2
The Web-HMI Server brings your Modbus-networked automation equipment and industrial manufacturing systems to the web. The device links to the targeted system with the vendor-neutral Modbus RTU protocol over a serial RS-232, RS-485 or RS-422 connection as master or slave. The integrated 2-port Ethernet switch on the underside connects the device IT-friendly to the existing LAN network. The terminal block on the front connects to the target system. The web visualization is managing the pages without plugins such as ActiveX®, Flash® or Java®. It can be executed by all leading web browsers. The interface scales automatically and adjusts to work on any web browser enabled device from a Smartphone all the way up to a web-enabled High-definition television. The simultaneous access of multiple browsers at a time is also supported. Although native web technology is being used no HTML code programming necessary. Front end creation as well as the dynamizations of the visualizing controls and gadgets are easily and quickly configured with a few mouse clicks. The Modbus values as basis are defined as tags in a symbol editor and just applied to the controls afterwards. Color change, movement, scaling, user rights, the support of all common graphic formats and multilingualism are possible. Online data monitoring, alarming/acknowledgment and data trending are supported. For best visual effects a large catalogue of high-quality graphics from the industrial sector is available as library on demand. Brings your Modbus-networked automation equipment to the web Enables platform neutral and free of charge visualization over all common browsers Lets you monitor and operate your machinery from any mobile anytime, anywhere Comes with touchscreen-ready controls and gad- gets for fast implementation without programming netSCADA Modbus Web-HMI Server for Modbus®RTU systems Visualizing modern, flexible and economically over the web

netSCADA Modbus Datasheet 10-2014 GB

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Page 1: netSCADA Modbus Datasheet 10-2014 GB

The Web-HMI Server brings your Modbus-networked automation equipment and industrial manufacturing systems to

the web. The device links to the targeted system with the vendor-neutral Modbus RTU protocol over a serial RS-232,

RS-485 or RS-422 connection as master or slave. The integrated 2-port Ethernet switch on the underside connects

the device IT-friendly to the existing LAN network. The terminal block on the front connects to the target system.

The web visualization is managing the pages without plugins such as ActiveX®, Flash® or Java®. It can be executed

by all leading web browsers. The interface scales automatically and adjusts to work on any web browser enabled

device from a Smartphone all the way up to a web-enabled High-definition television. The simultaneous access of

multiple browsers at a time is also supported.

Although native web technology is being used no HTML code programming necessary. Front end creation as well as

the dynamizations of the visualizing controls and gadgets are easily and quickly configured with a few mouse clicks.

The Modbus values as basis are defined as tags in a symbol editor and just applied to the controls afterwards. Color

change, movement, scaling, user rights, the support of all common graphic formats and multilingualism are possible.

Online data monitoring, alarming/acknowledgment and data trending are supported. For best visual effects a large

catalogue of high-quality graphics from the industrial sector is available as library on demand.

Brings your Modbus-networked automation

equipment to the web

Enables platform neutral and free of charge

visualization over all common browsers

Lets you monitor and operate your machinery

from any mobile anytime, anywhere

Comes with touchscreen-ready controls and gad-

gets for fast implementation without programming

netSCADA ModbusWeb-HMI Server for Modbus®RTU systems

Visualizing modern, flexible and economically over the web

Page 2: netSCADA Modbus Datasheet 10-2014 GB

Technical Data / Product Overview

HeadquartersGermanyHilscher Gesellschaft für Systemautomation mbHRheinstrasse 1565795 HattersheimPhone: +49 (0) 6190 9907-0 Fax: +49 (0) 6190 9907-50E-Mail: [email protected] Web: www.hilscher.com

JapanHilscher Japan KKTokyo, 160-0022Phone: +81 (0) 3-5362-0521E-Mail: [email protected] KoreaHilscher Korea Inc. Seongnam, Gyeonggi, 463-400Phone: +82 (0) 31-789-3715E-Mail: [email protected]

SwitzerlandHilscher Swiss GmbH 4500 SolothurnPhone: +41 (0) 32 623 6633E-Mail: [email protected] USAHilscher North America, Inc. Lisle, IL 60532Phone: +1 630-505-5301E-Mail: [email protected]

IndiaHilscher India Pvt. Ltd.Pune, Delhi, MumbaiPhone: +91- 8888 750 777E-Mail: [email protected] ItalyHilscher Italia S.r.l.20090 Vimodrone (MI)Phone: +39 02 25007068E-Mail: [email protected]

SubsidiariesChinaHilscher Systemautomation(Shanghai) Co. Ltd.200010 ShanghaiPhone: +86 (0) 21-6355-5161E-Mail: [email protected] FranceHilscher France S.a.r.l.69500 BronPhone: +33 (0) 4 72 37 98 40E-Mail: [email protected]

Distributors More information at www.hilscher.com

Note: All technical data may be changed without further notice.

10/2

014

GB

NSCD-T52-RS/ATVISE/MBR 1880.100/ATVISE/MBR netSCADA Modbus, Web-HMI Server for Modbus®RTU systems

ATVISE ELEMENTS 1701.432 Vector Graphics Library with over 4000 images of the industrial sector

Ove

rvie

w

Article Article Number Article Description

Parameter Value

Processor netX 52

Power Supply 18 … 30 V / ca. 60 mA @ 24 V

Supply Connection COMBICON MC 1,5/5 5-pin, light gray

LAN Connection 2 x RJ45 with integrated switch

Transmission Speed 10/100 Base-TX Ethernet

Modbus Connection COMBICON MSTB 2,5/5 5-pin, green

Modbus Interface RS-232, RS-485, RS-422 each non isolated

LED Indicators SYSTEM,CONFIG,MODBUS,ACTIVE,LOAD

Operating Temperature 0 … 50 °C

Dimensions (L x W x H) 88 mm x 22,5 mm x 78 mm

Weight approx. 84 g

Protection Class IP20

Mounting DIN EN 60715

EC Conformity Directive 2004/108/EG

Real-Time Clock Hardware supported, precision 20ppm

Real-Time Clock Buffering 7 days min., maintenance-free by SuperCap

Clock Synchronization Manual / cyclic over SNTP protocol

Web Application Memory 6 MByte, non-volatile FLASH memory

Trending Memory 8 Mbyte, non-volatile FLASH memory

Parameter Value

Modbus RTU modes Slave or Master to 16 Slaves

Modbus Function Codes FC1,FC2,FC3,FC4,FC5,FC15,FC16

Modbus Baud Rate 1,2 kBaud ... 115,2 kBaud

SNTP Client RFC 2030, Port 123, Time Synchronization

FTP Server RFC 959, Port 21, Passive Mode

HTTP Server RFC 2616, Port 80, HTTP/1.1

Supported Browsers Internet Explorer 8/9/10, Mozilla

Firefox 24; Safari 5.1.7, Chrome 31,

Opera 16.0, Blackberry 6 or 10

with at least 3 simultaneous connections

Web Visualization atvise® (webMI) with Hilscher Plugin

Engineering Tool atvise builder, Multi-User License

Variables/Data Points Unlimited

Web Memory Consumption 200kByte per page typically

Standard Functions Online, Alarm, Trend, User Management

Adaptability Entirely customizable using Java Scripting

Multilingualism Yes, german / english as standard

Trend Variables 32 max., Sampl. Rate 200msec to 24hrs.

Recording Time 8 Variables @60 seconds Rate = 45 days

18 Variables @1 hour Rate = 1200 days

Tec

hn

ical

Dat

a

ATVISE SUPPORT SERVICE 0027.002 Half-day atvise Phone Support / Adaption / Programming / Personal Training @Hattersheim