10
22/03/11 FV 1 NA62 DCS CAN bus lines

NA62 DCS CAN bus lines

  • Upload
    shubha

  • View
    29

  • Download
    0

Embed Size (px)

DESCRIPTION

NA62 DCS CAN bus lines. Short reminder. General properties of CAN bus Up to 64 nodes on one bus Different devices need different buses (WIENER, ISEG, ELMB,?) Transition rate depends on the length of cable (from 1 Mbit /s for 25m to 10 kbit /s for 5000m) - PowerPoint PPT Presentation

Citation preview

Page 1: NA62 DCS CAN bus lines

122/03/11 FV

NA62 DCS CAN bus lines

Page 2: NA62 DCS CAN bus lines

VF 2

Short reminder

• General properties of CAN buso Up to 64 nodes on one buso Different devices need different buses (WIENER, ISEG, ELMB,?)o Transition rate depends on the length of cable (from 1 Mbit/s for

25m to 10 kbit/s for 5000m)o Characteristic impedance 120 Ohm, termination on both endso The starting point of the CANbus cables is DCS rack(s) in the PC

farm area (b.918)

• ISEG CAN buso One module has two CAN-nodes, crate is one node. So one fully

populated crate with 8 Modules EDS 20 130n_504 equals 17 CAN-nodes

o Not more than 3 crates per cableo Peak PCAN-PCI two channel cards

22/03/11

Page 3: NA62 DCS CAN bus lines

VF 3

Short reminder -2

• ELMB CAN buso In addition to the CAN bus signals the cable also provide the

power for the ELMBs (12V) o Thick cable (SCEM code 04.21.60.491.2) will be used for long

distance to minimize the voltage drop, thin cable (SCEM code 04.21.60.430.5) for local distribution + junction box “a la ATLAS” (has to be investigated)

o Fixed double cable “PHOENIX CONTACT” connectorso Kvaser PCIcanx 4xHS cards

• WIENER CAN buso Kvaser PCIcanx 4xHS cardso TCP/IP option for the WIENER equipment control is under

consideration. Price for one fan-tray unit• CAN bus: 627 EURO• TCP/IP: 755 or 991 EURO• In total we will have about 60 crates

22/03/11

Page 4: NA62 DCS CAN bus lines

VF 4

Experimental Area

22/03/11

PC farm area

Page 5: NA62 DCS CAN bus lines

VF 5

ISEG CAN bus lines

22/03/11

GT 854 (to PC farm)GT 853 (to NA48 CR)

• MUV, SAV• LAV 12, 11, 10• LAV 9, 8, 7• LAV 6, 5, 4• LAV 3, 2, 1• CEDAR (?)

Page 6: NA62 DCS CAN bus lines

VF 6

ISEG CAN bus lines

22/03/11

• LAV 3, 2, 1

• CEDAR (?)

Page 7: NA62 DCS CAN bus lines

VF 7

WIENER crate control CAN bus lines

22/03/11

GT 854 (to PC farm)GT 853 (to NA48 CR)

• LKr• All other crates in EB, LAV12, LAV11, LAV10• Straw tracker• LAV 9, 8, 7, 6, 5, 4, 3, 2, 1, CHANTI, GTK (?),

CEDAR

Page 8: NA62 DCS CAN bus lines

VF 8

WIENER crate control CAN bus lines

8/02/11

• LAV 5, 4, 3, 2, 1, GTK (?), CHANTI, CEDAR

Page 9: NA62 DCS CAN bus lines

VF 9

ELMB CAN bus lines

8/02/11

• LKr• RICH, MUV, SAV• STRAW 1• STRAW 2• STRAW 3• STRAW 4• CHANTI, GTK3, GTK2, GTK1, CEDAR

Page 10: NA62 DCS CAN bus lines

VF 10

• Other CAN bus lineso CAN bus cables for LAV thresholds (one cable per

station) o Gas systems (one cable per system ?)o CEDAR NINO front-end cards control (one cable)?o RICH NINO front-end card control ?

22/03/10