MSC OF IGs

Embed Size (px)

Citation preview

  • 7/27/2019 MSC OF IGs

    1/133

    Grid-connected Induction Generators with Reference to Potential Small

    Power Plant Developments in Sudan

    By:

    SALIH AHMED OBEID SALIH

    B. Sc. (Honors) in Electrical Engineering, University of Khartoum, 1981

    A Thesis Submitted to the Graduate College, University of Khartoum in

    Partial Fulfillment for the Award of the Degree of M. Sc. in

    Electrical Power Engineering

    Supervisor: Dr. Fayez Mohammed El-sadik

    Co-supervisor: Dr. Kamal Ramadan Doud

    DEPARTMENT OF ELECTRICAL & ELECTRONIC ENGINEERING

    FACULTY OF ENGINEERING

    UNIVERSITY OF KHARTOUM

    February 2013

  • 7/27/2019 MSC OF IGs

    2/133

    I

    DEDICATION

    I would l ike to dedicate this work to my famil y starting with the loving

    Memories of my father , and to my mother Aeisha Salim I dri s who

    Helped and supported me very much and to my wife Sauad Hamid

    Mahadi who stood beside me all the time of thi s project and my love.

    To my chi ldren, Ahmed, Elhar ith , Leena, Hammam, Alaa, and Mohammed.

    Salih

  • 7/27/2019 MSC OF IGs

    3/133

    II

    Acknowledgement

    I am very grateful to my supervisor Dr. Fayez Mohammed EL-Sadik

    for his patience and guidance throughout the development stages of this

    project. His valuable suggestions, ideas, concepts and advices are greatly

    appreciated.

    My thanks are also extended to the former National Electricity Corporation

    (NEC) administration for their financial support during the initial stages of

    the M. Sc. project.

    Special thanks are due to the former gas turbine department manager,

    Roseires hydro power station manager, Jebel Aulia hydro matrix power

    station manager and his staff and to the technicians of Dr. Sherif thermal

    power station who have greatly assisted with the experimental test bed.

    Last but not least, my deepest thanks are extended to the faculty of

    engineering electrical machines laboratory staff.

  • 7/27/2019 MSC OF IGs

    4/133

    III

    Abstract

    The study aimed to investigate the possibility of generating small isolated

    (stand- alone) or connected power to the national grid.

    The studytook Jebel Aulia hydro matrix turbines as a study. The detail of the

    induction generators-based project which is supplying the national grid with

    30 MW of power with the minimum of running cost was described.

    A hard procured testbed was installed at the electrical laboratory at the

    faculty of Engineering to mimic steady state performance characteristic of the

    induction generators.

    The induction generator was operated above its rated synchronous speed

    then the national grid was fed with 1.8 kW at three phase supply voltage of

    220 V, 50 Hz and power factor of 0.82 which was further improved to be 0.98

    by means of capacitor banks. The results showed that these kinds of induction

    generators need neither DC excitation nor speed governing system as that

    used for conventional AC synchronous generators and hence considerable

    reduction of cost and size was achieved.

    The survey proposed the potential sites to install small hydro power

    generators to increase electric production in Sudan

  • 7/27/2019 MSC OF IGs

    5/133

    IV

    30

    .

    /. 1.8

    0 220 0.2 0.8

    . .

  • 7/27/2019 MSC OF IGs

    6/133

    V

    LIST OF CONTENTS

    DEDICATION........................................................................................................ I

    Acknowledgement.................................................................................................. II

    Abstract ................................................................................................................ III

    .................................................................................................................. IVChapter One........................................................................................................... 1

    I.1 General: ......................................................................................................... 2

    I.2 Sudan Installed Generation Capacity: ............................................................ 2I.3The Jebel Aulia Dam: ..................................................................................... 3

    I.4 The Induction Generator Alternative: ............................................................ 4

    I.5 Thesis Layout: ............................................................................................... 5

    Chapter Two .......................................................................................................... 7

    Grid Connected Induction Generators for Small Hydro: ..................................... 8

    THE JEBELL AULIA EXAMPLE ..................................................................... 8

    2.1 Technical Description: .................................................................................. 8

    2.2 Reasons for the Induction Generator Alternative: ....................................... 15

    2.3 System Protection: ...................................................................................... 17

    2.4 Power Station Performance:........................................................................ 21

    Chapter Three ...................................................................................................... 25

    Equipment Procured for Laboratory Induction Generator Tests ........................... 28

    3.1 General: ...................................................................................................... 28

    3.2 Induction Generator Test Equipment: ....................................................... 29

    3.3 Measurement of Induction Motor Parameters: ............................................ 36

    Chapter Four........................................................................................................ 41

  • 7/27/2019 MSC OF IGs

    7/133

    VI

    Steady-State Performance Measurements and Calculations ................................. 44

    4.1 Calculations and Measurements - Laboratory Tests: ................................... 44

    4.2 Power-factor Calculations Procedure: ......................................................... 51

    4.3 Calculations and Measurements for the Jebel aulia Hydro - matrix UnitsTests: ................................................................................................................ 54

    Chapter Five ........................................................................................................ 64

    Recommended Sites of Small Power Generation in Sudan................................... 67

    5.1 Utilization of Induction Motors and old Synchronous Generators:.............. 67

    5.1.1 Kilo-X gas turbine power station: ...................................................... 68

    5.1.2 Burri II Power Station: ......................................................................... 68

    5.1.3 Burri III Power Station:......................................................................... 69

    5.1.4 Kashm Elgirba Rehabilitation Project: ............................................... 69

    5.2 Potential for Small Hydro Power Schemes:................................................ 70

    Chapter Six .......................................................................................................... 85

    CONCLUSIONS AND RECOMMENDATIONS ............................................... 86

    6.1 General ....................................................................................................... 89

    6.2 The advantages of the experience:............................................................... 91

    References: .......................................................................................................... 93

  • 7/27/2019 MSC OF IGs

    8/133

    VII

    LIST OF FIGURES

    Figure (2.1) View of three modules of the hydro matrix turbine 8

    Figure (2.2) View of one module (two turbines and generators) 9

    Fig (2.3) Connection to the National Grid 10

    Fig.(2.4) Another view of the feeders seen on the PLC display with Z705 and

    Z8o5 11

    Fig (2.5) Single-Line Diagram of Jebel Aulia S/S 12

    Fig (2.6) Connection Layout of the two generators (courtesy of VA TECH

    HYDRO) 13

    Fig.(2.7) View of one turbo generator 14

    Fig (2.8) General arrangement of Somatic S7-300 PLC 16

    Fig (2.9) Layout of PV/WTG interconnected with EU and control strategy 18

    Fig (2.10) The electric drawing of one module 19

    Fig (2.11) Compensating circuit in 5 steps 20

    Fig (2.12) Shunt capacitors connected in series with the inductance to remove the

  • 7/27/2019 MSC OF IGs

    9/133

    VIII

    harmonics (courtesy of VA TECH HYDRO) 21

    Fig (3.1) 5.5KW DC motor-2.0 hp Induction Motor Generator Set 27

    Fig (3.2) 5.5 KW DC motor-1.0 hp Induction Motor Generator Set 28

    Fig (3.3) Power-factor Correction Capacitor Bank of 18 F units 29

    Fig (3.4) Rheostats ofdifferent sizes for dc motor speed control 30

    Fig.(3.5) The speed indicator of the 2 hp motor in r.pm. 31

    Fig (3.6) A View of the power quality analyzer (Fluke 434) 31

    Fig.(3.6) DC-Motor Prime-mover Arrangement for Induction Generator

    Experiments 33

    Fig (3.7) Stator winding resistance measurements 34

    Fig.(3.8) No-load test display data of the 2 hp motor 35

    Fig.(3.9) Locked-rotor test display of the 2 hp motor 36

    Fig (3.10) Equivalent circuit of No load test 37

    Fig (3.11) Equivalent circuit of locked rotor 37

  • 7/27/2019 MSC OF IGs

    10/133

    IX

    Fig.(4.1) Zero-slip 2hp motor test data 42

    Fig.(4.2) Generated Power Display = 1.8 KW 43

    Fig. (4.3) 2hp motor data display as generator 43

    Fig (4.4) The 2hp motor as a generator with capacitor banks 44

    Fig.(4.5) Active power /speed curve of the 2 hp motor 44

    Fig.(4.6) Torque /speed curve of the 2hp motor 45

    Fig.(4.7) Reactive power/speed curve of the 2 hp motor 45

    Fig.(4.8) Power factor/speed curve of the 2 hp motor 46

    Fig.(4.9) Efficiency /speed curve of the 2 hp motor 46

    Fig(4.10) The 2 hp motor with capacitors in series 47

    Fig.(4.11) The 2 hp motor with capacitors in series 47

    Fig.(4.12) The harmonic contents of the 2 hp motor 48

    Fig.(4.13) The red phase current harmonic content 48

  • 7/27/2019 MSC OF IGs

    11/133

    X

    Fig.(4.14) The yellow phase current harmonics content 49

    Fig.(4.15) The blue phase current harmonics content 49

    Fig.(4.16) Harmonics content of all three phase currents 56

    Fig.(4.17) Wave ofthe three phase currents 56

    Fig (4.18) Wave of the three phase voltage 57

    Fig.(4.19) Power and energy of the induction generator 57

    Fig.(4.20) Harmonic contents of the currents 58

    Fig.(4.21) Volt/amp/hertz of the induction generator 59

    Fig.(4.22) Display of the current waveform 59

    Fig.(4.23) Display of the voltage waveform 59

    Fig.(4.24) Power and energy of the induction generator 60

    Fig.(4.25) Another display of power and energy of the induction generator 60

    Fig.(4.26) Harmonic table for the three phase currents 61

  • 7/27/2019 MSC OF IGs

    12/133

    XI

    Fig.(4.27) Active power/speed curve 61

    Fig.(4.28) Reactive power/speed curve 62

    Fig.(4.29) Power factor/speed curve of the Jebel Aulia motor ..62

    Fig.(4.30) Torque /speed curve of Jebel IG 63

    Fig.(4.31) Simulation of capacitors connected in series 63

    Fig.(4.32) Simulation ofcapacitors connected in series 64

    Fig (5.1) Downstream view of Sennar dam 71

    Fig (5.2) Another view of Sennar dam 71

    Fig (5.3) Kilo 0 of Sennar dam 72

    Fig (5.4) Kilo 77 of Jazeera Canal 72

    Fig (5.5) Kilo 57 bridge of Jazeera Canals 73

    Fig (5.6) Kilo 77 on Jazeera Canal (side view) 74

    Fig (5.7) Kilo 57 bridge of Managil Canal 75

  • 7/27/2019 MSC OF IGs

    13/133

    IIX

    Fig (5.8) Kilo 57 on Managil Canal 75

    Fig (5.9) AbuRakham dam 78

    Fig (5.10) View No 2 of AbuRakham dam ...79

    Fig (5.11) Kilo 22 Bridge on Rahad Canal 80

    Fig (5.12) Kilo 36 bridge on Rahad Canal 81

    Fig (5.13) View no.2 of kilo 36 bridge 82

    Fig (5.14) Kilo 76 bridge of Rahad Canal 83

    Fig (5.15) View no.2 of kilo 76 bridge of Rahad Canal 84

    Fig (6.1) Typical arrangement of canal fall small hydropower station 88

    Fig (6.2) Typical arrangement of small hydro power station 89

    Fig (6.3) Another typical arrangement of small hydro power station .89

    Fig (6.4) Kalmoni 200 kW SHP project near Guwahati in Assam 90

  • 7/27/2019 MSC OF IGs

    14/133

    XIII

    LIST OF TABLES

    Table (3-1) Results of the no load test and blocked rotor test 36

    Table (3.2) Rules of thumb dividing rotor and stator reactance 39

    Table (4.1)The required KVAR of the capacitor for power factor correction..50

    Table (5.1) Data from Elmanagil project 76

    Table (5.2) Data from Aljazeera project 77

    Table (5.3) Data from Elrahad project 85

  • 7/27/2019 MSC OF IGs

    15/133

    XIV

    LIST OF APPENDICES

    APPENDIX A A

    APPENDIX B M

    APPENDIX C N

    APPENDIX D O

    APPENDIX E E

  • 7/27/2019 MSC OF IGs

    16/133

    CHAPTER I

    INTRODUCTION

  • 7/27/2019 MSC OF IGs

    17/133

    2

    Chapter One

    I.1General:

    In the National Energy Plan of 1985 and the National Strategy Plan of

    1992, the power sector objectives of Sudan were formulated. The plan of a

    hydro matrix power plant implementation at the Jebel Aulia Dam is fully in

    line with these objectives; in particular, the emphasis on the development of

    hydroelectric generation together with the provision of electricity at lowest

    possible cost, which can be fully met with this technology aiming at less civil

    construction, little excavation and no coffer dams, no additional land usage,

    and the maintenance of existing river flow patterns.

    I.2 Sudan Installed Generation Capacity:

    Sudan currently has an installed electricity generation capacity of 2588 MW,

    managed by the ministry of dams and electricity. It is composed of the

    thermal (mainly furnace) and hydropower plants. Hydroelectric power

    generation varies greatly over time, due to rainfall patterns. The maingenerating facility of hydro power is the Merowi dam located on the Main

    Nile river basin approximately 430 km north of Khartoum with ten

    generating units of a total 1250 MW. Roseires has an installed capacity of 280

    MW, but its output varies greatly as water levels on the river rise and fall

    throughout the year.

    VA-Tech-Hydro Hydro-matrix coordinator Herald Schmidt said: "The

    excellent business relation between NEC and VA-Tech-Hydro goes back to

    1968, when NEC ordered the original equipment for the Roseires hydropower

    plant. The original turbines were supplied and installed by VA-Tech-Hydro

    for NEC and just recently VA-Tech-Hydro has been awarded contracts to

  • 7/27/2019 MSC OF IGs

    18/133

    3

    rehabilitate these turbines. The modernization and rehabilitation of the

    turbines became necessary because of the wear and tear caused by the

    aggressive and heavy silt load of the Blue Nile"1.

    Schmidt continued: "The continuous engagement at the Roseires power

    station has led to the formation of an informal partnership between NEC and

    VA-Tech-Hydro under which VA-Tech-Hydro provides supplies, expert

    services and consultations in order to effectively support and assist NEC in its

    effort to maintain and improve electricity supply to Sudan's growing economy

    and private consumers".

    I.3The Jebel Aulia Dam:In the year 2001, VA-Tech-Hydro received its first large contract for a

    Hydro-matrix power plant. The contract was placed by the former National

    Electricity Corporation (NEC), the Sudanese state owned electricity producer

    and distributor. The total contract value was worth 30 million Euros. NEC

    awarded VA Tech Hydro with the supply of 40 Hydro-matrix power modules,

    each with two turbine generator sets, for 40 of the 50 openings of the Jebel

    Aulia dam on the White Nile in Sudan about 40 km south of the capital,

    Khartoum. The contract also included the required mechanical and electrical

    auxiliary systems as well as a new dam crane.

    The Jebel Aulia dam was built in 1933-37 and is used mainly for irrigation

    purposes and flood control. In March 2004 the first 20 Hydro-matrix turbines

    were handed over to the customer for commercial service and have been

    1Power Engineering International magazine, June 2004.

  • 7/27/2019 MSC OF IGs

    19/133

    4

    supplying electricity into the grid of NEC. Installation work on the next units

    is already in full swing, every two months ten turbine generator units were

    commissioned.

    Full operation of the power plant was scheduled for early 2005. The new

    Hydro-matrix power plant at Jebel Aulia has contributed considerably with

    30.4 MW to the generation capacity in Sudan by means of environmentally

    clean hydropower.

    Financing was one of the key issues of the project. At the time, bank

    guarantees to the satisfaction of VA Tech Hydro could not be obtained, butwith a special procedure this problem was solved. It was agreed with the

    customer that periodical payments would be made, while VA Tech Hydro will

    only perform according to milestone events. This procedure has turned out to

    be the best for both parties and is based on the long lasting excellent

    relationship and particularly with the previous National Electricity

    Corporation (NEC) which is the main supplier together with the new

    generation of Merowi Dam power station which is implemented by the Dam

    Implementation Unit(DIU) and adding a power of 1250 MW to the national

    grid of Sudan which is already having a power of 1338 MW, where an

    efficient electrical energy of 30 MW has been obtained from Jebel Aulia

    Hydro matrix power station as described below.

    I.4 the Induction Generator Alternative:

    Engine driven induction generators were ideal power sources for those

    industries and farmers required to curtail their demands during the power

  • 7/27/2019 MSC OF IGs

    20/133

    5

    shortage in northern California in the spring of 19482.

    The advantages of the

    induction generator were: control apparatus simplicity, freedom from

    hunting, neither excitation nor synchronization requirements, low fault

    currents, low cost, and subsequent general usefulness in later motor

    applications.

    The nameplate data on most induction machines would be those of motor

    ratings, and it is desirable to consider what changes must be made, if any, in

    order that the machine operate satisfactorily as generator. If the speed is

    driven above synchronism by the same revolutions per minute that the

    machine normally operates at below synchronism, the generator will deliver

    approximately rated current at rated voltage and rated efficiency. The electric

    power out will be approximately equal to the rated shaft motor power. The

    generator power factor will be much worse, being approximately equal to the

    motor power factor times the motor efficiency.

    I.5 Thesis Layout:

    The aim of this dissertation project is to present a study of the potential sites

    for hydropower development projects in Sudan with reference to induction

    generator applications, taking Jebel Aulia Hydro-matrix project as an

    example. To this end, Chapter II presents an over-view of the Hydro-matrix

    experience with induction generators in Sudan. Chapter III shows the kind of

    the experiments being done on the University of Khartoum Laboratory and

    the equipments procured for that work and it is followed in Chapter IV by the

    results of an investigation into the characteristics of grid-connected induction

    2 From a paper written by OTTO J. M. SMITH with the title (Generator Rating of Induction Motors)magazine AIEE magazine, volume69, 1950.

  • 7/27/2019 MSC OF IGs

    21/133

    6

    generators in terms of capability limits and power factors performance using

    a suitably-matched experimental test bed. Verification results of steady-state

    performance characteristics as well as experimental findings on the installed

    hydro-matrix generators are also presented in this Chapter. Chapter V

    presents the results of a research into the potential of additional sites for small

    hydropower developments as well as the identification of large motor

    installations for possible utilization as generators in Sudan.

  • 7/27/2019 MSC OF IGs

    22/133

    7

    CHAPTER II

    GRID-CONNECTED INDUCTION GENERATORS FOR SMALL HYDRO

    WITH REFERENCE TO THE JEBEL AULIA EXAMPLE

  • 7/27/2019 MSC OF IGs

    23/133

    8

    Chapter TwoGrid Connected Induction Generators for Small Hydro:

    THE JEBELL AULIA EXAMPLE2.1 Technical Description:

    The Hydro matrix power plant in Jebel Aulia consists of 80 turbine-generator

    sets, which are installed in 40 modules by pairs as seen in figure (2.1)

    Figure (2.1) view of three modules of the hydro matrix turbine

  • 7/27/2019 MSC OF IGs

    24/133

    9

    Figure (2.2) view of one module (two turbines and generators)

    Each module is equipped with two submerged, 380 kW horizontal propeller

    turbines. Each turbine has a 1120 mm diameter, three-bladed runner

    precision cast of aluminum bronze. Additionally, the scope of the VA Tech

    Hydro contract contains all mechanical and electrical auxiliaries. NEC

    carried out local activities for the accomplishment of the contract since Hydro

    matrix makes use of the existing dam structure, only very minor civil

    construction is needed. This is one of the predominant advantages of the

    technology. The Hydro matrix modules are shipped to the Jebel Aulia dam

    where they are installed into the existing water passage

    the on/off operation of the turbines will be accomplished by means of the

  • 7/27/2019 MSC OF IGs

    25/133

    1

    existing control gate. Both turbines of one module will be turned on or shut off

    simultaneously. The gate has only an open and closed position.

    Ten of the 690 V asynchronous generators feed into one common container

    type generator switchgear substation. This arrangement is one out of eight

    lots. Each one of these substations has its own control and step up transformer

    and also includes the reactive power compensation.

    A total of eight of these substations are installed at the dam side, on the

    opposite side of the machines and handle the total plant output of the 80 units.

    From these eight substations, individual 33 kv cables run to a 33 kv stationlocated beside the river. The whole power plant is managed from a central

    plant control station. With this concept it is possible to operate each lot

    independently from the others. The power station is connected to the national

    grid through two 33 kv feeders feeding the Jebel Aulia substation by two

    breakers named Z705 and Z805 as shown below in fig. (2-3)

  • 7/27/2019 MSC OF IGs

    26/133

    220KV220 KV

    110KV110KV

    33KV33KV

    Z705Z805GitainaJebel

    Jebel Auila power station Bus bar

    SUNDUS

    33KV

    33K

    V

    Jebel

    Gitaina

    Fig (2.3) Connection to the National Grid

  • 7/27/2019 MSC OF IGs

    27/133

    2

    Fig. (2.4) another view of the feeders seen on the PLC display with Z705 and Z

    805

  • 7/27/2019 MSC OF IGs

    28/133

    3

    Fig (2.5) Single-Line Diagram of Jebel Aulia S/S

  • 7/27/2019 MSC OF IGs

    29/133

    4

    For emergency power supply a diesel generator unit is installed and acts as a

    backup power supply in case of loss of net voltage for the control gates gear

    motors and the module crane.

    The induction generators as seen on (Figure 2.6) below

    Fig (2.6) Connection Layout of the two generators (courtesy of VA TECH

    HYDRO)

  • 7/27/2019 MSC OF IGs

    30/133

    5

    Fig.(2.7) View of one turbo generator

    2.2 Reasons for the Induction Generator Alternative:

    The induction generator has been selected for the project due to the following

    reasons:

    1-No need to excitation system of direct current for the voltage and reactive

    power control such as that used for synchronous generators.

    2-No need to electro hydraulic governor to control the speed or the generator

    frequency or any kind of speed droop as that used for synchronous machines.

  • 7/27/2019 MSC OF IGs

    31/133

    6

    3-The induction generators are self-protected during surges and system

    disturbances and have a very low fault current.

    4- The motors (induction generators) are robust and reliable with low cost

    and maintenance and high efficiency (squirrel cage type).

    5- No synchronization problems of voltage, frequency and phase angle, what is

    really needed ,is to have both the turbine and the generator to run at the same

    direction with speed above the synchronous speed of the motor (375rpm ) and

    the turbine is run with 379 rpm and then being connected to the system.

    6-The compensation of the reactive power being absorbed by the induction

    generators is done by means of shunt capacitors connected in steps manually

    or automatically.

    7-The operation and control of the hydro matrix turbines is simple and

    reliable and constitutes a good and simple example of renewable energy

    without pollution and complication if we consider the example of Egypt in

    wind turbines at the Zafarana wind turbine fields which is used to produce

    power with induction generators together with Photo Voltaic (PV) system

    which is a very complicated system of inversion and power electronics (see

    fig2.9).

    8-The system is monitored and operated and controlled by means of a

    Programmable Logic Controller (PLC) from Siemens Company (Somatic S7-

    300) and is configured by the National Load Dispatch Centre (NLDC) SCADA

    system by means of two servers according to the international relevant

    standards and that kind of automation is very suitable for such a system as

    shown below:

  • 7/27/2019 MSC OF IGs

    32/133

    7

    Fig (2.8) General arrangement of Somatic S7-300 PLC

    9 - There is a standby diesel engine generator to supply the low voltage system

    and the batteries and close the gates in the case of power failure.

    10-The induction generator is equipped by three sensors (pt100) formeasuring the temperature of the stator winding and giving alarm in case of

    high temperature and two sensors for the temperature of the bearings (DE

    &NDE) and three water level sensors to protect the generator from water

    coming inside the generator and also there is one magnetic pick up speed

    sensor.

    2.3 System Protection:

    A-Differential protection.

    B-Voltage monitoring (over-voltage 1&2 and undervoltage 1&2).

    C-Over-frequency 1&2 and under frequency 1&2.

  • 7/27/2019 MSC OF IGs

    33/133

    8

    D- Over d current protection.

    E-Earth-fault protection.

    F-Over-load protection.

    G-Reverse-power protection.

    H-Over-speed protection.

    I- Monitoring of stator windings temperature and bearings.

    J- Leakage water level.

  • 7/27/2019 MSC OF IGs

    34/133

    9

    NN=Neural Network.

    PV=Photo Voltaic cells.

    EU=Electric Utility.

    Fig (2.9) Zafarana Wind field schematic diagram with photo voltaic cells in

    Egypt

  • 7/27/2019 MSC OF IGs

    35/133

    21

    Fig (2.10) the electric drawing of one module

  • 7/27/2019 MSC OF IGs

    36/133

    2

    Fig (2.11) compensating circuit in 5 steps

    2.4 Power Station Performance:

    The power station is considered to be a very good example of efficient

    electrical energy, where it is friendly to the environmental surroundings with

    a very low cost and good price of MWHR (46.7 Sudanese pound), please refer

    to appendix (B ) although it is totally shut down for four months as the head

    goes below the required designed head (less than 1.88 m ) ,in spite of that

    outage the performance has been found in good situation and somemodifications have been done to make better performance such as :

    A- The total harmonic distortion (THD)of both voltage and current were

    found very high at the beginning of the power station start due to the

  • 7/27/2019 MSC OF IGs

    37/133

    22

    capacitor banks which are used for the power factor correction and

    reduction of the reactive load burden of NEC (i.e. THD is above 50 % )

    and that happened during the switching operation of capacitor banks

    which are selected in five steps to raise the power factor from 66% up to

    98%,and that high distortion obliged NEC to ask the help and advices of

    their consultant Dr. Abdelrahman Karrar,who is the NEC technical

    consultant and advisor, to study that problem where he stated that the

    harmonics are not from the generator winding design which is well

    designed and it is coming from NEC power system and the capacitors

    which are nonlinear load. The problem was solved by VA TECH through

    the insertion of passive filters (inductance) being connected in series with

    the capacitor banks and it was almost vanished and the harmonics are no

    longer

    seen,

    please see

    figure

    (2.12)

  • 7/27/2019 MSC OF IGs

    38/133

    23

    Fig (2.12) Shunt capacitors connected in series with the inductance to remove

    the harmonics (courtesy of VA TECH HYDRO).

    B- Since all the generators are submersible and have got no heaters to prevent

    condensation ,some water leakage are trapped inside the generators and the

    water is detected by some sensors and cause tripping of the generator and it

    was solved by means of drain pipes and small pumps, but it sometimes it

    causes condensation and weak insulation of the stator windings, and that

    problem was solved later by means of vacuum pump and heating system and

    further on, a new modification of heating system through the generator

    winding is proposed by NEC and Andritz Hydro will be going to implement

    it as shown on the diagram below which is a proposal of heating the module

  • 7/27/2019 MSC OF IGs

    39/133

    24

    With the use of direct current (DC) supply.

    C- Some contactors of both the generator and the compensating circuit are

    subject to failure and damage and burning from time to time during the

    system disturbance and that was solved by new modification of the sequence

    order of the system tripping by tripping of the capacitor bank at the first time

    and keep the generator contactor closed, however, on real fault the contactor

  • 7/27/2019 MSC OF IGs

    40/133

    25

    shall be tripped in normal condition and hence protecting the generator from

    over voltage which is the most dangerous situation.

    D- Connection of the power station with the main National load Dispatch

    Centre (NLDC) through the SCADA system and Siemens PLC automation for

    better communication.( only one channel is used and the other one could not

    be operated).

    E-The reactive power of the induction generators at the beginning of the

    scheme is fed from the (Majarous) substation, through feeders of 33 KV, as

    the substation is supplied with 110 KV and now it is fed from Jebel Aulia

    substation which is supplied with 220 KV, where the problem of the voltage

    drop is solved.

    F- The power cable of the hydro matrix generator is not a submersible one

    and sometimes it is subject to some damages and cut on the cable which leads

    to weak insulation of the whole system (the cable +induction generator) that

    problem is treated and solved by means of using a special kind of shrinkable

    heating to seal the cable not to allow water to go inside the live conductors.

    G-Runner Chamber and Draft Tube Problems:

    Some cracks and cavities appear in the runner chamber and the draft tube

    and many discussions with VA-TECH and the mechanical engineers of the

    power station were made and finally they came to a solution of using the

    coating devices which have the name (IRATHANE 155) and previously with

    (CRAME-KOT) and the company agreed to turn out the existing mild steel

    plates and install new stainless steel sleeves as already being fixed for the

    runner chambers as reliable and durable solution and by making new plates

    of stainless steel being welded above the original one.

    Finally we hope that our company, the Sudanese Hydro Power Generation

    Company Ltd (SHGC) with coordination of the ministry of dams and

  • 7/27/2019 MSC OF IGs

    41/133

    26

    electricity could consider more projects and schemes similar to Jebel Aulia to

    be implemented, like Sennar dam deep sluice gates and the Jazeera, Managil

    canals and Elrahad canals as some studies which are included within this

    thesis are done on this matter by the former NEC and the ministry of

    irrigation (MOI) and the Jazeera scheme board. The Andritz Hydro company

    has manufactured another design of hydro matrix with new system called

    Straflo matrix which is mainly a hydro matrix turbine, but with a

    synchronous generator that has a permanent magnet installed on the rotor of

    the generator, although, there will be no need to compensating capacitors but

    a further study and comprehensive load flow shall be done to select the best

    design of the permanent magnet and our company has to decide which option

    to select.

  • 7/27/2019 MSC OF IGs

    42/133

    27

    CHAPTER III

    EQUIPMENT PROCURED FOR LABORATORY INDUCTION

    GENERATOR TESTS

  • 7/27/2019 MSC OF IGs

    43/133

    28

    Chapter Three

    Equipment Procured for Laboratory Induction Generator Tests

    3.1 General:

    This Chapter describes the set of experiments conducted at the Electrical

    Machines Laboratory of the University of Khartoum aiming at investigating

    the steady-state performance characteristics of grid-connected induction

    generators. The equipment for these tests were obtained with considerable

    effort as the available laboratory test beds of motor-generator sets were

    thought unsuitable in terms of prime-mover power /generator ratios. Two

    different motor-generator sets of higher ratios were procured with the help of

    a NEC donation of a DC prime-mover motor and the technical assistance

    received with respect to mechanical couplings. Digital multi-meters and power

    quality analyzers were also made available for the active and reactive power

    recordings under different operating conditions, including those of the

    capacitor-compensated system aiming at power-factor improvements.

    Calculations results of power-factor correction capacitors ratings based on

    recommended practice tables are presented in this chapter.

  • 7/27/2019 MSC OF IGs

    44/133

    29

    3.2 Induction Generator Test Equipment:

    Fig (3.1) 5.5KW DC motor-2.0 hp Induction Motor Generator Set

  • 7/27/2019 MSC OF IGs

    45/133

    31

    Fig (3.2) 5.5 KW DC motor-1.0 hp Induction Motor Generator Set

  • 7/27/2019 MSC OF IGs

    46/133

    3

    Fig (3.3) Power-factor Correction Capacitor Bank of 18 F units

  • 7/27/2019 MSC OF IGs

    47/133

    32

    Fig (3.4) Rheostats of different sizes for dc motor speed control

  • 7/27/2019 MSC OF IGs

    48/133

    33

    Fig.(3.5)the speed indicator of the 2 hp motor in r.pm.

    Fig (3.6) A View of the power quality analyzer (Fluke 434)

  • 7/27/2019 MSC OF IGs

    49/133

    34

    The equipment acquired for the experiment consists of M-G sets, resistor and

    capacitor banks assemblies and measuring/recording instruments. These are

    shown in Figures (3.1 up to 3.6) where the corresponding specifications are

    given in Appendix (D).The acquisition of the M-G sets shown in Figures (3.1

    and 3.2) was in particular a hard and time-consuming task. In this respect, the

    donation by NEC of the DC motor drive and the technical assistance received

    with the alignment and coupling of the two experimental motors is greatly

    acknowledged.

    Since the prime mover is designed to run with a speed of 2900 rpm it is only

    possible to decrease the speed by armature control and we are able to do that.

    Many shots of operations were made for running the induction motor as a

    generator and could be seen on the results obtained and the application of

    capacitor banks (Figure 3.3) (shunt type) for both connection of star and delta

    and by the use of the compensation table which is attached to appendix (C)

    and even the attempts of connection of the series capacitor as explained.

    It is worth mentioning that during the tests of the series capacitors an accident

    happened which caused a complete failure of the coupling associated with a

    very high noise and after investigation and inspection it was found coming

    from the utility supply which was received at that time in a reverse direction

    and that was a mal operation by (NEC) operation and distribution staff after

    a maintenance work. That failure caused us too much time to find another

    motor and to make new coupling at the industrial area of Khartoum North.

  • 7/27/2019 MSC OF IGs

    50/133

    35

    Finally we get a new induction motor (squirrel cage) with a power of one hp.

    and being driven by the same 5.5 KW dc motor the schematic diagrams of

    both the dc motor and the induction motor can be seen on figure (3.6)

    Fig.(3.6) DC-Motor Prime-mover Arrangement for Induction Generator

    Experiments.As it is explained previously all our tests and experiments are done with that

    kind of grid connected generators, where the reactive power needed for the

    magnetization is obtained from the grid and due to the non-availability of

    Induction motor schematic diagram

    5.5 kw dc motor coupled with the induction motor

  • 7/27/2019 MSC OF IGs

    51/133

    36

    some devices and equipments such as the dynamometer or the LABVIEW

    equipments with its software and we started looking for dc source capable of

    running the 5.5 kw dc motor but we could not find it in Khartoum, some

    tests are simulated by MATLAB program such as series capacitor and speed

    torque curve and reactive power curve and the power factor to slip curve as

    can be seen on the results chapter

    3.3 Measurement of Induction Motor Parameters:

    The 2 hp induction motor parameters which are xs,xr,rs,rr,xm and rc were

    measured by means of the following tests:

    1-The DC test for stator resistance by means of battery voltage of 12 v dc and

    a limiting resistor of 8 ohm as shown below

    Fig (3.7) stator winding resistance measurements2-No load test

    3-Locked rotor test

    The stator winding resistance was obtained by means of a dc source from a

    car battery which was equivalent to 12.87 v dc and a limiting resistor of 8 ohm

    and by taking three readings as shown below

  • 7/27/2019 MSC OF IGs

    52/133

    37

    1-2rs=2.56 v/1.121A = 2.384 ohm

    2-2rs=2.59 v/1.124A = 2.304 ohm

    3-2rs=2.59 v/1.126 A= 2.300 ohm

    The average value of rs is (2.384+2.304+2.300)/6 = 1.165 ohm. And by the

    display of the fluke meter which is shown below seen on figure (3.8).

    Fig.(3.8) no-load test display data of the 2 hp motor

    DPF=Distortion Power factor

  • 7/27/2019 MSC OF IGs

    53/133

    38

    Fig.(3.9) locked-rotor test display of the 2 hp motor

    And the table (3-1) is showing the measured values of the No load test and the

    locked rotor test which was done by supply voltage of 50 Hz in frequency and

    reduced voltage as shown below:

    Table (3-1) results of the no load test and blocked rotor test

    S

    Speed

    in

    rad/sQPVavIcIbIaType of test

    0.63

    KVA

    157.08

    rad/s0.57 KVAR0.26

    KW231.3 V1.5

    A1.7 A1.5 ANo load test

    0.96

    KVA0

    Rad/s0.85 KVAR0.45

    KW77.16 V7.1

    A7.2 A7.3 ABlocked

    rotor test

  • 7/27/2019 MSC OF IGs

    54/133

    39

    It is worth mentioning that the locked rotor test is done by means of variable

    transformer of 1500 VA.

    Fig (3.10) equivalent circuit of No load testAlso the figure below shows the locked rotor equivalent circuit

    Fig(3.11) equivalent circuit of locked rotor

    From the figures shown above the following calculations are done for the

    parameters measurement

    From the No load test the following equation can be used

    (3.1)

    Average value of IO is (1.7+1.5+1.5)/3=1.566 A

    Znl =(0.57/ (1.5666)2)*1000 /3 = 77.48 ohm

    The above mentioned value is equivalent to X1 +XM

  • 7/27/2019 MSC OF IGs

    55/133

    41

    The stator copper loss is equal to

    PSCL =3IO2R =3*1.5666*1.566*1.165 = 8.57 w (3.2)

    Therefore the no load rotational losses are

    Prot =PinPSCL =260 -8.57=251.43 watts

    From this value we can find out the Rc resistance which is equivalent to:

    Rc = (Vph)2/Prot/3 = 17834.3/251.43/3 =212.8 ohm (3.3)

    From the locked rotor test,

    Iav= (7.3+7.2+7.1)/3 =7.2 A (3.4)

    The locked rotor reactance is XLR= (Q/3)/I2

    (3.5)

    = (850/3)/51.84

    =5.465 ohm

    From the rules of thumb which is dividing the stator and rotor reactances as

    it is made over years of experience since there no simple way to separate the

    contributions of the stator and rotor reactances from each other.

    The table below is showing the relation between stator and rotor reactance

  • 7/27/2019 MSC OF IGs

    56/133

    4

    Table (3.2) Rules of thumb dividing rotor and stator reactance

    X1 and X2 as a function of XLRRotor DesignX2X1

    0.5 XLR0.5 XLRWound rotor0.5 XLR0.5 XLRDesign A0.6 XLR0.4 XLRDesign B0.7 XLR0.3 XLRDesign C0.5 XLR0.5 XLRDesign D

    So the values of XLRis equal to(X1+ X2) since our rotor is wound type

    X1 = X2 =5.465/2 = 2.732 ohm (3.6)

    The locked rotor resistance, RLR=R1 +R2 (3.7)

    So the RLR= (P/3)/Iav2= (450/3)/ (7.2 *7.2) (3.8)

    = 2.89 ohm

    Then R2 is equal to 2.89-1.165 = 1.723 ohm

    Also we can find the value of XM which is equal to 77.48-2.732

    =74.74 ohmSo now we can arrange all the motor parameters as follows:

  • 7/27/2019 MSC OF IGs

    57/133

    42

    1- x1 = 2.732 ohm

    2- x2/= 2.732 ohm

    3- r1 = 1.165 ohm

    4- r2/= 1.723 ohm

    5- Synchronous speed =1500 rpm

    6- motor voltage line to line =230 v

    7- XM = 74.74 ohm

    8- Frequency =50 Hz9 - Rc =212.8 ohm

  • 7/27/2019 MSC OF IGs

    58/133

  • 7/27/2019 MSC OF IGs

    59/133

  • 7/27/2019 MSC OF IGs

    60/133

    45

    Fig.(4.2) Generated Power Display= 1.8 KW

    Fig.(4.3) 2hp motor data display as generator

  • 7/27/2019 MSC OF IGs

    61/133

    46

    Fig(4.4)the 2hp motor as a generator with capacitor banks

    For the measurement of the 2hp motor parameters the following displays

    were obtained:

    The MATLAB displays of the 2hp motors were shown below after obtaining

    the motor parameters on the previous chapter (chapter 3 and Appendix E)

  • 7/27/2019 MSC OF IGs

    62/133

    47

    Fig.(4.6) torque /speed curve of the 2hp motor

    Fig.(4.7) reactive power/speed curve of the 2 hp motor

  • 7/27/2019 MSC OF IGs

    63/133

    48

    Fig.(4.8) power factor/speed curve of the 2 hp motor

    Fig.(4.9) efficiency /speed curve of the 2 hp motor

    0 500 1000 1500 2000 2500 30000

    100

    200

    300

    400

    500

    600

    700

    800Induction Motor

    Efficiency(%)

    Speed (RPM)

    30

    40

    50

    60

    70

    80

    90

    100

  • 7/27/2019 MSC OF IGs

    64/133

    49

    Fig(4.10) the 2 hp motor with capacitors in series

    Fig.(4.11) the 2 hp motor with capacitors in series

  • 7/27/2019 MSC OF IGs

    65/133

    51

    And there were some other displays shown below:

    Fig.(4.12) the harmonic contents of the 2 hp motor

    Fig.(4.13)the red phase current harmonic content

  • 7/27/2019 MSC OF IGs

    66/133

    5

    Fig.(4.14) the yellow phase current harmonics content

    Fig.(4.15) the blue phase current harmonics content

    4.2 Power-factor Calculations Procedure:Table-based:

    The power factor calculations were based on the table shown below:

  • 7/27/2019 MSC OF IGs

    67/133

    52

    Table (4.1) the required KVAR of the capacitor for power factor correction

  • 7/27/2019 MSC OF IGs

    68/133

    53

    The 2hp motor power factor calculation was done as follows:Although the induction motor rated power was only 2 hp which was

    approximately equal to 1.5kw, and by driving the generator by the dc motor it

    was noticed that the generator was very stable and no more heat could be

    observed, but it was noticed that the rheostats which were rated by 16 ampere

    and used to control the dc motor speed became very hot and the current was

    almost equal to 25 A. Then it was seen that the power factor was equal to 0.84

    with a reactive power of 1.2 kvar and by the power factor correction table

    On the view of power factor correction table

    It became possible to use it and do the following calculation

    P (tan 1-tan2) = Q (4-1)

    Where P is rated power of the induction motor, and 1 is the power factor

    angle before the improvement and 2 is the power factor angle after the

    correction, and Q is the reactive power needed for the correction in (VAR).

    The rating of the capacitors can be obtained by the following formula

    Qn =Un.In (4-2)

    Where Unis root mean square (rms) value of the ac voltage applied.

    In is the rms of the capacitor current.

    Qn =Un.Un/Xn (4-3)

    Where Xn is the capacitive impedance and equal to

    Xn=1/wCn=1/2fCn ... (4-4)

  • 7/27/2019 MSC OF IGs

    69/133

    54

    Where f =fundamental frequency in Hz

    Cn =total capacitance in farad

    Calculation of the compensated reactive power in (vars) from 0.85 powerfactor to 0.98 power factor.

    1500(0.417) = 625.5 vars

    Cn =Qn/ (Un2*2*f) which is used for star () connected capacitor

    And when it is used for delta () the equation is

    Cn =Qn/ 3(Un2*2*f).. (4-5)

    So the capacitor value is equal to

    Cn() =625.5/ (220*22o*2**50) = 41.136 F

    This capacitor is connected in parallel to the induction generator and the

    improvement received is shown on figure (4.4) where a power factor equal to

    0.98 was got.

    4.3Calculations and Measurements for the Jebel Aulia Hydro -matrix Units

    Tests:

    The following calculations were made to find out the induction motor

    parameters and it was based on the factory tests which were done on the

    factory and it was as follows:

    The parameters of the induction generators of Jebel Aulia

    The following results are obtained from the factory tests of the induction

    generators in Austria.

  • 7/27/2019 MSC OF IGs

    70/133

    55

    Now we can find the average value of the stator winding resistance

    Rs= (0.007910+0.007932+0.007955)/3 =0.007932 ohm

    From the no load test we can find

    Zeq. = (V/3)/I. (4-6)

    =2.9995 /3 with angle 88.11

    =1.7317 sin 88.11

    = 1.7308 ohm

    =Xs +XM

    The stator copper losses

    PSCL=3I2Rs. (4-7)

    = 3(230.04)2(0, 007932)

    =1.256 KW

    Im = Iosin. (4-8)

  • 7/27/2019 MSC OF IGs

    71/133

    56

    =230.04 sin 88.11 = 229.91 A

    Ic= Iocos (4-9)

    =230.04 cos 88.11

    Rc =Vph/Ic (4-10)

    =398.371/7.586

    =52.63 ohm

    Locked Rotor Test

    Zsc =Vph/I (4-11)

    = (207.7/3)/460

    =119.915/460

    =0.2606 ohm

    =0.2606 cos

    =0.2606x0.174

    =0.0453 ohm =Rs +Rr

    Rr =0.0453-0.007932

    =0.03742 ohm

    Xeq = Zscsinsc (4-12)

    = 0.2606 sin 79.97

    =0.2566 ohm

  • 7/27/2019 MSC OF IGs

    72/133

    57

    Xeq = Xr +Xs..... (4-13)

    Xr = Xs

    = 0.2566/2

    = 0.1283 ohm

    XM= 1.73080.1283

    = 1.6025 ohm

    Now we can arrange all the induction motor parameters as follows

    Vs = 690 v line to line

    =398.371 v phase to ground

    Induction generator speed =379 rpm, which is obtained by the turbine and

    above the synchronous speed.

    Please note that the synchronous speed is equal to 375 rpm with total number

    of 16 poles

    XM =1.6025 ohm.

    XS = 0.1283 ohm.

    Xr/

    = 0.1283 ohm.

    rs =0.007932 ohm.

    rr/

    = 0.03742 ohm.

    RC = 52.63 ohm.

    We also made different displays at the power station and we got the following

  • 7/27/2019 MSC OF IGs

    73/133

    58

    Displays:

    Fig.(4.16) Harmonics content of all three phase currents

    Fig.(4.17) Wave of the three phase currents

  • 7/27/2019 MSC OF IGs

    74/133

    59

    Fig (4.18)Wave of the three phase voltage

    Fig.(4.19)Power and Energy of the induction generator of JebelAulia

  • 7/27/2019 MSC OF IGs

    75/133

    61

    Fig.(4.20) Harmonic contents of the currents

    Fig.(4.21) Volt/Amp/hertz of the induction generator of Jebel Aulia

  • 7/27/2019 MSC OF IGs

    76/133

    6

    Fig.(4.22) Display of the current waveform

    Fig.(4.23) Display of the voltage waveform

    Fig.(4.24) Power and Energy of the induction generator

  • 7/27/2019 MSC OF IGs

    77/133

    62

    Fig.(4.25) Another display of power and energy of the induction

    generator

    Fig.(4.26) Harmonic table for the three phase currentsAnd from the parameters obtained and by using MATLAB system the

    following displays were obtained for Jebel Aulia induction generators:

  • 7/27/2019 MSC OF IGs

    78/133

    63

    Fig.(4.27) Active power/speed curve

    Fig.(4.28) Reactive power/speed curve

    0 100 200 300 400 500 600 700 800-1

    -0.8

    -0.6

    -0.4

    -0.2

    0

    0.2

    0.4

    0.6

    0.8

    1x 10

    6 Induction Motor

    ActivePower(Watts)

    Speed (RPM)

  • 7/27/2019 MSC OF IGs

    79/133

    64

    Fig.(4.29) Power factor/speed curve of the jabal motor

    Fig.(4.30) Torque /speed curve of Jebel IG

  • 7/27/2019 MSC OF IGs

    80/133

    65

    Fig.(4.31) Simulation of capacitors connected in series

    Fig.(4.32) Simulation of capacitors connected in series

  • 7/27/2019 MSC OF IGs

    81/133

    66

    CHAPTER V

    RECOMMENDED SITES OF SMALL POWER GENERATION IN SUDAN

  • 7/27/2019 MSC OF IGs

    82/133

    67

    Chapter Five

    Recommended Sites of Small Power Generation in Sudan

    5.1 Utilization of Induction Motors and old Synchronous Generators:

    It is noticed that most of the highly industrial countries are making their best

    to get use of their old replaced electric machines whether they are

    synchronous or asynchronous. As an example to that on the Unites State of

    America (USA) they have what is called (VAR pumping stations) which means

    that their old synchronous machines are best utilized and being used as

    synchronous condensers (production of reactive power) after the removal of

    their old prime movers which are now replaced by new modern electric drives

    or by closing the guide vanes by means of compressed air system in case of

    hydro power generators. Also the induction motors can be made to operate as

    induction generators since induction generators control is very simple and

    need neither speed governor nor excitation system control.

    If we look at the situation of our country (Sudan) we can say that we have lost

    all of our old electric machines whether they are synchronous or

    asynchronous. When considering the history of the electric generation in

    Sudan and the industrial development of factories, we can start with different

    old power stations and they are described as follows:

  • 7/27/2019 MSC OF IGs

    83/133

    68

    5.1.1Kilo-X gas turbine power station:

    That power station which was used in the past for production of power and

    being used for voltage control as it was made operated as a synchronous

    condenser by means of an electric clutch which was used to disconnect the

    prime mover from the generator after the synchronization process and was

    left working alone with a few kilowatts to compensate the losses and by means

    of its Automatic Voltage Regulator (AVR), the reactive power was controlled

    very smoothly without any problem. One can consider the loss we had got and

    faced referring to its generator which had got an apparent power of 18.8

    MVA and a power of 15 MW if we could understand the difficulty of getting

    the spare parts of the gas turbine for its operation and sustainability. The

    NEC administration had decided as a consequence matter of the parts non

    availability to make the generator as a synchronous condenser by means of

    electric drive and NEC tried its best to place tenders so as to do that

    particular job, but in vain since as we discovered later that NEC was not

    willing to do that work as it was considered as a matter of high cost and that

    was on the year 2003 and the whole power station was put out of service and

    all its equipments were sold as scarabs and a good opportunity was lost for a

    device that could help on the national grid stability and contribute a good

    training tool for students of engineering colleges in Sudan.

    5.1.2Burri II Power Station:That was the first power station on Sudan and it consisted of different types

    of power plant units such as steam and diesel. As the power station was old

    and the difficulty of obtaining the spare parts and the original manufacturer's

  • 7/27/2019 MSC OF IGs

    84/133

  • 7/27/2019 MSC OF IGs

    85/133

    71

    generators and that had not been used at the time of power shortage. And

    almost most of them were treated similar to NEC policy.

    Utilization of old electric machines gets its importance from the comparison

    of the new static VAR compensating devices such as capacitors which are

    controlled by means of power electronic devices and their bad adverse of

    harmonics generation, whereas the old machines could produce a clean

    reactive power without any distortion and contribute actively to the steady

    state stability of the system.

    5.2Potential for Small Hydro Power Schemes:

    With reference to the high success of Jebel Aulia Hydro matrix project in

    Sudan as a unique scheme in Africa and aiming at best utilization of existing

    dams and canals for the production of electric energy with the minimum of

    new civil work or additional cost and damage to the environment, experts

    from ministry of irrigation ,the Jazeera Scheme board, Elrahad agricultural

    project and the previous national electricity corporation NEC decided tomake a feasibility study to study the existing dams and canals for both

    Elrahad and Jazeera and Managil schemes.

    It is worth mentioning that the expert team was established in the year 2004

    with the following engineers:

    1- Dr. Ahmed Salih Hussien.. Hydraulic Research Station

    Manager (MOI)

    2- Eng.Elkarori Elhaj Hamad Dams Directorate Manager

    (MOI)

    3- Eng. Adam Abbaker .Project Directorate Manager (MOI)

  • 7/27/2019 MSC OF IGs

    86/133

    7

    4- Eng.Elzain Abdelrahim..Agricultural Projects Manager (MOI)

    5- Eng.Mohamed Oro Salim.. Hydro Power Manager (NEC)

    6- Eng.Mudawi Abdelkarim Musa..Hydro Matrix Project Manager

    (NEC)

    7- Eng.Dafalla ElkabashiEngineering Directorate Manager

    (Jazeera Scheme Board)

    The expert team started this study from Sennar dam where a similar matrix

    turbines of Jebel Aulia could be erected as the dam itself can be divided into

    three parts:

    1- There are 80 deep sluice gates

    2-The gates of Jazeera and Managil canals

    3-Downstream canals such as kilo 57and kilo 77

    All these parts can be treated similar to Jebel Aulia Hydro matrix turbines

    and the estimated powers that would be produced are tabulated as in Data

    from Aljazeera, Managil and Elrahad projects shown below.

  • 7/27/2019 MSC OF IGs

    87/133

    72

    Fig (5.1) downstream view of Sennar Dam

    Fig (5.2) another view of Sennar dam

  • 7/27/2019 MSC OF IGs

    88/133

    73

    Fig (5.3) Kilo 0 of Sennar dam

    Fig (5.4) Kilo 77 of Jazeera Canal

  • 7/27/2019 MSC OF IGs

    89/133

    74

    Fig (5.5) Kilo 57 bridge of Jazeera Canals

  • 7/27/2019 MSC OF IGs

    90/133

  • 7/27/2019 MSC OF IGs

    91/133

  • 7/27/2019 MSC OF IGs

    92/133

    77

    The data obtained from Elmanagil is shown below on this table

    Table (5.1) data from Elmanagil project

    It starts from Sennar dam.

    It goes in the north direction parallel to Elmanagil canal until kilo 57.

    After kilo 57 they are separated and the Jazeera canal continuing to the

    north.

  • 7/27/2019 MSC OF IGs

    93/133

    78

    Table (5.2) Data from Al jazeera project

    STATION GATES(NUM,DIA)MAX.HEAD(M) Max.Discharge In

    M3/seconds

    ESTIMATED

    POWER(MW)

    Connection to the

    grid

    Citiesand

    villages

    kilo0 from

    Sennardam

    N=14,5*3M,MANU

    AL6.5 218.8 8.5 11 KV Sennar

    kilo 77N=4(2P),3*3.75M,M

    ANUAL 2.3 150.5 2.1 11KV5villages

    kilo 57N=6(2P),3*3.75M,MANUAL

    2.5 162.1 2.4 11KV4villages

    Beka kilo

    108

    N=3,3.5*6M,MANU

    AL2.3 92.6 1.3 11KV

    Many

    villages

  • 7/27/2019 MSC OF IGs

    94/133

  • 7/27/2019 MSC OF IGs

    95/133

    81

    Fig (5.10) View No 2 of AbuRakham dam

  • 7/27/2019 MSC OF IGs

    96/133

    8

    Fig (5.11) Kilo 22 Bridge on Rahad canal

  • 7/27/2019 MSC OF IGs

    97/133

  • 7/27/2019 MSC OF IGs

    98/133

    83

    Fig (5.13) View no.2 of kilo 36 bridge

  • 7/27/2019 MSC OF IGs

    99/133

  • 7/27/2019 MSC OF IGs

    100/133

  • 7/27/2019 MSC OF IGs

    101/133

  • 7/27/2019 MSC OF IGs

    102/133

    87

  • 7/27/2019 MSC OF IGs

    103/133

    88

    CHAPTER VI

    CONCLUSIONS AND RECOMMENDATIONS

  • 7/27/2019 MSC OF IGs

    104/133

    89

    CHAPTER VI

    CONCLUSIONS AND RECOMMENDATIONS

    6.1 General

    It can be shown that from the views shown below that India is very

    famous in this field and has got an excellent experience on the small

    hydro power schemes and our country can benefit from it with mutual

    cooperation between Sudan and India.

    Fig (6.1) typical arrangement of canal fall small hydro power station

  • 7/27/2019 MSC OF IGs

    105/133

    91

    Fig (6.2) typical arrangement of small hydro power station

    Fig. (6.3) another typical arrangement of small hydro power plant

  • 7/27/2019 MSC OF IGs

    106/133

    9

    Fig (6.4) Kalmoni 200 kW SHP project near Guwahati in Assam

    6.2The advantages of the experience:

    The main advantage in this experience is that they succeeded to generate

    hydroelectric power using the small quantity of water and low head.

    And the disadvantages when considering the power obtained by means

    of synchronous generators is that:

  • 7/27/2019 MSC OF IGs

    107/133

    92

    1-They use the conventional type of turbines and this needs more civil

    work in the existing dams.

    2-The diversion canal increases the civil work.3-The conventional type using of governor system and excitation system

    so it increase the capital cost.4-As general it is noticed that the new civil work makes a high cost.

    5-Synchronization of small synchronous generators to the grid is very

    difficult and risky since the load sharing will not be proper (KW)

    between the machines and the grid and the reactive power sharing is

    also very difficult (KVAR) and might lead to failure of the small

    synchronous generators.

    But when we consider the induction generators we can see that the

    advantages of the induction generator were: simplicity of control

    apparatus, freedom from hunting, no exciter required, no synchronizing

    required, low fault currents, low cost, and subsequent general

    usefulness in later motor applications and that it is the most suitable

    electric machines for such an application.

    We are looking forward at future to get use of all our water resources in

    our new projects and existing ones and even for the seasonal streams

    and canals in all Sudan.

  • 7/27/2019 MSC OF IGs

    108/133

    93

    References:

    1-Power Engineering International magazine, June 2004.

    2-Jebel Aulia hydro matrix power station documents

    3-International Energy agent Report (Key issues in developing Renewable

    1997)

    4-http://grz.g.andritz.com/c/com2011/00/01/24/12429/1/1/2/345644646/hy-

    hydromatrix-en.pdf

    5-Presentation of small hydro power station done by the joint committee of

    NEC and MOI and Jazeera Board.

    (http://www.4shared.com/document/bwv2Mzhl/small_hydro.html)

    6-Indian experience with small hydro power station

    (http://www.mnre.gov.in/prog-smallhydro.htm)

    7- from a paper written by OTTO J. M. SMITH with the title (Generator

    Rating of Induction Motors) magazine AIEE magazine, volume69, 1950

    8-Electric Machinery Fundamentals. By Stephen J.Chapman

    http://www.mnre.gov.in/prog-smallhydro.htmhttp://www.mnre.gov.in/prog-smallhydro.htmhttp://www.mnre.gov.in/prog-smallhydro.htm
  • 7/27/2019 MSC OF IGs

    109/133

    A

    APPENDIX A3

    Theory of Poly- phase Induction Machines

    The analysis begins with the development of single-phase equivalent circuits.The general form is suggested by the similarity of an induction machine to a

    transformer.

    The equivalent circuits can be used to study the electromechanical

    characteristics of an induction machine as well as the loading presented by the

    machine on its supply source.

    1. Introduction to Poly phase Induction Machines

    An induction machine is one in which alternating current is supplied to the

    stator directly and to the rotor by induction or transformer action from the

    stator.

    The stator winding is excited from a balanced poly phase source and produces

    a magnetic field in the air gap rotating at synchronous speed.

    The rotor winding may one of two types.

    A wound rotor is built with a poly phase winding similar to, and wound with

    the same number of poles as, the stator. The rotor terminals are available

    external to the motor.

    A squirrel-cage rotor has a winding consisting of conductor bars embedded in

    slots in the rotor iron and short-circuited at each end buy conducting end

    rings. It is the most commonly used type of motor in sizes ranging from

    fractional horsepower on up.

    The difference between synchronous speed and the rotor speed is commonly

    referred to as the slip of the rotor. The fractional slip s is

    3Appendix Reference: Electric al Machinery and transformer_ Bhag S.G

  • 7/27/2019 MSC OF IGs

    110/133

    B

    s

    s

    n ns

    n

    (a .1)

    The slip is often expressed in percent.

    n : Rotor speed in rpm

    s

    nsn 1(a .2)

    m : Mechanical angular velocity

    sm s 1(a .3)

    rf : The frequency of induced voltages, the slip frequency

    r ef s f(a .4)

    A wound-rotor induction machine can be used as a frequency changer.

    The rotor currents produce an air-gap flux wave that rotates at synchronous

    speed and in synchronism with that produced by the stator currents.

    With the rotor revolving in the same direction of rotation as the stator field,

    the rotor currents produce a rotating flux wave rotating at ssn with respect to

    the rotor in the forward direction.

    With respect to the stator, the speed of the flux wave produced by the rotor

    currents (with frequency esf ) equals

    s s s s1sn n sn n s n (a .5)

    Because the stator and rotor fields each rotate synchronously, they are

    stationary with respect to each other and produce a steady torque, thusmaintaining rotation of the rotor. Such torque is called an asynchronous

    torque.

    (a .6)The torque equation2

    sr r r

    polessin

    2 2T F

  • 7/27/2019 MSC OF IGs

    111/133

    C

    can be expressed in the form

    r rsinT KI (a .7)

    rI: The rotor current

    r: The angle by which the rotor mmf wave leads the resultant air-gap mmf

    wave

    Fig.( a.4) shows a typical poly phase squirrel-cage induction motor torque-

    speed curve. The factors influencing the shape of this curve can be

    appreciated in terms of the torque

    equation.

    Figure (a .4) typical induction-motor torque-speeds

    Curve for constant-voltage, constant-frequency operation.

    Under normal running conditions the slip is small: 2 to 10 percent at full load.

    The maximum torque is referred to as the breakdown torque.

    The slip at which the peak torque occurs is proportional to the rotor

    resistance.

    2. Currents and Fluxes in Poly phase Induction Machines

  • 7/27/2019 MSC OF IGs

    112/133

    D

    2.3 Induction-Motor Equivalent Circuit

    Only machines with symmetric poly phase windings exited by balanced poly

    phase voltages are considered. It is helpful to think of three-phase machines

    as being Y-connected.

    Stator equivalent circuit:

    11121 jXRIEV (a .8)

    1

    2

    1

    1

    1

    Stator line-to-neutral terminal voltage

    Counter emf (line-to-neutral) generated by the resultant air-gap flux

    Stator current

    Stator effective resistance

    Stator leakage reactance

    V

    E

    I

    R

    X

    Figure (a.7) Stator equivalent circuits for a poly phase induction motor.

    Rotor equivalent circuit:

    2

    22

    I

    EZ (a.9)

    2 22s rotor 2s eff eff rotor

    2s rotor

    E EZ N N Z

    I I

    (a.10)

    2sZ: the slip-frequency leakage impedance of the equivalent rotor

  • 7/27/2019 MSC OF IGs

    113/133

    E

    rotorZ: the slip-frequency leakage impedance

    2s2s 2 2

    2s

    EZ R jsX

    I (a.11)

    2R= Referred rotor resistance

    2sR= Referred rotor leakage reactance at slip frequency

    2X= Referred rotor leakage reactance at stator frequency

    ef

    Figure (a.8) Rotor equivalent circuits for a poly phase induction motor at slip

    frequency.

    22 II s (a.12)

    22 sEE s (a.13)

    22

    EsEs

    (a.14)

    222

    2

    2

    2

    2

    jsXRZI

    Es

    I

    Es

    s

    s (a.15)

  • 7/27/2019 MSC OF IGs

    114/133

  • 7/27/2019 MSC OF IGs

    115/133

    G

    s

    sRInP

    12

    2

    2phmech(a.21)

    gapmech 1 PsP (a.22)

    rotor gapP sP(a.23)

    Of the total power delivered across the air gap to the rotor, the fraction 1 s is

    converted to mechanical power and the fraction s is dissipated as ohmic loss

    in the rotor conductors.

    When power aspects are to be emphasized, the equivalent circuit can be

    redrawn in the manner of Fig. 6.10.

    Figure a.10 Alternative form of equivalent circuit.

    Consider the electromechanical torque mechT .

    mechmechmech 1 TsTP sm (a.24)

    s

    sRInPP

    T

    /22

    2ph

    s

    gap

    m

    mech

    mech

    (a.25)

    ee

    s

    f

    poles

    2

    poles

    4(a.26)

    rotmechshaft PPP (a.27)

  • 7/27/2019 MSC OF IGs

    116/133

  • 7/27/2019 MSC OF IGs

    117/133

    I

    Figure a.13 Induction-motor equivalent circuits simplified by Thevenins

    theorem.

    m

    m

    XXjR

    jXVV

    11

    1eq1,(a.29)

    1,eq 1,eq 1,eq 1 1 in parallel with mZ R jX R jX jX (a.30)

    m

    m

    XXjR

    jXRXjVZ

    11

    111eq1,

    (a.31)

    sRjXZ

    VI

    /

    22eq1,

    eq,1

    2

    (a.32)

    2

    2eq1,

    2

    2eq1,

    2

    2

    eq1,ph

    mech/

    /1

    XXsRR

    sRVnT

    s(a.33)

    The general shape of the torque-speed or torque-slip curve with motor

    connected to a constant-voltage, constant-frequency source is shown in Figs.

    a.14 and a.15.

  • 7/27/2019 MSC OF IGs

    118/133

    J

    Figure a.14 Induction-machine torque-slip curve showing braking, motor, and

    generator regions.

  • 7/27/2019 MSC OF IGs

    119/133

    K

    Figure a.15 Computed torque, power, and current curves for the 7.5-kW

    motor in Exps a.2 and a.3.

    Maximum electromechanical torque will occur at a value of slipmaxTs for

    which

    2

    221,eq 1,eq 2

    maxT

    RR X X

    s (a.34)

    2

    maxT22

    1,eq 1,eq 2

    Rs

    R X X

    (a.35)

    2

    2eq1,

    2

    eq1,eq1,

    2eq1,

    max

    5.01

    XXRR

    VnT

    ph

    s(a.36)

    Figure a.16 Induction-motor torque-slip curves showing effect of changing

    rotor-circuit resistance.

    (a.5)Parameter Determination from No-Load and Blocked-Rotor Tests

  • 7/27/2019 MSC OF IGs

    120/133

    L

    The equivalent-circuit parameters needed for computing the performance of a

    poly-phase induction motor under load can be obtained from the results of a

    no-load test, a blocked-rotor test, and measurement of the dc resistances of

    the stator windings.

    a.6.1 No-Load Test:

    Like the open-circuit test on a transformer, the no-load test on an induction m

    otor gives information with respect to exciting current and no-load losses.

    a.6.2 Blocked-Rotor Test:

    Like the short-circuit test on a transformer, the blocked-rotor test on an induc

    tion motor give information with respect to the leakage impedances.

  • 7/27/2019 MSC OF IGs

    121/133

    M

    APPENDIX B

  • 7/27/2019 MSC OF IGs

    122/133

    N

    APPENDIX C

    SIMPLE KW MULTIPLIER FOR POWER FACTOR CORRECTION

    Known Variables: Capacitor Voltage and Capacitor Reactance

    KVAR = (2fc)(kv)2

    /1000

    =(kv)2/1000xc

    Known Variables: Capacitor Frequency, Capacitance, and Voltage Rating

    KVAR = (2fc)(kv)2

    /1000

    =(kv)2/1000xc

    Reference:

    http://www.nepsi.com/powerfactor.htm

  • 7/27/2019 MSC OF IGs

    123/133

    O

    APPENDIX D

    All the tests and experiments have been done at the faculty of engineering

    laboratory (electrical machines lab.)And the following devices and equipments

    are used with the following specifications:

    Ac induction motor

    The motor has got a serial number of 5/15145/290/4/1 and size KKS 3

    Power: 2 hp,Speed: 1430rpm, Phases : 3, Frequency: 50 Hz

    Voltage:282 v,Current:4.7 Ampere Connection : star

    CONT: RatingBs, Insulation class: E, Rotor: 115v current: 8.6 A

    The motor is a wound type one where we make it similar to the squirrel cage

    one by making short to the windings of the rotor through the slip ring and it is

    possible to run it by direct supply of 220 v(three phase supply obtained from

    delta side of the lab transformer.)

    DC MOTOR

    The DC motor is used as a prime mover with the following specifications:

    Serial number: 1324-16180, Type: LAP 132-4M

    Standard: IEC 34/1 -1969 and now it is IEC 60034/1, Speed: 2900 rpm

    Duty: S1, Insulation class: F , Armature voltage: 240 v dc

    Armature current: 25.8 A , Excitation voltage: 240 v dc

    Excitation current: 0.595 A, IP : 54, IC: 0011 ,IM :1.001

  • 7/27/2019 MSC OF IGs

    124/133

    P

    Weight: 145 Kg.

    UCTION MOTORDTHE 1 HP IN

    This motor is smaller in size and equivalent of one hp and can be operated byeither, 400 v or 230 v of 50 HZ by means of connection of either star or delta;

    it has got the following specifications:

    The motor name plate is SAER ELETTRO POMPE

    Type: HT4-B3-80, Serial number: 1997522, HZ =50

    Rated voltage: 240/400 (star/delta), Rated current: 3.6/2.1 A

    Speed: 1470 rpm, Power in kW: 0.75, or 1 hp

    APPARATUS

    The following meters were used for most of the testing and measurements and

    all of them were calibrated

    a- Power Quality Analyzer (Fluke434)

    b- AC/DC multi meter (Fluke 87)c- Clamp meter for ac current measurement

  • 7/27/2019 MSC OF IGs

    125/133

  • 7/27/2019 MSC OF IGs

    126/133

    R

    % The parameters are R1, X1, X2, R2, Xm, Vt, Ns

    % Assumed is a three-phase motor

    % -----------------------------------------------------

    --

    Functionsc;

    R1 =0.007932;

    X1 = 0.1283;

    R2 =0.03742;

    X2 =0.1283;

    Xm =1.6025;

    Vt =398.37;

    Ns =375;

    s = -1:0.003:1; % vector of slip

    N = Ns .* (1 - s); % Speed, in RPM

    oms = 2*pi*Ns/60; % Synchronous speed in rad/secRr = R2 ./ s; % Rotor resistance

    Zr = j*X2 + Rr; % Total rotor impedance

    Za = j*Xm.*Zr./(j*Xm + Zr); % Air-gap impedance

    Zt = R1 + j*X1 +Za; % Terminal impedance

    Ia = Vt ./Zt; % Terminal Current

    I2 = Ia .*j*Xm./(Zr + j*Xm); % Rotor Current

    Pag = 3 .* abs(I2) .^2 .* Rr; % Air-Gap Power

    Pm = Pag .* (1 - s); % Converted Power

    Trq = Pag ./oms; % Developed Torque

    plot(N, Trq);title('Induction Motor');

    ylabel('Torque (N-m)');

    xlabel('Speed (RPM)');

    gridon;

    % -----------------------------------------------------

    -% Power Factor-Speed Curve for an Induction Motor

    % The machine is 482,8-hp, 690-V, wye-connected, three-

    phase, 50-Hz, 16-pole, 375 rpm

    % The parameters (referred to the stator) are R1, X1,

    X2, R2, Xm,

  • 7/27/2019 MSC OF IGs

    127/133

  • 7/27/2019 MSC OF IGs

    128/133

  • 7/27/2019 MSC OF IGs

    129/133

    U

    s = -1:0.003:1; % vector of slip

    N = Ns .* (1 - s); % Speed, in RPM

    oms = 2*pi*Ns/60; % Synchronous speed in rad/sec

    Rr = R2 ./ s; % Rotor resistance

    Zr = j*X2 + Rr; % Total rotor impedance

    Za = j*Xm.*Zr./(j*Xm + Zr); % Air-gap impedance

    Zt = R1 + j*X1 +Za; % Terminal impedance

    Ia = Vt ./Zt; % Terminal Current

    I2 = Ia .*j*Xm./(Zr + j*Xm); % Rotor Current

    Pag = 3 .* abs(I2) .^2 .* Rr; % Air-Gap Power

    Pm = Pag .* (1 - s); % Converted Power

    Trq = Pag ./oms; % Developed Torque

    plot(N, Trq);

    title('Induction Motor');

    ylabel('Torque (N-m)');xlabel('Speed (RPM)');

    gridon;

    % -----------------------------------------------------

    -

    % ActivePower-Speed Curve for an Induction Motor

    % Assumes the classical model

    % This is a single-circuit model

    % The parameters are R1, X1, X2, R2, Xm, Vt, Ns% Assumed is a three-phase motor

    % -----------------------------------------------------

    --

    functionapsc;

    R1 =6.93;

    X1 =2.63;

    R2 =3.82;

    X2 =2.63;

    Xm =104.31;

    Vt =230/sqrt(3);Ns =1500;

    s = -1:0.003:1; % vector of slip

    N = Ns .* (1 - s); % Speed, in RPM

    Rr = R2 ./ s; % Rotor resistance

    Zr = j*X2 + Rr; % Total rotor impedance

    Za = j*Xm.*Zr./(j*Xm + Zr); % Air-gap impedance

  • 7/27/2019 MSC OF IGs

    130/133

    V

    Zt = R1 + j*X1 +Za; % Terminal impedance

    Ia = Vt ./Zt; % Terminal Current

    P =3.*real(Vt.*conj(Ia)); % Total injected active power

    plot(N,P);

    title('Induction Motor');

    ylabel('Active Power (Watts)');

    xlabel('Speed (RPM)');

    gridon;

    %supply parameters

    Vin = 230; %voltage

    % f = 50 % frequency

    % induction motor parameters

    Rs = 0.403;

    Xs = 0.740;

    Rr = 0.511;

    Xr = 0.740;

    Xm = 12.258;

    Ns = 1500;

    W = 2*pi*Ns/60;

    % 1st case when Slip is constant and Xc varies

    % S = -0.02; %-ve slip Generator mode

    % Zf = i * Xm * (i * Xr + Rr/S) / ( Rr/S + i * (Xm +

    Xr));% Xc = 0:0.1:50 ;%variable series cap.

    % Ztotal = Zf + Rs + i * (Xs - Xc);

    % I = abs(Vin * Ztotal.^-1);

    % ph = angle(Vin * Ztotal.^-1);

    % subplot(2,1,1), plot(Xc,I)

    % xlabel('Series Capacitance')

    % ylabel('Current Amplitude')

    % subplot(2,1,2), plot(Xc,ph)

    % xlabel('Series Capacitance')

    % ylabel('Current phase')Xc = 0.25; % Set here the best value of series cap.

    impedance value

    S = -1:0.002:1;%variable slip

    S(501) = 0.001;% avoid division by zero

    Zf = i * Xm * (i * (Xs-Xc)+Rs)/(Rs + i*(Xs+Xm-Xc));

    Ztotal = Zf + Rs * S.^-1 + i * Xr;

  • 7/27/2019 MSC OF IGs

    131/133

    W

    Vth = Vin * Xm/(Rs + i*(Xm +Xs - Xc));

    Ir = abs(Vth * Ztotal .^-1);

    T = 3* Rr*(Ir.^2 ./ S)/W ;

    plot(S,T)

    title('Induction motor Torque/Slip Curve')

    xlabel('Slip')

    ylabel('Torque')

    %supply parameters

    Vin = 230; %voltage

    % f = 50 % frequency

    % induction motor parameters

    Rs = 0.403;

    Xs = 0.740;

    Rr = 0.511;

    Xr = 0.740;

    Xm = 12.258;

    % 1st case when Slip is constant and Xc varies

    S = -0.02; %-ve slip Generator mode

    Zf = i * Xm * (i * Xr + Rr/S) / ( Rr/S + i * (Xm +

    Xr));

    Xc = 0:0.1:50 ;%variable series cap.

    Ztotal = Zf + Rs + i * (Xs - Xc);

    I = abs(Vin * Ztotal.^-1);ph = angle(Vin * Ztotal.^-1);

    subplot(2,1,1), plot(Xc,I)

    xlabel('Series Capacitance')

    ylabel('Current Amplitude')

    subplot(2,1,2), plot(Xc,ph)

    xlabel('Series Capacitance')

    ylabel('Current phase')

    % 2nd case when Xc is constant and S varies

    Xc = 0.5; % series cap. impedance value

    S = -1:0.02:-0.001;%variable slipZfn = i * Xm * (i * Xr + Rr* S.^-1);

    Zfd= Rr*S.^-1 + i * (Xm + Xr);

    Zf = Zfn ./Zfd;

    Ztotal = Zf + Rs + i * (Xs - Xc);

    I = abs(Vin * Ztotal.^-1);

    ph = angle(Vin * Ztotal.^-1);

  • 7/27/2019 MSC OF IGs

    132/133

  • 7/27/2019 MSC OF IGs

    133/133

    Pm = Pag .* (1 - s); % Converted Power

    Pin = 3.*real(Vt.*conj(Ia)); % Total injected active

    power

    E = 100.*Pm./Pin; % Efficiency

    plot(N,E);

    title('Induction Motor');

    ylabel('Efficiency (%)');

    xlabel('Speed (RPM)');

    grid on;