Multipurpose Fire Tender with Water Mist System -Technical specifications
General Description
Design, fabrication and supply of multipurpose fire tender with water mist system to
be built on TATA LPT 2518/48, TC BS III. CE marked pump made in accordance to EN
1028 1&2 norms, Multi pressure Centrifugal Fire Pump having discharge capacity of 3000
LPM at 7 kg/cm2 pressure & High pressure discharge of 300 LPM @ 35 kg/cm2 pressure
with automatic Reciprocating type priming system, 1x100mm suction inlet and 4x63mm
delivery outlet with gun metal valve, Power Take Off (PTO) unit having ratio of 1:1:27,
Auxiliary plunger pump driven by gear box side PTO having discharge capacity of 150 LPM
at 100 kg/cm2 for water mist generator with delivery assembly consist of spray gun, indirect
cooling system, 6000 liters capacity Water Tank fabricated out of 304L fabricated out of
5mm thick sheet for bottom, 4mm thick sheet for other sides and 3mm thick sheet for
baffles, 2000 liters capacity Foam Compound Tank fabricated out of SS 304 L , 5mm thick
sheet for bottom, 4mm thick sheet for other sides and 3mm thick sheet for baffles,
automatic around-the-pump proportioning system, multipurpose monitor (water-cum-foam
Monitor), piping and fitting, pick up tube, open circuit type indirect cooling system, 1 x
20mm x 60m long and 1x20 mmx30 m long high pressure hose reel for main pump with
high pressure fog gun, 2 x 16 mm x 60mtr high pressure hose reel with water mist nozzle
for ultra high pressure pump, driver cabin with double compartment, Breathing Air (B.A) set
locker for accommodating B.A. sets (2sets), equipment lockers with aluminum rolling
shutters, light bar with inbuilt Public Address (PA) system, VHF base station- 1 No., 2 x 50
kg DCP Extinguishers with hose, 2x22.5kg CO2 cylinders with manifold hose and
discharge horn, one no. battery operated siren and one no. manually operated bell, Ladder
gallows for accommodating trussed type 10.5 m double extension aluminum ladder,
Lockers, standard accessories, control panel, tool box, CCE approved spark arrester,
trickle battery charger, wind screen wipers (electrically operated), best workmanship and
finish, instruction book, inspection/acceptance test, marking, etc. as per IS:10460 with
accessories as per Annexure-A.
All components to be used shall be CE/PESO approved/UL listed. Quote should
indicate the BRAND/MAKE of the components/systems without which offers are liable for
rejection.
Detailed scope of work and specifications are given below:
Scope
Design, Supply of material, Fabrication of Multipurpose Fire Tender on TATA LPT
2518/48, TC BS III Cowl Type Truck Chassis (free issue by IPRC) with multipurpose utility
(Water-6000 Ltrs, Foam-2000 Ltrs & DCP-2X50 Kg, CO2- 2X22.5 kg) as per IS: 950 along
with listed accessories. The Fire Tender shall be fabricated with the best material and good
workmanship, ensuring effective & efficient operation of the tender. All wiring shall be
properly fixed in position & be protected against heat, oil & physical damage and wherever
necessary wiring shall be passed through PVC sleeves. All important electrical circuits
shall have separate fuses suitably indicated & grouped in a common fuse box located in an
easily accessible position. Drag Hook or eye of adequate strength & design shall be
provided at the rear and front of chassis.
Vehicle Chassis
The purchaser shall free-issue the vehicle chassis. The chassis shall be collected by the vendor from IPRC, Mahendragiri, Tirunelveli District, Tamilnadu after producing BG for the value of the chassis. The value of the chassis is Rs.16,10,000/- (Sixteen Lakh Ten thousand ) only. The BG shall be valid till the delivery of the fire tender at IPRC.
After body building, the fire tender shall be handed over to the Purchaser at IPRC, Mahendragiri, Tirunelveli Dist, Tamilnadu by the vendor.
Documents to be submitted
Vendor shall submit documents like detailed drawing of the vehicle including load
distribution, computation of CG of the vehicle with full load and empty condition,
overall dimensions & part numbers of major components, including MAKE and
MOC of parts, before commencement of fabrication. For detailed list of
documentation, please refer to Annexure-C
Delivery period: The vendor should deliver the finished fire tender within SIX
months from the date of receipt of approved drawings from IPRC, Mahendragiri.
Water Tank
The water tank shall be of 6000 Lts capacity made out of SS 304 L grade
having 5mm thick sheet for bottom ,4 mm thick sheet for other sides and 3 mm thick sheet
for baffle plates complete fitted on the chassis so as to allow full flow of water to pump.
Material for pipes and fittings shall be A312 TP 304 & A403 TP 304 respectively. The tank
shall have baffle plates in longitudinal direction to avoid surge when the vehicle is braking,
accelerating and cornering. Tank shall be mounted on the chassis in a manner keeping in
view the proper load distribution of the axles. The baffles shall be arranged in a manner to
facilitate the passage of a man throughout the tank for cleaning purposes. Tank shall be
mounted on three cross bearers to counteract stresses caused by chassis flexing and shall
be so secured that it can be removed. The bolting shall be so designed and mounted as to
bring the centre of gravity off set the as low as possible. Tank shall be rectangular in shape
and the mounting of the tank also shall be flexible type to prevent the tank’s distortion due
to the chassis flexion. The mounting shall permit full contents of the tank flow into the
pump. Welding of the tank shall be carried out by GTAW process. All welding area shall be
smoothened. Water fill test shall be conducted and the tank shall be cleaned and dried
before integrating with the chassis.
An inspection manhole of not less than 450mm size shall be provided on the top the
tank and shall have a hinged cover so that the manhole shall also act as a filing orifice.
Cover shall be marked “WATER”.
Suitable eyes shall be provided on the shell of the tank to enable it to be lifted off
the vehicle for repairs/replacement as necessary.
A cleaning hole of 250 mm dia shall be provided at the bottom of the tank. The
cleaning hole shall be fitted with a 25mm dia drain pipe with a valve & plug connection and
shall be taken down to a point well below the chassis without reducing the effective ground
clearance.
The tank shall be fitted with a minimum 75mm bore overflow pipe taken down to a
point well below the chassis without affecting the effective ground clearance when fully
loaded and discharge away from the wheels. A 63 mm instantaneous hydrant connection
incorporating a strainer shall be provided close to the pump panel control for filling the tank
through 80mm bore pipe work for feeding the hose reel equipment. An 80mm pipeline shall
be taken from the tank to the suction inlet of the pump incorporating an 80mm quick action
spherical type valve. Drain plugs shall be provided. LED Electronic Level gauge shall be
provided at the control panel calibrated to ¼. ½, ¾ & full & water level indicator shall be
provided at suitable location on panel near operator controls.
The tank shall be connected with the pump and hose reel in such a manner that
pressurization of water tank or water tank pump connection is not possible when pumping
water from an outside source of supply. The plumbing between the pump and the hose reel
shall have a clear unobstructed waterway of not less than 25mm throughout without any
obstruction.
Foam tank
A foam tank of a 2000 Lts capacity shall be suitably mounted on the chassis. The
tank should be fabricated out of plates of SS 304 L grade, having 5mm thick sheet for the
bottom and 4mm thick sheet for sides, top and 3 mm thick sheet for baffles. The tank shall
be of welded construction having suitable eye hooks on the shell of the tank to enable it to
be lifted off from the chassis for maintenance purpose. The tank shall be provided with
baffle plate to prevent surging and adequate arrangement of suitable size for filling of tank.
A suitable sump with drain valve shall be provided at the bottom. One breathing valve shall
be fitted to the tank which shall work both way ie, at the time of filling the tank and drawing
the foam compound when the unit is in operation. Necessary pipelines shall be provided
for feeding the foam compound to the inductor. Metallurgy of all foam compound carrying
pipelines and components shall be compatible with AFFF concentrate. A level indicator
shall be provided for the foam tank.
Foam transfer pump
A suitable hand operated foam transfer pump shall be provided for transferring the
foam compound from drums to foam tank without causing any frothing in the tank.
Necessary connections for transfer the foam compound into the tank shall be provided from
the pump.
Main pump
CE marked /UL listed fire tender specific Fire pump having multi pressure discharge
capacity of 3000 LPM @ 7 kg/cm2 & 300 LPM @ 35 kg/cm2. The pump body shall be
made of high strength light weight Aluminium alloy with SS high tensile pump shaft & shall
be carried in anti friction bearings. Impeller shall be made out of bronze. Shaft seal shall be
of self-adjusting, maintenance free mechanical type. Pump shall be designed to operate in
both High Pressure – Low pressure modes simultaneously and independently. Both the
Impellers shall be mounted on single shaft.
The delivery outlet of pump shall be connected to monitor and 4 Nos. screwed 63
mm delivery female outlets instantaneous type with blank caps at the rear side along with
twist type lugs made of gunmetal. The monitor & other outlets shall be fitted with lever
operated valves. The pump shall have one suction inlet of minimum 100 mm size on rear
side & shall be provided with easily removable strainer. The pump shall be fitted with a
high pressure relief valve that shall operate automatically when the water pressure exceeds
design value. The pump shall also have a thermal relief valve, which shall operate if the
water temperature inside the pump exceeds design value.
Note : Brand/make of the pump, catalogue, performance curves and MOC of each
parts must be enclosed along with offer.
Primer
The main pump shall be fitted with twin piston reciprocating type primer. The primer
shall be capable of lifting water from 7 m at a rate of not less than 23 sec.
Note : Brand/make of the primier must be indicated in the offer.
Ultra High Pressure (UHP) PUMP (Auxiliary Pump)
An additional auxiliary pump shall be provided & shall be of 150 LPM @ 100 kg/cm2
capacity. The pump shall be a six plunger positive displacement type working to the
capacity at not more than 1000 RPM. A by-pass for letting the water back to the tank shall
be provided to release excess pressure generated due to shutting off the hand lines or
while discharging 150LPM @ 40 kg/cm2 or 75 LPM @ 100 kg/cm2 individually. The pump
shall be guaranteed for a minimum life of 5000 hours of operation. The pump shall have
double seal on each plunger with low pressure intermediate chamber to keep the water
seals cool & lubricated. This system shall also permit to re-circulate any leakage from the
high pressure back to pump inlet. The pump shall have pistons made of ceramic material.
The connecting rods shall be of an alloy which has low attrition co-efficient, high wear
resistance & high anti-seize up properties. Hydraulic structure should be designed to
simplify scheduled maintenance procedures (gasket & valve replacement). The pump
suction line shall have inline mesh filters. The pump shall deliver water to hose reel &
cooling system. The main components of the construction should be manufactured by the
pump manufacturer only. The pump shall be CE marked/UL listed.
Note : Brand/make of the pump, catalogue, performance curves and MOC of each
parts must be enclosed along with offer.
Hose Reels
Two high pressure hose reels with1x20mmx30 m and 1x20mmx 60 m
long shall be provided to facilitate operation of the Main Pump & shall be mounted so as to
be easily accessible. Working pressure of hose shall not be less than 40kg/cm2. The hose
reel shall be fitted with fog and jet gun. The Ultra High Pressure Pump (UHP pump) shall
operate through a separate hose reels of 60 m length – 2 Nos. which shall be provided at a
suitable place on the appliance. The hose used for the hose reel should be rated for 130
kg/cm2 working pressure (180 kg/cm2 test pressure) & shall be of minimum 16mm ID. It
shall have auto rewinding system. At the discharge end of the hose reels, high pressure
mist nozzle shall be provided which shall be capable of discharging 75LPM @100 kg/cm2
pressure in mist pattern. The jet range shall not be less than 20 m and the size of water
drop lets in the spray form shall be less than 250 microns at an angle of 45º.
Power Take Off (PTO) Unit for Main Pump
Heavy duty full torque PTO unit shall be fitted behind the engine gear box, to drive
the pump at the rear. The lever of the PTO unit shall be fitted in the driver’s cabin. A
suitable cooling system (copper coil) shall be inbuilt in the PTO to cool the oil in the PTO.
Maximum through torque of the PTO shall not be less than the maximum through torque of
the chassis engine. The PTO shall be connected to the chassis gear box & the pump
through heavy duty propeller shafts and centre bearings etc.
Note : Brand/make of the PTO must be indicated in the offer.
PTO unit for Auxiliary pump
The auxiliary pump shall be driven with the help of the side PTO provided by the
chassis manufacturer. If not provided, the party should provide the side PTO. The
connection from the side PTO shall be such that the pump does not put stress on the main
driving components and at the same time does not stress the engine also. Cooling for the
engine shall also be suitably provided.
Cooling system for the chassis engine
Indirect cooling system of open circuit type consisting of a special heat exchanger
shall be provided on the chassis to enable full power output to be maintained during the
pumping out without overheating.
Automatic Foam Proportioning System
Automatically governed around the pump proportioner inductor type shall be
provided between suction and delivery of the pump to induct 3% foam solution in the water
stream with no loss in delivery pressure from the pump. Automatic foam proportioner can
induce foam liquid proportionally to water discharge, for using monitor and any number of
foam branches in combination. Manual adjustment must be possible on proportioning.
Water – Foam Monitor
Water foam monitor made up of gun metal with aluminium alloy having discharge
capacity of 3000 LPM @ 7kg/cm2 duly treated with anticorrosion treatment shall be
mounted on the top of the appliance in such a manner that it can be manually operated by
a crewmember. The monitor shall be capable of traversing through 360º in horizontal
plane. Elevating from horizontal to 45º & depressing from horizontal to not less than 15º &
full rotation in both directions. The monitor shall be capable of projecting the foam
discharge to an effective distance of not less than 45 to 50 m in still air when operated at
design pressure. Monitor shall be provided with Jet-spray type Nozzle.
Note : Brand/make of the Water-Foam monitor must be indicated in the offer.
Water – Foam piping
All piping shall be sized so as to have minimum pressure drop & achieve the
required pressure & flow at various locations. All pipe fitting & valves (except butterfly
valves) shall be SS304. All piping shall be designed for 10% over the maximum pressures
encountered in the pipe. The piping shall be flanged for ease of maintenance. All lines
shall be hydraulically tested at 1.5 times the design pressure however in no case shall the
lines be hydraulically tested below 18 kg/cm2. All lines shall have suitable supports so as to
provide rigidity & avoid vibrations. All lines less than 38mm size shall be socket welded.
All lines above 50mm size shall be butt-welded with full penetration welds. All bolting shall
be of SS 304. The draw off pipe shall be provided in such a manner & in such a position
that sludge does not pass into foam piping. Necessary hydro test certificate shall be
provided.
Control Panels
Adequate illuminated pump operating control panel shall be provided on the rear
side of the Fire Tender. All controls of the system shall be spaced properly & marked for
easy operation. All valves shall be of lever operated type and shall be made of SS with
Teflon seats. All other controls like electrical siren, PA system and VHF base station shall
be provided at driver’s cabin. All control panels shall have clearly written operating
instruction plate.
Further following also to be provided on rear side or near control panel
Level indicators for water tank and foam tank
Compound gauge, normal pressure and high pressure gauge
Auxiliary throttle control of the engine
Cooling water circuit control
Hydrant connection for water tank filling pipes
Delivery outlets of the pump along with blank cap with chain
Suction inlet of pump along with black cap with chain
Operating instruction plate and flushing out instruction plate
Control for water tank to pump valve
Control for flushing out piping
- Pump to hose Reel
- Hydrant to Hose Reel
- Pump to Monitor
Light point for pump panel
Drain valve
In addition to the items mentioned above, any other items that may be essential shall also
be provided. Any of these items, which are also required in the driver’s cabin, shall be
provided at suitable locations.
Body work & Stowage
The cabin shall be designed, fabricated for better & wide vision, enough working
room inside the cabin & to have enough aesthetic value. Enclosed accommodation for six
to eight persons shall be provided in the driver cab-cum-crew compartment including the
driver and the in-charge of the crew. The cabin shall be double compartment without
partition. The driver seat & Fire crew leader seat shall be of an adjustable type (free
adjustable). All the seats shall have foam cushion and shall be covered with best quality
Rexene. Provisions shall be made to store BA sets in the back rest of the driver, officer
and the crew seats with suitable clamps and brackets where the BA set (2sets) ,single
cylinder shall rest and shall not be kept in a hanging condition. Two doors on each side
shall be provided on the driver cab cum crew compartment. Doors shall be fitted with
safety glasses and be of horizontally sliding type window. The wind screen glass shall be
toughened glass. The glasses on all the windows and doors shall be fixed in aluminum
sections & shall be fitted on rubber beading including wind screen glass to absorb the extra
pressure / jerks when the fire tender is moving. The sliding glasses shall be provided with
spring loaded locks operated from inside the cabin. Below the crew seat, space shall be
provided for storage of equipments like spare cylinders of the BA set of the same capacity,
mechanical tools etc. The doors shall be hinged type opening outwards, hung forward,
catch locks and flush type handles. Also six hangers for fire man’s helmets above crew
members sitting arrangement shall be provided.
The cabin and the lockers shall be of composite construction with sufficient rigidity,
reinforcement and as far as possible 32mm x 32mm x 2mm thick M.S. square tube of
sufficient strength shall be used for the super structure. 16 gauge aluminum sheets shall
be used for exterior paneling work all over. For inner lockers-walls 18 gauge aluminum
checkered sheet shall be used. 2 mm thick aluminum checkered plate shall be used on all
lockers and cab floors and top roof.
Lockers shall be provided for secure stowage of all accessories and equipments
provided with Fire vehicle. The lockers doors shall be provided with Aluminium rolling
shutters. All equipment shall be stowed very scientifically & systematically in the lockers
and each piece of equipment shall have its designated location so that at the time of
Emergency the required equipment can be very easily located & removed for use. Location
of equipment (labels) shall be provided on lockers for immediate identification. Each
equipment shall be properly clamped and strapped in the lockers to prevent shifting of the
equipment while the vehicle is in motion. The lockers shall have smooth operation. Locker
doors shall be equipped with electric switch to provide automatic switch on/off compartment
lights. All the space below the rear body and chassis shall be utilized for making lockers for
storage of equipment. These lockers shall be covered with flap type doors opening
downwards. Heavy duty chains and hinges shall be provided on these doors so that these
doors when open can be used as climbing steps for access to the lockers above it. Guide
rails over entire length on both sides shall be provided.
Suitable arrangement shall be provided to carry four 2.5 m, 4 nos. of suction hoses
in convenient location on top of the vehicle. Also one through locker behind crew cabin to
be provided where one side stowage for portable pump and other side stowage for various
equipments with drawer type latest arrangement to be provided.
Base Frame & Super structure:
MS (surface treated) tubular/square pressed sections of minimum 3 mm thickness
shall be used.
No welding shall be attempted on the vehicle chassis.
MS frame made from ISMC 100 (minimum) shall be clamped to the vehicle chassis.
All parts of the fire tender like tanks, pump, ladders, stowage cabins etc., shall be derived
only from this base frame. The above said MS frame shall be sand blasted and suitably
surface treated as per approved codes and norms.
The entire super structure shall be of aluminum pressed and profiled sheets.
In case of super structure all fasteners (U clamps, washers, bolts, and studs) shall
be surface treated and suitably hardened.
Other Construction Details
Grab rails & non-slips steps of heavy chequered plate shall be provided wherever
necessary. The entire structure of appliance shall be welded structure made of MS only,
square tubes, angles and channels. The paneling shall be done from 16g aluminium sheet
for outside & 18g aluminium sheet/chequered plate for inside. Complete flooring shall be of
16 gauge aluminium chequered plate. The vehicle shall be covered from top with 16g
chequered plate having rainwater channel at both side. The openings for equipments shall
be sealed properly to ensure no water goes inside. For all water fittings necessary
arrangement shall be made to enable the operator to locate the desired equipment instantly
& thereby save valuable time at the time of fire. This arrangement shall be such that none
of the items damage the internal paneling & thereby increase the life of the vehicle.
Suitable clamps, brackets, holders etc. shall be provided for all other items.
Ladder gallows
Gallows shall be provided to carry a 10.5 m trussed type extension ladder. The
design shall be such that the ladder can be released without difficulty from a reasonably
accessible position & shall embody rollers to permit easy withdrawal by one man. Means
shall also be provided for locking the ladder when stowed. The ladder shall be CE marked
as per JCDD 10 standard/IS: 4571.
Public address system and VHF base station
Battery operated lighting bar and Multi-tone hooters/mike with amplifier shall be
provided. A light bar operated with battery, having hooter & PA system in built amplifier
and a microphone and VHF base station shall be provided in front of officer’s seat in the
driver’s cabin.
Note : Brand/make of the PA system and VHF base station and catalogue must be
enclosed along with offer.
Electrical System
All important electrical circuits shall have separate fuses suitably indicated & shall
be grouped into a common fuse box located in an accessible position in Driver’s cab and
fitted with means for carrying spare fuses. All the wiring shall be dipole & properly fixed in
position and not be exposed to the atmosphere for protection against heat, oil & physical
injury. Conduits shall be used wherever necessary.
All equipments lockers shall have individual lights and these shall be
operated by means of a master switch (two way) on the dash board in the driver’s cabin as
well as from the local ie. from lockers.
The switch of the siren shall be provided on the left corner of the dash
board. (Near from left side)
Two fog lamps shall be suitably attached to the front bumper of the
appliance. Reverse lights with on-off buzzer, on either side shall be fixed suitably.
At the rear of the appliance with wire mesh in such a manner to prevent accidental
damage by the firemen while mounting the tank top.
Accessories
The vehicle shall be provided with the following accessories in addition to those
normally fitted to the chassis.
Reversing lights-lamp suitable to assist reversing 1set
Tools – All tools required for normal routine maintenance of fire tender
excluding the kit for the chassis
1set
Search light with rechargeable battery and charger – Adjustable to give flood
or beam light, mounted in convenient position with a beam range of 500 m.
1 No.
Tail lamps – Two of combined stop and tail 1set
Rear reflectors 1set
Adjustable spot light 1 No.
Portable inspection lamps 1 No.
Public address system and light bar LED 1 No.
Fire siren shall be mounted externally and shall be capable of being operated
from within driving compartment
1 No.
General requirements
The vehicle shall conform in all respect of the provisions contained in the M.V. Act
1988 and M.V. Rules 1989 or to any other statutory modifications or re-enactments thereon
from time to time. All the equipment necessary for RTO.’s clearance shall be provided on
vehicles.
Instruction Book, Accessories & Equipment
Instruction books for the guidance of the user, including both operating and normal
maintenance procedure shall be supplied. The book(s) shall include illustrated spare parts
giving reference numbers of all the wearing parts.
Dry Chemical Powder System (DCP)
The quantity of supplementary extinguishing system shall be 2X50 kg of Dry
Chemical Powder & conform to IS: 4308 – 1982. 50 kg Capacity Dry Chemical powder fire
extinguisher shall be provided at the convenient position on the appliance. Dry chemical
powder extinguisher system shall have 5 m high pressure hose with pistol type discharge
nozzle. The dry chemical powder vessel shall be fitted with CO2/N2 cylinder for expelling
dry powder. Extinguisher shall be ISI Marked and Expellant cylinder shall be approved by
Chief Controller of Explosives (CCE), Petroleum and Explosives Safety Organisation
Note : Brand/make of DCP cylinders must be mentioned in the offer.
CO2 System
2 x 22.5 kg capacity CO2 cylinders connected with one manifold of two cylinders
shall be provided with hose reels for CO2 discharge, reel fitted with 15 m long high pressure
hose. These cylinders shall be placed in lockers at a convenient position in the tender.
CO2 cylinders shall have CCE, PESO, Nagpur approval and ISI Marked.
Note : Brand/make of CO2 cylinders must be mentioned in the offer.
Annexure –A
Schedule of Equipment to be supplied with the appliance
Note : Brand/make of equipment, wherever applicable must be mentioned in the offer
1 Trussed type Extension Ladder 10.5 m as per JCDD 10 / IS:4571 1 No.
2 PVC suction hoses 100 mm dia in 2.5 m length fitted with round
threaded make and female couplings, heavy duty, made of
copper alloy of 100mm size conf. to IS:902
4 Nos.
3 Delivery hose 63 mm dia conforming to IS:636 type – B with ISI
Mark in 15 m. Length fitted with GM 63mm male & female instant
couplings IS:903 (hose & couplings are ISI Marked )
10 Nos.
4 Suction Metal strainer, 100mm size for item 2 1 No.
5 Basket strainer 100mm size for item 2 1 No.
6 Dividing breaching 63 mm with control valve made of light alloy
gunmetal
1 No.
7 Collecting breaching 63mm size made of light alloy gunmetal 1 No.
8 Wrenches for 100mm suction couplings Universal type 1 No.
9 Long line 50mm manila 30 m long IS:2080 1 No.
10 Short line 50mm manila 15m long IS:1084 1 No.
11 Hose bandages , rubberized IS:561 (Part 2) 10 Nos.
12 Hose clamps IS: 5612 (Part 1) 6 Nos.
13 Hydrant valve key and bar 1set
14 Gunmetal branch pipe Universal 63mm size 1 No.
15 Gunmetal branch pipe with revolving head 1 No.
16 Gunmetal short branch pipe complete with 63mm size male
instantaneous connection with gunmetal detachable nozzle as per
IS:903 (ISI Marked)
2 Nos.
17 Gunmetal nozzle of sizes 12mm, 16mm, 20mm ,25 mm and
32mm (2 Nos. each)
10 Nos.
a. Adaptor for 100 mm suction female screw coupling and 63mm
male inst.
1 No.
b. Adaptor double female instantaneous patter 63mm. IS: 901- 1 No.
1975
c. Adaptor double male instantaneous patter 63mm. IS: 901-1975 2 Nos.
18 Nozzle spanner 2 Nos.
19 Portable electric box lamp with rechargeable accumulator 2 Nos.
20 Hand lamp (torch – 4 cells) 2 Nos.
21 First aid box for 10 persons 1 No.
22 Hand gloves-heat and electric resistant, CE marked 2 pair
23 Asbestos gauntlets 1 pair
24 Fireman axe with belt and pouch tested at 20,000 V as per
IS:927
1 No.
25 Spade 1 No.
26 Fire beater 1No.
27 Pick axe 1 No.
28 Crow bar as per IS 704:1968 1 No.
29 Sledge hammer 6.5 Kg as per IS:841 1 No.
30 Power driven saw 1 No.
31 Hydraulic jack – 20 ton 1 No.
32 Fire Hook IS:927/1981 1 No.
33 Tool kit 1 No.
34 5 KVA portable generator- 4 stroke, petrol engine 1 No.
35 VHF base station 1 No.
Annexure-B
Inspection details
Inspection Procedures for water and foam tanks and related piping
The following test procedures shall be followed for the tanks
1. Approval of Welding Procedure (WPS) and welder qualification (PQR) as per
ASME
2. Review of Mill Test Certificates (MTC) and check on stamping of plates flanges &
nozzle and before start of fabrication
3. 100 % DP test of all socket welds and 25% X-Ray radiography of butt welds
4. DP test of all nozzles to shell (i.e) reinforcement pads for water and foam tanks
5. Visual and dimensional check of water and foam tanks before mounting on chassis
6. Water fill hold test of completed water and foam tanks at atmospheric pressure for
24 hours.
7. Hydrostatic test at 1.5 times design pressure for 30 minutes for pipelines
Inspection Procedures for Water pump and UHP Auxiliary pump
The following test procedures shall be followed for pump
1. Review of MTC for material of casing, impeller, shaft and mechanical seal
2. Review of manufacturers Test report for dynamic balancing of impeller, Hydro test
of casing and performance of pump for characteristic curves as per code
3. Performance testing of pump for duty point conditions including four-hour
mechanical run test (including noise & vibration measurement).
4. Parameters at maximum and minimum allowable speeds to establish performance
curves at these speeds
5. Visual and dimensional check
6. Performance test of primer (Main and auxiliary) at rated conditions
Inspection Procedures for Foam cum Water Monitors and valves
1. Review of MTC
2. Hydro test at 1.5 times design pressure. (if applicable)
3. Availability of the specified flow, throw and pressure of water and foam as per
specification.
4. Performance testing of valves and Monitor to establish the performance at rated
output.
Inspection Procedure for PTO units
All standard tests as specified by the PTO supplier
1. Review of mill test certificates for material of construction
2. Four-hour mechanical run test along with the pump on test bench with shop driver
3. Visual and dimensional check
Note: All the above inspections and tests shall be carried out at pump manufacturer’s shop
prior to dispatch. Stage inspections shall be carried out to review the internal documents
for the tests carried out by the manufacturer from time to time and be witness to the critical
test being carried out by the vendor during the final stage inspection.
Inspection Procedure for Fire Tender
The following test procedures shall be followed for Tender
1. Review of mill test certificates and Visual inspection of raw materials for framework,
cladding, flooring, fasteners etc. used for structure and body fabrication before start
of fabrication.
2. Inspection of framework (for cabin & body) for soundness of welding and fitment of
chassis and dimensional check including 10% DPT.
3. Inspection for proper installation of pumps, tanks, piping with supports and their
dimensional checks.
Inspection Procedures for completed vehicle
The following test procedures shall be followed for completed and fully laden fire tender
1. Check on actual payload on chassis, performance of engine, PTO engagement,
transmission and electrical systems at full load
2. Dimensional check, ground clearance check and suspension effectiveness.
3. Fire tender performance test Maximum speed, acceleration, turning radius and
grade ability test as per codes (NFPA1901/IS)
4. Vehicle sturdiness test (NFPA1901) – Cab interior sound level test, low and rated
voltage electrical system test, service and auxilary braking test.
5. Stability test: The stability of the appliance shall be such that when under fully
equipped and laden condition, if the surface on which the appliance stands is titled
to either side, the point at which over turning occurs is not passed at an angle of 27º
from horizontal.
6. Road test of vehicle to ensure all parameters are as specified by chassis
manufacturer for 15kms of paved and 8 kms of gravel road
7. Pump endurance test: The rating of pump shall be minimum 4 hrs. The pump
shall be tested for a continuous period of four hours non stop and the water shall
not be replenished in the radiator during this test. The engine shall not show signs
of over heating during this test. Test for water pump and associated equipment
while discharging water from water monitors and outlets individually and in
combination
8. Priming test: The priming shall be tested as per the latest standards and the
system shall be subjected to a test at a suction of 7 m. The priming shall be
achieved in less than 23 seconds.
9. Shower test: After completion of the fabrication, the vehicle shall be subjected to
shower test as per the norms laid down under BIS. The appliance shall not show
any signs of leakages during this test.
10. Foam proportioning system tests.
11. Functional testing of each hose outlet individually and in combination
12. Tests related to condition monitoring of pumps & shafts.
Stage wise inspection details for Fire tender
Stage – 1
After completion of understructure
i. Verification of material test certificates (MTC), components / subassemblies
identification, before fabrication
ii. Check dimensions of understructure on chassis, fabricated components as per
specifications & approved drawings
iii. Verification of all manufacturers / fabricators document including documents of
imported items
iv. Approval of welding procedure (WPS) welder qualifications (PQR) as per relevant
ASME codes / standard.
Stage - 2
After completion of paneling
i. Check overall dimensions, body work, cab interior fittings
ii. Verification of UT / Radiography/ DP test of SS / CS plates and nozzles of foam and
water tank, DCP vessel as applicable as per relevant procedure and standards
iii. Verification of NDT records of butt welded joins as per ASME sec.-V, (X-ray
radiography 25% for tanks & pipelines).
iv. Check construction details of water tank and foam tank and carry out water fill hold
test at atmospheric pressure. Check all piping fittings, internals, bolts & nuts of the
tanks for material. Leakage test for both the tanks for 24 hours. Check all piping
hydraulic test pressure of 18 kg/cm2 for a minimum 30 minutes
v. Check location / placement of control panel, instruments, controls, other equipment
& accessories etc.
vi. Test power take off units (PTO)
vii. Test the foam induction & foam compound proportionate system
viii. Verify monitor position and its movements
ix. Carryout hydrostatic test of pump (centrifugal) as per specification.
After completion of fitment & painting
i. Check stability of the unit after mounting all equipment and accessories. It should
be free from undue rattling and vibration
ii. Each appliance shall be clearly and permanently marked
iii. Check proper functioning of all types of signal lights, alarms, Bell etc.
iv. Check quality of workmanship
v. Painting of exterior / Interior of Foam Tender, Fire service Insignia conforming to
IS/IPRC norms.
vi. Check completeness of equipment for any deficiency in quantity to standard quality
or non-conformation to specification should be rechecked
vii. Check calibration of instruments, gauges, tools, accessories etc.
viii. Check operation of various levers, locks, caps, fitment of tanks, linkages, markings
and plumbing work
ix. Check storage space for adequacy.
Performance test
The following Performance test shall be carried out at vendor’s site
i. Pump Test: the pump shall be run for a period of four hours nonstop delivering the
rated output with a lift of 3 m. During the test all parameters like cooling system,
temperature of the engine oil, PTO sump oil temperature shall match as per
manufacturer’s recommendation
ii. Vehicle tests as defined in Annexure-B
iii. The pump casing and impeller shall be subjected to a hydraulic pressure 1.5 times
of maximum operating pressure to detect leakage performance etc.
iv. Priming Test: The primer shall be capable of lifting water at least 7m in less than 23
seconds.
v. Hose Reel: Performance shall be tested as per tender specification
vi. Foam making system
Introduction 3% at all five settings
Throw 40/20 m Monitor / branch
Expansion 8 time monitor & branch
vii. DCP system - Complete operation including flushing (DCP and N2 gas to be
provided free of cost by vendor for this test)
Functional test & Road test
Functional test & Road test shall be carried out as mentioned under “Inspection Procedure
for Completed vehicle”.
PROCEDURE FOR MECHANICAL CLEANING, DEGREASING, PICKLING,
PASSIVATION & PAINTING
SS TANKS (WATER & FOAM)
Mechanical cleaning
All metallic surfaces inside and outside having scales and foreign materials and
all welded surfaces have to be cleaned. This can be done by scrubbing with metallic brush
(stainless steel) followed by buffing to get a polished surface. The loose scales and
powders obtained from the above process can be cleaned by blowing, sucking or washing
with water. Mechanical cleaning and buffing shall be carried out after stress relieving but
before hydro test.
Pickling and passivation
Pickling and passivation shall be carried out as per the following method for the tanks after
buffing and hydro testing
Tank outer surface Tank inner surface
Swabbing method using Barium Sulphate Filling / Swabbing method
as an acid carrier
Method for Degreasing, pickling and passivation:
Degreasing
Degreasing has to be done by soaking with hot detergent solution of Lissapol at 60deg C to
70 deg. C for at least 2 hours till satisfaction.
Pickling
Pickling is to be carried out with solution containing Nitric Acid 15% by volume, hydro-
fluoric acid (HF) 2% by volume and balance potable water
Temperature : Ambient
Duration : 1 to 2 hours
Rinsing
Thorough potable water rinsing has to be carried out until all traces of acid are removed
from the surface.
Passivation
Passivation is to be carried out with solution of Nitric Acid 20-25% by volume and balance
potable water
Temperature : Ambient
Duration : 2 hours
Thorough rinsing with potable water has to be carried out until pH of the final rinse water is
between 6.5 to 7.5 to minimize residual stain. Surfaces must not be permitted to dry
between successive steps of the acid cleaning or passivation and rinsing procedures.
The concentration of iron should not exceed 5% by weight in case of pickling solution and
2% by weight in case of passivation.
Preparation of paste for Swabbing Method
The pickling and passivation of the outer surface shall be done with a solution as described
above and barium sulphate as carrier (chloride level <25ppm) in the form of paste. For
each of pickling and passivation operations, the paste has to be applied on the surface and
has to be kept for at least two hours. Paste has to be removed with waste cotton in each
operation and finally the surface has to be rinsed with potable water.
Checking
All the relevant tests shall be carried out to ensure proper pickling and passivation as per
ASTM A 380
Painting
a. All stainless steel plates, sheets, pump parts shall be suitably pickled & passivated
by means of filling / swabbing method
b. All metal surfaces including steel material shall be applied with a coat of epoxy
primer of minimum thickness 100 ± 10 microns followed by polyurethane finish paint
(of fire red colour – shade No. 536 of BIS-5) of minimum thickness 50 ± 10 microns,
so that to get an overall Dry film thickness (DFT) of minimum 160 microns.
c. The Chassis and under carriage including support legs of water tank shall be
applied with suitable anti-rust intermediate primer (Zinc chromate).
Annexure-C General conditions Inspection
Stage wise inspection and Pre-delivery inspection will be done by IPRC/ISRO Engineers at various milestone / stages as defined in the Annexure-B.The supplier shall provide at least one week advance intimation for participation in the testing.
Guarantee
The manufacturer shall guarantee the design, material workmanship and the
performance of the complete unit for a period of 18 months from the date of
delivery of completed vehicle. Any mechanical defect, faulty workmanship or
operational defects found during this period shall be rectified by the vendor at
owner’s premises within reasonable time without any extra cost to the buyer
(including transportation).Performance Bank Guarantee certificate to the extent
of 10% PO value shall be furnished along with supply.
Training
Vendor shall give undertaking to impart a comprehensive training to IPRC fire
service staff on use of Fire tender including operation and maintenance of various
components and accessories supplied along with fire tender, at IPRC, Mahendragiri
premises for a minimum period of one week. Training shall be imparted by
experienced and well-qualified instructors who have got first hand training for above
referred components and accessories.No costs shall be applicable for providing the
training.
Documents
After placement of order
The following documents are required to be submitted in 3 sets and got approved prior to
fabrication. Construction shall be carried out as per approved drawings only.
1. GA and cross sectional drawings of chassis and fire tender
2. Final load distribution and reaction diagram of major elements with respect to axles
3. Characteristic curves and other details of pumps & PTO
4. Flow diagram showing all piping tanks, pumps, valves etc.
5. Fabrication drawing of super structure and base frame
6. Single line flow diagram of water & foam piping systems
7. Line diagram for electrical circuits & schematics
8. Thickness calculation and fabrication drawing of DCP & CO2 vessels and piping.
9. Fabrication drawing of water tank and foam tank
10. Cross sectional and GA drawings for water monitor and valves
11. Cabin layout schematic
12. Drawings showing layout of all equipment, lockers, cabin etc.
13. Quality Assurance Plan for inspection and testing
14. Detailed technical specifications of all elements
15. Catalogues of all major components (pump, PTO, water monitor etc.)
16. Dimensional detail of pump, PTO & water monitor
After Completion of Order
The following documents are required to be submitted (3 sets & 1 soft copy) in the form of
Production Master File (PMF).
1. As built drawings of vehicle under chassis & tender
2. As built drawings of all fabricated tanks, DCP & CO2 systems.
3. Isometric drawing of water & foam pipelines and as built flow diagrams
4. As built drawings of power transmission systems and electrical circuits
5. Operation and Maintenance (O&M) manual and spare parts book of truss ladders,
pneumatic tools, instruments etc.,
6. Operation and maintenance (O&M) manual and spare parts book of instruments,
electronics and electrical items
7. Vehicle documents
8. Manufacturer’s test reports & performance test reports in ORIGINAL of individual
componentS (Pump, Engine, Hose, Monitor, Nozzle etc.)
9. Overall performance test report of Fire Tender
10. CCE Approvals for DCP and CO2 systems
Note : Imported elements, if any shall confirm to EN safety directive/ equipment norms
from country of Origin.
Annexure – D
Format for Quote
Sl.No. Description Brand / Make
If applicable Rate in Rs.
1. Water tank & Foam tank
Material : SS 304L
2. Main water pump
Cap:3000 LPM @ 7kg/cm2 & 300 LPM
@ 35kg/cm2
3. Priming pump
4. Ultra High Pressure pump (UHP)
Capacity : 150 LPM @ 100kg/cm2
5. Hose reels
a. 1 x 20mm x 30m b. 1 x 20mm x 60m c. 2 x 16mm x 60m
6. PTO for Main Water Pump
7. PTO for UHP pump
8. Cooling system for the chassis engine
9. Automatic foam proportioning system
10. Water – foam monitor
11. Control panels and related components
12. Piping systems for both water & foam
13. Accessories as mentioned in the tender
enquiry (9 Items)
14. Stowage Equipment as per annexure –A (35
Items)
15. DCP and CO2 systems
16. Electrical related works
17. Structural work and complete body
construction works
18. Painting
19. Chassis collection and delivery after
completion of body construction
20. Testing of pumps and vehicle
21. Cleaning, pickling and passivation
22. Any other cost
Vendors are free to add any other items and quote accordingly. Brand / make of the
components must be clearly indicated wherever applicable.
INSTRUCTIONS FOR TWO-PART TENDER
I PART I : TECHNICAL & COMMERCIAL BID Part – (a) Technical
i. This part should contain detailed specifications of the items quoted by you along with Technical literature,performance curves for pumps,brand/make of components and catalogue if any.
ii. A compliance statement showing the compliance of the item quoted by you with that of item tendered by us should be prepared and enclosed to this.
iii. Any other information called for in the tender related technical and specifications can also come in this part.
iv. Prices should not be indicated in this cover.
Part – (b) Commercial terms: (WITHOUT PRICES)
i. The commercial terms applicable for the item quoted by you should be indicated in this part.
ii. If any compliance statement is called for the commercial terms / contractual terms and conditions, the same is to be attached in this part.
iii. Prices should not be indicated in this part. However a copy of the price bid (without prices) can be enclosed in this part to enable to understand whether all the items required to be quoted by you have been quoted in the price bid. Alternatively a statement is to be made indicating that you have quoted prices for all the items as per the tender and enclosed in the Price Bid as per the format.
iv. The Commercial terms such as delivery terms, delivery period, payment terms, Warranty, validity of the offer, installation & commissioning, duties and taxes etc., shall come into this.
v. Company’s profile, Fire tenders supplied in the last FIVE years and the purchasers’ address, performance certificate issued by any organization, if any should be enclosed.
vi. Company’s turn over for the last FIVE years in the form of Profit & Loss statement,Audited Accounts Statement and Current financial status should be provided.
II PART II : PRICE BID
i. The prices applicable for the items, item-wise in response to the tender shall come into this part.
ii. Tenderer shall indicate very clearly item-wise prices with reference to their technical offer.