.05) 29,983 (13.6) 19,731 (8.95)

1200EXW3H 29,983 (13.6) 21,980 (9.97) 33,069 (15) 20,349 (9.23)1300EXW3H 32,849 (14.9) 22,708 (10.3) 34,172 (15.5) 23,589 (10.7)1400EXW3H 34,613 (15.7) 24,030 (10.9) 35,935 (16.3) 24,692 (11.2)1500EXW3H 36,817 (16.7) 24,030 (10.9) 36,156 (16.4) 27,558 (12.5)1600EXW3H 37,919 (17.2) 23,369 (10.6) 35,053 (15.9) 29,762 (13.5)

Table 7: Load points for standard efficiency

YHAU-CGNLoad point 1

lb (ton)Load point 2

lb (ton)Load point 3

lb (ton)Load point 4

lb (ton)120EXS 4,960 (2.25) 4,057 (1.84) 6,085 (2.76) 3,086 (1.4)150EXS 4,960 (2.25) 4,057 (1.84) 6,085 (2.76) 3,086 (1.4)180EXS 5,997 (2.72) 4,762 (2.16) 7,143 (3.24) 3,792 (1.72)240EXS 6,217 (2.82) 5,578 (2.53) 8,356 (3.79) 4,211 (1.91)300EXS 7,870 (3.57) 6,349 (2.88) 9,502 (4.31) 4,850 (2.2)360EXS 9,568 (4.34) 7,385 (3.35) 11,089 (5.03) 5,754 (2.61)400EXS 9,568 (4.34) 7,385 (3.35) 11,089 (5.03) 5,754 (2.61)450EXS 11,001 (4.99) 7,959 (3.61) 11,927 (5.41) 6,327 (2.87)500EXS 12,456 (5.65) 8,025 (3.64) 12,059 (5.47) 8,113 (3.68)560EXS 14,308 (6.49) 9,568 (4.34) 14,352 (6.51) 8,422 (3.82)600EXS 15,741 (7.14) 10,163 (4.61) 15,256 (6.92) 9,943 (4.51)700EXS 16,909 (7.67) 11,376 (5.16) 17,064 (7.74) 10,847 (4.92)800EXS 19,246 (8.73) 12,015 (5.45) 18,034 (8.18) 12,500 (5.67)

900EXWS 22,487 (10.2) 13,228 (6) 19,842 (9) 14,991 (6.8)1000EXWS 26,015 (11.8) 15,719 (7.13) 23,589 (10.7) 17,350 (7.87)1100EXWS 27,337 (12.4) 17,924 (8.13) 26,896 (12.2) 17,703 (8.03)

1200EXW3S 27,117 (12.3) 19,864 (9.01) 29,762 (13.5) 18,409 (8.35)1300EXW3S 29,542 (13.4) 20,371 (9.24) 30,644 (13.9) 21,164 (9.6)1400EXW3S 31,306 (14.2) 21,627 (9.81) 32,408 (14.7) 22,267 (10.1)1500EXW3S 34,833 (15.8) 22,708 (10.3) 34,172 (15.5) 26,015 (11.8)1600EXW3S 35,715 (16.2) 22,024 (9.99) 33,069 (15) 27,999 (12.7)

Table 8: Load points for standard efficiency

YHAU-CGHLoad point 1

lb (ton)Load point 2

lb (ton)Load point 3

lb (ton)Load point 4

lb (ton)120EXS 11,751 (5.33) 8,488 (3.85) 12,743 (5.78) 6,768 (3.07)150EXS 13,007 (5.9) 8,378 (3.8) 12,588 (5.71) 8,466 (3.84)180EXS 14,859 (6.74) 9,943 (4.51) 14,925 (6.77) 8,752 (3.97)240EXS 15,961 (7.24) 10,296 (4.67) 15,454 (7.01) 10,075 (4.57)

27Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Page 30: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Table 8: Load points for standard efficiency

YHAU-CGHLoad point 1

lb (ton)Load point 2

lb (ton)Load point 3

lb (ton)Load point 4

lb (ton)300EXS 17,108 (7.76) 11,508 (5.22) 17,262 (7.83) 10,979 (4.98)360EXS 21,385 (9.7) 13,360 (6.06) 20,040 (9.09) 13,889 (6.3)400EXS 21,385 (9.7) 13,360 (6.06) 20,040 (9.09) 13,889 (6.3)450EXS 27,117 (12.3) 16,380 (7.43) 24,471 (11.1) 18,100 (8.21)500EXS 29,101 (13.2) 19,070 (8.65) 28,660 (13) 18,850 (8.55)560EXS 28,660 (13) 21,054 (9.55) 31,526 (14.3) 19,511 (8.85)600EXS 31,526 (14.3) 21,848 (9.91) 32,849 (14.9) 22,686 (10.29)700EXS 33,290 (15.1) 23,104 (10.48) 34,613 (15.7) 23,810 (10.8)800EXS 35,715 (16.2) 23,369 (10.6) 35,053 (15.9) 26,676 (12.1)

900EXWS 36,817 (16.7) 22,641 (10.27) 33,951 (15.4) 28,660 (13)1000EXWS 27,117 (12.3) 16,380 (7.43) 24,471 (11.1) 18,100 (8.21)1100EXWS 29,101 (13.2) 19,070 (8.65) 28,660 (13) 18,850 (8.55)

1200EXW3S 28,660 (13) 21,054 (9.55) 31,526 (14.3) 19,511 (8.85)1300EXW3S 31,526 (14.3) 21,848 (9.91) 32,849 (14.9) 22,686 (10.29)1400EXW3S 33,290 (15.1) 23,104 (10.48) 34,613 (15.7) 23,810 (10.8)1500EXW3S 35,715 (16.2) 23,369 (10.6) 35,053 (15.9) 26,676 (12.1)1600EXW3S 36,817 (16.7) 22,641 (10.27) 33,951 (15.4) 28,660 (13)

Figure 3: Load point views for EX and EXW models

Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater28

Page 31: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Split Shipment - High Efficiency - CGNTable 9: Split shipment - high efficiency

Double effect direct fired absorption chillerMain shell unit HX unit HG unit

YHAU-CGN Lengthft (m)

Widthft (m)

Heightft (m)

Weightlb (ton)

Lengthft (m)

Widthft (m)

Heightft (m)

Weightlb (ton)

Lengthft (m)

Widthft (m)

Heightft (m)

Weightlb (ton)

120EXH

150EXH 8.53 (2.6) 6.56 (2) 7.55 (2.3) 8,819 (4) 8.53 (2.6) 4.92 (1.5) 3.94 (1.2) 2,205 (1) 9.19 (2.8) 3.28 (1) 4.92 (1.5) 3,307 (1.5)180EXH 10.5 (3.2) 6.56 (2) 7.55 (2.3) 9,921 (4.5) 10.5 (3.2) 4.92 (1.5) 3.94 (1.2) 2,205 (1) 10.17 (3.1) 3.28 (1) 4.92 (1.5) 3,307 (1.5)240EXH 12.47 (3.8) 6.56 (2) 7.55 (2.3) 10,362 (4.7) 11.15 (3.4) 4.92 (1.5) 3.61 (1.1) 3,086 (1.4) 11.81 (3.6) 3.28 (1) 4.92 (1.5) 3,968 (1.8)300EXH 15.42 (4.7) 6.56 (2) 7.55 (2.3) 12,787 (5.8) 13.78 (4.2) 4.92 (1.5) 3.61 (1.1) 3,968 (1.8) 13.12 (4) 3.28 (1) 4.92 (1.5) 4,850 (2.2)360EXH 19.03 (5.8) 6.56 (2) 7.55 (2.3) 14,991 (6.8) 18.7 (5.7) 4.92 (1.5) 3.61 (1.1) 5,952 (2.7) 16.73 (5.1) 3.28 (1) 6.56 (2) 5,732 (2.6)400EXH 19.03 (5.8) 6.56 (2) 7.55 (2.3) 14,991 (6.8) 18.7 (5.7) 4.92 (1.5) 3.61 (1.1) 5,952 (2.7) 16.73 (5.1) 3.28 (1) 6.56 (2) 5,732 (2.6)450EXH 16.08 (4.9) 7.55 (2.3) 9.19 (2.8) 21,605 (9.8) 15.42 (4.7) 5.25 (1.6) 3.61 (1.1) 5,071 (2.3) 15.42 (4.7) 3.28 (1) 6.56 (2) 5,953 (2.7)500EXH 17.72 (5.4) 7.55 (2.3) 9.19 (2.8) 22,046 (10) 17.06 (5.2) 5.25 (1.6) 3.61 (1.1) 5,512 (2.5) 15.75 (4.8) 4.59 (1.4) 6.56 (2) 7,496 (3.4)560EXH 19.36 (5.9) 7.55 (2.3) 9.19 (2.8) 24,471 (11.1) 18.7 (5.7) 5.25 (1.6) 3.61 (1.1) 5,953 (2.7) 16.73 (5.1) 4.59 (1.4) 6.56 (2) 7,716 (3.5)600EXH 21 (6.4) 8.2 (2.5) 9.19 (2.8) 26,896 (12.2) 20.34 (6.2) 5.25 (1.6) 3.61 (1.1) 6,393 (2.9) 17.06 (5.2) 4.59 (1.4) 6.56 (2) 8,598 (3.9)700EXH 23.62 (7.2) 8.2 (2.5) 9.19 (2.8) 32,628 (14.8) 22.97 (7) 5.25 (1.6) 3.61 (1.1) 7,055 (3.2) 19.36 (5.9) 4.59 (1.4) 6.56 (2) 8,819 (4)800EXH 25.92 (7.9) 8.2 (2.5) 9.19 (2.8) 38,801 (17.6) 25.26 (7.7) 5.25 (1.6) 3.61 (1.1) 7,716 (3.5) 21.65 (6.6) 4.59 (1.4) 6.56 (2) 9,921 (4.5)

900EXWH 23.95 (7.3) 8.53 (2.6) 9.19 (2.8) 45,415 (20.6) 21.98 (6.7) 5.91 (1.8) 3.61 (1.1) 6,834 (3.1) 19.36 (5.9) 5.58 (1.7) 9.19 (2.8) 12,787 (5.8)1000EXWH 26.25 (8) 8.53 (2.6) 9.19 (2.8) 49,163 (22.3) 23.95 (7.3) 5.91 (1.8) 3.61 (1.1) 7,275 (3.3) 19.36 (5.9) 5.58 (1.7) 9.19 (2.8) 12,787 (5.8)1100EXWH 28.54 (8.7) 8.53 (2.6) 9.19 (2.8) 54,675 (24.8) 26.25 (8) 5.91 (1.8) 3.61 (1.1) 7,937 (3.6) 21.33 (6.5) 5.58 (1.7) 9.19 (2.8) 14,991 (6.8)

1200EXW3H 29.53 (9) 8.53 (2.6) 9.51 (2.9) 57,100 (25.9) 26.25 (8) 5.91 (1.8) 3.61 (1.1) 7,937 (3.6) 21.33 (6.5) 5.58 (1.7) 9.19 (2.8) 14,991 (6.8)1300EXW3H 31.17 (9.5) 8.53 (2.6) 10.5 (3.2) 61,068 (27.7) 27.89 (8.5) 5.91 (1.8) 3.61 (1.1) 8,378 (3.8) 22.31 (6.8) 5.58 (1.7) 9.19 (2.8) 15,432 (7)1400EXW3H 32.81 (10) 8.53 (2.6) 10.5 (3.2) 65,036 (29.5) 29.53 (9) 5.91 (1.8) 3.61 (1.1) 10,582 (4.8) 22.31 (6.8) 5.58 (1.7) 9.19 (2.8) 15,432 (7)

1500EXW3H 34.45 (10.5) 8.53 (2.6) 10.5 (3.2) 69,005 (31.3) 31.17 (9.5) 5.91 (1.8) 3.61 (1.1) 13,228 (6) 23.62 (7.2) 6.56 (2) 10.5 (3.2)23,149(10.5)

1600EXW3H 36.09 (11) 8.53 (2.6) 10.5 (3.2) 72,973 (33.1) 32.81 (10) 5.91 (1.8) 3.61 (1.1) 13,889 (6.3) 23.62 (7.2) 6.56 (2) 10.5 (3.2)23,149(10.5)

29Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Page 32: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Split Shipment - High Efficiency - CGHTable 10: Split shipment - high efficiency

Double effect direct fired absorption chillerMain shell unit HX unit HG unit

YHAU-CGH Lengthft (m)

Widthft (m)

Heightft (m)

Weightlb (ton)

Lengthft (m)

Widthft (m)

Heightft (m)

Weightlb (ton)

Lengthft (m)

Widthft (m)

Heightft (m)

Weightlb (ton)

120EXH

150EXH

180EXH

240EXH

300EXH

360EXH

400EXH

450EXH 16.08 (4.9) 7.55 (2.3) 9.19 (2.8) 21,506 (9.8) 15.42 (4.7) 5.25 (1.6) 3.61 (1.1) 5,071 (2.3) 15.42 (4.7) 4.59 (1.4) 6.56 (2) 7,496 (3.4)500EXH 17.72 (5.4) 7.55 (2.3) 9.19 (2.8) 22,046 (10) 17.06 (5.2) 5.25 (1.6) 3.61 (1.1) 5,512 (2.5) 15.75 (4.8) 4.59 (1.4) 6.56 (2) 8,598 (3.9)

560EXH 19.36 (5.9) 7.55 (2.3) 9.19 (2.8)24,471(11.1)

18.7 (5.7) 5.25 (1.6) 3.61 (1.1) 5,953 (2.7) 16.73 (5.1) 4.59 (1.4) 6.56 (2) 8,598 (3.9)

600EXH 21 (6.4) 8.2 (2.5) 9.19 (2.8)26,896(12.2)

20.34 (6.2) 5.25 (1.6) 3.61 (1.1) 6,393 (2.9) 17.06 (5.2) 4.59 (1.4) 6.56 (2) 9,921 (4.5)

700EXH 23.62 (7.2) 8.2 (2.5) 9.19 (2.8)32,628(14.8)

22.97 (7) 5.25 (1.6) 3.61 (1.1) 7,055 (3.2) 19.36 (5.9) 4.59 (1.4) 6.56 (2) 9,921 (4.5)

800EXH 25.92 (7.9) 8.2 (2.5) 9.19 (2.8)38,801(17.6)

25.26 (7.7) 5.25 (1.6) 3.61 (1.1) 7,716 (3.5) 21.65 (6.6) 5.58 (1.7) 9.19 (2.8) 15,432 (7)

900EXWH 23.95 (7.3) 8.53 (2.6) 9.19 (2.8)45,415(20.6)

21.98 (6.7) 5.91 (1.8) 3.61 (1.1) 6,834 (3.1) 19.36 (5.9) 5.58 (1.7) 9.19 (2.8) 14,991 (6.8)

1000EXWH 26.25 (8) 8.53 (2.6) 9.19 (2.8)49,163(22.3)

23.95 (7.3) 5.91 (1.8) 3.61 (1.1) 7,276 (3.3) 19.36 (5.9) 5.58 (1.7) 9.19 (2.8) 14,991 (6.8)

1100EXWH 28.54 (8.7) 8.53 (2.6) 9.19 (2.8)54,675(24.8)

26.25 (8) 5.91 (1.8) 3.61 (1.1) 7,937 (3.6) 21.33 (6.5) 5.58 (1.7) 9.19 (2.8) 15,432 (7)

1200EXW3H 29.53 (9) 8.53 (2.6) 9.51 (2.9)57,100(25.9)

26.25 (8) 5.91 (1.8) 3.61 (1.1) 7,937 (3.6) 21.33 (6.5) 5.58 (1.7) 9.19 (2.8) 15,432 (7)

1300EXW3H 31.17 (9.5) 8.53 (2.6) 10.5 (3.2)61,068(27.7)

27.89 (8.5) 5.91 (1.8) 3.61 (1.1) 8,378 (3.8) 22.31 (6.8) 6.56 (2) 10.5 (3.2)23,149(10.5)

1400EXW3H 32.81 (10) 8.53 (2.6) 10.5 (3.2)65,036(29.5)

29.53 (9) 5.91 (1.8) 3.61 (1.1) 10,582 (4.8) 22.31 (6.8) 6.56 (2) 10.5 (3.2)23,149(10.5)

1500EXW3H 34.45 (10.5) 8.53 (2.6) 10.5 (3.2)69,005(31.3)

31.17 (9.5) 5.91 (1.8) 3.61 (1.1) 13,228 (6) 23.62 (7.2) 6.56 (2) 10.5 (3.2)28,881(13.1)

1600EXW3H 36.09 (11) 8.53 (2.6) 10.5 (3.2)72,973(33.1)

32.81 (10) 5.91 (1.8) 3.61 (1.1) 13,889 (6.3) 23.62 (7.2) 6.56 (2) 10.5 (3.2)28,881(13.1)

Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater30

Page 33: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Split Shipment - Standard Efficiency - CGNTable 11: Split shipment - standard efficiency

Double effect direct fired absorption chillerMain shell unit HX unit HG unit

YHAU-CGN Lengthft (m)

Widthft (m)

Heightft (m)

Weightlb (ton)

Lengthft (m)

Widthft (m)

Heightft (m)

Weightlb (ton)

Lengthft (m)

Widthft (m)

Heightft (m)

Weightlb (ton)

120EXS

150EXS 8.53 (2.6) 6.56 (2) 7.55 (2.3) 8,819 (4) 8.53 (2.6) 4.92 (1.5) 3.94 (1.2) 1,543 (0.7) 9.19 (2.8) 3.28 (1) 4.92 (1.5) 3,307 (1.5)180EXS 10.5 (3.2) 6.56 (2) 7.55 (2.3) 9,920 (4.5) 10.5 (3.2) 4.92 (1.5) 3.94 (1.2) 1,543 (0.7) 10.17 (3.1) 3.28 (1) 4.92 (1.5) 3,307 (1.5)240EXS 12.47 (3.8) 6.56 (2) 7.55 (2.3) 10,362 (4.7) 11.15 (3.4) 4.92 (1.5) 3.61 (1.1) 1,543 (0.7) 11.81 (3.6) 3.28 (1) 4.92 (1.5) 3,968 (1.8)300EXS 15.42 (4.7) 6.56 (2) 7.55 (2.3) 12,787 (5.8) 13.78 (4.2) 4.92 (1.5) 3.61 (1.1) 1,764 (0.8) 13.12 (4) 3.28 (1) 4.92 (1.5) 4,850 (2.2)360EXS 19.03 (5.8) 6.56 (2) 7.55 (2.3) 14,991 (6.8) 18.7 (5.7) 4.92 (1.5) 3.61 (1.1) 2,646 (1.2) 16.73 (5.1) 3.28 (1) 6.56 (2) 5,732 (2.6)400EXS 19.03 (5.8) 6.56 (2) 7.55 (2.3) 14,991 (6.8) 18.7 (5.7) 4.92 (1.5) 3.61 (1.1) 2,646 (1.2) 16.73 (5.1) 3.28 (1) 6.56 (2) 5,732 (2.6)450EXS 16.08 (4.9) 7.55 (2.3) 9.19 (2.8) 21,605 (9.8) 15.42 (4.7) 5.25 (1.6) 3.61 (1.1) 2,646 (1.2) 15.42 (4.7) 3.28 (1) 6.56 (2) 5,952 (2.7)500EXS 17.72 (5.4) 7.55 (2.3) 9.19 (2.8) 22,046 (10) 17.06 (5.2) 5.25 (1.6) 3.61 (1.1) 2,646 (1.2) 15.75 (4.8) 4.59 (1.4) 6.56 (2) 7,496 (3.4)

560EXS 19.36 (5.9) 7.55 (2.3) 9.19 (2.8)24,471(11.1)

18.7 (5.7) 5.25 (1.6) 3.61 (1.1) 2,646 (1.2) 16.73 (5.1) 4.59 (1.4) 6.56 (2) 7,716 (3.5)

600EXS 21 (6.4) 8.2 (2.5) 9.19 (2.8)26,896(12.2)

20.34 (6.2) 5.25 (1.6) 3.61 (1.1) 2,646 (1.2) 17.06 (5.2) 4.59 (1.4) 6.56 (2) 8,598 (3.9)

700EXS 23.62 (7.2) 8.2 (2.5) 9.19 (2.8)32,628(14.8)

22.97 (7) 5.25 (1.6) 3.61 (1.1) 3,086 (1.4) 19.36 (5.9) 4.59 (1.4) 6.56 (2) 8,819 (4)

800EXS 25.92 (7.9) 8.2 (2.5) 9.19 (2.8)38,801(17.6)

25.26 (7.7) 5.25 (1.6) 3.61 (1.1) 3,527 (1.6) 21.65 (6.6) 4.59 (1.4) 6.56 (2) 9,921 (4.5)

900EXWS 23.95 (7.3) 8.53 (2.6) 9.19 (2.8)45,415(20.6)

21.98 (6.7) 5.91 (1.8) 3.61 (1.1) 3,748 (1.7) 19.36 (5.9) 5.58 (1.7) 9.19 (2.8) 12,787 (5.8)

1000EXWS 26.25 (8) 8.53 (2.6) 9.19 (2.8)49,163(22.3)

23.95 (7.3) 5.91 (1.8) 3.61 (1.1) 3,968 (1.8) 19.36 (5.9) 5.58 (1.7) 9.19 (2.8) 12,787 (5.8)

1100EXWS 28.54 (8.7) 8.53 (2.6) 9.19 (2.8)54,675(24.8)

26.25 (8) 5.91 (1.8) 3.61 (1.1) 3,968 (1.8) 21.33 (6.5) 5.58 (1.7) 9.19 (2.8) 14,991 (6.8)

1200EXW3S 29.53 (9) 8.53 (2.6) 9.51 (2.9)57,100(25.9)

26.25 (8) 5.91 (1.8) 3.61 (1.1) 3,968 (1.8) 21.33 (6.5) 5.58 (1.7) 9.19 (2.8) 14,991 (6.8)

1300EXW3S 31.17 (9.5) 8.53 (2.6) 10.5 (3.2)61,068(27.7)

27.89 (8.5) 5.91 (1.8) 3.61 (1.1) 4,850 (2.2) 22.31 (6.8) 5.58 (1.7) 9.19 (2.8) 15,432 (7)

1400EXW3S 32.81 (10) 8.53 (2.6) 10.5 (3.2)65,036(29.5)

29.53 (9) 5.91 (1.8) 3.61 (1.1) 4,850 (2.2) 22.31 (6.8) 5.58 (1.7) 9.19 (2.8) 15,432 (7)

1500EXW3S 34.45 (10.5) 8.53 (2.6) 10.5 (3.2)69,005(31.3)

31.17 (9.5) 5.91 (1.8) 3.61 (1.1) 6,393 (2.9) 23.62 (7.2) 6.56 (2) 10.5 (3.2)23,149(10.5)

1600EXW3S 36.09 (11) 8.53 (2.6) 10.5 (3.2)72,973(33.1)

32.81 (10) 5.91 (1.8) 3.61 (1.1) 6,614 (3) 23.62 (7.2) 6.56 (2) 10.5 (3.2)23,149(10.5)

31Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Page 34: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Split Shipment - Standard Efficiency - CGHTable 12: Split shipment - standard efficiency

Double effect direct fired absorption chillerMain shell unit HX unit HG unit

YHAU-CGH Lengthft (m)

Widthft (m)

Heightft (m)

Weightlb (ton)

Lengthft (m)

Widthft (m)

Heightft (m)

Weightlb (ton)

Lengthft (m)

Widthft (m)

Heightft (m)

Weightlb (ton)

120EXS

150EXS

180EXS

240EXS

300EXS

360EXS

400EXS

450EXS 17.72 (5.4) 7.55 (2.3) 9.19 (2.8) 22,046 (10) 17.06 (5.2) 5.25 (1.6) 3.61 (1.1) 2,646 (1.2) 15.75 (4.8) 4.59 (1.4) 6.56 (2) 8,598 (3.9)

500EXS 19.36 (5.9) 7.55 (2.3) 9.19 (2.8)24,471(11.1)

18.7 (5.7) 5.25 (1.6) 3.61 (1.1) 2,646 (1.2) 16.73 (5.1) 4.59 (1.4) 6.56 (2) 8,598 (3.9)

560EXS 21 (6.4) 8.2 (2.5) 9.19 (2.8)26,896(12.2)

20.34 (6.2) 5.25 (1.6) 3.61 (1.1) 2,646 (1.2) 17.06 (5.2) 4.59 (1.4) 6.56 (2) 9,921 (4.5)

600EXS 23.62 (7.2) 8.2 (2.5) 9.19 (2.8)32,628(14.8)

22.97 (7) 5.25 (1.6) 3.61 (1.1) 3,087 (1.4) 19.36 (5.9) 4.59 (1.4) 6.56 (2) 9,921 (4.5)

700EXS 25.92 (7.9) 8.2 (2.5) 9.19 (2.8)38,801(17.6)

25.26 (7.7) 5.25 (1.6) 3.61 (1.1) 3,527 (1.6) 21.65 (6.6) 5.58 (1.7) 9.19 (2.8) 15,432 (7)

800EXS 23.95 (7.3) 8.53 (2.6) 9.19 (2.8)45,415(20.6)

21.98 (6.7) 5.91 (1.8) 3.61 (1.1) 3,748 (1.7) 19.36 (5.9) 5.58 (1.7) 9.19 (2.8) 14,991 (6.8)

900EXWS 26.25 (8) 8.53 (2.6) 9.19 (2.8)49,163(22.3)

23.95 (7.3) 5.91 (1.8) 3.61 (1.1) 3,968 (1.8) 19.36 (5.9) 5.58 (1.7) 9.19 (2.8) 14,991 (6.8)

1000EXWS 28.54 (8.7) 8.53 (2.6) 9.19 (2.8)54,675(24.8)

26.25 (8) 5.91 (1.8) 3.61 (1.1) 3,968 (1.8) 21.33 (6.5) 5.58 (1.7) 9.19 (2.8) 15,432 (7)

1100EXWS 29.53 (9) 8.53 (2.6) 9.51 (2.9)57,100(25.9)

26.25 (8) 5.91 (1.8) 3.61 (1.1) 3,968 (1.8) 21.33 (6.5) 5.58 (1.7) 9.19 (2.8) 15,432 (7)

1200EXW3S 31.17 (9.5) 8.53 (2.6) 10.5 (3.2)61,068(27.7)

27.89 (8.5) 5.91 (1.8) 3.61 (1.1) 4,850 (2.2) 22.31 (6.8) 6.56 (2) 10.5 (3.2)23,149(10.5)

1300EXW3S 32.81 (10) 8.53 (2.6) 10.5 (3.2)65,036(29.5)

29.53 (9) 5.91 (1.8) 3.61 (1.1) 4,850 (2.2) 22.31 (6.8) 6.56 (2) 10.5 (3.2)23,149(10.5)

1400EXW3S 34.45 (10.5) 8.53 (2.6) 10.5 (3.2)69,005(31.3)

31.17 (9.5) 5.91 (1.8) 3.61 (1.1) 6,393 (2.9) 23.62 (7.2) 6.56 (2) 10.5 (3.2)28,881(13.1)

1500EXW3S 36.09 (11) 8.53 (2.6) 10.5 (3.2)72,973(33.1)

32.81 (10) 5.91 (1.8) 3.61 (1.1) 6,614 (3) 23.62 (7.2) 6.56 (2) 10.5 (3.2)28,881(13.1)

1600EXW3S 36.09 (11) 8.53 (2.6) 10.5 (3.2)72,973(33.1)

32.81 (10) 5.91 (1.8) 3.61 (1.1) 6,614 (3) 23.62 (7.2) 6.56 (2) 10.5 (3.2)28,881(13.1)

Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater32

Page 35: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Figure 4: - SPLIT SHIPMENT VIEWS FOR MAIN SHELL, HX AND HG UNITS

33Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Page 36: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Electrical Data - CG/AN

Main breakerSolution

circulationpump

Solutionspray pump

Refrigerantpump

Vacuumpump

Burner fanYHAU-CG/AN

Powersource

(V-PH-Hz) Ratedcurrent

Framesize

KW FLA LRA KW FLA LRA KW FLA LRA KW FLA LRA KW FLA LRA

Totalcapacity

KVA

Totalconsumption

KW

MCAA

MOPA

SCCRKA

150EX(H/S)

AC460V-3Ph-60Hz

20 A 125 A 2.2 5.2 24 1.1 3 12.9 0.2 1.05 4 0.75 1.8 9 0.75 1.6 12.9 9.6 7.7 15.8 20.2 5

180EX(H/S)

AC460V-3Ph-60Hz

25 A 125 A 2.2 5.2 24 2.2 5.2 24 0.4 1.5 4.7 0.75 1.8 9 1.12 2.4 12.9 11.8 9.4 20.1 23.6 5

240EX(H/S)

AC460V-3Ph-60Hz

25 A 125 A 2.2 5.2 24 2.2 5.2 24 0.4 1.5 4.7 0.75 1.8 9 1.12 2.4 22.5 12.8 10.2 20.1 23.6 5

300EX(H/S)

AC460V-3Ph-60Hz

30 A 125 A 3 7.1 31 2.2 5.2 24 0.4 1.5 4.7 0.75 1.8 9 3.73 6 22.5 14.1 11.3 27 31.5 5

360EX(H/S)

AC460V-3Ph-60Hz

35 A 125 A 3 7.1 31 2.2 5.2 24 0.4 1.5 4.7 0.75 1.8 9 5.6 8.6 31.5 15 12 30.3 36 5

400EX(H/S)

AC460V-3Ph-60Hz

35 A 125 A 3 7.1 31 2.2 5.2 24 0.4 1.5 4.7 0.75 1.8 9 5.6 8.6 31.5 15 12 30.3 36 5

450EX(H/S)

AC460V-3Ph-60Hz

40 A 125 A 5.5 11.1 68 2.2 5.2 24 0.4 1.5 4.7 0.75 1.8 9 5.6 8.6 31.5 19.1 15.2 35.1 42.9 5

500EX(H/S)

AC460V-3Ph-60Hz

40 A 125 A 5.5 11.1 68 2.2 5.2 24 0.4 1.5 4.7 0.75 1.8 9 5.6 8.6 79.8 21.2 17 35.1 42.9 5

560EX(H/S)

AC460V-3Ph-60Hz

40 A 125 A 5.5 11.1 68 2.2 5.2 24 0.4 1.5 4.7 0.75 1.8 9 5.6 8.6 79.8 21.2 17 35.1 42.9 5

600EX(H/S)

AC460V-3Ph-60Hz

45 A 125 A 5.5 11.1 68 2.2 5.2 24 0.4 1.5 4.7 0.75 1.8 9 7.46 12 79.8 21.2 17 39.4 47.5 5

700EX(H/S)

AC460V-3Ph-60Hz

45 A 125 A 5.5 11.1 68 2.2 5.2 24 0.4 1.5 4.7 0.75 1.8 9 7.46 12 79.8 21.2 17 39.4 47.5 5

800EX(H/S)

AC460V-3Ph-60Hz

35 A 125 A 5.5 11.1 68 2.2 5.2 24 0.4 1.5 4.7 0.75 1.8 9 3.73 6 100 23.3 18.6 31.9 40.3 5

900EX(H/S)

AC460V-3Ph-60Hz

35 A 125 A 5.5 11.1 68 2.2 5.4 24.5 1.3 3.4 14 0.75 1.8 9 3.73 6 144 27.4 21.9 34.5 42.2 5

1000EXW(H/S)

AC460V-3Ph-60Hz

50 A 125 A 7.5 16.5 76 2.2 8.8 38 1.3 3.9 13.8 0.75 1.8 9 3.73 6 144 30 24.8 46.3 58.6 5

1100EXW(H/S)

AC460V-3Ph-60Hz

60 A 125 A 7.5 16.5 76 3.7 8.8 38 1.5 3.9 13.8 0.75 1.8 9 7.46 12 144 34.3 27.4 53.8 64.6 5

1200EXW3(H/

S)

AC460V-3Ph-60Hz

60 A 125 A 7.5 16.5 76 3.7 8.8 38 1.5 3.9 13.8 0.75 1.8 9 7.46 12 144 34.3 27.4 53.8 64.6 5

1300EXW3(H/

S)

AC460V-3Ph-60Hz

70 A 125 A 7.5 16.5 76 3.7 8.8 38 1.5 3.9 13.8 0.75 1.8 9 11.9 17.5 126 39.1 31.3 60.6 71.4 5

1400EXW3(H/

S)

AC460V-3Ph-60Hz

70 A 125 A 7.5 16.5 76 3.7 8.8 38 1.5 3.9 13.8 0.75 1.8 9 11.9 17.5 126 39.1 31.3 60.6 71.4 5

1500EXW3(H/

S)

AC460V-3Ph-60Hz

70 A 125 A 7.5 16.5 76 3.7 8.8 38 1.5 3.9 13.8 0.75 1.8 9 11.9 17.5 198 44.1 35.3 60.6 71.4 5

1600EXW3(H/

S)

AC460V-3Ph-60Hz

70 A 125 A 7.5 16.5 76 3.7 8.8 38 1.5 3.9 13.8 0.75 1.8 9 11.9 17.5 198 44.1 35.3 60.6 71.4 5

Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater34

Page 37: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Electrical Data - CG/AH

Main breakerSolution

circulationpump

Solutionspray pump

Refrigerantpump

Vacuum pump Burner fanYHAU-CG/AH

Powersource(V-PH-

HZ) Ratedcurrent

Framesize

KW FLA LRA KW FLA LRA KW FLA LRA KW FLA LRA KW FLA LRWA

Totalcapacity

KVA

Totalconsumption

KW

SCCRKA

450EX(H/S)

AC460-3P-60Hz

40 A 125 A 5.5 14.2 60 2.2 6.1 23 0.4 1.5 4.7 0.75 1.8 9 5.6 8.6 94 22.9 18.3 5

500EX(H/S)

AC460-3P-60Hz

45 A 125 A 5.5 14.2 60 2.2 6.1 23 0.4 1.5 4.7 0.75 1.8 9 7.46 12 79.9 25.6 20.5 5

560EX(H/S)

AC460-3P-60Hz

45 A 125 A 5.5 14.2 60 2.2 6.1 23 0.4 1.5 4.7 0.75 1.8 9 7.46 12 79.9 25.6 20.5 5

600EX(H/S)

AC460-3P-60Hz

35 A 125 A 5.5 14.2 60 2.2 6.1 23 0.4 1.5 4.7 0.75 1.8 9 3.73 6 56.4 20.8 16.7 5

700EX(H/S)

AC460-3P-60Hz

35 A 125 A 5.5 14.2 60 2.2 6.1 23 0.4 1.5 4.7 0.75 1.8 9 3.73 6 56.4 20.8 16.7 5

800EX(H/S)

AC460-3P-60Hz

35 A 125 A 5.5 14.2 60 2.2 6.5 20.3 0.4 1.5 4.7 0.75 1.8 9 3.73 6 56.4 20.8 16.7 5

900EX(H/S)

AC460-3P-60Hz

45 A 125 A 5.5 14.2 60 2.2 6.5 20.3 1.3 3.9 14 0.75 1.8 9 7.46 12 78.9 27.3 21.8 5

1000EXW(H/S)

AC460-3P-60Hz

60 A 125 A 7.5 19.8 68.6 2.2 6.5 20.3 1.5 3.9 13.8 0.75 1.8 9 7.46 12 78.9 34.8 27.8 5

1100EXW(H/S)

AC460-3P-60Hz

70 A 125 A 7.5 19.8 60 3.7 10.6 34 1.5 3.9 13.8 0.75 1.8 9 11.19 17.5 118.3 39.1 31.3 5

1200EXW3(H/S)

AC460-3P-60Hz

70 A 125 A 7.5 19.8 60 3.7 10.6 20.3 1.5 3.9 13.8 0.75 1.8 9 11.19 17.5 118.3 39.1 31.3 5

1300EXW3(H/S)

AC460-3P-60Hz

70 A 125 A 7.5 19.8 60 3.7 10.6 20.3 1.5 3.9 13.8 0.75 1.8 9 11.19 17.5 118.3 39.1 31.3 5

1400EXW3(H/S)

AC460-3P-60Hz

70 A 125 A 7.5 19.8 60 3.7 10.6 20.3 1.5 3.9 13.8 0.75 1.8 9 11.19 17.5 118.3 39.1 31.3 5

1500EXW3(H/S)

AC460-3P-60Hz

70 A 125 A 7.5 19.8 60 3.7 10.6 20.3 1.5 3.9 13.8 0.75 1.8 9 11.19 17.5 118.3 39.1 31.3 5

1600EXW3(H/S)

AC460-3P-60Hz

70 A 125 A 7.5 19.8 60 3.7 10.6 20.3 1.5 3.9 13.8 0.75 1.8 9 11.19 17.5 118.3 39.1 31.3 5

35Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Page 38: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Nozzle Arrangements120 - 300EX(H/S)

Nozzle locationChilled/hot Water Cooling waterYHAU-CGN/H

Inlet Outlet Inlet OutletGas inlet Exhaust gas outlet

Odd pass B Odd pass B120-300EX(H/S) A

Even pass AA

Even pass AB A

Note: These images are representations of nozzle arrangements. Reference generalarrangement drawings for detailed nozzle locations for each specific unit.

Figure 5: YHAU-CGN/H-120-300EX(H/S) nozzle locations

Item Description1 Chilled/Hot Water Outlet (Odd Pass)2 Cooling Water Outlet (Odd Pass)3 Gas Inlet4 Cooling Water Outlet (Even Pass)5 Chilled/Hot Water Outlet (Even Pass)6 Chilled/Hot Water Inlet7 Cooling Water Inlet8 Exhaust Gas Outlet

360EX - 1600EXW3(H/S)Nozzle location

Chilled/hot water Cooling waterYAU-CGN/HInlet Outlet Inlet Outlet

Gas inlet Exhaust gas outlet

Odd pass A Odd pass A360EX-1600EXW3(H/S) B

Even pass BB

Even pass BB A

Note: These images are representations of nozzle arrangements. Reference generalarrangement drawings for detailed nozzle locations for each specific unit.

Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater36

Page 39: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Figure 6: YHAU-CGN/H-360EX-1600EXW3(H/S) nozzle locations

Item Description1 Chilled/Hot Outlet (Even Pass)2 Cooling Water Outlet (Even Pass)3 Gas Inlet4 Cooling Water Inlet5 Chilled/Hot Water Inlet6 Cooling Water Outlet (Odd Pass)7 Chilled/Hot Water Outlet (Odd Pass)8 Exhaust Gas Outlet

37Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Page 40: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Sound DataOctave band

Location Overall31.5 Hz 63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz 16 kHz

1 78 / 87 36 / 70 52 / 78 65 / 82 62 / 71 63 / 67 66 / 66 70 / 69 66 / 63 60 / 57 49 / 472 76 / 89 43 / 77 55 / 80 65 / 82 64 / 73 61 / 64 65 / 64 66 / 64 63 / 61 55 / 55 42 / 403 79 / 93 50 / 85 57 / 80 69 / 83 65 / 73 61 / 63 62 / 62 66 / 65 65 / 63 61 /58 38 / 364 80 / 88 40 / 74 52 / 77 64 / 79 59 / 67 58 / 62 66 / 66 70 / 69 67 / 66 63 / 61 41 / 395 67 / 82 35 / 73 42 / 69 60 / 77 53 / 62 51 / 55 54 / 54 53 / 52 48 / 47 34 / 33 25 / 25

Note: These data are reference values as the chiller-heater unit was not covered with thermalinsulation materials and the water pipes (for chilled water, cooling water, and gas) weretemporary during the measurement.

Figure 7: Sound data

Unit of measure: dB(A)/dB(C)Position of instrument: Height - 59 in.Horizontal - 39 in. from chiller-heater surface

Noise emission information: The direct fired chiller-heater running with the burner mightproduce A-weighted emission sound pressure level in excess of 80 dB(A). Normally the A-weightedsound power level is less than 100 dB(A). Hearing protection must be worn at all times whenoperating the chiller-heater. This hearing protection can impact the way that operators mustcommunicate to be understood.

Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater38

Page 41: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Process and InstrumentationThe following system flow and process and instrumentation diagrams are used for quoting andbidding.

Cooling only (evaporator)

Figure 8: YHAU- CGN/H direct fired chiller-heater with evaporator heating flow diagram(cooling only)

39Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Page 42: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Heating only (evaporator)

Figure 9: YHAU- CGN/H direct fired chiller-heater with evaporator heating flow diagram(heating only)

Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater40

Page 43: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Residential hot water (auxiliary heat exchanger)

Figure 10: YHAU- CGN/H direct fired chiller-heater with evaporator heating flow diagramresidential hot water (auxiliary heat exchanger only)

41Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Page 44: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Simultaneous heating and residential hot water only

Figure 11: YHAU-CGN/H direct fired chiller-heater with evaporator heating flow diagram -simultaneous heating and residential hot water

Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater42

Page 45: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Simultaneous cooling and residential hot water

Figure 12: YHAU- CGN/H direct fired chiller-heater with evaporator heating flow diagram -simultaneous cooling and residential hot water only

43Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Page 46: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Figure 13: YHAU-CH/AN/H direct fired chiller-heater with additional heat exchanger heatingflow diagram - cooling

Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater44

Page 47: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Figure 14: YHAU-CG/AN/H direct fired chiller-heater with additional heat exchanger heatingflow diagram - heating

45Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Page 48: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Figure 15: Process and instrumentation diagram - cooling only

Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater46

Page 49: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Guide SpecificationsGeneralDouble-Effect Gas Direct-Fired Absorption Chiller-Heaters are capable of producing chilled or hotwater as outlined by the capacities shown on drawings and schedules. Each chiller-heater is ofhermetic design and factory helium leak tested.The chiller-heater ships as a one-piece assembly, charged with nitrogen, and without solution andrefrigerant water charging.All unit mounted controls, control panels, and forced draft linkless type gas burner are factorymounted, wired, tested, and shipped preinstalled as integral components of the chiller-heater. Thegas train is shipped loose for field installation.Purchase price includes start-up service and parts and labor warranty for a period of one year fromstart-up or eighteen months from delivery, whichever occurs first.

Base unit includes:• Absorber, evaporator, and condenser

• ANSI flanges for chilled/hot water and cooling water mating flanges are not included

• High temperature generator and low temperature generator

• High temperature solution heat exchanger and low temperature solution heat exchanger

• Ltg refrigerant condensate heat exchanger

• Hermetic solution circulation pump, solution spray pump and refrigerant pump

• Compact 150 psig waterboxes for chilled/hot water

• Compact 150 psig waterboxes for cooling water for models up to -300EX(H/S)

• Marine type 150 psig waterboxes for cooling water for models -360EX (H/S) or above

• YORK Caribbean blue (Munsell 4.65G)

• Epoxy paint inside chilled/hot waterboxes and cooling waterboxes

• Control panel

• Power supply 460V/3 phase/60 Hz with 3 wires

• Rupture disc for over pressure relief 12.0 psig, +/- 2.0 psi.

• Chilled/hot water pressure differential switch

• Compound gauge

• Automatic purge system including purge pump

• 4-20 Ma remote temperature reset control for chilled/hot water

• LiBr (lithium bromide + lithium molybdate inhibitor)

47Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Page 50: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

• Gas burner

• Gas train (that is installed at the field)

• UL labeling

• Deionized water refrigerant

• 2-Ethyl Hexyl Alcohol

• Modbus / RTU / TCP

• Factory end of line function test

• Initial startup

• Dry shipment

Base unit does not include:• Cold surface insulation (Option)

• Hot surface insulation (By Contractor)

• Cooling water pressure differential switch (Option)

• Factory performance test (Option)

• Field reassembly of split shipped units

ConstructionThe chiller-heater consists of a low temperature generator, a high temperature generator, hightemperature solution heat exchanger, low temperature solution heat exchanger, LTG refrigerantcondensate heat exchanger, absorber, condenser, and evaporator. To minimize the risk ofcorrosion, the evaporator dispersion tray and the absorber dispersion tray are of stainless steel.Each dispersion tray has two stage constructions and any foreign material is removed from theLiBr solution or the refrigerant at the first stage tray to avoid any degradation of dispersionperformance by clogging.The evaporator, absorber, condenser, and low temperature generator are of shell and tubeconstruction. The high temperature generator is a liquid tube type. A shell-side rupture disc isfurnished and set to blow at 12.0 psig, +/- 2.0 psi.The evaporator cycle and the absorber cycle consist of a two-step technology (upper stage andlower stage). This technology makes absorber solution concentration weak and makes the hightemperature generator solution temperature lower than the ordinary machine, that extends themachine life. Low temperature generator is a falling liquid film type.Three plate-type solution heat exchangers (high temperature solution heat exchanger, lowtemperature solution heat exchanger and LTG refrigerant condensate heat exchangers) areequipped to achieve higher efficiency.The LiBr solution flow type is in parallel flow cycle. The flow of weak solution pumped fromthe absorber initially passes through the low temperature solution heat exchanger to improveoperating efficiency by preheating and is divided into two paths. One path leads to the hightemperature generator through the high temperature solution heat exchanger and the other leadsto the low temperature generator in parallel.

Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater48

Page 51: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

The unit is hermetically tight and built to very stringent conditions. It operates under a bettervacuum, that improves performance and reliability ensuring design performance to GB/T18362-2008 Standard (2.03*10-6 Pa*m3/s).

Tube materialsEvaporator tubes are Low Residual Phosphorus Deoxidized Copper (C1201), finned type with awall thickness before finning of 0.024 in. The absorber, condenser, and low temperature generatortubes are bare type and made of 0.024 in. wall stainless steel (SUS436LTB). High temperaturegenerator tubes are carbon steel.

WaterboxesWaterboxes are removable to facilitate tube cleaning and replacement whereas absorber andcondenser waterboxes for CGN/H360EX(H/S) model or larger are the marine type. Water circuittubing to be replaceable from either end of the absorption unit. All waterboxes and associatedwater circuit nozzles and tube bundles are designed for 150 psig working pressure and is watertested at 188 psig. Vent and drain connections are provided on each waterbox. All the waterconnections are equipped with ANSI flanges. Mating flanges are not included. The inside of thewaterboxes and waterbox covers are coated with epoxy resin paint.

Automatic decrystallization systemThe chiller-heater must have an anti-crystallization system. The absorber and the evaporator arelocated side by side in a same shell and separated by the eliminator. When the concentration rateof lithium bromide in the chiller-heater goes up, the water level at the evaporator increases andautomatically spills over to the absorber and the concentration rate of the solution at the absorbergoes down.

PumpsSolution pump, solution spray pump, and refrigerant pumps are hermetically sealed, self-lubricating, totally enclosed, factory-mounted, wired, and tested. Motor windings must not beexposed to lithium bromide or water. The suction and discharge connections for each pump is fullywelded to the unit piping to minimize the opportunity for leaks. Pump durability is designed tooperate for a total of 60,000 hours. Components in the pumps such as bearings and sealing gasketsrequire inspection every 20,000 hours and are replaced depending on necessity.

Fully automatic purging systemThe chiller-heater is equipped with an automatic purging system to remove non-condensable gasesfrom the unit during operation. Non-condensables are collected by an eductor and accumulatedin the purge tank. The control panel can sense the pressure increase in the purge tank andautomatically remove the non-condensable gas through the operation of an electric vacuum pump.The purge pump is a oil rotary double stage design, and is furnished complete with a motor andall required accessories. The purge pump is shipped mounted on the chiller-heater and connectinghose is factory installed. The purge pump oil is charged at the factory.

Lithium bromide and refrigerantLithium bromide contains lithium molybdate corrosion inhibitor to minimize the rate of ferrousmetal corrosion on both the solution and refrigerant sides of the unit. The solution and deionizedrefrigerant water are kept in barrels and shipped with the chiller. They are then charged at the fieldduring the commissioning.

49Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Page 52: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Dry shipmentThe solution and refrigerant water are kept in the barrels and shipped with the chiller. They arecharged in the field during the commissioning. The chiller is charged with N2 to 4.4 psig during thedelivery.

Linkless type gas burnerGas burner and gas train are designed and built according to UL Standards and codes. Capacitycontrol for the gas burner is proportional control. Linkless type gas burner ensures ideal air-fuelratio and high combustion efficiency throughout its capacity control range. Air-fuel ratio can beadjusted through the touch panel screen on the control panel - simply enter the required valveopening value, no mechanical adjustment is required.The gas burner includes a main and pilot gas shut off valve, main and pilot gas governor, highand low gas pressure switch, low air pressure switch, flame detector, gas pressure gauge and gasstrainer.

Control panelEach unit is furnished complete with a factory mounted and pre-wired control system. The controlpanel enclosure is equipped with a hinged access door with lock and key. Protection rating of thecontrol panel is equivalent to IP42. All temperature sensors and other control devices necessaryto sense unit operating parameters are factory mounted and wired to panel. The control panelincludes a touch panel showing all system parameters in various languages with numeric data inimperial or metric units.The operating program is stored in nonvolatile memory (SRAM) to eliminate chiller-heater failuredue to AC power failure.Capacity Control - The control panel automatically controls the input gas flow rate to maintain theprogrammed leaving chilled or hot water setpoint for cooling loads. Capacity control range understandard condition is 20% to 100%. The input (gas) flow rate is manually adjustable from the controlpanel to any setting between minimum and maximum when automatic operation is not required.Solution Pump Variable Frequency Drive (Option) – Frequency control unit for solutioncirculation pump and solution spray pump can be equipped on direct-fired absorption chiller-heaters as an option. This unit controls frequency of solution pumps to improve part load efficiencyof chiller-heater depending on high temperature pressure, temperature and concentration.

Main screen1. Equipment Status

- Chiller-heater Stop / Operating / Failure Activating

- Burner Combustion ON / OFF

- Solution Circulation Pump, Solution Spray Pump, Refrigerant Pump ON / OFF

- Purge Pump ON / OFF

- Burner Fan Motor ON / OFF

- Chilled/Hot Water Pump/Cooling Water Pump ON / OFF

2. Operation Status

- Startup

Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater50

Page 53: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

- Low Combustion

- Temperature Control

- Thermo OFF

- Dilution Operation

- Set Point of Chilled/Hot Water Leaving Temperature

- Burner control valve Control Output

- Burner control valve position

- Chilled/Hot Water Entering/Leaving Temperature

- Cooling Water Entering/Leaving Temperature

- Refrigerant Temperature

- Absorber Temperature

- High Temperature Generator Temperature

- High Temperature Generator Pressure

- High Temperature Generator Concentration

- Exhaust Gas Temperature

- Purge Tank Pressure

3. Condition Lamps

- Chiller-heater Stop/Operation

- Local/Remote

- Failure / Alarm

4. Operation Button

- Chiller-heater Stop / Operation

- Local / Remote Mode Select

51Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Page 54: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Data screen1. Measured Value

- Chilled/Hot Water Entering Temperature (°F)

- Chilled/Hot Water Leaving Temperature (°F)

- Cooling Water Entering Temperature (°F)

- Cooling Water Leaving Temperature (°F)

- Evaporator Refrigerant Temperature (°F)

- Absorber Temperature (°F)

- High Temperature Generator Temperature (°F)

- High Temperature Generator Pressure (mmHg)

- High Temperature Generator Concentration (wt %)

- Exhaust Gas Temperature (°F)

- Purge Tank Pressure (mmHg)

- Burner Control Valve Control Output (%)

- Residential Hot Water Temperature (°F) (Residential hot water heat exchanger equippedmodel only).

2. Operation Hours

- Total Operation Hours

- Cooling Operation Hours

- Heating Operation Hours

- Solution Pump Operation Hours

- Refrigerant Pump Operation Hours

- Burner Combustion Hours

3. Frequency

- Total operation times

- Cooling Operation Times

- Heating Operation Times

- Start Times

- Failure Times

Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater52

Page 55: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

- Alarm Times

- Auto Purge Times

4. Trend

- Chilled/Hot Water Temperature

- Cooling Water Temperature

- High Temperature Generator Temperature

- High Temperature Generator Pressure

5. History Menu

- Hourly Temperature Trend (12 hours)

- Minutely Temperature Trend (12 minutes)

- Failure History (6 times)

- Alarm History (6 times)

53Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Page 56: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Failure / alarm screen1. Failure

- Chilled/Hot Water Time Out

- Cooling Water Time Out

- Ignition Time Out

- Ignition Condition Unsatisfied

- Operation Interlock

- Cooling Water Pump Interlock

- Chilled/Hot Water Suspension

- Chilled Water Overcooled/Hot Water High Temperature

- Refrigerant Overcooled

- Constantly Monitoring Interlock

- Combustion Monitoring Interlock

- Emergency Failure Interlock

- Low Cooling Water Inlet Temperature

- High Temp Generator High Temperature

- High Temp Generator High Pressure

- High Cut (High Temp GEN High Pressure)

- High Exhaust Gas Temperature

- Flame Failure

- Fuel Line Abnormal

- High Temp Generator Low Liquid Level

- Solution Circulation Pump Abnormal

- Solution Spray Pump Abnormal

- Refrigerant Pump Abnormal

- Burner Fan Abnormal

- Control Sensor Abnormal

- CPU Abnormal

Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater54

Page 57: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

2. Alarm

- Abnormal Purge Frequency

- Purge System Abnormal

- Chilled Water Overcool Prevention Control

- Refrigerant Overcool Prevention Control

- Cooling Water Tube Fouling

- High Temp Generator Tube Fouling

- Refrigerant Pump Stop

- High Temp Generator High Pressure Prevention Control

- High Temp Generator High Temperature Prevention Control

- High Temp Generator High Concentration Prevention Control

- Low Cooling Water Inlet Temperature

- High Cooling Water Inlet Temperature

- Recording Sensor Abnormal

- Low Battery

Setting screen1. Control Parameter

- Setting Method Local/Remote

- Setting Base Temperature

- Remote Setting Differential

- Chilled / Hot Water Set Point (Display)

- Automatic Stop Temperature

- Automatic Restart Temperature

2. Valve Operation

- Control Valve Mode Auto / Manual

- Burner Control Valve Position Setting

3. Operation Switch

- Forced Dilution ON/OFF

- Refrigerant Pump Auto or Stop

55Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

Page 58: Model YHAU-CGN/H Double Effect Direct Fired Chiller-Heater

- Operation Mode - Cooling/Heating

- Cool/Heat Simultaneous OFF / ON (Only Residential Hot Water Supply Model)

- Purge Mode Auto/Manual

- Manual Purge ON / OFF

4. Select Language

- Japanese/English/Chinese

5. Date & Time

Touch panel mechanical specification -

• Screen Size : 10.4 inches

• Electrical Power Supply : DC24 V

• Electrical Power Consumption : Less than 17 W

• Display : TFT 65,536 colors

• Graphic Mode : 640x480 dot (VGA)

Communication – Modbus communication as standard.

• Modbus RTU

• Modbus TCP

© 2020 Johnson Controls. 5000 Renaissance Drive, New Freedom, York, PA 17349, USA. www.johnsoncontrols.com Subjectto change without notice. All rights reserved www.york.com/