N+1 UPS
N+1, also called parallel redundancy, is a safeguard to ensure that an uninterruptiblepower supply (UPS) system is always available. N+1 stands for the numberof UPS
modules that are required to handle an adequate supply of power for essential connectedsystems, plus one more.
If an enterprise data center uses a single large UPS, and that module fails, systems will bedisrupted. In an N+1 scheme, multiple small UPS modules and batteries are integrated
together. During normal operations, the load is shared equally across all modules, which
behave as if they were a single large UPS device. If a single module fails or needs to be
taken offline for service, the UPS system will still be able to provide an adequate supplyof power because it's already been configured with one extra module.
When N+1 is used for redundancy, the UPS modules should be sized so that the total
anticipated load can be carried by three modules. The benefits of N+1 diminish after thatpoint.
Five tips for N+1 uninterruptible power
supply (UPS) design
By Robin Roy
searchDataCenter.in
Digg This
Stumble
Delicious
N+1 redundancy (or parallel redundancy) is a safeguard to ensure a UPS system's
availability in the event of component failure especially in a tier 2 or a tier 3
datacenter. When considering an N+1 UPS configuration, it's essential to keep in mindthat the UPS' specifications should be outlined keeping in mind criticality of applications
rather than the data center's size.
Tip 1: Ideal scenarios to deploy an N+1 UPS configuration
When it comes to the UPS, it is not enough to have redundancy built into just a single
system. In India, many data centers still use legacy systems. N+1 UPS can be achieved insuch systems using static transfer switches (STS). STS transfers this load to a bypass
source in case of loss of power at the UPS' output. STS can be deployed in front of a
single input load, such that two independent power supplies from two clusters of UPS canbe used to further boost system reliability.
http://searchdatacenter.techtarget.com/sDefinition/0,290660,sid80_gci214161,00.htmlhttp://searchdatacenter.techtarget.com/sDefinition/0,290660,sid80_gci214161,00.htmlhttp://digg.com/submit?phase=2&url=http://searchdatacenter.techtarget.in/tip/Five-tips-for-N1-uninterruptible-power-supply-UPS-design&title=Five%20tips%20for%20N+1%20uninterruptible%20power%20supply%20(UPS)%20design&topic=tech_news&bodytext=Critical%20infrastructure%20calls%20for%20redundancy%20in%20the%20form%20of%20N+1%20uninterruptible%20power%20supply%20(UPS)%20systems.%20Here%20are%20some%20handy%20N+1%20UPS%20design%20tips.http://digg.com/submit?phase=2&url=http://searchdatacenter.techtarget.in/tip/Five-tips-for-N1-uninterruptible-power-supply-UPS-design&title=Five%20tips%20for%20N+1%20uninterruptible%20power%20supply%20(UPS)%20design&topic=tech_news&bodytext=Critical%20infrastructure%20calls%20for%20redundancy%20in%20the%20form%20of%20N+1%20uninterruptible%20power%20supply%20(UPS)%20systems.%20Here%20are%20some%20handy%20N+1%20UPS%20design%20tips.http://www.stumbleupon.com/submit?url=http://searchdatacenter.techtarget.in/tip/Five-tips-for-N1-uninterruptible-power-supply-UPS-design&title=Five%20tips%20for%20N+1%20uninterruptible%20power%20supply%20(UPS)%20designhttp://del.icio.us/post?v=4&noui&jump=close&url=http://searchdatacenter.techtarget.in/tip/Five-tips-for-N1-uninterruptible-power-supply-UPS-design&title=Five%20tips%20for%20N+1%20uninterruptible%20power%20supply%20(UPS)%20designhttp://searchdatacenter.techtarget.com/sDefinition/0,290660,sid80_gci214161,00.htmlhttp://searchdatacenter.techtarget.com/sDefinition/0,290660,sid80_gci214161,00.htmlhttp://digg.com/submit?phase=2&url=http://searchdatacenter.techtarget.in/tip/Five-tips-for-N1-uninterruptible-power-supply-UPS-design&title=Five%20tips%20for%20N+1%20uninterruptible%20power%20supply%20(UPS)%20design&topic=tech_news&bodytext=Critical%20infrastructure%20calls%20for%20redundancy%20in%20the%20form%20of%20N+1%20uninterruptible%20power%20supply%20(UPS)%20systems.%20Here%20are%20some%20handy%20N+1%20UPS%20design%20tips.http://www.stumbleupon.com/submit?url=http://searchdatacenter.techtarget.in/tip/Five-tips-for-N1-uninterruptible-power-supply-UPS-design&title=Five%20tips%20for%20N+1%20uninterruptible%20power%20supply%20(UPS)%20designhttp://del.icio.us/post?v=4&noui&jump=close&url=http://searchdatacenter.techtarget.in/tip/Five-tips-for-N1-uninterruptible-power-supply-UPS-design&title=Five%20tips%20for%20N+1%20uninterruptible%20power%20supply%20(UPS)%20design8/7/2019 N + 1 UPS
2/6
Tip 2: Incorporating system efficiency in N+1 UPS design
Blade servers have high power density, many a time escalating power requirements. For
example, if a normal server setup requires 5 kW, blade servers may push therequirements to 20 kW. Hence you should use a higher power density UPS for
To continue reading for free, register below orlogin
Requires Membership to View
To gain access to this and all member only content, please provide the followinginformation:
Email Address:Become a Member
By submitting your registration information to searchDataCenter.in you agree to receive email
communications from the TechTarget network of sites, and/or third party content providers that haverelationships with TechTarget, based on your topic interests and activity, including updates on new content,
event notifications, new site launches and market research surveys. Please verify all information and
selections above. You may unsubscribe at any time from one or more of the services you have selected by
editing your profile, unsubscribing via email or by contacting us here
Your use of searchDataCenter.in is governed by ourTerms of Use
We designed ourPrivacy Policy to provide you with important disclosures abouthow we collect and use your registration and other information. We encourage
you to read the Privacy Policy, and to use it to help make informed decisions.
If you reside outside of the United States, by submitting this registrationinformation you consent to having your personal data transferred to and processed
in the United States.
Digg This
Stumble
Delicious
Data Center RELATED LINKS
Ads by Google
UPS Power SystemsFor All Your UPS Needs. Great ValueReliable, State-Of-The-Art Productswww.p2roinc.com/UPS
PoweredgeSolutions Phils
Do you need an UPS in the Phils?Than we have a GE UPS for you!www.poweredge.com.ph
http://searchdatacenter.techtarget.in/loginhttp://searchdatacenter.techtarget.in/loginmailto:[email protected]://searchdatacenter.techtarget.in/about/copyrighthttp://www.techtarget.com/html/privacy_policy.htmlhttp://digg.com/submit?phase=2&url=http://searchdatacenter.techtarget.in/tip/Five-tips-for-N1-uninterruptible-power-supply-UPS-design&title=Five%20tips%20for%20N+1%20uninterruptible%20power%20supply%20(UPS)%20design&topic=tech_news&bodytext=Critical%20infrastructure%20calls%20for%20redundancy%20in%20the%20form%20of%20N+1%20uninterruptible%20power%20supply%20(UPS)%20systems.%20Here%20are%20some%20handy%20N+1%20UPS%20design%20tips.http://digg.com/submit?phase=2&url=http://searchdatacenter.techtarget.in/tip/Five-tips-for-N1-uninterruptible-power-supply-UPS-design&title=Five%20tips%20for%20N+1%20uninterruptible%20power%20supply%20(UPS)%20design&topic=tech_news&bodytext=Critical%20infrastructure%20calls%20for%20redundancy%20in%20the%20form%20of%20N+1%20uninterruptible%20power%20supply%20(UPS)%20systems.%20Here%20are%20some%20handy%20N+1%20UPS%20design%20tips.http://www.stumbleupon.com/submit?url=http://searchdatacenter.techtarget.in/tip/Five-tips-for-N1-uninterruptible-power-supply-UPS-design&title=Five%20tips%20for%20N+1%20uninterruptible%20power%20supply%20(UPS)%20designhttp://del.icio.us/post?v=4&noui&jump=close&url=http://searchdatacenter.techtarget.in/tip/Five-tips-for-N1-uninterruptible-power-supply-UPS-design&title=Five%20tips%20for%20N+1%20uninterruptible%20power%20supply%20(UPS)%20designhttp://googleads.g.doubleclick.net/aclk?sa=L&ai=B115XWl9yTbzbMoz_cJm-6dAEys2kmQLq0f2pHsCNtwGg8NMFEAEYASCBjMgZKAQ4AFCLuaSnAWDhpLqFkBqyAR5zZWFyY2hkYXRhY2VudGVyLnRlY2h0YXJnZXQuaW7IAQHaAWJodHRwOi8vc2VhcmNoZGF0YWNlbnRlci50ZWNodGFyZ2V0LmluL3RpcC9GaXZlLXRpcHMtZm9yLU4xLXVuaW50ZXJydXB0aWJsZS1wb3dlci1zdXBwbHktVVBTLWRlc2lnbqkCrWsr4hbSWD6oAwHoA-kF9QMCAADE&num=1&sig=AGiWqtw9ghMbRCx2FnjgVGvg8P5ZF6GhSQ&client=ca-pub-6050985421795229&adurl=http://www.p2roinc.com/http://googleads.g.doubleclick.net/aclk?sa=L&ai=B115XWl9yTbzbMoz_cJm-6dAEys2kmQLq0f2pHsCNtwGg8NMFEAEYASCBjMgZKAQ4AFCLuaSnAWDhpLqFkBqyAR5zZWFyY2hkYXRhY2VudGVyLnRlY2h0YXJnZXQuaW7IAQHaAWJodHRwOi8vc2VhcmNoZGF0YWNlbnRlci50ZWNodGFyZ2V0LmluL3RpcC9GaXZlLXRpcHMtZm9yLU4xLXVuaW50ZXJydXB0aWJsZS1wb3dlci1zdXBwbHktVVBTLWRlc2lnbqkCrWsr4hbSWD6oAwHoA-kF9QMCAADE&num=1&sig=AGiWqtw9ghMbRCx2FnjgVGvg8P5ZF6GhSQ&client=ca-pub-6050985421795229&adurl=http://www.p2roinc.com/http://googleads.g.doubleclick.net/aclk?sa=L&ai=B115XWl9yTbzbMoz_cJm-6dAEys2kmQLq0f2pHsCNtwGg8NMFEAEYASCBjMgZKAQ4AFCLuaSnAWDhpLqFkBqyAR5zZWFyY2hkYXRhY2VudGVyLnRlY2h0YXJnZXQuaW7IAQHaAWJodHRwOi8vc2VhcmNoZGF0YWNlbnRlci50ZWNodGFyZ2V0LmluL3RpcC9GaXZlLXRpcHMtZm9yLU4xLXVuaW50ZXJydXB0aWJsZS1wb3dlci1zdXBwbHktVVBTLWRlc2lnbqkCrWsr4hbSWD6oAwHoA-kF9QMCAADE&num=1&sig=AGiWqtw9ghMbRCx2FnjgVGvg8P5ZF6GhSQ&client=ca-pub-6050985421795229&adurl=http://www.p2roinc.com/http://googleads.g.doubleclick.net/aclk?sa=l&ai=BWq3kWl9yTbzbMoz_cJm-6dAEhqf-zgGO2M6FHcCNtwGQ9eEFEAIYAiCBjMgZKAQ4AFCV98UHYOGkuoWQGqABitfo3QOyAR5zZWFyY2hkYXRhY2VudGVyLnRlY2h0YXJnZXQuaW7IAQHaAWJodHRwOi8vc2VhcmNoZGF0YWNlbnRlci50ZWNodGFyZ2V0LmluL3RpcC9GaXZlLXRpcHMtZm9yLU4xLXVuaW50ZXJydXB0aWJsZS1wb3dlci1zdXBwbHktVVBTLWRlc2lnboACAakCrWsr4hbSWD6oAwHoA-kF9QMCAADE&num=2&sig=AGiWqtwqU83fcOfK9YSmLMxFZZYyGVeizQ&client=ca-pub-6050985421795229&adurl=http://www.poweredge.com.phhttp://googleads.g.doubleclick.net/aclk?sa=l&ai=BWq3kWl9yTbzbMoz_cJm-6dAEhqf-zgGO2M6FHcCNtwGQ9eEFEAIYAiCBjMgZKAQ4AFCV98UHYOGkuoWQGqABitfo3QOyAR5zZWFyY2hkYXRhY2VudGVyLnRlY2h0YXJnZXQuaW7IAQHaAWJodHRwOi8vc2VhcmNoZGF0YWNlbnRlci50ZWNodGFyZ2V0LmluL3RpcC9GaXZlLXRpcHMtZm9yLU4xLXVuaW50ZXJydXB0aWJsZS1wb3dlci1zdXBwbHktVVBTLWRlc2lnboACAakCrWsr4hbSWD6oAwHoA-kF9QMCAADE&num=2&sig=AGiWqtwqU83fcOfK9YSmLMxFZZYyGVeizQ&client=ca-pub-6050985421795229&adurl=http://www.poweredge.com.phhttp://googleads.g.doubleclick.net/aclk?sa=l&ai=BWq3kWl9yTbzbMoz_cJm-6dAEhqf-zgGO2M6FHcCNtwGQ9eEFEAIYAiCBjMgZKAQ4AFCV98UHYOGkuoWQGqABitfo3QOyAR5zZWFyY2hkYXRhY2VudGVyLnRlY2h0YXJnZXQuaW7IAQHaAWJodHRwOi8vc2VhcmNoZGF0YWNlbnRlci50ZWNodGFyZ2V0LmluL3RpcC9GaXZlLXRpcHMtZm9yLU4xLXVuaW50ZXJydXB0aWJsZS1wb3dlci1zdXBwbHktVVBTLWRlc2lnboACAakCrWsr4hbSWD6oAwHoA-kF9QMCAADE&num=2&sig=AGiWqtwqU83fcOfK9YSmLMxFZZYyGVeizQ&client=ca-pub-6050985421795229&adurl=http://www.poweredge.com.phhttp://searchdatacenter.techtarget.in/loginmailto:[email protected]://searchdatacenter.techtarget.in/about/copyrighthttp://www.techtarget.com/html/privacy_policy.htmlhttp://digg.com/submit?phase=2&url=http://searchdatacenter.techtarget.in/tip/Five-tips-for-N1-uninterruptible-power-supply-UPS-design&title=Five%20tips%20for%20N+1%20uninterruptible%20power%20supply%20(UPS)%20design&topic=tech_news&bodytext=Critical%20infrastructure%20calls%20for%20redundancy%20in%20the%20form%20of%20N+1%20uninterruptible%20power%20supply%20(UPS)%20systems.%20Here%20are%20some%20handy%20N+1%20UPS%20design%20tips.http://www.stumbleupon.com/submit?url=http://searchdatacenter.techtarget.in/tip/Five-tips-for-N1-uninterruptible-power-supply-UPS-design&title=Five%20tips%20for%20N+1%20uninterruptible%20power%20supply%20(UPS)%20designhttp://del.icio.us/post?v=4&noui&jump=close&url=http://searchdatacenter.techtarget.in/tip/Five-tips-for-N1-uninterruptible-power-supply-UPS-design&title=Five%20tips%20for%20N+1%20uninterruptible%20power%20supply%20(UPS)%20designhttp://googleads.g.doubleclick.net/aclk?sa=L&ai=B115XWl9yTbzbMoz_cJm-6dAEys2kmQLq0f2pHsCNtwGg8NMFEAEYASCBjMgZKAQ4AFCLuaSnAWDhpLqFkBqyAR5zZWFyY2hkYXRhY2VudGVyLnRlY2h0YXJnZXQuaW7IAQHaAWJodHRwOi8vc2VhcmNoZGF0YWNlbnRlci50ZWNodGFyZ2V0LmluL3RpcC9GaXZlLXRpcHMtZm9yLU4xLXVuaW50ZXJydXB0aWJsZS1wb3dlci1zdXBwbHktVVBTLWRlc2lnbqkCrWsr4hbSWD6oAwHoA-kF9QMCAADE&num=1&sig=AGiWqtw9ghMbRCx2FnjgVGvg8P5ZF6GhSQ&client=ca-pub-6050985421795229&adurl=http://www.p2roinc.com/http://googleads.g.doubleclick.net/aclk?sa=L&ai=B115XWl9yTbzbMoz_cJm-6dAEys2kmQLq0f2pHsCNtwGg8NMFEAEYASCBjMgZKAQ4AFCLuaSnAWDhpLqFkBqyAR5zZWFyY2hkYXRhY2VudGVyLnRlY2h0YXJnZXQuaW7IAQHaAWJodHRwOi8vc2VhcmNoZGF0YWNlbnRlci50ZWNodGFyZ2V0LmluL3RpcC9GaXZlLXRpcHMtZm9yLU4xLXVuaW50ZXJydXB0aWJsZS1wb3dlci1zdXBwbHktVVBTLWRlc2lnbqkCrWsr4hbSWD6oAwHoA-kF9QMCAADE&num=1&sig=AGiWqtw9ghMbRCx2FnjgVGvg8P5ZF6GhSQ&client=ca-pub-6050985421795229&adurl=http://www.p2roinc.com/http://googleads.g.doubleclick.net/aclk?sa=l&ai=BWq3kWl9yTbzbMoz_cJm-6dAEhqf-zgGO2M6FHcCNtwGQ9eEFEAIYAiCBjMgZKAQ4AFCV98UHYOGkuoWQGqABitfo3QOyAR5zZWFyY2hkYXRhY2VudGVyLnRlY2h0YXJnZXQuaW7IAQHaAWJodHRwOi8vc2VhcmNoZGF0YWNlbnRlci50ZWNodGFyZ2V0LmluL3RpcC9GaXZlLXRpcHMtZm9yLU4xLXVuaW50ZXJydXB0aWJsZS1wb3dlci1zdXBwbHktVVBTLWRlc2lnboACAakCrWsr4hbSWD6oAwHoA-kF9QMCAADE&num=2&sig=AGiWqtwqU83fcOfK9YSmLMxFZZYyGVeizQ&client=ca-pub-6050985421795229&adurl=http://www.poweredge.com.phhttp://googleads.g.doubleclick.net/aclk?sa=l&ai=BWq3kWl9yTbzbMoz_cJm-6dAEhqf-zgGO2M6FHcCNtwGQ9eEFEAIYAiCBjMgZKAQ4AFCV98UHYOGkuoWQGqABitfo3QOyAR5zZWFyY2hkYXRhY2VudGVyLnRlY2h0YXJnZXQuaW7IAQHaAWJodHRwOi8vc2VhcmNoZGF0YWNlbnRlci50ZWNodGFyZ2V0LmluL3RpcC9GaXZlLXRpcHMtZm9yLU4xLXVuaW50ZXJydXB0aWJsZS1wb3dlci1zdXBwbHktVVBTLWRlc2lnboACAakCrWsr4hbSWD6oAwHoA-kF9QMCAADE&num=2&sig=AGiWqtwqU83fcOfK9YSmLMxFZZYyGVeizQ&client=ca-pub-6050985421795229&adurl=http://www.poweredge.com.ph8/7/2019 N + 1 UPS
3/6
RF and DC Power Supplies
Vacuum deposition, etching, sputterSold tested with 90 day warranty
www.ptb-sales.com
delta product
Agency many original quality goodsQuantity more preferential
www.szaver.com/en/
Related Content
Data center power and coolingo Data center cabling - Placing and design best practices
o CtrlS tier 4 data center infrastructure: A detailed walkthrough
o Green data center design best practices: Power and cooling approaches
o Preventing a data center power crisis
o Hot aisle - cold aisle design best practices for data centers
o Data center power management at forefront of IT agenda
o Five tips for N+1 uninterruptible power supply (UPS) designo Power-saving design for efficient cost-effective data center infrastructure
o Data center power & cooling strategies that drive Godfrey Phillips
o Avoid common pitfalls when calculating data center power load
Data center planning and layouto Data center cabling - Placing and design best practices
o CtrlS tier 4 data center infrastructure: A detailed walkthrough
o Capacity planning no longer a guessing game
o How to determine the appropriate failover disaster recovery site: hot, cold
or warm
o FAQ: How to select optimal memory, CPU and storage for virtualization
o New requirements for data center infra arise at Manipal eCommerce
o A data center hosting and management outsourcing checklist
o IT wish list: Better ways to analyze data center environmental metrics
o A business continuity management standard would offer consistency
o Cleaning under the raised-floor plenum: Data center maintenance basics
Related Resources
2020software.com, trial software downloads foraccounting software,ERP
software,CRM softwareand Business Software Systems
Search Bitpipe.com for the latestwhite papers and business webcasts Whatis.com, the online computer dictionary
http://googleads.g.doubleclick.net/aclk?sa=L&ai=B1GNpWl9yTbzbMoz_cJm-6dAE4ZKc1gHf1vyNAcCNtwGgwh4QAxgDIIGMyBkoBDgAUIm25Ln7_____wFg4aS6hZAasgEec2VhcmNoZGF0YWNlbnRlci50ZWNodGFyZ2V0LmluyAEB2gFiaHR0cDovL3NlYXJjaGRhdGFjZW50ZXIudGVjaHRhcmdldC5pbi90aXAvRml2ZS10aXBzLWZvci1OMS11bmludGVycnVwdGlibGUtcG93ZXItc3VwcGx5LVVQUy1kZXNpZ26oAwHoA-kF9QMCAADE&num=3&sig=AGiWqtx6J_0zTfQjoCXuau2DEBuR7hB8kQ&client=ca-pub-6050985421795229&adurl=http://www.ptb-sales.com/vacuum/source/http://googleads.g.doubleclick.net/aclk?sa=L&ai=B1GNpWl9yTbzbMoz_cJm-6dAE4ZKc1gHf1vyNAcCNtwGgwh4QAxgDIIGMyBkoBDgAUIm25Ln7_____wFg4aS6hZAasgEec2VhcmNoZGF0YWNlbnRlci50ZWNodGFyZ2V0LmluyAEB2gFiaHR0cDovL3NlYXJjaGRhdGFjZW50ZXIudGVjaHRhcmdldC5pbi90aXAvRml2ZS10aXBzLWZvci1OMS11bmludGVycnVwdGlibGUtcG93ZXItc3VwcGx5LVVQUy1kZXNpZ26oAwHoA-kF9QMCAADE&num=3&sig=AGiWqtx6J_0zTfQjoCXuau2DEBuR7hB8kQ&client=ca-pub-6050985421795229&adurl=http://www.ptb-sales.com/vacuum/source/http://googleads.g.doubleclick.net/aclk?sa=L&ai=B1GNpWl9yTbzbMoz_cJm-6dAE4ZKc1gHf1vyNAcCNtwGgwh4QAxgDIIGMyBkoBDgAUIm25Ln7_____wFg4aS6hZAasgEec2VhcmNoZGF0YWNlbnRlci50ZWNodGFyZ2V0LmluyAEB2gFiaHR0cDovL3NlYXJjaGRhdGFjZW50ZXIudGVjaHRhcmdldC5pbi90aXAvRml2ZS10aXBzLWZvci1OMS11bmludGVycnVwdGlibGUtcG93ZXItc3VwcGx5LVVQUy1kZXNpZ26oAwHoA-kF9QMCAADE&num=3&sig=AGiWqtx6J_0zTfQjoCXuau2DEBuR7hB8kQ&client=ca-pub-6050985421795229&adurl=http://www.ptb-sales.com/vacuum/source/http://googleads.g.doubleclick.net/aclk?sa=L&ai=BBORqWl9yTbzbMoz_cJm-6dAE1ef6hwLt08nZI8CNtwGA86oBEAQYBCCBjMgZKAQ4AFCjh4qCAWDhpLqFkBqyAR5zZWFyY2hkYXRhY2VudGVyLnRlY2h0YXJnZXQuaW7IAQHaAWJodHRwOi8vc2VhcmNoZGF0YWNlbnRlci50ZWNodGFyZ2V0LmluL3RpcC9GaXZlLXRpcHMtZm9yLU4xLXVuaW50ZXJydXB0aWJsZS1wb3dlci1zdXBwbHktVVBTLWRlc2lnbqkCAQVPjy5whD7IAuXS2xqoAwHoA-kF9QMCAADE&num=4&sig=AGiWqty3dB7Alxy6t3GddCLGheSjYKm7ww&client=ca-pub-6050985421795229&adurl=http://www.szaver.com/en/http://googleads.g.doubleclick.net/aclk?sa=L&ai=BBORqWl9yTbzbMoz_cJm-6dAE1ef6hwLt08nZI8CNtwGA86oBEAQYBCCBjMgZKAQ4AFCjh4qCAWDhpLqFkBqyAR5zZWFyY2hkYXRhY2VudGVyLnRlY2h0YXJnZXQuaW7IAQHaAWJodHRwOi8vc2VhcmNoZGF0YWNlbnRlci50ZWNodGFyZ2V0LmluL3RpcC9GaXZlLXRpcHMtZm9yLU4xLXVuaW50ZXJydXB0aWJsZS1wb3dlci1zdXBwbHktVVBTLWRlc2lnbqkCAQVPjy5whD7IAuXS2xqoAwHoA-kF9QMCAADE&num=4&sig=AGiWqty3dB7Alxy6t3GddCLGheSjYKm7ww&client=ca-pub-6050985421795229&adurl=http://www.szaver.com/en/http://googleads.g.doubleclick.net/aclk?sa=L&ai=BBORqWl9yTbzbMoz_cJm-6dAE1ef6hwLt08nZI8CNtwGA86oBEAQYBCCBjMgZKAQ4AFCjh4qCAWDhpLqFkBqyAR5zZWFyY2hkYXRhY2VudGVyLnRlY2h0YXJnZXQuaW7IAQHaAWJodHRwOi8vc2VhcmNoZGF0YWNlbnRlci50ZWNodGFyZ2V0LmluL3RpcC9GaXZlLXRpcHMtZm9yLU4xLXVuaW50ZXJydXB0aWJsZS1wb3dlci1zdXBwbHktVVBTLWRlc2lnbqkCAQVPjy5whD7IAuXS2xqoAwHoA-kF9QMCAADE&num=4&sig=AGiWqty3dB7Alxy6t3GddCLGheSjYKm7ww&client=ca-pub-6050985421795229&adurl=http://www.szaver.com/en/http://searchdatacenter.techtarget.in/resources/Data-center-power-and-coolinghttp://searchdatacenter.techtarget.in/tip/Data-center-cabling-Placing-and-design-best-practiceshttp://searchdatacenter.techtarget.in/tip/Data-center-cabling-Placing-and-design-best-practiceshttp://searchdatacenter.techtarget.in/tutorial/Ctrl-S-tier-4-data-center-infrastructure-A-detailed-walkthroughhttp://searchdatacenter.techtarget.in/tutorial/Ctrl-S-tier-4-data-center-infrastructure-A-detailed-walkthroughhttp://searchdatacenter.techtarget.in/tip/Green-data-center-design-best-practices-Power-and-cooling-approacheshttp://searchdatacenter.techtarget.in/tip/Green-data-center-design-best-practices-Power-and-cooling-approacheshttp://searchdatacenter.techtarget.in/tip/Preventing-a-data-center-power-crisishttp://searchdatacenter.techtarget.in/tip/Preventing-a-data-center-power-crisishttp://searchdatacenter.techtarget.in/tip/Hot-aisle-cold-aisle-design-best-practices-for-data-centershttp://searchdatacenter.techtarget.in/tip/Hot-aisle-cold-aisle-design-best-practices-for-data-centershttp://searchdatacenter.techtarget.in/news/1426153/Data-center-power-management-at-forefront-of-IT-agendahttp://searchdatacenter.techtarget.in/news/1426153/Data-center-power-management-at-forefront-of-IT-agendahttp://searchdatacenter.techtarget.in/tip/Five-tips-for-N1-uninterruptible-power-supply-UPS-designhttp://searchdatacenter.techtarget.in/tip/Five-tips-for-N1-uninterruptible-power-supply-UPS-designhttp://searchdatacenter.techtarget.in/tip/Power-saving-design-for-efficient-cost-effective-data-center-infrastructurehttp://searchdatacenter.techtarget.in/tip/Power-saving-design-for-efficient-cost-effective-data-center-infrastructurehttp://searchdatacenter.techtarget.in/news/1510951/Data-center-power-cooling-strategies-that-drive-Godfrey-Phillipshttp://searchdatacenter.techtarget.in/news/1510951/Data-center-power-cooling-strategies-that-drive-Godfrey-Phillipshttp://searchdatacenter.techtarget.in/tip/Avoid-common-pitfalls-when-calculating-data-center-power-loadhttp://searchdatacenter.techtarget.in/tip/Avoid-common-pitfalls-when-calculating-data-center-power-loadhttp://searchdatacenter.techtarget.in/resources/Data-center-planning-and-layouthttp://searchdatacenter.techtarget.in/tip/Data-center-cabling-Placing-and-design-best-practiceshttp://searchdatacenter.techtarget.in/tip/Data-center-cabling-Placing-and-design-best-practiceshttp://searchdatacenter.techtarget.in/tutorial/Ctrl-S-tier-4-data-center-infrastructure-A-detailed-walkthroughhttp://searchdatacenter.techtarget.in/tutorial/Ctrl-S-tier-4-data-center-infrastructure-A-detailed-walkthroughhttp://searchdatacenter.techtarget.in/news/2240023944/Capacity-planning-no-longer-a-guessing-gamehttp://searchdatacenter.techtarget.in/news/2240023944/Capacity-planning-no-longer-a-guessing-gamehttp://searchdatacenter.techtarget.in/tip/How-to-determine-the-appropriate-failover-disaster-recovery-site-hot-cold-or-warmhttp://searchdatacenter.techtarget.in/tip/How-to-determine-the-appropriate-failover-disaster-recovery-site-hot-cold-or-warmhttp://searchdatacenter.techtarget.in/tip/How-to-determine-the-appropriate-failover-disaster-recovery-site-hot-cold-or-warmhttp://searchdatacenter.techtarget.in/tip/FAQ-How-to-select-optimal-memory-CPU-and-storage-for-virtualizationhttp://searchdatacenter.techtarget.in/tip/FAQ-How-to-select-optimal-memory-CPU-and-storage-for-virtualizationhttp://searchdatacenter.techtarget.in/news/2240021052/New-requirements-for-data-center-infra-arise-at-Manipal-eCommercehttp://searchdatacenter.techtarget.in/news/2240021052/New-requirements-for-data-center-infra-arise-at-Manipal-eCommercehttp://searchdatacenter.techtarget.in/tip/A-data-center-hosting-and-management-outsourcing-checklisthttp://searchdatacenter.techtarget.in/tip/A-data-center-hosting-and-management-outsourcing-checklisthttp://searchdatacenter.techtarget.in/news/1373804/IT-wish-list-Better-ways-to-analyze-data-center-environmental-metricshttp://searchdatacenter.techtarget.in/news/1373804/IT-wish-list-Better-ways-to-analyze-data-center-environmental-metricshttp://searchdatacenter.techtarget.in/tip/A-business-continuity-management-standard-would-offer-consistencyhttp://searchdatacenter.techtarget.in/tip/A-business-continuity-management-standard-would-offer-consistencyhttp://searchdatacenter.techtarget.in/tip/Cleaning-under-the-raised-floor-plenum-Data-center-maintenance-basicshttp://searchdatacenter.techtarget.in/tip/Cleaning-under-the-raised-floor-plenum-Data-center-maintenance-basicshttp://www.2020software.com/http://www.2020software.com/http://www.2020software.com/compare-software/category/32/Manufacturing-ERP-Software/http://www.2020software.com/compare-software/category/32/Manufacturing-ERP-Software/http://www.2020software.com/compare-software/category/32/Manufacturing-ERP-Software/http://www.2020software.com/compare-software/category/32/Manufacturing-ERP-Software/http://www.2020software.com/compare-software/category/5/CRM-Software/http://www.2020software.com/compare-software/category/5/CRM-Software/http://www.2020software.com/http://searchdatacenter.rl.techtarget.in/http://searchdatacenter.rl.techtarget.in/http://searchdatacenter.rl.techtarget.in/webcastshttp://whatis.techtarget.com/http://googleads.g.doubleclick.net/aclk?sa=L&ai=B1GNpWl9yTbzbMoz_cJm-6dAE4ZKc1gHf1vyNAcCNtwGgwh4QAxgDIIGMyBkoBDgAUIm25Ln7_____wFg4aS6hZAasgEec2VhcmNoZGF0YWNlbnRlci50ZWNodGFyZ2V0LmluyAEB2gFiaHR0cDovL3NlYXJjaGRhdGFjZW50ZXIudGVjaHRhcmdldC5pbi90aXAvRml2ZS10aXBzLWZvci1OMS11bmludGVycnVwdGlibGUtcG93ZXItc3VwcGx5LVVQUy1kZXNpZ26oAwHoA-kF9QMCAADE&num=3&sig=AGiWqtx6J_0zTfQjoCXuau2DEBuR7hB8kQ&client=ca-pub-6050985421795229&adurl=http://www.ptb-sales.com/vacuum/source/http://googleads.g.doubleclick.net/aclk?sa=L&ai=B1GNpWl9yTbzbMoz_cJm-6dAE4ZKc1gHf1vyNAcCNtwGgwh4QAxgDIIGMyBkoBDgAUIm25Ln7_____wFg4aS6hZAasgEec2VhcmNoZGF0YWNlbnRlci50ZWNodGFyZ2V0LmluyAEB2gFiaHR0cDovL3NlYXJjaGRhdGFjZW50ZXIudGVjaHRhcmdldC5pbi90aXAvRml2ZS10aXBzLWZvci1OMS11bmludGVycnVwdGlibGUtcG93ZXItc3VwcGx5LVVQUy1kZXNpZ26oAwHoA-kF9QMCAADE&num=3&sig=AGiWqtx6J_0zTfQjoCXuau2DEBuR7hB8kQ&client=ca-pub-6050985421795229&adurl=http://www.ptb-sales.com/vacuum/source/http://googleads.g.doubleclick.net/aclk?sa=L&ai=BBORqWl9yTbzbMoz_cJm-6dAE1ef6hwLt08nZI8CNtwGA86oBEAQYBCCBjMgZKAQ4AFCjh4qCAWDhpLqFkBqyAR5zZWFyY2hkYXRhY2VudGVyLnRlY2h0YXJnZXQuaW7IAQHaAWJodHRwOi8vc2VhcmNoZGF0YWNlbnRlci50ZWNodGFyZ2V0LmluL3RpcC9GaXZlLXRpcHMtZm9yLU4xLXVuaW50ZXJydXB0aWJsZS1wb3dlci1zdXBwbHktVVBTLWRlc2lnbqkCAQVPjy5whD7IAuXS2xqoAwHoA-kF9QMCAADE&num=4&sig=AGiWqty3dB7Alxy6t3GddCLGheSjYKm7ww&client=ca-pub-6050985421795229&adurl=http://www.szaver.com/en/http://googleads.g.doubleclick.net/aclk?sa=L&ai=BBORqWl9yTbzbMoz_cJm-6dAE1ef6hwLt08nZI8CNtwGA86oBEAQYBCCBjMgZKAQ4AFCjh4qCAWDhpLqFkBqyAR5zZWFyY2hkYXRhY2VudGVyLnRlY2h0YXJnZXQuaW7IAQHaAWJodHRwOi8vc2VhcmNoZGF0YWNlbnRlci50ZWNodGFyZ2V0LmluL3RpcC9GaXZlLXRpcHMtZm9yLU4xLXVuaW50ZXJydXB0aWJsZS1wb3dlci1zdXBwbHktVVBTLWRlc2lnbqkCAQVPjy5whD7IAuXS2xqoAwHoA-kF9QMCAADE&num=4&sig=AGiWqty3dB7Alxy6t3GddCLGheSjYKm7ww&client=ca-pub-6050985421795229&adurl=http://www.szaver.com/en/http://searchdatacenter.techtarget.in/resources/Data-center-power-and-coolinghttp://searchdatacenter.techtarget.in/tip/Data-center-cabling-Placing-and-design-best-practiceshttp://searchdatacenter.techtarget.in/tutorial/Ctrl-S-tier-4-data-center-infrastructure-A-detailed-walkthroughhttp://searchdatacenter.techtarget.in/tip/Green-data-center-design-best-practices-Power-and-cooling-approacheshttp://searchdatacenter.techtarget.in/tip/Preventing-a-data-center-power-crisishttp://searchdatacenter.techtarget.in/tip/Hot-aisle-cold-aisle-design-best-practices-for-data-centershttp://searchdatacenter.techtarget.in/news/1426153/Data-center-power-management-at-forefront-of-IT-agendahttp://searchdatacenter.techtarget.in/tip/Five-tips-for-N1-uninterruptible-power-supply-UPS-designhttp://searchdatacenter.techtarget.in/tip/Power-saving-design-for-efficient-cost-effective-data-center-infrastructurehttp://searchdatacenter.techtarget.in/news/1510951/Data-center-power-cooling-strategies-that-drive-Godfrey-Phillipshttp://searchdatacenter.techtarget.in/tip/Avoid-common-pitfalls-when-calculating-data-center-power-loadhttp://searchdatacenter.techtarget.in/resources/Data-center-planning-and-layouthttp://searchdatacenter.techtarget.in/tip/Data-center-cabling-Placing-and-design-best-practiceshttp://searchdatacenter.techtarget.in/tutorial/Ctrl-S-tier-4-data-center-infrastructure-A-detailed-walkthroughhttp://searchdatacenter.techtarget.in/news/2240023944/Capacity-planning-no-longer-a-guessing-gamehttp://searchdatacenter.techtarget.in/tip/How-to-determine-the-appropriate-failover-disaster-recovery-site-hot-cold-or-warmhttp://searchdatacenter.techtarget.in/tip/How-to-determine-the-appropriate-failover-disaster-recovery-site-hot-cold-or-warmhttp://searchdatacenter.techtarget.in/tip/FAQ-How-to-select-optimal-memory-CPU-and-storage-for-virtualizationhttp://searchdatacenter.techtarget.in/news/2240021052/New-requirements-for-data-center-infra-arise-at-Manipal-eCommercehttp://searchdatacenter.techtarget.in/tip/A-data-center-hosting-and-management-outsourcing-checklisthttp://searchdatacenter.techtarget.in/news/1373804/IT-wish-list-Better-ways-to-analyze-data-center-environmental-metricshttp://searchdatacenter.techtarget.in/tip/A-business-continuity-management-standard-would-offer-consistencyhttp://searchdatacenter.techtarget.in/tip/Cleaning-under-the-raised-floor-plenum-Data-center-maintenance-basicshttp://www.2020software.com/http://www.2020software.com/compare-software/category/32/Manufacturing-ERP-Software/http://www.2020software.com/compare-software/category/32/Manufacturing-ERP-Software/http://www.2020software.com/compare-software/category/5/CRM-Software/http://www.2020software.com/http://searchdatacenter.rl.techtarget.in/http://searchdatacenter.rl.techtarget.in/webcastshttp://whatis.techtarget.com/8/7/2019 N + 1 UPS
4/6
8/7/2019 N + 1 UPS
5/6
blade servers.
In N+1 redundancy, the UPS is being used to only 50% of its efficiency. In normal
situations, you can push it to 75%. The part load efficiency of any system is alwaysinferior to its full load efficiency. Thus, one of the challenges is to improve part load
efficiency, for which the efficiency curve should be kept very flat.
Tip 3: Things to consider during UPS module selection
Cost is always top of the mind when it comes to selection of UPS modules for an N+1
UPS setup. Apart from cost, electricity consumption is another area which directly affectsUPS module selection.
In Indian conditions, if the UPS can work on a wider range of input voltages, it does not
consume battery power. UPS batteries tend to wear out earlier with more usage, bringing
in huge replacement costs. Thus, you should look at UPS technologies like advanced
battery management, which closely monitors battery charging. If you can make the UPSwork over a wider input range, then batteries can be discarded altogether.
Another belief is that you can increase the UPS' reliability through UPS oversizing. Such
cases always involve restricting the amount of extractable UPS reliability.
,
Tip 4: Investigate the UPS system's loads during design
Till date, data center managers have always played it very conservative when it comes to
N+1 UPS design. They typically size the UPS according to the available connected load.
Servers are typically designed for a certain power rating. Hence IT managers shouldjudiciously consider that adversity factor, as well as the simultaneity factor (how many
loads will come at a given point of time) during N+1 UPS design. This will help them in
terms of not oversizing the UPS.
Another belief is that you can increase the UPS' reliability through UPS oversizing. Suchcases always involve restricting the amount of extractable UPS reliability.
It is best to go for a modular UPS system when it comes to N+1 UPS setups. In this case,
another UPS module can take over if a module becomes faulty. However, in such casesyou should also look at the system's hot swappability.
Tip 5: Handling UPS power consumption
The N+1 UPS' power consumption will depend on the server's kilowatt demand.
Unfortunately, we continue have a mix of legacy systems and new blade servers in India.
8/7/2019 N + 1 UPS
6/6
In the future, there will be more IT equipment with power factor correction. In a
conventional system, if the UPS develops a fault, it gets raw power through the bypass.
Thus, continuity of power is maintained. Modular systems have an extra module, so ifthere is a failure, the other module still remains in online mode. Thus, there is no question
of the UPS system going into the bypass.
About the author: Robin Roy is the product manager for UPS solutions at Delta Energy
Systems (I) Pvt. Ltd. He is responsible for introduction of new products for differentmarket segments, business verticals and applications, with state-of-the-art technology for
power conditioning.
(As told to Jasmine Desai.)