Motor--protective circuit--breaker system J7M-AM/-BM
J7M--AM SystemRated operational current 25 A.Switching capacity up to 10 A, 100 kA/415 V.Switching capacity 16 A, 20 A , 25 A, 16 kA/415 V.Fixed short--circuit release 14 x Iu.Overload release, adjustable 0.6--1 x Iu.Single--phasing sensitivity.
Auxiliary contacts modulesON/OFF indication for motor--protectivecircuit--breaker.Differential fault indication of overload/short--circuittripping.
Current limiterIncreases the switching capacity of theJ7M--AM--16, --20, --25 motor--protectivecircuit--breakers to 100 kA/440 V.Suitable for individual and group protection.
AccessoriesUndervoltage release.Shunt release.Three--phase commoning link for series mounting.Door coupling handle IP65Indication of switch position: ON/OFF / Tripped.Lockable by means of 3 padlocks.Lockable rotary handle by means of 1 padlock.Surface mounting enclosures with IP55.Flush mounting enclosures front IP55.
Undervoltage releaseorShunt release
Motor--protectivecircuit--breaker
Standardauxiliary contactmodule
Standardauxiliary contactmodule
Current limiter
Door couplinghandle
Trip--indicatingauxiliarycontact module
IEC 947, EN 60947
J7M--BM SystemRated operational current 40 A, 18.5 kW/415 V.Switching capacity 30 kA/415 V.Plug--in trip block.Short--circuit release, adjustable.Overload release, adjustable.Single--phasing sensitivity.Finger proof terminals.
Auxiliary contacts modulesON/OFF indication for motor--protectivecircuit--breaker.Differential fault indication of overload/short--circuittripping.
AccessoriesUndervoltage release.Three--phase commoning link for series mounting.Lockable handle by means of 1 padlock(hasp thickness 4--6 mm). Undervoltage
release
Motor--protectivecircuit--breaker
Standardauxiliary contactmodule
Trip--indicatingauxiliary contactmodule
IEC 947, EN 60947
J7M-AM/-BM J7M-AM/-BM
32
Ordering InformationModel Number Legend:
1. Frame size:A or B
2. Load:M: motor load
3. Trip current:--x, xx = in case of incorporated trip unit(J7M--AM)./TB--xx = in case of exchangeable trip block(J7M--BM).
J7M-- j j / j
1 2 3
Motor--protective circuit--breaker:
1. Frame size:A or B
2. Application:M = Motor.
3. No. of contacts and configuration
4. Mounting:--E = build in (only J7M--AM).
J73M-- j j -- j j
1 2 3 4
Auxiliary contact modules:
1. Frame size of the Motor--protective circuit--breaker:A or B
2. Type of accessories:TI = Trip indicating auxiliary contact module(TI--10, TI--01 for J7MA, TI--11 for J7MB).L3-- = Link 3 pole devices (1/2, 1/3, 1/4, 1/5 for J7MA,1/2, 1/3 for J7MB).S--L3 = Shroud for L3...TC-- = Terminal connection 3phases (25/3 for J7MA,50/3 for J7MB).AK = Lockable rotary handle (only for J7MA).IE--G(R) = Insulated enclosure for surface mounting (only for J7MA).FE--GR = Insulated enclosure for flush mounting (only for J7MA).PF--IE = Padlocking facility (only for J7MA--IE--G(R)).PF--FE = Padlocking facility (only for J7MA--FE--GR.CL = Current limiter.RH = Door coupling handle.SR = Shunt release.U = Undervoltage release.
J7M j -- j
1 2
Accessories:
Available typesJ7M--AM system
Type
Motor--protective circuit--breakers J7M--AM--0,16p
J7M--AM--0,25
J7M--AM--0,4
J7M--AM--0,63
J7M--AM--1
J7M--AM--1,6
J7M--AM--2,5
J7M--AM--4
J7M--AM--6,3
J7M--AM--10
J7M--AM--16
J7M--AM--20
J7M--AM--25
Standard auxiliary contact modules J73M--AM--11y
J73M--AM--11--E
Trip--indicating auxiliary contactd l
J7MA--TI--01p g ymodules J7MA--TI--10
Current limiter J7MA--CL
Undervoltage releases J7MA--U(110V50Hz)g
J7MA--U(230V50Hz)
J7MA--U(415V50Hz)
Shunt releases J7MA--SR(415V50Hz)
J7MA--SR(230V50Hz)
J7MA--SR(48V50Hz)
J7MA--SR(24V50Hz)
J7MA--SR(24VDC)
J7M--BM system
Type
Motor--protective circuit--breakers J7M--BM/TB--10p
J7M--BM/TB--16
J7M--BM/TB--25
J7M--BM/TB--32
J7M--BM/TB--40
Standard auxiliary contact module J73M--BM--11
Trip--indicating auxiliary contactmodule
J7MB--TI--11
Undervoltage releases J7MB--U(415V50Hz)g
J7MB--U(230V50Hz)
J7MB--U(110V50Hz)
J7MB--U(48V50Hz)
J7MB--U(24V50Hz)
J7M-AM/-BM J7M-AM/-BM
33
System overviewMotor--protective circuit--breakersJ7M--AM System
J7M--AMI
L
T
Article No. Max. AC--3 rating Rateduninterrupted
Overloadrelease setting
Short circuitrelease (Irm)
Std.pack
220 V230 V240 V(kW)
380 V400 V415 V(kW)
440 V
(kW)
500 V
(kW)
660 V690 V
(kW)
uninterruptedcurrent (Iu)
(A)
release settingrange (Ir)
(A)
release (Irm)
(A)I
pack
J7M--AM--0,16 -- -- -- -- 0.06 0.16 0.1 -- 0.16 2.2 2 off
J7M--AM--0,25 -- 0.06 0.06 0.06 0.12 0.25 0.16 -- 0.25 3.5 2 off
J7M--AM--0,4 0.06 0.09 0.12 0.12 0.18 0.4 0.25 -- 0.4 5.6 2 off
J7M--AM--0,63 0.09 0.12 0.18 0.25 0.25 0.63 0.4 -- 0.63 8.8 2 off
J7M--AM--1 0.12 0.25 0.25 0.37 0.55 1.0 0.63 -- 1.0 14.0 2 off
J7M--AM--1,6 0.25 0.55 0.55 0.75 1.1 1.6 1.0 -- 1.6 22.0 2 off
J7M--AM--2,5 0.37 0.75 1.1 1.1 1.5 2.5 1.6 -- 2.5 35.0 2 off
J7M--AM--4 0.75 1.5 1.5 2.2 3.0 4.0 2.5 -- 4.0 56.0 2 off
J7M--AM--6,3 1.1 2.2 3.0 3.0 4.0 6.3 4.0 -- 6.3 88.0 2 off
J7M--AM--10 2.2 4.0 4.0 4.0 7.5 10.0 6.3 -- 10.0 140.0 2 off
J7M--AM--16 4.0 7.5 9.0 9.0 12.5 16.0 10.0 -- 16.0 224.0 2 off
J7M--AM--20 5.5 9.0 11.0 12.5 15.0 20.0 16.0 -- 20.0 280.0 2 off
J7M--AM--25 5.5 12.5 12.5 15.0 22 25.0 20.0 -- 25.0 350.0 2 off
Note: Single--phasing sensitivity to IEC 947--4--1. For snap fitting to EN 50022--35 top--hat rail, height 7.5 or 15 mm.
J7MA--CL Current limiterI
L
T
Article No. Max. AC--3 rating Ratedi t t d
Overloadl tti
Short circuitl (I )
Std.k220 V
230 V240 V(kW)
380 V400 V415 V(kW)
440 V
(kW)
500 V
(kW)
660 V690 V
(kW)
uninterruptedcurrent (Iu)
(A)
release settingrange (Ir)
(A)
release (Irm)
(A)I
pack
J7MA--CL To increase the switching capacity of J7M--AM 0--16,--20, --25 motor--protective circuit--breakers which are notinherently short--circuit--proof, to 100 kA/440 V.
63.0 -- -- 2 off
Note: Max. rated operational voltage Ue = 690 V. For individual and group protection in combination with J7M--AM 0--16, --20, --25motor--protectice circuit--breakers.Use input terminals J7MA--TC--25/3 for bigger cable section (≥10 mm2).
J7M-AM/-BM J7M-AM/-BM
34
Standard auxiliary contact modulesFor motor--protective circuit--breakers.
Article No. Contacts
M = MakeB = Break
Contact sequence Std.pack
J73M--AM--11 1) 1M 1B 1.21
1.22
1.13
1.14
I
L1L2L3
J73M--AM--11
O I 5
J73M--AM--11--E 2) 1M 1B 1.61
1.62
1.53
1.54
L1L2L3
J73M--AM--11--E
O I 5
Note: 1. Can be fitted to the right of: Motor--protective circuit--breaker. Can be combined with: J7MA--TI trip--indicating auxiliary contact.
2. 45 mm width of the motor--protective circuit--breaker remains unchanged.
Trip--indicating auxiliary contact modulesFor motor--protective circuit--breakers.
Article No. Contacts
M = MakeB = Break
Contact sequence Std.pack
J7MA--TI--10 2 x 1M
L1L2L3
“+”
O I
“I >”
ON/OFF
L1L2L3
“+”
O I
“I >”
Trip “+”
I
“I >”4.13
4.14
b)
“+”4.43
4.44
a)
Differential indicationa) General trip indication (overload)b) Short circuit trip
Local short--circuit indicaton by redindicator, can be reset manually.
1
J7MA--TI--01 2 x 1B
Differential indicationa) General trip indication (overload)b) Short circuit trip
Local short--circuit indicaton by redindicator, can be reset manually.
L1L2L3
“+”
O I
“I >”
ON/OFF
L1L2L3
“+”
O I
“I >”
Trip “+”
“I >”4.21
4.22
b)
“+”4.31
4.32
a)
1
Note: Can be fitted to the right of: Motor--protective circuit--breaker. Can be combined with: J73M--AM--11 standard auxiliary contact.
J7M-AM/-BM J7M-AM/-BM
35
Shunt release
For DC and ACDC: intermittent operation 5 s.
Article No. Std.pack
J7MA--SR (415 V, 50 Hz)J7MA--SR (230 V, 50 Hz)J7MA--SR (48 V, 50 Hz)J7MA--SR (24 V, 50 Hz)J7MA--SR (24 VDC)
C1
C2
2
Note: Can be fitted to the left of: Motor--protective circuit--breaker.Can not be combined with: J7MA--U undervoltage release.
Undervoltage releaseFor ACCan be combined with motor--protective circuit--breakerfor emergency--stop facility to VDE 0113
Article No. Std.pack
J7MA--U (415 V, 50 Hz)J7MA--U (230 V, 50 Hz)J7MA--U (110 V, 50 Hz)J7MA--U (48 V, 50 Hz)J7MA--U (24 V, 50 Hz)
D1
D2
U <
2
Note: Can be fitted to the left of: Motor--protective circuit--breaker.Cannot be combined with: J7MA--SR shunt release.
AccessoriesInsulated enclosures for surface mounting for motor--protective circuit--breakers
Article No. Degree ofprotection
Note For use with Std.pack
J7MA--IE--G IP55 With black/grey rotary handle. J7M--AM--.. + J73M--AM--11 +J7MA--TI--.. + J73M--AM--11--E
or
J7M--AM--.. + J7MA--U +J73M--AM--11--E
or
J7M--AM--.. + J7MA--SR +J73M--AM--11--E
2
J7MA--IE--GR IP55 With red/yellow rotary handle. J7M--AM--.. + J73M--AM--11 +J7MA--TI--.. + J73M--AM--11--E
or
J7M--AM--.. + J7MA--U +J73M--AM--11--E
or
J7M--AM--.. + J7MA--SR +J73M--AM--11--E
2
J7MA--PF--IE -- Padlocking facility for J7MA--IE--G(R) surfacemounting enclosure for up to 3 padlocks with ahasp thickness of 3--6 mm.
Can be locked in the OFF position of theJ7M--AM.
J7MA--IE--G
or
J7MA--IE--GR
1
J7M-AM/-BM J7M-AM/-BM
36
Insulated enclosure for flush mounting for motor--protective circuit--breakers
Article No. Degree ofprotection
Note For use with Std.pack
J7MA--FE--GR Front IP55 With red/yellow rotary handle. J7M--AM--.. + J73M--AM--11 +J7MA--TI--.. + J73M--AM--11--EorJ7M--AM--.. + J7MA--SR +J73M--AM--11--EorJ7M--AM--.. + J7MA--U +J73M--AM--11--E
1
J7MA--PF--FE -- Padlocking facility for J7MA--FE--GR flushmounting enclosure for up to 3 padlocks with ahasp thickness of 3--6 mm.
Can be locked in the OFF position of theJ7M--AM.
J7MA--FE--GR 1
Door coupling handle
Article No. Degree ofprotection
Note For use with Std.pack
J7MA--RH IP65 For main switch with emergency--stopfunction.Colour: red/yellowThe plug--fit extension shaft can be cut to anyrequired lenght for mounting depths from100--240 mm.
Note:The driver pin and extension shaft aresupplied with door coupling handle.
J7M--AM--.. 1
Lockable rotary handle
Article No. Note For use with Std.pack
J7MA--AK For locking the motor--protectivecircuit--breaker in the OFF POSITION bymeans of a padlock, hasp thickness3--6.35 mm.
J7M--AM--.. 1
J7M-AM/-BM J7M-AM/-BM
37
Three--phase commoning linksProtection against accidental contact Ue = 690 V, Iu = 63 A.Can be extended by mounting in reversed position.
Article No. Number ofMPCB
Lenght Unit width Note: Std.pack
J7MA--L3--1/2 2 99 mm 45 + 9 mm For motor--protective circuit--breakers havingone auxiliary contact or trip--indicatingauxiliary contact fitted on the right.
10
J7MA--L3--1/3 3 153 mm 45 + 9 mm 10
J7MA--L3--1/4 4 207 mm 45 + 9 mm 10
J7MA--L3--1/5 5 261 mm 45 + 9 mm 10
Terminal for three--phase commoning link
Article No. Note Std.pack
J7MA--TC25/3 For three--phase commoning links.Protection against accidental contact, Ue = 690 V, Iu = 63 A.
For connecting conductor cross--sections of:6--25 mm2 stranded6--16 mm2 flexible with ferrule
5
Shroud for unused terminals
Article No. Note For use with Std.pack
J7MA--S--L3 Protection against accidental contact.
To cover unused terminals on a three--phasecommoning link.
J7MA--L3--1/2J7MA--L3--1/3J7MA--L3--1/4J7MA--L3--1/5
20
J7M-AM/-BM J7M-AM/-BM
38
Motor--protective circuit--breakersJ7M--BM System
J7M--BMI
L
T
Article No. Max. AC--3 rating Rateduninterrupted
Overloadrelease setting
Short circuitrelease (Irm)
Std.pack
220 V230 V240 V(kW)
380 V400 V415 V(kW)
440 V
(kW)
500 V
(kW)
660 V690 V
(kW)
uninterruptedcurrent (Iu)
(A)
release settingrange (Ir)
(A)
release (Irm)
(A)I
pack
J7M--BM/TB--10 2.5 4.0 5.0 5.5 7.5 10.0 6.0 -- 10.0 80.0 -- 140.0 1 off
J7M--BM/TB--16 4.0 7.5 9.0 10.0 13.5 16.0 10.0 -- 16.0 130.0 -- 220.0 1 off
J7M--BM/TB--25 5.5 12.5 12.5 15.0 22.0 25.0 16.0 -- 25.0 200.0 -- 350.0 1 off
J7M--BM/TB--32 7.5 15.0 17.5 22.0 22.0 32.0 24.0 -- 32.0 275.0 -- 425.0 1 off
J7M--BM/TB--40 11.0 20.0 22.0 24.0 27.0 40.0 32.0 -- 40.0 350.0 -- 500.0 1 off
Note: 1. Single--phasing sensitivity to IEC 947--4--1.Can be snap fitted onto a 7.5 or 15 mm top--hat rail to EN 50022--35.
2. Overload release, adjustable Ir = 0.6--1.0 x Iu.Short--circuit release, adjustable Irm = 8.5--14 x Iu (factory--set to 12 x Iu).
Standard auxiliary contactFor motor--protective circuit--breakers.
Article No. Contacts
M = MakeB = Break
Contact sequence Std.pack
J73M--BM--11 1M 1B
L1L2L3
J73M--BM
O I
ON
+
I
J7M--BM/TB
1.21
1.22
1.13
1.14
1 off
Note: When the motor--protective circuit--breaker is in the tripped position “+”, the contacts of the J73M--BM auxiliary contact module are inthe OFF position.
Can be fitted to motor--protective circuit--breakers. Can be used in conjunction with J7MB--TI--11 trip--indicating contacts.
Trip indicating auxiliary contacts including short--circuit indicatorFor motor--protective circuit--breakers.
Article No. Contacts
M = MakeB = Break
Contact sequence Std.pack
J7MB--TI--11 2 x1M 1B
Differential remote indicationa) General trip indication “+”,(overload)b) Short circuit trip
L1L2L3
J7MB--TI
O I
Trip “+”
+
I
J7M--BM/TB
4.13
4.14
4.21
4.22
J7MB--TI
4.31
4.32
4.43
4.44
“+” “I>”1 off
Note: Can be fitted to motor--protective circuit--breakers. Can be combined with J73M--BM standard auxiliary contacts.
J7M-AM/-BM J7M-AM/-BM
39
Undervoltage releasesNon delayedFor AC and DC.In combination with motor--protective circuit--breakers suitable for emergency--stop disconnection to IEC 204.
Article No. Std.pack
J7MB--U (230 V, 50 Hz)J7MB--U (110 V, 50 Hz)J7MB--U (24 VDC)
D1
D2
U <
1 off
Note: Can be fitted to motor--protective circuit--breakers.
Accessories
Three--phase commoning linksProtection against accidental contact for group mounting of two or three circuit breakers 120 A (3 x 40 A).
Article No. Number ofmotor--protectivecircuit--breakers
Lenght Note: Std.pack
J7MB--L3--1/2 2 140 mm Space is provided for either one auxiliary contact or onevoltage release.
5
J7MB--L3--1/3 3 222 mm Space is provided for either two auxiliary contact or twovoltage release.
5
Terminal for three--phase commoning linkTerminal is back--of--hand and finger--proof.For connection of large cable cross--sections or loops.
Article No. Note Std.pack
J7MB--TC50/3 For connecting:1 x 50 mm2 or2 x 35 mm2, one above the othermin. 1 x 1 mm2 or 2 x 1 mm2
1
Shroud for unused terminals
Article No. Note For use with Std.pack
J7MB--S--L3 Protection against accidental contacts.To cover unused terminals on a three--phasecommoning link.
J7MB--L3--1/2J7MB--L3--1/3
10
J7M-AM/-BM J7M-AM/-BM
40
Modules for motor--starter combinationsType “1” coordinaton400/415 V AC
The motor--starter combinations constist of :Motor--protective circuit--breaker and contactor.
They conform to IEC 947--4--1, EN 60 947--4--1.Iq = Rated conditional short--circuit current.
Motor--t ti
Contactor Motor data Ratedi d
Ratedh i i
Setting rangeprotectivecircuit--breaker
AC--3380 V400 V415 V
Ratedoperationalcurrent400 V
uninterruptedcurrent
short--circuitcurrent380--400/415 V
Overload release Short--circuitrelease
I
P(kW)
Ie(A)
Iu(A)
Iq(kA)
Ir(A)
Irm(A)
J7M--AM--0,25 J7K--AMA--10(..) 0.06 0.2 0.25 100/100 0.16 -- 0.25 3.5
J7M--AM--0,4 J7K--AMA--10(..) 0.09 0.9 0.4 100/100 0.2 -- 0.4 5.6
J7M--AM--0,63 J7K--AMA--10(..) 0.12 0.4 0.63 100/100 0.4 -- 0.63 8.8
J7M--AM--0,63 J7K--AMA--10(..) 0.18 0.58 0.63 100/100 0.4 -- 0.63 8.8
J7M--AM--1 J7K--AMA--10(..) 0.25 0.81 1.0 100/100 0.63 -- 1.0 14.0
J7M--AM--1,6 J7K--AMA--10(..) 0.37 1.05 1.6 100/100 1.0 -- 1.6 22.0
J7M--AM--1,6 J7K--AMA--10(..) 0.55 1.42 1.6 100/100 1.0 -- 1.6 22.0
J7M--AM--2,5 J7K--AMA--10(..) 0.75 1.86 2.5 100/100 1.6 -- 2.5 35.0
J7M--AM--4 J7K--AMA--10(..) 1.1 2.65 4.0 100/100 2.5 -- 4.0 56.0
J7M--AM--4 J7K--AMA--10(..) 1.5 3.6 4.0 100/100 2.5 -- 4.0 56.0
J7M--AM--6,3 J7K--AMA--10(..) 2.2 5.2 6.3 100/100 4.0 -- 6.3 88.0
J7M--AM--10 J7K--AMA--10(..) 3.0 6.8 10.0 100/100 6.3 -- 10.0 140.0
J7M--AM--10 J7K--AMA--10(..) 4.0 8.8 10.0 100/100 6.3 -- 10.0 140.0
J7M--AM--16 J7K--BMA(..) 5.0 11.4 16.0 16/16 10.0 -- 16.0 224.0
J7M--AM--16 J7K--CM(..) 7.5 15.4 16.0 16/16 10.0 -- 16.0 224.0
J7M--AM--25 J7K--CMA(..) 11.0 22.1 25.0 16/16 16.0 -- 25.0 350.0
Type “1” coordinaton400/415 V AC
The motor--starter combinations constist of :Motor--protective circuit--breaker and contactor.
They conform to IEC 947--4--1, EN 60 947--4--1.Iq = Rated conditional short--circuit current.
Setting note:Set the Irm short--circuit release of the J7M--BM/TB motor--protective circuit--breaker to8.5--14 x rated operational current Ie.
Motor--t ti
Contactor Motor data Ratedi d
Ratedh i i
Setting rangeprotectivecircuit--breaker
AC--3380 V400 V415 V
Ratedoperationalcurrent400 V
uninterruptedcurrent
short--circuitcurrent380--415 V
Overload release Short--circuit release
I
P(kW)
Ie(A)
Iu(A)
Iq(kA)
Ir(A)
Irm(A)
J7M--BM/TB--10 J7K--CM(..) 3.0 6.8 10.0 100 6.0 --10.0 80.0 -- 140.0
J7M--BM/TB--10 J7K--CM(..) 4.0 8.8 10.0 100 6.0 -- 10.0 80.0 -- 140.0
J7M--BM/TB--16 J7K--CM(..) 5.5 11.4 16.0 100 10.0 --16.0 130.0 -- 220.0
J7M--BM/TB--16 J7K--CM(..) 7.5 15.4 16.0 100 10.0 --16.0 130.0 -- 220.0
J7M--BM/TB--25 J7K--CMA(..) 11.0 22.1 25.0 30 16.0 --25.0 200.0 -- 350.0
J7M--BM/TB--32 J7K--DM(..) 15.0 28.5 32.0 30 24.0 -- 32.0 275.0 -- 425.0
J7M--BM/TB--40 J7K--DMA(..) 18.5 35.0 40.0 30 32.0 -- 40.0 350.0 -- 500.0
I
M3 phase
I
M3 phase
J7M-AM/-BM J7M-AM/-BM
41
Type “1” coordinaton400/415 V AC
Modules for reversing starter combinationsThe reversing--starter combinations constist of :Motor--protective circuit--breaker and two contactor.
They conform to IEC 947--4--1, EN 60 947--4--1.Iq = Rated conditional short--circuit current.
Motor--t ti
Contactor Motor data Ratedi d
Ratedh i i
Setting rangeprotectivecircuit--breaker
AC--3380 V400 V415 V
Ratedoperationalcurrent 400 V
uninterruptedcurrent
short--circuitcurrent380--415 V
Overload release Short--circuitrelease
I
P(kW)
Ie(A)
Iu(A)
Iq(kA)
Ir(A)
Irm(A)
J7M--AM--0,25 2 x J7K--AMA(..) 0.06 0.2 0.25 100 0.16 -- 0.25 3.5
J7M--AM--0,4 2 x J7K--AMA(..) 0.09 0.29 0.4 100 0.25 -- 0.4 5.6
J7M--AM--0,63 2 x J7K--AMA(..) 0.12 0.4 0.63 100 0.4 -- 0.63 8.8
J7M--AM--0,63 2 x J7K--AMA(..) 0.18 0.58 0.63 100 0.4 -- 0.63 8.8
J7M--AM--1 2 x J7K--AMA(..) 0.25 0.81 1.0 100 0.63 -- 1.0 14.0
J7M--AM--1,6 2 x J7K--AMA(..) 0.37 1.05 1.6 100 1.0 -- 1.6 22.0
J7M--AM--1,6 2 x J7K--AMA(..) 0.55 1.42 1.6 100 1.0 -- 1.6 22.0
J7M--AM--2,5 2 x J7K--AMA(..) 0.75 1.86 2.5 100 1.6 -- 2.5 35.0
J7M--AM--4 2 x J7K--AMA(..) 1.1 2.65 4.0 100 2.5 -- 4.0 56.0
J7M--AM--4 2 x J7K--AMA(..) 1.5 3.6 4.0 100 2.5 -- 4.0 56.0
J7M--AM--6,3 2 x J7K--AMA(..) 2.2 5.2 6.3 100 4.0 -- 6.3 88.0
J7M--AM--10 2 x J7K--AMA(..) 3.0 6.8 10.0 100 6.3 -- 10.0 140.0
J7M--AM--10 2 x J7K--AMA(..) 4.0 8.8 10.0 100 6.3 -- 10.0 140.0
J7M--AM--16 2 x J7K--BMA(..) 5.0 11.4 16.0 16 10.0 -- 16.0 224.0
J7M--AM--16 2 x J7K--CM(..) 7.5 15.4 16.0 16 10.0 -- 16.0 224.0
J7M--AM--25 2 x J7K--CMA(..) 11.0 22.1 25.0 16 20.0 -- 25.0 350.0
I
M 3 phase
J7M-AM/-BM J7M-AM/-BM
42
Type “2” coordinaton400/415 V AC
Modules for motor--starter combinationsThe motor--starter combinations constist of:Motor--protective circuit--breaker and contactor.
They conform to IEC 947--4--1, EN 60 947--4--1.Iq = Rated conditional short--circuit current.
Motor--t ti
Contactor Motor data Ratedi d
Ratedh i i
Setting rangeprotectivecircuit--breaker
AC--3380 V400 V415 V
Ratedoperationalcurrent 400 V
uninterruptedcurrent
short--circuitcurrent380--415 V
Overload release Short circuitrelease
I
P(kW)
Ie(A)
Iu(A)
Iq(kA)
Ir(A)
Irm(A)
J7M--AM--0,25 J7K--AMA(..) 0.06 0.2 0.25 100 0.16 -- 0.25 3.5
J7M--AM--0,4 J7K--AMA(..) 0.09 0.29 0.40 100 0.25 -- 0.4 5.6
J7M--AM--0,63 J7K--AMA(..) 0.12 0.4 0.63 100 0.4 -- 0.63 8.8
J7M--AM--0,63 J7K--AMA(..) 0.18 0.58 0.63 100 0.4 -- 0.63 8.8
J7M--AM--1 J7K--AMA(..) 0.25 0.81 1.0 100 0.63 -- 1.0 14.0
J7M--AM--1,6 J7K--AMA(..) 0.37 1.05 1.6 100 1.0 -- 1.6 22.0
J7M--AM--1,6 J7K--AMA(..) 0.55 1.42 1.6 100 1.0 -- 1.6 22.0
J7M--AM--2,5 J7K--CM(..) 0.75 1.86 2.5 100 1.6 -- 2.5 35.0
J7M--AM--4 J7K--CM(..) 1.1 2.65 4.0 100 2.5 -- 4.0 56.0
J7M--AM--4 J7K--CM(..) 1.5 3.6 4.0 100 2.5 -- 4.0 56.0
J7M--AM--6,3 J7K--CM(..) 2.2 5.2 6.3 100 4.0 -- 6.3 88.0
J7M--AM--10 J7K--CM(..) 3.0 6.8 10.0 100 6.3 -- 10.0 140.0
J7M--AM--10 J7K--CM(..) 4.0 8.8 10.0 100 6.3 -- 10.0 140.0
J7M--AM--16 J7K--CM(..) 5.5 11.4 16.0 16 10.0 -- 16.0 224.0
J7M--AM--16 J7K--CM(..) 7.5 15.4 16.0 16 10.0 -- 16.0 224.0
J7M--AM--25 J7K--CMA(..) 11.0 22.1 25.0 16 20.0 -- 25.0 350.0
I
M3 phase
J7M-AM/-BM J7M-AM/-BM
43
Type “2” coordinaton400/415 V AC
Modules for reversing starter combinationsThe reversing starter combinations constist of :Motor--protective circuit--breaker and two contactors.
They conform to IEC 947--4--1, EN 60 947--4--1.Iq = Rated conditional short--circuit current.
Motor--t ti
Contactor Motor data Ratedi d
Ratedh i i
Setting rangeprotectivecircuit--breaker
AC--3380 V400 V415 V
Ratedoperationalcurrent 400 V
uninterruptedcurrent
short--circuitcurrent380--415 V
Overload release Short--circuitrelease
I
P(kW)
Ie(A)
Iu(A)
Iq(kA)
Ir(A)
Irm(A)
J7M--AM--0,25 2 x J7K--AMA(..) 0.06 0.2 0.25 100 0.16 -- 0.25 3.5
J7M--AM--0,4 2 x J7K--AMA(..) 0.09 0.29 0.40 100 0.25 -- 0.4 5.6
J7M--AM--0,63 2 x J7K--AMA(..) 0.12 0.4 0.63 100 0.4 -- 0.63 8.8
J7M--AM--0,63 2 x J7K--AMA(..) 0.18 0.58 0.63 100 0.4 -- 0.63 8.8
J7M--AM--1 2 x J7K--AMA(..) 0.25 0.81 1.0 100 0.63 -- 1.0 14.0
J7M--AM--1,6 2 x J7K--AMA(..) 0.37 1.05 1.6 100 1.0 -- 1.6 22.0
J7M--AM--1,6 2 x J7K--AMA(..) 0.55 1.42 1.6 100 1.0 -- 1.6 22.0
J7M--AM--2,5 2 x J7K--CM(..) 0.75 1.86 2.5 100 1.6 -- 2.5 35.0
J7M--AM--4 2 x J7K--CM(..) 1.1 2.65 4.0 100 2.5 -- 4.0 56.0
J7M--AM--4 2 x J7K--CM(..) 1.5 3.6 4.0 100 2.5 -- 4.0 56.0
J7M--AM--6,3 2 x J7K--CM(..) 2.2 5.2 6.3 100 4.0 -- 6.3 88.0
J7M--AM--10 2 x J7K--CM(..) 3.0 6.8 10.0 100 6.3 -- 10.0 140.0
J7M--AM--10 2 x J7K--CM(..) 4.0 8.8 10.0 100 6.3 -- 10.0 140.0
J7M--AM--16 2 x J7K--CM(..) 5.5 11.4 16.0 16 10.0 -- 16.0 224.0
J7M--AM--16 2 x J7K--CM(..) 7.5 15.4 16.0 16 10.0 -- 16.0 224.0
J7M--AM--25 2 x J7K--CMA(..) 11.0 22.1 25.0 16 20.0 -- 25.0 350.0
I
M 3 phase
J7M-AM/-BM J7M-AM/-BM
44
Specifications
General
Typ J7M--AM J7M--BM
Standards IEC 947, EN 60947, DIN VDE 0660, UL 508 , CSA C 22.2 No. 14,GL, LRs, DNV, PRS, BV, RINA, RS
Climatic proofing Damp heat, constant, to IEC 68 Part 2--3Damp heat, cyclic, to IEC 68 Part 2--30
Ambient temperature Storage min. --25 !C/ max. + 70 !C min. --25 !C/ max. + 70 !Cp
Open min. --25 !C/ max. + 55 !C min. --25 !C/ max. + 60 !C
Mounting position90!90! 90! 90!
90!90!
Direction of incoming supply As required
Degree of protection to IEC 947 (terminals) IP20 (IP00) IP20
Protection against electric shock Finger-- and back--of--hand proof
Mechanical shock resistance Half--sinusoidal shock 10 ms 25 g --
Half--sinusoidal shock 20 ms -- 30 g
Altitude 2000 m
Terminal capacities 1 conductor (solid); min./max. 1 -- 6 mm2 --p
1 conductor (solid), stranded; min./max. -- 1.0/16
1 conductor (flexible with ferrule); min./max. 1 -- 4 mm2 1.5/10
2 conductor (solid); min./max. 1 -- 2.5 mm2 --
2 conductor (solid), stranded; min./max. -- 1.0/6
2 conductor (flexible with ferrule); min./max. 1 -- 2.5 mm2 1.5/6( ); /
18 -- 10 AWG 14/6 AWG
Specified tightening torque fori l
Main cable 1.7 Nm 1.8 Nmp g g qterminal screws Control circuit cable 1.0 Nm 1.0 Nm
Main contacts
Typ J7M--AM J7M--BM
Rated impulse withstand voltage Uimp 6000 V
Overvoltage category / pollution degree III/3
Rated operational voltage Ue 690 V AC
Rated uninterrupted current Iu % rated operational current Ie 25 A or setting current of overloadrelease
40 A
Rated frequency 40 -- 60 Hz 50 -- 60 Hz
Number of poles 3 3
Current heat losses (3--pole at operational temperature) 6 W 14 W
Lifespan mechanical 0.1 x 106 Operations 0.1 x 106 Operationsp
electrical (100 %; AC--3/400 V) 0.1 x 106 Operations 0.05 x 106 Operations
Max. operating frequency 40 Ops./hour 60 Ops./hour
Motor switching capacity AC--3 max. 690 V AC max. 690 V ACg p y
DC--5 max. 250 V DC max. 250 V DC
-- max. 40 A DC
Rated short--circuit breakingi I
250 V DC; L/R = 15 ms -- 30 kAgcapacity Icn 125 V DC; L/R = 15 ms -- 50 kA
Operating times underh i i di i
Minimum command time -- Approx. 2 msp gshort--circuit conditions Opening delay -- Approx. 0.5 ms
Total opening time -- Approx. 6 ms
J7M-AM/-BM J7M-AM/-BM
45
Trip blocks
Typ J7M--AM J7M--BM
Temperature compensation IEC 947, EN 60947, DIN VDE 0660 min. -- 5 !C/ max. + 40 !C min. -- 5 !C/ max. + 40 !Cp p
Operating range min. -- 25 !C/ max. + 55 !C
Temperature compensation residual error to IEC 947, EN 60947, DIN VDE 0660 ≤ 0.25 -- 0.4 %/K 0.25 %/K
Adjustable overload releases 0.6 -- 1 x IuFixed short--circuit releases 14 x Iu --
Adjustable short--circuit releases -- 8.5 -- 14 x IuShort--circuit release tolerance 20 %
Single--phasing sensitivity IEC 947--4--1, EN 60947--4--1, DIN VDE 0660 Part 102
Current limiter
Typ J7MA--CL --
Rated impulse withstand voltage Uimp 6000 V --
Overvoltage category / pollution degree III/3 --
Rated operational voltage Ue 440 V AC --
Rated uninterrupted current Iu 63 A --
Terminal for three--phase commoning link
Typ J7MA--TC25/3 J7MB--TC50/3
Rated impulse withstand voltage Uimp 6000 V 6000 V
Overvoltage category/pollution degree III/3 III/3
Rated operational voltage Ue 690 V AC 690 V AC
Rated uninterrupted current Iu 63 A 120 A
Three--phase commoning links
Typ J7MA--L3--... J7MB--L3--...
Rated impulse withstand voltage Iimp 6000 V 6000 V
Overvoltage category/pollution degree III/3 III/3
Rated operational voltage Ue 690 V AC 690 V AC
Rated uninterrupted current Iu 63 A (J7MA--L3--./.) 120 A (3 x 40 A) (J7MB--L3--1/3)120 A (J7MB--L3--1/2)
J7M-AM/-BM J7M-AM/-BM
46
Auxiliary contact modules
Typ J7M--AM J7M--BM
Rated impulse withstand voltage Uimp 6000 V (4000 for J73M--AM--11--E) 6000 V
Overvoltage category/pollution degree III/3 III/3
Rated operational voltage Ue 500 V AC, 250 V DC 500 V AC
Safe isolation to DIN VDE 0106 Part 101 and Part 101 A1 between auxiliarycontacts and main contacts
690 VAC --
Rated operational current Ie AC--15 220--240 V 3.5 A (1 A for J73M--AM--11--E) --p e
380--415 V 2 A --
440--500 V 1 A --
AC--15(J73M BM 11)
230--240 V -- 6 A(J73M--BM--11) 400--415 V -- 3 A
440--500 V -- 1.5 A
AC--15(J7MB TI 11)
230--240 V -- 5 A(J7MB--TI--11) 400--415 V -- 3 A
440--500 V -- 1.5 A
DC--13(L/R 100 )
24 V 2 A --(L/R ≤ 100 ms) 60 V 1.5 A (1 A for J73M--AM--11--E) --
110 V 1 A (0.5 A for J73M--AM--11--E) --
220 V 0.25 A --
Component lifespan mechanical J73M--jM--11 0.1 x 106 Ops. 0.1 x 106 Ops.p p
J73M--AM--11--E 0.1 x 106 Ops. --
J7Mj--TI--.. 0.01 x 106 Ops. 0.01 x 106 Ops.
electricial J73M--jM--11 0.01 x 106 Ops. 0.05 x 106 Ops.
J73M--AM--11--E 0.1 x 106 Ops. --
J7Mj--TI 5 x 103 Ops. 5 x 103 Ops.
Control circuit reliabilityFault probability HF at rated operational voltage 24 V DC
Umin =17 V,Imin = 5.4 mA
< 10--8, < fault in 1 x 108 operations --au t p obab ty F at ated ope at o a o tage C
Umin = 24 V,Imin = 10 mA
-- Fail--safe over the entire mechanicallifespan
Interlocked opposing contacts to ZH 1/457 J73M--AM--11 J7MB--TI--11
Short--circuit rating withoutldi
Fuseless Please enquire 240 V (J7M--AM--6,3)gwelding -- 415 V (J7M--AM--4)
-- 500 V (J7M--AM--1,6)
Fuse 10 A gL 10 A gL
Terminal capacities 1 conductor or 2 conductors solid or flexiblewith ferrule
min. 0.75 mm2 -- max. 2.5 mm2
(min. 0.75 mm2 -- max. 1.5 mm2
for J73M--AM--11--E)
min. 18 AWG -- max. 14 AWG(min. 18 AWG -- max. 16 AWGfor J73M--AM--11--E)
min. 0.75 mm2 -- max. 2.5 mm2
min. 22 AWG -- max. 14 AWG
Voltage release
Typ J7MA--U J7MB--U
Rated impulse withstand voltage Uimp 6000 V
Overvoltage category/pollution degree III/3
Rated operational voltage Ue 42 -- 480 V AC24 -- 250 V DC
24 -- 600 V AC24 -- 125 V DC
Terminal capacities 1 conductor or 2 conductors solid or flexiblewith ferrule
min. 0.75 mm2 -- max. 2.5 mm2
min. 18 AWG -- max. 14 AWGmin. 0.75 mm2 -- max. 2.5 mm2
min. 22 AWG -- max. 14 AWG
J7M-AM/-BM J7M-AM/-BM
47
Shunt release
Typ J7MA--SR --
Operating range AC 0.7--1.1 x Us --p g g
DC (intermittent operaton: 5 s) 0.7--1.1 x Us --
Power consumption Pull--in AC 5 VA --p
Holding AC 3 VA --
Pull--in DC 3 W --
Holding DC 3 W --
Undervoltage release
Typ J7MA--U J7MB--U
Pick--up voltage 0.85 x Us --
Drop--out voltage 0.7 -- 0.35 x Us 0.7 -- 0.35 x Us
Power consumption Pull--in AC 5 VA 5 VAp
Holding AC 3 VA 3 VA
Pull--in DC -- 3 W
Holding DC -- 3 W
Switching capacity to IEC 947--4--1, coordination types “1” and “2” and to IEC 947--2Motor--protective circuit--breaker J7M--AMRated uninterrupted current IuRated conditional short--circuit current Iq (IEC 947--4--1)Rated ultimate short--circuit breaking capacity Icu (IEC 947--2)Rated service short--circuit breaking capacity Ics (IEC 947--2)
230 V 400 V 440 V 500 V 690 V
Iu
A
Iq
(kA)
Icu
(kA)
Ics
(kA) A 2)
Iq
(kA)
Icu
(kA)
Ics
(kA) A 2)
Iq
(kA)
Icu
(kA)
Ics
(kA) A 2)
Iq
(kA)
Icu
(kA)
Ics
(kA) A 2)
Iq
(kA)
Icu
(kA)
Ics
(kA) A 2)
0.16--1.0 1)1.6
)
2.5 5 5 5 50
4.0 3 3 3 50
6.3 6 6 6 50 3 3 2 50
10.0 10 10 10 50 6 6 6 50 3 3 2 50
16.0 16 16 8 50 16 16 8 50 10 10 10 50 6 6 6 50 3 3 2 50
20.0 16 16 8 50 16 16 8 50 10 10 10 50 6 6 6 50 3 3 2 50
25.0 16 16 8 50 16 16 8 50 10 10 10 50 6 6 6 50 3 3 2 50
J7M--AM + J7MA--CL
0.16--1.0 1) N 3) 1) N 3) 1) N 3) 1) N 3) 1) A 4) N 3)
1.6)
N 3))
N 3))
N 3))
N 3))
A 4) N 3)
2.5 N 3) N 3) N 3) N 3) 20 20 A 4) N 3)
4.0 N 3) N 3) N 3) N 3) 20 20 A 4) N 3)
6.3 N 3) N 3) N 3) 50 50 50 N 3) 20 20 A 4) N 3)
10.0 N 3) N 3) N 3) 20 20 20 N 3) 20 20 A 4) N 3)
16.0 N 3) N 3) N 3) 20 20 20 N 3) 5 5 A 4) N 3)
20.0 N 3) N 3) N 3) 10 10 10 N 3) 5 5 A 4) N 3)
25.0 N 3) N 3) N 3) 10 10 10 N 3) 5 5 A 4) N 3)
Note: 1. No upstream protective device required, inherently short--circuit--proof range (100 kA)2. Back--up fuse required when the fault current exceeds the rated short--circuit breaking capacity
of the motor--protective circuit--breaker Icc > IcnThe rated conditional short--circuit current Iq depending on the fuse used:50 A gL: Iq = 100 kA100 A gL: Iq = 30 kA
3. N = Not necessary4. A = Please, ask for more information
J7M-AM/-BM J7M-AM/-BM
48
Switching capacity to IEC 947--4--1, coordination types “1” and “2” and to IEC 947--2Motor--protective circuit--breaker J7M--BMRated uninterrupted current IuRated conditional short--circuit current Iq (IEC 947--4--1)Rated ultimate short--circuit breaking capacity Icu (IEC 947--2)Rated service short--circuit breaking capacity Ics (IEC 947--2)
230 V 400 V 440 V 500 V 690 V
Iu
A
Iq
(kA)
Icu
(kA)
Ics
(kA) A 2)
Iq
(kA)
Icu
(kA)
Ics
(kA) A 2)
Iq
(kA)
Icu
(kA)
Ics
(kA) A 2)
Iq
(kA)
Icu
(kA)
Ics
(kA) A 2)
Iq
(kA)
Icu
(kA)
Ics
(kA) A 2)
10.0 1) 30 1) 30 1) 10 10 5 80 7 7 3.5 80 4.5 4.5 2.5 80
16.0)
30)
30)
10 10 5 100 7 7 3.5 100 4.5 4.5 2.5 100
25.0 30 30 7.5 160 30 30 7.5 160 10 10 5 125 7 7 3.5 125 4.5 4.5 2.5 125
32.0 30 30 7.5 160 30 30 7.5 160 10 10 5 160 7 7 3.5 160 4.5 4.5 2.5 160
40.0 30 30 7.5 160 30 30 7.5 160 10 10 5 160 7 7 3.5 160 4.5 4.5 2.5 160
Note: 1. No upstream protective device required, inherently short--circuit--proof range (100 kA)
2. Back--up fuse required when the fault current exceeds the rated short--circuit breaking capacityof the motor--protective circuit--breaker Icc > Icn
1-- and 2--pole circuits for J7M--AM and J7M--BM devices usedfor DC and AC switching
1--pole 2--pole
I
53
6
1
4
I I
2
I
53
6
1
4
I I
2
Protection of PVC--insulated cables againstthermal overload in fault conditions
The tables shows which minimum cable cross--sections are pro-tected by J7M devices up to their rated short--circuit current Iq.
Device type Min. cross--section protected380--415 V, 50 Hz, Cu mm2
Device type 4.0 2.5 1.5 1.0 0.75
J7M--AM--0.16 X X X X X
J7M--AM--6.3 X X X X X
J7M--AM--10 X X X X
J7M--AM--16 X X X
J7M--AM--20 X X X
J7M--AM--25 X X
J7M--BM--10 X X X
J7M--BM--16 X X
J7M--BM--25 X
J7M--BM--32 X
J7M--BM--40 X
J7M-AM/-BM J7M-AM/-BM
49
Engineering DataJ7M--AMTripping characteristicsmotor--protective circuit--breakers
x Rated operational current &
J7M--AM--..
ms
sec
min
J7M--BMTripping characteristicsmotor--protective circuit--breakers
x Rated operatonal current &
J7M--BM/TB--..
ms
sec
min
J7M-AM/-BM J7M-AM/-BM
50
DimensionsJ7M--AM systemMotor--protective circuit--breakerJ7M--AM--.. + J73M--AM--11--E
Motor--protective circuit--breakerwith lockable rotary handleJ7M--AM--.. + J7MA--AK
Voltage releasesJ7MA--UJ7MA--SR
J7MA--UJ7MA--SR
Current limiterJ7MA--CL
Top--hatrail toEN 50022--35
Standard auxiliary contact moduleJ73M--AM--11
Trip--indicating auxiliary contact moduleJ7MA--TI--..
J7M-AM/-BM J7M-AM/-BM
51
Three--phase commoning linkJ7MA--L3--(1/5, 1/4, 1/3, 1/2)
TerminalJ7MA--TC25/3
Shroud for unused terminalsJ7MA--S--L3
Overlappingmounting to extendthree--phasecommoning link
J7MA--IE--G(R) Insulated enclosures for surface mountingJ7MA--PF--IE Padlocking facility
Door coupling handleJ7MA--RH
J7MA--PF--IE
Drilling dimensions
J7MA--FE--GR Insulated enclosures for flush mountingJ7MA--PF--FE Padlocking facility
116--118
70--72
Aperture for 2--6 mmpanel thickness
Mounting aperture
J7MA--PF--FE
J7M-AM/-BM J7M-AM/-BM
52
J7M--BM systemMotor--protective circuit--breakersJ7M--BM/TB
Trip--indicating contact moduleJ7MB--TI--11
Standard auxiliary contact moduleJ73M--BM--11
Undervoltage releaseJ7MB--U
Three--phase commoning linkJ7MB--L3--1/3 J7MB--L3--1/2
TerminalJ7MB--TC50/3
Shroud forunused terminalsJ7MB--S--L3
Cat. No. J501--E2--01
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.To convert millimeters into inches or grams into ounces, please see page 107.