Product Range of application Your advantages The multisensor suction smoke detector Helios TDS is a detection system for earliest fire detection. Helios TDS is an intelligent fire detector with highest sensitivity. It detects smallest concentrations of thermal decomposition products in the sucked air reliably and nuisance-safe. The optionally available fire gas detector GMX1002 CO belongs to a new generation of fire detectors for an even more reliable early detection of burgeoning fires. For the first time – developed by Minimax – there is a fire detector for the detection of smouldering fires available, which reacts on carbon monoxide. Four alarm relays and one mal- function relay with one floating changeover contact each facilitate connection to any fire detection system. Together with the Minimax fire detection control panels, single detector identification can be realized via MxLoop ® ring bus technology. Multisensor suction smoke detector Helios TDS is especially suitable for monitoring air conditioned rooms and other areas, where a reliable early detection is required: - information and communication technologies - electronic and electrical systems - high-quality production systems - clean and super-clean rooms - medical areas - control rooms - suspended ceilings - false floors - cable ducts - cultural assets Immediate detection due to a highly sensitive sensor system High reliability due to new analysis algorithms Optical measuring chamber with laser technology Simultaneous two-channel measurement Multisensor system with optional gas detector GMX1002 CO Sensitivity starting at 0,005 %/m subdueing of light and 5 ppm CO Permanent air flow supervision Automatic adjustment to ambient conditions Intelligent function with 6 sensitivity steps Functional status display Multisensor suction smoke detector Helios TDS Safe for certain. FIRE DETECTION SYSTEMS FIRE DETECTORS VdS

MX Multisinsor suction smoke detector Hilios TDS.pdf

Embed Size (px)

Citation preview

Page 1: MX Multisinsor suction smoke detector Hilios TDS.pdf

Product Range of application Your advantages

The multisensor suction smokedetector Helios TDS is a detectionsystem for earliest fire detection.Helios TDS is an intelligent firedetector with highest sensitivity. It detects smallest concentrations of thermal decomposition productsin the sucked air reliably and nuisance-safe.

The optionally available fire gasdetector GMX1002 CO belongs to a new generation of fire detectorsfor an even more reliable earlydetection of burgeoning fires. For the first time – developed byMinimax – there is a fire detectorfor the detection of smoulderingfires available, which reacts on carbon monoxide.

Four alarm relays and one mal-function relay with one floatingchangeover contact each facilitateconnection to any fire detectionsystem.Together with the Minimax firedetection control panels, singledetector identification can be realized via MxLoop® ring bus technology.

Multisensor suction smoke detectorHelios TDS is especially suitable formonitoring air conditioned roomsand other areas, where a reliableearly detection is required:

- information and communication technologies

- electronic and electrical systems- high-quality production systems- clean and super-clean rooms- medical areas- control rooms- suspended ceilings- false floors- cable ducts - cultural assets

Immediate detection due to a highly sensitive sensor system

High reliability due to new analysis algorithms

Optical measuring chamber with laser technology

Simultaneous two-channel measurement

Multisensor system with optionalgas detector GMX1002 CO

Sensitivity starting at 0,005 %/msubdueing of light and 5 ppm CO

Permanent air flow supervision

Automatic adjustment to ambient conditions

Intelligent function with 6 sensitivity steps

Functional status display

Multisensor suction smoke detectorHelios TDS

Safe for certain.

FIRE DETECTION SYSTEMS

FIRE DETECTORS

VdS

Page 2: MX Multisinsor suction smoke detector Hilios TDS.pdf

The air flow is measured with a volume flow sensor andcompared to the adjusted setpoint value. Deviations(pipe break or choking) of ±10% can already be reliablydetected and release an alarm.

The detector measures the laser light scattering causedby thermal decomposition products at two differentangles and thus, it ensures nuisance-safe detection of burgeoning fires. Four alarm thresholds can be pro-grammed for the entire measuring range, so that Helioscan be individually adjusted to the basic particle load inthe monitoring room.

PB33

eF_0

1/02

.03/

OPH

Prin

ted

in G

erm

any

Technical data

VdSCertfied acc. toISO 9001

★N

r. S

892

01

350

300

250

200

150

100

50

1

Main alarm

Smo

ke /

Gas

den

sity

Alarm thresholdconventional smoke detector

Info alarm

Time

Multi suction smoke detectorHELIOS TDS

Radiation trapLens

Smoke particle

Intake hole

Lens Laser

Air flow

Signalprocessor

Smoke concentrationparticle size

Backward scatter

Forwardscatter

Minimax GmbHIndustriestrasse 10/12 D-23840 Bad OldesloePhone: +49 (0) 45 31 8 03-0 Fax: +49 (0) 45 31 8 03-2 48E-mail: [email protected]

Subject to technical alterations

Function

Multisensor suction smoke detector Helios TDS uses an optical two-channel laser measuring system for qualitative and quantitative smoke particle analysis(twin-detection system). Optionally a CO fire gas detec-tor can be used depending on the monitored fire load.Air probes of the monitored area are sucked via a pipework and supplied to the optical measuring chamber and optionally to the CO fire gas detector of the Helios TDS.

Supply voltage: Nominal voltage: 24 V DC (min. 19.5 V, max. 31 V)

Power consumption: 230 mA (standby)

Ambient conditions: Temperature range:-5 °C to +50 °C (for a short time 55 °C)relative air humidity 96 %, (condensation must be excluded)

Storage: -10 °C to +65 °C,

Weight: 6.1 kg

Dimensions: 546 x 267 x 71 mm (W x H x D)

Noise generation: 49 dB (1 m distance)

Optical system: Infrared diode laser, 785 nm, 2 mW, in double circuit scattered light detection system. Laser class 3A, service life > 15 Jahre

Gas detection system: 1 slot for an optional fire gas detector module (CO), Enhanced multi sensor system analysis (= 3 detection thresholds plus gas alarm threshold)

Detector sensitivity: Detection sensitivity: 0.005 %/m Relative dynamic detection area: 0.005 %/m to 1 %/m

Connections: 24 V power supply4 floating alarm centre-zero relays (max. 30 V / 1 A DC) 1 floating malfunction centre-zero relay (max. 30 V / 1 A DC)1 detector line connection (autom. 9 V line, 2 alarm thresholds, for Minimax fire detection control panel) 1 ring main connection (MxLoop®: 2 alarms + alarm indication are addressable),1 RS232 interface (9-Pol SubD)

Measuring memory: 5,760 entries as ring memory. (volatile memory, RAM)Measured values of the ambient level and system status information

Event memory: 1,010 entries as ring memory (non-volatile memory, EEPROM)Malfunctions, alarms and maintenance information with date and time

Air flow system: Suction pipe: max. system length 100 m, (max. 35 m as single range pipe), up to 1,000 m2 monitoring area. Pipe diameter: typ. 25 mm. Number of aspirating sections: min. 10 to max. 25. Aspirating section diameter: approx. 3 mm. Air flow supervision: programmable sensitivity adjustment. Fan power consumption: 5 W

VdS approval: (Helios: G295044, Helios TDS: pending)