Insight ™

Ducted Air HandlerProduct Data

Heat Pump Split System Air Conditioning

30 to 50 MBh - 50 Hz

TWE-PRC001-EN-10-15-99

Air Handler ModelsTWE030CATWE040CATWE050CA

Condensing ModelsTWJ020-036CATWA030-060CD

Page 2: Multi Pos

©American Standard Inc. 1999 TWE5-PRC001-EN-10-15-99

Features andBenefits

TWATWJ

TWE

Air Handling Units

Condensing Units

Benefits:• Flexibility in application• Quality and reliability• Uniform covering for a smooth, attractive

and corrosion-resistant finish

New Features• Improved filter access and latch -

Eliminate current T-bar and shippingbracket.

• Provision for 1-1/8 inches thick fieldsupplied electrostatic filter

• Reversible Duct Flanges - Fits up to1-1/2 inches duct board

• Improve controls access with controlbox mounted next to blower.

• 40 VA transformer with 5 amp automo-tive style fuse on 3 tons and less

• 5 Amp automotive style fuse replacesBussman “red cap” fuse on 3.5 to 5 tonmodels

• Blower mounting brackets improved -Front access to screw with power driver

• Improved bottom carton cushioning• 1 inch thick foil faced insulation for all

models

Features• Ships horizontal

• Six way convertibility-horizontal (left andright), upflow, downflow (front and rearaccess)

• Electrical, refrigerant, condensate andblower access convertible to either side

• Corrosion resistant galvanized steelwith attractive finish

• Internally enhanced finned coil tubes• Direct drive motor

• Standard filters• Multi-speed blower• 220 volt primary and 24 volt secondary

transformer• Insulated cabinet• External access to heater circuit

breakers• Start kits are not required• Built-in indoor fan delay function for

increased efficiency. No kit required.

Features:• Vertical Air Discharge• High Efficiency TRANE Climatuff®

Compressor• Powder Paint finish• Brazed connections

• Spine Fin™ Outdoor Coil• Switchover Valves

Page 3: Multi Pos

TWE5-PRC001-EN-10-15-99 3

Contents

Features and Benefits 2Air Handling Units 2Condensing Units 2

System Performance 4

Selection Procedure 4Model Number Nomenclature 4

General Data 5TWE030CA40B 5TWE040CA40C 5TWE050CA50D 5TWJ020CA00A0 6TWJ024CA00A0 6TWJ030CA00A0 6TWJ036CA00A0 6TWA030CD00A0 7TWA040CD00A0 7TWA050CD00A0 7TWA060CD00A0 7

Performance Data 8TWJ/TWE Cooling 8TWA/TWE Cooling 12TWJ/TWE Heating 16TWA/TWE Heating 20Evaporator Fan Performance 24Air Pressure Drop 26

Supplementary Heaters 27

Electrical Data 28

Dimensions 29

Convertibility 31

Mechanical Specification Options 32

Page 4: Multi Pos

4 TWE5-PRC001-EN-10-15-99

PRODUCT TYPETW = Split System Component

Heat Pump Compatible

AIRFLOW CONFIGURATIONE = Convertible

REFRIGERANT CONNECTIONS0 = Brazed

NOMINAL NET COOLINGCAPACITY30 = 30 MBh40 = 40 MBh50 = 50 MBh

MAJOR DESIGN MODIFICATION

PRODUCTSERVICE CHANGE

MINOR DESIGNMODIFICATION

NOT USED

REFRIGERANT FLOW CONTROL4 = Accutron™ Flow Control/Check Valve5 = Bleed TXV

ELECTRICAL CHARACTERISTICSA = 220V/1/50

SystemPerformance

Model Number Nomenclature

SelectionProcedure

1 2 3 4 5 6 7 8 9 10 11 12

T W E 0 3 0 C A 4 0 A 0

Cooling Capacity95° F (35° C)

Outdoor Unit Indoor Unit CFM CMH MBh Kw Ducted Air HandlersTWJ020CA00A TWE030CA00A 700 1185 20 6TWJ024CA00A TWE030CA00A 900 1520 27 8TWJ030CA00A TWE030CA00A 1000 1690 31 9TWJ030CA00A TWE040CA00A 1100 1860 33 9.5TWJ036CA00A TWE030CA00A 1100 1860 38 11TWJ036CA00A TWE040CA00A 1325 2240 40.5 11.5TWJ036CA00A TWE050CA00A 1400 2360 41.6 12TWA030CD00A TWE030CA00A 1000 1690 32 9TWA030CD00A TWE040CA00A 1100 1860 34 9.6TWA040CD00A TWE040CA00A 1300 2200 42 12TWA040CD00A TWE050CA00A 1500 2535 43 12.5TWA050CD00A TWE050CA00A 1800 3040 51 14.5TWA060CD00A TWE050CA00A 1800 3040 63 18

Page 5: Multi Pos

TWE5-PRC001-EN-10-15-99 5

GeneralData TWE

TWE Product SpecificationsModel TWE030CA40B TWE040CA40C TWE050CA50DPower Conn.— Volts/Ph/Hz 220/1/50 220/1/50 220/1/50Indoor Coil - Type Plate Fin Plate Fin Plate Fin

Rows 3 3 3Fins per inch (Fins per 25.4 mm) 14 14 14Face Area sq ft (sq m) 3.21 (.30) 5.04 (.47) 6.19 (.58)Tube Size in. (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)Refrigerant Control FCCV FCCV FCCVDrain Conn. Size in. (mm) 3/4 NPT 3/4 NPT 3/4 NPTDuct Connections See Outline Drawing See Outline Drawing See Outline Drawing

Indoor Fan - Type Centrifugal Centrifugal CentrifugalNo. Used 1 1 1Diameter in. (mm) 10.0 (254.0) 10.0 (254.0) 11.0 (279.4)Width in. (mm) 8.0 (203.2) 10.0 (254.0) 10.0 (254.0)Type Drive - No. Speeds Direct - 3 Direct - 3 Direct - 3Airflow (High)

CFM @ 0.0 in. w.g. See Fan Performance Table See Fan Performance Table See Fan Performance TableCMH @ 0.0 Pa See Fan Performance Table See Fan Performance Table See Fan Performance Table

No. Motors - HP 1 - 1/3 1 - 1/3 1 - 3/4Motor RPM 1000 900 900Volts/Ph/Hz 220/1/50 220/1/50 220/1/50F.L. Amps 2.6 2.1 4.5L.R. Amps 3.3 4.2 10.1

FiltersVertical Applications

Filter Furnished Yes Yes YesType Furnished Throwaway Throwaway High VelocityNo.-Size-Thickness 1 - 20 x 20 - 1 1 - 20 x 20 - 1 1 - 2 2 x 20 - 1

Horizontal ApplicationsFilter Furnished No No NoType Recommended See Note Below See Note Below See Note BelowNo.-Size-Thickness See Note Below See Note Below See Note Below

Refrigerant Line SizeLine Size ID Gas in. (mm) 7/8 (22.23) 1-1/8 (28.56) 1-1/8 (28.56)Line Size ID Liquid in. (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)

Dimensions (H x W x D)Crated - in. 44.5 x 24.0 x 23.5 53.25 x 26.0 x 23.5 59.5 x 26.0 x 23.5

- (mm) (1130 x 610 x 597) (1353 x 660 x 597) (1511 x 660 x 597)Uncrated - in. 43.0 x 21.5 x 21.0 52.0 x 23.5 x 21.0 58.0 x 23.5 x 21.0

- (mm) (1092 x 546 x 533) (1321 x 597x 533) (1473 x 597 x 533)Weight Ibs. (kg)

Shipping 125 (56.7) 165 (74.8) 198 (898)Net 115 (52.2) 150 (68.0) 183 (83.0)

Minimum filter size for horizontal applications based on airflow selection and calculated as follows:Low Velocity Filter: Face Area (sq ft) = CFM/300High Velocity Filter: Face Area (sq ft) = CFM/500

Page 6: Multi Pos

6 TWE5-PRC001-EN-10-15-99

TWJ Product Specifications 12

ModelPower Conn. - Volts/Ph/Hz

Fuse Size - max. ampsCompressor - Type

No. Used - No. SpeedsVolts/Ph/HzF.L. Amps - L.R. Amps

Outdoor Fan - TypeNo. UsedDiameter in. (mm)Type Drive - No. Speeds

CFM @ 0.0 in. w.g. 3(M) 3/HR. @ 0.0 mm w.g. 3

No. Motors - HPMotor Speed (RPM)Volts/Ph/HzF.L. Amps

Outdoor Coil - TypeNo. RowsFins/in. (mm)Face Area sq ft (sq m)Tube Size in. (mm)

RefrigerantR-22 (O.D. Unit) 4 - lbs. (kg)Factory SuppliedLine Size - OD Gas 5 in. (mm)Line Size - OD Liq. 5 in. (mm)

FCCVRestrictor Orifice Size in. (mm)

Dimensions (H x W x D)Crated - in.

- (mm)Uncrated

Weight lbs. (kg) Shipping Net

NOTES:1 RATING CONDITIONS (COOLING): 80F (27C) D.B. 67F (20C) W.B. ENTERING AIR TO INDOOR COIL OF APPLICABLE TYPE.

95F (35C) D.B. ENTERING AIR TO OUTDOOR COIL.INDOOR COIL AND UNIT CONNECTED BY 25 FT. (7.62 METERS) TUBING.

2 RATING CONDITIONS (HEATING): 70F (21C) D.B. ENTERING AIR TO INDOOR COIL; 47F (8C) D.B.43F (6C) W.B. ENTERING AIR TO OUTDOOR COIL.NO SUPPLEMENTARY HEAT INCLUDED.

3 STANDARD AIR - DRY COIL - OUTDOOR4 THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT NAMEPLATE AND SERVICE INSTRUCTIONS.5 MAX. OF 80 FT. (24.38 METERS) TOTAL MEASURED LENGTH INCLUDING 60 FT. (18.29 METERS) MAX. LIFT BETWEEN O.D. AND I.D. SECTIONS.

GeneralData TWJ

TWJ020CA00A0200/230/1/60

PER LOCAL CODESCLIMATUFF®

1 - 1200/230/1/50

10 - 60PROPELLER

118 (457)

DIRECT - 11503709

1 - 1/8690

200/230/1/60/500.90

SPINE FIN™1

24 (.945)12.22 (1.14)3/8 (9.52)

5 LBS., 4 OZ (2.38)YES

3/4 (19.1)5/16 (7.94)

0.051 (1.30)

25 X 26-1/2 X 30(635 X 673 X 762)

SEE OUTLINE DRAWINGS

170 (77.1)162 (73.5)

TWJ024CA00A0200/230/1/60

PER LOCAL CODESCLIMATUFF®

1 - 1200/230/1/50

17.9 - 69PROPELLER

118 (457)

DIRECT - 11987938

1 - 1/51075

200/230/1/501.60

SPINE FIN™1

24 (.945)16.84 (1.56)3/8 (9.52)

4 LBS, 13 OZ. (2.18)YES

3/4 (19.1)5/16 (7.94)

0.061 (1.55)

33-1/4 X 30 X 26-1/2(845 X 762 X 673)

SEE OUTLINE DRAWINGS

187 (84.8)178 (80.7)

TWJ030CA00A0200/230/1/60

PER LOCAL CODESCLIMATUFF®

1 - 1200/230/1/50

19 - 94PROPELLER

118 (457)

DIRECT - 11975932

1 - 1/5900

200/230/1/60/501.60

SPINE FIN™1

24 (.945)16.84 (1.56)3/8 (9.52)

6 LBS., 12 OZ. (3.06)YES

7/8 (22.2)3/8 (9.52)

0.065 (1.65)

33-1/4 X 26-1/2 X 30(845 X 673 X 762)

SEE OUTLINE DRAWINGS

214 (97.1)205 (93.0)

TWJ036CA00A0200/230/1/60

PER LOCAL CODESCLIMATUFF®

1 - 1200/230/1/60/50

21.9 - 95PROPELLER

122 (559)

DIRECT - 1274812971 - 1/4900

200/230/1/501.40

SPINE FIN™1

24 (.945)23.11 (2.15)3/8 (9.52)

8 LBS., 2 OZ. (3.69)YES

7/8 (22.2)3/8 (9.52)

0.073 (1.85)

37-1/2 X 34-3/4 X 30-1/2(953 X 883 X 775)

SEE OUTLINE DRAWINGS

252 (114)238 (108)

Page 7: Multi Pos

TWE5-PRC001-EN-10-15-99 7

GeneralData TWA

TWA Product Specifications 12

ModelPower Conn. - Volts/Ph/Hz

Fuse Size - max. ampsCompressor - Type

No. Used - No. SpeedsVolts/Ph/HzF.L. Amps - L.R. Amps

Outdoor Fan - TypeNo. UsedDiameter in. (mm)Type Drive - No. Speeds

CFM @ 0.0 in. w.g. 3(M) 3/HR. @ 0.0 mm w.g. 3

No. Motors - HPMotor Speed (RPM)Volts/Ph/HzF.L. Amps

Outdoor Coil - TypeNo. RowsFins/in. (mm)Face Area sq ft (sq m)Tube Size in. (mm)

RefrigerantR-22 (O.D. Unit) 4 - lbs. (kg)Factory SuppliedLine Size - OD Gas 5 in. (mm)Line Size - OD Liq. 5 in. (mm)

FCCVRestrictor Orifice Size in. (mm)

Dimensions (H x W x D)Crated - in.

- (mm)Uncrated

Weight lbs. (kg) Shipping Net

NOTES:1 RATING CONDITIONS (COOLING): 80F (27C) D.B. 67F (20C) W.B. ENTERING AIR TO INDOOR COIL OF APPLICABLE TYPE.

95F (35C) D.B. ENTERING AIR TO OUTDOOR COIL.INDOOR COIL AND UNIT CONNECTED BY 25 FT. (7.62 METERS) TUBING.

2 RATING CONDITIONS (HEATING): 70F (21C) D.B. ENTERING AIR TO INDOOR COIL; 47F (8C) D.B.43F (6C) W.B. ENTERING AIR TO OUTDOOR COIL.NO SUPPLEMENTARY HEAT INCLUDED.

3 STANDARD AIR - DRY COIL - OUTDOOR4 THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT NAMEPLATE AND SERVICE INSTRUCTIONS.5 MAX. OF 80 FT. (24.38 METERS) TOTAL MEASURED LENGTH INCLUDING 60 FT. (18.29 METERS) MAX. LIFT BETWEEN O.D. AND I.D. SECTIONS.

TWA030CD00A0380/415/3/60

PER LOCAL CODESCLIMATUFF®

1 - 1380/415/3/50

5 - 51PROPELLER

118 (457)

DIRECT - 11976933

1 - 1/41075/900

460/1/60/500.80

SPINE FIN™1

24 (.945)16.84 (1.56)3/8 (9.52)

6 LBS.,12 OZ. (3.06)YES

7/8 (22.2)3/8 (9.52)

0.065 (1.65)

33-1/4 X 30 X 26-1/2(845 X 762 X 673)

SEE OUTLINE DRAWINGS

219 (99.3)210 (95.3)

TWA040CD00A0380/415/3/60

PER LOCAL CODESCLIMATUFF®

1 - 1380/415/3/50

7 - 51PROPELLER

122 (559)

DIRECT - 1273812921 - 1/3

825/690460/1/60/50

1.0SPINE FIN™

124 (.945)

20.32 (1.89)3/8 (9.52)

8 LBS.,13 OZ. (4.00)YES

1-1/8 (3.18)3/8 (9.52)

0.075 (1.91)

33-1/4 X 34-3/4 X 30-1/2(845 X 883 X 775)

SEE OUTLINE DRAWINGS

251 (114)239 (108)

TWA050CD00A0380/415/3/60

PER LOCAL CODESCLIMATUFF®

1 - 1380/415/3/50

9 - 71PROPELLER

126 (660)

DIRECT - 1314114821 - 1/3

825/690460/1/60/50

1.0SPINE FIN™

124 (.945)

28.91 (2.69)3/8 (9.52)

10 LBS.,9 OZ. (4.79)YES

1-1/8 (3.18)3/8 (9.52)

0.086 (2.18)

37-1/2 X 40-3/4 X 36-1/2(953 X 1035 X 927)

SEE OUTLINE DRAWINGS

308 (140)293 (133)

TWA060CD00A0380/415/3/60

PER LOCAL CODESCLIMATUFF®

1 - 1380/415/3/50

10.6 - 64PROPELLER

126 (660)

DIRECT - 1393118551 - 1/3825

460/1/60/501.7

SPINE FIN™2

24 (.945)35.39 (3.29)3/8 (9.52)

16 LBS.,12 OZ. (7.60)YES

1-1/8 (3.18)3/8 (9.52)

0.086 (2.18)

45-1/2 X 41 X 37(1156 X 1041 X 940)

SEE OUTLINE DRAWINGS

395 (179)376 (171)

Page 8: Multi Pos

8 TWE5-PRC001-EN-10-15-99

PerformanceData Cooling English Units

TWJ020CA WITH TWE030CA4 AT 700 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 72 74 76 78 80 KW

59 18.2 15.5 16.7 18.0 18.6* 19.1* 1.3485 63 19.7 13.0 14.3 15.5 16.8 18.1 1.39

67 21.2 10.3 11.6 12.8 14.1 15.4 1.4471 22.7 7.5 8.8 10.1 11.3 12.6 1.4959 17.9 15.3 16.6 17.8 18.4* 18.8* 1.40

90 63 19.3 12.8 14.1 15.4 16.7 17.9 1.4567 20.8 10.1 11.4 12.7 13.9 15.2 1.5071 22.3 7.4 8.6 9.9 11.2 12.4 1.5559 17.5 15.2 16.4 17.6* 18.1* 18.5* 1.46

95 63 18.9 12.7 14.0 15.2 16.5 17.8 1.5167 20.4 10.0 11.3 12.5 13.8 15.1 1.5671 21.9 7.2 8.5 9.8 11.0 12.3 1.6259 17.0 15.0 16.2 17.2* 17.7* 18.1* 1.53

100 63 18.4 12.5 13.8 15.0 16.3 17.6 1.5867 19.8 9.8 11.0 12.3 13.6 14.9 1.6371 21.3 7.0 8.3 9.5 10.8 12.1 1.6859 16.5 14.7 16.0 16.8* 17.3* 17.7* 1.59

105 63 17.9 12.3 13.6 14.8 16.1 17.4 1.6467 19.2 9.6 10.8 12.1 13.4 14.6 1.7071 20.7 6.8 8.1 9.3 10.6 11.9 1.7559 15.6 14.3 15.6* 16.0* 16.4* 16.9* 1.72

115 63 16.8 11.9 13.1 14.4 15.7 16.9* 1.7867 18.1 9.2 10.4 11.7 13.0 14.2 1.8371 19.4 6.4 7.7 8.9 10.2 11.5 1.89

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 625 800TOTAL CAP. X0.99 X1.01SENS. CAP. X0.95 X1.06COMPR. KW X0.99 X1.01

VALUES AT 95/80/67 RATING CONDITIONS

GROSS CAPACITY = 20400 BTUHAIRFLOW = 700 CFMCOMPRESSOR POWER = 1562 WATTSI.D. FAN POWER = 310 WATTSO.D. FAN POWER = 130 WATTSS.E.E.R. = 10.30 BTUH/WATTE.E.R. = 9.50 BTUH/WATT

NOTE:RATED WITH 25 FEET OF 3/4 SUCT.AND 5/16 LIQUID LINE

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

TWJ024CA WITH TWE030CA4 AT 900 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 72 74 76 78 80 KW

59 24.2 19.7 21.3 22.9 24.3* 24.9* 1.9285 63 26.0 16.7 18.3 19.8 21.4 23.0 1.98

67 28.0 13.3 14.9 16.5 18.0 19.6 2.0571 30.0 9.9 11.5 13.0 14.6 16.2 2.1259 23.8 19.6 21.1 22.7 24.0* 24.6* 2.01

90 63 25.6 16.5 18.1 19.7 21.2 22.8 2.0867 27.5 13.2 14.7 16.3 17.9 19.4 2.1471 29.5 9.7 11.3 12.8 14.4 16.0 2.2159 23.4 19.4 21.0 22.5 23.7* 24.3* 2.10

95 63 25.2 16.4 17.9 19.5 21.0 22.6 2.1767 27.1 13.0 14.5 16.1 17.7 19.2 2.2471 29.0 9.5 11.1 12.7 14.2 15.8 2.3159 22.8 19.2 20.7 22.3 23.2* 23.8* 2.21

100 63 24.6 16.1 17.7 19.2 20.8 22.4 2.2767 26.4 12.7 14.3 15.9 17.4 19.0 2.3471 28.3 9.3 10.9 12.4 14.0 15.6 2.4159 22.2 18.9 20.5 22.0 22.8* 23.3* 2.31

105 63 24.0 15.9 17.4 19.0 20.6 22.1 2.3767 25.7 12.5 14.1 15.6 17.2 18.8 2.4471 27.6 9.0 10.6 12.2 13.7 15.3 2.5159 21.1 18.4 20.0 21.3* 21.8* 22.4* 2.52

115 63 22.7 15.4 16.9 18.5 20.1 21.6 2.5867 24.4 12.0 13.6 15.1 16.7 18.3 2.6571 26.2 8.6 10.1 11.7 13.3 14.8 2.71

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 800 1025TOTAL CAP. X0.99 X1.01SENS. CAP. X0.95 X1.06COMPR. KW X0.99 X1.01

VALUES AT 95/80/67 RATING CONDITIONS

GROSS CAPACITY = 27100 BTUHAIRFLOW = 900 CFMCOMPRESSOR POWER = 2239 WATTSI.D. FAN POWER = 430 WATTSO.D. FAN POWER = 180 WATTSE.E.R. = 8.90 BTUH/WATT

NOTE:RATED WITH 25 FEET OF 3/4 SUCT.AND 5/16 LIQUID LINE

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

TWJ030CA WITH TWE030CA4 AT 1000 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 72 74 76 78 80 KW

59 29.0 22.8 24.5 26.2 28.0 29.3* 2.5785 63 31.2 19.4 21.2 22.9 24.6 26.3 2.66

67 33.5 15.7 17.4 19.2 20.9 22.6 2.7571 35.8 11.9 13.6 15.3 17.1 18.8 2.8559 28.5 22.6 24.3 26.0 27.7 28.9* 2.69

90 63 30.6 19.2 20.9 22.7 24.4 26.1 2.7867 32.9 15.5 17.2 18.9 20.7 22.4 2.8871 35.2 11.7 13.4 15.1 16.9 18.6 2.9759 28.0 22.3 24.1 25.8 27.5 28.5* 2.82

95 63 30.1 19.0 20.7 22.4 24.2 25.9 2.9167 32.3 15.3 17.0 18.7 20.4 22.2 3.0071 34.6 11.5 13.2 14.9 16.6 18.4 3.1059 27.3 22.1 23.8 25.5 27.2 28.0* 2.95

100 63 29.4 18.7 20.4 22.1 23.9 25.6 3.0467 31.5 15.0 16.7 18.4 20.1 21.9 3.1371 33.8 11.2 12.9 14.6 16.3 18.1 3.2359 26.6 21.8 23.5 25.2 26.8* 27.4* 3.08

105 63 28.7 18.4 20.1 21.9 23.6 25.3 3.1767 30.8 14.7 16.4 18.1 19.9 21.6 3.2671 32.9 10.9 12.6 14.3 16.1 17.8 3.3659 25.3 21.2 22.9 24.6 25.7* 26.3* 3.35

115 63 27.2 17.8 19.6 21.3 23.0 24.7 3.4367 29.2 14.1 15.8 17.6 19.3 21.0 3.5271 31.3 10.3 12.0 13.8 15.5 17.2 3.62

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 875 1125TOTAL CAP. X0.98 X1.01SENS. CAP. X0.95 X1.05COMPR. KW X0.99 X1.01

VALUES AT 95/80/67 RATING CONDITIONS

GROSS CAPACITY = 32400 BTUHAIRFLOW = 1000 CFMCOMPRESSOR POWER = 3002 WATTSI.D. FAN POWER = 440 WATTSO.D. FAN POWER = 195 WATTSE.E.R. = 8.30 BTUH/WATT

NOTE:RATED WITH 25 FEET OF 7/8 SUCT.AND 3/8 LIQUID LINE

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

Page 9: Multi Pos

TWE5-PRC001-EN-10-15-99 9

PerformanceData Cooling Metric Units

TWJ020CA WITH TWE030CA4 AT 1189 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 5.3 4.5 4.9 5.3 5.4* 5.6* 1.329.4 17.2 5.8 3.8 4.2 4.5 4.9 5.3 1.4

19.4 6.2 3.0 3.4 3.8 4.1 4.5 1.421.7 6.7 2.2 2.6 3.0 3.3 3.7 1.515.0 5.2 4.5 4.9 5.2 5.4* 5.5* 1.4

32.2 17.2 5.7 3.8 4.1 4.5 4.9 5.2 1.519.4 6.1 3.0 3.3 3.7 4.1 4.5 1.521.7 6.5 2.2 2.5 2.9 3.3 3.6 1.515.0 5.1 4.5 4.8 5.2* 5.3* 5.4* 1.5

35.0 17.2 5.5 3.7 4.1 4.5 4.8 5.2 1.519.4 6.0 2.9 3.3 3.7 4.0 4.4 1.621.7 6.4 2.1 2.5 2.9 3.2 3.6 1.615.0 5.0 4.4 4.7 5.0* 5.2* 5.3* 1.5

37.8 17.2 5.4 3.7 4.0 4.4 4.8 5.2 1.619.4 5.8 2.9 3.2 3.6 4.0 4.4 1.621.7 6.2 2.1 2.4 2.8 3.2 3.5 1.715.0 4.8 4.3 4.7 4.9* 5.1* 5.2* 1.6

40.6 17.2 5.2 3.6 4.0 4.3 4.7 5.1 1.619.4 5.6 2.8 3.2 3.5 3.9 4.3 1.721.7 6.1 2.0 2.4 2.7 3.1 3.5 1.815.0 4.6 4.2 4.6* 4.7* 4.8* 5.0* 1.7

46.1 17.2 4.9 3.5 3.8 4.2 4.6 5.0* 1.819.4 5.3 2.7 3.0 3.4 3.8 4.2 1.821.7 5.7 1.9 2.3 2.6 3.0 3.4 1.9

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1061 1358TOTAL CAP. X0.99 X1.01SENS. CAP. X0.95 X1.06COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 5.98 KWAIRFLOW = 1189 CMHCOMPRESSOR POWER = 1562 WATTSI.D. FAN POWER = 310 WATTSO.D. FAN POWER = 130 WATTSS.E.E.R. = 10.30 BTUH/WATTE.E.R. = 9.50 BTUH/WATT

NOTE:RATED WITH 7.62 METERS OF 19 MM SUCT.AND 8 MM LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

TWJ024CA WITH TWE030CA4 AT 1528 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 7.1 5.8 6.2 6.7 7.1* 7.3* 1.929.4 17.2 7.6 4.9 5.4 5.8 6.3 6.7 2.0

19.4 8.2 3.9 4.4 4.8 5.3 5.7 2.021.7 8.8 2.9 3.4 3.8 4.3 4.7 2.115.0 7.0 5.7 6.2 6.7 7.0* 7.2* 2.0

32.2 17.2 7.5 4.8 5.3 5.8 6.2 6.7 2.119.4 8.1 3.9 4.3 4.8 5.2 5.7 2.121.7 8.6 2.8 3.3 3.8 4.2 4.7 2.215.0 6.9 5.7 6.2 6.6 6.9* 7.1* 2.1

35.0 17.2 7.4 4.8 5.2 5.7 6.2 6.6 2.219.4 7.9 3.8 4.2 4.7 5.2 5.6 2.221.7 8.5 2.8 3.3 3.7 4.2 4.6 2.315.0 6.7 5.6 6.1 6.5 6.8* 7.0* 2.2

37.8 17.2 7.2 4.7 5.2 5.6 6.1 6.6 2.319.4 7.7 3.7 4.2 4.7 5.1 5.6 2.321.7 8.3 2.7 3.2 3.6 4.1 4.6 2.415.0 6.5 5.5 6.0 6.4 6.7* 6.8* 2.3

40.6 17.2 7.0 4.7 5.1 5.6 6.0 6.5 2.419.4 7.5 3.7 4.1 4.6 5.0 5.5 2.421.7 8.1 2.6 3.1 3.6 4.0 4.5 2.515.0 6.2 5.4 5.9 6.2* 6.4* 6.6* 2.5

46.1 17.2 6.7 4.5 5.0 5.4 5.9 6.3 2.619.4 7.1 3.5 4.0 4.4 4.9 5.4 2.721.7 7.7 2.5 3.0 3.4 3.9 4.3 2.7

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1358 1741TOTAL CAP. X0.99 X1.01SENS. CAP. X0.95 X1.06COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 7.94 KWAIRFLOW = 1528 CMHCOMPRESSOR POWER = 2239 WATTSI.D. FAN POWER = 430 WATTSO.D. FAN POWER = 180 WATTSE.E.R. = 8.90 BTUH/WATT

NOTE:RATED WITH 7.62 METERS OF 19 MM SUCT.AND 8 MM LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

TWJ030CA WITH TWE030CA4 AT 1698 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 8.5 6.7 7.2 7.7 8.2 8.6* 2.629.4 17.2 9.1 5.7 6.2 6.7 7.2 7.7 2.7

19.4 9.8 4.6 5.1 5.6 6.1 6.6 2.821.7 10.5 3.5 4.0 4.5 5.0 5.5 2.815.0 8.4 6.6 7.1 7.6 8.1 8.5* 2.7

32.2 17.2 9.0 5.6 6.1 6.7 7.1 7.6 2.819.4 9.6 4.5 5.0 5.5 6.1 6.6 2.921.7 10.3 3.4 3.9 4.4 5.0 5.4 3.015.0 8.2 6.5 7.1 7.6 8.1 8.4* 2.8

35.0 17.2 8.8 5.6 6.1 6.6 7.1 7.6 2.919.4 9.5 4.5 5.0 5.5 6.0 6.5 3.021.7 10.1 3.4 3.9 4.4 4.9 5.4 3.115.0 8.0 6.5 7.0 7.5 8.0 8.2* 3.0

37.8 17.2 8.6 5.5 6.0 6.5 7.0 7.5 3.019.4 9.2 4.4 4.9 5.4 5.9 6.4 3.121.7 9.9 3.3 3.8 4.3 4.8 5.3 3.215.0 7.8 6.4 6.9 7.4 7.9* 8.0* 3.1

40.6 17.2 8.4 5.4 5.9 6.4 6.9 7.4 3.219.4 9.0 4.3 4.8 5.3 5.8 6.3 3.321.7 9.6 3.2 3.7 4.2 4.7 5.2 3.415.0 7.4 6.2 6.7 7.2 7.5* 7.7* 3.3

46.1 17.2 8.0 5.2 5.7 6.2 6.7 7.2 3.419.4 8.6 4.1 4.6 5.2 5.7 6.2 3.521.7 9.2 3.0 3.5 4.0 4.5 5.0 3.6

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1486 1910TOTAL CAP. X0.98 X1.01SENS. CAP. X0.95 X1.05COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 9.49 KWAIRFLOW = 1698 CMHCOMPRESSOR POWER = 3002 WATTSI.D. FAN POWER = 440 WATTSO.D. FAN POWER = 195 WATTSE.E.R. = 8.30 BTUH/WATT

NOTE:RATED WITH 7.62 METERS OF 22 MM SUCT.AND 9.5 MM LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

Page 10: Multi Pos

10 TWE5-PRC001-EN-10-15-99

PerformanceData Cooling English Units

TWJ030CA WITH TWE040CA4-B AT 1100 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 72 74 76 78 80 KW

59 30.7 25.1 27.1 29.1 31.0* 31.6* 2.6585 63 33.0 21.2 23.2 25.2 27.2 29.2 2.75

67 35.3 16.9 18.9 20.9 22.9 24.9 2.8471 37.7 12.5 14.5 16.5 18.5 20.4 2.9459 30.1 24.9 26.9 28.9 30.5* 31.2* 2.78

90 63 32.3 21.0 22.9 24.9 26.9 28.9 2.8767 34.6 16.6 18.6 20.6 22.6 24.6 2.9771 37.0 12.2 14.2 16.2 18.2 20.2 3.0759 29.5 24.6 26.6 28.6 30.0* 30.7* 2.91

95 63 31.7 20.7 22.7 24.7 26.7 28.7 3.0067 33.9 16.4 18.4 20.4 22.3 24.3 3.1071 36.2 12.0 14.0 15.9 17.9 19.9 3.2059 28.8 24.3 26.3 28.3 29.3* 30.0* 3.04

100 63 30.9 20.4 22.4 24.3 26.3 28.3 3.1367 33.0 16.0 18.0 20.0 22.0 24.0 3.2371 35.3 11.6 13.6 15.6 17.6 19.6 3.3359 28.0 24.0 26.0 27.9 28.7* 29.4* 3.17

105 63 30.0 20.0 22.0 24.0 26.0 28.0 3.2767 32.1 15.7 17.7 19.7 21.7 23.7 3.3671 34.3 11.3 13.3 15.3 17.3 19.3 3.4659 26.5 23.3 25.3 26.8* 27.4* 28.1* 3.45

115 63 28.4 19.4 21.4 23.4 25.4 27.3 3.5467 30.4 15.1 17.1 19.0 21.0 23.0 3.6371 32.4 10.7 12.7 14.6 16.6 18.6 3.73

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 975 1275TOTAL CAP. X0.98 X1.02SENS. CAP. X0.95 X1.07COMPR. KW X0.99 X1.01

VALUES AT 95/80/67 RATING CONDITIONS

GROSS CAPACITY = 34100 BTUHAIRFLOW = 1125 CFMCOMPRESSOR POWER = 3104 WATTSI.D. FAN POWER = 300 WATTSO.D. FAN POWER = 195 WATTSE.E.R. = 9.05 BTUH/WATT

NOTE:RATED WITH 25 FEET OF 7/8 SUCT.AND 3/8 LIQUID LINE

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT. AREVALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

TWJ036CA WITH TWE030CA4 AT 1100 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 72 74 76 78 80 KW

59 33.9 25.9 27.8 29.7 31.6 33.4 2.5285 63 36.7 22.4 24.3 26.1 28.0 29.9 2.60

67 39.5 18.4 20.3 22.1 24.0 25.9 2.6871 42.5 14.3 16.2 18.0 19.9 21.8 2.7759 33.4 25.7 27.6 29.4 31.3 33.2 2.65

90 63 36.1 22.1 24.0 25.9 27.8 29.6 2.7367 38.9 18.1 20.0 21.9 23.8 25.6 2.8271 41.8 14.0 15.9 17.8 19.7 21.5 2.9159 32.8 25.4 27.3 29.2 31.1 32.9* 2.78

95 63 35.5 21.9 23.8 25.6 27.5 29.4 2.8767 38.3 17.9 19.8 21.6 23.5 25.4 2.9571 41.2 13.8 15.7 17.5 19.4 21.3 3.0459 32.1 25.1 27.0 28.9 30.7 32.4* 2.92

100 63 34.7 21.5 23.4 25.3 27.2 29.0 3.0067 37.4 17.6 19.4 21.3 23.2 25.1 3.0971 40.2 13.5 15.3 17.2 19.1 21.0 3.1859 31.3 24.8 26.7 28.5 30.4 31.8* 3.06

105 63 33.9 21.2 23.1 25.0 26.8 28.7 3.1467 36.5 17.2 19.1 21.0 22.8 24.7 3.2371 39.3 13.1 15.0 16.9 18.7 20.6 3.3159 29.8 24.1 26.0 27.9 29.7 30.6* 3.35

115 63 32.2 20.5 22.4 24.3 26.2 28.0 3.4267 34.8 16.5 18.4 20.3 22.2 24.0 3.5071 37.4 12.5 14.3 16.2 18.1 19.9 3.58

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 975 1275TOTAL CAP. X0.98 X1.02SENS. CAP. X0.95 X1.06COMPR. KW X0.99 X1.01

VALUES AT 95/80/67 RATING CONDITIONS

GROSS CAPACITY = 38500 BTUHAIRFLOW = 1125 CFMCOMPRESSOR POWER = 2957 WATTSI.D. FAN POWER = 540 WATTSO.D. FAN POWER = 235 WATTSE.E.R. = 9.65 BTUH/WATT

NOTE:RATED WITH 25 FEET OF 7/8 SUCT.AND 3/8 LIQUID LINE

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

TWJ036CA WITH TWE040CA4-B AT 1400 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 72 74 76 78 80 KW

59 37.2 30.6 33.0 35.5 37.6* 38.5* 2.6385 63 40.1 25.8 28.3 30.7 33.1 35.6 2.71

67 43.1 20.6 23.0 25.4 27.9 30.3 2.8071 46.2 15.2 17.6 20.1 22.5 25.0 2.8959 36.5 30.3 32.7 35.2 37.0* 37.9* 2.76

90 63 39.3 25.5 28.0 30.4 32.8 35.3 2.8567 42.3 20.3 22.7 25.1 27.6 30.0 2.9471 45.3 14.9 17.3 19.8 22.2 24.7 3.0359 35.8 30.0 32.4 34.9 36.5* 37.3* 2.90

95 63 38.6 25.2 27.7 30.1 32.5 35.0 2.9967 41.5 20.0 22.4 24.8 27.3 29.7 3.0771 44.4 14.6 17.0 19.5 21.9 24.4 3.1759 34.9 29.6 32.0 34.5 35.7* 36.5* 3.04

100 63 37.6 24.8 27.3 29.7 32.1 34.6 3.1367 40.4 19.6 22.0 24.4 26.9 29.3 3.2271 43.3 14.2 16.6 19.1 21.5 24.0 3.3159 34.0 29.2 31.6 34.1* 34.9* 35.8* 3.19

105 63 36.6 24.4 26.9 29.3 31.7 34.2 3.2767 39.3 19.2 21.6 24.0 26.5 28.9 3.3671 42.1 13.8 16.2 18.7 21.1 23.6 3.4559 32.1 28.4 30.8 32.6* 33.4* 34.2* 3.48

115 63 34.6 23.6 26.1 28.5 30.9 33.4 3.5667 37.1 18.4 20.8 23.2 25.7 28.1 3.6471 39.8 13.0 15.4 17.9 20.3 22.8 3.73

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1175 1525TOTAL CAP. X0.97 X1.01SENS. CAP. X0.92 X1.04COMPR. KW X0.98 X1.01

VALUES AT 95/80/67 RATING CONDITIONS

GROSS CAPACITY = 41300 BTUHAIRFLOW = 1350 CFMCOMPRESSOR POWER = 3066 WATTSI.D. FAN POWER = 360 WATTSO.D. FAN POWER = 235 WATTSE.E.R. = 10.80 BTUH/WATT

NOTE:RATED WITH 25 FEET OF 7/8 SUCT.AND 3/8 LIQUID LINE

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

Page 11: Multi Pos

TWE5-PRC001-EN-10-15-99 11

TWJ030CA WITH TWE040CA4-B AT 1868 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 9.0 7.4 7.9 8.5 9.1* 9.3* 2.729.4 17.2 9.7 6.2 6.8 7.4 8.0 8.6 2.8

19.4 10.3 5.0 5.5 6.1 6.7 7.3 2.821.7 11.0 3.7 4.2 4.8 5.4 6.0 2.915.0 8.8 7.3 7.9 8.5 8.9* 9.1* 2.8

32.2 17.2 9.5 6.2 6.7 7.3 7.9 8.5 2.919.4 10.1 4.9 5.4 6.0 6.6 7.2 3.021.7 10.8 3.6 4.2 4.7 5.3 5.9 3.115.0 8.6 7.2 7.8 8.4 8.8* 9.0* 2.9

35.0 17.2 9.3 6.1 6.7 7.2 7.8 8.4 3.019.4 9.9 4.8 5.4 6.0 6.5 7.1 3.121.7 10.6 3.5 4.1 4.7 5.2 5.8 3.215.0 8.4 7.1 7.7 8.3 8.6* 8.8* 3.0

37.8 17.2 9.1 6.0 6.6 7.1 7.7 8.3 3.119.4 9.7 4.7 5.3 5.9 6.4 7.0 3.221.7 10.3 3.4 4.0 4.6 5.2 5.7 3.315.0 8.2 7.0 7.6 8.2 8.4* 8.6* 3.2

40.6 17.2 8.8 5.9 6.4 7.0 7.6 8.2 3.319.4 9.4 4.6 5.2 5.8 6.4 6.9 3.421.7 10.0 3.3 3.9 4.5 5.1 5.7 3.515.0 7.8 6.8 7.4 7.9* 8.0* 8.2* 3.5

46.1 17.2 8.3 5.7 6.3 6.9 7.4 8.0 3.519.4 8.9 4.4 5.0 5.6 6.2 6.7 3.621.7 9.5 3.1 3.7 4.3 4.9 5.4 3.7

PerformanceData Cooling Metric Units

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1656 2165TOTAL CAP. X0.98 X1.02SENS. CAP. X0.95 X1.07COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 9.99 KWAIRFLOW = 1910 CMHCOMPRESSOR POWER = 3104 WATTSI.D. FAN POWER = 300 WATTSO.D. FAN POWER = 195 WATTSE.E.R. = 9.05 BTUH/WATT

NOTE:RATED WITH 7.62 METERS OF 22 MM SUCT.AND 9.5 MM LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

TWJ036CA WITH TWE030CA4 AT 1868 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 9.9 7.6 8.1 8.7 9.3 9.8 2.529.4 17.2 10.8 6.6 7.1 7.6 8.2 8.8 2.6

19.4 11.6 5.4 5.9 6.5 7.0 7.6 2.721.7 12.5 4.2 4.7 5.3 5.8 6.4 2.815.0 9.8 7.5 8.1 8.6 9.2 9.7 2.7

32.2 17.2 10.6 6.5 7.0 7.6 8.1 8.7 2.719.4 11.4 5.3 5.9 6.4 7.0 7.5 2.821.7 12.2 4.1 4.7 5.2 5.8 6.3 2.915.0 9.6 7.4 8.0 8.6 9.1 9.6* 2.8

35.0 17.2 10.4 6.4 7.0 7.5 8.1 8.6 2.919.4 11.2 5.2 5.8 6.3 6.9 7.4 3.021.7 12.1 4.0 4.6 5.1 5.7 6.2 3.015.0 9.4 7.4 7.9 8.5 9.0 9.5* 2.9

37.8 17.2 10.2 6.3 6.9 7.4 8.0 8.5 3.019.4 11.0 5.2 5.7 6.2 6.8 7.4 3.121.7 11.8 4.0 4.5 5.0 5.6 6.2 3.215.0 9.2 7.3 7.8 8.4 8.9 9.3* 3.1

40.6 17.2 9.9 6.2 6.8 7.3 7.9 8.4 3.119.4 10.7 5.0 5.6 6.2 6.7 7.2 3.221.7 11.5 3.8 4.4 5.0 5.5 6.0 3.315.0 8.7 7.1 7.6 8.2 8.7 9.0* 3.3

46.1 17.2 9.4 6.0 6.6 7.1 7.7 8.2 3.419.4 10.2 4.8 5.4 5.9 6.5 7.0 3.521.7 11.0 3.7 4.2 4.7 5.3 5.8 3.6

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1656 2165TOTAL CAP. X0.98 X1.02SENS. CAP. X0.95 X1.06COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 11.28 KWAIRFLOW = 1910 CMHCOMPRESSOR POWER = 2957 WATTSI.D. FAN POWER = 540 WATTSO.D. FAN POWER = 235 WATTSE.E.R. = 9.65 BTUH/WATT

NOTE:RATED WITH 7.62 METERS OF 22 MM SUCT.AND 9.5 MM LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

TWJ036CA WITH TWE040CA4-B AT 2378 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 10.9 9.0 9.7 10.4 11.0* 11.3* 2.629.4 17.2 11.7 7.6 8.3 9.0 9.7 10.4 2.7

19.4 12.6 6.0 6.7 7.4 8.2 8.9 2.821.7 13.5 4.5 5.2 5.9 6.6 7.3 2.915.0 10.7 8.9 9.6 10.3 10.8* 11.1* 2.8

32.2 17.2 11.5 7.5 8.2 8.9 9.6 10.3 2.819.4 12.4 5.9 6.7 7.4 8.1 8.8 2.921.7 13.3 4.4 5.1 5.8 6.5 7.2 3.015.0 10.5 8.8 9.5 10.2 10.7* 10.9* 2.9

35.0 17.2 11.3 7.4 8.1 8.8 9.5 10.3 3.019.4 12.2 5.9 6.6 7.3 8.0 8.7 3.121.7 13.0 4.3 5.0 5.7 6.4 7.1 3.215.0 10.2 8.7 9.4 10.1 10.5* 10.7* 3.0

37.8 17.2 11.0 7.3 8.0 8.7 9.4 10.1 3.119.4 11.8 5.7 6.4 7.1 7.9 8.6 3.221.7 12.7 4.2 4.9 5.6 6.3 7.0 3.315.0 10.0 8.6 9.3 10.0* 10.2* 10.5* 3.2

40.6 17.2 10.7 7.1 7.9 8.6 9.3 10.0 3.319.4 11.5 5.6 6.3 7.0 7.8 8.5 3.421.7 12.3 4.0 4.7 5.5 6.2 6.9 3.515.0 9.4 8.3 9.0 9.6* 9.8* 10.0* 3.5

46.1 17.2 10.1 6.9 7.6 8.4 9.1 9.8 3.619.4 10.9 5.4 6.1 6.8 7.5 8.2 3.621.7 11.7 3.8 4.5 5.2 5.9 6.7 3.7

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1995 2590TOTAL CAP. X0.97 X1.01SENS. CAP. X0.92 X1.04COMPR. KW X0.98 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 12.10 KWAIRFLOW = 2293 CMHCOMPRESSOR POWER = 3066 WATTSI.D. FAN POWER = 360 WATTSO.D. FAN POWER = 235 WATTSE.E.R. = 10.80 BTUH/WATT

NOTE:RATED WITH 7.62 METERS OF 22 MM SUCT.AND 9.5 MM LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

Page 12: Multi Pos

12 TWE5-PRC001-EN-10-15-99

PerformanceData Cooling English Units

TWA030CD WITH TWE030CA4 AT 1000 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 72 74 76 78 80 KW

59 28.8 22.6 24.4 26.1 27.8 29.2* 2.1385 63 31.0 19.3 21.0 22.8 24.5 26.2 2.21

67 33.3 15.6 17.3 19.1 20.8 22.5 2.2971 35.7 11.8 13.6 15.3 17.0 18.7 2.3759 28.3 22.4 24.1 25.8 27.6 28.7* 2.24

90 63 30.4 19.1 20.8 22.5 24.2 26.0 2.3267 32.7 15.4 17.1 18.8 20.5 22.3 2.4071 35.1 11.6 13.3 15.0 16.8 18.5 2.4859 27.7 22.2 23.9 25.6 27.3 28.3* 2.35

95 63 29.9 18.9 20.6 22.3 24.0 25.7 2.4267 32.1 15.2 16.9 18.6 20.3 22.0 2.5171 34.4 11.4 13.1 14.8 16.5 18.2 2.5959 27.0 21.9 23.6 25.3 27.1* 27.7* 2.46

100 63 29.1 18.5 20.3 22.0 23.7 25.4 2.5467 31.3 14.8 16.6 18.3 20.0 21.7 2.6271 33.5 11.1 12.8 14.5 16.2 17.9 2.7059 26.3 21.6 23.3 25.0 26.5* 27.2* 2.57

105 63 28.3 18.2 20.0 21.7 23.4 25.1 2.6567 30.4 14.5 16.2 18.0 19.7 21.4 2.7371 32.6 10.7 12.5 14.2 15.9 17.6 2.8159 24.9 21.0 22.7 24.4 25.4* 26.0* 2.80

115 63 26.8 17.6 19.3 21.1 22.8 24.5 2.8767 28.8 13.9 15.6 17.3 19.1 20.8 2.9571 30.8 10.1 11.8 13.6 15.3 17.0 3.02

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 875 1125TOTAL CAP. X0.98 X1.01SENS. CAP. X0.95 X1.05COMPR. KW X0.99 X1.01

VALUES AT 95/80/67 RATING CONDITIONS

GROSS CAPACITY = 32200 BTUHAIRFLOW = 1000 CFMCOMPRESSOR POWER = 2505 WATTSI.D. FAN POWER = 440 WATTSO.D. FAN POWER = 214 WATTSE.E.R. = 9.55 BTUH/WATT

NOTE:RATED WITH 25 FEET OF 7/8 SUCT.AND 3/8 LIQUID LINE

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

TWA030CD WITH TWE040CA4-B AT 1100 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 72 74 76 78 80 KW

59 30.8 25.2 27.1 29.1 31.0* 31.7* 2.2185 63 33.0 21.2 23.2 25.2 27.2 29.2 2.29

67 35.4 16.9 18.9 20.9 22.9 24.9 2.3771 37.9 12.5 14.5 16.5 18.5 20.5 2.4559 30.1 24.9 26.9 28.9 30.5* 31.2* 2.32

90 63 32.3 21.0 23.0 24.9 26.9 28.9 2.4067 34.7 16.7 18.6 20.6 22.6 24.6 2.4871 37.0 12.3 14.2 16.2 18.2 20.2 2.5659 29.5 24.6 26.6 28.6 29.9* 30.6* 2.43

95 63 31.6 20.7 22.7 24.7 26.7 28.6 2.5167 33.9 16.4 18.4 20.4 22.3 24.3 2.5971 36.2 12.0 14.0 16.0 17.9 19.9 2.6759 28.6 24.2 26.2 28.2 29.3* 29.9* 2.54

100 63 30.8 20.3 22.3 24.3 26.3 28.3 2.6267 32.9 16.0 18.0 20.0 22.0 24.0 2.7071 35.2 11.6 13.6 15.6 17.6 19.6 2.7859 27.8 23.9 25.9 27.9* 28.6* 29.2* 2.66

105 63 29.9 20.0 22.0 23.9 25.9 27.9 2.7367 32.0 15.7 17.6 19.6 21.6 23.6 2.8171 34.2 11.3 13.2 15.2 17.2 19.2 2.9059 26.2 23.2 25.2 26.5* 27.2* 27.8* 2.89

115 63 28.1 19.3 21.2 23.2 25.2 27.2 2.9667 30.1 14.9 16.9 18.9 20.9 22.9 3.0471 32.1 10.6 12.5 14.5 16.5 18.5 3.11

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 975 1275TOTAL CAP. X0.98 X1.02SENS. CAP. X0.95 X1.07COMPR. KW X0.99 X1.01

VALUES AT 95/80/67 RATING CONDITIONS

GROSS CAPACITY = 34100 BTUHAIRFLOW = 1125 CFMCOMPRESSOR POWER = 2594 WATTSI.D. FAN POWER = 300 WATTSO.D. FAN POWER = 214 WATTSE.E.R. = 10.45 BTUH/WATT

NOTE:RATED WITH 25 FEET OF 7/8 SUCT.AND 3/8 LIQUID LINE

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

TWA040CD WITH TWE040CA4-B AT 1500 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 72 74 76 78 80 KW

59 39.3 32.2 34.8 37.4 39.6* 40.5* 2.7985 63 42.2 27.1 29.7 32.3 34.9 37.4 2.90

67 45.2 21.5 24.1 26.7 29.3 31.8 3.0171 48.4 15.8 18.4 21.0 23.6 26.1 3.1359 38.5 31.9 34.4 37.0 39.0* 39.9* 2.93

90 63 41.4 26.8 29.4 32.0 34.5 37.1 3.0467 44.3 21.2 23.8 26.4 28.9 31.5 3.1671 47.4 15.5 18.1 20.7 23.2 25.8 3.2959 37.7 31.5 34.1 36.7 38.4* 39.2* 3.07

95 63 40.5 26.5 29.1 31.6 34.2 36.8 3.1867 43.4 20.9 23.5 26.0 28.6 31.2 3.3171 46.4 15.2 17.7 20.3 22.9 25.5 3.4459 36.7 31.1 33.7 36.3 37.5* 38.4* 3.21

100 63 39.4 26.0 28.6 31.2 33.8 36.4 3.3367 42.3 20.5 23.0 25.6 28.2 30.8 3.4671 45.2 14.7 17.3 19.9 22.5 25.1 3.5959 35.7 30.7 33.3 35.9* 36.7* 37.6* 3.36

105 63 38.4 25.6 28.2 30.8 33.4 35.9 3.4867 41.1 20.0 22.6 25.2 27.8 30.3 3.6171 44.0 14.3 16.9 19.5 22.1 24.6 3.7559 33.7 29.9 32.4 34.2* 35.0* 35.9* 3.65

115 63 36.2 24.8 27.4 29.9 32.5 35.1 3.7867 38.8 19.2 21.8 24.3 26.9 29.5 3.9271 41.5 13.5 16.1 18.6 21.2 23.8 4.06

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1325 1700TOTAL CAP. X0.98 X1.01SENS. CAP. X0.95 X1.06COMPR. KW X0.99 X1.01

VALUES AT 95/80/67 RATING CONDITIONS

GROSS CAPACITY = 43500 BTUHAIRFLOW = 1500 CFMCOMPRESSOR POWER = 3309 WATTSI.D. FAN POWER = 420 WATTSO.D. FAN POWER = 244 WATTSE.E.R. = 10.45 BTUH/WATT

NOTE:RATED WITH 25 FEET OF 1-1/8 SUCT.AND 3/8 LIQUID LINE

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

Page 13: Multi Pos

TWE5-PRC001-EN-10-15-99 13

TWA030CD WITH TWE030CA4 AT 1698 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 8.4 6.6 7.1 7.6 8.1 8.6* 2.129.4 17.2 9.1 5.7 6.2 6.7 7.2 7.7 2.2

19.4 9.8 4.6 5.1 5.6 6.1 6.6 2.321.7 10.5 3.5 4.0 4.5 5.0 5.5 2.415.0 8.3 6.6 7.1 7.6 8.1 8.4* 2.2

32.2 17.2 8.9 5.6 6.1 6.6 7.1 7.6 2.319.4 9.6 4.5 5.0 5.5 6.0 6.5 2.421.7 10.3 3.4 3.9 4.4 4.9 5.4 2.515.0 8.1 6.5 7.0 7.5 8.0 8.3* 2.3

35.0 17.2 8.8 5.5 6.0 6.5 7.0 7.5 2.419.4 9.4 4.5 5.0 5.4 5.9 6.4 2.521.7 10.1 3.3 3.8 4.3 4.8 5.3 2.615.0 7.9 6.4 6.9 7.4 7.9* 8.1* 2.5

37.8 17.2 8.5 5.4 5.9 6.4 6.9 7.4 2.519.4 9.2 4.3 4.9 5.4 5.9 6.4 2.621.7 9.8 3.3 3.8 4.2 4.7 5.2 2.715.0 7.7 6.3 6.8 7.3 7.8* 8.0* 2.6

40.6 17.2 8.3 5.3 5.9 6.4 6.9 7.4 2.719.4 8.9 4.2 4.7 5.3 5.8 6.3 2.721.7 9.6 3.1 3.7 4.2 4.7 5.2 2.815.0 7.3 6.2 6.7 7.1 7.4* 7.6* 2.8

46.1 17.2 7.9 5.2 5.7 6.2 6.7 7.2 2.919.4 8.4 4.1 4.6 5.1 5.6 6.1 3.021.7 9.0 3.0 3.5 4.0 4.5 5.0 3.0

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1486 1910TOTAL CAP. X0.98 X1.01SENS. CAP. X0.95 X1.05COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 9.43 KWAIRFLOW = 1698 CMHCOMPRESSOR POWER = 2505 WATTSI.D. FAN POWER = 440 WATTSO.D. FAN POWER = 214 WATTSE.E.R. = 9.55 BTUH/WATT

NOTE:RATED WITH 7.62 METERS OF 22 MM SUCT.AND 9.5 MM LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

PerformanceData Cooling Metric Units

TWA030CD WITH TWE040CA4-B AT 1868 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 9.0 7.4 7.9 8.5 9.1* 9.3* 2.229.4 17.2 9.7 6.2 6.8 7.4 8.0 8.6 2.3

19.4 10.4 5.0 5.5 6.1 6.7 7.3 2.421.7 11.1 3.7 4.2 4.8 5.4 6.0 2.515.0 8.8 7.3 7.9 8.5 8.9* 9.1* 2.3

32.2 17.2 9.5 6.2 6.7 7.3 7.9 8.5 2.419.4 10.2 4.9 5.4 6.0 6.6 7.2 2.521.7 10.8 3.6 4.2 4.7 5.3 5.9 2.615.0 8.6 7.2 7.8 8.4 8.8* 9.0* 2.4

35.0 17.2 9.3 6.1 6.7 7.2 7.8 8.4 2.519.4 9.9 4.8 5.4 6.0 6.5 7.1 2.621.7 10.6 3.5 4.1 4.7 5.2 5.8 2.715.0 8.4 7.1 7.7 8.3 8.6* 8.8* 2.5

37.8 17.2 9.0 5.9 6.5 7.1 7.7 8.3 2.619.4 9.6 4.7 5.3 5.9 6.4 7.0 2.721.7 10.3 3.4 4.0 4.6 5.2 5.7 2.815.0 8.1 7.0 7.6 8.2* 8.4* 8.6* 2.7

40.6 17.2 8.8 5.9 6.4 7.0 7.6 8.2 2.719.4 9.4 4.6 5.2 5.7 6.3 6.9 2.821.7 10.0 3.3 3.9 4.5 5.0 5.6 2.915.0 7.7 6.8 7.4 7.8* 8.0* 8.1* 2.9

46.1 17.2 8.2 5.7 6.2 6.8 7.4 8.0 3.019.4 8.8 4.4 5.0 5.5 6.1 6.7 3.021.7 9.4 3.1 3.7 4.2 4.8 5.4 3.1

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1656 2165TOTAL CAP. X0.98 X1.02SENS. CAP. X0.95 X1.07COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 9.99 KWAIRFLOW = 1910 CMHCOMPRESSOR POWER = 2594 WATTSI.D. FAN POWER = 300 WATTSO.D. FAN POWER = 214 WATTSE.E.R. = 10.45 BTUH/WATT

NOTE:RATED WITH 7.62 METERS OF 22 MM SUCT.AND 9.5 MM LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

TWA040CD WITH TWE040CA4-B AT 2547 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 11.5 9.4 10.2 11.0 11.6* 11.9* 2.829.4 17.2 12.4 7.9 8.7 9.5 10.2 11.0 2.9

19.4 13.2 6.3 7.1 7.8 8.6 9.3 3.021.7 14.2 4.6 5.4 6.2 6.9 7.6 3.115.0 11.3 9.3 10.1 10.8 11.4* 11.7* 2.9

32.2 17.2 12.1 7.9 8.6 9.4 10.1 10.9 3.019.4 13.0 6.2 7.0 7.7 8.5 9.2 3.221.7 13.9 4.5 5.3 6.1 6.8 7.6 3.315.0 11.0 9.2 10.0 10.8 11.3* 11.5* 3.1

35.0 17.2 11.9 7.8 8.5 9.3 10.0 10.8 3.219.4 12.7 6.1 6.9 7.6 8.4 9.1 3.321.7 13.6 4.5 5.2 5.9 6.7 7.5 3.415.0 10.8 9.1 9.9 10.6 11.0* 11.3* 3.2

37.8 17.2 11.5 7.6 8.4 9.1 9.9 10.7 3.319.4 12.4 6.0 6.7 7.5 8.3 9.0 3.521.7 13.2 4.3 5.1 5.8 6.6 7.4 3.615.0 10.5 9.0 9.8 10.5* 10.8* 11.0* 3.4

40.6 17.2 11.3 7.5 8.3 9.0 9.8 10.5 3.519.4 12.0 5.9 6.6 7.4 8.1 8.9 3.621.7 12.9 4.2 5.0 5.7 6.5 7.2 3.815.0 9.9 8.8 9.5 10.0* 10.3* 10.5* 3.7

46.1 17.2 10.6 7.3 8.0 8.8 9.5 10.3 3.819.4 11.4 5.6 6.4 7.1 7.9 8.6 3.921.7 12.2 4.0 4.7 5.4 6.2 7.0 4.1

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 2250 2887TOTAL CAP. X0.98 X1.01SENS. CAP. X0.95 X1.06COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 12.75 KWAIRFLOW = 2547 CMHCOMPRESSOR POWER = 3309 WATTSI.D. FAN POWER = 420 WATTSO.D. FAN POWER = 244 WATTSE.E.R. = 10.45 BTUH/WATT

NOTE:RATED WITH 7.62 METERS OF 28.6 MM SUCT.AND 9.5 MM LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

Page 14: Multi Pos

14 TWE5-PRC001-EN-10-15-99

PerformanceData Cooling English Units

TWA040CD WITH TWE050CA5-C AT 1500 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 72 74 76 78 80 KW

59 40.1 33.2 35.9 38.6 40.6* 41.5* 2.7885 63 43.1 28.0 30.7 33.3 36.0 38.7 2.89

67 46.1 22.2 24.9 27.5 30.2 32.9 3.0171 49.3 16.3 18.9 21.6 24.3 27.0 3.1359 39.1 32.8 35.5 38.2 39.8* 40.7* 2.91

90 63 42.0 27.5 30.2 32.9 35.6 38.2 3.0267 44.9 21.7 24.4 27.1 29.8 32.4 3.1471 48.0 15.8 18.5 21.2 23.8 26.5 3.2759 38.1 32.4 35.0 37.7 38.9* 39.8* 3.04

95 63 40.9 27.1 29.8 32.4 35.1 37.8 3.1567 43.7 21.3 24.0 26.6 29.3 32.0 3.2871 46.7 15.4 18.0 20.7 23.4 26.1 3.4159 37.0 31.9 34.6 37.2* 38.0* 38.9* 3.16

100 63 39.7 26.6 29.3 32.0 34.6 37.3 3.2967 42.5 20.8 23.5 26.2 28.8 31.5 3.4171 45.3 14.9 17.6 20.2 22.9 25.6 3.5559 35.9 31.4 34.1 36.3* 37.1* 37.9* 3.30

105 63 38.5 26.1 28.8 31.5 34.2 36.8 3.4267 41.2 20.3 23.0 25.7 28.4 31.0 3.5571 44.0 14.4 17.1 19.8 22.4 25.1 3.6959 33.6 30.5 33.2 34.4* 35.2* 36.0* 3.56

115 63 36.1 25.2 27.9 30.6 33.2 35.9 3.6967 38.6 19.4 22.1 24.7 27.4 30.1 3.8271 41.2 13.5 16.2 18.8 21.5 24.2 3.96

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1325 1700TOTAL CAP. X0.99 X1.01SENS. CAP. X0.95 X1.06COMPR. KW X0.99 X1.01

VALUES AT 95/80/67 RATING CONDITIONS

GROSS CAPACITY = 43800 BTUHAIRFLOW = 1500 CFMCOMPRESSOR POWER = 3279 WATTSI.D. FAN POWER = 510 WATTSO.D. FAN POWER = 244 WATTSE.E.R. = 10.30 BTUH/WATT

NOTE:RATED WITH 25 FEET OF 1-1/8 SUCT.AND 3/8 LIQUID LINE

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

TWA050CD WITH TWE050CA5-C AT 1800 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 72 74 76 78 80 KW

59 48.8 39.6 42.7 45.8 49.0* 50.1* 3.6085 63 52.3 33.4 36.5 39.6 42.7 45.9 3.72

67 55.9 26.6 29.7 32.8 35.9 39.0 3.8471 59.6 19.6 22.7 25.8 29.0 32.1 3.9659 47.6 39.1 42.2 45.3 48.0* 49.1* 3.77

90 63 51.0 32.9 36.0 39.1 42.2 45.3 3.8867 54.5 26.0 29.2 32.3 35.4 38.5 4.0071 58.1 19.1 22.2 25.3 28.4 31.5 4.1359 46.4 38.5 41.6 44.8 47.0* 48.1* 3.93

95 63 49.7 32.3 35.5 38.6 41.7 44.8 4.0567 53.1 25.5 28.6 31.7 34.9 38.0 4.1771 56.6 18.6 21.7 24.8 27.9 31.0 4.3059 45.1 38.0 41.1 44.2 45.9* 46.9* 4.10

100 63 48.2 31.8 34.9 38.0 41.1 44.2 4.2167 51.5 24.9 28.1 31.2 34.3 37.4 4.3371 54.9 18.0 21.1 24.2 27.3 30.4 4.4659 43.7 37.4 40.5 43.6 44.8* 45.8* 4.27

105 63 46.8 31.2 34.3 37.4 40.5 43.7 4.3867 50.0 24.4 27.5 30.6 33.7 36.8 4.5071 53.2 17.4 20.5 23.6 26.8 29.9 4.6259 41.1 36.3 39.4 41.6* 42.5* 43.5* 4.61

115 63 43.9 30.1 33.2 36.3 39.4 42.5 4.7167 46.9 23.2 26.3 29.5 32.6 35.7 4.8371 49.9 16.3 19.4 22.5 25.6 28.7 4.94

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1575 2025TOTAL CAP. X0.99 X1.01SENS. CAP. X0.95 X1.05COMPR. KW X0.99 X1.01

VALUES AT 95/80/67 RATING CONDITIONS

GROSS CAPACITY = 53100 BTUHAIRFLOW = 1800 CFMCOMPRESSOR POWER = 4171 WATTSI.D. FAN POWER = 750 WATTSO.D. FAN POWER = 255 WATTSE.E.R. = 9.65 BTUH/WATT

NOTE:RATED WITH 25 FEET OF 1-1/8 SUCT.AND 3/8 LIQUID LINE

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

TWA060CD WITH TWE050CA5-C AT 1800 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 72 74 76 78 80 KW

59 57.2 43.7 46.8 50.0 53.1 56.3 4.6185 63 61.6 37.6 40.7 43.9 47.0 50.2 4.77

67 66.1 30.8 34.0 37.1 40.2 43.4 4.9371 70.8 23.8 27.0 30.1 33.3 36.4 5.1059 55.9 43.1 46.3 49.4 52.6 55.7 4.80

90 63 60.1 37.0 40.2 43.3 46.5 49.6 4.9667 64.6 30.2 33.4 36.5 39.7 42.8 5.1371 69.1 23.2 26.4 29.5 32.7 35.8 5.3059 54.6 42.5 45.7 48.8 52.0 55.0* 5.00

95 63 58.7 36.4 39.6 42.7 45.9 49.0 5.1667 63.1 29.6 32.8 35.9 39.1 42.2 5.3371 67.5 22.7 25.8 29.0 32.1 35.3 5.5059 53.2 41.9 45.1 48.2 51.4 53.8* 5.23

100 63 57.2 35.8 38.9 42.1 45.2 48.4 5.3867 61.4 29.0 32.1 35.3 38.4 41.6 5.5571 65.8 22.0 25.2 28.3 31.5 34.6 5.7159 51.8 41.3 44.4 47.6 50.7 52.7* 5.45

105 63 55.7 35.2 38.3 41.5 44.6 47.8 5.6167 59.8 28.4 31.5 34.7 37.8 40.9 5.7771 64.0 21.4 24.5 27.7 30.8 34.0 5.9359 48.9 40.1 43.2 46.3 49.3* 50.4* 5.91

115 63 52.6 33.9 37.1 40.2 43.4 46.5 6.0667 56.5 27.1 30.2 33.4 36.5 39.7 6.2071 60.5 20.1 23.3 26.4 29.6 32.7 6.36

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 1575 2025TOTAL CAP. X0.98 X1.01SENS. CAP. X0.95 X1.05COMPR. KW X0.99 X1.01

VALUES AT 95/80/67 RATING CONDITIONS

GROSS CAPACITY = 63100 BTUHAIRFLOW = 1800 CFMCOMPRESSOR POWER = 5326 WATTSI.D. FAN POWER = 750 WATTSO.D. FAN POWER = 395 WATTSE.E.R. = 9.20 BTUH/WATT

NOTE:RATED WITH 25 FEET OF 1-1/8 SUCT.AND 3/8 LIQUID LINE

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES F.

Page 15: Multi Pos

TWE5-PRC001-EN-10-15-99 15

TWA040CD WITH TWE050CA5-C AT 2547 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 11.7 9.7 10.5 11.3 11.9* 12.2* 2.829.4 17.2 12.6 8.2 9.0 9.8 10.5 11.3 2.9

19.4 13.5 6.5 7.3 8.1 8.8 9.6 3.021.7 14.4 4.8 5.5 6.3 7.1 7.9 3.115.0 11.5 9.6 10.4 11.2 11.7* 11.9* 2.9

32.2 17.2 12.3 8.1 8.8 9.6 10.4 11.2 3.019.4 13.2 6.4 7.1 7.9 8.7 9.5 3.121.7 14.1 4.6 5.4 6.2 7.0 7.8 3.315.0 11.2 9.5 10.3 11.0 11.4* 11.7* 3.0

35.0 17.2 12.0 7.9 8.7 9.5 10.3 11.1 3.219.4 12.8 6.2 7.0 7.8 8.6 9.4 3.321.7 13.7 4.5 5.3 6.1 6.9 7.6 3.415.0 10.8 9.3 10.1 10.9* 11.1* 11.4* 3.2

37.8 17.2 11.6 7.8 8.6 9.4 10.1 10.9 3.319.4 12.5 6.1 6.9 7.7 8.4 9.2 3.421.7 13.3 4.4 5.2 5.9 6.7 7.5 3.515.0 10.5 9.2 10.0 10.6* 10.9* 11.1* 3.3

40.6 17.2 11.3 7.6 8.4 9.2 10.0 10.8 3.419.4 12.1 5.9 6.7 7.5 8.3 9.1 3.521.7 12.9 4.2 5.0 5.8 6.6 7.4 3.715.0 9.8 8.9 9.7 10.1* 10.3* 10.5* 3.6

46.1 17.2 10.6 7.4 8.2 9.0 9.7 10.5 3.719.4 11.3 5.7 6.5 7.2 8.0 8.8 3.821.7 12.1 4.0 4.7 5.5 6.3 7.1 4.0

TWA050CD WITH TWE050CA5-C AT 3057 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 14.3 11.6 12.5 13.4 14.4* 14.7* 3.629.4 17.2 15.3 9.8 10.7 11.6 12.5 13.4 3.7

19.4 16.4 7.8 8.7 9.6 10.5 11.4 3.821.7 17.5 5.7 6.7 7.6 8.5 9.4 4.015.0 13.9 11.5 12.4 13.3 14.1* 14.4* 3.8

32.2 17.2 14.9 9.6 10.5 11.5 12.4 13.3 3.919.4 16.0 7.6 8.6 9.5 10.4 11.3 4.021.7 17.0 5.6 6.5 7.4 8.3 9.2 4.115.0 13.6 11.3 12.2 13.1 13.8* 14.1* 3.9

35.0 17.2 14.6 9.5 10.4 11.3 12.2 13.1 4.119.4 15.6 7.5 8.4 9.3 10.2 11.1 4.221.7 16.6 5.4 6.4 7.3 8.2 9.1 4.315.0 13.2 11.1 12.0 13.0 13.4* 13.7* 4.1

37.8 17.2 14.1 9.3 10.2 11.1 12.0 13.0 4.219.4 15.1 7.3 8.2 9.1 10.0 11.0 4.321.7 16.1 5.3 6.2 7.1 8.0 8.9 4.515.0 12.8 11.0 11.9 12.8 13.1* 13.4* 4.3

40.6 17.2 13.7 9.1 10.0 11.0 11.9 12.8 4.419.4 14.6 7.1 8.1 9.0 9.9 10.8 4.521.7 15.6 5.1 6.0 6.9 7.9 8.8 4.615.0 12.0 10.6 11.5 12.2* 12.5* 12.7* 4.6

46.1 17.2 12.9 8.8 9.7 10.6 11.5 12.5 4.719.4 13.7 6.8 7.7 8.6 9.6 10.5 4.821.7 14.6 4.8 5.7 6.6 7.5 8.4 4.9

PerformanceData Cooling Metric Units

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 2250 2887TOTAL CAP. X0.99 X1.01SENS. CAP. X0.95 X1.06COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 12.83 KWAIRFLOW = 2547 CMHCOMPRESSOR POWER = 3279 WATTSI.D. FAN POWER = 510 WATTSO.D. FAN POWER = 244 WATTSE.E.R. = 10.30 BTUH/WATT

NOTE:RATED WITH 7.62 METERS OF 28.6 MM SUCT.AND 9.5 MM LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 2675 3439TOTAL CAP. X0.99 X1.01SENS. CAP. X0.95 X1.05COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONS

GROSS CAPACITY = 15.56 KWAIRFLOW = 3057 CMHCOMPRESSOR POWER = 4171 WATTSI.D. FAN POWER = 750 WATTSO.D. FAN POWER = 255 WATTSE.E.R. = 9.65 BTUH/WATT

NOTE:RATED WITH 7.62 METERS OF 28.6 MM SUCT.AND 9.5 MM LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT.ARE VALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

TWA060CD WITH TWE050CA5-C AT 3057 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW

15.0 16.8 12.8 13.7 14.6 15.6 16.5 4.629.4 17.2 18.0 11.0 11.9 12.9 13.8 14.7 4.8

19.4 19.4 9.0 10.0 10.9 11.8 12.7 4.921.7 20.7 7.0 7.9 8.8 9.8 10.7 5.115.0 16.4 12.6 13.6 14.5 15.4 16.3 4.8

32.2 17.2 17.6 10.8 11.8 12.7 13.6 14.5 5.019.4 18.9 8.8 9.8 10.7 11.6 12.5 5.121.7 20.2 6.8 7.7 8.6 9.6 10.5 5.315.0 16.0 12.5 13.4 14.3 15.2 16.1* 5.0

35.0 17.2 17.2 10.7 11.6 12.5 13.4 14.4 5.219.4 18.5 8.7 9.6 10.5 11.5 12.4 5.321.7 19.8 6.7 7.6 8.5 9.4 10.3 5.515.0 15.6 12.3 13.2 14.1 15.1 15.8* 5.2

37.8 17.2 16.8 10.5 11.4 12.3 13.2 14.2 5.419.4 18.0 8.5 9.4 10.3 11.3 12.2 5.621.7 19.3 6.4 7.4 8.3 9.2 10.1 5.715.0 15.2 12.1 13.0 13.9 14.9 15.4* 5.4

40.6 17.2 16.3 10.3 11.2 12.2 13.1 14.0 5.619.4 17.5 8.3 9.2 10.2 11.1 12.0 5.821.7 18.8 6.3 7.2 8.1 9.0 10.0 5.915.0 14.3 11.7 12.7 13.6 14.4* 14.8* 5.9

46.1 17.2 15.4 9.9 10.9 11.8 12.7 13.6 6.119.4 16.6 7.9 8.8 9.8 10.7 11.6 6.221.7 17.7 5.9 6.8 7.7 8.7 9.6 6.4

CORRECTION FACTORS - OTHER AIRFLOWS(MULTIPLY OR ADD AS INDICATED)

AIRFLOW 2675 3439TOTAL CAP. X0.98 X1.01SENS. CAP. X0.95 X1.05COMPR. KW X0.99 X1.01

VALUES AT ARI RATING CONDITIONSGROSS CAPACITY = 18.49 KWAIRFLOW = 3057 CMHCOMPRESSOR POWER = 5326 WATTSI.D. FAN POWER = 750 WATTSO.D. FAN POWER = 395 WATTSE.E.R. = 9.20 BTUH/WATT

NOTE:RATED WITH 7.62 METERS OF 28.6 MM SUCT.AND 9.5 MM LIQUID LINES

* DRY COIL CONDITION (TOTAL CAPACITY =SENSIBLE CAPACITY)TOTAL CAPACITY, COMP. KW AND APP. DEW PT. AREVALID ONLY FOR WET COILALL TEMPERATURES IN DEGREES C.

Page 16: Multi Pos

16 TWE5-PRC001-EN-10-15-99

PerformanceData Heating English Units

TWJ020CA WITH TWE030CA4 AT 700 CFMO.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.F. 60 70 75 80 60 70 75 80-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-8 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.002 6.79 6.60 6.50 6.41 1.47 1.54 1.58 1.617 8.13 7.90 7.78 7.67 1.50 1.57 1.61 1.64

12 9.48 9.20 9.06 8.92 1.52 1.60 1.63 1.6717 10.8 10.5 10.3 10.2 1.55 1.63 1.66 1.7022 11.2 10.9 10.7 10.5 1.56 1.64 1.68 1.7127 11.6 11.2 11.0 10.9 1.57 1.65 1.69 1.7332 11.9 11.6 11.4 11.2 1.58 1.66 1.70 1.7437 12.3 11.9 11.8 11.6 1.60 1.68 1.71 1.7542 12.7 12.3 12.1 11.9 1.61 1.69 1.73 1.7747 18.9 18.3 18.0 17.7 1.71 1.79 1.84 1.8852 20.2 19.6 19.3 19.0 1.73 1.82 1.87 1.9157 21.6 20.9 20.6 20.2 1.76 1.85 1.90 1.9462 22.9 22.2 21.8 21.5 1.79 1.88 1.92 1.9767 24.3 23.5 23.1 22.7 1.81 1.91 1.95 2.0072 25.6 24.8 24.4 24.0 1.84 1.93 1.98 2.03

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 700 CFM TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 625 800HEATING CAP. X0.99 X1.02COMPR. KW X1.01 X0.98VALUES AT ARI RATING CONDITIONS OF:

70&47/43 (HIGH TEMP. POINT)70&17/15 (LOW TEMP. POINT)

AIRFLOW = 700 CFMHEATING CAP. (HIGH TEMP.) = 18300 BTUHHEATING CAP. (LOW TEMP.) = 10500 BTUHCOMPR. POWER (HIGH TEMP.) = 1354 WATTSCOMPR. POWER (LOW TEMP.) = 1185 WATTSCOEFF. OF PERF. (HIGH TEMP.) = 3.00COEFF. OF PERF. (LOW TEMP.) = 1.88OUTDOOR FAN POWER = 130 WATTSINDOOR FAN POWER = 310 WATTSNOTE: RATED WITH 25 FEET OF 3/4

SUCTION AND 5/16 LIQUID LINE

TWJ024CA WITH TWE030CA4 AT 900 CFMO.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.F. 60 70 75 80 60 70 75 80-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-8 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-3 8.10 7.93 7.85 7.77 1.86 1.94 1.98 2.032 9.91 9.70 9.60 9.49 1.92 2.01 2.06 2.107 11.7 11.5 11.3 11.2 1.99 2.08 2.13 2.17

12 13.5 13.2 13.1 12.9 2.06 2.15 2.20 2.2517 15.3 15.0 14.8 14.7 2.12 2.22 2.27 2.3222 16.2 15.9 15.7 15.5 2.18 2.28 2.33 2.3827 17.1 16.7 16.5 16.3 2.23 2.34 2.39 2.4432 18.0 17.6 17.4 17.2 2.29 2.40 2.45 2.5137 18.9 18.4 18.2 18.0 2.34 2.45 2.51 2.5742 19.8 19.3 19.1 18.9 2.39 2.51 2.57 2.6347 26.2 25.6 25.3 25.0 2.52 2.65 2.71 2.7752 28.0 27.4 27.0 26.7 2.59 2.72 2.78 2.8557 29.8 29.1 28.8 28.4 2.66 2.79 2.86 2.9262 31.6 30.9 30.5 30.2 2.72 2.86 2.93 3.0067 33.5 32.7 32.3 31.9 2.79 2.93 3.00 3.0772 35.3 34.4 34.0 33.6 2.86 3.00 3.07 3.14

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 900 CFM TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 800 1025HEATING CAP. X0.99 X1.02COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

70&47/43 (HIGH TEMP. POINT)70&17/15 (LOW TEMP. POINT)

AIRFLOW = 900 CFMHEATING CAP. (HIGH TEMP.) = 25600 BTUHHEATING CAP. (LOW TEMP.) = 15000 BTUHCOMPR. POWER (HIGH TEMP.) = 2038 WATTSCOMPR. POWER (LOW TEMP.) = 1614 WATTSCOEFF. OF PERF. (HIGH TEMP.) = 2.84COEFF. OF PERF. (LOW TEMP.) = 1.96OUTDOOR FAN POWER = 180 WATTSINDOOR FAN POWER = 430 WATTSNOTE: RATED WITH 25 FEET OF 3/4

SUCTION AND 5/16 LIQUID LINE

TWJ030CA WITH TWE030CA4 AT 1000 CFMO.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.F. 60 70 75 80 60 70 75 80-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-8 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-3 9.79 9.60 9.51 9.41 2.27 2.38 2.44 2.492 11.8 11.6 11.5 11.4 2.36 2.47 2.53 2.597 13.9 13.6 13.5 13.3 2.44 2.56 2.62 2.69

12 15.9 15.6 15.4 15.3 2.53 2.65 2.72 2.7817 18.0 17.6 17.4 17.2 2.61 2.74 2.81 2.8822 18.9 18.5 18.3 18.2 2.69 2.83 2.89 2.9627 19.9 19.5 19.3 19.1 2.77 2.91 2.98 3.0532 20.9 20.4 20.2 20.0 2.85 2.99 3.06 3.1437 21.8 21.4 21.2 20.9 2.92 3.07 3.15 3.2242 22.8 22.3 22.1 21.8 3.00 3.16 3.23 3.3147 30.2 29.6 29.3 29.0 3.12 3.28 3.37 3.4552 32.3 31.6 31.3 30.9 3.21 3.37 3.46 3.5457 34.3 33.6 33.2 32.9 3.29 3.46 3.55 3.6462 36.4 35.6 35.2 34.8 3.38 3.55 3.64 3.7367 38.4 37.6 37.2 36.8 3.46 3.64 3.74 3.8372 40.5 39.6 39.2 38.7 3.55 3.73 3.83 3.92

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1000 CFM TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 875 1125HEATING CAP. X0.99 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

70&47/43 (HIGH TEMP. POINT)70&17/15 (LOW TEMP. POINT)

AIRFLOW = 1000 CFMHEATING CAP. (HIGH TEMP.) = 29600 BTUHHEATING CAP. (LOW TEMP.) = 17600 BTUHCOMPR. POWER (HIGH TEMP.) = 2649 WATTSCOMPR. POWER (LOW TEMP.) = 2109 WATTSCOEFF. OF PERF. (HIGH TEMP.) = 2.64COEFF. OF PERF. (LOW TEMP.) = 1.86OUTDOOR FAN POWER = 195 WATTSINDOOR FAN POWER = 440 WATTSNOTE: RATED WITH 25 FEET OF 7/8

SUCTION AND 3/8 LIQUID LINE

Page 17: Multi Pos

TWE5-PRC001-EN-10-15-99 17

PerformanceData Heating Metric Units

TWJ020CA WITH TWE030CA4 AT 1189 CMHO.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7

-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-22.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-19.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-16.7 2.0 1.9 1.9 1.9 1.5 1.5 1.6 1.6-13.9 2.4 2.3 2.3 2.2 1.5 1.6 1.6 1.6-11.1 2.8 2.7 2.7 2.6 1.5 1.6 1.6 1.7-8.3 3.2 3.1 3.0 3.0 1.5 1.6 1.7 1.7-5.6 3.3 3.2 3.1 3.1 1.6 1.6 1.7 1.7-2.8 3.4 3.3 3.2 3.2 1.6 1.6 1.7 1.70.0 3.5 3.4 3.3 3.3 1.6 1.7 1.7 1.72.8 3.6 3.5 3.5 3.4 1.6 1.7 1.7 1.85.6 3.7 3.6 3.5 3.5 1.6 1.7 1.7 1.88.3 5.5 5.4 5.3 5.2 1.7 1.8 1.8 1.9

11.1 5.9 5.7 5.7 5.6 1.7 1.8 1.9 1.913.9 6.3 6.1 6.0 5.9 1.8 1.9 1.9 1.916.7 6.7 6.5 6.4 6.3 1.8 1.9 1.9 2.019.4 7.1 6.9 6.8 6.7 1.8 1.9 2.0 2.022.2 7.5 7.3 7.1 7.0 1.8 1.9 2.0 2.0

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1189 CMH TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 1061 1358HEATING CAP. X0.99 X1.02COMPR. KW X1.01 X0.98VALUES AT ARI RATING CONDITIONS OF:

21.1& 8.3/6.1(HIGH TEMP. POINT)21.1&-8.3/-9.4(LOW TEMP. POINT)

AIRFLOW = 1189 CMHHEATING CAP. (HIGH TEMP.) = 5.36 KWHEATING CAP. (LOW TEMP.) = 3.08 KWCOMPR. POWER (HIGH TEMP.) = 1354 WATTSCOMPR. POWER (LOW TEMP.) = 1185 WATTSCOEFF. OF PERF. (HIGH TEMP.) = 3.00COEFF. OF PERF. (LOW TEMP.) = 1.88OUTDOOR FAN POWER = 130 WATTSINDOOR FAN POWER = 310 WATTSNOTE: RATED WITH 7.62 METERS OF 19 MM

SUCTION AND 8 MM LIQUID LINE

TWJ024CA WITH TWE030CA4 AT 1528 CMHO.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7

-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-22.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-19.4 2.4 2.3 2.3 2.3 1.9 1.9 2.0 2.0-16.7 2.9 2.8 2.8 2.8 1.9 2.0 2.1 2.1-13.9 3.4 3.4 3.3 3.3 2.0 2.1 2.1 2.2-11.1 4.0 3.9 3.8 3.8 2.1 2.2 2.2 2.3-8.3 4.5 4.4 4.3 4.3 2.1 2.2 2.3 2.3-5.6 4.7 4.7 4.6 4.5 2.2 2.3 2.3 2.4-2.8 5.0 4.9 4.8 4.8 2.2 2.3 2.4 2.40.0 5.3 5.2 5.1 5.0 2.3 2.4 2.5 2.52.8 5.5 5.4 5.3 5.3 2.3 2.5 2.5 2.65.6 5.8 5.7 5.6 5.5 2.4 2.5 2.6 2.68.3 7.7 7.5 7.4 7.3 2.5 2.7 2.7 2.8

11.1 8.2 8.0 7.9 7.8 2.6 2.7 2.8 2.813.9 8.7 8.5 8.4 8.3 2.7 2.8 2.9 2.916.7 9.3 9.1 8.9 8.8 2.7 2.9 2.9 3.019.4 9.8 9.6 9.5 9.3 2.8 2.9 3.0 3.122.2 10.3 10.1 10.0 9.8 2.9 3.0 3.1 3.1

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1528 CMH TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 1358 1741HEATING CAP. X0.99 X1.02COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

21.1& 8.3/6.1(HIGH TEMP. POINT)21.1&-8.3/-9.4(LOW TEMP. POINT)

AIRFLOW = 1528 CMHHEATING CAP. (HIGH TEMP.) = 7.50 KWHEATING CAP. (LOW TEMP.) = 4.39 KWCOMPR. POWER (HIGH TEMP.) = 2038 WATTSCOMPR. POWER (LOW TEMP.) = 1614 WATTSCOEFF. OF PERF. (HIGH TEMP.) = 2.84COEFF. OF PERF. (LOW TEMP.) = 1.96OUTDOOR FAN POWER = 180 WATTSINDOOR FAN POWER = 430 WATTSNOTE: RATED WITH 7.62 METERS OF 19 MM

SUCTION AND 8 MM LIQUID LINE

TWJ030CA WITH TWE030CA4 AT 1698 CMHO.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7

-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-22.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-19.4 2.9 2.8 2.8 2.8 2.3 2.4 2.4 2.5-16.7 3.5 3.4 3.4 3.3 2.4 2.5 2.5 2.6-13.9 4.1 4.0 4.0 3.9 2.4 2.6 2.6 2.7-11.1 4.7 4.6 4.5 4.5 2.5 2.7 2.7 2.8-8.3 5.3 5.2 5.1 5.0 2.6 2.7 2.8 2.9-5.6 5.5 5.4 5.4 5.3 2.7 2.8 2.9 3.0-2.8 5.8 5.7 5.7 5.6 2.8 2.9 3.0 3.00.0 6.1 6.0 5.9 5.9 2.8 3.0 3.1 3.12.8 6.4 6.3 6.2 6.1 2.9 3.1 3.2 3.25.6 6.7 6.5 6.5 6.4 3.0 3.2 3.2 3.38.3 8.8 8.7 8.6 8.5 3.1 3.3 3.4 3.5

11.1 9.5 9.3 9.2 9.1 3.2 3.4 3.5 3.513.9 10.0 9.8 9.7 9.6 3.3 3.5 3.5 3.616.7 10.7 10.4 10.3 10.2 3.4 3.5 3.6 3.719.4 11.3 11.0 10.9 10.8 3.5 3.6 3.7 3.822.2 11.9 11.6 11.5 11.3 3.5 3.7 3.8 3.9

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1698 CMH TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 1486 1910HEATING CAP. X0.99 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

21.1& 8.3/6.1(HIGH TEMP. POINT)21.1&-8.3/-9.4(LOW TEMP. POINT)

AIRFLOW = 1698 CMHHEATING CAP. (HIGH TEMP.) = 8.67 KWHEATING CAP. (LOW TEMP.) = 5.16 KWCOMPR. POWER (HIGH TEMP.) = 2649 WATTSCOMPR. POWER (LOW TEMP.) = 2109 WATTSCOEFF. OF PERF. (HIGH TEMP.) = 2.64COEFF. OF PERF. (LOW TEMP.) = 1.86OUTDOOR FAN POWER = 195 WATTSINDOOR FAN POWER = 440 WATTSNOTE: RATED WITH 7.62 METERS OF 22 MM

SUCTION AND 9.5 MM LIQUID LINE

Page 18: Multi Pos

18 TWE5-PRC001-EN-10-15-99

PerformanceData Heating English Units

TWJ030CA WITH TWE040CA4-B AT 1100 CFMO.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.F. 60 70 75 80 60 70 75 80-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-8 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-3 9.46 9.27 9.17 9.08 2.12 2.24 2.30 2.362 11.6 11.3 11.2 11.1 2.19 2.31 2.37 2.447 13.6 13.4 13.2 13.1 2.26 2.39 2.45 2.52

12 15.7 15.4 15.2 15.1 2.33 2.47 2.53 2.6017 17.8 17.5 17.3 17.1 2.40 2.54 2.61 2.6822 18.9 18.5 18.3 18.1 2.47 2.61 2.68 2.7627 19.9 19.5 19.3 19.1 2.54 2.69 2.76 2.8332 21.0 20.5 20.3 20.1 2.61 2.76 2.83 2.9137 22.0 21.6 21.3 21.1 2.67 2.83 2.91 2.9942 23.1 22.6 22.3 22.1 2.74 2.90 2.98 3.0647 30.4 29.7 29.4 29.1 2.83 3.00 3.08 3.1752 32.5 31.8 31.4 31.1 2.91 3.08 3.16 3.2557 34.6 33.8 33.5 33.1 2.98 3.15 3.24 3.3362 36.7 35.9 35.5 35.1 3.05 3.23 3.32 3.4167 38.8 37.9 37.5 37.1 3.12 3.31 3.40 3.4972 40.9 40.0 39.5 39.1 3.19 3.38 3.48 3.57

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1100 CFM TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 975 1275HEATING CAP. X0.99 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

70&47/43 (HIGH TEMP. POINT)70&17/15 (LOW TEMP. POINT)

AIRFLOW = 1125 CFMHEATING CAP. (HIGH TEMP.) = 29800 BTUHHEATING CAP. (LOW TEMP.) = 17500 BTUHCOMPR. POWER (HIGH TEMP.) = 2504 WATTSCOMPR. POWER (LOW TEMP.) = 2047 WATTSCOEFF. OF PERF. (HIGH TEMP.) = 2.92COEFF. OF PERF. (LOW TEMP.) = 2.00OUTDOOR FAN POWER = 195 WATTSINDOOR FAN POWER = 300 WATTSNOTE: RATED WITH 25 FEET OF 7/8

SUCTION AND 3/8 LIQUID LINE

TWJ036CA WITH TWE030CA4 AT 1100 CFMO.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.F. 60 70 75 80 60 70 75 80-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-8 8.32 8.18 8.11 8.04 2.00 2.09 2.13 2.18-3 10.8 10.6 10.5 10.4 2.13 2.22 2.27 2.322 13.3 13.0 12.9 12.8 2.25 2.36 2.41 2.467 15.8 15.5 15.3 15.2 2.38 2.49 2.54 2.60

12 18.3 17.9 17.7 17.5 2.50 2.62 2.68 2.7417 20.7 20.3 20.1 19.9 2.63 2.75 2.82 2.8822 21.9 21.5 21.3 21.1 2.71 2.85 2.91 2.9827 23.1 22.7 22.4 22.2 2.80 2.94 3.01 3.0832 24.3 23.8 23.6 23.3 2.89 3.03 3.10 3.1837 25.5 25.0 24.7 24.5 2.98 3.13 3.20 3.2742 26.7 26.2 25.9 25.6 3.06 3.22 3.30 3.3747 35.6 34.9 34.5 34.2 3.38 3.55 3.64 3.7252 38.1 37.3 36.9 36.6 3.50 3.68 3.77 3.8757 40.6 39.8 39.3 38.9 3.63 3.82 3.91 4.0162 43.1 42.2 41.8 41.3 3.75 3.95 4.05 4.1567 45.6 44.6 44.2 43.7 3.88 4.08 4.19 4.2972 48.0 47.1 46.6 46.1 4.00 4.22 4.32 4.43

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1100 CFM TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 975 1275HEATING CAP. X0.99 X1.02COMPR. KW X1.02 X0.97VALUES AT ARI RATING CONDITIONS OF:

70&47/43 (HIGH TEMP. POINT)70&17/15 (LOW TEMP. POINT)

AIRFLOW = 1125 CFMHEATING CAP. (HIGH TEMP.) = 35000 BTUHHEATING CAP. (LOW TEMP.) = 20400 BTUHCOMPR. POWER (HIGH TEMP.) = 2776 WATTSCOMPR. POWER (LOW TEMP.) = 1982 WATTSCOEFF. OF PERF. (HIGH TEMP.) = 2.88COEFF. OF PERF. (LOW TEMP.) = 2.16OUTDOOR FAN POWER = 235 WATTSINDOOR FAN POWER = 540 WATTSNOTE: RATED WITH 25 FEET OF 7/8

SUCTION AND 3/8 LIQUID LINE

TWJ036CA WITH TWE040CA4-B AT 1400 CFMO.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.F. 60 70 75 80 60 70 75 80-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00-8 7.73 7.59 7.52 7.45 1.84 1.93 1.98 2.03-3 10.3 10.1 10.0 9.94 1.94 2.05 2.10 2.152 12.9 12.7 12.5 12.4 2.05 2.16 2.22 2.277 15.5 15.2 15.1 14.9 2.16 2.27 2.33 2.39

12 18.1 17.7 17.6 17.4 2.26 2.39 2.45 2.5217 20.7 20.3 20.1 19.9 2.37 2.50 2.57 2.6422 22.0 21.6 21.3 21.1 2.44 2.58 2.65 2.7227 23.3 22.8 22.6 22.4 2.52 2.66 2.73 2.8132 24.6 24.1 23.9 23.6 2.59 2.74 2.82 2.8937 25.9 25.4 25.1 24.9 2.67 2.82 2.90 2.9742 27.2 26.7 26.4 26.1 2.74 2.90 2.98 3.0647 36.3 35.5 35.1 34.8 3.00 3.18 3.27 3.3652 38.9 38.1 37.7 37.2 3.11 3.29 3.39 3.4857 41.5 40.6 40.2 39.7 3.22 3.41 3.50 3.6062 44.1 43.1 42.7 42.2 3.32 3.52 3.62 3.7267 46.6 45.7 45.2 44.7 3.43 3.63 3.74 3.8472 49.2 48.2 47.7 47.2 3.54 3.75 3.85 3.96

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1400 CFM TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 1175 1525HEATING CAP. X0.98 X1.01COMPR. KW X1.03 X0.99VALUES AT ARI RATING CONDITIONS OF:

70&47/43 (HIGH TEMP. POINT)70&17/15 (LOW TEMP. POINT)

AIRFLOW = 1350 CFMHEATING CAP. (HIGH TEMP.) = 35400 BTUHHEATING CAP. (LOW TEMP.) = 20200 BTUHCOMPR. POWER (HIGH TEMP.) = 2590 WATTSCOMPR. POWER (LOW TEMP.) = 1906 WATTSCOEFF. OF PERF. (HIGH TEMP.) = 3.24COEFF. OF PERF. (LOW TEMP.) = 2.36OUTDOOR FAN POWER = 235 WATTSINDOOR FAN POWER = 360 WATTSNOTE: RATED WITH 25 FEET OF 7/8

SUCTION AND 3/8 LIQUID LINE

Page 19: Multi Pos

TWE5-PRC001-EN-10-15-99 19

PerformanceData Heating Metric Units

TWJ030CA WITH TWE040CA4-B AT 1868 CMHO.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7

-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-22.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-19.4 2.8 2.7 2.7 2.7 2.1 2.2 2.3 2.4-16.7 3.4 3.3 3.3 3.3 2.2 2.3 2.4 2.4-13.9 4.0 3.9 3.9 3.8 2.3 2.4 2.5 2.5-11.1 4.6 4.5 4.5 4.4 2.3 2.5 2.5 2.6-8.3 5.2 5.1 5.1 5.0 2.4 2.5 2.6 2.7-5.6 5.5 5.4 5.4 5.3 2.5 2.6 2.7 2.8-2.8 5.8 5.7 5.7 5.6 2.5 2.7 2.8 2.80.0 6.2 6.0 5.9 5.9 2.6 2.8 2.8 2.92.8 6.4 6.3 6.2 6.2 2.7 2.8 2.9 3.05.6 6.8 6.6 6.5 6.5 2.7 2.9 3.0 3.18.3 8.9 8.7 8.6 8.5 2.8 3.0 3.1 3.2

11.1 9.5 9.3 9.2 9.1 2.9 3.1 3.2 3.313.9 10.1 9.9 9.8 9.7 3.0 3.2 3.2 3.316.7 10.8 10.5 10.4 10.3 3.0 3.2 3.3 3.419.4 11.4 11.1 11.0 10.9 3.1 3.3 3.4 3.522.2 12.0 11.7 11.6 11.5 3.2 3.4 3.5 3.6

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1868 CMH TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 1656 2165HEATING CAP. X0.99 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

21.1& 8.3/6.1(HIGH TEMP. POINT)21.1&-8.3/-9.4(LOW TEMP. POINT)

AIRFLOW = 1910 CMHHEATING CAP. (HIGH TEMP.) = 8.73 KWHEATING CAP. (LOW TEMP.) = 5.13 KWCOMPR. POWER (HIGH TEMP.) = 2504 WATTSCOMPR. POWER (LOW TEMP.) = 2047 WATTSCOEFF. OF PERF. (HIGH TEMP.) = 2.92COEFF. OF PERF. (LOW TEMP.) = 2.00OUTDOOR FAN POWER = 195 WATTSINDOOR FAN POWER = 300 WATTSNOTE: RATED WITH 7.62 METERS OF 22 MM

SUCTION AND 9.5 MM LIQUID LINE

TWJ036CA WITH TWE030CA4 AT 1868 CMHO.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7

-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-22.2 2.4 2.4 2.4 2.4 2.0 2.1 2.1 2.2-19.4 3.2 3.1 3.1 3.0 2.1 2.2 2.3 2.3-16.7 3.9 3.8 3.8 3.8 2.3 2.4 2.4 2.5-13.9 4.6 4.5 4.5 4.5 2.4 2.5 2.5 2.6-11.1 5.4 5.2 5.2 5.1 2.5 2.6 2.7 2.7-8.3 6.1 5.9 5.9 5.8 2.6 2.8 2.8 2.9-5.6 6.4 6.3 6.2 6.2 2.7 2.8 2.9 3.0-2.8 6.8 6.7 6.6 6.5 2.8 2.9 3.0 3.10.0 7.1 7.0 6.9 6.8 2.9 3.0 3.1 3.22.8 7.5 7.3 7.2 7.2 3.0 3.1 3.2 3.35.6 7.8 7.7 7.6 7.5 3.1 3.2 3.3 3.48.3 10.4 10.2 10.1 10.0 3.4 3.5 3.6 3.7

11.1 11.2 10.9 10.8 10.7 3.5 3.7 3.8 3.913.9 11.9 11.7 11.5 11.4 3.6 3.8 3.9 4.016.7 12.6 12.4 12.2 12.1 3.8 4.0 4.1 4.219.4 13.4 13.1 13.0 12.8 3.9 4.1 4.2 4.322.2 14.1 13.8 13.7 13.5 4.0 4.2 4.3 4.4

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1868 CMH TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 1656 2165HEATING CAP. X0.99 X1.02COMPR. KW X1.02 X0.97VALUES AT ARI RATING CONDITIONS OF:

21.1& 8.3/6.1(HIGH TEMP. POINT)21.1&-8.3/-9.4(LOW TEMP. POINT)

AIRFLOW = 1910 CMHHEATING CAP. (HIGH TEMP.) = 10.25 KWHEATING CAP. (LOW TEMP.) = 5.98 KWCOMPR. POWER (HIGH TEMP.) = 2776 WATTSCOMPR. POWER (LOW TEMP.) = 1982 WATTSCOEFF. OF PERF. (HIGH TEMP.) = 2.88COEFF. OF PERF. (LOW TEMP.) = 2.16OUTDOOR FAN POWER = 235 WATTSINDOOR FAN POWER = 540 WATTSNOTE: RATED WITH 7.62 METERS OF 22 MM

SUCTION AND 9.5 MM LIQUID LINE

TWJ036CA WITH TWE040CA4-B AT 2378 CMHO.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7

-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0-22.2 2.3 2.2 2.2 2.2 1.8 1.9 2.0 2.0-19.4 3.0 3.0 2.9 2.9 1.9 2.0 2.1 2.2-16.7 3.8 3.7 3.7 3.6 2.0 2.2 2.2 2.3-13.9 4.5 4.5 4.4 4.4 2.2 2.3 2.3 2.4-11.1 5.3 5.2 5.2 5.1 2.3 2.4 2.5 2.5-8.3 6.1 5.9 5.9 5.8 2.4 2.5 2.6 2.6-5.6 6.4 6.3 6.2 6.2 2.4 2.6 2.7 2.7-2.8 6.8 6.7 6.6 6.6 2.5 2.7 2.7 2.80.0 7.2 7.1 7.0 6.9 2.6 2.7 2.8 2.92.8 7.6 7.4 7.4 7.3 2.7 2.8 2.9 3.05.6 8.0 7.8 7.7 7.6 2.7 2.9 3.0 3.18.3 10.6 10.4 10.3 10.2 3.0 3.2 3.3 3.4

11.1 11.4 11.2 11.0 10.9 3.1 3.3 3.4 3.513.9 12.2 11.9 11.8 11.6 3.2 3.4 3.5 3.616.7 12.9 12.6 12.5 12.4 3.3 3.5 3.6 3.719.4 13.7 13.4 13.2 13.1 3.4 3.6 3.7 3.822.2 14.4 14.1 14.0 13.8 3.5 3.8 3.8 4.0

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 2378 CMH TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 1995 2590HEATING CAP. X0.98 X1.01COMPR. KW X1.03 X0.99VALUES AT ARI RATING CONDITIONS OF:

21.1& 8.3/6.1(HIGH TEMP. POINT)21.1&-8.3/-9.4(LOW TEMP. POINT)

AIRFLOW = 2293 CMHHEATING CAP. (HIGH TEMP.) = 10.37 KWHEATING CAP. (LOW TEMP.) = 5.92 KWCOMPR. POWER (HIGH TEMP.) = 2590 WATTSCOMPR. POWER (LOW TEMP.) = 1906 WATTSCOEFF. OF PERF. (HIGH TEMP.) = 3.24COEFF. OF PERF. (LOW TEMP.) = 2.36OUTDOOR FAN POWER = 235 WATTSINDOOR FAN POWER = 360 WATTSNOTE: RATED WITH 7.62 METERS OF 22 MM

SUCTION AND 9.5 MM LIQUID LINE

Page 20: Multi Pos

20 TWE5-PRC001-EN-10-15-99

PerformanceData Heating English Units

TWA030CD WITH TWE030CA4 AT 1000 CFMO.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.F. 60 70 75 80 60 70 75 80-18 7.48 7.28 7.18 7.08 1.69 1.76 1.79 1.83-13 8.81 8.57 8.45 8.33 1.78 1.85 1.89 1.92-8 10.1 9.86 9.72 9.59 1.86 1.94 1.98 2.02-3 11.4 11.1 11.0 10.8 1.95 2.03 2.08 2.122 12.8 12.4 12.3 12.1 2.03 2.13 2.17 2.227 14.1 13.7 13.5 13.4 2.12 2.22 2.27 2.31

12 15.4 15.0 14.8 14.6 2.20 2.31 2.36 2.4117 16.7 16.3 16.1 15.9 2.29 2.40 2.45 2.5122 17.7 17.3 17.0 16.8 2.36 2.47 2.53 2.5827 18.7 18.2 18.0 17.7 2.42 2.54 2.60 2.6632 19.7 19.2 19.0 18.7 2.49 2.61 2.67 2.7337 20.7 20.2 19.9 19.6 2.55 2.68 2.74 2.8042 21.7 21.2 20.9 20.6 2.62 2.75 2.81 2.8847 28.8 28.0 27.6 27.2 2.73 2.87 2.93 3.0052 30.8 30.0 29.5 29.1 2.80 2.94 3.01 3.0857 32.8 31.9 31.5 31.0 2.88 3.02 3.09 3.1762 34.8 33.9 33.4 32.9 2.95 3.10 3.17 3.2567 36.8 35.8 35.3 34.8 3.02 3.18 3.25 3.3372 38.8 37.8 37.2 36.7 3.10 3.26 3.33 3.41

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1000 CFM TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 875 1125HEATING CAP. X0.98 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

70&47/43 (HIGH TEMP. POINT)70&17/15 (LOW TEMP. POINT)

AIRFLOW = 1000 CFMHEATING CAP. (HIGH TEMP.) = 28000 BTUHHEATING CAP. (LOW TEMP.) = 16300 BTUHCOMPR. POWER (HIGH TEMP.) = 2212 WATTSCOMPR. POWER (LOW TEMP.) = 1745 WATTSCOEFF. OF PERF. (HIGH TEMP.) = 2.86COEFF. OF PERF. (LOW TEMP.) = 1.98OUTDOOR FAN POWER = 214 WATTSINDOOR FAN POWER = 440 WATTSNOTE: RATED WITH 25 FEET OF 7/8

SUCTION AND 3/8 LIQUID LINE

TWA030CD WITH TWE040CA4-B AT 1100 CFMO.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.F. 60 70 75 80 60 70 75 80-18 7.58 7.37 7.26 7.16 1.49 1.56 1.59 1.63-13 8.87 8.62 8.50 8.38 1.58 1.65 1.69 1.73-8 10.2 9.88 9.74 9.60 1.66 1.75 1.79 1.83-3 11.4 11.1 11.0 10.8 1.75 1.84 1.88 1.932 12.7 12.4 12.2 12.0 1.84 1.93 1.98 2.037 14.0 13.6 13.5 13.3 1.92 2.02 2.08 2.13

12 15.3 14.9 14.7 14.5 2.01 2.12 2.17 2.2317 16.6 16.2 15.9 15.7 2.10 2.21 2.27 2.3322 17.7 17.2 16.9 16.7 2.15 2.27 2.33 2.3927 18.7 18.2 18.0 17.7 2.21 2.33 2.39 2.4532 19.8 19.2 19.0 18.7 2.27 2.39 2.46 2.5237 20.8 20.3 20.0 19.7 2.32 2.45 2.52 2.5842 21.9 21.3 21.0 20.7 2.38 2.51 2.58 2.6547 29.1 28.3 27.9 27.5 2.47 2.61 2.68 2.7552 31.2 30.4 29.9 29.5 2.53 2.68 2.75 2.8257 33.3 32.4 31.9 31.5 2.60 2.74 2.82 2.8962 35.4 34.4 33.9 33.4 2.66 2.81 2.89 2.9667 37.5 36.5 35.9 35.4 2.72 2.88 2.96 3.0372 39.6 38.5 37.9 37.4 2.78 2.94 3.02 3.10

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1100 CFM TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 975 1275HEATING CAP. X0.99 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

70&47/43 (HIGH TEMP. POINT)70&17/15 (LOW TEMP. POINT)

AIRFLOW = 1125 CFMHEATING CAP. (HIGH TEMP.) = 28400 BTUHHEATING CAP. (LOW TEMP.) = 16200 BTUHCOMPR. POWER (HIGH TEMP.) = 2097 WATTSCOMPR. POWER (LOW TEMP.) = 1698 WATTSCOEFF. OF PERF. (HIGH TEMP.) = 3.16COEFF. OF PERF. (LOW TEMP.) = 2.14OUTDOOR FAN POWER = 214 WATTSINDOOR FAN POWER = 300 WATTSNOTE: RATED WITH 25 FEET OF 7/8

SUCTION AND 3/8 LIQUID LINE

TWA040CD WITH TWE040CA4-B AT 1500 CFMO.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.F. 60 70 75 80 60 70 75 80-18 9.52 9.31 9.20 9.10 1.88 1.97 2.02 2.06-13 11.1 10.9 10.8 10.6 1.96 2.06 2.11 2.16-8 12.8 12.5 12.3 12.2 2.04 2.14 2.20 2.25-3 14.4 14.1 13.9 13.7 2.12 2.23 2.29 2.352 16.0 15.6 15.5 15.3 2.20 2.32 2.38 2.447 17.6 17.2 17.0 16.9 2.28 2.41 2.47 2.54

12 19.2 18.8 18.6 18.4 2.36 2.49 2.56 2.6317 20.8 20.4 20.2 20.0 2.44 2.58 2.65 2.7222 22.2 21.7 21.5 21.3 2.52 2.67 2.75 2.8227 23.6 23.1 22.8 22.6 2.61 2.76 2.84 2.9232 24.9 24.4 24.1 23.9 2.69 2.86 2.94 3.0237 26.3 25.7 25.4 25.2 2.78 2.95 3.03 3.1142 27.7 27.1 26.8 26.5 2.87 3.04 3.12 3.2147 36.6 35.8 35.4 35.0 3.09 3.28 3.37 3.4652 39.2 38.4 37.9 37.5 3.20 3.39 3.49 3.5957 41.9 40.9 40.5 40.0 3.30 3.51 3.61 3.7162 44.5 43.5 43.0 42.5 3.41 3.62 3.73 3.8367 47.1 46.1 45.5 45.0 3.52 3.74 3.85 3.9672 49.7 48.6 48.1 47.5 3.63 3.85 3.97 4.08

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1500 CFM TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 1325 1700HEATING CAP. X0.99 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

70&47/43 (HIGH TEMP. POINT)70&17/15 (LOW TEMP. POINT)

AIRFLOW = 1500 CFMHEATING CAP. (HIGH TEMP.) = 35800 BTUHHEATING CAP. (LOW TEMP.) = 20400 BTUHCOMPR. POWER (HIGH TEMP.) = 2612 WATTSCOMPR. POWER (LOW TEMP.) = 1918 WATTSCOEFF. OF PERF. (HIGH TEMP.) = 3.18COEFF. OF PERF. (LOW TEMP.) = 2.32OUTDOOR FAN POWER = 244 WATTSINDOOR FAN POWER = 420 WATTSNOTE: RATED WITH 25 FEET OF 1-1/8

SUCTION AND 3/8 LIQUID LINE

Page 21: Multi Pos

TWE5-PRC001-EN-10-15-99 21

PerformanceData Heating Metric Units

TWA030CD WITH TWE030CA4 AT 1698 CMHO.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7

-27.8 2.2 2.1 2.1 2.1 1.7 1.8 1.8 1.8-25.0 2.6 2.5 2.5 2.4 1.8 1.9 1.9 1.9-22.2 3.0 2.9 2.8 2.8 1.9 1.9 2.0 2.0-19.4 3.3 3.3 3.2 3.2 2.0 2.0 2.1 2.1-16.7 3.8 3.6 3.6 3.5 2.0 2.1 2.2 2.2-13.9 4.1 4.0 4.0 3.9 2.1 2.2 2.3 2.3-11.1 4.5 4.4 4.3 4.3 2.2 2.3 2.4 2.4-8.3 4.9 4.8 4.7 4.7 2.3 2.4 2.5 2.5-5.6 5.2 5.1 5.0 4.9 2.4 2.5 2.5 2.6-2.8 5.5 5.3 5.3 5.2 2.4 2.5 2.6 2.70.0 5.8 5.6 5.6 5.5 2.5 2.6 2.7 2.72.8 6.1 5.9 5.8 5.7 2.5 2.7 2.7 2.85.6 6.4 6.2 6.1 6.0 2.6 2.8 2.8 2.98.3 8.4 8.2 8.1 8.0 2.7 2.9 2.9 3.0

11.1 9.0 8.8 8.6 8.5 2.8 2.9 3.0 3.113.9 9.6 9.3 9.2 9.1 2.9 3.0 3.1 3.216.7 10.2 9.9 9.8 9.6 3.0 3.1 3.2 3.319.4 10.8 10.5 10.3 10.2 3.0 3.2 3.3 3.322.2 11.4 11.1 10.9 10.8 3.1 3.3 3.3 3.4

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1698 CMH TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 1486 1910HEATING CAP. X0.98 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

21.1& 8.3/6.1(HIGH TEMP. POINT)21.1&-8.3/-9.4(LOW TEMP. POINT)

AIRFLOW = 1698 CMHHEATING CAP. (HIGH TEMP.) = 8.20 KWHEATING CAP. (LOW TEMP.) = 4.78 KWCOMPR. POWER (HIGH TEMP.) = 2212 WATTSCOMPR. POWER (LOW TEMP.) = 1745 WATTSCOEFF. OF PERF. (HIGH TEMP.) = 2.86COEFF. OF PERF. (LOW TEMP.) = 1.98OUTDOOR FAN POWER = 214 WATTSINDOOR FAN POWER = 440 WATTSNOTE: RATED WITH 7.62 METERS OF 22 MM

SUCTION AND 9.5 MM LIQUID LINE

TWA030CD WITH TWE040CA4-B AT 1868 CMHO.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7

-27.8 2.2 2.2 2.1 2.1 1.5 1.6 1.6 1.6-25.0 2.6 2.5 2.5 2.5 1.6 1.6 1.7 1.7-22.2 3.0 2.9 2.9 2.8 1.7 1.8 1.8 1.8-19.4 3.3 3.3 3.2 3.2 1.8 1.8 1.9 1.9-16.7 3.7 3.6 3.6 3.5 1.8 1.9 2.0 2.0-13.9 4.1 4.0 4.0 3.9 1.9 2.0 2.1 2.1-11.1 4.5 4.4 4.3 4.2 2.0 2.1 2.2 2.2-8.3 4.9 4.7 4.7 4.6 2.1 2.2 2.3 2.3-5.6 5.2 5.0 5.0 4.9 2.2 2.3 2.3 2.4-2.8 5.5 5.3 5.3 5.2 2.2 2.3 2.4 2.50.0 5.8 5.6 5.6 5.5 2.3 2.4 2.5 2.52.8 6.1 5.9 5.9 5.8 2.3 2.5 2.5 2.65.6 6.4 6.2 6.2 6.1 2.4 2.5 2.6 2.78.3 8.5 8.3 8.2 8.1 2.5 2.6 2.7 2.8

11.1 9.1 8.9 8.8 8.6 2.5 2.7 2.8 2.813.9 9.8 9.5 9.3 9.2 2.6 2.7 2.8 2.916.7 10.4 10.1 9.9 9.8 2.7 2.8 2.9 3.019.4 11.0 10.7 10.5 10.4 2.7 2.9 3.0 3.022.2 11.6 11.3 11.1 11.0 2.8 2.9 3.0 3.1

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1868 CMH TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 1656 2165HEATING CAP. X0.99 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

21.1& 8.3/6.1(HIGH TEMP. POINT)21.1&-8.3/-9.4(LOW TEMP. POINT)

AIRFLOW = 1910 CMHHEATING CAP. (HIGH TEMP.) = 8.32 KWHEATING CAP. (LOW TEMP.) = 4.75 KWCOMPR. POWER (HIGH TEMP.) = 2097 WATTSCOMPR. POWER (LOW TEMP.) = 1698 WATTSCOEFF. OF PERF. (HIGH TEMP.) = 3.16COEFF. OF PERF. (LOW TEMP.) = 2.14OUTDOOR FAN POWER = 214 WATTSINDOOR FAN POWER = 300 WATTSNOTE: RATED WITH 7.62 METERS OF 22 MM

SUCTION AND 9.5 MM LIQUID LINE

TWA040CD WITH TWE040CA4-B AT 2547 CMHO.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7

-27.8 2.8 2.7 2.7 2.7 1.9 2.0 2.0 2.1-25.0 3.3 3.2 3.2 3.1 2.0 2.1 2.1 2.2-22.2 3.8 3.7 3.6 3.6 2.0 2.1 2.2 2.3-19.4 4.2 4.1 4.1 4.0 2.1 2.2 2.3 2.3-16.7 4.7 4.6 4.5 4.5 2.2 2.3 2.4 2.4-13.9 5.2 5.0 5.0 5.0 2.3 2.4 2.5 2.5-11.1 5.6 5.5 5.4 5.4 2.4 2.5 2.6 2.6-8.3 6.1 6.0 5.9 5.9 2.4 2.6 2.7 2.7-5.6 6.5 6.4 6.3 6.2 2.5 2.7 2.8 2.8-2.8 6.9 6.8 6.7 6.6 2.6 2.8 2.8 2.90.0 7.3 7.1 7.1 7.0 2.7 2.9 2.9 3.02.8 7.7 7.5 7.4 7.4 2.8 3.0 3.0 3.15.6 8.1 7.9 7.9 7.8 2.9 3.0 3.1 3.28.3 10.7 10.5 10.4 10.3 3.1 3.3 3.4 3.5

11.1 11.5 11.3 11.1 11.0 3.2 3.4 3.5 3.613.9 12.3 12.0 11.9 11.7 3.3 3.5 3.6 3.716.7 13.0 12.7 12.6 12.5 3.4 3.6 3.7 3.819.4 13.8 13.5 13.3 13.2 3.5 3.7 3.8 4.022.2 14.6 14.2 14.1 13.9 3.6 3.8 4.0 4.1

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 2547 CMH TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 2250 2887HEATING CAP. X0.99 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

21.1& 8.3/6.1(HIGH TEMP. POINT)21.1&-8.3/-9.4(LOW TEMP. POINT)

AIRFLOW = 2547 CMHHEATING CAP. (HIGH TEMP.) = 10.49 KWHEATING CAP. (LOW TEMP.) = 5.98 KWCOMPR. POWER (HIGH TEMP.) = 2612 WATTSCOMPR. POWER (LOW TEMP.) = 1918 WATTSCOEFF. OF PERF. (HIGH TEMP.) = 3.18COEFF. OF PERF. (LOW TEMP.) = 2.32OUTDOOR FAN POWER = 244 WATTSINDOOR FAN POWER = 420 WATTSNOTE: RATED WITH 7.62 METERS OF 28.6 MM

SUCTION AND 9.5 MM LIQUID LINE

Page 22: Multi Pos

22 TWE5-PRC001-EN-10-15-99

PerformanceData Heating English Units

TWA040CD WITH TWE050CA5-C AT 1500 CFMO.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.F. 60 70 75 80 60 70 75 80-18 9.68 9.46 9.36 9.25 1.94 2.04 2.08 2.13-13 11.3 11.1 11.0 10.8 2.02 2.13 2.18 2.23-8 13.0 12.7 12.6 12.4 2.10 2.21 2.27 2.32-3 14.6 14.3 14.2 14.0 2.19 2.30 2.36 2.422 16.3 15.9 15.8 15.6 2.27 2.39 2.45 2.517 17.9 17.6 17.4 17.2 2.35 2.48 2.54 2.61

12 19.6 19.2 19.0 18.8 2.43 2.57 2.63 2.7017 21.2 20.8 20.6 20.4 2.51 2.65 2.73 2.8022 22.6 22.1 21.8 21.6 2.59 2.74 2.82 2.8927 23.9 23.4 23.1 22.8 2.67 2.83 2.91 2.9932 25.2 24.6 24.4 24.1 2.76 2.92 3.00 3.0837 26.5 25.9 25.6 25.3 2.84 3.01 3.09 3.1742 27.8 27.2 26.9 26.6 2.92 3.09 3.18 3.2747 37.2 36.4 36.0 35.6 3.13 3.32 3.41 3.5152 39.9 39.0 38.6 38.1 3.23 3.43 3.53 3.6357 42.5 41.6 41.1 40.7 3.34 3.54 3.64 3.7562 45.2 44.2 43.7 43.2 3.44 3.65 3.76 3.8667 47.9 46.8 46.3 45.7 3.54 3.76 3.87 3.9872 50.5 49.4 48.8 48.3 3.65 3.88 3.99 4.10

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1500 CFM TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 1325 1700HEATING CAP. X0.99 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

70&47/43 (HIGH TEMP. POINT)70&17/15 (LOW TEMP. POINT)

AIRFLOW = 1500 CFMHEATING CAP. (HIGH TEMP.) = 36400 BTUHHEATING CAP. (LOW TEMP.) = 20800 BTUHCOMPR. POWER (HIGH TEMP.) = 2566 WATTSCOMPR. POWER (LOW TEMP.) = 1900 WATTSCOEFF. OF PERF. (HIGH TEMP.) = 3.18COEFF. OF PERF. (LOW TEMP.) = 2.30OUTDOOR FAN POWER = 244 WATTSINDOOR FAN POWER = 510 WATTSNOTE: RATED WITH 25 FEET OF 1-1/8

SUCTION AND 3/8 LIQUID LINE

TWA050CD WITH TWE050CA5-C AT 1800 CFMO.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.F. 60 70 75 80 60 70 75 80-18 12.5 12.2 12.1 12.0 2.50 2.62 2.67 2.73-13 14.9 14.6 14.4 14.2 2.60 2.72 2.78 2.84-8 17.3 16.9 16.7 16.5 2.69 2.82 2.88 2.94-3 19.7 19.2 19.0 18.8 2.78 2.92 2.98 3.052 22.0 21.6 21.3 21.1 2.87 3.02 3.09 3.167 24.4 23.9 23.7 23.4 2.97 3.12 3.19 3.27

12 26.8 26.3 26.0 25.7 3.06 3.22 3.30 3.3817 29.2 28.6 28.3 28.0 3.15 3.32 3.40 3.4822 30.2 29.5 29.2 28.9 3.25 3.42 3.51 3.5927 31.1 30.5 30.2 29.8 3.34 3.52 3.61 3.7032 32.1 31.4 31.1 30.8 3.44 3.63 3.72 3.8137 33.1 32.4 32.0 31.7 3.54 3.73 3.83 3.9242 34.0 33.3 33.0 32.6 3.63 3.83 3.93 4.0347 48.0 47.0 46.5 46.0 4.00 4.23 4.34 4.4552 51.2 50.1 49.5 49.0 4.14 4.38 4.50 4.6157 54.3 53.1 52.5 52.0 4.28 4.53 4.65 4.7862 57.5 56.2 55.6 54.9 4.43 4.68 4.81 4.9467 60.6 59.3 58.6 57.9 4.57 4.83 4.97 5.1072 63.7 62.3 61.6 60.9 4.71 4.98 5.12 5.26

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1800 CFM TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 1575 2025HEATING CAP. X0.99 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

70&47/43 (HIGH TEMP. POINT)70&17/15 (LOW TEMP. POINT)

AIRFLOW = 1800 CFMHEATING CAP. (HIGH TEMP.) = 47000 BTUHHEATING CAP. (LOW TEMP.) = 28600 BTUHCOMPR. POWER (HIGH TEMP.) = 3222 WATTSCOMPR. POWER (LOW TEMP.) = 2313 WATTSCOEFF. OF PERF. (HIGH TEMP.) = 3.24COEFF. OF PERF. (LOW TEMP.) = 2.50OUTDOOR FAN POWER = 255 WATTSINDOOR FAN POWER = 750 WATTSNOTE: RATED WITH 25 FEET OF 1-1/8

SUCTION AND 3/8 LIQUID LINE

TWA060CD WITH TWE050CA5-C AT 1800 CFMO.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.F. 60 70 75 80 60 70 75 80-18 14.0 13.8 13.7 13.5 3.24 3.37 3.43 3.50-13 16.9 16.6 16.4 16.3 3.36 3.50 3.57 3.64-8 19.7 19.4 19.2 19.1 3.49 3.64 3.71 3.79-3 22.6 22.2 22.0 21.8 3.62 3.77 3.85 3.932 25.4 25.0 24.8 24.6 3.74 3.91 3.99 4.077 28.3 27.8 27.6 27.3 3.87 4.04 4.13 4.22

12 31.1 30.6 30.3 30.1 3.99 4.18 4.27 4.3617 34.0 33.4 33.1 32.8 4.12 4.31 4.41 4.5022 35.7 35.1 34.8 34.5 4.52 4.74 4.85 4.9527 37.4 36.8 36.5 36.2 4.93 5.17 5.28 5.4032 39.1 38.5 38.2 37.8 5.33 5.59 5.72 5.8537 40.9 40.2 39.8 39.5 5.74 6.02 6.16 6.3042 42.6 41.9 41.5 41.2 6.14 6.45 6.60 6.7647 53.9 53.0 52.5 52.1 5.33 5.59 5.72 5.8552 57.2 56.3 55.8 55.3 5.53 5.80 5.94 6.0857 60.6 59.5 59.0 58.5 5.73 6.02 6.16 6.3062 63.9 62.8 62.3 61.7 5.94 6.23 6.38 6.5367 67.2 66.1 65.5 64.9 6.14 6.44 6.60 6.7572 70.5 69.3 68.7 68.1 6.34 6.66 6.82 6.98

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 1800 CFM TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 1575 2025HEATING CAP. X0.99 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

70&47/43 (HIGH TEMP. POINT)70&17/15 (LOW TEMP. POINT)

AIRFLOW = 1800 CFMHEATING CAP. (HIGH TEMP.) = 53000 BTUHHEATING CAP. (LOW TEMP.) = 33400 BTUHCOMPR. POWER (HIGH TEMP.) = 4446 WATTSCOMPR. POWER (LOW TEMP.) = 3166 WATTSCOEFF. OF PERF. (HIGH TEMP.) = 2.76COEFF. OF PERF. (LOW TEMP.) = 2.26OUTDOOR FAN POWER = 395 WATTSINDOOR FAN POWER = 750 WATTSNOTE: RATED WITH 25 FEET OF 1-1/8

SUCTION AND 3/8 LIQUID LINE

Page 23: Multi Pos

TWE5-PRC001-EN-10-15-99 23

PerformanceData Heating Metric Units

TWA040CD WITH TWE050CA5-C AT 2547 CMHO.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7

-27.8 2.8 2.8 2.7 2.7 1.9 2.0 2.1 2.1-25.0 3.3 3.3 3.2 3.2 2.0 2.1 2.2 2.2-22.2 3.8 3.7 3.7 3.6 2.1 2.2 2.3 2.3-19.4 4.3 4.2 4.2 4.1 2.2 2.3 2.4 2.4-16.7 4.8 4.7 4.6 4.6 2.3 2.4 2.5 2.5-13.9 5.2 5.2 5.1 5.0 2.3 2.5 2.5 2.6-11.1 5.7 5.6 5.6 5.5 2.4 2.6 2.6 2.7-8.3 6.2 6.1 6.0 6.0 2.5 2.7 2.7 2.8-5.6 6.6 6.5 6.4 6.3 2.6 2.7 2.8 2.9-2.8 7.0 6.9 6.8 6.7 2.7 2.8 2.9 3.00.0 7.4 7.2 7.1 7.1 2.8 2.9 3.0 3.12.8 7.8 7.6 7.5 7.4 2.8 3.0 3.1 3.25.6 8.1 8.0 7.9 7.8 2.9 3.1 3.2 3.38.3 10.9 10.7 10.5 10.4 3.1 3.3 3.4 3.5

11.1 11.7 11.4 11.3 11.2 3.2 3.4 3.5 3.613.9 12.5 12.2 12.0 11.9 3.3 3.5 3.6 3.816.7 13.2 13.0 12.8 12.7 3.4 3.7 3.8 3.919.4 14.0 13.7 13.6 13.4 3.5 3.8 3.9 4.022.2 14.8 14.5 14.3 14.2 3.7 3.9 4.0 4.1

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 2547 CMH TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 2250 2887HEATING CAP. X0.99 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

21.1& 8.3/6.1(HIGH TEMP. POINT)21.1&-8.3/-9.4(LOW TEMP. POINT)

AIRFLOW = 2547 CMHHEATING CAP. (HIGH TEMP.) = 10.67 KWHEATING CAP. (LOW TEMP.) = 6.09 KWCOMPR. POWER (HIGH TEMP.) = 2566 WATTSCOMPR. POWER (LOW TEMP.) = 1900 WATTSCOEFF. OF PERF. (HIGH TEMP.) = 3.18COEFF. OF PERF. (LOW TEMP.) = 2.30OUTDOOR FAN POWER = 244 WATTSINDOOR FAN POWER = 510 WATTSNOTE: RATED WITH 7.62 METERS OF 28.6 MM

SUCTION AND 9.5 MM LIQUID LINE

TWA050CD WITH TWE050CA5-C AT 3057 CMHO.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7

-27.8 3.7 3.6 3.5 3.5 2.5 2.6 2.7 2.7-25.0 4.4 4.3 4.2 4.2 2.6 2.7 2.8 2.8-22.2 5.1 5.0 4.9 4.8 2.7 2.8 2.9 2.9-19.4 5.8 5.6 5.6 5.5 2.8 2.9 3.0 3.0-16.7 6.4 6.3 6.2 6.2 2.9 3.0 3.1 3.2-13.9 7.1 7.0 6.9 6.9 3.0 3.1 3.2 3.3-11.1 7.9 7.7 7.6 7.5 3.1 3.2 3.3 3.4-8.3 8.6 8.4 8.3 8.2 3.2 3.3 3.4 3.5-5.6 8.8 8.6 8.6 8.5 3.3 3.4 3.5 3.6-2.8 9.1 8.9 8.8 8.7 3.3 3.5 3.6 3.70.0 9.4 9.2 9.1 9.0 3.4 3.6 3.7 3.82.8 9.7 9.5 9.4 9.3 3.5 3.7 3.8 3.95.6 10.0 9.8 9.7 9.6 3.6 3.8 3.9 4.08.3 14.1 13.8 13.6 13.5 4.0 4.2 4.3 4.4

11.1 15.0 14.7 14.5 14.4 4.1 4.4 4.5 4.613.9 15.9 15.6 15.4 15.2 4.3 4.5 4.7 4.816.7 16.8 16.5 16.3 16.1 4.4 4.7 4.8 4.919.4 17.8 17.4 17.2 17.0 4.6 4.8 5.0 5.122.2 18.7 18.3 18.0 17.8 4.7 5.0 5.1 5.3

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 3057 CMH TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 2675 3439HEATING CAP. X0.99 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

21.1& 8.3/6.1(HIGH TEMP. POINT)21.1&-8.3/-9.4(LOW TEMP. POINT)

AIRFLOW = 3057 CMHHEATING CAP. (HIGH TEMP.) = 13.77 KWHEATING CAP. (LOW TEMP.) = 8.38 KWCOMPR. POWER (HIGH TEMP.) = 3222 WATTSCOMPR. POWER (LOW TEMP.) = 2313 WATTSCOEFF. OF PERF. (HIGH TEMP.) = 3.24COEFF. OF PERF. (LOW TEMP.) = 2.50OUTDOOR FAN POWER = 255 WATTSINDOOR FAN POWER = 750 WATTSNOTE: RATED WITH 7.62 METERS OF 28.6 MM

SUCTION AND 9.5 MM LIQUID LINE

TWA060CD WITH TWE050CA5-C AT 3057 CMHO.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT

TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7

-27.8 4.1 4.0 4.0 4.0 3.2 3.4 3.4 3.5-25.0 5.0 4.9 4.8 4.8 3.4 3.5 3.6 3.6-22.2 5.8 5.7 5.6 5.6 3.5 3.6 3.7 3.8-19.4 6.6 6.5 6.4 6.4 3.6 3.8 3.8 3.9-16.7 7.4 7.3 7.3 7.2 3.7 3.9 4.0 4.1-13.9 8.3 8.1 8.1 8.0 3.9 4.0 4.1 4.2-11.1 9.1 9.0 8.9 8.8 4.0 4.2 4.3 4.4-8.3 10.0 9.8 9.7 9.6 4.1 4.3 4.4 4.5-5.6 10.5 10.3 10.2 10.1 4.5 4.7 4.8 4.9-2.8 11.0 10.8 10.7 10.6 4.9 5.2 5.3 5.40.0 11.5 11.3 11.2 11.1 5.3 5.6 5.7 5.82.8 12.0 11.8 11.7 11.6 5.7 6.0 6.2 6.35.6 12.5 12.3 12.2 12.1 6.1 6.4 6.6 6.88.3 15.8 15.5 15.4 15.3 5.3 5.6 5.7 5.8

11.1 16.8 16.5 16.3 16.2 5.5 5.8 5.9 6.113.9 17.8 17.4 17.3 17.1 5.7 6.0 6.2 6.316.7 18.7 18.4 18.3 18.1 5.9 6.2 6.4 6.519.4 19.7 19.4 19.2 19.0 6.1 6.4 6.6 6.822.2 20.7 20.3 20.1 20.0 6.3 6.7 6.8 7.0

CORRECTION FACTORS - OTHER AIRFLOWS(VALUE AT 3057 CMH TIMES CORR. FACTOR

= VALUE AT NEW AIRFLOW)AIRFLOW 2675 3439HEATING CAP. X0.99 X1.01COMPR. KW X1.02 X0.98VALUES AT ARI RATING CONDITIONS OF:

21.1& 8.3/6.1(HIGH TEMP. POINT)21.1&-8.3/-9.4(LOW TEMP. POINT)

AIRFLOW = 3057 CMHHEATING CAP. (HIGH TEMP.) = 15.53 KWHEATING CAP. (LOW TEMP.) = 9.79 KWCOMPR. POWER (HIGH TEMP.) = 4446 WATTSCOMPR. POWER (LOW TEMP.) = 3166 WATTSCOEFF. OF PERF. (HIGH TEMP.) = 2.76COEFF. OF PERF. (LOW TEMP.) = 2.26OUTDOOR FAN POWER = 395 WATTSINDOOR FAN POWER = 750 WATTSNOTE: RATED WITH 7.62 METERS OF 28.6 MM

SUCTION AND 9.5 MM LIQUID LINE

Page 24: Multi Pos

24 TWE5-PRC001-EN-10-15-99

PerformanceData

Evaporator Fan PerformanceBlower Performance — TWE030CA40B — Wet Coil

EXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)UPFLOW & DOWNFLOW (See Notes) HORIZONTAL; NO FILTER (See Notes)

220 VOLTS 220 VOLTSCFM CMH Hl MED LO Hl MED LO600 1018.8 0.72 (179.4) 0.71 (176.9)650 1103.7 0.62 (154.4) 0.61 (152.0)700 1188.6 0.86 (214.2) 0.51 (127.0) 0.84 (209.2) 0.50 (124.6)750 1273.5 0.75 (186.8) 0.40 (99.6) 0.72 (179.4) 0.39 (97.1)800 1358.4 0.89 (221.7) 0.65 (161.9) 0.29 (72.2) 0.87 (216.7) 0.62 (154.4) 0.28 (69.7)850 1443.3 0.81 (201.8) 0.54 (134.5) 0.18 (44.8) 0.79 (196.8) 0.51 (127.0) 0.17 (42.3)900 1528.2 0.72 (179.4) 0.43 (107.1) 0.06 (14.9) 0.69 (171.9) 0.40 (99.6) 0.08 (19.9)950 1613.1 0.63 (156.9) 0.32 (79.7) 0.61 (152.0) 0.30 (74.7)

1000 1698.0 0.53 (132.0) 0.21 (52.3) 0.51 (127.0) 0.17 (42.3)1050 1782.9 0.42 (104.6) 0.10 (24.9) 0.40 (99.6) 0.02 (5.0)1100 1867.8 0.31 (77.2) 0.31 (77.2)1150 1952.7 0.20 (49.8) 0.22 (54.8)1200 2037.6 0.08 (19.9) 0.10 (24.9)

NOTES:Vertical: With filter, no horizontal drip tray. Subtract 0.06" W.G. (15) for downflow.Horizontal: As shipped, but without filter. Subtract 0.05" W.G. (12.5) for horizontal left.

Blower Performance — TWE040CA40C — Wet Coil

EXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)UPFLOW & DOWNFLOW (See Notes) HORIZONTAL; NO FILTER (See Notes)

220 VOLTS 220 VOLTSCFM CMH Hl MED LO Hl MED LO700 1188.6 0.58 (144.5)750 1273.5 0.61 (152.0) 0.55 (137.0)800 1358.4 0.61 (152.0) 0.58 (144.5) 0.52 (129.5) 0.58 (144.5)850 1443.3 0.57 (142.0) 0.54 (134.5) 0.48 (119.6) 0.52 (129.5)900 1528.2 0.53 (132.0) 0.51 (127.0) 0.44 (109.6) 0.49 (122.1)950 1613.1 0.49 (122.1) 0.47 (117.1) 0.40 (99.6) 0.57 (142.0) 0.45 (112.1)

1000 1698.0 0.45 (112.1) 0.43 (107.1) 0.34 (84.7) 0.53 (132.0) 0.50 (124.6) 0.40 (99.6)1050 1782.9 0.40 (99.6) 0.38 (94.7) 0.28 (69.7) 0.48 (119.6) 0.45 (112.1) 0.35 (87.2)1100 1867.8 0.36 (89.7) 0.34 (84.7) 0.22 (54.8) 0.43 (107.1) 0.40 (99.6) 0.30 (74.7)1150 1952.7 0.31 (77.2) 0.29 (72.2) 0.15 (37.4) 0.39 (97.1) 0.37 (92.2) 0.22 (54.8)1200 2037.6 0.26 (64.8) 0.24 (59.8) 0.08 (19.9) 0.35 (87.2) 0.32 (79.7) 0.17 (42.3)1250 2122.5 0.21 (52.3) 0.18 (44.8) 0.00 (0.0) 0.31 (77.2) 0.28 (69.7) 0.10 (24.9)1300 2207.4 0.17 (42.3) 0.13 (32.4) 0.26 (64.8) 0.22 (54.8) 0.01 (2.5)1350 2292.3 0.11 (27.4) 0.07 (17.4) 0.21 (52.3) 0.18 (44.8)1400 2377.2 0.06 (14.9) 0.01 (2.5) 0.15 (37.4) 0.12 (29.9)1450 2462.1 0.01 (2.5) 0.11 (27.4) 0.08 (19.9)1500 2547.0 0.00 0.05 (12.5) 0.02 (5.0)

NOTES:Vertical: With filter, no horizontal drip tray. Small apex baffle. Subtract 0.06" W.G. (15) for downflow.Horizontal: As shipped, but without filter. Subtract 0.05" W.G. (12.5) for horizontal left.

Page 25: Multi Pos

TWE5-PRC001-EN-10-15-99 25

PerformanceData

Blower Performance — TWE050CA50D — Wet Coil

EXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)UPFLOW & DOWNFLOW (See Notes) HORIZONTAL; NO FILTER (See Notes)

220 VOLTS 220 VOLTSCFM CMH Hl MED LO Hl MED LO900 1528.2950 1613.1 0.63 (156.9)1000 1698.0 0.61 (152.0) 0.62 (154.4)1050 1782.9 0.58 (144.5) 0.60 (149.5)1100 1867.8 0.54 (134.5) 0.57 (142.0)1150 1952.7 0.50 (124.6) 0.53 (132.0)1200 2037.6 0.45 (112.1) 0.49 (122.1)1250 2122.5 0.61 (152.0) 0.39 (97.1) 0.64 (159.4) 0.44 (109.6)1300 2207.4 0.59 (147.0) 0.57 (142.0) 0.33 (82.2) 0.62 (154.4) 0.61 (152.0) 0.38 (94.7)1350 2292.3 0.56 (139.5) 0.53 (132.0) 0.26 (64.8) 0.59 (147.0) 0.58 (144.5) 0.32 (79.7)1400 2377.2 0.52 (129.5) 0.49 (122.1) 0.18 (44.8) 0.56 (139.5) 0.55 (137.0) 0.25 (62.3)1450 2462.1 0.48 (119.6) 0.45 (112.1) 0.10 (24.9) 0.52 (129.5) 0.52 (129.5) 0.18 (44.8)1500 2547.0 0.44 (109.6) 0.40 (99.6) 0.01 (2.5) 0.49 (122.1) 0.48 (119.6) 0.11 (27.4)1550 2631.9 0.40 (99.6) 0.35 (87.2) 0.47 (117.1) 0.44 (109.6) 0.00 (0.0)1600 2716.8 0.35 (87.2) 0.30 (74.7) 0.45 (112.1) 0.40 (99.6)1650 2801.7 0.31 (77.2) 0.25 (62.3) 0.41 (102.1) 0.35 (87.2)1700 2886.6 0.26 (64.8) 0.20 (49.8) 0.36 (89.7) 0.28 (69.7)1750 2971.5 0.21 (52.3) 0.14 (34.9) 0.30 (74.7) 0.20 (49.8)1800 3056.4 0.16 (39.9) 0.08 (19.9) 0.24 (59.8) 0.13 (32.4)1850 3141.3 0.11 (27.4) 0.02 (5.0) 0.17 (42.3) 0.07 (17.4)1900 3226.2 0.05 (12.5) 0.10 (24.9) 0.01 (2.5)1950 3311.1 0.02 (5.0)

NOTES:Vertical: With filter, no horizontal drip tray. Small apex baffle. Subtract 0.06" W.G. (15) for downflow.Horizontal: As shipped, but without filter. Subtract 0.05" W.G (12.5) for horizontal left.

Evaporator Fan Performance

Page 26: Multi Pos

26 TWE5-PRC001-EN-10-15-99

PerformanceData

Air Pressure Drop (Inches) - Electric Heaters

Pressure Drop For Electric Heaters In Air Handler Models

NUMBER OF RACKS1 2 3 4 5

AIRFLOW AIRFLOW AIR PRESSURE DROPCFM CMH IN. W.G. (PASCALS)600 1018.8 0.01 (2.5) 0.02 (5.0) 0.02 (5.0)700 1188.6 0.01 (2.5) 0.02 (5.0) 0.02 (5.0)800 1358.4 0.02 (5.0) 0.03 (7.5) 0.03 (7.5) 0.04 (10.0)900 1528.2 0.03 (7.5) 0.03 (7.5) 0.04 (10.0) 0.05 (12.5)

1000 1698.0 0.04 (10.0) 0.04 (10.0) 0.05 (12.5) 0.06 (14.9)1100 1867.8 0.04 (10.0) 0.05 (12.5) 0.06 (14.9) 0.07 (17.4) 0.08 (19.9)1200 2037.6 0.05 (12.5) 0.06 (14.9) 0.07 (17.4) 0.08 (19.9) 0.09 (22.4)1300 2207.4 0.06 (14.9) 0.07 (17.4) 0.08 (19.9) 0.09 (22.4) 0.11 (27.4)1400 2377.2 0.07 (17.4) 0.08 (19.9) 0.10 (24.9) 0.11 (27.4) 0.13 (32.4)1500 2547.0 0.08 (19.9) 0.09 (22.4) 0.11 (27.4) 0.13 (32.4) 0.15 (37.4)1600 2716.8 0.09 (22.4) 0.10 (24.9) 0.12 (29.9) 0.15 (37.4) 0.17 (42.3)1700 2886.6 0.10 (24.9) 0.11 (27.4) 0.14 (34.9) 0.17 (42.3) 0.19 (47.3)1800 3056.4 0.11 (27.4) 0.13 (32.4) 0.16 (39.9) 0.19 (47.3) 0.21 (52.3)1900 3226.2 0.13 (32.4) 0.15 (37.4) 0.18 (44.8) 0.21 (52.3) 0.23 (57.3)2000 3396.0 0.14 (34.9) 0.17 (42.3) 0.20 (49.8) 0.23 (57.3) 0.26 (64.8)

NOTES:1. See Product Data or Air Handler nameplate for approved combinations of Air Handlers and Heaters.2. Heater model numbers may have additional suffix digits.

HEATER RACKSHEATER NO. OF

MODEL NO. RACKSBAY96X1405 1BAY96X1406 2BAY96X1408 2BAY96X1410 2BAY96X1411 3BAY96X1415 3BAY96X1419 4BAY96X1421 4BAY96X1426 5BAY96X3411 3BAY96X3415 3

Page 27: Multi Pos

TWE5-PRC001-EN-10-15-99 27

SupplementaryHeaters

THESE AIR HANDLERS ARE CONVERTIBLE AND MOTOR SPEED TAPS VARY BY THE UNIT ORIENTATION.

TWE030C-Heater Model Number BAY96XUnit 1405 1406 1408,F 1410,F 1410A 1411 1411A 1415 1419 1421 3411 3415Position Application 4.0 KW 4.8 KW 6.4 KW 8.0 KW 8.8 KW 8.8 KW 8.8 KW 12.8 KW 16.0 KW 17.6 KW 8.8 KW 12.8 KWVertical A/C or Elec. Furnace L L L L L L L L L L L LUpflow Heat Pump L L L L L L L L M M L LVertical A/C or Elec. Furnace L L L L L L L L L L L LDownflow Heat Pump L L L L L L L L H H L HHorizontal A/C or Elec. Furnace L L L L L L L L L L L LLeft Heat Pump L L L L L L L L M M L LHorizontal A/C or Elec. Furnace L L L L L L L L L L L LRight Heat Pump L L L L L L L L H H L L

(L) Low, (M) Medium, (H) High indicate minimum heating speed setting for blower/motor operation. 1414 and 1426 not approved for this model.

TWE040C-Heater Model Number BAY96XUnit 1405 1406 1408,F 1410,F 1410A 1411 1411A 1415 1419 1421 3411 3415Position Application 4.0 KW 4.8 KW 6.4 KW 8.0 KW 8.8 KW 8.8 KW 8.8 KW 12.8 KW 16.0 KW 17.6 KW 8.8 KW 12.8 KWVertical A/C or Elec. Furnace L L L L L L L L L L L LUpflow Heat Pump L L L L L M M H H H M MVertical A/C or Elec. Furnace L L L L L L L L L L L LDownflow Heat Pump L L L L L L L H H H L LHorizontal A/C or Elec. Furnace L L L L L L L L L L L LLeft Heat Pump L L L L L L L H H H L LHorizontal A/C or Elec. Furnace L L L L L L L L L L L LRight Heat Pump L L L L L L L H H H L L

(L) Low, (M) Medium, (H) High indicate minimum heating speed setting for blower/motor operation. 1414 not approved for this model.

TWE050C-Heater Model Number BAY96XUnit 1405 1406 1408,F 1410,F 1410A 1415 1419 1421 1426 3415Position Application 4.0 KW 4.8 KW 6.4 KW 8.0 KW 8.8 KW 12.8 KW 16.0 KW 17.6 KW 21.6 KW 12.8 KWVertical A/C or Elec. Furnace — — L L L L L L L LUpflow Heat Pump L L L L L L M M H LVertical A/C or Elec. Furnace — — L L L L L L L LDownflow Heat Pump L L L L L L H H H LHorizontal A/C or Elec. Furnace — — L L L L L L L LLeft Heat Pump L L L L L L H H H LHorizontal A/C or Elec. Furnace — — L L L L L L L LRight Heat Pump L L L L L L M M H L

(L) Low, (M) Medium, (H) High indicate minimum heating speed setting for blower/motor operation. 14141,A and 1414 not approved for this model.

Page 28: Multi Pos

28 TWE5-PRC001-EN-10-15-99

ElectricalData

System Wiring Diagram

NOTES:

1. DO NOT USE REQ TRANSFORMER LEAD IN THIS APPLICATION

2. ACCESSORY KIT BAY24X038 MAY BE USED WHEN AUTOMATIC SPEEDCHANGE FOR HEATING/COOLING OPERATION IS DESIRED.

Legend

Symbols

Page 29: Multi Pos

TWE5-PRC001-EN-10-15-99 29

Dimensions

TWE030-050C Outline DrawingALL DIMENSIONS ARE IN INCHES (MM)

MINIMUM UNIT CLEARANCE SALETO COMBUSTIBLE SERVICE CLEARANCE

MATERIAL (REQUIRED) (RECOMMENDED)SIDES 0 (0) 2 (50.8)FRONT 0 (0) 21 (533.4)BACK 0 (0) 0 (0)

INLET DUCT 0 (0) 1 (25.4)OUTLET DUCT 1 (25.4)

MODEL NO. A B C D E FTWE030CA4 43.00 15.57 21.50 19.50 20.28 21.63 FCCV

(1092.2) (395.5) (761.1) (495.3) (515.1) (549.4)TWE040CA4 51.75 24.32 23.50 21.50 22.28 23.63 FCCV

(1134.5) (617.7) (596.9) (761.1) (565.9) (600.2)TWE050CA5 57.90 30.47 23.50 21.50 22.28 23.63 TXV

(1470.7) (773.9) (596.9) (761.1) (565.9) (600.2)

FLOWCONTROL

Page 30: Multi Pos

30 TWE5-PRC001-EN-10-15-99

Dimensions

TWJ020-036CA and TWA030-060CA Outline DrawingAll dimensions are in inches (mm)

From Dwg. 21D147562 Rev. 6

LIQUID LINE SERVICE VALVE, "E" O.D. FEMALE BRAZED CONNECTION WITH 1/4" SAE FLARE PRESSURE TAP FITTING.

GAS LINE BALL SERVICE VALVE, BALL 1/4 TURN "D" O.D. FEMALE BRAZED CONNECTION WITH 1/4" SAE FLARE PRESSURE TAP FITTING.

FIG. 1

9(229)

23/8 (60)

5(127)

TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR AT LEAST FIVE (5) FEET ABOVE UNIT. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES NOT POUR DIRECTLY ON UNIT, AND SHOULD BE AT LEAST 12" (305) FROM WALL AND ALL SURROUNDING SHRUBBERY ON TWO SIDES. OTHER TWO SIDES UNRESTRICTED.

GAS LINE SERVICE VALVE, "D" O.D. FEMALE BRAZED CONNECTION WITH 1/4" SAE FLARE PRESSURE TAP FITTING.

LIQUID LINE SERVICE VALVE, "E" O.D. FEMALE BRAZED CONNECTION WITH 1/4" SAE FLARE PRESSURE TAP FITTING.

ELECTRICAL AND REFRIGERANT COMPONENTS CLEARANCES PER PREVAILING

SERVICE PANEL

15/8 (41)

11/8 (28.6) DIA. K.O. WITH7/8 (22.2) DIA. HOLE ELECTRICAL POWER

7/8 (22.2) DIA. HOLE LOW VOLTAGE

2 (51)

81/4(210) 43/4

(121)

93/4(248)

67/8(175) 11/4

(32)

A

B

C

FIG. 2

MODEL Figure A B C D ETWJ020CA00A 1 243/8 281/4 245/8 3/4 5/16

(619) (718) (625) (19) (8)TWJ024CA00A 1 323/4 281/4 245/8 3/4 5/16

(832) (718) (625) (19) (8)TWJ030CA00A 1 323/4 281/4 245/8 7/8 3/8

(832) (718) (625) (22.2) (9.53)TWJ036CA00A 2 37 327/8 283/4 7/8 3/8

(940) (835) (730) (22.2) (9.53)TWA030CD00A 1 323/4 281/4 245/8 7/8 3/8

(832) (718) (625) (22.2) (9.53)TWA040CD00A 2 323/4 327/8 283/4 11/8 3/8

(832) (835) (730) (28.6) (9.53)TWA050CD00A 2 37 387/8 343/4 11/8 3/8

(940) (987) (883) (28.6) (9.53)TWA060CD00A 2 443/4 387/8 343/4 11/8 3/8

(1137) (987) (883) (28.6) (9.53)

Page 31: Multi Pos

TWE5-PRC001-EN-10-15-99 31

Convertibility

TWE030 Through 050 ConvertibilitySix (6) Way Convertibility

One Unit - 4 Applications Easy Conversion to Opposite Side Access

Page 32: Multi Pos

The Trane CompanyTrane International Unitary Systems1789 Chaussée de Wavre1160 BrusselsBelgiumwww.trane.com

An American Standard Company

File Number P.I.

Supersedes

Stocking Location

Since The Trane Company has a policy of continuous product improvement, it reserves the right to changedesign and specifications without notice.

MechanicalSpecification Options

TWE5-PRC001-EN-10-15-99

TWE5-PRC000-EN

P.I.-L

GeneralBlower coil units shall be completelyfactory assembled including coil, conden-sate drain pan, fan, motor, filters andcontrols in an insulated casing that canbe applied in horizontal or verticalconfiguration.

This new line of TWE-C air handlersprovides exclusive compact size com-bined with simple four-way convertibilityin three sizes. The unit ships in the righthand horizontal configuration andconverts to vertical upflow just bystanding the unit on end. No toolsrequired. Simple coil rotation providesdownflow and horizontal left applications.

The four-way convertibility provides youinventory benefits and service/installationflexibility. The simple conversion providesopposite side access for installation andservice.

CasingUnits shall have rugged sheet metal andsteel frame construction and shall bepainted with an enamel finish. Casingshall be insulated and knockouts shall beprovided for electrical power and controlwiring.

Refrigerant CircuitsThe TWE units shall have a singlerefrigerant circuit. TWE03-040C refriger-ant circuit shall be controlled by a flowcontrol check valve (FCCV). TheTWE050C refrigerant circuit shall becontrolled by a factory-installed thermalexpansion valve.

CoilAluminum fin surface shall be mechani-cally bonded to 3/8-inch OD coppertubing. Coils shall be factory pressureand leak tested.

FanForward curved, dynamically andstatically balanced with three-speeddirect drive shall be standard, fan motorbearing shall be permanently lubricated.

ControlsFan contactor, and plug-in module foraccessory electric heat control shall beincluded. TWE models shall also includecheck valves.

FiltersFilters shall be included as standard.

AccessoriesElectric Heaters — Shall be available ina wide range of capacities and voltageswith various staging options and plug incontrol wiring. Heaters shall fit insideinternal compartment.