Upload
kopi143
View
219
Download
0
Embed Size (px)
Citation preview
7/29/2019 Module (05) High-Voltage A.C.pdf
1/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page1of35
Module
05High-Voltage A.C
Circuit Breakers
7/29/2019 Module (05) High-Voltage A.C.pdf
2/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page2of35
5.1 INTRODUCTION
In this chapter, the constructional aspectsof circuit breakers have been briefly discussed. The
theoreticalaspectsregardingtransientvariationofcurrentandvoltage,arcextinctionprocessand
thevarious typesofcircuitbreakershavebeendescribed indetail inotherchapters.Thecircuitbreakersareautomaticswitcheswhichcaninterruptfaultcurrents.Insomeapplicationslikesingle
phase traction system, single pole circuit breakers are used. The part of the circuit breakers
connected inonephase iscalled the 'pole'.Acircuitbreakersuitable for threephasesystem is
calleda'triplepolecircuitbreaker'.
Each pole of the circuit breaker comprises one or more 'interrupter' or 'arcextinguishing
chambers'.Theinterruptersaremountedonsupportinsulators.Theinterrupterenclosesasetof
'fixedandmovingcontacts'.Themovingcontactscanbedrawnapartbymeansoftheoperating
linksoftheoperatingmedium.Theoperatingmechanismofthecircuitbreakergivesthenecessary
energyforopeningandclosingofcontactsofthecircuitbreakers.
The arc produced by the separation of current carrying contacts is interrupted by a suitable
medium and by adopting suitable techniques for arc extinction. The circuit breaker can be
classifiedonthebasisofthearcextinctionmedium.
5.2THE
FAULT
CLEARING
PROCESS
During thenormaloperatingcondition thecircuitbreakercanbeopenedorclosedbyastation
operatorforthepurposeofswitchingandmaintenance.Duringtheabnormalorfaultyconditions
the relays sense the faultandclose the tripcircuitof thecircuitbreaker.Thereafter thecircuit
breakeropens.Thecircuitbreakerhastwoworkingpositions,openandclosed.Thesecorrespond
toopencircuitbreakercontactsandclosedcircuitbreakercontactsrespectively.Theoperationof
automaticopeningandclosingthecontact isachievedbymeansoftheoperatingmechanismof
the circuit breaker. As the relay contacts close, the triple circuit is closed and the operating
mechanismofthecircuitbreakerstartstheopeningoperation.
The contacts of the circuit breaker open and an arc is drawn between them. The arc is
extinguished at some natural current zero of a.c. wave. The process of current interruption is
completedwhenthearcisextinguishedandthecurrentreachesfinalzerovalue.Thefaultissaid
tobecleared.Theprocessoffaultclearinghasthefollowingsequence:
FaultOccurs:As the faultoccurs, the fault impedancebeing low, thecurrents increaseand therelaygetsactuated.Therelaytakessometimetocloseitscontacts.
7/29/2019 Module (05) High-Voltage A.C.pdf
3/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page3of35
Relay contacts close the trip circuitof the circuitbreaker closes and trip coil is energized. The
operating mechanism starts operating for the opening operation. The circuit breaker contacts
separate.
Arc is drawn between the breaker contacts. The arc is extinguished in the circuit breaker by
suitabletechniques.Thecurrentreachesfinalzeroasthearcisextinguishedanddoesnotrestrike
again.
5.3 TRIPCIRCUIT
The basic connection of the circuitbreaker control, for the opening operation, is illustrated in
Figure5.1.
Figure(5.1)SimplifiedDiagramofCircuitBreakerControlforOpeningOperation
Theprotectedcircuit is shownbydashed line.Whena faultoccurs in theprotectedcircuit, the
relayconnectedtotheCTandPTactuatesandclosesitscontacts.Currentflowsfromthebattery
(source) in the trip circuit.As the trip coilof the circuitbreaker (C.B.) is energized, the circuit
breaker operating mechanism is actuated and it operates for the opening operation. Auxiliary
switchisanimportantiteminthecircuit.
7/29/2019 Module (05) High-Voltage A.C.pdf
4/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page4of35
5.4 HISTORICALREVIEW
Long ago, before 1875, the problem of the circuit breaking was relatively simple. The power
systemswerebelow15kVandfaultMVA1wasoftheorderof250.Mercuryswitchesandknife
switcheswereused forswitching.Fusesgaveshortcircuitprotection.Today thepowersystemshavebecomecomplexandhuge.Thevoltagesusedfortransmissionareoftheorderof220kV,
400kV,500kVand750kV.Thecapacityof thecircuitbreakersonEHV lines isof theorderof
35,000MVA.Today'scircuitbreakersarefaster(2cycles,2.5cycles).
Theoilcircuitbreakerwasdevelopedaround1885.Intheoilcircuitbreakers,dielectricoilisused,
forinsulatonandforarcextncton.Later(1900),arcextnctondeviceswereintroduced.Thearc
extinctiondevicesaresemiclosedchambersofdielectricmaterial,whicharefixedtothecontacts
forassistingthearcextinctioninoilcircuitbreakers.Minimumoilcircuitbreakersweredeveloped
toreplacethebulkoilcircuitbreakers.Today theminimumoilcircuitbreakersarebeingwidely
used.
The firstshortcircuit testingplantwasbuilt in1916 inEurope.Theairblastcircuitbreakerwas
developed in 1930's. In air blast circuit breakers, high pressure air is forced on the arc at the
instantofthecontactseparationandarcgetsextinguishedbytheblasteffect.Theairblastcircuit
breakershaveseveraladvantagessuchasfastoperation,highrupturingcapacityetc.TheAirBlast
CircuitBreakerbecamequitepopularby1950.
The inventon of SF6 circuit breakers is a very important development in the circuit breaker
technology. SF6 (sulphurhexafluoride) gas has good dielectric and arc quenching properties.
DoublepressuretypeoutdoorSF6circuitbreakersweredevelopedbyWestnghouse,USAduring
1950's. This was followed by development of single pressure puffer type SF6 circuit breakers
(1970).TodaySF6circuitbreakersandSF6 insulatedmetalenclosed switchgearareverywidely
usedforvoltagesfrom72.5kVto760kV.
Vacuumwasknowntobeagooddielectricmedium.Buttocreatevacuumandmaintainvacuum
wasaproblem.Vacuum interruptershavebeendevelopedduring1960'sandarebeingusedfor
applicatonsbelow36kV.
Otherinterestingdevelopmentsforlowandmediumvoltageapplicationsincludeminiaturecircuit
breakers,mouldedcasecircuitbreakers,contactors,solidstateswitchingdevices.Miniaturecircuit
breakersandmouldedcasecircuitbreakershavecertainadvantagesoverconventionalHRCfuses.
1 Fault MVA =610
3 IV whereV is the service voltage in volts and I is the fault current in amperes
7/29/2019 Module (05) High-Voltage A.C.pdf
5/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page5of35
Contactorshavebeendeveloped forawide rangeofa.c.andd.c. ratings.Solid state switching
devicesarebeingincreasinglyusedinindustrialcontrols.
5.5CLASSIFICATION
BASED
ON
ARC
QUENCHING
MEDIUM
Thecircuitbreakerscanbeclassifiedonthebasisofratedvoltages:Circuitbreakersbelowrated
voltageof1000Varecalledlowvoltagecircuitbreakersandabove1000Varecalledhighvoltage
circuitbreakers.
Thetypeofthecircuitbreakerisusuallyidentifiedaccordingtothemediumofarcextinction.The
classificationofthecircuitbreakersbasedonthemediumofarcextinctionisasfollows:
AirBreakCircuitBreaker.
MiniatureCircuitBreaker.
OilCircuitBreaker(TankTypeorBulkOil).
MinimumOilCircuitBreaker.
AirBlastCircuitBreaker.
SulphurHexafluorideCircuitBreaker
(SinglePressureorDoublePressure).
Vacuumcircuitbreaker.
Eachcircuitbreakerwillbestudiedthoroughlyinthesubsequentsections.Thesecircuitbreakers
employvarioustechniquestoextinguishthearcresultingfromseparationofthecurrentcarrying
contacts. The mode of arc extinction is either 'high resistance interruption' or 'zeropoint
interruption'.
HighResistanceInterruption:Inthisprocesstheresistanceofthearc is increasedbylengthening
andcoolingittosuchanextentthatthesystemvoltageisnolongerabletomaintainthearcand
thearcgetsextinguished.Thistechniqueisemployedinairbreakcircuitbreakersandd.c.circuit
breakers.
LowResistanceor ZeroPoint Interruption: In thisprocess, the arc getsextinguished atnatural
currentzeroofthealternatingcurrentwaveandispreventedfromrestrikingagainbyrapidbuild
upofdielectric strengthof thecontact space.Theprocess isemployed inalmostalla.c.circuit
breakers.
Each leadingmanufacturerofcircuitbreakerdevelops twoormore typesofcircuitbreakers for
everyvoltageclass.Theconstructionofthecircuitbreakerdependsupon itstype(arcquenching
medium),voltageratingandstructuralform.
7/29/2019 Module (05) High-Voltage A.C.pdf
6/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page6of35
Airbreak circuitbreakers:Utilizeair at atmosphericpressure forarcextinction.Airblast circuit
breakers:Utilizehighpressurecompressedairforarcextinction.Theyneedcompressedairplant.
BulkoilandMinimumoilcircuitbreakers:UtilizeDielectricoil(Transformeroil)forarcextinction.
InBulkoilcircuitbreakers,thecontactsareseparatedinsideasteeltankfilledwithdielectricoil.Inminimumoil circuitbreakers the contracts are separated in an insulating housing (interrupter)
filledwithdielectricoil.
SF6circuitbreakers:SulphurHexaFluoridegasisusedforarcextinction.Therearetwotypes:
SinglepressurepuffertypeSF6circuitbreakers,inwhichtheentrecircuitbreakerisfilledwithSF6
gasat singlepressure (4 to6kg/cm2).Thepressureandgasflow required forarcextncton is
obtainedbypistonaction.
DoublepressuretypeSF6circuitbreaker inwhichthegasfromhighpressuresystem isreleased
into low pressure system over the arc during the arc quenching process. This type has been
supersededbyputtertype.
Vacuum circuit breakers: In vacuum circuit breaker the fixed and moving contacts are housed
inside a permanently sealed vacuum interrupter. The arc is quenched as the contacts are
separatedinhighvacuum.
AbriefcomparisonbetweenthedifferenttypesofcircuitbreakersisgiveninTable5.1.
5.6 TECHNICALPARTICULARSOFACIRCUITBREAKER
Acircuitbreakerisidentifiedbythefollowingparticulars:Typeofmediumforarcextinction.
Ratedvoltage.Thiscorrespondstohighestpowerfrequencyvoltagebetweenphasetophase,e.g.
3.6kV,7.2kV,12kV,36kV,72.5kV,145kV,245kV.
Ratedbreakingcurrent.
Otherratedcharacteristics.
Typeofconstruction.
Indoormetalcladtype
Outdoortype
MetalcladSF6gasinsulatedtype.
Typeofoperatingmechanism.
Totalbreaktme,e.g.2cycle,3cycle,5cycle.
Structuralform:
LivetanktypeDeadtanktype.
7/29/2019 Module (05) High-Voltage A.C.pdf
7/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page7of35
Table(5.1)ComparisonofCircuitbreakers
Type Medium Voltage, breaking capacity Design Features Remarks
1. Air-break
circuit-
breaker
Air at atmospheric
pressure
430-600 V, 5-15-35 MVA
recently 3.6-12 kV, 500
MVA
Incorporates: Arc
runners, arc
splitters, magnetic
coils
Used for
medium/low
voltage, A.C.,
D.C., Industrial
circuit-breakers.
Have current
limiting features.
Miniature
C.B.
Air at atmospheric
pressure
430-600 V small size, current
limiting feature
Used for low and
medium voltages.
2. Tank type
oil circuit-
breaker
Dielectric oil 12-36 kV One tank up to 36
kV, 3 tanks above
36 kV, fitted with
arc control
devices
Getting obsolete,
used up to 12 kV,
500 MVA
3. Minimum-
oil circuit-
breaker
Dielectric oil 3.6-245 kV The circuit
breaking chamber
is separate from
supporting
chamber. Small
size, arc control
device used
Used for metal
enclosed
switchgear up to
36 kV. Outdoor
type between 36
and 245 kV
4. Air-blast
circuit-
breaker
Compressed air
(20-30 kgf/cm2)
245 kV, 35,000 MVA up
to1100 kV, 50,000 MVA,
also 36 kV, 500 MVA
Unit type
construction,
several units per
pole, auxiliary
compressed air
system required
Suitable for all
EHV applications,
fast opening-
closing. Also for
arc furnace duty
5. SF6
circuit-
breaker-
Single-
pressurepuffer type
SF6 gas
(5 kgf/cm2)
145 kV, 7500 MVA
245 kV, 10,000 MVA
12 kV, 1000 MVA
36 kV, 2000 MVA
Live tank/Dead
tank design,
single pressure
type preferred
Suitable for SF6
switchgear, and
medium voltage
switchgear. EHV
circuit breaker.Maintenance free
6. Vacuum
circuit-
breaker
Vacuum Preferred for indoor
switchgear rated up to 36
kV, 750 MVA
Variety of
designs, long life,
modest
maintenance
Suitable for a
variety of
applications from
3.6 kV up to 36 kV
7. H.V.D.C.
circuit-
breaker
Vacuum or SF6 +500 kV DC, 15 kA/20 kA Artificial current
zero by switching
in capacitors
Recently
developed, used
in HVDC systems.
Installed in USA
7/29/2019 Module (05) High-Voltage A.C.pdf
8/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page8of35
5.7 ASSEMBLYOFOUTDOORCIRCUITBREAKERS
Thedesignfeaturesofanindividualcircuitbreakerdependuponitsvoltage,otherratingsandthe
type.Thecircuitbreakersmanufacturedbydifferentcompaniesmayhavequitedifferentdesign
patterns. However, a general description of an EHV circuit breaker can be given to cover thevarious types. The low voltage circuit breakers have different design features as the voltage,
capacityandfrequencyofoperationisdifferentfromthatoftheEHVcircuitbreakers.
Figure5.2 shows three identcalpolesofa circuitbreakerassembledonacommon frame.The
distancebetween thepoles isdeterminedby the voltagebetween their conductingparts. The
currentcarryingpartsaresupportedbydielectricmaterials.Thecurrent is interrupted inclosed
chamberknownasarcextnctonchamber(item3)orinterrupter.Thecontacts(10)aregenerally
inpairsoffixedcontactandmovingcontact.
Circuitbreakerpole
Operatingmechanism
Interrupter
Supportporcelain
Conductor
Terminals
Operatingrod
Insulatingoperatingrod
Frame
Contacts
Transfer contacts between
movingcontactsandterminal
Linkages
Figure(5.2)DiagramIllustratingtheAssemblyofanOutdoorCircuitBreaker
Themovingcontact ismovedmechanically.Toachievethisoperationofclosingandopening,an
OperatingMechanismisnecessary.Thefunctionofoperatingmechanismistoopenandclosethe
contactswhendesired. Theoperatingmechanismmaybecommonforthethreepolesormaybeseparateoneforeachpole.
7/29/2019 Module (05) High-Voltage A.C.pdf
9/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page9of35
Inadditiontotheoperatingmechanism,there isa 'ControlCabinet'orwhat isknownas 'Switch
Cabinet'.Thevariouscontrol,interlocking,indicatingconnectionsarethroughthiscontrolcabinet
placednear thebreaker.Thus a complete threephase circuitbreaker consistsof the following
subassemblies:
ThreePoles
OperatingMechanism
ControlCabinet
Auxiliaries
5.8 STRUCTURALFORMOFCIRCUITBREAKERS
Thestructuralformofacircuitbreakerdependsonitstype,ratedvoltage,typeofdesign,typeof
operatingmechanismetc.Inindoor,metalcladswitchgear,thethreepolesofthecircuitbreaker
aremountedonawithdrawaltruck.Suchconfigurationiscommonlyusedforratedvoltagesupto
36kV.
For36kVandabove,outdoorcircuitbreakersarepreferred.Thestructuralformofoutdoorcircuit
breakers depends on rated voltage, number of interrupters per pole and type of operating
mechanism.Circuitbreakersofratedvoltagesuptoand145kVgenerallyhaveasingleinterrupter
per pole. In such a structural form, the interrupter porcelain and support porcelain should
withstandthepowerfrequencyandimpulsetestvoltagesinternallyandexternally.245kVcircuit
breakers have two or more identical interrupter units (elements) per pole. The number of
interruptersperpoledependsupon the ratedvoltageand ratedbreaking currentof the circuit
breaker.Suchcircuitbreakerpolecomprises identicaltwininterrupterunitsmountedonasingle
support porcelain column in T or Y formation. Such a structural form is preferred in outdoor
minimum oil circuit breakers, airblast circuit breakers and live tank type outdoor SF6 circuit
breakers. The configuration with modular construction has advantages with reference to the
shortcircuit testing and the interchangeability of interrupter modules. The single twin
interruptermodulecanbetestedforshortcircuitduties insteadoftestingafullpolecomprising
severaltwininterruptermodules.Thisiscalled'UnitTesting'or"ElementTesting'.
Inmultibreak typeconstruction,voltagegradingcapacitor isconnectedacrosseach interrupter
for equalizing the voltage shared by the interrupter during interruption process. Preclosing
resistors are also connected in parallel whenever necessary. The preinsertion resistors (Pre
closing resistors) are necessary to limit overvoltages occurring during closing unloaded
transmissionlines.
7/29/2019 Module (05) High-Voltage A.C.pdf
10/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page10of35
Circuitbreakersforratedvoltageabove145kVgenerallyhave independentpoleoperaton.The
operatingmechanismofeachpoleisindependentandeachpolecanbetrippedindependentlyby
aseparaterelay.Independentpoleoperationisdesirableforimprovingthestabilityofthepower
system. Structural form of EHV metalclad SF6 insulated switchgear is quite different thanconventionalequipmentdiscussedabove.
5.9 ELECTRICALCONTACTSINCIRCUITBREAKERS
Thepowercurrentpassesthroughtheconductngmaterialintheinterruptngchamber(Fig.5.3).
Variouspartsthatarejoinedtogetherformtheconductingmaterial.Thedifferentjunctionsform
theelectricalcontacts.Electricalcontactisobtainedbyplacingtwoconductingobjectsinphysical
contact.Thiscanbedoneinseveralways.Eventhoughthereisawiderangeofcontactdesignsin
interruptingchambers,theymaybegroupedinfourmajorcategories:
Makebreakcontacts whichmaymakeorbreakunderload;
Slidingcontacts whichmaintaincontactduringrelativemovement;
Fixedcontacts whichmaybeclampedtogetherpermanentlyforyearsandneveropened.
Demountablecontacts whichmakeorbreakoffload.Usuallyseeninmetalcladmedium
voltageswitchgear.
Figure(5.3)FlowofCurrentthroughConductingMaterialinInterruptingChamber
Figure5.4 isasymbolicschematcofatypicalcontactarchitectureandclearlyshowsthecurrent
flow through three of the main types of contacts during the sequence of events of an open
operation.Inallthreetypes,thecontactismadebythetouchingsurfacesofeachcomponent.
7/29/2019 Module (05) High-Voltage A.C.pdf
11/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page11of35
Figure(5.4)Schematicdiagramoftypicalcontactarchitecture
5.9.1 MAKEBREAKCONTACTS
The typesofmakebreak contacts canbe subdividedbypower rating, startingwith the
highest:
Highcurrent,highvoltagecircuitbreakercontacts,whichdisconnectlargeelectricalloads,
andproduce arcs, are containedwithin special arcing chambers.Thesemaybe in air at
normal pressure or in a blast of air, in Sulfur Hexafluoride (SF6), in oil or another arc
extinguishingmedium,includingavacuum.
It includes a moving contact and a stationary contact. Usually one of them is a ring of
sprungcoppercontactfingers(insertontype,Fig.5.5orbu type),ortheother isasolid
rodofcopper.Thecontactsmaybetippedwithanarcresistantmaterialtoresisterosion
from the highpower arc, and the surfaces may be plated (e.g. with silver) to improve
conductivity. Themechanicalpropertiesof copper combinedwith itsexcellentelectrical
conductivity and good arcing endurance in oilhavemade it thepreferred metal in this
application.
7/29/2019 Module (05) High-Voltage A.C.pdf
12/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page12of35
Figure(5.5)InsertionTypeContact
In vacuum circuitbreakers, the contactsare also generally copper,mixedwith tungsten
andspeciallyshaped toensureproperdistributionof theelectric fieldandmovementof
thearcroot.Smallerairbreakcircuitbreakers(mediumvoltage),usecopperinallinternal
conducting parts, but the contacts are often faced with a silver based alloy to resist
welding.Suchcircuitbreakers,beingprotectivedevices,rarelyopenorclose.
5.9.2 SLIDINGCONTACTS(FIG.5.6)
Thesecanbeofverydifferentnature.High speed,heavycurrent types, theyareusually
found inpower interrupterchambers.Thesecontactsmusthaveaveryhighresistanceto
mechanicalwear,astheirrelatvespeedmayreach10meterspersecondormore.
5.9.3 FIXEDCONTACTS
These include awide rangeofbolted and crimped contacts.A clampedjoint avoids the
reduction in cross section caused by drilling to insert bolts, and gives a more uniform
distribution of the contact force, making the contact more efficient and hence running
cooler.Boltingisusedbecauseitischeapandconvenient.
Figure(5.6)SlidingTypeContact
7/29/2019 Module (05) High-Voltage A.C.pdf
13/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page13of35
Crimpedjointsemploytheultimateextremeforceofcontactmaking,causingthemetalto
flowandmakeapermanentconnection.The troublefreenatureofthesejoints,andthe
simplicityandrapidityofthecrimpingoperationmakesthistypeofjointveryattractivefor
permanentconnections.Boltedorcrimpedcontactsareused in interruptingchamberstosecureandtomaintaintheintegrityoftheelectricalcomponent.
5.9.4 DEMOUNTABLECONTACTS
Found in medium voltage metal clad breakers. It helps in taking the breaker off the
networkbyeasilyslidingitoffthebusbarsformaintenancepurposes.Thishastobedone
offload.
Figure(5.7)Demountabletypecontact
These contacts, like the makebreak contacts, may be carrying high currents at high
voltages(e.g.highvoltageisolatorsorhighormediumvoltagefusecontacts).Theyhaveto
carrycurrentreliablyfor longperiods,withoutoverheatingor lossofcontact,butdonot
makeorbreakcurrent.Theyarenotsubjectedtothestressofarcing;hencetheydonot
get the inherentcleaningactionassociatedwith it.Theyarefrequentlydesignedtohave
somefrictionalactiononclosingtoremovesuperficialoxideorcorrosionfilmswhichmight
impedecontact,andcopperand itsalloysarethemostfrequentlyusedmaterialsforthe
bulkofdemountablecontacts.
The characteristicof these contacts is that theyhaveahigh contact force,muchhigher
thanforcircuitbreakersofsimilarcurrentrating,butnotsohighasthecontactforceina
boltedcontact,becauseof theexcessivemechanicalwearwhichwouldbecausedwhen
separatingthecontacts.
7/29/2019 Module (05) High-Voltage A.C.pdf
14/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page14of35
5.9.5 CONTACTRESISTANCE
Aswe said, thecontactoccurswhen two surfaces touch.For theelectriccurrent, if it is
conductivematerial, itmeans apath for it to flow. Observation on a microscopic scale
shows that the contact surface is actually rough even though it seems smooth to theunaided eye. In fact, as the microscope shows, the real contact between two surfaces
happens through a number of small surfaces, called micro contacts (Fig. 5.8), spread
randomly insidethe limitsofthevisiblecontactarea. It isthesumoftheareasofallthe
microcontactsthatconstitutestheeffectivecontactarea.
Figure(5.8)SchematicDiagramofMicroContactAreas
Since theresistanceofanelectricalcontact is inverselyproportional to thecontactarea,
thesmallertheeffectveareathegreatertheresistance(Fig.5.9).
Figure(5.9)SchematicDiagramoftheEffectiveAreainaContact
5.9.6 EFFECTOFCONTACTRESISTANCE
WhenacurrentIpassthroughanareaAthathasaresistanceR,theEnergyEabsorbedbyA
is:
E=RI2t
wheretisthetimedurationofI.
7/29/2019 Module (05) High-Voltage A.C.pdf
15/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page15of35
WeknowthattemperatureTisdirectlyrelatedtoEbythefollowingequation:
E= T
where isafunctionoftheheatdissipationrate.
ForaconstantcurrentIo,ifRincreases,Ethenincreases,leadingtoincreasingtemperature
of thecontact. IfTcontinues to increase thematerialof thecontactcanreach itsmelting
point,leadingtoitsdestructon(Fig.5.10).
Figure(5.10) Contactdestruction
5.9.7 ELEMENTSAFFECTINGTHECONTACTRESISTANCE
5.9.7.1 OXIDATION
Athinlayerofinsulatingoxidecoveringtheareaofasinglemicrocontactwouldhavelittle
effectontheconductivityofthecontactasawhole.Assoonastheoxidelayerextendstoa
significant number of microcontacts, the currentbearing area would reduce, thus
increasing its resistance. Increased resistance will increase the contact temperature,
leadingtoitsdestruction.
Allambientatmospheresthatcontainsgasescapabletoreactwiththecontact'smaterial,
suchasO2,SO2,H2O,H2S,etc.,wouldbefavorabletoproducingoxidelayerseventhough
thecontact isclosed.Withtime, thegaswouldsucceed inpenetratingandreactingwith
thecontactsurfacetodegradeitscharacteristicsandtoincreaseitsresistance.
Figure5.11showstheresistancevalueincreasingwith tme.Aswecansee,theresistance
changeisnotsignificantuntilacertainpointintimewherethedegradationincreasesfast.
Similarresultsareobtainedforcoppercontactsinoil.
7/29/2019 Module (05) High-Voltage A.C.pdf
16/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page16of35
These results show interesting behavior and indicate the urgency of a maintenance
interventionwhenacontact'sresistancestartstoincrease.
5.9.7.2CONTACT
WEAR
Mechanically, itcanbeduetothemovementandfrictionofthecontactsandelectrically
due to thearceffect (mainly themakebreak contact).Contactweardirectlyaffects the
contact resistanceandmakes it increasedramatically if thewear is inanadvancedstate
(Fig.5.12).
Figure(5.11)ChangeofContactResistancewithTime
Figure(5.12)AdvancedWearinaContact
5.9.7.3 FRETTING
A formof acceleratedoxidation ispossible, if the contact surfaces experience a cycling
movementrelativelytoeachother.Forexample,thecontactswouldnotcloseatthesameareaeach tme(Fig.5.13).
7/29/2019 Module (05) High-Voltage A.C.pdf
17/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page17of35
Figure(5.13)Changeincontactarea
Thisphenomenonwasnoticed longagobut itsmagnitudewas recognizedonly recently.
When a contact moves from its previous position, a part is exposed to the ambientatmosphere.Anoxidationlayerthenforms.Whenthecontactgoesbacktothisposition,it
breaksthethin layerandpushes itaside.Thisphenomenonrepeatsmanytimesuntilthe
oxidation layerbecomesofasignificant thickness,enough to increase its resistance.The
resistanceincreasesrapidlyrightaferitstartstochange.Figure5.14showssimilarcaseto
figure5.11,butaccelerated.
Figure(5.14)Changeofcontactresistancewithtimeincaseoffrettingphenomenon
5.9.7.4CONTACT
FORCE
Asknown,theresistanceRisfunctionofthecontactmaterial'sresistivity andareaS,(R=
/S).
Sisthesumofallcontactpointsareas.Thecontactpointsareasarefunctionoftheapplied
forceFandthematerialhardnessH,(kisaconstant).
7/29/2019 Module (05) High-Voltage A.C.pdf
18/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page18of35
IfFdecreases,SdecreasesaswellandR then increases.Fcandecreasedue todifferent
factors,forexample:
Excessivewearofcontactsurface;
Fatigueofcontactspringsovertime;Chemicalreactionofspringmaterialwithambientatmosphere;
Looseormisalignedcontact,etc.
Springmaterialsare thusan importantelement to take intoconsideration.By the same
logic,animportantprecautiontotakeistoavoidlettingthespringbeacurrentpath,asthe
increaseinitstemperaturewouldcauseaweaknessoftheresultantforceF.
5.9.7.5TEMPERATURE
ForanincreasingtemperatureTofthecontacts,thematerialofthecontactsmaysoftento
thepointwhereitwillreducethecontactforce,leadingtoaquickincreaseofthecontact
resistance.
5.10 OPERATINGMECHANISMS
5.10.1 GENERAL
Circuitbreakershavetwoworkingpositionsopenandclose.Duringtheclosingoperation,
thecircuitbreakercontactscloseagainstopposing forces.During theopeningoperation,
theclosedcontactsareseparatedasearlyaspossible.Operatingmechanismsareprovided
to achieve the opening and closing operations. The main requirement of the operating
mechanismistoopenandclosethecontactsofthecircuitbreakerwithinaspecifiedtime.
Theoperatingmechanismshallprovidethefollowingconsecutivefunctions:
Chargingandstoringofenergy
Releaseofenergy
Transmissionofenergy
Operationofthecontacts
In addition, an operating mechanism shall provide control and signaling interface to a
networks control and protection system. Operating mechanisms are also necessary for
isolators.Figure5.15andFigure5.16showthelocatonoftheoperatngmechanism.
7/29/2019 Module (05) High-Voltage A.C.pdf
19/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page19of35
Figure5.15
Threepole operated circuit breaker with one
interrupterperpole.
Figure5.16
One pole of a singlepole operated circuit breaker with
twointerruptersperpole.
1.Breakingunit 5.Tripmechanism 9.Gradingcapacitor(ifrequired)
2.Supportinsulator 6.Gassupervision(onoppositeside) 10.Preinsertionresistor(PIR)(ifrequired)
3.Supportstructure 7.Pullrodwithprotectivetube 11.Primaryterminals
4.Operatngmechanism 8.Positonindicator
Thecircuitbreakeroperatingmechanismsmustbecapableofdealingwith large forces,athigh
speeds, with complete reliability even if the circuit breaker has remained idle for a prolonged
duration.Theopeningshouldbefast, inordertoreducecircuitbreakertime.Theoperatingtimebetween
instantofreceivingtripsignalandfinalcontactseparaton isoftheorderof0.03second, i.e.1.5
cyclesinmodernEHVcircuitbreakers.Inslowcircuitbreakersusedindistributionsystemtimecan
beabout3cycles.
Whileclosing,thecontactclosureshouldbefast,sure,withouthesitation,withadequatecontact
pressureat theendofcontact travel. If theseconditionsarenot satisfied, contactwelding can
result.
7/29/2019 Module (05) High-Voltage A.C.pdf
20/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page20of35
Theoperatingmechanismsshouldbecapableofgivingthespecifieddutyofthebreaker(sequence
ofopeningandclosingas specified instandard specifications).A requirementcommon tomost
circuitbreakers, regardlessof the typeofoperatingmechanisms, is tocarryoutanopenclose
open (O 0.3s CO)sequencewithnoexternalpowersupplytotheoperatingmechanism.Thecircuit breaker shall, after a closing operation, always be able to trip immediately without
intentionaltimedelay.Forcircuitbreakers intendedforrapidautoreclosing,theoperatingduty
cycleinaccordancewithIEC62271100is:
O 0.3s CO 3min CO
The tmeof3ministhe tmeneededfortheoperatngmechanismtorestoreitspoweraferaO
0.3s CO.Modernspringandhydraulicoperatngmechanismsdonotneed3mintorestoretheir
power,asanalternative IECspecifies that the tmevalues15s.or1min.canalsobeused.The
dead tmeof0.3 s isbasedon the recovery tmeof the air surrounding anexternal arc in the
system(i.e.ashortcircuit).SometimestheoperatingsequenceCO 15s COisspecified.
Thebreakershouldalsopasstheoperationaltestswhichascertainthecapabilityoftheoperating
mechanisms.The interlocksareprovidedbetweenbreaker isolatorandearthingswitch,soasto
avoid wrong operation and to assure operation in a correct sequence. The functions of the
operatingmechanismscanbesummarizedasfollows:
Toprovidemeanswherebythecircuitbreakercanbeclosedrapidly,withouthesitationat
allcurrentsfromzerotoratedmakingcurrentcapacity.
Toholdthecircuitbreakerinclosedpositionbytogglesorlatchestillthetrippingsignalis
received.
Toallowthecircuitbreakertoopenwithoutdelayimmediatelyonreceivingtrippingsignal.
Toperformtheautoreclosurecycle.
Toperformtherelatedfunctionssuchasindication,control.
5.10.2 CLOSINGOPERATION(C)
Normally,closingthecircuitbreakercontactsduringnormalloadconditionsdoesnotcause
any difficulty. The operating mechanism has to overcome friction and accelerate the
moving masses. However, when the circuit breaker has to close against a short circuit,
additionalthermalstressesandelectromagneticstressesareinvolved.
InEHVcircuitbreakers,thearcisestablishedpriortofinalcontacttouch.Thisisknownas
prearcing.Prearcingcauseshighertemperaturestresses.Thecontactsshouldclosewithsufficientspeedtominimizetheprearcing.
7/29/2019 Module (05) High-Voltage A.C.pdf
21/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page21of35
Assoonas thecontactscloseonanexistingshortcircuit,breaker issubjected tomaking
current. The electromagnetic forces, setup by the making current, tend to repel the
contacts. The circuit breaker should have rated making capacity, i.e. the highest peak
current against which the circuit breaker canbe closed at a given voltage. The makingcapacityofthecircuitbreakerdependsupon the forceandspeedwithwhich theclosing
operationiscarriedout.
Whileclosingthecircuitbreaker,theoperatingmechanismshouldhaveenoughpowerto
overcometheopposingforcesandacceleratethemovingcontactassemblyrapidlywithin
specifiedshorttime.
Theopposing
forces
during
closing
operation:
Electromagnetic forces between contacts: When the contacts touch during the closing
operation,electromagneticforcesappearatthe instantofcontacttouch,theirmagnitude
being proportional to square of the current and the direction being opposite to the
directionclosing.These forcesare large if thebreaker isclosingonexistingshortcircuit.
Breakershouldbecapableofclosingonshortcircuit.
Actionofoperatingspring:Themovingcontactsofcircuitbreakersareopenedbyspring
pressure.Whileclosing,thesespringsopposetheclosure.Inertiaofmovablesubassembly:
The movable subassembly contacts, their holders, tension rods, operating links of
operatingmechanisms,etc.Themassof thesubassemblies isquite large inEHVcircuit
breakers. And their inertia tries to oppose rapid acceleration. In modern EHV circuit
breakers,thesepartsaremadeaslightaspossible.
Opposing forcesdue tomedium such asoil, SF6 gas:Themovable subassemblyhas to
moveindielectricmediumwhichis,insomecases,compressedoratarehighpressureand
density.Thetotalforcesoftheoperatingmechanismshouldbemorethanthesumofthe
abovementionedopposingforces.Friction:Staticanddynamic.
5.10.3 OPENINGOPERATION(O)
The opening operation is significant in the faultclearing process. As the trip coil is
energized, the opening operation is initiated. The energy required for the opening
operationisobtainedfromoneofthefollowingmethods:
Openingspringschargedduringtheclosingoperation Highpressurehydraulicoilstoredinaccumulators
7/29/2019 Module (05) High-Voltage A.C.pdf
22/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page22of35
Highpressurecompressedairstoredinauxiliaryairreceivers.
Thefunctionalrequirementsoftheopeningmechanismareasfollows:
Toacceleratethemovingmassesincludingcontactsandlinkagesrapidlytoachieve
desiredopeningcharacteristic.
Toachievedesiredspeedofcontactatcontactseparationandduringtheopening
stroke(3to7m/s).
Todampthespeedattheendofthetravelbydampers.
Theforcesandenergyshouldbeadequatetocaterofthefollowing:
Opposingforcesduringopeningoperating
Electromagneticforcesduetocontactgrip:Thefingercontactsarespringloadedandtheir
grip opposes the movement of moving contract. During the shortcircuit condition, the
electromagneticforcestendtoincreasethegripofthefingercontactassembly.Theforce
ofcontactgrip increases inproportiontosquareofcurrent.Hence it issignificantduring
highershortcircuitcurrents.
Friction:Thevariousoperating links,bearingsurfaces,matingsurfacesbetweenmovable
and fixed parts, etc. offer static friction. The frictional component depends upon the
coefficientof friction, smoothnessofmating surfaces,configurationofmovingpartsetc.
Highfrictioncanreducetheinitialspeedofmovingcontactwhichmayresultindisastrous
consequenceoffailureofthecircuit breakertoquenchthearc.
Inertiaofmovableparts:Energyintheoperatingmechanismisutilizedinacceleratingthe
movablesubassembliestorequiredspeed.Opposingforcesduetoquenchingmedium:The
quenching medium (compressed air, dielectric oil, SF6 gas) itself may offer substantal
opposingforcestothemovement.
Theoperatingmechanisms shouldbe capableofovercoming theseopposing forcesend
shouldachievedesiredopening characteristicofcontact travelduringnormaland short
circuitopeningoperations.
5.10.4 CLOSINGFOLLOWEDBYOPENINGOPERATING(CO)
The rated operating sequence of the circuit breaker demands the operation 'CO'. The
operating mechanism should have enough stored energy and capability to perform COoperationandratedoperatingsequenceundershortcircuitcondition.
7/29/2019 Module (05) High-Voltage A.C.pdf
23/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page23of35
5.10.5TYPESOFMECHANISMS
Theoperatingmechanisms in circuitbreakersareeither 'dependable'or 'storedenergy'
type.Dependentoperatingmechanismsdependoncontinuityofpowersupplyormanual
forcesduringclosing.Theyareaccordinglycalledas:
Dependablemanualoperatingmechanisms
Dependablepowermechanisms
The stored energy type operating mechanisms are called independent operating
mechanisms as they are independent of continuity of power supply or the skill of the
operator.Insuchmechanisms,theenergyrequiredforclosingisstoredinachargedspring
orincompressedgas/hydraulicoil.
SpringOperatedMechanism:
In the spring mechanism, the energy for open and closeoperation is stored in springs.
When themechanisms control system receives anopenor close command, theenergy
stored inthespringwillbereleasedandtransmittedthroughasystemof leversand links
andthecontactswillmovetotheopenorclosedposition.
Inmostdesigns theclosing springhas two tasks: toclose thecontacts,andat the same
timetochargetheopeningspring(orsprings).Thusthecriteriastatedabovearefulfilled;
thecircuitbreakerinclosedpositionisalwaysreadytotrip.
AftertheO 0.3s COoperation,theclosingspringwillberechargedbyanelectricmotor,
aprocedurethatlasts1020seconds.ThecircuitbreakerwillthenbereadyforanotherCO
operation.
OneexampleofaspringmechanismisshowninFigure5.17.Thistypeofmechanismhasa
setofparallelhelicalwound springswith linearmotion. The electricmotor charges the
springsviaanendlesschain.Whentheclosing latch isreleased, theenergystored inthe
springsistransmittedviaarotatingcamdiscandasystemofleversandlinkstothecircuit
breaker pole or poles. The trip spring is in this case located outside the operating
mechanism. Insteadofhelical springs, clock springsmaybe applied.The function is the
same as for thehelical springsdescribed above. Figure 5.18 shows a systemwith clock
springforclosingoperation.Theadvantageofthespringoperatedmechanism isthatthe
systemispurelymechanical;thereisnoriskofleakageofoilorgas,whichcouldjeopardize
thereliability.Awellbalancedlatchingsystemprovidesstableoperatingtimes.
7/29/2019 Module (05) High-Voltage A.C.pdf
24/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page24of35
Furthermore, the spring system is less sensitive to variations in temperature than
pneumatic or hydraulic mechanisms are. This ensures stability even at extreme
temperatures.Thespringmechanismhasfewercomponentsthanhydraulicandpneumatic
mechanisms,whichimprovesitsreliability.
MotorDrive:
Oneof themost recentlydevelopedoperatingmechanisms is the electricalmotordrive
(Fig.5.19).Themotordriveusesaservomotortoperformasmoothandsilentoperatonof
the circuitbreaker. The operation is actively controlled by a sensor which continuously
readsthepositionofthemotorandadjuststhemotorcurrenttoobtainanoptimaltravel
curve.Theenergyisstoredinacapacitorbankandcanbedeliveredinstantaneouslytothe
converter,whichtransformsdcfromthecapacitorsandfeedsthemotorwithregulatedac.
Figure5.17
Springoperatingmechanismwithhelicalwound
springs.Tripandclosespringsinchargedposition.
ABBtypeBLG.
Figure5.18
Springoperatingmechanismwithclock
spring.ABBtypeBLK.
1.Linkgear 5.Closingdamper 1.Tripspring 5.Closinglatchwith
coil
2.Tripspring 6.Trippinglatchwithcoil 2.Linkgear 6.Motor
3.Closinglatchwith
coil
7.Openingdamper 3.Closespring 7.Openingdamper
4.Motor 8.Closesprings 4.Trippinglatchwith
coil
7/29/2019 Module (05) High-Voltage A.C.pdf
25/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page25of35
Figure(5.19)BlockdiagramshowingfunctionoftheMotorDrive
1. Charger unit that converts supply voltage and feeds the capacitors and internal
electronics.
2. Capacitorunitstorestheenergyforoperation.
3. Theconverterunittransformsdcfromthecapacitorstoacforthemotor.
4. Servomotor thatdelivers the force tomove the contacts, integratedposition sensor
givesinformationtothecontrolunit.
5. The I/O unit takes care of signaling between the station control system and the
operatingmechanism.
6. Control unit that controls and regulates the motion of the contacts. The interlock
functionsarealsohandledbythismodule.
7. Linkgearthattransformsrotarymovementtolinearmovement.
The major advantage of the motor drive is the minimized mechanical system, which
reduces theserviceneed toaminimumandmakes the technology ideal forapplicationswithfrequentoperation.
PneumaticOperatedMechanism:
The pneumaticoperated mechanism uses compressed air as energy storage, and
pneumatic cylinders for operation. Solenoid valves allow the compressed air into the
actuatingcylinderforclosingorforopening.Thecompressedairtank isreplenishedbya
compressorunit.Theuseofpneumaticoperatingmechanisms isdecreasing.Due to the
high operating pressure, there is always a risk of leakage of air, particularly at lowtemperatures.Thereisalsoariskofcorrosionduetohumidityinthecompressedair.
7/29/2019 Module (05) High-Voltage A.C.pdf
26/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page26of35
HydraulicOperatedMechanism:
Thehydraulicmechanismusuallyhasoneoperatingcylinderwithadifferentialpiston.The
oil is pressurized by a gas cushion in an accumulator, and the operating cylinder is
controlledbyamainvalve.
The hydraulic mechanism has the advantages of high energy and silent operation.
However,therearealsosomedisadvantages.Thereareseveralcriticalcomponentswhich
require specialized production facilities. The risk of leakage cannot be neglected as the
operatngpressure is intherangeof3040MPa(300400bar). It isnecessarynotonlyto
checkthepressureassuchbutalsotosupervisetheoillevelintheaccumulatoror,inother
words,thevolumeofthegascushion.Largevariationsintemperatureleadtovariationsin
operatingtime.
Untl recently several manufacturers used hydraulic mechanisms for their SF6 circuit
breakers.However,withtheintroductionofselfblastcircuitbreakers,therequirementof
highenergyforoperationisdecreasingandthehydraulicmechanismsarelosinggroundto
springoperatedmechanisms.
HydraulicSpringOperatedMechanism:
Thehydraulicspringoperatedmechanismisanoperatingmechanismcombininghydraulics
andsprings.Energy isstored inaspringset that is tensionedhydraulically.Adifferential
piston,poweredbyoil that ispressurizedby the springpackage, isused tooperate the
circuit breaker during opening and closing. Figure 5.20 gives an example of such
mechanism.
Figure(5.20)HydraulicspringOoperatedMechanism.ABBtypeHMB
7/29/2019 Module (05) High-Voltage A.C.pdf
27/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page27of35
OtherTypesofOperatingMechanisms:
In addition to the types of operating mechanisms mentioned above, there are other
variants, e.g. a design which basically applies the same technology as the pneumatic
mechanisms but with SF6 gas instead of air. Another design is the magnetic actuatormechanism,whichisappliedonlyforcertainmediumvoltagecircuitbreakers.
5.11 INTERLOCKS,INDICATIONANDAUXILIARYSWITCH
Interlockingdevicesarethosewhichmaketheoperationoftheswitchingdevicedependentupon
thepositionoroperationofotherequipment.Interlocksareprovidedasasafetymeasureagainst
erroneousoperationof a switchingdevice.The interlocks areof the following forms: Electrical
interlock, Mechanical Interlock. Electrical interlock can be used between remote equipment.
Mechanicalinterlockcanbeprovidedwheretheoperatingmechanismsofthetwoequipmentsare
inneighborhood.Theelectrical interlockcomprisescoilandbolt.Whenthecoil isenergized,the
bolt is drawn by magnetic attraction and the interlocking is achieved. Interlocks are provided
betweencircuitbreaker,isolatorandearthingswitchtoensurethefollowingsequence:
Whileopening:
Firsttoopen:Circuitbreaker
Nexttoopen:Isolato
Thentheearthingswitch(ifany)toclose
Whileclosing:
Openearthingswitch
Close:Isolator
Thenclosecircuitbreaker.
Thissequencemustbefollowedbecauseisolatorsarenoloaddisconnectingdevices.Theydonot
havebreakingcapacity,nordotheyhavemakingcapacity.Hencebreakerperformstheopeningandclosingduty.
Indicator or indicating device indicates whether the switching device is in 'open' or 'closed'
position.Suchindicationisavailableontheglasswindowonthecontrolcabinetnearthebreaker,
in formofa flagmarkedopen/close.Onbreakerpanel, the indication isobtainedbymeansof
lamps.Thus, from thecontrolroom, theoperatorcanknow thepositionofcircuitbreakersand
isolators.(BreakerPanelisinstalledincontrolroom.)
7/29/2019 Module (05) High-Voltage A.C.pdf
28/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page28of35
Auxiliaryswitcheshavestandardnumberofpairsofcontracts(6,8,and12).Auxiliaryswitchhas
two positions 'open' and 'close' corresponding to the position of the circuit breaker. In each
position, some auxiliary circuits are opened and some are closed. The auxiliary circuits serve
severalpurposessuchas:
Indication:Breakeropenorclosedbylamps,nearcircuitbreakerandataremoteplace.Electrical
Interlocks:Thebreaker is interlockedelectricallywith isolators.Theconnections to solenoids in
operatingmechanismaremade through theauxiliary switch.Connections for relaying,auxiliary
circuitsofoperatingmechanisms.Thevariousterminalsareconnectedinaterminalblocksinthe
operatingcubical.
5.12AUTO
RECLOSURE
Manyfaultsonoverheadtransmissionlinesaretransientinnature.Statisticalevidenceshowsthat
about90%offaultsonoverheadtransmissionlinesarecausedbylightningorbypassingofobjects
nearorthroughlines(birds,vines,treebranchesetc.).Theseconditionsresultingarcingfaultsand
the arc in the fault can be extinguished by deenergizing the line by simultaneous opening of
circuitbreakersonbothendsof the lineorononeendof the line.Since thecauseof transient
faultsmentionedabovedisappearsafterashorttimethecircuitbreakerscanbereclosedassoon
as the arc in fault has been extinguished and the path has regained its dielectric strength.
Reclosing of lines restores the supply. Continuity of service is the major advantage of
autoreclosure.Ifthefaultistransientonethenormalconditionisrestoredbyautoreclosure.
Figure(5.21)SequenceofAutoreclosureforEHV,bulk
PowerTransmissionLines,SingleShotScheme
7/29/2019 Module (05) High-Voltage A.C.pdf
29/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page29of35
Highspeedtrippingandhighspeedreclosing improvesthestabilityofpowersystem.Hencethe
circuitbreakersandrelayingonEHVlinesareprovidedwithautoreclosingfeature.Testsonhigh
voltage systems have shown that a reclosure in 12 cycles (0.24 sec) is practcal, the period
dependinguponthetimenecessarytodissipatetheionizedairofarcpath.TheAutoreclosingofEHVlinesisofhighspeedandsingleshot,i.e.onlyonereclosingisaempted(Fig.5.21).
5.13 AUTORECLOSUREOFEHVCIRCUITBREAKERSFORTRANSMISSION
[Voltages36to245kV,Breakingcapacites:25to40kA]
Experienceshowsthatgenerallyminimum tmeof0.2secondmustbeallowedtoelapsetoenable
thefaultzonetobecomedeionizedcompletely,henceadead tmeof0.3secondhasbeenchosen
asasafereclosure tme.Figure5.22illustratesatypicalcircuitbreakercontacttravelcharacteristc
andalsogivesascheduleoftypicaloperatingtimesoftheabovecircuitbreaker.Incaseofsome
otherrelayingthecyclemaydiffer.
Figure(5.22)FaultClearingandReclosingTimeSequence, ContactTravel.
LookinginFig.5.22,thefollowingsequencecanbeobserved:
Sequence
No.
Time in
1/100sec. Operation Remarks
1 0 Faultoccurs
Circuitbreaker closed. Protective gear
startsoperating
2 04 Relaytime Fastrelaying
3 4 Tripcircuitclosed Operatingmechanismstartstoopen
7/29/2019 Module (05) High-Voltage A.C.pdf
30/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page30of35
4 49 Openingtimeofbreaker
5 912 Totalbreaktime Breakerisof4cycles
6 1236 Deadtime 12cycles,fordeionization.CBremainsopen
7 27 Contactsstartclosing8 36 Contacttouchforreclose
9 40 Circuitbreakerreclosed
Will be opened again if fault persists and
willlockopen
10 Singleshot iscomplete,thecircuitbreakerwillremainclosed iffaulthasvanished.
CBwillopenagainiffaultpersistsandwillremainlockedopen
Several aspects need careful consideration while selecting autoreclosure schemes of EHV
transmissionlines.Someoftheseaspectsarediscussedhereinbrief.
Thefaultlevelsonsuchlinesarehigh(ascomparedwiththoseondistributionlines).Switchingof
suchlinesresultsinovervoltagetransientswhichareharmfultoinsulationandshould,therefore,
avoidedasfaraspossible.Thesynchronismbetweentwosidesofthecircuitbreakershouldnotbe
lost.Asregardsthesystemconsiderations,thestabilityofthesystem(conditionofsynchronism)
shouldnotbelostbythetimeofreclosing.Duetotheseaspects,theautoreclosureofEHVlineis
generallySINGLESHOTAUTORECLOSURE.Thebreakersused for suchautoreclosureare fast in
opening,closing. Further, the circuit breakers at both ends of the line should reclose almost
simultaneously.
ThetimingofEHVautoreclosureisbasedonthefollowingrequirements:
itshouldbeless,intheordertoavoidlossofsynchronismbetweeneithersidesoftheC.Bs
thearcinC.B.andthatinthefaultshoulddeionizedbeforeallowingreclosure
theoperatingmechanismsofC.B.toopenandtocloseshouldbecapableofachievingthedesired
timeschedule
C.Bsatbothendsofthelineshouldreclosesimultaneously.
Deionization time for arc space in fault on overhead linedepends on several aspects such as
magnitudeof faultcurrent,servicevoltage, lengthof linewindcondition,spacingofconductors
etc.Generallythetimeallowedisbasedonratedvoltageoflineandisasfollows:
7/29/2019 Module (05) High-Voltage A.C.pdf
31/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page31of35
VoltageofTransmission line,
(kV)
RatedVoltageofC.B.,
(kV)
MinimumDeionizationtime
necessary,Hz
66 72.5 5
132 145 9
220 245 14
400 420 18
Thecircuitbreakersshouldbecapableofwithstandingtheelectrodynamicstressincasetheyare
reclosingonanexistingshortcircuit.Thepressureinthereservoirgenerallyreducesafterthefirst
opening;therebythereisareductioninbreakingcapacityforthesubsequentopening.Thisaspect
shouldbetakencareofwhiledesigningthecircuitbreakerssuitableforautoreclosure.
5.14 AUTORECLOSUREFORDISTRIBUTIONLINES
Inruraldistribution,overhead linesareused.Thespacingbetweenconductors isrelativelyclose.
The disturbances on such lines are generally transient, as described earlier. Autoreclosure is
therefore, suitable in improving the continuity of service. The usual procedure was to reclose
circuit breaker three tmes between 15 to 120 seconds. If the breaker trips afer the third
reclosure, itopensandremainsopen.Theattendant therebyknows that thefault ispermanent
and sends electricians to locate and correct the fault. The autoreclosure cycle is illustrated in
Fig.5.23,but thesequencemayvary inothercases.Thispractce isnomore favored inmodern
distributionsystems.
Figure5.23Autoreclosurecycleofa12kVC.B.forruraldistributon
7/29/2019 Module (05) High-Voltage A.C.pdf
32/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page32of35
5.15 TRIPFREEFEATURE
Suppose the breaker has been instructed to close by manual instruction by pushing of push
button.Theoperatingmechanismwillstartoperatingforclosingoperation.Meanwhileafaulthas
takenplaceandarelayclosesthetripcircuitofthebreaker.TheTripFreemechanismpermitsthecircuitbreakertobetrippedbytheprotectiverelayevenifitisundertheprocessofclosing.This
feature is called Trip Free feature. Another feature of operating mechanisms is to prevent
Pumping,i.e.alternatetrippingandclosingiftheclosingbuttonisheldclosedduringafault.Inoil
circuitbreakersandpuffertypeSF6circuitbreakers,thecontactsmaybeallowedtotouchduring
theendoftheclosingstroke,beforethestartoftheopeningoperation.
5.16 MATERIALSANDSOMEDESIGNASPECTS
Thematerialsareimportantinswitchgearmanufacturing.Normallyalltheincomingmaterialsare
tested in the factorybeforeacceptance.Themanufacturermaintainswithhimall thenecessary
standardsofmaterialspecifications.Thesestandardsgivethespecificationsofchemical,electrical,
metallurgical and mechanical properties of the corresponding materials. The heat treatment,
surface treatment is equally important in the manufacturing process. The materials used in
switchgearsingeneralandcircuitbreakerinparticularcanbeclassifiedinausualway:
Conductingmaterials
Dielectricorinsulatingmaterials
Othermaterialsformanufacturing
Circuitbreakerdesignisgenerallybackedbythevastdesigndata,theexperienceandtheresearch
results.Beforedetaildesignoffunctionalsubassemblies,thestructuralformofthecircuitbreaker
isdecided.Thedimensiondrawingsaremadethis isfollowedbydetaildesignofsubassemblies
and components. Each subassembly and component isdesigned on the basisof its functional
requirementsandtheinformationalreadyavailablewiththedesigners.Aftercompletionofdesign
theprototypes aremanufactured.Theprototypes are subjected to rigorousdevelopment tests
andfullseriesofTypeTests.
7/29/2019 Module (05) High-Voltage A.C.pdf
33/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page33of35
Table(5.2)MaterialsusedinCircuitBreakers
Material Applications Remarks
Porcelain Enclosures for Interruptersupport, support for busbars
insulating tubes solid rods,
etc.
Compressionstrength6000kgf/cm2.Tensilestrength 3000 kgf/cm2. Ceramic material
madeby firingclay,glazingand firingagain.
Suitableforoutdooruse.
EpoxyResin Support insulators for indoor
applications, enclosures cover
encapsulation,etc.
Used insolidform.Obtainedbymixingwith
suitable hardener and curing a suitable
temperature, suitable fillers used. Not
suitableforoutdooruse.
Glass fibre reinforced
syntheticresin
Insulating drive rods,
insulating tubes for
interrupters
High tensile strength, withstand pressure,
dielectricstrength.
Polytetra fluroethelene
PTFE
Nozzles for SF6 Breakers,
bearings,Pistonrings,etc.
Low friction; arc resistant; can be
moulded/machined. Pure PTFE is insulating
usedwithvariousfillers.
Electrolytic Copper
(99.9%purity)
Busbars, main contacts
conductingparts,terminals
Electrical grade
aluminum
Busbars, conducting parts,
casting, terminals, enclosures
ofSF6GIS,enclosuresofbus
bars,enclosuresofbusducts
TungstenCopper Arcingcontacts 80% Tungsten, 20% copper, sintered
material
StainlessSteel Enclosures of SF6 GIS pars
enclosedcircuits
Copperbismuth
CopperChromium
Copperberrylium
Main contacts of Vacuum
interrupters,contactors
Highconductivity,lowweldingtendency
CURRENTSCARRYINGPARTS:
These includecontacts,contactstems,flanges,busbarsbushingconductors,connectorsetc.The
designofconductingpartsisbasedonthefollowingrequirements:
Temperature rise during normal continuous currenttemperature stresses during shorttime
current(rateddurationofshortcircuits.
Mechanicalstressduringopeningandclosingoperation.Mechanicalstressesduetoelectromagneticforcesundershortcircuitconditions.
7/29/2019 Module (05) High-Voltage A.C.pdf
34/35
LV,MV&HVSwitchgear
Module(05)HighVoltageA.CCircuitBreakers Page34of35
INSULATINGPARTS:
These include interrupterenclosures insulating supports for interrupters, insulating supports to
busbars, insulating pullrods, connecting the operating mechanism to the moving contracts,
insulatingtubesenclosingthearccontroldevicesetc. Insulatingpartsaresubjectedtodielectricstressesandmechanicalstresses.
5.17 DESIGNANDDEVELOPMENT
Circuit breaker design and development is relatively longer and costlier process as it involves
shortcircuit type testsandhighvoltage type tests.Circuitbreakersaredevelopmentbyvarious
leadingmanufacturers.Presently theresearchanddevelopment is focusedonSF6switchgear in
EHV range and vacuum switchgear in medium voltage range. Besides product development,
research is also in progress regarding system studies, testing procedures, reliability studies,
materials etc. Details about design and development are beyond the scope of this manual;
howeverthegeneralapproachismentionedinvariouschapters.Thedevelopmentofanewcircuit
breakercomprisesthefollowingmajoractivities:
Research: The research on arc quenching techniques, various thermal, electrical, mechanical
stressesundervariousswitchingconditions,designprincipleforarcquenchingetc.This iscarried
outinresearchlaboratories.
Design and development of Prototypes: The structural configuration is decided first. Then the
various subassemblies are designed and finally the complete breaker is designed. Full scale
prototypes aremanufactured.DevelopmentTesting:Variousdevelopment testsare carriedout
subassemblies,poles,mechanismandcompletebreaker.
TypeTests forCertifications: These areexhaustive tests asper standards.Actual Installation in
systemforobservingperformance.
5.18 SUMMARY
The circuit breaker assembly consists of switch cubicle, operating mechanism, poles, current
carryingparts,dielectricpartsandotherpartsoftheassembly.
The types of a.c. circuit breakers include (1) Airbreak circuit breaker, (2) Tank type oil circuit
breaker, (3)Minimumoilcircuitbreaker, (4)Airblastcircuitbreaker, (5)SF6circuitbreaker, (6)
Vacuuminterrupter.Thesearewidevarietiesofdesignsineachtype.
Airbreakcircuitbreakersemployairatatmosphericpressureforarcextinction.Theyincorporate
7/29/2019 Module (05) High-Voltage A.C.pdf
35/35
LV,MV&HVSwitchgear
arcrunnersandblowoutsforlengtheningthearc.Theyarewidelyusedforlow/mediumvoltages
andalsoforvoltagesupto12kV.Miniaturecircuitbreakersareusedfordomesticandcommercial
applications.Theyare finding increasinguse inmotorprotection, railway applications and low
voltage switchgear. Minimum oil circuit breaker has been developed for wide range of ratingbetween3.6to245kV.ABCBandSF6CBarepreferredforEHVapplicatons.Vacuuminterrupters
andcircuitbreakersarefinding increasinguseforawiderangeofapplicationsforratedvoltages
upto36kV.
SF6circuitbreakershavetwotypesofdesigns (1)doublepressuretype, (2)singlepressure type
(PufferType).
The operating mechanisms play an important role in the operation of circuit breakers and
isolators. The operating mechanisms are either 'dependent' or 'stored energy' type. Manual,
springloadedmanual,motorwoundspringtype,pneumatic,hydraulic,etc.arethevarioustypes
ofoperatingmechanism.Theoperatingmechanisms forEHVcircuitbreakersshouldbesuitable
forrapidautoreclosing.
Thematerialsused inswitchgear includeconductingmaterial likeelectrolyticcopper,aluminum;
insulatingmaterial likeporcelain, epoxy resins.Arcing contactsof circuitbreakers aremadeof
coppertungstenalloy.Themaincontactsaremadeofelectrolyticcopper.