8
MP7 link fault 18/8/2011 Davide Bozzini, 19 th of August 2011

MP7 link fault 18/8/2011 Davide Bozzini, 19 th of August 2011

  • Upload
    milt

  • View
    28

  • Download
    0

Embed Size (px)

DESCRIPTION

MP7 link fault 18/8/2011 Davide Bozzini, 19 th of August 2011 . SPS power network consolidation. Nature of works. Crossing points and trial holes. Crossing points and trial holes. Trial holes shall be done whenever necessary to exactly localize the crossing known and unknown utilities - PowerPoint PPT Presentation

Citation preview

Page 1: MP7 link fault 18/8/2011 Davide Bozzini, 19 th  of August 2011

MP7 link fault 18/8/2011Davide Bozzini, 19th of August 2011

Page 2: MP7 link fault 18/8/2011 Davide Bozzini, 19 th  of August 2011

SPS power network consolidation

2

Page 3: MP7 link fault 18/8/2011 Davide Bozzini, 19 th  of August 2011

3

Nature of works

Page 4: MP7 link fault 18/8/2011 Davide Bozzini, 19 th  of August 2011

Crossing points and trial holes

4

Page 5: MP7 link fault 18/8/2011 Davide Bozzini, 19 th  of August 2011

Crossing points and trial holes

5

Trial holes shall be done whenever necessary to exactly localize the crossing known and unknown utilities

Trial holes shall provide information on the nature of the ground for excavating and timbering purposes

All known crossing points shall be confirmed by a trial hole

CERN known crossing points are shown in each concerned work package set of drawings

The contractor shall identify any crossed utility before starting digging

Page 6: MP7 link fault 18/8/2011 Davide Bozzini, 19 th  of August 2011

6

Nature of fault- Damage of a 18 kV power cable during excavation- The trial hole was done during the TS to exactly determine

position and depth- Excavation to be done durin machine operation according to

work status

Page 7: MP7 link fault 18/8/2011 Davide Bozzini, 19 th  of August 2011

7

Preliminary outcome

- The trial hole was done during the TS to exactly determine position and depth

- Excavation to be done during machine operation according to work status

- BA2 18 networks crossed without any problem. Excellent execution

- Today accident:- Operators ad-interim to cope with staff holidays- Supervisors absent during the accident 11h45

- HSE unit inspection on site today Friday morning- Setting up of the fact finding group to be confirmed by DG- Trial holes and crossing works suspended- Normal operation of network expected by tonight

Page 8: MP7 link fault 18/8/2011 Davide Bozzini, 19 th  of August 2011

8