New AMV System
Control System
TECHNICAL SUPPORT DIVISION 2015.7
2 New AMV System – Control System
Content
1. Outdoor Unit and Indoor Unit PCB 3
2. Communication System 20
3. Controllers 24
3 New AMV System – Control System
1. Outdoor unit and indoor unit PCB
1.1 Outdoor unit main control board.
1.1.1 Outdoor unit PCB outlook
No. Content No. Content 1 Phase inspection port 18 SV5,SV6 four way valve control port
2 Discharge temp.( sensing port of inverter compressor, sensing port of NO.1and NO.2 fixed compressor) 19 SV1,SV2,SV3,SV4 control port (SV3 is reserved )
3 Terminal Communication between indoor and outdoor units 20 SV7,SV8 control port(SV7,SV8 is reserved)
4 Outdoor unit network and electric meter terminal 21 NO.1 EXV activation port
5 Control port of DC fan 1 22 NO.2 EXV activation port
6 Control port of DC fan 2 23 Power input of the No.2 transformer
7 ON/OFF signal input port for system Hi-pressure inspection 24 Power input of the No.1 transformer
8 ON/OFF signal input port for system low pressure inspection
25 Cap. of outdoor unit dial switch
9 Current inspection port of inverter and fixed compressors 26 Outdoor address switch
10 Inspection port for condenser coil temp.(black) 27 SW7, compressor restarting gap.
11 Inspection port for outdoor ambient temp(white) 28 SW8, night time silent operation mode and automatically assign address switch
12 Input port for system pressure inspection 29 SW9, mode selection dial switch
13 Communication ports among outdoor units 30 SW5, Outdoor fan static pressure switch
14 communication port between outdoor main board and the frequency conversion compressor module board
31 SW4, Night time silent operation selection switch
15 Power output of the No.2 transformer 32 Query button
16 Power output of the No.1 transformer 33 Constraint cooling button
17 Loading output terminal ─
3 4 5 6 7 8 9 10 11
12
13 14
15
16
17
18 19 20 21 22 23 24 25 26
27 28 29
30 31
32
33
2
1
4 New AMV System – Control System
1.1.2 Dial codes definition
SW4 Parameter setting for night time silent operation
Meaning
After 6 hours of daytime peak temperature, night time silent operation start, last for 8 hours, then return to normal operation.
After 8 hours of daytime peak temperature, night time silent operation start, last for 10 hours, then return to normal operation.
After 6 hours of daytime peak temperature, night time silent operation start, last for 12 hours, then return to normal operation.
After 8 hours of daytime peak temperature, night time silent operation start, last for 8 hours, then return to normal operation.
Demonstration
(Default setting)
Remarks It is available only when user turn on the night time silent operation mode in SW8. Night time silent operation mode is default ON.
SW5 Outdoor fan ESP setting
Meaning Outdoor fan ESP is 0 Pa. Outdoor fan maximum ESP can be up to 85 Pa.
Demonstration
(Default setting)
SW4
SW12
SW5
SW10
SW9
SW13 SW6
SW7
SW11
SW8
5 New AMV System – Control System
SW6 Outdoor unit address setting
Meaning Master unit Slave unit Slave unit Slave unit
Demonstration
Poniting to 0
Poniting to1
Poniting to 2
Poniting to 3
Remarks Only 0,1,2,3 is available, address bigger than 3 will cause system failure.
SW7 1. System first start time setting 2. Snow-blowing function: when outdoor temperature is lower than 0°C and system is standby, every one
hour outdoor fan motor will turn on for 30 seconds.
Meaning
1. System can be start only after power on for 12 minutes.
2. Snow-blowing function is OFF.
1. System can be start only after power on for 3 minutes.
2. Snow-blowing function is OFF.
1. System can be start only after power on for 12 minutes.
2. Snow-blowing function is ON.
1. System can be start only after power on for 3 minutes.
2. Snow-blowing function is ON.
Demonstration
1 2
ON
(Default setting)
1 2
ON
1 2
ON
1 2
ON
Remarks DO NOT change this setting without professional guidance.
SW8 Turn ON or OFF night time silent operation mode and automatically addressing
Meaning
1. Night time silent operation mode is ON
2. Automatically addressing is ON.
1. Night time silent operation mode is ON.
2. Automatically addressing is OFF.
Clear all auto assigned addresses of indoor units.
1. Night time silent operation mode is OFF.
2. Automatically addressing is ON.
1. Night time silent operation mode is OFF.
2. Automatically addressing is OFF.
Demonstration
(Default setting)
Remarks When automatically addressing is OFF, user need to set indoor unit address manual by indoor unit address setting controller.
6 New AMV System – Control System
SW9 Operation mode restriction setting
Meaning Heating priority Cooling priority First start mode
priority Heating only Cooling only
Demonstration
(Default setting)
Remarks When automatically addressing is OFF, user need to set indoor unit address manual by indoor unit address setting controller.
SW11 Outdoor unit PCB selector
Meaning 8HP 10HP 12HP 14HP 16HP
Demonstration
Poniting to 0
Poniting to1
Poniting to 2
Poniting to 3
Poniting to 4
Remarks Only 0,1,2,3,4 is available, address bigger than 4 will cause system failure.
SW12 PCB identification
Meaning For 380V-415/3PH/50Hz & 380V-415/3PH/60Hz For 280V-230V/3PH/60Hz
Demonstration
(Default setting)
Remarks DO NOT change this setting without professional guidance.
SW3: Forced cooling button
1) After pressing it once, all indoor units and outdoor units will start cooling, no matter what mode they are running on, no matter whether they are ON or OFF.
2) The forced cooling function is available for master unit only.
3) During forced cooling mode.
All indoor EXVs open to 300 pulses. All indoor fans are in high speed. All compressors are ON. All outdoor fan motors are OFF Outdoor EXVs opens to 480 pulses SV6 is ON
4) When program starts:
All the compressors are on Indoor fan is running at high speed
5) When the process is last for 1h or the button is pressed again, program will quit.
SW10: reserved, DO NOT change the default setting. SW13: reserved, DO NOT change the default setting.
7 New AMV System – Control System
1.1.3 Query procedures.
No. Display Content Remarks
/ - - Quantity of indoor units which can be communication with outdoor unit
Displays when system standby
/ - - Inverter compressor frequency Displays when system is running
1 1 - - Outdoor unit’s address 0(master unit),1(slave unit),2(slave unit),3(slave unit),4(slave unit)
2 2 - - Outdoor unit capacity 8(HP), 10(HP), 12(HP), 14(HP), 16(HP)
3 3 - - Outdoor unit quantity Only available for master unit
4 4 - - All outdoor units total capacity Total HP
5 5 - - All indoor units total capacity demand Only available for master unit
6 6 - - Total amended capacity demand Only available for master unit
7 7 - - Operation mode 0 (OFF or Fan only) 2 (Cooling) 3 (Heating) 4 (Forced cooling)
8 8 - - Outdoor unit actual capacity output Actual output HP
9 9- - Outdoor fan speed range 0,1,2,3,4,5,6,7,8,9
10 10 - - T2/T2B (indoor coil average temperature)
Display in actual value
11 11 - - T3 (outdoor coil temperature) Display in actual value
12 12 - - T4 (ambient temperature) Display in actual value
13 13 - - Inverter compressor discharge temperature
Display in actual value, normally it should be 75~85˚C
14 14 - - Fixed compressor 1 discharge temperature
Display in actual value, normally it should be 75~85˚C
15 15 - - Fixed compressor 2 discharge temperature
Display in actual value, normally it should be 75~85˚C
16 16 - - Inverter compressor current Display in actual value, normally it should be 3~10A
17 17 - - Fixed compressor 1 current Display in actual value, normally it should be 7~10A
18 18 - - Fixed compressor 2 current Display in actual value, normally it should be 7~10A
19 19 - - EXV opening Actual pulse = Display value ×8
20 20 - - Discharge pressure Actual value = Display value ×0.1MPa 2.7~3.1MPa in cooling, 2.2~2.7MPa in heating
21 21 - - Secondary current Display in actual value, system will stop when bigger than 14A
22 22 - - Secondary voltage Display in actual value, it should be 11~13
23 23 - - Priority operation mode 0: Heating first 1: cooling first 2: First start first 3: Heating only 4: Cooling only 5: Reserved 6: Reserved
24 24 - - Connected indoor unit quantity Indoor unit that is able to communicating to master outdoor unit
25 25 - - Last protection code or error code Display 00 if no protection code or error code.
26 26 - - / End
Note:
1) When operation of system lasts 1 hour and stays stability, press checkup button on PCB of outdoor master unit, query one by one and fill out the above table according to facts.
2) Description of display:
Normal display: when in standby mode, it indicates number of indoor units, when running, it indicates output percentage value of compressor.
Running mode: 0(OFF); 1(fan only); 2(Cooling); 3(Heating); 4(Forced cooling) Outdoor fan speed range: 0(OFF); 1~9──Speed increasing in turn. EXV opening: Actual pulse = Display value ×8. Number of indoor unit: indoor units which are capable of communicating with outdoor unit normally.
8 New AMV System – Control System
1.1.4 Outdoor error codes.
Code Malfunction or protection Remark
E0 Outdoor unit communication malfunction Only slave unit displays
E1 Phase sequence malfunction
E2 Communication between master outdoor unit and indoor units
E3 reserved
E4 Ambient temperature sensor malfunction
E5 reserved
E6 Outdoor heat exchanger temperature sensor malfunction
E7 reserved
E8 Outdoor unit address incorrect
E9 reserved
H0 Communication malfunction between DSP and 0547
H1 Communication malfunction between 0537 and 0547
H2 Outdoor unit quantities decreasing malfunction Only master unit displays
H3 Outdoor unit quantities increasing malfunction Only master unit displays
H4 There is 3 times P6 protection in 30 minutes. Repower on to clear the error code.
H5 There is 3 times P2 protection in 30 minutes. Repower on to clear the error code.
H6 There is 3 times P4 protection in 100 minutes. Repower on to clear the error code.
H7 Indoor unit quantities decreasing malfunction over 3 minutes Recover when indoor unit quantity is
correct
H8 Discharge pressure sensor error When discharge pressure is lower than
0.3MPa
H9 There is 3 times P9 protection in 30 minutes. Repower on to clear the error code.
P1 High pressure protection
P2 Low pressure protection
P3 Inverter compressor over current protection
P4 Discharge temperature sensor protection
P5 Heat exchanger temperature sensor protection
P6 Inverter module protection
P7 Fix compressor 1 current protection
P8 Fix compressor 2 current protection
P9 Fan module protection
L0 Inverter compressor malfunction
Error code after P6 protection
L1 DC generatrix low voltage protection
L2 DC generatrix high voltage protection
L3 reserved
L4 MCE malfunction/simultaneously/cycle loop
L5 Zero speed protection
L6 reserved
L7 Wrong phase protection
L8 Speed difference >15Hz protection between the front and the back clock
L9 Speed difference >15Hz protection between the real and the setting speed
9 New AMV System – Control System
1.2 Description of main control board of indoor unit.
1.2.1 There are two shapes of main control board that used to all types of indoor unit matching with New AMV outdoor unit.
1) Shape A
No. Content No. Content
1 Communication port of P Q E 9 EXV activation port
2 SW2 10 Transformer output port
3 Remote control port 11 Fan motor output interface
4 SW3 12 Transformer input port
5 Port for electric auxiliary heater 13 220V AC N interface
6 Port for display board and remote control receiver 14 220V AC L interface
7 SW1 15 Temperature sensor port
8 Download port 16 Remote control switch
1 4 2 3 5 6 7 8 9
10 11 12 13 14
15 16
10 New AMV System – Control System
2) Shape B
No. Content No. Content
1 Communication port of P Q E 11 Transformer input port
2 Port for display board and remote control receiver 12 SW1
3 EXV activation port 13 Remote control port
4 Stepper motor control port (a total of 4 port) 14 Remote control switch
5 Fan motor output interface 15 SW3
6 Pump output interface 16 SW2
7 Transformer output port 17 The water level switch interface
8 220V AC N interface 18 Temperature sensor port
9 220V AC L interface 19 Download port
10 Port for electric auxiliary heater ─
1 2 3 5 6 7 8
11 9
4 18
10 13 12 14 15 16 17
19
11 New AMV System – Control System
1.2.2 Error code & meanings
LED display LED light Meanings
FE TIMER and RUN both flash 4Hz, No address when indoor unit first time power on
E1 TIMER flashes at 4Hz Communication error between indoor and outdoor units
E2 RUN flashes 4Hz Temperature sensor T1 error
E3 RUN flashes 4Hz Temperature sensor T2 error
E4 RUN flashes 4Hz Temperature sensor T2B error
E5 ALARM flashes 0.5Hz, Outdoor unit error
E6 / Zero crossing detection error
E7 DEFOST flashes 0.5Hz, EEPROM error
E8 / Indoor fan motor error
E9 / Wired controller communication error
EE ALARM flashes 4Hz Water level alarm error
EF DEFOST flashes 4Hz Mode conflict
12 New AMV System – Control System
1.2.3 SW2, only available in heating mode.
Name Switch number 1,2 of SW2
Function Reserved
Setting
1 2 3 4 5 6 7 8
Default setting
Name Switch number 3,4 of SW2
Function Heating temperature compensation value selection. When temperature difference between setting
temperature and room temperature is higher than the setting value, indoor fan motor turns off. DO NOT change the default setting without professional guidance.
Setting
1 2 3 4 5 6 7 8
6 ˚C Default setting
1 2 3 4 5 6 7 8
2 ˚C
1 2 3 4 5 6 7 8
4 ˚C
1 2 3 4 5 6 7 8
8 ˚C
ON OFF
ON OFF
ON OFF
ON OFF
13 New AMV System – Control System
Name Switch number 5,6 of SW2
Function Temperature selection of turning off fan motor in anti-cold-wind-blow mode. When indoor heat
exchanger temperature is lower than the setting value, indoor fan motor turns off. DO NOT change the default setting without professional guidance.
Setting
1 2 3 4 5 6 7 8
15 ˚C Default setting
1 2 3 4 5 6 7 8
20 ˚C
1 2 3 4 5 6 7 8
24 ˚C
1 2 3 4 5 6 7 8
26 ˚C
ON OFF
ON OFF
ON OFF
ON OFF
14 New AMV System – Control System
Name Switch number 7,8 of SW2
Function
Indoor fan motor stopping gap selection in heating mode. When room temperature gets to (set point + temperature value in Switch number 3,4 of SW2), at this
moment indoor unit capacity requirement is 0, indoor fan motor turns off for 4 minutes ( this stopping duration time can be changed by below setting). After that indoor fan will run in low speed for 1 minute (this timing is fixed), if indoor unit capacity requirement is still 0, then indoor fan motor keeps off for 4 minutes, and then cycles.
DO NOT change the default setting without professional guidance.
Setting
1 2 3 4 5 6 7 8
4 minutes Default setting
1 2 3 4 5 6 7 8
8 minutes
1 2 3 4 5 6 7 8
12 minutes
1 2 3 4 5 6 7 8
16 minutes
1.2.4 SW8, reserved, leave it as default setting (both switches dial down).
ON OFF
ON OFF
ON OFF
ON OFF
15 New AMV System – Control System
1.3 Electric wiring installations
1.3.1 Highlights of electrical installation
1) Please separately design the special power of indoor units and outdoor units.
2) The power adopts special circuit, and installs circuit breaker and manual switch.
3) The indoor units’ power, circuit breaker and manual switch connecting to the same outdoor unit must be general. All
indoor units must be the same circuit, and must simultaneously on or off; otherwise, system life will seriously effect,
and appear the situation not to solve.
4) The communication line between indoor units and outdoor units please use 2-core shielded wiring, while don’t use
the multi core wiring without shielded affect, for the interference is reduced each other
5) Purchased wiring, parts and materials should be in compliance with the local and national regulations.
6) All field wiring construction should be finished by qualified electrician.
7) Air conditioning equipment should be grounded according to the relevant local and national electrical regulations.
8) Current leakage protection switch should be installed (select current leakage breaker in light of the 1.5-2 times of
total loading rated current.)
9) When connecting wiring and wire holder, use cable clamp to fix and make sure no exposure.
10) Refrigerant piping system and wiring system of indoor and outdoor unit belongs to the different system.
11) Do not connect the power wire to the terminal of signal wire.
12) When power wire is parallel with signal wire, put wires to their own wire tube and remain proper gap (the current
capacity of power wire is: 10A below 300mm, 50A below 500mm).
13) Voltage discrepancy of power wire terminal (side of power transformer) and end voltage (side of unit) should be less
than 2%. If its length could not be shortened, thicken the power wire. Voltage discrepancy between phases shall not
pass 2% rated value and Current discrepancy between highest and lowest phase should be less than 3% rated value.
1.3.2 Selection of wiring
1.3.2.1 The selection of wiring area shall in accordance with the requirements below:
1) Voltage lose of wire shall meet the requirement of terminal voltage for normal operation and startup.
2) The wiring current-carrying capacity determined by installed method and environment is not less than the largest
current of unit.
3) Conductor shall ensure the stability of movement and heating.
4) The conductor’s smallest sectional area should satisfy the requirement of mechanical strength.
5) When earth protection line (shortly called PE line) is made of material the same as phase line, the smallest sectional
area of PE line should be in accordance with the regulation below:
Sectional area of core to phase line (mm²) Smallest sectional area of PE line(mm²)
S≤16 S
16<S≤35 16
S>35 S/2
1.3.2.2 Distribution highlights of distribution wiring
1) When distributing wiring, select wirings with different colors for phase line, zero line and protection earth according
to relevant regulations.
2) The power wire and control wire of concealed engineering is prohibited to bind together with refrigerant piping. It is necessary to pass through wire tube and be distributed separately, and the gap between control line and power wire should be 500mm at least.
16 New AMV System – Control System
3) When distributing wiring by passing through pipe, the following should be paid attention to:
Metal wire tube could be used in indoor and outdoor, but it is not suitable to the place with acid – alkali
corrosion.
Plastic wire tube is generally used in indoor and place with corrosion, but it is not suitable to situation with
mechanical damage.
The wiring through pipe shall not be in the form with ends jointing. If there must be joint, connection box
should be installed at the corresponding place.
The wiring with different voltage should not pass through the same wire tube.
Total sectional area of wiring through wire tube shall not exceed 40% valid area of stuffing tube.
Fixing point of wire tube support shall follow the standard below:
Normal diameter of wire tube
(Mm)
Largest gap between fixed points of wire tube
Metal pipe Plastic pipe
15~20 1.5m 1m
25~32 2m 1.5m
40~50 2.5m 2m
1.3.2.3 Outdoor unit power wiring selection
1) Separate Power Supply without power facility.
Model Power supply
The shortest wiring diameter
(mm2) Manual switch (A)
Circuit breaker
≤20m ≤50m GND Capacity Fuse
AMV-V252W/ZR1-B
380-415V
3 Phase
50Hz
4×10 4×16 10 75 50 <100mA, 0.1sec
AMV-V280W/ZR1-B 4×10 4×16 10 75 50 <100mA, 0.1sec
AMV-V335W/ZR1-B 4×10 4×16 10 75 50 <100mA, 0.1sec
AMV-V400W/ZR1-B 4×16 4×25 16 100 70 <100mA, 0.1sec
AMV-V450W/ZR1-B 4×16 4×25 16 100 70 <100mA, 0.1sec
Note: The length in the table equals the value of power cord connecting outdoor units, indicating the condition that the
voltage dropping range is within 2%. If the length exceeds the above figure, please select the wire diameter according to
relevant standard.
17 New AMV System – Control System
2) With power facilities:
a) Case 1:
b) Case 2:
Note:
Select power wire for these five models separately according to relevant standard.
The wiring diameter and the length in the table indicate the condition that the voltage dropping range is
within 2%. If the length exceeds the above figure, please select the wire diameter according to relevant
standard.
Outdoor unitpower supply
Leakageprotector
Manualswitch
Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit
GND
GND
GND
GNDBranch box
LeakageprotectorManualswitch
380-415V 3N~ 50Hz
(a)
LeakageprotectorManualswitch
GND
Branch box
Outdoor unit
GNDOutdoor unit
GNDOutdoor unit
GNDOutdoor unit
GNDOutdoor unit
GNDOutdoor unit
(b)
(a)
Power facilities 1(with leakage protector)
Power facilities 2(with leakage protector)
18 New AMV System – Control System
3) Power wire selection
Power wiring includes the main wire (a) connecting to branch box and the wire (b) between branch box and power
facilities.
Please select the wire diameter according to the following requirement.
a) Diameter of main wire (a): depends on the total horse power (HP) of outdoor unit (See (5)).
Example:
In system: 8HP×1 unit+8HP×1 unit+10HP×1 unit
So totally 26HP → See (5) → size of wire is 25mm2 (within 20m)
b) Diameter of wire (b): depends on the number of combined outdoor unit.
If outdoor unit quantity ≤ 5, the wire (b) diameter selection is same as main wire (a) selection (See (5)).
If outdoor unit quantity > 5, there will be 2 electric control boxes, the wire (b) diameter selection depends
on the total horse power (HP) of outdoor units connecting to each electric control box (See (5)).
4) Select the capacity of manual switch and fuse of the branch box depends on the total horsepower (HP).
Total capacity(HP) Manual switch(A) Fuse(A) Total capacity(HP) Manual switch(A) Fuse(A)
8-12 75 50 29- 40 150 120
13-22 100 70 41- 48 200 150
23-28 150 100 49- 64 200 175
5) Reference table of the cable size for each capacity
Total
capacity
(HP)
Minimum wire diameter (mm2 ) Total
capacity
(HP)
Minimum wire diameter (mm2 )
Wire length ≤
20m 20m<Wire length≤ 50m Wire length ≤ 20m
20m<Wire length≤
50m
8 10 16 38 35 50
10 10 16 40 35 50
12 10 16 42 50 70
14 16 25 44 50 70
16 16 25 46 50 70
18 16 25 48 50 70
20 16 25 50 70 95
22 16 25 52 70 95
24 25 35 54 70 95
26 25 35 56 70 95
28 25 35 58 70 95
30 35 50 60 70 95
32 35 50 62 70 95
34 35 50 64 70 95
36 35 50 Remark:
The above selection is for reference.
For an actual electrical project, it should be considered that the cable layout, space between cable and surroundings,
etc.
19 New AMV System – Control System
1.5.5 Indoor unit power wiring selection
Note:
Set refrigerant piping system, signal wires between indoor-indoor unit, and that between outdoor-outdoor units into
one system.
Please do not put the signal wire and power wire in the same wire tube; keep distance between the two tubes.
(Current capacity of power supply: less than 10A--300mm, less than 50A--500mm.)
Make sure to set address of outdoor unit in case of parallel multi-outdoor units.
20 New AMV System – Control System
2. Communication system
2.1 Control system introduction
2.1.1 Connecting highlights of control line (RS-485 communication)
1. The control line should be shielded wire (wire diameter of the core wire≥0.75 mm2). Using other wiring shall create
signal interference, thus leading to error operation.
2. The shielded nets at the two sides of shielded wires are either grounded to the earth, or connected with each other
and jointed to the sheet metal along to the earth.
3. Control wire could not be bound together with refrigerant pipeline and power wire. When power wire and control wire
is distributed in parallel form, keep gap between them above 300mm so as to preventing signal interference.
4. Control wire could not form closed loop.
5. Control wire has polarity, so be careful when connecting.
2.1.2 Selection of control wire specification
The ordinary shielded wire includes:
Model Name
AVP Copper core PVC insulation shielded wire
AVP-105 Heat-resistant 105˚C PVC insulation shielded wire
RVP PVC insulation shielded flexible wire
RVP-105 Heat-resistant 105˚C PVC insulation shielded flexible wire
RVVP PVC insulation shielded PVC sheath flexible wire
RVVP1 PVC insulation entangled shielded PVC sheath flexible wire
2.1.3 Signal wire of indoor/outdoor units
Signal line shall adopt 2-core shielded wire with an area above 0.75 mm2, the 2 cores are connected to P,Q or H1,H2 terminals, the shielded layer are connected to E terminals.
21 New AMV System – Control System
L1 L2 L3 N
A B C N H1 H2 E P Q E A B C N A B C NH1 H2 E P Q E H1 H2 E P Q E
L N P Q E L N P Q E L N P Q E
Main power Supply (380V~415V/3PH/50Hz)
L1 L2 L3 N
Outdoor unit (Master) Outdoor unit (Slave) Outdoor unit (Slave)
Indoor unit Indoor unit Indoor unit
Sheilded layer
Powerdistributor
Communication wired between outdoor units
Communication wired between outdoor units
Sheilded layer
Indoor unit power cable
Outdoor unit power cable
Power distributor Power distributor Power distributor
Note:
The signal connecting line between outdoor units, indoor and outdoor units and indoor units has polarity. When
connecting, be careful to prevent error connection.
Signal line shall adopt 2-core shielded wire with an area above 0.75 mm2, the 2 cores are connected to P,Q or
H1,H2 terminals, the shielded layer are connected to E terminals.
Do not bind signal line and copper pipe together with belting.
Make sure that the shield metal layer should be grounded well indoor control box in order to prevent interference.
it’s forbidden to connect 200V or above high-volt live wire to the communication terminal.
22 New AMV System – Control System
2.1.4 Correct connection
Note: Shielded layer should be connected to steel pane of electrical control box.
2.1.5 Typical wrong connection
1) Loop connection of signal wire
2) Star connection of signal wire
a) Star connection of part signal wires
b) Star connection of all signal wires
3) Reverse connection of signal wire
23 New AMV System – Control System
a) Outdoor unit to indoor unit
b) Indoor unit to indoor unit
24 New AMV System – Control System
3. Controllers
3.1 Wireless remote controller
The model of the following remote controller is Lingtong common remote controller
3.1.1 Buttons and functions descriptions
1) MODE: Press the key to switch modes in order: AUTO →COOL →DRY →HEAT →FAN →AUTO
2) ON/OFF: Push this button to turn on the unit. Push the button again to turn off the unit.
3) FAN SPEED: This button is used for setting fan speed in the sequence that goes from AUTO, LOW, MED to HIGH, then back
to AUTO.
4) TIMER: Preset the time ON (start to operate) and the time OFF (turn off the operation).
5) TURBO: Reserved
6) LAMP: Reserved
7) CLEAN: Reserved
8) HOLD: Push this button to select hold mode and canceling hold mode.
9) SLEEP: Reserved
10) AIR FLOW: Reserved
11) SWING: Push this switch button to change the louver angle.
12) TEMP: Push the button to increase the indoor temperature setting or to adjust the TIMER in a clockwise direction.
25 New AMV System – Control System
3.1.2 LCD display indications:
1) AUTO,COOL,DAY,HEAT,FAN display
2) TEMPERATURE Display
3) SLEEP,LAMP,CLEAN,HOLD display
4) TIMER Display
3.2 Wired controller
3.2.1 The remote control board is responsible for the operational status of the system through the control button, through the
LCD to display the working status of the whole system, responsible for system control board for communication
3.2.2 Safety precautions:
1) Please read this safety precaution carefully, before installation. Do observe the following safety precautions, for they are
very important.
2) Confirm there is no abnormal phenomenon during test operation after installation completed, then hand the manual to the
user.
3) Installation must be conducted by professionals
4) Improper installation may cause electric shock or fire;
5) A random disassembly may cause abnormal operation or heating, which may result in fire.
6) Don't install it in a place where combustible gas easily leaks. Once combustible gas leaks and remains around Controller,
fire may be caused.
26 New AMV System – Control System
7) Wire must be suitable for the current of Controller. Otherwise electricity leakage or heating may be caused, which may
result in fire.
8) Wire must be suitable for controller, never bring outside force to bear on the terminal. Otherwise wire break or heating may
be caused, which may result in fire.
3.2.3 Installation
1) Do not install it in a place with oil, steam or sculpture gas, or else deform or malfunction may occur.
2) Wire controller installation notice:
Please refer to indoor unit installation manual for connecting between wire controller and indoor unit.
Circuit of wire controller is low voltage circuit. Never connect it with a standard 220V/380V circuit or put it into a same
wiring tube with the circuit.
The shield cable must be connected stable to the ground, or transmission may fail.
Do not attempt to extend the shield cable by cutting, if it is necessary, use Terminal Connection Block to connect.
After finishing connection, do not use Mugger to have the insulation check to the signal wire.
Note:
When the air conditioner needs wired controller, be sure adding a wire joint with 5 terminal named A, B, C, D, E in indoor
unit, and fixing a infrared emitter whose anode and cathode connecting with A and B near the receiver in the indoor unit switch
board, then connecting the terminal +5V, GND, run in the switch board to C, D, E respectively.
27 New AMV System – Control System
3.3 Address setting remote controller
SET
ENTER
CHECK0
SET
CHECK
3.3.1 User’s instructions
1) The operation method in the address set mode
Press the "SET" key to enter the address set mode, while the triangle on the right side of the "SET" key light, the
address parameters display.
Press a certain numeric pad which corresponding to the tens-digit of a desired setting address parameters, and the
tens-digit stop blinking immediately after pressing the key, indicating the completion of a set of tens-digit.
Press a certain numeric pad again which corresponding to the ones-digit of a desired setting address parameters,
and the ones-digit stop blinking immediately after pressing the key, indicating the completion of a set of ones-digit.
Confirm whether the address of current set is right, and press the " ENTER " key of remote controller to send the
address parameters to the receiving light panel or wired controller of indoor unit if it is right; if not, press the "SET"
key to reset address parameters.
2) The operation method of address query
Press the “CHECK" key and enter the address query mode, the triangle on the right side of "CHECK" key lights and
the address parameters blinking.
Set the remote controller towards receiving light panel or wired controller and then press the "ENTER" key to send
the request to the indoor unit, the plate or wired controller connected to indoor unit will display relevant address
parameters.
3.3.2 Notices
1) Address setting range of parameters must be 0 to 63; otherwise you can’t complete the parameters setting.
2) The methods and instructions of displaying indoor unit’s address
Ducted type indoor unit (with a wired controller): Execute address query operation or press the "CHECK" key of wired
controller once, the address display area of wired controller will indicate the current address parameters for 5
seconds and then return to normal display.
Wall-mounted indoor unit (with digital display board): Execute address query operation or press the "EMERGENT" key
of the indoor electrical control board, digital tube flashes to indicate the current address parameters for 10 seconds
and then return to normal display.
4-way cassette indoor unit, floor ceiling indoor unit (with 4 LED light board): Execute address query operation or press
and hold the "EMERGENT" key on the light board for 5 to 10 seconds, according to four different LED display status
(off, steady or flashing) and tweet buzzer to indicate the address parameters, the light board return to the normal
display and the buzzer resume normal working condition after 10 seconds or loosen the lamp board "EMERGENT".
SET key: Press this key to enter the
address setting mode.
CHECK key: Press this key to enter
the address query mode.
Enter key: Press this key can send the
set address or the address query
request to indoor unit.
Numeric key: Press these key can set
address parameters, it is available
only in the address setting mode.
28 New AMV System – Control System
3) The table of the corresponding relationship between LED type and numeric.
Based on the number and type of LED lights, address parameters is the sum of number the LED corresponding to according to
the table below; if the LED is flashing, accumulate and increase 16 is the address of indoor unit; if buzzer tweet at the same time,
accumulate and increase 32 is the address of the indoor unit.
LED Corresponding numeric
Running light 8
Defrosting lamp 4
Timing lamp 2
Warning light 1 4) The table of the corresponding relationship between address parameters range and the light board & buzzer:
Address 4 LED display Tweet buzzer
0~15 steady quiet
16~31 flashing quiet
32~47 steady sound
48~63 flashing sound
3.4 Centralized controller
29 New AMV System – Control System
Centralized controller is a remote wired controller that is used for controlling up to 64 indoor units. Moreover, we could create
our AC network with this device, including the PC central monitoring system and the BMS(Building Management System).
Memory function: It can record the running parameters (mode/fan speed/temp.) when using the controller to turn on
the indoor units, all the unit will work as the last setting.
Automatically record all setting info when lose power
RS485 communication protocol
Clear & bright LCD display screen,
Background light, more parameters display
Emergency ON/OFF control with simple dry contact input 3.4.1 System configure
1) With it, we could both centrally control the indoor units and bridge up to 64 indoor units to the PC monitoring software or
BMS. In fact, on the purpose of connecting the indoor units to the PC or the gateway, which makes the indoors units visible
and can be controlled, it is necessary.
2) All the indoor units and outdoor units are NEW AMV series, the topology of the network is as follows:
3) For the network topology, either of the connection below is available.
4) To establish a steady network the following should be noted The signal wire should be 2-core shielded wire and the wire should be provided by licensed electricians.
30 New AMV System – Control System
To make signal transmission steady and to protect the facilities, the signal transmission wires should not be near to
the power line. An interval of 300mm-500mm should exist between these two kinds of wires.
The signal wire of each network should be less than 1,200m.
The unit and the centralized controller should be connected hand-in-hand, which means that all the units’ same port
should be connected to a 2-core wire and the signal wire should be linear in topology. Or else, the facilities could not
work normally.
units’ same port should be connected to a 2-core wire and the signal wire should be linear in topology. Or else, the
facilities could not work normally.
5) Structure and composition
3.4.2 Wiring
1) These 2 ways are both available
1st way:
2nd way:
31 New AMV System – Control System
2) The Centralized controller wiring ports are as follows. X, Y, E terminals are used for outdoor master unit connections. E
joint is the common grounded terminal. P, Q terminals is reserved, no need to connect.
3) Below 2 switches are reserved, no need to change.
3.4.3 Power supply
It is uses a power adaptor to obtain power supply from the normal AC220V. Remember to connect the adaptor’s connector.
3.4.4 Functions
1. Power-on or reset
After power-on or reset of the centralized controller, at first, the liquid crystal display will have its all display sections
lighting up for 2 seconds, in 1 second after all sections have gone out, the system will enter the state of normal display,
and the centralized controller will be in the state of the homepage display to show the data of the first page and search
the air conditioners online in the network.
2. Centralized controller network area address (reserved)
The local computer or gateway can be connected to 16 centralized controllers at most for communications, and as an area
32 New AMV System – Control System
of an air conditioner network, each centralized controller can be distinguished by the centralized controller through
dialing to select the corresponding address, with the setting range of 0~ 15.
3. Status indicator
If any air conditioner online in the network has failed, or the centralized controller network itself has any fault, the
indicator will flash at the frequency of 2Hz.
If one or more air conditioners online in the network are running, including the timing operation, the indicator will light up
and if idle, the indicator will flash at the frequency of 1Hz.
4. Centralized controller lock (reserved)
On receiving the centralized controller locking command sent by the computer, the centralized controller will not allow for
switching on or off the air conditioner, as well as any mode setting operation, and at the same time a command will be
sent for remote control locking of all air conditioners within the centralized controller network. On receiving the unlocking
command, the centralized controller will be actuated to conduct switching-on/off operations, and simultaneously send a
command to disable the remote controller locking state of all air conditioners.
The remote control locking state can be locked or unlocked separately by any computer or the centralized controller.
After the monitor has its power cut off, the centralized controller locking state will be memorized, and will not be
eliminate after power recovery, unless an unlocking command is received.
5. Mode locking function (reserved)
On receiving the mode locking switching-on/off command, the command is forwarded to the air conditioner, and
simultaneously the centralized controller is up set allowing for selection of the startup mode set without any conflict to
the locked mode. After the command is received to disable the mode locking, the shutdown state can be free to choose
the startup mode.
3.4.5 Button operations
1) “CHECK” button
At any time, press the button, and then the operation mode is selected as querying the operation state of the air
33 New AMV System – Control System
conditioner. By default, the first online air conditioner will be queried, and you can use the “ADDR+” and “ADDR-” buttons
to change the parameter pages for query, or you can use the “PAGE UP” and “PAGE DOWN” buttons to change the
address for querying other online air conditioners.
2) “SET” button
In any other display mode, press this button to enter the setting mode with the default of setting a single unit to display
the first online air conditioner. While setting the operation mode, again press this button, and then select to operate all air
conditioners in the network, and repeatedly press this button to switch between single settings and full setting.
3) “MODE” button
While setting the operation mode, press this button, and then select to set the air conditioner operation mode as the
cooling mode, or heating mode, or air supply mode.
4) “SPEED” button
While setting the operation mode, press this button, and then select to set the running mode of the indoor fan as
automatic speed adjustment, high speed, medium speed, or low speed.
5) “TIMER” button
While setting the operation mode, press this button, and then select to set the timer function startup time of the air
conditioner; again press this button, and then select to set the timer function shutdown time of the air conditioner; and
again press this button to select to quit the timer setting and come back to the normal operation mode.
6) “SWING” button
While setting the operation mode, press this button, and then select to enable or disable the swing function, but if all air
conditioners currently selected have no swing function or no wind speed status, this button shall be invalid.
7) “PAGE UP” button
In the “CHECK” mode, once press this button, then it will display the operation status data of the previous air conditioner,
and if already at the first unit, then again press this button to display the data of the last unit. If this button is long pressed,
then the address will decrease progressively.
In the “SET” mode, once press this button, and if the operation targets a single unit, then select the previous air
conditioner with an online address number. If it is a full operation mode, this button shall be invalid.
8) “PAGE DOWN” button
In the “CHECK” mode, once press this button, then it will display the operation status data of the next air conditioner, and
if already at the last unit, then again press this button to display the data of the first unit. If this button is long pressed,
then the address will increase progressively.
Single unit All units
COOLING HEATING FAN ONLY OFF
AUTO LOW MED HIGH
TIMER ON TIMER OFF Normal operation
34 New AMV System – Control System
In the “SET” mode, once press this button, and if the operation targets a single unit, then select the next air conditioner
with an online address number. If it is a full operation mode, this button shall be invalid.
9) “ADDR+” button
On the homepage or in the “CHECK” mode, once press this button, then it will display the next page data of the current
page, but if already on the last page, then press this button once again to display the data of the first page.
In the “Setting” mode, once press this button, and if it is in the temperature conditioning mode, then the set temperature
will increase by 1 degree, but will stop increasing any more up to the highest temperature allowed to be set; if it is the
setting mode of timed starting or shutdown time, then select the next time setting, and if there is no timing, it will show
0.0, with the specific changes as follows:
10) “ADDR-” button
On the homepage or in the “CHECK” mode, once press this button, then it will display the previous page data of the
current page, but if already on the first page, then press this button once again to display the data of the last page.
In the “SET” mode, once press this button, and if it is in the temperature conditioning mode, then the set temperature will
decrease by 1 degree, but will stop decreasing any more up to the lowest temperature allowed to be set; if it is the setting
mode of timed starting or shutdown time, then select the previous time setting, and if there is no timing, it will show 0.0,
with the specific changes as follows:
11) “ON / OFF” button
At any time, once press this button to complete centralized ON/OFF operation on all air conditioners currently online
within the centralized controller network. If all air conditioners online in the network are at the OFF state, then press this
button to complete the startup operation; if it is currently on the page for mode setting with the startup mode,
temperature, wind speed and other parameters selected, then it will follow the selected parameters for startup; if there is
no mode currently selected, but shutdown, or it is currently at other display pages, then it shall be the default startup
mode, namely it will be started in the cooling mode and strong wind, with the set temperature of 24˚C and the swing
function enabled, the default startup mode will be locked according to the system mode or judged by other restriction
conditions; if there is any conflict, it will be automatically adjusted to the next mode without conflict; if all modes are
subject to conflicts, the startup will be impossible. If one or more air conditioners online in the network are at the startup
mode (including the timing process of timed startup or shutdown), then press the button to complete all shut down
operations.
12) `“LOCK” button
In the “Mode Setting” mode, press the “Remote Controller Lock” button to lock / unlock the remote controller of the air
conditioner currently selected, with the operation mode as follows: if you select “Single Unit Setting”, then only operate
the air conditioner of the current address; if the air conditioner is in the state of remote controller locking, then it will
35 New AMV System – Control System
send a command for unlocking, or send a command for locking. If you have not selected “Single Unit Setting”, then if one
or more air conditioners currently selected are in the state of remote controller locking, then it will send a command for
unlocking and if the air conditioners currently selected are all in an unlocking state, then it will send a command for
remote controller locking.
If the remote controller is in the locking state, the air conditioner does not receive the remote control signals from its
remote controller and wire controller, until unlocked and restored to its normal receiving.
If it is currently in the state of button locking, then press the locking button to unlock it, but if it is currently in the state of
unlocking, then press the button to lock it. If it is in the state of button locking, except for the unlocking operation, any
other button operation shall be invalid.
13) “CONFIRM” button
In the setting mode, press the button to have the mode status and auxiliary functions currently selected sent to the air
conditioner already selected.
After the air conditioner has already had its operation mode, auxiliary functions and status information selected, if the
“CONFIRM” button is not pressed, then the selected information will not be sent to the air conditioner, and the current
operation of the air conditioner will not be affected.
You do not need the “CONFIRM” button for the remote control locking and unlocking operations, but only need to directly
send the command information by pressing the locking button.
14) “RESET” button
Press the button at any time, and the centralized controller will reset, with the result identical to that after power-off
recovery.
3.4.6 Settings
1) The centralized controller can be set through the panel buttons.
a. Select the “Operation Settings” page, on which you can select the operation target as a single unit or all air
conditioners.
b. The operation mode can be selected by means of the “Mode” button, and normally, you can select such modes as
cooling, heating and air supply only.
c. When the address is first selected of an air conditioner to be set, if the air conditioner is running, then the default
operation mode will display and continue to maintain the setting as the current operating status, but you can select other
startup modes by the mode selector button, and use other buttons to select the temperature setting, wind speed and
timing, or select to shut down, and the mode selection is subject to mode conflicts and mode locking judgment. If the air
conditioner is in its shutdown state, the default should be the status of startup, and the default startup mode parameters
should be followed. If the default startup parameters have any conflict with the system line running state in mode, then
select the next mode free of conflicts. The startup can not be selected if all startup modes are subject to conflicts (For
example, when a single cooler is running in the heating mode).
d. The running fan speed can be selected through the wind speed button, and normally, you can select the automatic
wind, strong wind, medium wind and slow wind.
e. The temperature can be set through the temperature control button, with the temperature setting range of 17~30˚C.
f. You can select to set the timed startup or shutdown time by means of the timer button, and if the time is set as 0, it
indicates there is no timing operation. The first timing operation is set as 0 by default, namely, there is no timing.
g. Enable or disable the swing auxiliary function through the auxiliary function button.
h. Enter the setting page for the first time, and the default should be a single mode. If the air conditioner is in the state
of shutdown, the default startup parameters should be as follows: cooling mode, temperature set as 24˚C, high speed
and no timing, with the swing function enabled.
36 New AMV System – Control System
i. At any time, press the ON / OFF button to enable or disable all air conditioners currently online. As long as one of the
air conditioner online is running, including running in the state of delay shutdown, press the button, and all online air
conditioners will shut down. If all the air conditioners currently online are in the state of shutdown, then the startup
command shall be sent as follows: If the button is pressed in the mode of page setting, then follow the currently selected
mode, wind speed, set temperature, timing, auxiliary function and other options for startup. If the button is pressed
anytime else, with no selected mode setting data and no mode limit, the startup will be enabled by default following the
cooling mode, temperature set as 24˚C, strong wind and no timing, with the swing function enabled.
2) Settings through the computer (reserved)
After receipt of the mode information sent from the computer, if there is no mode or function conflict with the selected air
conditioner, then the mode setting information is forwarded to the network interface module and air conditioner, with the
setting results sent to the computer. If there is any conflict or the mode setting is not successful, then the fault
information will be transmitted to the upper computer.
3.4.7 Instructions
Before use of the centralized controller, please confirm that the centralized controlling system has its wiring; address
setting for the outdoor unit and centralized controller, and installation of computer monitoring software are in the correct
state.
1. Initial power-on, address setting and state display of the centralized controller
(1) Power-on or reset display state
After power-on or reset of the centralized controller, at first, the liquid crystal display will have its all display sections
lighting up for 2 seconds, in 1 second after all sections have gone out, the system will enter the state of normal display,
and the centralized controller will be in the state of the homepage display to show the data of the first page. In case of
initial power-on, you must be waiting for 15 seconds before button operations.
(2). Centralized controller network area address setting (reserved)
The local computer or gateway can be connected to 16 centralized controllers at most for
communications, and as an area of an air conditioner network, each centralized controller can
be distinguished by code dialing to select the address, with the setting range of 0~ 15.
(3). Status indicator
If any air conditioner online in the network has failed, or the centralized controller network
itself has any fault, the indicator will flash at the frequency of 2Hz.
If one or more air conditioners online in the network are running, including the timing
operation, the indicator will light up and if idle, the indicator will flash at the frequency of 1Hz.
2. Basic functions of the centralized controller
(1) Network control function of the centralized controller
Control and regulate the status, parameters and on/off state of the indoor units of all air conditioners in the network.
(2). Locking functions of the centralized controller and remote controller
On receiving the centralized controller locking command sent from the computer, the centralized controller does not
allow for air conditioner on/off and mode setting operations, and at the same time, all the air conditioners within the
centralized controller network will have their remote controllers locked. On receiving the unlocking command, the
centralized controller will be actuated to complete on/off operations, and simultaneously send a command to unlock the
remote controllers of all air conditioners.
Locking state of remote controllers: The locking or unlocking operations can be completed by an individual computer or
you can press the remote controller locking button to complete the locking or unlocking operations (Irrespective of a
single indoor unit or several indoor ones, if originally locked, then unlock it; if not locked, then lock it).
37 New AMV System – Control System
(3) Mode locked function (reserved)
On receiving the computer-mode ON/OFF locking command, the air conditioner will be locked to the fixed mode, at the
same time, the centralized controller only allows selection of the set starting mode without conflict with the locking mode,
and the machines with conflicts between the current operation mode and the locking mode will automatically shut down.
On receiving the command to disable the mode locking, you can be free to choose the starting mode in the shutdown
state.
3. Centralized controller query procedures
4 Centralized controller ON / OFF operation procedure
At any time, if the ON / OFF button is directly pressed, you can complete the centralized ON / OFF operations on all air
conditioners currently online within the centralized controller network to send the parameters and mode currently
displayed on the interface to the air conditioner; if necessary, some individual or all air conditioners can be started after
such operations as mode and parameter setting are completed. Please refer to the procedure as follows:
Standby or running
Press the “CHECK” button to inquiry the running state of the first air conditioner by default.
Press the “PAGE UP/DOWN” button to search the running state of other online air conditioners by default.
Press the “ADDR+” or “ADDR-” button to search the running state of other online air conditioners by default.
Press the “CHECK” button to exit.
38 New AMV System – Control System
Initial power-on, standby or already running
1. Press the “SET” button to enter the state for setting a single air conditioner; and repeatedly press the button to switch between “Single” and “All”. If the “Single” button is selected, press the “ADDR+” or “ADDR-” to select a specific unit.
2. Directly press the “PAGE UP” and “PAGE DOWN” buttons to adjust the temperature setting; or press the “Timing” button to enter the state for setting the air conditioner timed on / off or temperature, repeatedly press the button to switch among such three modes as timed startup, timed shutdown and temperature status; after entry into one of the setting states, press the “PAGE UP” and “PAGE DOWN” buttons to set the specific parameters.
3. Press the “SPEED” button to set the wind speed of the air conditioner fans, which can be switched among such four modes as automatic speed adjustment, high speed, medium speed, or low speed.
4. Press the “MODE” button to set the operation mode of the air conditioner, which can be switched among such three modes as cooling, heating and fan only.
5. Press the “LOCK” button to lock the remote controller
Press the “CONFIRM” button to determine the set contents and send to the corresponding air conditioner to start up according to the set contents or change the parameters and mode.
6. Press the “MODE” button to select shutdown.
Press the “CONFIRM” button (continuously) to shut down.
39 New AMV System – Control System
In this operation process, Steps 1, 2, 3, 4, 5 and 6 can be performed separately, but not necessarily in order; after a certain
step is set, you can press the “CONFIRM” button to continuously set the next step and then press the “CONFIRM” button;
or you can set all the contents or only set a certain step, and then press the “CONFIRM” button. Note: Once you press the
“CONFIRM” button, the machine will soon receive the instruction information and operate as required.
3.4.8 2.4.1.7 Important notice
a. Selection of the mode button - In time of a single-unit operation, if the air conditioner is only a cooler, then the heating
mode can not be selected; in time of the full-control mode, as long as there is only one set of cooling and heating air
conditioner, then you can select the heating mode, but if there are some single coolers among the air conditioners already
selected, it will prompt function conflicts, but the mode setting operations will not be limited.
b. If the set time is 0, it indicates that there is no timing operation. In time of first entry into the timing operation, the
default time is 0, namely, no timing.
c. Swing auxiliary function – Only if the auxiliary function button selection is enabled or disabled, and as long as one of
all air conditioners selected for operations can support the selected auxiliary functions, then this function can be enabled.
Otherwise, it can not be enabled. As long as one of all air conditioners selected for operations can not support the
auxiliary functions selected as “Enabled”, then it will prompt function conflicts, but the mode setting operations will not
be limited.
d. In time of first entry into the setting page, the default mode is a single unit, if the air conditioner is idle, it will follow
the cooling mode by default for startup - The temperature is set as 24˚C, featuring strong wind and no timing, with the
swing function enabled.
e. At any time, press the ON / OFF button to enable or disable all air conditioners currently online. As long as one of the
air conditioner online is running, including running in the state of delay shutdown, press the button, and all online air
conditioners will shut down. If all the air conditioners currently online are in the state of shutdown, then the startup
command shall be sent as follows: If the button is pressed in the mode of page setting, then follow the currently selected
mode, wind speed, set temperature, timing, auxiliary function and other options for startup. If the button is pressed
anytime else, with no selected mode setting data, the startup will be enabled by default following the cooling mode,
temperature set as 24˚C, strong wind and no timing, with the swing function enabled or according to the contents
displayed on the current page.
5.3.5. Communication to the upper computer (reserved)
Once receiving the data sent to the local address from the upper computer, it will enter the network control state, but if
not for 1 consecutive minute, it will exit from the network control state. If the data communication has produced frame
errors or data check errors, then it will result in communication fault between the centralized controller and the
computer, with the fault code of “03#”, and the fault will be removed after the communication has become normal or
exited from the network control state.
40 New AMV System – Control System
3.4.9 Table for faults and protection codes
Code Fault Contents Code Protection Contents
Air conditioner faults and protection
EF Other faults PF Other protections
EE Water level detection fault PE Reserved
ED Outdoor unit fault protection PD Reserved
EC Fresh fault (reserved) PC Reserved
EB Frequency conversion module protection (reserved)
PB Reserved
EA Compressor overflow (four times) (reserved) PA Reserved
E9 Main board and display board communication fault
P9 Reserved
E8 Wind speed detection runaway (reserved) P8 Compressor overflow
E7 EEPROM error (reserved) P7 Power supply overvoltage and under voltage protection
E6 Zero crossing detection fault (reserved) P6 Exhaust low pressure protection
E5 T3 sensor fault or T4 or digital compressor discharge temperature sensor fault (reserved)
P5 Exhaust high pressure protection
E4 T2B sensor fault P4 Exhaust pipe temperature protection
E3 T2A sensor fault P3 Compressor temperature protection
E2 T1 sensor fault P2 Condenser high temperature protection
E1 Indoor and outdoor communication fault (reserved)
P1 Anti-cold wind or defrosting protection
E0 Phase sequence error or phase missing (reserved)
P0 Evaporator temperature protection
Network fault
03# Communication fault between the centralized controller and the computer (gateway)
02# Communication fault between the centralized controller and the function module
01# Communication fault between the centralized controller and the network interface module
00# Communication fault between the network interface module and the main control panel