7/28/2019 Modul Izolator Scurtcircuit 6202l
1/2
5.SERVICESCHEDULETable1
Task Periodicity1. Inspectionforvisiblephysicaldamage weekly2. Satisfactoryoperationtest monthly3. Checkandcleandustcontamination every6months4.
Check
and
clean
base
and
head
contacts
and
connections
Annually
6.WARRANTYThemanufacturerguaranteesproductcompliancewiththeEN54-7:2001.Thewarrantperiodis36months from thedateofpurchase,providing that requirementscovered insection5havebeenobserved.
UniPOSLtdSHORTCIRCUITISOLATOR 6202L
1.INTRODUCTIONShort circuit isolator6202L isdesigned tocutoff (to isolate)ashortcircuitedsegment ina line(loop).Inthiswaythevariableunitsautomaticfiredetectors,manualcallpointsandothers,whicharenot in theshortcircuitedsegment remainactiveand the line (loop)protection level ishigher.Whereisolatorsarenotincluded,incaseofashortcircuitthefirecontrolpanelinterruptsthepowersupplyoftheline(loop)andallunitsstopworking.Asegmentisapartofaloopbetweentwoadjacentisolators.2.TECHNICALDATA2.1.Supplyvoltage -(18-26)VDC2.2.Currentconsumptioninquiescentstate,at26VDC -notmorethan100A2.3.Equivalentresistanceofisolatorinaline:
-inquiescentstate -6,5k
2.4.Connectiontofirecontrolpanel -two-wire2.5.Degreeofprotection -IP40
2.6.Operating temperaturerange -minus10/plus602.7.Temperaturelimits -minus40/plus702.8.Relativehumidityresistance -(92+3
-2)%at 25
7/28/2019 Modul Izolator Scurtcircuit 6202l
2/2