EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 Installation Instructions NOTE: Read the entire instruction manual before starting the installation. NOTE: Installation Instructions include Single and Dual point connection instructions separately. SAFETY CONSIDERATIONS Installation and servicing of this equipment can be hazardous due to mechanical and electrical components. Only trained and qualified personnel should install, repair, or service this equipment. Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on this equipment, observe precautions in the literature, on tags, and on labels attached to or shipped with the unit and other safety precautions that may apply. Follow all safety codes. Installation must be in compliance with local and national building codes. Wear safety glasses, protective clothing, and work gloves. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes, the current editions of the National Electrical Code (NEC) NFPA 70. In Canada refer to the current editions of the Canadian Electrical Code CSA C22.1. Recognize safety information. This is the safety-alert symbol/_. When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand these signal words; DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation. Follow all safety codes. Wear safety glasses and work gloves. Have a fire extinguisher available. Before proceeding with heater installation, inspect thoroughly for shipping damage. Notify shipper immediately if any damage is found. Clean all dirt, dust and moisture from heater package. Check for proper clearances of live parts, between phases and to ground. Make sure that all required barriers are in place. Check conductors run in multiple to insure that they are properly wired. Refer to unit installation instructions for complete unit installation details. The maximum duct static for safe electric heater operation is shown in Table 1. ELECTRICALSHOCKHAZARD Failure to follow this warning could result in personal injury or death. Before performing installation, service or maintenance operations on this system, turn off all main power to system. There may be more than one disconnect switch. Turn off accessory heater power switch if applicable. Lockout and tag switch with a suitable warning label. CUT HAZARD Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts. DESCRIPTION AND USAGE This electric heater series is engineered, designed and listed to be installed only in the models shown in Table 2. Before proceeding, verify the heater label for correct voltage and kW requirements. PACKAGE CONTENTS Electric Heater Packaqe Contents 1. Heater assembly 2. UPC heater label 3. Installation instructions 4. Identification label 5. Schematic on lid door for all fused units 6. Schematic on sticker to be placed inside unit panel for non-fused units 7. Wire connectors (3) 8. Wire ties-6-in. (5) 9. Screws #10A (5) 10. Dual Point Warning Label 11. Dual Point Electrical Rating Label 518 06 160200 8/11/10

MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

EHNA Electric Heaters 5-20kWFor 60 Hz Small Packaged Products

MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3

Installation Instructions

NOTE: Read the entire instruction manual before starting theinstallation.

NOTE: Installation Instructions include Single and Dual pointconnection instructions separately.

SAFETY CONSIDERATIONS

Installation and servicing of this equipment can be hazardousdue to mechanical and electrical components. Only trained andqualified personnel should install, repair, or service thisequipment.

Untrained personnel can perform basic maintenance functionssuch as cleaning and replacing air filters. All other operationsmust be performed by trained service personnel. When workingon this equipment, observe precautions in the literature, on tags,and on labels attached to or shipped with the unit and othersafety precautions that may apply.

Follow all safety codes. Installation must be in compliance withlocal and national building codes. Wear safety glasses,protective clothing, and work gloves. Have fire extinguisheravailable. Read these instructions thoroughly and follow allwarnings or cautions included in literature and attached to theunit. Consult local building codes, the current editions of theNational Electrical Code (NEC) NFPA 70.In Canada refer to the current editions of the Canadian ElectricalCode CSA C22.1.

Recognize safety information. This is the safety-alert symbol/_.

When you see this symbol on the unit and in instructions ormanuals, be alert to the potential for personal injury. Understandthese signal words; DANGER, WARNING, and CAUTION.These words are used with the safety-alert symbol. DANGERidentifies the most serious hazards which will result in severe

personal injury or death. WARNING signifies hazards whichcould result in personal injury or death. CAUTION is used toidentify unsafe practices which may result in minor personalinjury or product and property damage. NOTE is used tohighlight suggestions which will result in enhanced installation,reliability, or operation.

Follow all safety codes. Wear safety glasses and work gloves.Have a fire extinguisher available.

Before proceeding with heater installation, inspect thoroughly forshipping damage. Notify shipper immediately if any damage isfound. Clean all dirt, dust and moisture from heater package.Check for proper clearances of live parts, between phases andto ground. Make sure that all required barriers are in place.Check conductors run in multiple to insure that they are properlywired. Refer to unit installation instructions for complete unitinstallation details. The maximum duct static for safe electric

heater operation is shown in Table 1.

ELECTRICALSHOCKHAZARD

Failure to follow this warning could result in personal injury ordeath.

Before performing installation, service or maintenanceoperations on this system, turn off all main power to system.There may be more than one disconnect switch. Turn offaccessory heater power switch if applicable. Lockout and tagswitch with a suitable warning label.

CUT HAZARD

Failure to follow this caution may result in personal injury.

Sheet metal parts may have sharp edges or burrs. Use careand wear appropriate protective clothing and gloves whenhandling parts.

DESCRIPTION AND USAGE

This electric heater series is engineered, designed and listed tobe installed only in the models shown in Table 2. Beforeproceeding, verify the heater label for correct voltage and kWrequirements.

PACKAGE CONTENTS

Electric Heater Packaqe Contents

1. Heater assembly2. UPC heater label

3. Installation instructions

4. Identification label

5. Schematic on lid door for all fused units

6. Schematic on sticker to be placed inside unit panel fornon-fused units

7. Wire connectors (3)

8. Wire ties-6-in. (5)

9. Screws #10A (5)

10. Dual Point Warning Label

11. Dual Point Electrical Rating Label

518 06 160200 8/11/10

Page 2: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

INSTALLATION

SINGLE POINT HEATER INSTALLATION

NOTE: Thermostat used must be capable of energizing "G"(indoor fan) on a call for "W" (heating). If "G" is not energizedsystem malfunction wilt occur.

1. Open all electrical disconnects and install lockout tagbefore beginning any installation or service work.

2. Check for proper equipment model number from list.

3. Verify that unit ductwork is installed per base unitinstructions.

4. Remove unit electrical access panel (See Fig. 1).

5. Locate and remove the heater access cover plate insideunit access panel (See Fig. 3). Save screws.

6. Remove electric heater from the packaging.

7. Install heater, sliding assembly carefully through accesshole. Ensure that mounting holes of heater align withmounting holes on the unit. Secure heater assembly withscrews provided.

8. Attach provided heater wiring labels at appropriate loca-tions (see Fig. 11 or Fig. 12).

9. Dress wires with wire ties provided.

Fig. 1 - Unit Access Panel and Label Location

ELECTRICAL ELECTRICALACCESS ELECTRIC RATING

WARNING LABELPANEL HEATLABEL ACCESS LOCATION

PANEL

Fig. 2 - Second Power Line Access Hole Location

,,_ _ 6=--==-=a L==_==J _ L=_ 0

0

)_Qf 7/8" (22.2 mm)ELECTRIC

J HEATACCESS

PANEL

8-3/4" (222.25 mm)

--4

@

OF

O2-1/2" (63.5 mm)

@@

L _._1:

SINGLE POINT ELECTRICAL CONNECTION

NOTE: All electrical connections, wire sizes and type of conduitshall meet the National Electric Code (NEC) and state and local

codes (or International Electric Code) as applicable.

NOTE: Use minimum 75°C copper wire only.

1. Make sure all disconnects are still open and tagged out asrequired previously.

2. Mark the main unit nameplate with an "X" for the electricheater size being installed. Refer to the electrical datamarked with an "X" on the nameplate for wire andmaximum over current protection sizing.

3. Connect low voltage wires as shown in unit schematicdiagrams found on the base unit installation instructions.These connections must be made in the 24v barrier

section inside the unit panel (See Fig. 3).

4. Insert field power line through the electrical heater accesspanel hole (see Fig. NO TAG or NO TAG) and connect toelectric heater as shown in their respective wiring diagram.Fused electrical heaters field lines wilt be connected to the

fuse block tugs (see Fig. NO TAG) and non fused electricheater field lines wilt be connected to heater leads usingwire nuts. Ground electrical equipment in the appropriatelocations.

IMPORTANT: Heaters with factory installed fuses may beinstalled on a branch circuit protected by either a fuse or circuitbreaker. For all other heaters, the branch circuit must beprotected by a fuse or circuit breaker supplied by others.

5. Connect stripped wires from heater to compressorcontactor leads using supplied wire nuts according to theirheater wiring diagram.

NOTE: Dress wires with wire ties provided. For fused heaters,use pre-mounted wire tires inside of fuse box cover to secureand strain relieve wires.

6. Separate all wires from incoming power leads.

7. Close electrical access panel.

DUAL POINT HEATER INSTALLATION

NOTE: Complete single point heater installation proceduresbefore completing the follow steps.

1. Open all electrical disconnects and install lockout tagbefore beginning any installation or service work.

2. Remove electric access panel (see Fig. 1), check to makesure there is clearance on the inside of control box above

the existing high voltage knockout. Using a knockoutpunch and die combination, make a 7/8-in. hole on theElectrical Heat access panel for second power circuit (seeFig. 2). A knockout punch and die combination or equi-valent toot is required to make this hole. Other types of drillbits or standard hole saws are not acceptable.

3. Attach warning and rating labels in the selected location(see Fig. 1).

4. Mark the main unit nameplate with an "X" next to theaccessory heater "none". Mark the dual point rating labelinstalled at step 3 with an "X" for the electrical heater sizebeing installed. Refer to the electrical data marked with an"X" on each nameplate for wire and maximum over currentprotection sizing.

5. Remove power line connection from heater to unitcontactor and compressor (see Fig. NO TAG and Fig.NO TAG). These are the stripped end wires black andyellow, with opened ends.

518 06 1602 00 2

Page 3: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

DUAL POINT ELECTRICAL CONNECTION

NOTE: AIt electrical connections, wire sizes and type of conduitshall meet the national Electric Code (NEC) and state and local

codes (or International Electric Code) as applicable.

NOTE: Use a minimum 75°C copper wire only.

1. Make sure att disconnects are still open and tagged out asrequired previously.

2. Connect low voltage wires as shown in unit schematicdiagrams found on base unit installation instructions.These connections must be made in the 24v barrier

section inside the unit panel (see Fig. 3).

3. Insert first field power line through the electrical heateraccess panel bottom hole (see Fig. NO TAG or Fig.NO TAG) and connect to electric heater as shown in theirrespective wiring diagram found on the heater accessorykit. Fused electrical heaters field lines wilt be connected to

the fuse block tugs (see Fig. NO TAG.) and non fusedelectric heater field lines will be connected to heater leads

using wire nuts. Ground electrical equipment in theappropriate locations.

Fig. 3 - Heater Blank Plate Location

IMPORTANT: Heaters with factory installed fuses may beinstalled on a a branch circuit protected by either a fuse or circuitbreaker. For att other heaters, the branch circuit must beprotected by a fuse or circuit breaker supplied by others.

NOTE: Dress wires with wire ties provided. For fused heaters,

use pre-mounted wire ties inside of fuse box cover to secureand strain relieve wires.

4. Insert second field power line through the electrical heateraccess panel top hole (see Fig. NO TAG or Fig. NO TAG)and connect to unit contactor black and yellow leads usingwire nuts. Ground electrical equipment in the appropriatelocations.

5. Separate att wires from incoming power leads.

6. Close electrical access panel.

HEATERBLANKPLATE

24V BARRIER

3 518 06 1602 00

Page 4: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

Fig. 4 - Wiring Diagram Example for Fused Heater

WIRES TO BE

REMOVED

I

@ Control WMng I

Power Wiring

Field WJdng

Fig. 5 - Wiring Diagram Example for Non-Fused HeaterTO UNITCONTROLWIRING 24V _ --_ -- -- -- _"_ .......

WIRES TO BE '_ ITO COMPRESSOR YtUW

REMOVEDI CO"TACTOR_OAWG______ III I

L1

1III

I I I

Control Wiring

Power Wiring

Field Wirin

518 06 1602 O0 4

Page 5: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

Fig. 6 - Single Point Connections for Fused Heater

©

iPOWERLINETOHEATER

24 VOLT FIELDWIRING BOX

5 518 06 1602 O0

Page 6: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

Fig. 7 - Single Point Connections for Non-Fused Heater

©

©

POWERLINETO HEATER

24 VOLT FIELDWIRING BOX

518 06 1602 O0 6

Page 7: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

Fig. 8 - Dual Point Connections for Fused Heater

SECOND FIELD

POWER LINE TO

UNIT CONTACTOR

FIRST FIELD POWERLINE TO HEATER

/"

24 VOLT FIELDWIRING BOX

Fig. 9 - Dual Point Connection for Non-Fused Heater

SECOND FIELD POWER

LINE TO UNIT CONTACTOR

FIRST FIELD POWERLINE TO HEATER

24 VOLT FIELDWIRING BOX

? 518 06 1602 00

Page 8: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

START-UP

ELECTRICALSHOCKHAZARD

Failure to follow this warning could result in personal injuryor death.

Before proceeding, verify that all wiring is correct per factoryapproved schematic. Notify factory immediately of anydiscrepancies.

NOTE: Refer to base unit installation instructions as required.1. Check for loose terminal connections.

2. Check that all fuse and circuit breaker short circuit

interrupting ratings are adequate.

3. Turn on unit and heater power.

4. Set thermostat to call for heat.

5. Check operation of heater.6. Check that airflow across the heater is at or above the

minimum recommended CFM requirement (See unitinstallation instructions). Adjust indoor blower heat speedas required. Check that duct system conforms to staticpressure limits in Table 1.

NOTE: See Table 1 for Non-Export units (with -3, -5 or -6 aselectrical option-see product data).

7. Any modifications or repairs to this equipment withoutwritten permission from the factory will be done at theinstaller's own risk and expense.

TROUBLESHOOTING

1. Fuses - Malfunction wilt interrupt power to the unit. Checkfor cause of failure, replace fuses.

2. Limit Switch - Malfunction prevents heating element(s)from being energized. Replace switch if malfunctionoccurs,

3. Contactor - Malfunction wilt not allow heater to energize.Replace faulty contactor. Do not attempt to replace coil ordress contacts.

UNIT

(60 HZ UNITS) 05LO024 030 036 042 048 N

Table 1 -Maximum Duct Static Pressure for Non-ExportUnits (IN. W.C.) (pa)

MAXIMUMSTATICPRESSUREUNIT SIZE

.30 .30" .30 .50 .50 .50Heat Pump (75) (75) (75) (125) (125) (125)

Electric .30 .30 .30 .50 .50 .50

Cooling (75) (75) (75) (125) (125) (125)

*15kW size 030 heat pump must be used with medium speed only. Allothers can be run at low speed.

Fig. 10 - Fused Heater Control Box

HeaterFuse Block -- --

Field WireConnection

\\

i

Heater Door(Fused Models Only)Shown Open --

I

C°n_Parc_SS°vvire In 1 _

Yellow & Black _ _-

1Strain Relief for .J_Field Power Wires /

L

i

Attach Heaterwith 5 Screws

Door Latch

Low Voltage Wiring

Ground LugLocation

518 06 1602 O0 8

Page 9: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

Fig. 11 - Schematic Location for Fused Heaters

L_

iT.,ss,o oplc

to de-energize this equipment, Open all remote 1

disconneots befor_ servicing.

DO not block or otherwise cover control cabinet

with in_uletion or other meterial8.

HeaterSchematic

m

_i I

)

Heater DoorShown Closed

Fig. 12 - Schematic Location for Non-Fused Heater

ELECTRIC HEATERWIRING LABEL

9 518 06 1602 O0

Page 10: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

Table 2 - Electric Heater Usage Chart--Non-Export Units

PAD& WPA3 ( C Series) PAD4 (C Series)

EHNA Code kW V PH Fuse 24 30 36 42 48 60 24 30 36 42

05KON UL 5 230 1 0 x x x x x x x x x x x

05K4F UL 5 230 1 4 x x x x x x x x x x x

07KON UL 7.2 230 1 0 x x x x x x x x x x x

07K4F UL 7.2 230 1 4 x x x x x x x x x x x

IOKON UL 10 230 1 0 x x x x x x x x

IOK4F UL 10 230 1 4 x x x x x x x x x x x

15K4F UL 15 230 1 4 x x x x x x

15K6F UL 15 230 1 d x x x x x x x x x

20K4F UL 20 230 1 4 x x

20K6F UL 20 230 1 d x x x x x

05HON UL 5 230 3 0 x x x x x !!_!_!J_ii_i!!_!i!!!!!i!!i!!i!!i!!i!!i!!i!_ii_i!!i!!i!!i!!i!!i!!i!!i!!i!iii_!_!_ix x x x

IOHON UL 10 230 3 0 x x x x x x x x x

IOH6F UL 10 230 3 d x x x x x x x x x

15HON UL 15 230 3 0 x x x x x x x x x

15H6F UL 15 230 3 d x x x x x x x x x

20H6F UL 20 230 3 d x x x x x

05LON UL 5 460 3 0 x x x x x x x

IOLON UL 10 460 3 0 x x x x x x x

15LON UL 15 460 3 0 x x x x x x x

20 460 3 0 x x x x x20LON UL

48 60

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

= base unit not offeredx = Approved combination

Table 2 -- Electric Heater Usage--Non-Export Units Chart Continued

PHD3, WPH3 (C Series) PHD4 (D Series)

EHNA Code kW V PH Fuse 24 30 36 42 48 60 24 30 36 42 48 60

05KON UL 5 230 1 0 x x x x x x

05K4F UL 5 230 1 4 x x x x x x x x x x x x

07KON UL 7.2 230 1 0

07K4F UL 7.2 230 1 4 x x x x x x x x x x x x

IOKON UL 10 230 1 0

IOK4F UL 10 230 1 4 x x x x x x x x x x x x

15K4F UL 15 230 1 4

15K6F UL 15 230 1 d x x x x x x x x x x

20K4F UL 20 230 1 4

20K6F UL 20 230 1 d x x x x x x

05HON UL 5 230 3 0 x x x x x x x x x x

IOHON UL 10 230 3 0 x x x x x x x

IOH6F UL 10 230 3 d x x x x x x x x x x

15HON UL 15 230 3 0

15H6F UL 15 230 3 d x x x x x x x x x x

20H6F UL 20 230 3 d x x x x x x

05LON UL 5 460 3 0 x x x x x x x x

IOLON UL 10 460 3 0 x x x x x x x x

15LON UL 15 460 3 0 x x x x x x x x

20LON UL 20 460 3 0 iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii!ili!iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii!ix x × iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii;iiliiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii!ilx x x

= base unit not offeredx = Approved combination

518 06 1602 O0 10

Page 11: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

Table 2 -- Electric Heater Usage--Non-Export Units Chart Continued

PAD5(C Series) PHD5 (C Series)

36 42

x

EHNA Code kW V PH Fuse 24 30 36 42 48 60 24 30 48 60

05KON UL 5 230 1 0 x x x x x x x

05K4F UL 5 230 1 4 x x x x x x x x

07KON UL 7.2 230 1 0 x x x x x x

07K4F UL 7.2 230 1 4 x x x x x x x x x x x x

10KON UL 10 230 1 0 x x x

10K4F UL 10 230 1 4 x x x x x x x x x x x x

15K4F UL 15 230 1 4

15K6F UL 15 230 1 6 x x x x x x

20K4F UL 20 230 1 4

20K6F UL 20 230 1 6 x x x x

111001866

tom BROWNTO UNIT CONTROL

WIRING 24V wl ¢@HITE

YELLO_"k_]_]_ TO COMPRESSOR

CONTACTOR 10 AWG ,u BI ¢C,K

L1

L2

FUSE BLOCK

T_

YELLOW

YELLOW

i ii i ii i ii i i

iii ELI AUTO-LIMIT

I

KILOWATTSVOLTS-PH-HZCONTROL VOLTSSTEPSHEATER AMPS

HEATER FUSES T1, T2M1, M2

7.5/10.0208/240-1-6024236.1/41.760A50A

*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C

Use copper conductor wiring only.Field wire, NEC Class I**Replace Auto Reset with Therm-O-Disctype 60TX11-F165Replace with 250VAC type SIo-Blow fuses

*** Wires for single point connection only. Removewires for dual point connection.

I

Control WiringPower Wiring

Field Wiring

Fig. 13 - EHNA10K4F Wiring Diagram

A10348

11 518 06 1602 00

Page 12: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

111001867

COM BROW[,ITO UNIT CONTROL

WIRING 24V Wl WHITE

W2 .... vJ#J_.T .....W3 PINK

YELLOW_'_ TO COMPRESSOR

CONTACTOR 10 AWG = BL_CI(

L1,

_t

FUSE BLOCK

BLACK

_ 8_CK

11 1 _L, AOTO-L,_,T

1 --

11

HR3

YELLOW

YELLOW

KILOWATTS 11.3/15.0

VOLTS-PH-HZ 208/240-1-60CONTROL VOLTS 24

STEPS 3HEATER AMPS 54.2/62.5

HEATER FUSES T1, T4 30A

T2, T3 60A

*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C

Use copper conductor wiring only.Field wire, NEC Class I

**Replace Auto Reset with Therm-O-Disctype 60TX11 -F165 & 64TX11-F165

Replace with 250VAC type Slow-Blow fuses

*** Wires for single point connection only. Removewires for dual point connection.

I

Control WiringPower WiringField Wiring

A10349

Fig. 14 - EHNA15K4F Wiring Diagram

518 06 1602 00 12

Page 13: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

111001868

TO UM_ CONTROL

WIRING 24V

_ TO COMPRESSOR

CONTACTOR10AWG

L1

y_

mv_ m m m _HtTF ....... ,_

YELLO_

• nl_6K

BLACKJ

/I II II II I

_BLACK _

HR1

EL1

AUTO_IMIT

i

YELLOW

KILOWATTSVOLTS-PH-HZ

CONTROL VOLTSSTEPSHEATER AMPS

3.8/5.0

208/240-1-60241

18.1/20.8

*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C

Use copper conductor wiring only.Field wire, NEC Class I

**Replace Auto Reset with Therm-O-Disctype 60TX11-F165

*** Wires for single point connection only. Removewires for dual point connection.

Control WiringPower WiringField Wiring

IFig. 15 - EHNA05KON Wiring Diagram

A10350

13 518 06 1602 00

Page 14: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

112005832

TO UNIT CONTROL

WIRING 24V

_',_ TO COMPRESSORCONTACTOR 10 AWG

L1,

iw4 GR_y

YELLOW

11111t1111L__

'1

11t1

L_EL3 AUTO LIIvlIT

_cK YEL "k'_

HR3

EL4 AUTO LIIvlITBLACK YEL

EL1 AUTO-LIMIT

EL2 AUTO LIIvIIT

LA _, YEL "#'#

KILOWATTSVOLTS-PH-HZ

CONTROL VOLTSSTEPSHEATER AMPS

HEATER FUSES T1, T4T2, T3

15.0/20.0

208/240-1-60244

72.2/83.360A

60A

*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C

Use copper conductor wiring only.Field wire, NEC Class I

**Replace Auto Reset with Therm-O-Disctype 64TXl 1-F165

Replace with 250VAC type Slo-Blow fuses*** Wires for single point connection only. Remove

wires for dual point connection.

I

Control WiringPower WiringField Wiring

A10351

Fig. 16 - EHNA2OK4F Wiring Diagram

518 06 1602 00 14

Page 15: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

111001870

TO UNIT CONTROL

WIRING 24V

COM BROWN

_ .... WriTE--,V_ VIOLET

,V4 CRA_

YELLOW_ _J__J_ TO COMPRESSOR

COMTACTOR 10 AWG _ BIAOK

L2

FUSE BLOCK

T4

B_CK

t

I BLACK EL1 YEt AUTO-LIMIT

EL2 AUTO LIMIT

1 1 BR2

t EL3 AUTO LIMIT

tHR3

EL4 AUTO LIMITBLACK YEL

YELLOW

YELLOW

YELLOW

KILOWATTS 15.0/20.0VOLTS-PH-HZ 208/240-1-60CONTROL VOLTS 24STEPS 4HEATER AMPS 72.2/83.3

HEATER FUSES M1, M2 50AT1, T4 60AT2, T3 60A

*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C

Use copper conductor wiring only.Field wire, NEC Class I

**Replace Auto Reset with Therm-O-Disctype 64TX11-F165

Replace with 250VAC type SIo-Blow fuses

*** Wires for single point connection only. Removewires for dual point connection.

Control Wiring

Power Wiring

Field Wiring

IFig. 17 - EHNA20K6F Wiring Diagram

A10352

15 518 06 1602 O0

Page 16: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

111001871

TO UNIT CONTROL

WIRING 24V

_€ "k _1_ TO COMPRESSOR

CONTACTOR 10 AWG

L2

IM

L3

CON BROV_N

Wl WHITE

aWE

YELLOW

,M nlA_K 1"

f

IM

SLACK

YELLOW

II II I

EL1 AUTO-LIMIT

_cK YEL _Y_

. EL2 _ AUTO LIMIT

EL3 AUTO LIMIT

HR3

BLUE

BLACK •

KILOWATTS

VOLTS-PH-HZCONTROL VOLTS

STEPSHEATER AMPS

3.8/5.0208/240-3-60

243

10.4/12.0

*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C

Use copper conductor wiring only.

Field wire, NEC Class I**Replace Auto Reset with Therm-O-Disc

type 60TXl 1-F165 & 64TX11-F165

*** Wires for single point connection only. Removewires for dual point connection.

Control WiringPower WiringField Wiring

IFig. 18 - EHNAO5HON Wiring Diagram

A10353

518 06 1602 00 16

Page 17: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

111001872

TO UNIT CONTROLWIRING 24V

_ TO COMPRESSOR

CONTACTOR10AWG

L1

,i,I

L2

,.M

L3

CON

Wl

BROWN

WHITE

..... V OLET,_*_

YELLOW

BLACK

• I BLAcK

YELLOW

JBLUE

/

BLUE

II

I II I

I --II

EL1 AUTO-LIMIT

BLACK YEt _

EL2 AUTO LIMIT

____ H

EL3 AUTO LIMIT

HR3

YELLOW

®BLACK

,)

KILOWATTS

VOLTS-PH-HZCONTROL VOLTS

STEPSHEATER AMPS

7.5/10.0208/240-3-60

243

20.8/24.1

*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C

Use copper conductor wiring only.

Field wire, NEC Class I**Replace Auto Reset with Therm-O-Disc

type 60TX11-F165 & 64TX11-F165

*** Wires for single point connection only. Removewires for dual point connection.

Control Wiring

Power Wiring

Field Wiring

IFig. 19 - EHNAIOHON Wiring Diagram

A10354

17 518 06 1602 00

Page 18: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

111001873

COM

TO UNIT CONTROLWIRING 24V wl

_ w,__2

"k _k _1_ TO COMPRESSOR

CONTACTOR 10 AWG

L2

L3

BLUE

YELLOW

,, nlA_K l"

,M

BROWN

WHITE

BLACK

YELLOW

_ BLUE

_ /

BLUE

11 1I 1

EL1 AUTO-LIMIT

_cK YE[

. EL2 W'/,r AUTO LIMIT

EL3 AUTO LIMIT

HR3

BLACK

KILOWATTS

VOLTS-PH-HZCONTROL VOLTS

STEPSHEATER AMPS

11.3/15.0208/240-3-60

243

31.3/36.1

*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C

Use copper conductor wiring only.

Field wire, NEC Class I**Replace Auto Reset with Therm-O-Disc

type 60TX11-F165 & 64TX11-F165

*** Wires for single point connection only. Removewires for dual point connection.

Control WiringPower WiringField Wiring

IFig. 20 - EHNA15HON Wiring Diagram

A10355

518 06 1602 00 18

Page 19: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

......... . 112005837q

TO UNIT CONTROL WHITE

WIRING 24V

_... _-2 v__LECT "_ j

___ _ ...... _ iI"il

_I_I_ TO COMPRESSOR _ _UE , ICONTACTOR O AWG _ELLQW -- I ' I V I ' --.

B .... _'_ .... I 1,,_1 I_,,_L B[K_ A A AE,_ A A A A A A A A YEL ,_UTO L NIT

" x/ r ' I _ - vvvvvvvvvvvvv - _.=___ - -FUSE BLOCK I HR1

_TI_ JJ-- --_[ J I L_ EL2 AUTO LIMIT

......

" qll L--_ EL3 AUTO LIMIT

I I / BLU BLK

L ....... ._ /"- _LUE

TT "_ _ BLUE J

L3 -- _

KILOWATTS 11.3/15.0VOLTS-PH-HZ 208/240-3-60CONTROL VOLTS 24STEPS 3HEATE R AM PS 31.3/36.1

HTR FUSES T1, T3, T5 50AM1, M2, M3 40A

*Power supply wiring per NEC & local codes.Suitable for at least 75 ° CUse copper conductor wiring only.Field wire, NEC Class I**Replace Auto Reset with Therm-O-Disctype 60TX11-F165 & 64TXl 1-F165Replace with 250VAC type Slow-Blow fuses*** Wires for single point connection only. Removewires for dual point connection.

I

Control WiringPower WiringField Wiring

Fig. 21 - EHNA15H6F Wiring DiagramA10356

19 518 06 1602 00

Page 20: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

112005838

COM BROWNTO UNIT CONTROLWIRING 24V _','1 _fHITE

PINK

_1_1_1_ TO COMPRESSOR BLUE YELLOW

CONTACTOR 10 AWG EL1 AUTO-LIMIT

FUSE BLOCK

YELLOW EL2 _ AUTO LIM T

L__ L__

BLUE BLU EL3 BLK AUTO LIMIT

YELLOW

L2 BLACK

L3 _ BLUE

I_l *Power supply wiring per NEC & local codes.L_J Suitable for at least 75° C

Use copper conductor wiring only.Field wire, NEC Class I**Replace Auto Reset with Therm-O-Disc

KILOWATTS 14.9/19.9 type 64TX11-F165 & 60TXl 1-F165VOLTS-PH-HZ 208/240-3-60 Replace with 250VAC type Slow-Blow fusesCONTROL VOLTS 24 *** Wires for single point connection only. RemoveSTEPS 3 wires for dual point connection.HEATER AMPS 41.4/47.9HTR FUSES T1, T3, T5 60A Control Wiring

Ul, M2, M3 40A Power Wiring

Field Wiring

IFig. 22 - EHNA2OH6F Wiring Diagram

A10357

518 06 1602 00 20

Page 21: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

112005839

COM BROWNTO UNIT CONTROL

WIRING 24V wl WHITE

_ TO COMPRESSOR

CONTACTOR10AWG

L2

_r

L3

,i,,ll

,i

BLUE

YELLOW

BLACK i 8_cK+i +LUEl

AUTO-LIMIT

LS1 EL1BLACK BLACK RED

KILOWATTS

VOLTS-PH-HZCONTROL VOLTS

STEPSHEATER AMPS

5.0480-3-602416.0

*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C

Use copper conductor wiring only.

Field wire, NEC Class I**Replace Auto Reset with Therm-O-Disc

type 64TXX11-F165

*** Wires for single point connection only. Remove

wires for dual point connection.

Control WiringPower WiringField Wiring

IFig. 23 - EHNAO5LON Wiring Diagram

A10358

21 518 06 1602 00

Page 22: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

112005840

COM BROWNTO UNIT CONTROL

WIRING 24V wl WHITE

_ TO COMPRESSOR

CONTACTOR10AWG

L2

L3

BLUE

YELLOW

,, BIA_K l"

I

1

AUTO-LIMIT

LS1 EL1

BLACK RED

AUTO LIMIT

LS1 EL2

YELLOW

EL3

KILOWATTS

VOLTS-PH-HZCONTROL VOLTS

STEPSHEATER AMPS

10.0480-3-6024112.0

*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C

Use copper conductor wiring only.

Field wire, NEC Class I**Replace Auto Reset with Therm-O-Disc

type 64TXX11-F165

*** Wires for single point connection only. Remove

wires for dual point connection.

I

Control WiringPower WiringField Wiring

A10359

Fig. 24 - EHNAIOLON Wiring Diagram

518 06 1602 00 22

Page 23: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

COM BROWNTO UNIT CONTROL

WIRING 24V Wl WHITE

'_ '_ '_ TO COMPRESSOR

CONTACTOR 10 AWG

L1

L2

L3

BLUE

YELLOW

BLACK "_BLACK

IBLACK

LE__BLACK BLACK EL1 YELLOWAUTO-LIMITLS1 r _

CONTACTOR E

AUTO-LIMIT

'/t_ BLUE

KILOWATTSVOLTS-PH-HZ

CONTROL VOLTSSTEPS

HEATER AMPS

15.0480-3-6024118.0

*Power supply wiring per NEC & local codes.Suitable for at least 75° CUse copper conductor wiring only.Field wire, NEC Class I**Replace Auto Reset with Therm-O-Disctype 64TXX11 -F165*** Wires for single point connection only. Removewires for dual point connection.

IFig. 25 - EHNA15LONWiring Diagram

Control Wiring

Power Wiring

Field Wiring

A10360

23 518 06 1602 00

Page 24: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

TO UNIT CONTROL

WIRING 24V

_1__1__1_ TO COMPRESSOR

OONTACTOR 10AWG

L2

CON BROWN

Wl WHITE

IM BLUE

YELLOW

BLACKBLACK

1 j I# .... OW BLUE

] h1BLACK

AUTO-LIMIT i/"

1 " 1 BLACK LS1 BLACK | EL1 :YELLOW

CONTACTOR E

t LSI I EL3

_'# BLUE

KILOWATTSVOLTS-PH-HZ

CONTROL VOLTSSTEPS

HEATER AMPS

20.0480-3-6024124.1

*Power supply wiring per NEC & local codes.Suitable for at least 75° CUse copper conductor wiring only.Field wire, NEC Class I**Replace Auto Reset with Therm-O-Disctype 64TXX11 -F165

*** Wires for single point connection only. Removewires for dual point connection.

IFig. 26 - EHNA2OLONWiring Diagram

Control Wiring

Power Wiring

Field Wiring

A10361

518 06 1602 00 24

Page 25: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

111001880

COM BROWN"k_'_ TO UNIT CONTROL

WIRING 24V wl WHITE

TO COMPRESSOR

CONTACTOR10AWG

YELLOWlU

L1

L2

IIII

EL1 AUTO-LIMIT

KILOWATTS 3.8/5.0

VOLTS-PH-HZ 208/240-1-60CONTROL VOLTS 24

STEPS 1HEATER AMPS 18.1/20.8

HEATER FUSES T1, T2 30A

M1, M2 50A

*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C

Use copper conductor wiring only.

Field wire, NEC Class I**Replace Auto Reset with Therm-O-Disc

type 60TX11-F165

Replace with 250VAC type Slo-Blow fuses

*** Wires for single point connection only. Remove

wires for dual point connection.

I

Control WiringPower WiringField Wiring

Fig. 27 - EHNA05K4F Wiring DiagramA10362

25 518 06 1602 00

Page 26: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

111001881

TO UNIT CONTROL

WIRING 24V

_ _ -_1_ TO COMPRESSOR

CONTACTOR 10 AWG

L1

t_

tom BROWN

Wl WHITE

C_,,-__-LLC=...... -qBLACK

,,,I

,M

BLACK

1 1I I 1I I 1I I 1

1EL1 AUTO-LIMIT

1

BLACK EL2 YEL AUTO'LIMIT

YELLOW

YELLOW/

KILOWATTS

VOLTS-PH-HZCONTROL VOLTS

STEPSHEATER AMPS

7.5/10.0208/240-1-60

242

36.1/41.7

*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C

Use copper conductor wiring only.

Field wire, NEC Class I**Replace Auto Reset with Therm-O-Disc

type 60TXl 1-F165

*** Wires for single point connection only. Remove

wires for dual point connection.

I

Control WiringPower WiringField Wiring

A10363

Fig. 28 - EHNAIOKON Wiring Diagram

518 06 1602 00 26

Page 27: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

111001882

TO UNIT CONTROL

WIRING 24V

CON BROWNX

Wl WHITE -4W2 VIOLET

YELLOW

_ TO COMPRESSOR _1

CONTACTOR 1O AWG BLACK

FUSE BLOCK

EL2 AUTO LIMIT

_j

Lfl ................._ i EL3 AUTOLIMIT"" ............_ i i : v vvv vvv vvv vv v ** .........,\_..

T3 ..... ..............................i ....................................................................._£_£E .............................................................................................................................................................................................................................................................................................................................................................../

YELLOW " i

\/

L2

....................._ z

KILOWATTS ! !,.31!5,0 ..........................................

VO LTS- PH- HZ ..... .........................

CONTROL VOLTS .....24 ..........................................................................STEPS 3HEATE R AM PS 54.2/62.5

HEATER FUSES T1, T4 ....60AT2, T3 .....30A ................................................................................M 1, M2 .....50A ...............................................................................

*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C

Use copper conductor wiring only.Field wire, NEC Class I

**Replace Auto Reset with Therm-O-Disctype 60TX11-F165 & 64TXl 1-F165

Replace with 250VAC type SIo-Blow fuses

*** Wires for single point connection only. Remove

wires for dual point connection.

I

Control WiringPower WiringField Wiring

Fig. 29 - EHNA15K6F Wiring DiagramA10364

27 518 06 1602 00

Page 28: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

112OO5847

COM BROWN

TO UNIT CONTROLWIRING 24V wl WHITE

W2 _LE_

BLUE"k_k_l_ TO COMPRESSOR

YELLOW

CONTACTOR10AWG: _IAnK

FUSEBLOCK

T1

L2 T_

L3 T_

F

fBLK

_ YEL

BLUE

I11 HR1

I_ AUTO-UM'T

illI _ _ AUTOLIMIT

_ _ EL2 _t,k LS1

J •

BLUE ,_

KILOWATTS

VOLTS-PH-HZCONTROL VOLTS

STEPS

HEATER AMPS

HTR FUSES T1, T3, T5M1, M2, M3

7.5/10.0

208/240-3-6024

320.8/24.135A

40A

*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C

Use copper conductor wiring only.Field wire, NEC Class I**Replace Auto Reset with Therm-O-Disc

type 60TX 11-F 165 & 64TX 11 -F 165

Replace with 250VAC type SIo-Blow fuses*** Wires for single point connection only. Remove

wires for dual point connection.

I

Control WiringPower WiringField Wiring

Fig. 30 - EHNAIOH6F Wiring DiagramA10366

518 06 1602 00 28

Page 29: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

111001885

COM BROWNTO UNIT CONTROLWIRING 24V wl WHITE

4

_ TO COMPRESSOR ,ICONTACTOR10AWG

L1

,,11

,i

,i

YELLOW

BLACK

BLACK

YELLOW

YELLO_V

1 11 11 11 1

EL1 AUTO-LIMITBLACF YEL "_t "]1

HR1

BLACK EL2 YEL AUTO-LIMIT

KILOWATTS

VOLTS-PH-HZCONTROL VOLTS

STEPSHEATER AMPS

5.4/7.2

208/240-1-60242

25.9/30.0

*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C

Use copper conductor wiring only.

Field wire, NEC Class I**Replace Auto Reset with Therm-O-Disc

type 60TX11-F165

*** Wires for single point connection only. Remove

wires for dual point connection.

I

Control WiringPower WiringField Wiring

A10367

Fig. 31 - EHNA07KON Wiring Diagram

29 518 06 1602 00

Page 30: MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 … · 2012. 10. 19. · EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5,

111001886

CO_4 BRO_NTO UNIT CONTROLWIRING 24V wl WHITE

*** TOOTO2_'RESS%G,: ...._.......",

___FUSE BLOCK

1_2

BLACK

1 11 I 1I 1 1I 1 1

1l EL1 AUTO-LIMIT

1

HR2

YELLOW

KILOWATTS 5.4/7.2

VOLTS-PH-HZ 208/240-1-60CONTROL VOLTS 24

STEPS 2HEATER AMPS 25.9/30.0

HEATER FUSES T1, T3 60A

M1, M2 50A

*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C

Use copper conductor wiring only.Field wire, NEC Class I

**Replace Auto Reset with Therm-O-Disctype 60TX11-F165

Replace with 250VAC type Slow-Blow fuses

*** Wires for single point connection only. Remove

wires for dual point connection.

I

Control WiringPower WiringField Wiring

A10368

Fig. 32 - EHNA07K4F Wiring Diagram

518 06 1602 00 30