DF-60601:A1 • 12/07/2010 — Page 1 of 6 MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In Communicator Addressable Fire Alarm Control Panel DF-60601:A1 • A1-60 52422cov.jpg General The Fire•Lite MS-9200UDLS Rev 3 with Version 5.0 firmware is a combination FACP (Fire Alarm Control Panel) and DACT (Digital Alarm Communicator/Transmitter) all on one circuit board. This compact intelligent addressable control panel has an extensive list of powerful features. While the MS-9200UDLS Rev 3 may be used with an SLC configured in the CLIP (Classic Loop Interface Protocol) mode, it can also operate in LiteSpeed™ mode—Fire•Lite’s latest polling technology—for a quicker device response time. LiteSpeed’s patented technology polls 10 devices at a time. This improvement allows a fully-loaded panel with up to 198 devices to report an incident and activate the notification cir- cuits in under 10 seconds. With Litespeed polling, devices can be wired on standard twisted, unshielded wire up to a distance of 10,000 feet. The MS-9200UDLS Rev 3’s quick-remove chassis protects the electronics during construction. The backbox can be installed allowing field wiring to be pulled. When construction is com- pleted, the electronics can be quickly installed with just two bolts. New features for Rev 3 with Version 5.0 firmware include removable terminal blocks, improved transient protection, additional secondary ANN-BUS, and increased power for the resettable and remote sync outputs. Available accessories include ANN-BUS devices as well as ACS LED, graphic and LCD annunciators, and reverse polar- ity/city box transmitter. The integral DACT transmits system status (alarms, superviso- ries, troubles, AC loss, etc.) to a Central Station via the public switched telephone network. It also allows remote and local programming of the control panel using the PS-Tools Upload/ Download utility. In addition, the control panel may be pro- grammed or interrogated off-site via the public switched tele- phone network. Any personal computer with Windows® XP or greater, a compatible modem, and PS-Tools—the Fire•Lite Upload/Download software kit—may serve as a Service Termi- nal. This allows download of the entire program or upload of the entire program, history file, walktest data, current status and system voltages. The panel can also be programmed through the FACP’s keypad or via a standard PS-2 computer keyboard, which can be plugged directly into the printed circuit board. This permits easy typing of address labels and other programming information. Version 5.0 firmware supports the following: Primary and Sec- ondary ANN-bus devices, AD355 (LiteSpeed), USB port, NAC circuit diagnostics, a new report has been added to the walk- test that lists untested devices, new device types added: audio telephone type code for ACC 25/50ZST, Photo Supervisory and auto-resettable Drill (non-latching). The FireWatch Series internet monitoring modules IPDACT-2 and IPDACT-2UD permit monitoring of alarm signals over the Internet saving the monthly cost of two dedicated business telephone lines. Although not required, the secondary tele- phone line may be retained providing backup communication over the public switched telephone line. NOTE: Unless otherwise specified, the term MS-9200UDLS is used in this document to refer to both the MS-9200UDLS and the MS-9200UDLS(E) FACPs (Fire Alarm Control Panels). Features Listed to UL standard 864, 9th edition. On-board DACT. Remote site or local USB port upload/download, using PS- Tools. Four (4) Style Y (Class B) NAC circuits, which can be con- verted to four (4) Style Z (Class A) circuits with optional ZNAC-92 converter module. (Up to 6.0 amps total NAC power when using optional XRM-24B.) Selectable strobe synchronization for System Sensor, Wheelock, and Gentex devices. Remote Acknowledge, Silence, Reset and Drill via address- able monitor modules or LCD-80F, ANN-80 or Legacy ACS Annunciators. ANN-BUS for connection to following optional modules (cannot be used if ACS annunciators are used): ANN-80(-W) Remote LCD Annunciator ANN-I/O LED Driver ANN-S/PG Printer Module ANN-RLY Relay Module ANN-LED Annunciator Module ANN-RLED Annunciator Module alarms only ROME Relay Option Module Enclosure ACS/TERM: ACS Annunciators: Up to 32 Legacy ACM Series annun- ciators (ACM-16AT or ACM-32 series). Cannot be used if ANN-BUS devices are used. Terminal-mode Annunciators: Up to 32 Legacy LCD-80F remote annunciators.

MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

  • Upload
    ngonga

  • View
    240

  • Download
    6

Embed Size (px)

Citation preview

Page 1: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

DF-60601:A1 • 12/07/2010 — Page 1 of 6

MS-9200UDLS(E) Rev 3Intelligent Addressable FACP with Built-In Communicator

Addressable Fire Alarm Control Panel

DF-60601:A1 • A1-60

5242

2cov

.jpg

GeneralThe Fire•Lite MS-9200UDLS Rev 3 with Version 5.0 firmwareis a combination FACP (Fire Alarm Control Panel) and DACT(Digital Alarm Communicator/Transmitter) all on one circuitboard. This compact intelligent addressable control panel hasan extensive list of powerful features.

While the MS-9200UDLS Rev 3 may be used with an SLCconfigured in the CLIP (Classic Loop Interface Protocol) mode,it can also operate in LiteSpeed™ mode—Fire•Lite’s latestpolling technology—for a quicker device response time.LiteSpeed’s patented technology polls 10 devices at a time.This improvement allows a fully-loaded panel with up to 198devices to report an incident and activate the notification cir-cuits in under 10 seconds. With Litespeed polling, devices canbe wired on standard twisted, unshielded wire up to a distanceof 10,000 feet.

The MS-9200UDLS Rev 3’s quick-remove chassis protects theelectronics during construction. The backbox can be installedallowing field wiring to be pulled. When construction is com-pleted, the electronics can be quickly installed with just twobolts.

New features for Rev 3 with Version 5.0 firmware includeremovable terminal blocks, improved transient protection,additional secondary ANN-BUS, and increased power for theresettable and remote sync outputs.

Available accessories include ANN-BUS devices as well asACS LED, graphic and LCD annunciators, and reverse polar-ity/city box transmitter.

The integral DACT transmits system status (alarms, superviso-ries, troubles, AC loss, etc.) to a Central Station via the publicswitched telephone network. It also allows remote and localprogramming of the control panel using the PS-Tools Upload/Download utility. In addition, the control panel may be pro-grammed or interrogated off-site via the public switched tele-phone network. Any personal computer with Windows® XP orgreater, a compatible modem, and PS-Tools—the Fire•LiteUpload/Download software kit—may serve as a Service Termi-nal. This allows download of the entire program or upload ofthe entire program, history file, walktest data, current statusand system voltages. The panel can also be programmedthrough the FACP’s keypad or via a standard PS-2 computerkeyboard, which can be plugged directly into the printed circuitboard. This permits easy typing of address labels and otherprogramming information.

Version 5.0 firmware supports the following: Primary and Sec-ondary ANN-bus devices, AD355 (LiteSpeed), USB port, NACcircuit diagnostics, a new report has been added to the walk-test that lists untested devices, new device types added: audiotelephone type code for ACC 25/50ZST, Photo Supervisoryand auto-resettable Drill (non-latching).

The FireWatch Series internet monitoring modules IPDACT-2and IPDACT-2UD permit monitoring of alarm signals over theInternet saving the monthly cost of two dedicated businesstelephone lines. Although not required, the secondary tele-phone line may be retained providing backup communicationover the public switched telephone line.

NOTE: Unless otherwise specified, the term MS-9200UDLS isused in this document to refer to both the MS-9200UDLS and theMS-9200UDLS(E) FACPs (Fire Alarm Control Panels).

Features• Listed to UL standard 864, 9th edition.• On-board DACT.• Remote site or local USB port upload/download, using PS-

Tools.• Four (4) Style Y (Class B) NAC circuits, which can be con-

verted to four (4) Style Z (Class A) circuits with optionalZNAC-92 converter module. (Up to 6.0 amps total NACpower when using optional XRM-24B.)

• Selectable strobe synchronization for System Sensor,Wheelock, and Gentex devices.

• Remote Acknowledge, Silence, Reset and Drill via address-able monitor modules or LCD-80F, ANN-80 or Legacy ACSAnnunciators.

• ANN-BUS for connection to following optional modules (cannotbe used if ACS annunciators are used):

– ANN-80(-W) Remote LCD Annunciator

– ANN-I/O LED Driver– ANN-S/PG Printer Module– ANN-RLY Relay Module

– ANN-LED Annunciator Module– ANN-RLED Annunciator Module alarms only– ROME Relay Option Module Enclosure

• ACS/TERM: – ACS Annunciators: Up to 32 Legacy ACM Series annun-

ciators (ACM-16AT or ACM-32 series). Cannot be used ifANN-BUS devices are used.

– Terminal-mode Annunciators: Up to 32 Legacy LCD-80Fremote annunciators.

Page 2: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

Page 2 of 6 — DF-60601:A1 • 12/07/2010

• EIA-232 printer/PC interface (variable baud rate) on maincircuit board, for use with optional UL-listed printer PRN-6F.

• Integral 80-character LCD display with backlighting.

• Real-time clock/calendar with automatic daylight savingscontrol.

• Detector sensitivity test capability (NFPA 72 compliant).• History file with 1,000-event capacity.• Maintenance alert warns when smoke detector dust accu-

mulation is excessive.• Automatic device type-code verification.

• One person audible or silent walk test with walk-test log andprintout.

• Point trouble identification.• Waterflow (nonsilenceable) selection per monitor point.• System alarm verification selection per detector point.

• PAS (Positive Alarm Sequence) and presignal delay perpoint (NFPA 72 compliant).

NOTE: Only detectors may participate in PAS.

SLC LOOP:

• SLC can be configured for NFPA Style 4, 6, or 7 operation.• SLC supports up to 198 addressable devices per loop (99

detectors and 99 monitor, control, or relay modules).• SLC loop maximum length 10,000 ft. (3,000 m.).

See installation manual for wire tables.

NOTIFICATION APPLIANCE CIRCUITS (NACS):

• Four onboard NACs with additional NAC capability usingoutput control modules (CMF-300 or CMF-300-6). The fourClass B NACs can be converted to four Class A NACs withoptional ZNAC-92 converter module.

• Silence Inhibit and Auto Silence timer options.• Continuous, March Time, Temporal or California code for

main circuit board NACs with two-stage capability.• Selectable strobe synchronization per NAC.

• 2.5 amps maximum per each NAC circuit.NOTE: Maximum 24VDC system power output is shared amongall NAC circuits and 24VDC special-application auxiliary poweroutputs. Total available output is 3.0 amps. Using the optionalXRM-24B transformer increases 24VDC output to 6.0 amps.

PROGRAMMING AND SOFTWARE:

• Autoprogram (learn mode) reduces installation time.

• Custom English labels (per point) may be manually enteredor selected from an internal library file.

• Three Form-C relay outputs (two programmable).• 99 software zones.• Continuous fire protection during online programming at the

front panel. • Program Check automatically catches common errors not

linked to any zone or input point.• OFFLINE PROGRAMMING: Create the entire program in

your office using a Windows®-based software package(order programming kit PS-Tools, separately). Upload/download system programming locally to the MS-9200UDLS Rev 3 in less than one minute.

• USB upload/download programming with standard Male-Ato Male-B cable.

User Interface

LED INDICATORS

• AC Power (green)

• Fire Alarm (red)

• Supervisory (yellow)

• Alarm Silenced (yellow)• System Trouble (yellow)• Maintenance/Presignal (yellow)

• Disabled (yellow)• Battery Fault (yellow)• Ground Fault (yellow)

KEYPAD CONTROLS

• Acknowledge/Step• Alarm Silence

• Drill• System Reset (lamp test)• 16-key alpha-numeric pad (similar to telephone keypad)

• 4 cursor keys• Enter

Product Line InformationMS-9200UDLS: 198-point addressable Fire Alarm ControlPanel, one SLC loop. Includes 80-character LCD display, sin-gle printed circuit board mounted on chassis, and cabinet. 120VAC operation.

MS-9200UDLSE: Same as MS-9200UDLS, except with 240VAC operation.

4XTMF Reverse Polarity Transmitter Module: Providessupervised output for local energy municipal box transmitter,alarm, and trouble.

ZNAC-92: Optional converter module which converts four (4)Style Y (Class B) NAC circuits to four (4) Style Z (Class A) cir-cuits.

PK-CD Programming software for Windows®-based PC com-puter (cable not included), available on www.firelite.com.

DP-9692: Optional dress panel for MS-9200UDLS Rev 3.

TR-CE: Optional trim Ring for semi-flush mounting.

BB-26: Battery backbox, holds up to two 25 AH batteries andCHG-75.

BB-55F: Battery box, houses two 55 AH batteries.

CHG-75: Battery charger for lead-acid batteries with a ratingof 25 to 75 AH.

CHG-120F: Remote battery charging system for lead-acid bat-teries with a rating of 55 to 120 AH. Requires additional BB-55F for mounting.

BAT Series: Batteries, see data sheet DF-52397.

XRM-24B(E): Optional transformer. Increases system poweroutput to 6.0 amps. Use XRM-24BE with MS-9200UDLS Rev3(E).

PRT/PK-CABLE: Cable printer/personal computer interfacecable; required for printer or for local upload/download pro-gramming and updating panel firmware.

PRN-6F: UL listed compatible event printer. Uses tractor-fedpaper.

IPDACT-2/2UD, IPDACT Internet Monitoring Module:Mounts in bottom of enclosure with optional mounting kit (PNIPBRKT). Connects to primary and secondary DACT tele-phone output ports for internet communications over customerprovided ethernet internet connection. Requires compatibleTeldat VisorALARM Central Station Receiver. Can use DHCPor static IP. (See data sheet DF-60407 or DF-52424 for moreinformation.)

Gerry
Line
Page 3: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

DF-60601:A1 • 12/07/2010 — Page 3 of 6

IPBRKT: Mounting kit for IPDACT-2/2UD in common enclo-sure.

IPSPLT: Y-adaptor option allows connection of both paneldialer outputs to one IPDACT-2/2UD cable input.

COMPATIBLE ANNUNCIATORS

ANN-80(-W): LCD Annunciator is a remote LCD annunciatorthat mimics the information displayed on the FACP LCD dis-play. Recommended wire type is un-shielded. (Basic model isred; order -W version for white; see DF-52417.)

ANN-LED: Annunciator Module provides three LEDs for eachzone: Alarm, Trouble and Supervisory. Ships with red enclo-sure (see DF-60241).

ANN-RLED: Provides alarm (red) indicators for up to 30 inputzones or addressable points. (See DF-60241).

ANN-RLY: Relay Module, which can be mounted inside thecabinet, provides 10 programmable Form-C relays. (See DF-52431.)

ROME: Relay Option Module Enclosure. Provides one ANN-RLY Relay Module already installed. The ROME Series pro-vides mounting space for one additional Relay Module or oneaddressable Multi-module. (See Installation Sheet PN 53530.)

ANN-S/PG: Serial/Parallel Printer Gateway module provides aconnection for a serial or parallel printer. (See DF-52429.)

ANN-I/O: LED Driver Module provides connections to a usersupplied graphic annunciator. (See DF-52430.)

ACM-8RF: Relay module provides 8 Form-C 5.0 amp relays.

ACS-LED Zone Series: LED-type fire annunciators capable ofproviding up to 99 software zones of annunciation. Available inincrements of 16 or 32 points to meet a variety of applications.

LDM Graphic Series: Lamp Driver Module series for use withcustom graphic annunciators.

LCD-80F (Liquid Crystal Display) point annunciator:80-character, backlit LCD-type fire annunciators capable ofdisplaying English-language text.

NOTE: For more information on Compatible Annunciators for usewith the MS-9200UDLS Rev 3, see the following data sheets (doc-ument numbers) ACM-8RF (DF-51555), ACS/ACMSeries (DF-52378), LDM Series (DF-51384), LCD-80F (DF-52185).

LITESPEED COMPATIBLE ADDRESSABLE DEVICES

All feature a polling LED and rotary switches for addressing.

CP355: Addressable low-profile ionization smoke detector.

SD355: Addressable low-profile photoelectric smoke detector.

SD355T: Addressable low-profile photoelectric smoke detec-tor with thermal sensor.

SD355R: Addressable remote test capable detector for usewith D355PL or DNR(W) duct smoke detector housings.

H355: Fast-response, low-profile heat detector.

H355R: Fast-response, low-profile heat detector with rate-of-rise option.

H355HT: Fixed high-temperature detector that activates at190F/88C.

AD355(A): Low-profile, intelligent, “Adapt” multi-sensor detec-tor (B350LP base included).

BEAM355: Intelligent beam smoke detector.

BEAM355S: Intelligent beam smoke detector with integralsensitivity test.

D355PL: Innovair Flex low-flow non-relay duct-detector hous-ing. SD355R included.

DNRW: Innovair Flex low-flow non-relay duct-detector hous-ing, with NEMA-4 rating. Watertight. (Order SD355R sepa-rately.)

MMF-300: Addressable Monitor Module for one zone of nor-mally-open dry-contact initiating devices. Mounts in standard4.0" (10.16 cm.) box. Includes plastic cover plate and end-of-line resistor. Module may be configured for either a Style B(Class B) or Style D (Class A) IDC.

MDF-300: Dual Monitor Module. Same as MMF-300 except itprovides two Style B (Class B) only IDCs.

MMF-301: Miniature version of MMF-300. Excludes LED andStyle D option. Connects with wire pigtails. May mount indevice backbox.

MMF-302: Similar to MMF-300, but may monitor up to 20 con-ventional two-wire detectors. Requires resettable 24 VDCpower. Consult factory for compatible smoke detectors.

Gerry
Line
Page 4: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

Page 4 of 6 — DF-60601:A1 • 12/07/2010

CMF-300: Addressable Control Module for one Style Y/Z(Class B/A) zone of supervised polarized Notification Appli-ances. Mounts directly to a 4.0" (10.16 cm.) electrical box.Notification Appliance Circuit option requires external 24 VDCto power notification appliances.

CRF-300: Addressable relay module containing two isolatedsets of Form-C contacts, which operate as a DPDT switch.Mounts directly to a 4.0" (10.16 cm.) box, surface mount usingthe SMB500.

BG-12LX: Addressable manual pull station with interface mod-ule mounted inside.

I300: Fault Isolator Module. This module isolates the SLC loopfrom short circuit conditions (required for Style 6 or 7 opera-tion).

SMB500: Used to mount all modules except the MMF-301 andM301.

MMF-300-10: Ten-input monitor module. Mount one or twomodules in a BB-2F cabinet (optional). Mount up to six mod-ules on a CHS-6 chassis in a BB-6F.

MMF-302-6: Six-zone interface module for compatible conven-tional two-wire detectors. Mount one or two modules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6chassis in a BB-6F.

CMF-300-6: Six-circuit supervised control module. Mount oneor two modules in a BB-2F cabinet (optional). Mount up to sixmodules on a CHS-6 chassis in a BB-6F.

CRF-300-6: Six Form-C relay control module. Mount one ortwo modules in a BB-2F cabinet (optional). Mount up to sixmodules on a CHS-6 chassis in a BB-6F.

NOTE: 1) For more information on Compatible AddressableDevices for use with the MS-9200UDLS Rev 3, see the followingdata sheets (document numbers): AD355 (DF-52324), BG-12LX(DF-52013), CMF-300-6 (DF-52365), CRF-300-6 (DF-60379),CMF/CRF Series (DF-52130), CP355 (DF-52383), D355PL (DF-52398), H355 Series (DF-52385), I300 (DF-52389), MMF-300Series/MDF-300 (DF-52121), MMF-300-10 (DF-52347), MMF-302-6 (DF-52356), SD355/SD355T (DF-52384). 2) Legacy 300Series detection devices such as the CP300/CP350, SD300(T)/SD350(T) and older modules such as the M300, M301, M302,C304, and BG-10LX are not compatible with LiteSpeed polling. Ifthe SLC contains one of these devices, polling must be set forstandard LiteSpeed protocol. Please consult factory for furtherinformation on previous 300 Series devices.

Wiring RequirementsWhile shielded wire is not required, it is recommended that allSLC wiring be twisted-pair to minimize the effects of electricalinterference. Wire size should be no smaller than 18 AWG(0.78 mm²) and no larger than 12 AWG (3.1 mm²). The wiresize depends on the length of the SLC circuit. Refer to thepanel manual for wiring details.

( )

Page 5: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

DF-60601:A1 • 12/07/2010 — Page 5 of 6

Page 6: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

Page 6 of 6 — DF-60601:A1 • 12/07/2010

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.

For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105.www.firelite.com

Made in the U.S. A.

System Capacity• Intelligent Signalling Line Circuits....................................... 1 • Addressable device capacity .......................................... 198• Programmable software zones ......................................... 99

• ACS Annunciators ............................................................ 32• ANN-bus devices.............................................................. 16

Electrical SpecificationsAC Power: MS-9200UDLS Rev 3: 120 VAC, 60 Hz, 3.0 amps.MS-9200UDLS Rev 3E: 240 VAC, 5 0 Hz, 1.5 amps. Wire size:minimum 14 AWG (2.00 mm²) with 600 V insulation.

Battery charger capacity: 7 AH - 18 AH batteries. Up to two18 Ah batteries can be housed in the FACP cabinet. Largerbatteries require an external battery charger such as the CHG-75 or CHG-120, and a separate battery cabinet such as theBB-26 or NFS-LBB.

Communication Loop: Supervised and power-limited.

Notification Appliance Circuits: Each terminal block pro-vides connections for two Style Y (Class B) for a total of fourStyle Y (Class B) or with an optional ZNAC-92 module con-verts to four Style Z (Class A) NACs. Maximum signaling cur-rent per circuit: 2.5 amps. End-of-Line Resistor: 4.7K ohm, 1/2watt (P/N 71252 UL listed) for Style Y (Class B) NAC. Refer topanel documentation and Fire•Lite Device Compatibility Docu-ment for listed compatible devices.

Two Programmable Relays and One Fixed Trouble Relay: Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30VAC (resistive). Form-C relays.

Special Application Non-resettable Power (24 VDC Nomi-nal): Jumper selectable (JP4) for conversion to resettablepower output. Up to 1.0 amp total DC current available fromeach output. Power-limited.

Special Application Resettable Power (24 VDC nominal):Jumper selectable (JP6) for conversion to non-resettablepower. Up to 1.0 amp total DC current available. Refer to theFire•Lite Device Compatibility Document for listed compatibledevices.

Remote Sync Output: Remote power supply synchronizationoutput. Nominal special application power: 24 VDC. Maximumcurrent: 300 mA. End-of-Line Resistor: 4.7K ohm. Outputlinked to NAC 1 control. Supervised and power-limited.

Telephone Interface: Unless used with Teldat VISORALARM,requires dedicated business telephone number with a mini-mum of 5 volts DC (off-hook voltage). Obtain dedicated phoneline directly from your local phone company. Do not use sharedphone lines or PBX (digital) type phone line extensions.

Cabinet SpecificationsDoor: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x0.12" (.30 cm.) deep. Backbox: 19.00" (48.26 cm.) high x

16.65" (42.29 cm.) wide x 5.20" (13.34 cm.) deep. Trim Ring(TR-CE): 22.00" (55.88 cm.) high x 19.65" (49.91 cm.) wide.

Shipping SpecificationsWeight: 26.9 lbs. (12.20 kg.) Dimensions: 20.00” (50.80 cm.)high x 22.5” (57.15 cm.) wide x 8.5” (21.59 cm.) deep.

Temperature and Humidity RangesThis system meets NFPA requirements for operation at 0 –49°C/32 – 120°F and at a relative humidity 93% ± 2% RH(noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, theuseful life of the system's standby batteries and the electroniccomponents may be adversely affected by extreme tempera-ture ranges and humidity. Therefore, it is recommended thatthis system and its peripherals be installed in an environmentwith a normal room temperature of 15 – 27°C/60 – 80°F.

NFPA StandardsThe MS-9200UDLS Rev 3 complies with the following NFPA72 Fire Alarm Systems requirements:

– LOCAL (Automatic, Manual, Waterflow and SprinklerSupervisory).

– AUXILIARY (Automatic, Manual and Waterflow) (requires4XTMF).

– REMOTE STATION (Automatic, Manual, Waterflow andSprinkler Supervisory) (Where a DACT is not accepted,the alarm, trouble and supervisory relays may be con-nected to UL 864 listed transmitters. For reverse polaritysignaling of alarm and trouble, 4XTMF is required.)

– PROPRIETARY (Automatic, Manual, Waterflow andSprinkler Supervisory).

– CENTRAL STATION (Automatic, Manual, Waterflow andSprinkler Supervisory).

– OT, PSDN (Other Technologies, Packet-switched DataNetwork)

Agency Listings and ApprovalsThe listings and approvals below apply to the basic MS-9200UDLS Rev 3 control panel. In some cases, certain mod-ules may not be listed by certain approval agencies, or listingmay be in process. Consult factory for latest listing status.

• UL Listed: S624• FM approved • CSFM: 7165-0075:0208

• MEA: 120-06-EFor ULC-listed version, see DF-60599.

FireLite® Alarms® is a registered trademark of Honeywell International Inc.Wheelock® is a registered trademark of and Exceder™ is a trademark ofCooper Notification.©2010 by Honeywell International Inc. All rights reserved. Unauthorized useof this document is strictly prohibited.

SYSTEM SPECIFICATIONS

Page 7: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION

OFFICE OF THE STATE FIRE MARSHAL

FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE

LISTING No. 7165-0075:0208 Page 1 of 1

CATEGORY: 7165 -- FIRE ALARM CONTROL UNIT (COMMERCIAL)

LISTEE: FIRE-LITE ALARMS INC.One Fire-Lite Place, Northford, CT 06410-1653

Contact: Brian Reynolds (203) 484-7161 Fax (203) 484-7309

Email: [email protected]

DESIGN: Models MS-9200UD and *MS-9200UDLS addressable control units. Local, auxiliary, remote

station, central station and proprietary (protected premise). Refer to listee's data sheet for

detailed product description, operational considerations and required/optional accessories.

When required, accessories shall be CSFM listed.

RATING: 120 VAC, 60 Hz, 2.06 A Primary, 24 VDC Secondary

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances

and in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model number, electrical rating and UL label.

APPROVAL: Listed as an addressable fire alarm control panel for use with separately listed compatible

initiating and indicating devices. Refer to listee’s Installation Instruction Manual for details .

This control unit can generate a distinctive three-pulse Temporal Pattern Fire Alarm

Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition.

This control unit meets the requirements of UL-864, 9th Edition Standards.

NOTE: For Fire Alarm Verification Feature (delay of fire alarm signal), the maximum

Retard/Reset/Restart period shall not exceed 30 seconds.

04-21-09

July 01, 2013Date Issued: Listing Expires June 30, 2014

Authorized By:

Fire Engineering Division

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed

the test results and/or other data but does not make an independent verification of any claims. This listing is not

an endorsement or recommendation of the item listed. This listing should not be used to verify correct

operational requirements or installation criteria. Refer to listee’s data sheet, installation instructions and/or other

JAMES PARSEGIAN, Program Coordinator

Page 8: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

DF-52310:A2 • 5/17/13 — Page 1 of 4

FCPS-24FS88-Amp, 24-Volt Power Supply

Power Supplies/Accessories

DF-52310:A2 • D-050

GeneralThe Fire•Lite FCPS-24FS8(C/E) is a compact, cost-effec-tive, 8-amp remote power supplies with battery charger. TheFCPS-24FS8C/E) may be connected to any 12 or 24 volt firealarm control panel (FACP) or may stand-alone. Primary appli-cations include notification appliance (bell) circuit (NAC)expansion (to support ADA requirements and NAC synchroni-zation) or auxiliary power to support 24 volt system accesso-ries. The FCPS provides regulated and filtered 24 VDC powerto four notification appliance circuits configured as either twoClass B (Style Y) and Class A (Style Z, with ZNAC-4 optionmodule) or four class B only. Alternately, the four outputs maybe configured as any combination of resettable/non-resettablepower outputs (optimal for powering four-wire smoke detec-tors. The FFCPS-24FS8(C/E) also contains a battery chargercapable of charging up to 18.0 Amp hour batteries. FCPS-24FS8C/E) is ULC-listed.

NOTE: Unless otherwise specified, the term FCPS-24FS8 used inthis document refers to the standard FCPS-24FS8, FCPS-24FS8C, FCPS-24FS8E

Features• UL-Listed Notification Appliance Circuit (NAC) synchroniza-

tion using System Sensor, Wheelock, or Gentex “Com-mander2” appliances.

• Operates as a “sync-follower” or as a “sync-generator”(default). See note on page 2.

• Contains two fully-isolated input/control circuits - triggeredfrom FACP NAC (NAC expander mode) or jumped perma-nently “ON” (stand-alone mode).

• Two Class B (Style Y) or Class A (Style Z, with ZNAC-4module) NACs (circuits 1 & 3)

• 8-amp full load output, with 3 amps maximum/circuit, inNAC expander mode (UL 864).

• 6-amp continuous output in stand-alone mode (UL 1481).• Compatible with coded inputs; signals passed through.

• Optional power-supervision relay (EOLR-1).• In stand-alone mode, output power circuits may be config-

ured as: resettable, (reset line from FACP required),non-resettable, or a mix of two and two.

• Fully regulated and filtered power output - optimal for pow-ering four-wire smoke detectors, annunciators, and othersystem peripherals requiring regulated/filtered power.

• Power-limiting technology meets UL power-limiting require-ments.

• Form-C normally-closed trouble relay.

• Fully supervised power supply, battery, and NACs.• Selectable earth fault detection.• AC trouble report selectable for immediate 2-hour delay.

• Works with virtually any UL 864 fire alarm control which uti-lizes an industry-standard reverse-polarity notification cir-cuit (including unfiltered and unregulated bell power).

• Requires input trigger voltage of 9 - 32 VDC.

• Self-contained in compact, locking cabinet - 15”H x 14.5”Wx 2.75”D (cm: 38.1H x 36.83W x 6.985D).

• Includes integral battery charger capable of charging up to18 AH batteries. Cabinet capable of housing 7.0 AH batter-ies.

• Battery charger may be disabled via DIP switch for applica-tions requiring larger batteries.

• Fixed, clamp-type terminal blocks accommodate up to 12AWG (3.1mm2) wire.

SpecificationsPrimary (AC) Power:

• FCPS-24FS8: 120 VAC, 60 Hz, 3.2A maximum.• FCPS-24FS8/E: 240 VAC, 50 Hz, 1.6A maximum.• Wire Size: minimum #14 AWG (2.0mm2) with 600 V insula-

tion.Control Input Circuit:

• Trigger Input Voltage: 9 to 32 VDC.• Trigger Current: 2.0 mA (16 - 32 V); Per Input: 1.0 mA (9

- 16 V).Trouble Contact Rating: 5 A at 24 VDC.

Auxiliary Power Output: Specific application power 500 mAmaximum.

Output Circuits:

• +24 VDC filtered, regulated.• 3.0 A maximum for any one circuit.• Total continuous current for all outputs (stand-alone mode):

– FCPS-24FS8: 6.0 A maximum.• Total short-term current for all outputs (NAC expander mode):

– FCPS-24FS8: 8.0 A maximum.

Page 9: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

Page 2 of 4 — DF-52310:A2 • 5/17/13

Secondary Power (Battery) Charging Circuit:

• Supports lead-acid batteries only.• Float-charge voltage: 27.6 VDC.• Maximum current charge: 250 mA.

• Maximum battery capacity: 7.0 AH.

ApplicationsExample 1: Expand notification appliance power an additional8.0 A. Use up to four Class B (Style Y) outputs or four Class A(Style Z) outputs (using ZNAC-4). For example, the FACP noti-fication appliance circuits will activate the FCPS when reverse-polarity activation occurs. Trouble conditions on the FCPS aresensed by the FACP through the notification appliance circuit.

Example 2: Use the FCPS to expand auxiliary regulated 24-volt system power up to 6.0 A. Both resettable and non-reset-table power options are available. Resettable outputs are cre-ated by connecting the resettable output from the FACP to oneor both of the FCPS inputs.

Example 3: Use addressable control modules to activate theFCPS instead of activating it through the FACP notificationappliance circuits. This typically allows for mounting the FCPSat greater distances* away from the FACP while expandingsystem architecture in various applications.

For example, an addressable control module is used to acti-vate the FCPS, and an addressable monitor module is used tosense FCPS trouble conditions. Local auxiliary power outputfrom the FCPS provides power to the addressable controlmodule.

*NOTE: Addressable FACPs are capable of locating control andmonitor modules at distances of up to 10,000 feet (3,046 meters) .

Sync Follower/Generator NoteIn some installations, it is necessary to synchronize the flashtiming of all strobes in the system for ADA compliance.Strobes accomplish this by monitoring very short timing pulseson the NAC power which are created by the FACP. Wheninstalled at the end of a NAC wire run, the FCPS-24FS8 cantrack (i.e. “follow”) the strobe synchronization timing pulses onthe existing NAC wire run. This maintains the overall systemflash timing of the additional strobes attaches to the FCPS.

When the FCPS-24FS8 is configured (via DIP switch settings)as a “sync follower,” the FCPS’s NAC outputs track the strobesynchronization pulses present at the FCPS’s sync input ter-minal. The pulses originate from an upstream FACP or otherpower supply.

When the FCPS-24FS8 is configured (via DIP switch settings)as a “sync generator,” the FCPS’s sync input terminals are notused. Rather, the FCPS is the originator of the strobe synchro-nization pulses on the FCPS’s NAC outputs. In “sync genera-tor” mode, the sync type (System Sensor, Wheelock, orGentex) is selectable via DIP switch settings.

Standards and CodesThe FCPS-24FS8 complies with the following standards:

• NFPA 72 National Fire Alarm Code.• UL 864 Standard for Control Units for Fire Alarm Systems

(NAC expander mode).• UL 1481 Power Supplies for Fire Alarm Systems.

Agency Listings and ApprovalsThese listings and approvals apply to the modules specified inthis document. In some cases, certain modules or applicationsmay not be listed by certain approval agencies, or listing maybe in process. Consult factory for latest listing status.

• UL Listed: S2424

• ULC Listed: S2424• CSFM Approved: 7315-0075:206• MEA: 219-02E

Ordering InformationFCPS-24FS8: 6.0 A, 120 VAC remote charger power supply.Includes main printed circuit board, transformers, enclosure(15”H x 14.5”W x 2.75”D [cm: 38.1H x 36.83W x 6.985D]), andinstallation instructions.

FCPS-24FS8 is ULC-listed.

FCPS-24FS8E: 6.0 A, 240 VAC remote charger power supply.Includes main printed circuit board, transformers, enclosure(15”H x 14.5”W x 2.75”D [cm: 38.1H x 36.83W x 6.985D]), andinstallation instructions.

ZNAC-4: Class A (Style Y) NAC option module.

EOLR-1: 12/24 VDC end-of-line relay for monitoring four-wiresmoke detector power.

BAT-1270: Battery, 12-volt, 7.0 AH (two required).

PS-1270: Battery, 12-volt, 7.0 AH (two required).

90286: Optional module mounting kit, is required to install anaddressable module on the power supply main circuit board.

Page 10: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

DF-52310:A2 • 5/17/13 — Page 3 of 4

6927blok.wm

f

Simplified Block Diagram

Page 11: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

Page 4 of 4 — DF-52310:A2 • 5/17/13

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.

For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105.www.firelite.com

System Sensor® and FireLite® Alarms are registered trademarks ofHoneywell International Inc. ©2013 by Honeywell International Inc. All rights reserved. Unauthorized useof this document is strictly prohibited.

Made in the U.S. A.

Board Layout

Page 12: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION

OFFICE OF THE STATE FIRE MARSHAL

FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE

LISTING No. 7315-0075:0206 Page 1 of 1

CATEGORY: 7315 -- POWER UNITS

LISTEE: FIRE-LITE ALARMS INC.One Fire-Lite Place, Northford, CT 06410-1653

Contact: Brian Reynolds (203) 484-7161 Fax (203) 484-7309

Email: [email protected]

DESIGN: Models FCPS-24FS6 and FCPS-24FS8 are power limited power supply/battery chargers

used for supervision and expanded power driving capability of up to four Notification Appliance

Circuits (FACP Fire Circuits, Signaling Devices) or resettable/non resettable outputs. Model

ZNAC-4 Class A converter. Refer to listee’s data sheet for additional detailed product

description and operational considerations.

RATING: 120 VAC, 24 VDC

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances

and in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, product designation, electrical rating and UL label.

APPROVAL: Listed as a Power Supply/Battery Charger for use with separately listed compatible fire alarm

control units.

NOTE:

*Rev. 05-06-05JW

July 01, 2013Date Issued: Listing Expires June 30, 2014

Authorized By:

Fire Engineering Division

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed

the test results and/or other data but does not make an independent verification of any claims. This listing is not

an endorsement or recommendation of the item listed. This listing should not be used to verify correct

operational requirements or installation criteria. Refer to listee’s data sheet, installation instructions and/or other

JAMES PARSEGIAN, Program Coordinator

Page 13: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

DF-52013:D • 4/13/2012 — Page 1 of 2

BG-12LXAddressable Manual Pull Station

Addressable Devices

DF-52013:D • E-100

FLP

ullS

tatio

n.jp

g

GeneralThe Fire·Lite BG-12LX is a state-of-the-art, dual-action (i.e.,requires two motions to activate the station) pull station thatincludes an addressable interface (mounted inside) forFire·Lite’s addressable fire alarm control panels (FACPs)Because the BG-12LX is addressable, the control panel candisplay the exact location of the activated manual station. Thisleads fire personnel quickly to the location of the alarm.

Features• Maintenance personnel can open station for inspection and

address setting without causing an alarm condition.

• Built-in bicolor LED, which is visible through the handle ofthe station, flashes in normal operation and latches steadyred when in alarm.

• Handle latches in down position and the word “ACTIVATED”appears to clearly indicate the station has been operated.

• Captive screw terminals wire-ready for easy connection toSLC loop (accepts up to 12 AWG/3.25 mm² wire).

• Can be surface mounted (with SB-10 or SB-I/O) or semi-flush mounted. Semi-flush mount to a standard single-gang, double-gang, or 4" (10.16 cm) square electrical box.

• Smooth dual-action design.• Meets ADAAG controls and operating mechanisms guide-

lines (Section 4.1.3[13]); meets ADA requirement for 5 lb.maximum activation force.

• Highly visible.• Attractive shape and textured finish.

• Key reset.• Includes Braille text on station handle.• Optional trim ring (BG12TR).

• Meets UL 38, Standard for Manually Actuated SignalingBoxes.

ConstructionShell, door, and handle are molded of durable polycarbonatematerial with a textured finish.

Specifications• Shipping Weight: 9.6 oz. (272.15 g)• Normal operating voltage: 24 VDC.• Maximum SLC loop voltage: 28.0 VDC.

• Maximum SLC standby current: 375 μA.• Maximum SLC alarm current: 5 mA.• Temperature Range: 32°F to 120°F (0°C to 49°C)

• Relative Humidity: 10% to 93% (noncondensing)• For use indoors in a dry location

InstallationThe BG-12LX will mount semi-flush into a single-gang, double-gang, or standard 4" (10.16 cm) square electrical outlet box, orwill surface mount to the model SB-10 or SB-I/O surface back-box. If the BG-12LX is being semi-flush mounted, then theoptional trim ring (BG12TR) may be used. The BG12TR is

usually needed for semi-flush mounting with 4" (10.16 cm) ordouble-gang boxes (not with single-gang boxes).

OperationPushing in, then pulling down on the handle causes it to latchin the down/activated position. Once latched, the word “ACTI-VATED” (in bright yellow) appears at the top of the handle,while a portion of the handle protrudes from the bottom of thestation. To reset the station, simply unlock the station with thekey and pull the door open. This action resets the handle; clos-ing the door automatically resets the switch.

Each manual station, on command from the control panel,sends data to the panel representing the state of the manualswitch. Two rotary decimal switches allow address settings (1 – 159 with Breakaway Tab removed for MS-9600 Series, 1 –99 and MS-9200UDLS, 1 – 50 for MS-9050UD).

Architectural/Engineering SpecificationsManual Fire Alarm Stations shall be non-coded, with a key-operated reset lock in order that they may be tested, and sodesigned that after actual Emergency Operation, they cannotbe restored to normal except by use of a key. An operated sta-tion shall automatically condition itself so as to be visuallydetected as activated. Manual stations shall be constructed ofred-colored polycarbonate material with clearly visible operat-ing instructions provided on the cover. The word FIRE shallappear on the front of the stations in white letters, 1.00 inches(2.54 cm) or larger. Stations shall be suitable for surfacemounting on matching backbox SB-10 or SB-I/O; or semi-flushmounting on a standard single-gang, double-gang, or4" (10.16 cm) square electrical box, and shall be installed

Page 14: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

Page 2 of 2 — DF-52013:D • 4/13/2012

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.

For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105.www.firelite.com

FireLite® Alarms® is a registered trademark of Honeywell International Inc.©2012 by Honeywell International Inc. All rights reserved. Unauthorized useof this document is strictly prohibited.

Made in the U.S. A.

within the limits defined by the Americans with Disabilities Act(ADA) or per national/local requirements. Manual Stationsshall be Underwriters Laboratories listed.

Manual stations shall connect with two wires to one of the con-trol panel SLC loops. The manual station shall, on commandfrom the control panel, send data to the panel representing thestate of the manual switch. Manual stations shall provideaddress setting by use of rotary decimal switches.

Product Line InformationBG-12LX: Dual-action addressable pull station. Includes keylocking feature. (Listed for Canadian and non-Canadian appli-cations.)

SB-10: Surface backbox; metal.

SB-I/O: Surface backbox; plastic.

BG12TR: Optional trim ring.

17003: Keys, set of two.

Agency Listings and ApprovalsIn some cases, certain modules or applications may not belisted by certain approval agencies, or listing may be in pro-cess. Consult factory for latest listing status.

• UL/ULC Listed: S711 (listed for Canadian and non-Cana-dian applications).

• MEA: 67-02-E.

• CSFM: 7150-0075:0184.• FM Approved. Patented: U.S. Patent No. D428,351; 6,380,846; 6,314,772;6,632,108.

Page 15: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION

OFFICE OF THE STATE FIRE MARSHAL

FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE

LISTING No. 7150-0075:0184 Page 1 of 1

CATEGORY: 7150 -- FIRE ALARM PULL BOXES

LISTEE: FIRE-LITE ALARMS INC.One Fire-Lite Place, Northford, CT 06410-1653

Contact: Brian Reynolds (203) 484-7161 Fax (203) 484-7309

Email: [email protected]

DESIGN: Models BG-12, BG-12S, BG-12NC, BG-12W, BG-12LW, BG-12WP, BG-12LWP, BG-12L,

BG-12LX, BG-12LA, BG-12PS, BG-12LSP, BG-12SP, BG-12LR, BG-12LRA, BG-12LAO,

BG-12LAOB, BG-12-LO, BG-12LOB, BG-12LPS, BG-12LPSP, BG-12SL, UT-PS1 and

UT-PS2 fire alarm pull boxes. The BG-12 series is a dual action pull station that has

normally open switch contacts. Refer to listee's data sheet for detailed product description

and operational considerations.

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances

and in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model number and UL label.

APPROVAL: Listed as fire alarm boxes for use with separately listed compatible fire alarm control units.

Models BG-12WP, BG-12W, BG-12LW and BG-12LWP are intended for outdoor use when

installed with Model WP-10 back box. Models BG-LAOB and BG-12LOB are intended for

outdoor use when installed with Model WBB or WP-10 back box.

* These manual pull boxes meet the requirements of UL Standard 38, 1999 Edition and

California amendments.

XLF: 7150-0028:0199

*Updated 08-17-09 fm

July 01, 2013Date Issued: Listing Expires June 30, 2014

Authorized By:

Fire Engineering Division

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed

the test results and/or other data but does not make an independent verification of any claims. This listing is not

an endorsement or recommendation of the item listed. This listing should not be used to verify correct

operational requirements or installation criteria. Refer to listee’s data sheet, installation instructions and/or other

JAMES PARSEGIAN, Program Coordinator

Page 16: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

DF-52384:C • 12/07/2011 — Page 1 of 2

SD355(A) SeriesAddressable Photoelectric Smoke Detectors

Addressable Devices

DF-52384:C • E-160

GeneralThe SD355(A), SD355T(A), and SD355R(A) addressable, low-profile plug-in photoelectric detectors use a state-of-the-art pho-toelectric sensing chamber with communications to provideopen area protection and are used exclusively with Fire•Lite’sAddressable Fire Alarm Control Panels (FACPs). TheSD355T(A) adds thermal sensors that will alarm at a fixed tem-perature of 135°F (57°C). Since these detectors are address-able, they will help emergency personnel quickly locate a fireduring its early stages, potentially saving precious rescue timewhile also reducing property damage. Two LEDs on each sen-sor light to provide a local, visible sensor indication. RemoteLED annunciator capability is available as an optional acces-sory, PN RA100Z(A). The SD355R(A) is a remote test capabledetector for use with D355PL(A) or DNR(A)/DNRW duct smokedetector housings.

FeaturesSLC loop

• Two-wire loop connection.• Unit uses base for wiring.Addressing

• Addressable by device.• Rotary, decimal addressing: 01 – 99 with MS-9200 series,

and 01 – 159 with MS-9600 series.Architecture

• Unique single-source, dual-chamber design to respondquickly and dependably to a broad range of fires.

• Sleek, low-profile design.• Integral communications and built-in type identification.• Built-in tamper-resistant feature.• Removable cover and insect-resistant screen for simple field

cleaning.Operation

• Withstands air velocities up to 4,000 feet-per-minute (20 m/sec.) without triggering a false alarm.

• Factory preset at 1.5% nominal sensitivity for panel alarmthreshold level.

• Visible LED “blinks” when the unit is addressed (communicat-ing with the fire panel) and latches on in alarm.

Mechanicals

• Sealed against back pressure.• Direct surface mounting or electrical box mounting.• Mounts to: single-gang box, 3.5" (8.89 cm) or 4.0" (10.16 cm)

octagonal box, or 4.0" (10.16 cm) square electrical box (usinga plaster ring — included).

Other system features

• Fully coated circuit boards and superior RF/transient protec-tion.

• 94-V0 plastic flammability rating.• Low standby current.Options

• Remote LED output connection, PN RA100Z(A).

ApplicationsUse photoelectric detectors in life-safety applications to providea broad range of fire-sensing capability, especially where smol-dering fires are anticipated. Ionization detectors are often betterthan photoelectric detectors at sensing fast, flaming fires.

ConstructionThese detectors are constructed of off-white fire resistant plas-tic. SD355(A) series plug-in, low-profile smoke detectors aredesigned to commercial standards and offer an attractiveappearance.

InstallationSD355(A) series plug-in detectors use a detachable mountingbase to simplify installation, service and maintenance.

Mount base (all base types) on an electrical backbox which is atleast 1.5" (3.81 cm) deep. For a chart of compatible junctionboxes, see DF-60059.

NOTE: Because of the inherent supervision provided by the SLCloop, end-of-line resistors are not required. Wiring “T-taps” orbranches are permitted for Style 4 (Class B) wiring. SD355R(A)mounts in a D355PL(A) or DNR(A)/DNRW duct detector housing.

OperationEach SD355(A) series detector uses one of 99 possibleaddresses on the MS-9200 series and up to 318 (159 on eachloop) on the MS-9600 series Signaling Line Circuit (SLC). Itresponds to regular polls from the system and reports its typeand status.

The addressable photoelectric sensor in the SD355(A) serieshas a unique unipolar chamberthat responds quickly and uni-formly to a broad range of smoke conditions. It can withstandwind gusts up to 4,000 feet-per-minute (20 m/sec.) withoutsending an alarm level signal. Because of its unipolar chamber,the SD355(A) series is approximately two times more respon-sive than most photoelectric sensors. This makes it a more sta-ble detector.

SD355(A) in B210LP(A) Base B21

0-29

51.jp

g

Page 17: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

Page 2 of 2 — DF-52384:C • 12/07/2011

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.

For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105.www.firelite.com

Fire•Lite® Alarms is a registered trademark of Honeywell International Inc. ©2011 by Honeywell International Inc. All rights reserved. Unauthorized useof this document is strictly prohibited.

Made in the U.S. A.

Detector Sensitivity TestEach detector can have its sensitivity tested (required per NFPA72, Chapter 14 on Inspection, Testing and Maintenance) wheninstalled/connected to a MS-9200 series or MS-9600 seriesaddressable fire alarm control panel. The results of the sensitiv-ity test can be printed off the MS-9200 series or MS-9600 seriesfor record keeping.

SpecificationVoltage range: 15 – 32 VDC (peak).

Standby current: 300 μA @ 24 VDC.

LED current: 6.5 mA @ 24 VDC (latched “ON”).

Air velocity: 4,000 ft./min. (20 m/sec.) maximum.

Size: 2.1" (5.33 cm) high; base determines diameter.

– B210LP(A): 6.1" (15.5 cm) diameter.– B501(A): 4.1" (10.4 cm) diameter.– B200SR(A): 6.875" (17.46 cm) diameter. – B224RB(A): 6.2" (15.748 cm) diameter.

Weight: 3.6 oz. (102 g).

Operating temperature range: for SD355(A): 0°C to 49°C(32°F to 120°F); for SD355T(A): 0°C to 38°C (32°F to 100°F).SD355R(A): installed in a DNR(A)/DNRW -20°C to 70°C (-4°Fto 158°F).

Temperature: 0°C – 49°C (32°F – 120°F).

Relative humidity: 10% – 93%, non-condensing.

ListingsListings and approvals below apply to the SD355(A),SD355T(A), and SD355RT(A) detectors. In some cases, certainmodules may not be listed by certain approval agencies, or list-ing may be in process. Consult factory for latest listing status.

• UL Listed: S1059.• ULC Listed: S1059.• CSFM: 7272-0075:0194.• MEA: 243-02-E.• FM approved.

Product Line InformationNOTE: “A” suffix indicates ULC Listed model.

SD355: Adressable photoelectric detector; B210LP baseincluded.

SD355A: Sames as SD355 with ULC Listing; B210LPA baseincluded.

SD355T: Same as SD355 but with thermal element; B210LPbase included.

SD355TA: Same as SD355T with ULC Listing; B210LPA baseincluded.

SD355R: Remote test capable addressable photoelectric detec-tor for use with a D355PL(A) or DNRA/DNRW duct detectorhousing; B210LP base included.

SD355RA: Same as SD355R with ULC Listing for use with aD355PLA or DNRA duct detector housing; B210LPA baseincluded.

INTELLIGENT BASESNOTE: “A” suffix indicates ULC Listed model.

NOTE: The detector’s plug-in base can be changed off for specialapplications. For details about intelligent bases and their mount-ing, see DF-60059.

B210LP(A): Plug-in detector base (included); standard U.S.flanged low-profile mounting base.

B210LPBP: Bulk pack of B210LP; package contains 10.

B501(A): Standard European flangeless mounting base.

B501BP: Bulk pack of B501; package contains 10.

B200SR(A): Intelligent sounder base capable of producingsound output with ANSI Temporal 3 or continuous tone.Replaces B501BH series bases in retrofit applications.

B224RB(A): Plug-in System Sensor relay base. Screw termi-nals: up to 14 AWG (2.0 mm²). Relay type: Form-C. Rating: 2.0A @ 30 VDC resistive; 0.3 A @ 110 VDC inductive; 1.0 A @ 30VDC inductive.

B224BI(A): Plug-in System Sensor isolator detector base.Maximum 25 devices between isolator bases (see DF-52389).

ACCESSORIESF110: Retrofit flange to convert B210LP(A) to match theB350LP(A) profile, or to convert older high-profile bases to low-profile.

F110BP: Bulk pack of F110; package contains 15.

F210: Replacement flange for B210LP(A) base.

RA100Z(A): Remote LED annunciator. 3 – 32 VDC. Mounts to aU.S. single-gang electrical box. For use with B501(A) andB210LP(A) bases only.

SMB600: Surface mounting kit

M02-04-00:Test magnet.

M02-09-00: Test magnet with telescoping handle.

XR2B: Detector removal tool. Allows installation and/or removalof detector heads from bases in high ceiling applications.

XP-4: Extension pole for XR2B. Comes in three 5-foot (1.524 m)sections.

T55-127-010: Detector removal tool without pole.

BCK-200B: Black detector covers for use with SD355(A) only;box of 10.

WCK-200B: White detector covers for use with SD355(A) only;box of 10.

Page 18: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION

OFFICE OF THE STATE FIRE MARSHAL

FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE

LISTING No. 7272-0075:0194 Page 1 of 1

CATEGORY: 7272 -- SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC

LISTEE: FIRE-LITE ALARMS INC.One Fire-Lite Place, Northford, CT 06410-1653

Contact: Brian Reynolds (203) 484-7161 Fax (203) 484-7309

Email: [email protected]

DESIGN: Models SD350, SD350T, SD355, SD355R*, SD355T and AD355 photoelectric type smoke

detectors. Model SD350T and SD355T has a 135°F supplement integral heat sensor which

only assists in a fire situation. The purpose of this thermal circuitry is to increase the

sensitivity of the detector. This thermal circuitry is NOT approved for use as a heat detector.

Refer to listee's printed data sheet for additional detailed product description and operational

considerations.

RATING: 24VDC

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances

and a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model number, electrical rating and UL label.

APPROVAL: Listed as photoelectric smoke detectors for use with separately listed compatible fire alarm

control units. All units are suitable for open areas and inside duct installations with air

velocities between 0-4,000 FPM. Models SD355 and SD355R* are also approved for

installations inside Fire-Lite Duct Housing D355PL (CSFM Listing No. 3242-0075:221) and

System Sensor Duct Housing DNRW (CSFM Listing No. 3242-1653:210).

NOTE: The photoelectric type detectors are generally more effective at detecting slow , smoldering

fires which smolder for hours before bursting into flame. Sources of these fires may include

cigarettes burning in couches or bedding. The ionization type detectors are generally more

effective at detecting fast, flaming fires which consume combustible materials rapidly and

spread quickly. Sources of these fires may include paper burning in a waste container or a

grease fire in the kitchen.

*Rev. 01-11-2010 fm

July 01, 2013Date Issued: Listing Expires June 30, 2014

Authorized By:

Fire Engineering Division

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed

the test results and/or other data but does not make an independent verification of any claims. This listing is not

an endorsement or recommendation of the item listed. This listing should not be used to verify correct

operational requirements or installation criteria. Refer to listee’s data sheet, installation instructions and/or other

JAMES PARSEGIAN, Program Coordinator

Page 19: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

D355PL(A)/DNRW InnovairFlexIntelligent Non-Relay PhotoelectricDuct Smoke Detector

Intelligent Addressable Devices

DF-60430:C2 • E-650

GeneralThe Fire•Lite InnovairFlex® D355PL(A) intelligent non-relay photoelectric duct smoke detector and DNRW watertight non-relay photoelectric duct smoke detector feature a pivoting housing that fits both square and rectangular footprints capa-ble of mounting to a round or rectangular duct.

DNRW duct smoke detector, with its NEMA-4 rating, is listed as a watertight, UV resistant enclosure providing protection against falling dirt, rain, and windblown dust, splashing and hose directed water, allowing operators to use the detector in the most extreme environments.

These units sense smoke in the most challenging conditions, operating in airflow speeds of 100 to 4,000 feet per minute (0.5 to 20.32 m/s), temperatures of -4°F to 158°F (-20°C to 70°C), and a humidity range of 0 to 95 percent (non-condensing.)

An improved cover design isolates the sensor head, which allows for ease of maintenance. A cover tamper feature indi-cates a trouble signal for a removed or improperly installed sensor cover. The Fire•Lite InnovairFlex housing provides a 3/4-inch conduit knockout and ample space to facilitate easy wir-ing and mounting of a relay module.

The Fire•Lite InnovairFlex duct smoke detector can be custom-ized to meet local codes and specifications without additional wiring. The new InnovairFlex product line is compatible with all previous Innovair models, including remote test accessories.

Features• Photoelectric, integrated low-flow technology.• Air velocity rating from 100 ft/min to 4,000 ft/min (0.5 m/s to

20.32 m/s).• Versatile mounting options: square or rectangular configu-

ration.• Broad ranges for operating temperature (-4°F to 158°F, -

20°C to 70°C) and humidity (0% to 95% non-condensing).• Patented sampling tube installs from front or back of the

detector with no tools required.• Cover tamper signal.

• Increased wiring space with a newly added 3/4” conduit knockout.

• Available space within housing to accommodate mounting of a relay module.

• Easily accessible code wheels on sensor head (sold sepa-rately).

• Clear cover for convenient visual inspection.• Remote testing capability.• Requires com line power only.

• Accommodates the installation of an addressable relay module, sold separately, (CRF-300) for applications requir-ing a Form-C relay.

SpecificationsSize: (Rectangle) 14.38 in (37 cm) Length; 5 in (12.7 cm) Width, 2.5 in (6.6 cm) Depth.

Size: (Square) 7.75 in (19.7 cm) Length; 9 in (22.9 cm) Width; 2.5 in (6.35 cm) Depth.

Weight: 1.6 lb (0.73 kg).

Operating Temperature Range: -4°F to 158°F (-20°C to 70°C).

Storage Temperature Range: -22°F to 158°F (-30°C to 70°C).

Operating Humidity Range: 0% to 95% relative humidity (non-condensing).

Air Duct Velocity: 100 to 4,000 ft/min (0.5 to 20.32 m/s).

AccessoriesFire•Lite provides system flexibility with a variety of accesso-ries, including two remote test stations and different means of visible and audible system annunciation. As with our duct smoke detectors, all duct smoke detectors accessories are UL listed.

D355PLs and DNRWs with a date code of 0013 or higher do not require external 24VDC for remote test applications when used with a remote-test-capable detector.

ACCESSORY CURRENT LOADS AT 24 VDC

Agency Listings and Approvals Consult product manual for lists of compatible UL-Listed devices. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Con-sult factory for latest listing status.

• UL: S1059.• ULC: S1059

Device Standby Alarm

RA100Z 0mA 12 mA Max

RTS151/RTS151KEY

0mA 12mA Max

intelligent innovair-

DF-60430:C2 • 12/18/2012 — Page 1 of 2

Page 20: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

Fire•Lite® Alarms is a registered trademark of Honeywell International Inc. ©2012 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

• CSFM: 3242-1653:0209.

• FM approved.

Product Line InformationD355PL: Intelligent non-relay photoelectric low flow smoke detector housing. Includes SD355R Detector.

DNRW: Watertight intelligent non-relay photoelectric low flow duct smoke detector housing. Does not include detector head.

SD355R(A): Remote test capable addressable low-profile photoelectric smoke detector.

SD355(A): Addressable low-profile photoelectric smoke detec-tor.

DCOIL: Remote test coil. Required for older DNR(W) duct detector housing.

DST1: Metal sampling tube duct width up to 1 ft (0.3m).

DST1.5: Metal sampling tube duct widths up to 1 ft to 2 ft (0.3 to 0.6 m).

DST3: Metal sampling tube duct widths up to 2 ft to 4 ft (0.6 to 1.2 m).

DST5: Metal sampling tube duct widths up to 4 ft to 8 ft (1.2 to 2.4 m).

DST10: Metal sampling tube duct widths up to 8 ft to 12 ft (2.4 to 3.7 m).

DH400OE-1: Weatherproof enclosure.

ETX: Metal exhaust tube duct, width 1 ft (0.3 m).

M02-04-00: Test magnet.

P48-21-00: End cap for metal sampling tubes.

RA100Z: Remote annunciator alarm LED.

RTS151: Remote test station.

RTS151KEY: Remote test station with key lock.

Important Note• DNRW duct detector housings with a date code of 0013 or

higher do not require a DCOIL or auxiliary 24 VDC for remote test applications when used with a remote test capable detector.

• DNRW duct detector housings with a date code of 0012 or earlier require a DCOIL and auxiliary 24 VDC power for remote test applications.

Page 2 of 2 — DF-60430:C2 • 12/18/2012

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.

For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105.www.firelite.com

Made in the U.S. A.

Page 21: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION

OFFICE OF THE STATE FIRE MARSHAL

FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE

LISTING No. 3240-0075:0196 Page 1 of 1

CATEGORY: 3240 -- DUCT SMOKE DETECTOR HOUSING/BASE

LISTEE: FIRE-LITE ALARMS INC.One Fire-Lite Place, Northford, CT 06410-1653

Contact: Brian Reynolds (203) 484-7161 Fax (203) 484-7309

Email: [email protected]

DESIGN: Model D350P, D350PL, D350RP, and D350RPL automatic smoke detector for duct

application. The unit consists of a plastic enclosure, relay, electrical components, listed

open area detector, and a sampling and exhausted tube. Refer to listee's data sheet for

additional detailed product description and operational considerations.

RATING:

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances

and in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model designation, electrical rating, and UL label.

APPROVAL: Listed as duct smoke detector for use with listee's separately listed compatible fire alarm

control units. Suitable for use in ducts where air velocity is between 100 and 4000 fpm.

NOTE:

*Rev. 05-06-05KK

July 01, 2013Date Issued: Listing Expires June 30, 2014

Authorized By:

Fire Engineering Division

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed

the test results and/or other data but does not make an independent verification of any claims. This listing is not

an endorsement or recommendation of the item listed. This listing should not be used to verify correct

operational requirements or installation criteria. Refer to listee’s data sheet, installation instructions and/or other

JAMES PARSEGIAN, Program Coordinator

Page 22: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

H355(A) SeriesIntelligent Addressable Thermal Detectors

Addressable Devices

DF-52385:D • E-710

GeneralThe Fire•Lite Alarms H355(A) Series thermal detectors are addressable sensors that use a state-of-the-art thermistor sensing circuit for fast response. These sensors provide open-area protection and are intended for use with Fire•Lite’saddressable Fire Alarm Control Panels (FACPs).

The H355(A) and H355R(A) sensors provide fixed tempera-ture alarm detection at 135°F (57°C). The H355R(A) sensor also responds to rate-of-rise conditions of greater than 15°F (8.3°C) per minute. The H355HT(A) is a fixed high-tempera-ture detector that activates at 190°F (88°C). These thermal detectors provide addressable property protection in a variety of applications.

Two LEDs on each sensor light to provide a local, visible sen-sor indication. Remote LED annunciator capability is available using an optional accessory, the RA100Z.

FeaturesSLC loop:

• Two-wire SLC loop connection.• Unit uses base for wiring.Addressing:

• Addressable by device.• Rotary, decimal addressing: 01 – 159 with MS-9600 series,

01 – 99 with MS-9200 series.Architecture:

• Sleek, low-profile, stylish design.

• State-of-the-art thermistor technology for fast response.• Integral communications and built-in device-type identifica-

tion.• Built-in tamper resistant feature.• Built-in functional test switch activated by external magnet.

Operation:

• Factory preset at 135°F (57°C) for the H355(A) and H355R(A); 190°F (88°C) for the H355HT(A).

• Rate-of-rise triggers at 15°F (8.3°C) per minute for the H355R(A).

• 360°-field viewing angle of the visual alarm indicators (two bicolor LEDs). LEDs blink red in Normal condition and turn on steady red in Alarm.

• Visible LEDs “blink” every time the unit is addressed.Mechanicals:

• Sealed against back pressure.• SEMS screws for wiring of the separate base.• Designed for direct-surface or electrical-box mounting.

• Plugs into separate base for ease of installation and main-tenance.

• Separate base allows interchange of photoelectric, ioniza-tion and thermal sensors.

Other system features:

• Remote test feature from the panel.• Walk test with address display.

• Low standby current.

• 94-5V plastic flammability rating.

Options:

• Remote LED output connection to optional RA100Z remote LED annunciator.

• Flanged surface mounting kit.

InstallationH355(A) Series plug-in intelligent thermal detectors use a detachable base to simplify installation, service and mainte-nance. Installation instructions are shipped with each detector.

Mount base (all base types) on an electrical backbox which is at least 1.5" (3.81 cm) deep. For a chart of compatible junction boxes, see DF-60059.

NOTE: Because of the inherent supervision provided by the SLC loop, end-of-line resistors are not required. Wiring “T-taps” or branches are permitted for Style 4 (Class “B”) wiring only.

ApplicationsUse thermal detectors for protection of property.

ConstructionThese detectors are constructed of off-white fire-resistant plastic. The H355(A) Series plug-in intelligent thermal detec-tors are designed to commercial standards and offer an attrac-tive appearance.

OperationEach H355(A) Series detector uses one of 159 (MS-9600 series) or 99 (MS-9200 series) possible addresses on a con-trol panel SLC loop. It responds to regular polls from the con-trol panel and reports its type and the status. If it receives a test command from the panel (or a local magnet test), it stimu-lates its electronics and reports an alarm. It blinks its LEDs when polled and turns the LEDs on when commanded by the panel. The H355(A) Series offers features and performance that represent the latest in thermal detector technology.

H355(A) in B210LP(A) Base B2

10-2

251

.jpg

DF-52385:D • 5/17/2013 — Page 1 of 2

Page 23: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

Fire•Lite® Alarms is a registered trademark of Honeywell International Inc. ©2013 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

SpeficationsSize: 2.1" (5.3 cm) high; base determines diameter.

– B210LP(A): 6.1" (15.5 cm) diameter.

– B501(A): 4.1" (10.4 cm) diameter.– B200SR(A): 6.875" (17.46 cm) diameter. – B224RB(A): 6.2" (15.748 cm) diameter.

Shipping weight: 4.8 oz. (137 g).

Installation temperature:

– H355(A), H355R(A): –4°F to 100°F (–20°C to 38°C).

– H355HT(A): –4°F to 150°F (–20°C to 66°C).Humidity range: 10% to 93% relative humidity (noncon-densing).

Voltage range: 15 to 32 VDC peak.

Standby current: 300 μA @ 24 VDC (one communication every five seconds with LED blink enabled).

LED current: 6.5 mA @ 24 VDC.

Mounting: B210LP(A) flanged base, included. See “Product Line Information: Intelligent Bases” if using a different base.

Fixed-temperature setpoint: 135°F (57°C) for the H355(A)and H355R(A); 190°F (88°C) for the H355HT(A).

Rate-of-rise detection: responds to greater than 15°F (8.3°C) per minute.

Listings and ApprovalsListings and approvals below apply to the H355(A) Series detectors. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.

• UL Listed: S2517.

• ULC Listed (models H355A, H355RA, H355HTA).• CSFM approved: 7270-0075:0195.• FM approved.

Product Line InformationNOTE: “A” suffix indicates ULC Listed model.

H355: Intelligent thermal sensor; 135° F (57° C); B210LP base included.

H355A: Same as H355 but with ULC Listing; B210LPA base included.

H355R: Same as H355 with rate-of-rise feature; B210LP base included.

H355RA: Same as H355R but with ULC Listing; B210LPA base included.

H355HT: Intelligent fixed high-temperature thermal detector; 190° F (88° C); B210LP base included.

H355HTA: Same as H355HT but with ULC Listing; B210LPA base included.

INTELLIGENT BASESNOTE: “A” suffix indicates ULC Listed model.

NOTE: The detector’s plug-in base can be changed off for special applications. For details about intelligent bases and their mount-ing, see DF-60059.

B210LP(A): Plug-in detector base (included); standard U.S. flanged low-profile mounting base.

B210LPBP: Bulk pack of B210LP; package contains 10.

B501(A): Standard European flangeless mounting base.

B501BP: Bulk pack of B501; package contains 10.

B200SR(A): Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone. Replaces B501BH series bases in retrofit applications.

B224RB(A): Plug-in System Sensor relay base. Screw termi-nals: up to 14 AWG (2.0 mm²). Relay type: Form-C. Rating: 2.0 A @ 30 VDC resistive; 0.3 A @ 110 VDC inductive; 1.0 A @ 30 VDC inductive.

B224BI(A): Plug-in System Sensor isolator detector base. Maximum 25 devices between isolator bases (see DF-52389).

ACCESSORIESF110: Retrofit flange to convert B210LP(A) to match the B350LP(A) profile, or to convert older high-profile bases to low-profile.

F110BP: Bulk pack of F110; package contains 15.

F210: Replacement flange for B210LP(A) base.

RA100Z(A): Remote LED annunciator. 3 – 32 VDC. Mounts to a U.S. single-gang electrical box. For use with B501(A) and B210LP(A) bases only.

SMB600: Surface mounting kit

M02-04-00:Test magnet.

M02-09-00: Test magnet with telescoping handle.

XR2B: Detector removal tool. Allows installation and/or removal of detector heads from bases in high ceiling applica-tions.

XP-4: Extension pole for XR2B. Comes in three 5-foot (1.524 m) sections.

T55-127-010: Detector removal tool without pole.

Page 2 of 2 — DF-52385:D • 5/17/2013

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.

For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105.www.firelite.com

Made in the U.S. A.

Page 24: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION

OFFICE OF THE STATE FIRE MARSHAL

FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE

LISTING No. 7270-0075:0195 Page 1 of 1

CATEGORY: 7270 -- HEAT DETECTOR

LISTEE: FIRE-LITE ALARMS INC.One Fire-Lite Place, Northford, CT 06410-1653

Contact: Brian Reynolds (203) 484-7161 Fax (203) 484-7309

Email: [email protected]

DESIGN: Models H350, H355, and H355HT fixed temperature heat detectors. Models H350R and

H355R rate-of-rise with fixed temperature heat detectors. Refer to listee's data sheet for

detailed product description and operational considerations.

RATING: H350, H355, and H355HT 135° F fixed temperature

H350R and H355R 15° F rate-of-rise

H355HT 190° F fixed temperature

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances

and in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model number, electrical rating and UL label.

APPROVAL: Listed as heat detectors for use with separately listed compatible fire alarm control units.

NOTE:

Rev. 05-06-05JEW

July 01, 2013Date Issued: Listing Expires June 30, 2014

Authorized By:

Fire Engineering Division

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed

the test results and/or other data but does not make an independent verification of any claims. This listing is not

an endorsement or recommendation of the item listed. This listing should not be used to verify correct

operational requirements or installation criteria. Refer to listee’s data sheet, installation instructions and/or other

JAMES PARSEGIAN, Program Coordinator

Page 25: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

df-60379:A1 • 08/04/09 — Page 1 of 2

CRF-300(A)Relay Module

Addressable Devices

df-60379:A1 • E-400

GeneralThe CRF-300(A) Addressable Relay Module provides the sys-tem with a dry-contact output for activating a variety of auxil-iary devices, such as fans, door holders, dampers, controlequipment, etc. Addressability allows the dry contact to beactivated through panel programming, on a select basis.

LiteSpeed™ is a communication protocol developed byFire•Lite Engineering that greatly enhances the speed of com-munication between analog intelligent devices. Intelligentdevices communicate in a grouped fashion. If one of thedevices within the group has new information, the panel CPUstops the group poll and concentrates on single points. Thenet effect is response speed greater than five times that ofother designs.

Features• Built-in type identification automatically identifies these

devices to the control panel.• Internal circuitry and relay powered directly by two-wire

SLC loop.• Integral LED “blinks” green each time a communication is

received from the control panel and turns on in steady redwhen activated.

• High noise immunity (EMF/RFI).• Wide viewing angle of LED.

• SEMS screws with clamping plates for wiring ease.• Direct-dial entry of address: 01– 159 for MS-9600(A) series

panels, 01 – 99 on MS-9200UDLS(A) and MS-9050UD(A).

ApplicationsThe CRF-300(A) may be programmed to operate dry contactsfor door holders, Air Handling Unit shutdown, etc., and to resetfour-wire smoke detector power.

Construction• The face plate is made of off-white heat-resistant plastic.• Controls include two rotary switches for direct-dial entry of

address setting. • The CRF-300(A) is configured for a single Class B (Style Y)

or Class A (Style Z) Notification Appliance Circuit.• The CRF-300(A) provides two Form-C dry contacts that

switch together.

OperationEach CRF-300(A) uses one of the addresses on a SLC loop. Itresponds to regular polls from the control panel and reports itstype and status, including the open/normal/short status of itsNotification Appliance Circuit (NAC). The LED blinks with eachpoll received. On command, it activates its internal relay.

NOTE: Open/short supervision is suspended with the CRF-300.

Rotary switches set a unique address for each module. Theaddress may be set before or after mounting. The built-inTYPE CODE (not settable) will identify the module to the con-trol panel, so as to differentiate between a control module anda relay module.

SpecificationsNormal operating voltage: 15 to 32 VDC.

Maximum SLC current draw: 6.5 mA (LED on).

Average operating current: 230 μA direct poll (CLIP mode),255 μA group poll (LiteSpeed mode) with LED flashing.

EOL resistance: not used.

Temperature range: 32°F to 120°F (0°C to 49°C).

Humidity range: 10% to 93% non-condensing.

Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x2.125" (5.398 mm) deep box.

Relay Contact Ratings

Load Description Application Maximum Voltage

Current Rating

Resistive Non-Coded 30 VDC 3.0 A

Resistive Coded 30 VDC 2.0 A

Resistive Non-Coded 110 VDC 0.9 A

Resistive Non-Coded 125 VAC 0.9 A

Inductive (L/R=5ms) Coded 30 VDC 0.5 A

Inductive (L/R=2ms) Coded 30 VDC 1.0 A

Inductive (PF=0.35) Non-Coded 125 VAC 0.5 A

CRF-300(A)

6037

9cov

.jpg

Page 26: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

Page 2 of 2 — df-60379:A1 • 08/04/09

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.

For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105.www.firelite.com

LiteSpeed™ is a trademark and Fire•Lite® Alarms is a registered trademarkof Honeywell International Inc. ©2009 by Honeywell International Inc. All rights reserved. Unauthorized useof this document is strictly prohibited.

Made in the U.S. A.

Agency Listings and ApprovalsIn some cases, certain modules may not be listed by certainapproval agencies, or listing may be in process. Consult fac-tory for latest listing status.

• UL: S2424• ULC: S2424• FM approved• CSFM: 7300-0075:185• MEA: 72-01-E

Product Line InformationCRF-300(A): Intelligent addressable relay module.

: Intelligent addressable relay module, ULC listed model.

SMB500: Optional surface-mount backbox.

NOTE: For installation instructions, see document I56-1190-005and refer to the SLC Wiring Manual, document 51309.

Page 27: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION

OFFICE OF THE STATE FIRE MARSHAL

FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE

LISTING No. 7300-0075:0185 Page 1 of 1

CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES

LISTEE: FIRE-LITE ALARMS INC.One Fire-Lite Place, Northford, CT 06410-1653

Contact: Brian Reynolds (203) 484-7161 Fax (203) 484-7309

Email: [email protected]

DESIGN: Models MDF-300, MMF-301, MMF-300, MMF-302, MCF-300 monitor modules; Models

CRF-300 and CMF-300 control modules; and MMF-302-6 six zone interface signaling device

module. Refer to listee's data sheet for additional detailed product description and operational

considerations.

RATING: 15-32 VDC

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances

and in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model designation, electrical rating, and UL label.

APPROVAL: Listed as control unit accessories for use with listee's separately listed electrically

compatible fire alarm control units.

NOTE:

*Rev. 05-06-05 JW

July 01, 2013Date Issued: Listing Expires June 30, 2014

Authorized By:

Fire Engineering Division

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed

the test results and/or other data but does not make an independent verification of any claims. This listing is not

an endorsement or recommendation of the item listed. This listing should not be used to verify correct

operational requirements or installation criteria. Refer to listee’s data sheet, installation instructions and/or other

JAMES PARSEGIAN, Program Coordinator

Page 28: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

DF-52121:C • 10/06/2010 — Page 1 of 4

MMF-300(A) Series, MDF-300(A)Addressable Monitor Modules

Addressable Devices

DF-52121:C • E-325

GeneralFour different monitor modules are available for Fire•Lite’sintelligent control panels to suit a variety of applications. Moni-tor modules are used to supervise a circuit of dry-contact inputdevices, such as conventional heat detectors and pull stations,or monitor and power a circuit of two-wire smoke detectors(MMF-302(A)).

MMF-300(A) is a standard-sized module (typically mounts to a4" [10.16 cm] square box) that supervises either a Style D(Class A) or Style B (Class B) circuit of dry-contact inputdevices.

MMF-301(A) is a miniature monitor module a mere 1.3" (3.302cm) H x 2.75" (6.985 cm) W x 0.5" (1.270 cm) D used to super-vise a Style B (Class B) circuit of dry-contact input devices. Itscompact design allows the MMF-301(A) to be mounted in asingle-gang box behind the device it monitors.

MMF-302(A) is a standard-sized module used to monitor andsupervise compatible two-wire, 24 volt, smoke detectors on aStyle D (Class A) or Style B (Class B) circuit.

MDF-300(A) is a standard-sized dual monitor module used tomonitor and supervise two independent two-wire Style B(Class B) dry-contact initiating device circuits (IDCs) at twoseparate, consecutive addresses in intelligent, two-wire systems.

LiteSpeed™ is a communication protocol developed byFire•Lite Engineering that greatly enhances the speed of com-munication between analog intelligent devices. Intelligentdevices communicate in a grouped fashion. If one of thedevices within the group has new information, the panel CPUstops the group poll and concentrates on single points. Thenet effect is response speed greater than five times that ofother designs. designs.

MMF-300(A) Monitor Module• Built-in type identification automatically identifies this device

as a monitor module to the control panel.

• Powered directly by two-wire SLC loop. No additional powerrequired.

• High noise (EMF/RFI) immunity.• SEMS screws with clamping plates for ease of wiring.• Direct-dial entry of address: 01 – 159 on MS-9600 series

panels, 01 – 99 on other compatible systems. • LED flashes during normal operation and latches on steady

to indicate alarm.The MMF-300(A) Monitor Module is intended for use in intelli-gent, two-wire systems, where the individual address of eachmodule is selected using the built-in rotary switches. It pro-vides either a two-wire or four-wire fault-tolerant InitiatingDevice Circuit (IDC) for normally-open-contact fire alarm andsupervisory devices. The module has a panel-controlled LEDindicator. The MMF-300(A) can be used to replace M300(A)modules in existing systems.

MMF-300(A) APPLICATIONSUse to monitor a zone of four-wire smoke detectors, manualfire alarm pull stations, waterflow devices, or other normally-open dry-contact alarm activation devices. May also be usedto monitor normally-open supervisory devices with specialsupervisory indication at the control panel. Monitored circuit

may be wired as an NFPA Style B (Class B) or Style D (ClassA) Initiating Device Circuit. A 47K ohm End-of-Line Resistor(provided) terminates the Style B circuit. No resistor isrequired for supervision of the Style D circuit.

MMF-300(A) OPERATIONEach MMF-300(A) uses one of the available moduleaddresses on an SLC loop. It responds to regular polls fromthe control panel and reports its type and the status (open/nor-mal/short) of its Initiating Device Circuit (IDC). A flashing LEDindicates that the module is in communication with the controlpanel. The LED latches steady on alarm (subject to currentlimitations on the loop).

MMF-300(A) SPECIFICATIONSNominal operating voltage: 15 to 32 VDC.

Maximum current draw: 5.0 mA (LED on).

Average operating current: 350 μA (LED flashing), 1 com-munication every 5 seconds, 47k EOL.

Maximum IDC wiring resistance: 40 ohms.

EOL resistance: 47K ohms.

Temperature range: 32°F to 120°F (0°C to 49°C).

Humidity range: 10% to 93% noncondensing.

Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x2.125" (5.398 cm) deep box.

MMF-300(A) (Type H)

6999

cov.

jpg

Page 29: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

Page 2 of 4 — DF-52121:C • 10/06/2010

MMF-301(A) Mini Monitor Module• Built-in type identification automatically identifies this device

as a monitor module to the panel.• Powered directly by two-wire SLC loop. No additional power

required.• High noise (EMF/RFI) immunity.• Tinned, stripped leads for ease of wiring.

• Direct-dial entry of address: 01 – 159 on MS-9600 seriespanels, 01 – 99 on other compatible systems

The MMF-301(A) Mini Monitor Module can be installed in asingle-gang junction directly behind the monitored unit. Itssmall size and light weight allow it to be installed without rigidmounting. The MMF-301(A) is intended for use in intelligent,two-wire systems where the individual address of each moduleis selected using rotary switches. It provides a two-wire initiat-ing device circuit for normally-open-contact fire alarm devices.The MMF-301(A) can be used to replace M301(A) modules inexisting systems.

MMF-301(A) APPLICATIONSUse to monitor a single device or a zone of four-wire smokedetectors, manual fire alarm pull stations, waterflow devices, orother normally-open dry-contact devices. May also be used tomonitor normally-open supervisory devices with special super-visory indication at the control panel. Monitored circuit/deviceis wired as an NFPA Style B (Class B) Initiating Device Circuit.A 47K ohm End-of-Line Resistor (provided) terminates the cir-cuit.

MMF-301(A) OPERATIONEach MMF-301(A) uses one of the available moduleaddresses on an SLC loop. It responds to regular polls fromthe control panel and reports its type and the status (open/nor-mal/short) of its Initiating Device Circuit (IDC).

MMF-301(A) SPECIFICATIONSNominal operating voltage: 15 to 32 VDC.

Average operating current: 350 μA, 1 communication every5 seconds, 47k EOL; 600 μA Max. (Communicating, IDCShorted).

Maximum IDC wiring resistance: 40 ohms.

Maximum IDC Voltage: 11 Volts.

Maximum IDC Current: 400 μA.

EOL resistance: 47K ohms.

Temperature range: 32°F to 120°F (0°C to 49°C).

Humidity range: 10% to 93% noncondensing.

Dimensions: 1.3" (3.302 cm) high x 2.75" (6.985 cm) wide x0.65" (1.651 cm) deep.

Wire length: 6" (15.24 cm) minimum.

MMF-302(A) Interface Module• Supports compatible two-wire smoke detectors.• Supervises IDC wiring and connection of external power

source.• High noise (EMF/RFI) immunity.

• SEMS screws with clamping plates for ease of wiring.• Direct-dial entry of address: 01 – 159 on MS-9600 series

panels, 01 – 99 on other compatible systems.• LED flashes during normal operation.• LED latches steady to indicate alarm on command from

control panel.The MMF-302(A) Interface Module is intended for use in intelli-gent, addressable systems, where the individual address ofeach module is selected using built-in rotary switches. Thismodule allows intelligent panels to interface and monitor two-wire conventional smoke detectors. It transmits the status (nor-mal, open, or alarm) of one full zone of conventional detectorsback to the control panel. All two-wire detectors being moni-tored must be UL compatible with the module. The MMF-302(A) can be used to replace M302(A) modules in existingsystems.

MMF-302 (A) APPLICATIONSUse the MMF-302(A) to monitor a zone of two-wire smokedetectors. The monitored circuit may be wired as an NFPAStyle B (Class B) or Style D (Class A) Initiating Device Circuit.A 3.9 K ohm End-of-Line Resistor (provided) terminates theend of the Style B or D (class B or A) circuit (maximum IDCloop resistance is 25 ohms). Install ELR across terminals 8and 9 for Style D application.

MMF-302(A) OPERATIONEach MMF-302(A) uses one of the available moduleaddresses on an SLC loop. It responds to regular polls fromthe control panel and reports its type and the status (open/nor-mal/short) of its Initiating Device Circuit (IDC). A flashing LEDindicates that the module is in communication with the controlpanel. The LED latches steady on alarm (subject to currentlimitations on the loop).

MMF-302(A) SPECIFICATIONSNominal operating voltage: 15 to 32 VDC.

Maximum current draw: 5.1 mA (LED on).

Maximum IDC wiring resistance: 25 ohms.

Average operating current: 300 μA, 1 communication and 1LED flash every 5 seconds, 3.9k eol.

EOL resistance: 3.9K ohms.

External supply voltage (between Terminals T3 and T4):DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrmsmaximum. Current: 90 mA per module maximum.

Temperature range: 32°F to 120°F (0°C to 49°C).

Humidity range: 10% to 93% noncondensing.

Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x2.125" (5.398 cm) deep box.

6720m101.w

mf

Page 30: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

DF-52121:C • 10/06/2010 — Page 3 of 4

MDF-300(A) Dual Monitor ModuleThe MDF-300(A) Dual Monitor Module is intended for use inintelligent, two-wire systems. It provides two independent two-wire initiating device circuits (IDCs) at two separate, consecutiveaddresses. It is capable of monitoring normally open contact firealarm and supervisory devices. The module has a single panel-controlled LED.

NOTE: The MDF-300(A) provides two Style B (Class B) IDC cir-cuits ONLY. Style D (Class A) IDC circuits are NOT supported inany application.

MDF-300(A) SPECIFICATIONSNormal operating voltage range: 15 to 32 VDC.

Maximum current draw: 6.4 mA (LED on).

Average operating current: 750 μA (LED flashing).

Maximum IDC wiring resistance: 1,500 ohms.

Maximum IDC Voltage: 11 Volts.

Maximum IDC Current: 240 μA

EOL resistance: 47K ohms.

Maximum SLC Wiring resistance: 40 Ohms.

Temperature range: 32° to 120°F (0° to 49°C).

Humidity range: 10% to 93% (non-condensing).

Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x2.125" (5.398 cm) deep.

MDF-300(A) AUTOMATIC ADDRESSINGThe MDF-300(A) automatically assigns itself to two address-able points, starting with the original address. For example, ifthe MDF-300(A) is set to address “26”, then it will automati-cally assign itself to addresses “26” and “27”.

NOTE: “Ones” addresses on the MDF-300(A) are 0, 2, 4, 6, or 8only. Terminals 6 and 7 use the first address, and terminals 8 and9 use the second address.

InstallationMMF-300(A), MMF-302(A), and MDF-300(A) modules mountdirectly to a standard 4" (10.16 cm) square, 2.125" (5.398 cm)deep, electrical box. They may also be mounted to theSMB500 surface-mount box. Mounting hardware and installa-tion instructions are provided with each module. All wiringmust conform to applicable local codes, ordinances, and regu-lations. These modules are intended for power-limited wiringonly.

The MMF-301(A) module is intended to be wired and mountedwithout rigid connections inside a standard electrical box. Allwiring must conform to applicable local codes, ordinances, andregulations.

Agency Listings and ApprovalsIn some cases, certain modules may not be listed by certainapproval agencies, or listing may be in process. Consult fac-tory for latest listing status.

• UL: S2424• ULC: S2424

• FM Approved • CSFM: 7300-0075:0185• MEA: 72-01-E

Product Line InformationNOTE: “A” suffix indicates ULC-listed model.

MMF-300(A): Monitor module.

MMF-301(A): Monitor module, miniature.

MMF-302(A): Monitor module, two-wire detectors.

MDF-300(A): Monitor module, dual, two independent Class Bcircuits.

SMB500: Optional surface-mount backbox.

NOTE: See installation instructions and refer to the SLC WiringManual, PN 51309.

Architects’/Engineers’ SpecificationsSpecifications of these devices and all FireLite products areavailable from FireLite.

! CAUTION: Avoid duplicating addresses on the system.

Page 31: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

Page 4 of 4 — DF-52121:C • 10/06/2010

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.

For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105.www.firelite.com

Fire·Lite® and LiteSpeed® are registered trademarks and FireWatch™ is atrademark of Honeywell International Inc.©2010 by Honeywell International Inc. All rights reserved. Unauthorized useof this document is strictly prohibited.

Made in the U.S. A.

Page 32: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION

OFFICE OF THE STATE FIRE MARSHAL

FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE

LISTING No. 7300-0075:0185 Page 1 of 1

CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES

LISTEE: FIRE-LITE ALARMS INC.One Fire-Lite Place, Northford, CT 06410-1653

Contact: Brian Reynolds (203) 484-7161 Fax (203) 484-7309

Email: [email protected]

DESIGN: Models MDF-300, MMF-301, MMF-300, MMF-302, MCF-300 monitor modules; Models

CRF-300 and CMF-300 control modules; and MMF-302-6 six zone interface signaling device

module. Refer to listee's data sheet for additional detailed product description and operational

considerations.

RATING: 15-32 VDC

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances

and in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model designation, electrical rating, and UL label.

APPROVAL: Listed as control unit accessories for use with listee's separately listed electrically

compatible fire alarm control units.

NOTE:

*Rev. 05-06-05 JW

July 01, 2013Date Issued: Listing Expires June 30, 2014

Authorized By:

Fire Engineering Division

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed

the test results and/or other data but does not make an independent verification of any claims. This listing is not

an endorsement or recommendation of the item listed. This listing should not be used to verify correct

operational requirements or installation criteria. Refer to listee’s data sheet, installation instructions and/or other

JAMES PARSEGIAN, Program Coordinator

Page 33: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

Description:

Strobe, Horn Strobe, and Horn Notification Appliances

Ceiling Wall

TM

***

***

Wheelock® ExcederTM Series LED Notification AppliancesNotification

5

The Wheelock® ExcederTM Series of notification appliances feature a sleek modern design that will please building owners with reduced total cost of ownership. Installers will benefit from its comprehensive feature list, including the most candela options in one appliance, low current draw, no tools needed for setting changes, voltage test points, 12/24 VDC operation, universal mounting base and multiple mounting options for both new and retrofit construction.

The Wheelock® ExcederTM Series incorporates high reliability and high efficiency optics to minimize current draw allowing for a greater number of appliances on the notification appliance circuit. All strobe models feature an industry first of 8 candela settings on a single appliance. Models with an audible feature 3 sound settings (90, 95, 99 dB). All switches to change settings, can be set without the use of a tool and are located behind the appliance to prevent tampering. Wall models feature voltage test points to take readings with a voltage meter for troubleshooting and AHJ inspection.

The Wheelock® ExcederTM Series of wall and ceiling notification appliances feature a Universal Mounting Base (UMB) designed to simplify the installation and testing of horns, strobes, and combination horn strobes. The separate universal mounting base can be pre-wired to allow full testing of circuit wiring before the appliance is installed and the surface is finished. It comes complete with a Contact Cover for protection against dirt, dust, paint and damage to the contacts. The Contact Cover also acts as a shunting device to allow pre-wire testing for common wiring issues. The Contact Cover is polarized to prevent it from being installed incorrectly and prevents the appliance from being installed while it is on the UMB. When the Contact Cover is removed the circuit will show an open until the appliance is installed. The UMB allows for consistent installation and easy replacement of appliances if required. Wall models provide an optional locking screw for extra secure installation, while the ceiling models provide a captivated screw to prevent the screw from falling during installation.

Compliance- UL 1971, UL 464, ULC, CSFM, FM- ADA/NFPA/ANSI/OSHA- RoHS

- Save up to 48% in current draw*

- Up to 9 models now in 1 appliance

- Save up to 14% cost of installation**

Compatibility and Requirements- Synchronize using the Wheelock® Sync Modules or panels with built-in Wheelock® Patented Sync Protocol- Compatible with UL “Regulated Voltage” using filtered VDC or unfiltered VRMS input voltage- Strobes produce 1 flash per second over the “Regulated Voltage” range

* Compared to competitive models** Compared to previous models

*** Patented

Page 34: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

* UL max current rating is the maximum RMS current within the listed voltage range (16-33 VDC for 24 VDC units). For strobes the UL max current is usually at the minimum listed voltage (16 VDC for 24 VDC units). For audibles the max current is usually at the maximum listed voltage (33 VDC for 24 VDC units). For unfiltered ratings, see installation instructions.

Specification & Ordering Information

Model Strobe Candela

Sync w/ DSM or

Wheelock Power Supplies

12/24 VDC* Mounting Options

Horn Strobes

HSR 15/1575/30/75/95/110/135/185 X X UMB**

HSW 15/1575/30/75/95/110/135/185 X X UMB**

HSRC 15/30/60/75/95/115/150/177 X X UMB**

HSWC 15/30/60/75/95/115/150/177 X X UMB**

Strobes

STR 15/1575/30/75/95/110/135/185 X X UMB**

STW 15/1575/30/75/95/110/135/185 X X UMB**

STRC 15/30/60/75/95/115/150/177 X X UMB**

STWC 15/30/60/75/95/115/150/177 X X UMB**

Horn

HNR X X UMB**

HNW X X UMB**

HNRC X X UMB**

HNWC X X UMB**

Strobe Ratings per UL Standard 1971

UL Max Current*

24 VDC / 24 FWR 12 VDC

Model Regulated Voltage Range VDC 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75

ST 8.0-33.0 0.057 0.070 0.085 0.135 0.163 0.182 0.205 0.253 0.110 0.140

STC 8.0-33.0 0.061 0.085 0.103 0.135 0.163 0.182 0.205 0.253 0.110

Horn Strobe Ratings per UL 1971 & Anechoic at 24 VDC

UL Max Current* at Anechoic 99 dBA

24 VDC 12 VDC

Model Regulated Voltage Range VDC 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75

HS 8.0-33.0 0.082 0.095 0.102 0.148 0.176 0.197 0.242 0.282 0.125 0.159

HSC 8.0-33.0 0.082 0.102 0.141 0.148 0.176 0.197 0.242 0.282 0.125

UL Max Current* at Anechoic 95 dBA

24 VDC 12 VDC

Model Regulated Voltage Range VDC 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75

HS 8.0-33.0 0.073 0.083 0.087 0.139 0.163 0.186 0.230 0.272 0.122 0.153

HSC 8.0-33.0 0.073 0.087 0.128 0.139 0.163 0.186 0.230 0.272 0.122

UL Max Current* at Anechoic 90 dBA

24 VDC 12 VDC

Model Regulated Voltage Range VDC 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75

HS 8.0-33.0 0.065 0.075 0.084 0.136 0.157 0.184 0.226 0.267 0.120 0.148

HSC 8.0-33.0 0.065 0.084 0.120 0.136 0.157 0.184 0.226 0.267 0.120

Horn Ratings per UL Anechoic

Model Regulated Voltage Range VDC 99 dB 95 dB 90 dB

HN 16-33.0 0.064 0.044 0.022

HNC 16-33.0 0.084 0.044 0.022

HN 8.0-17.5 0.047 0.026 0.017

HNC 8.0-17.5 0.047 0.026 0.017

Model Legend

HN = HornST = StrobeHS = Horn StrobeC = Ceiling MountW = WhiteR = Red

Example 1: STRC = Strobe, Red, Ceiling MountExample 2: HSR = Horn Strobe, Red, Wall MountExample 3: HSW = Horn Strobe, White, Wall MountExample 4: STW-AL = Strobe, White, Wall Mount, Alert Lettering

Common base for wall and ceiling with 5 mounting options

Voltage test points for quick troubleshooting and easy spot checking (wall models only)

Low Current Draw = Fewer Power Supplies

Example: HSR

8 ca

ndel

as o

n 1

dev

ice

1 g

ang

, 2 g

ang

, 4”

sq, 3

.5”

oct

al &

4”

oct

al b

oxe

s

8 candela settings

NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Cooper Wheelock Inc., dba Cooper Notification standard terms and conditions.

**UMB = Universal Mounting Base

*UMB

Eas

y to

rem

emb

er m

od

el c

od

es

NOTE: All CAUTIONS and WARNINGS are identified by the symbol . All warnings are printed in bold capital letters. WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING

OR APPLYING THIS PRODUCT. VISIT WWW.COOPERNOTIFICATION.COM OR CONTACT COOPER NOTIFICATION FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.

General Notes:General Notes:• Strobes are designed to flash at 1 flash per second minimum over their “Regulated Voltage Range”.• All candela ratings represent minimum effective strobe intensity based on UL Standard 1971.• Series Exceder Strobe products are Listed under UL Standards 1971 and 464 for indoor use with a temperature range of 32°F to 120°F (0°C to 49°C) and maximum humidity of 93% (± 2%) UL 464 (85% UL 1971).• Series Exceder horns are under UL Standard 464 for audible signal appliances (Indoor use only).

Example: HSWC

Contact Cover

*12 VDC models feature 15 & 15/75 settings

A = Agent Lettering (Strobes only) AL = Alert Lettering (Strobes only)N = No Lettering (Strobes only)

Page 35: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

The notification appliances shall be Wheelock® Exceder™ Series HS Audible Strobe appliances, Series ST Visual Strobe appliances and Series HN Audible appliances or approved equals. The Series HS and ST Strobes shall be listed for UL Standard 1971 (Emergency Devices for the Hearing-Impaired) for Indoor Fire Protection Service. The Series HS and HN Audibles shall be UL Listed under Standard 464 (Fire Protective Signaling). All Series shall meet the requirements of FCC Part 15 Class B. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP) with the ability to operate from 8 to 33 VDC. Indoor wall models shall incorporate voltage test points for easy voltage inspection.The Series HS Audible Strobe and ST Strobe appliances shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens. The Series shall be of low current design. Where Multi-Candela appliances are specified, the strobe intensity shall have 8 field selectable settings at 15, 15/75, 30, 75, 95, 110, 135, 185 candela for wall mount and 15, 30, 60, 75, 95, 115, 150, 177 candela for ceiling mount. The selector switch for selecting the candela shall be tamper resistant. The 15/75 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on-axis is required (e.g. ADA compliance). Appliances with candela settings shall show the candela selection in a visible location at all times when installed.The audible shall have a minimum of three (3) field selectable settings for dBA levels and shall have a choice of continuous or temporal (Code 3) audible outputs. The Series HS Audible Strobe, ST Strobe and Series HN Audible shall incorporate a patented Universal Mounting Base that shall allow mounting to a single-gang, double-gang, 4-inch square, 3.5-inch octal, 4-inch octal or 100mm European type back boxes. Two wire appliance wiring shall be capable of directly connecting to the mounting base. Continuity checking of the entire NAC circuit prior to attaching any notification appliances shall be allowed. Product shall come with Contact Cover to protect contact springs. Removal of an appliance shall result in a supervision fault condition by the Fire Alarm Control Panel (FACP). The mounting base shall be the same base among all horn, strobe, horn strobe, wall and ceiling models. All notification appliances shall be backwards compatible.The Series HS and ST wall models shall have a low profile measuring 5.24” H x 4.58” W x 2.19” D. Series HN wall shall measure 5.24” H x 4.58” W x 1.6” D. The Series HSC and STC shall been round and have a low profile with a diameter of 6.68” x 2.63” D. Series HNC ceiling shall have a diameter of 6.68” x 1.50” D.When synchronization is required, the appliance shall be compatible with Wheelock®’s DSM Sync Modules, Wheelock® Power Supplies or other manufacturer’s panels with built-in Wheelock® Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync protocol fails to operate, the strobe shall revert to a non-synchronized flash-rate and still maintain (1) flash per second over its Regulated Voltage Range. The appliance shall also be designed so that the audible signal may be silenced while maintaining strobe activation when used with Wheelock® synchronization protocol.

Wall Appliances – UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM, RoHSCeiling Appliances – UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM, RoHS

Exceder - Spec Sheet 5/13

WE ENCOURAGE AND SUPPORT NICET CERTIFICATION3 YEAR WARRANTY

NotificationCooper Notification is

NJ Location273 Branchport Ave.Long Branch, NJ 07740P: 800-631-2148F: 732-222-8707www.coopernotification.com

Architects and Engineers Specifications

Page 36: MS-9200UDLS(E) Rev 3 - PROtech Security & Electronicsprotechsecurity.us/wp-content/uploads/2013/12/Honeywell-Fire-Lite...MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In

CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION

OFFICE OF THE STATE FIRE MARSHAL

FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE

LISTING No. 7125-0785:0168 Page 1 of 1

CATEGORY: 7125 -- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED

LISTEE: Cooper Wheelock Inc.7246 16th St. E., Ste. 105, Sarasota, FL 34243

Contact: Tom Conover (941) 487-2336

Email: [email protected]

DESIGN: Exceder Series: Models ST strobe, HS horn strobe and HN horn. Model ST is a synchronous

and non-synchronous strobe light. Model HS a visual/audible appliance and Model HN is an

audible signal appliance. All units followed by R (red) or W (white). Additionally, a ‘C’ may be

added for ceiling models and/or a ‘-NR’ may be added for non-resettable models. For non

-NR models and optional ‘S’ for silver fascia may be added*. Refer to listee's data sheet for

additional detailed product description and operational considerations.

RATING: Electrical: 12 VDC/24VDC/FWR

Candela (wall)*: 15, 15/75, 30, 75, 95, 110, 135 & 185

Candela (ceiling)*: 15, 30, 60, 75, 95, 115, 150, & 177

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances

and in a manner acceptable to the authority having jurisdiction. All models are for indoor use

and for wall mount only or ceiling mount only*

MARKING: Listee's name, model number, electrical/candela rating, and UL label.

APPROVAL: Listed as horn for fire alarm signaling and strobe, horn/strobe for the hearing impaired when

used with separately listed electrically compatible fire alarm control units. Refer to listee’s

Installation Instructions Manual for details.

*Rev. 9-24-09 fm

July 01, 2013Date Issued: Listing Expires June 30, 2014

Authorized By:

Fire Engineering Division

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed

the test results and/or other data but does not make an independent verification of any claims. This listing is not

an endorsement or recommendation of the item listed. This listing should not be used to verify correct

operational requirements or installation criteria. Refer to listee’s data sheet, installation instructions and/or other

JAMES PARSEGIAN, Program Coordinator