New Buildings for IIT Madras Research Park – Phase – II,
SH: - Supply, Installation, Testing and Commissioning of Lifts
BLOCK - E
PASSENGER
LIFT#PL-
01/02/03
SERVICE
LIFT#SL-01
PASSENGER
LIFT#PL-01
PASSENGER
LIFT#PL-02
PASSENGER
LIFT#PL-04
/05
PASSENGER
LIFT PL-07
PASSENGER LIFT
PL-01 /02
SERVICE LIFT#SL-
01
PASSENGER
LIFT#PL01 /03
1088 @ 1.75
M/C ABOVE
1360 @ 1.5
M/C ABOVE
1600 @ 1.75
M/C ABOVE
1600 @ 1.75
M/C ABOVE
1088 @ 1.6
MRL
1088 @ 1.6
MRL
1088 @ 1.75 M/C
ABOVE
1360 @ 1.50 M/C
ABOVE
1088 @ 1.75
M/C ABOVE
2x 3 1 x 2 1 1 2 1 2 1 2
A
Quote should be net
including supply and
installation of lifts with
scaffolding, minor builders
work and all steel materials
such as machine beams,
bearing plates, buffer
support ladder, sill angles,
fascias etc., and should be
inclusive of all applicable
taxes.
Rs
No. of units Rs 6 2 1 1 2 1 2 1 2
Total Rs
Grand Total Rs
BLOCK - D BLOCK - C BLOCK - A & BBLOCK NO & NAME
Lift Designation
Duty (K.G.) & Speed (M.P.S.)
No. of Lifts
BOQ Summary 1 / 47
PASSENGER LIFTS
1
2
3
4
5
6
7
Project RequirementSuppliers confirmation
(MANDATORY)
A Basic
1 Equipment Source Country of Manufacture
2 No of lifts SIX (6)Three in each Tower
3 Lift designation PL 01/02/03
4 Lift shaft lay out See plan of architectural
drawings5 Capacity 1088 kgs
6 Speed 1.75 mps
7 No of stops Eleven (11)
8 No of opening at front All at front
9 No of opening at rear Nil
10 Floors Served G,1-10 .
11 Travel Height 41.0 Meter
12 Hoist way Size per lift 2200 mm(w) x2500 mm(d)
13 Overhead 5200 mm
14 Pit depth Available 1800 mm
15 Lift cabin size 1700 mm W x 1500 mm D x
2800 mm H 16 Clear entrance size 900 mm x 2400 mm C/Opng
17 Machine Room Above at Terrace Floor
IIT Block A& B Passenger Lifts PL 01/02/03
PRODUCT1.02 Summary – Traction Lift Equipment
Lift specification
Prices should be Firm for the Quoted Delivery / Completion period.
All formalities in arranging the Lift License shall be the responsibility of the lift
contractor. Owner shall extend all co operation such as signing the necessary forms
etc.
Quote for AMC should be in separate head along with lift BOQ.
GENERAL
1.01 Quality Assurance
All work shall be performed in accordance with the latest edition of the IS -14655, PARTS
1, 2, 3, 4, 5, IS 14671, IS-2147 & IS 2332,NBC 2005, state and local codes as may be
applicable
Following data sheet must be duly filled in along with source of supply. Please do
not indicate as “Standard” the standard must be specified under Suppliers
Confirmation.
Prices should be inclusive of all Taxes & Duties at the prevailing rate.
Quoted Prices should be valid for acceptance for 60 days.
Delivery / Completion: Delivery of materials 4 months from approval of shop
drawings. Lift to be erected and handed over after inspection & testing within 3
months thereafter. Shop drawings to be furnished within two weeks from date of
LOI.
Block A B
Passenger Lifts 2 / 47
PASSENGER LIFTS
Project RequirementSuppliers confirmation
(MANDATORY)Lift specification
415 Volts, 3Phase, 50 Hertz,
±10%230 Volts, I Phase , 50 Hertz
±10%B Equipment
1 Hoist Machine AC Gearless Traction
2 Roping type 1:1 or 2:1
3 Hoist Motor Permanent Magnet
synchronous motor4 Hoist motor insulation Class ‘F’
5 Hoist motor drive control
Variable Voltage Variable
Frequency with digital closed
loop velocity encoder
6 Brake system Built in to machine
,electromagnetic ± 3 mm at all load conditions
With Releveling Feature
Advance Door Opening
8 Speed variation ± 1% of rated speed
9 Main controller Microprocessor controller.
10 Group controller Built into main controller with
all features ,refer drawings.
11 Type of operation control Group operation with all
related features,
13 Door motor High speed heavy duty A/C
motor
14 Door drive control Variable Voltage Variable
Frequency control
15 Door controller Programmable microprocessor
based
16 Car doors type 900 mm(w) x2400 mm(h)
C/OPNG
17 Door Protection
Two dimensional Panachrome
Infra red door detector covering
full height &width of entrance
with minimum 150 cross beams
with LEDs on edges & with
variable timing , nudging
,limited door reversal,,
recommended Panachrome
manufactured by TL Jones.
18 Landing doors type 900 mm(w) x 2400 mm(h) C/
Opng
19 Car and Landing sills Polished hard aluminum
extrusion with non slip grooves
20 Counter weight
Cast iron fillers fitted in steel
channel frame of size and
numbers as per manufacturers
standard
21 Car and cwt guide rails Machined guide rails of
suitable size and fish plates
7
Power Characteristics
Leveling accuracy
18
Block A B
Passenger Lifts 3 / 47
PASSENGER LIFTS
Project RequirementSuppliers confirmation
(MANDATORY)Lift specification
22 Car and cwt guide shoes Spring loaded sliding / swivel
roller type
23 Load compensation Encapsulated chain with pit
guideC Safety Features
1 Emergency manual
release
Provision for manually releasing
of brake and winding
wheel/handle built in to hoist
machine 2 Car safety Flexible guide clamp type
3 Counterweight safety if
required Flexible guide clamp type
4 Over speed protection Over speed governor at
machine room
5 Landing door lock safety Emergency door unlocking
device with key6 Landing door lock Electromechanical
7 Door fire protection One(1) hour
8 Safety buffers Spring / Oil buffers
D Operating &Signal
features
1 no. COP in 3mm thick s/s
plate consists of:-a. Vandal resistant micro press
self illuminating floor markings
using LED’sb. Vandal resistant micro press
door close/open buttonc. Vandal resistant micro press
door alarm buttone .Attendant /Normal with
removable key and switchf. Car ventilator control switchg. Inter communication
switch/buttonh. Inbuilt speaker and
microphonei. Capacity plate and emergency
display
j, Scrolling type car position
indicator and directional arrows
k. All buttons are to be of
Braille type l. Lockable concealed service
control buttons/switch box
Hall call station 1 riser/ floor( configuration
dependent)
Bottom terminal landing
St / St 2mm thick cover plate
with Vandal resistant micro
press UP button
Car
All Pass & Service lifts
except Fireman’s Lift to
be quoted with option
of Conventional COP &
Touch Screen Panels.
1
Block A B
Passenger Lifts 4 / 47
PASSENGER LIFTS
Project RequirementSuppliers confirmation
(MANDATORY)Lift specification
Intermediate landing
St / St 2mm thick cover plate
with Vandal resistant micro
press UP and DN buttons
Top terminal landing
St / St 2mm thick cover plate
with Vandal resistant micro
press DN button
3 Hall position indicator at
terminal floors
Highly visible horizontal digital
or Scrolling type position
indicator combined with hall
lanternsE Finishes
Car
1 Car side panels Stainless Still 304 Grade Brush
finish
2 Car Rear panel Stainless Still 304 Grade Brush
finish
3 Car front return panels Stainless Still 304 Grade Brush
finish
4 Car transom Stainless Still 304 Grade Brush
finish
5 Car door panels Stainless Still 304 Grade Brush
finish
6 Hand rails
45mm dia, Stainless steel Brush
finish on REAR side- min 16
gauge grade 304,
7 Flooring 25 mm recess for granite or
marble
8 Kick plates 3mm(thick) x120mm( w) in
stainless steel on all sides
9 False ceiling
Selection from vendors options
or as directed by owner /
architect
10 Lighting Indirect CFL fluorescent type
of 400 lux Landing
1 Landing door panels Stainless Still 304 Grade Brush
finish
Landing entrance frames
A. At main lobbywide type (full width of wall) to
match landing door
B. At typical floors Narrow type in to match
landing door F Other Features
1 Number of start per hour Min 180 start/stops
2 Communication system
Three way communication
between car and 24 hours
security desk and lift machine
room
3 Car top inspection control
Located on car top easily
accessible with common
/up/dn/stop buttons
2
2
Block A B
Passenger Lifts 5 / 47
PASSENGER LIFTS
Project RequirementSuppliers confirmation
(MANDATORY)Lift specification
4 Car top/bottom lightLight fitting with guard and 5
amps socket with switch
5 Car top safety barrier
On three sides of car top to
height of 800mm to as
protection
6 Fireman service feature Provide fireman service feature
7 Automatic Rescue Device
To bring car and open door at
slow speed in the event of
power failure (Optional)
8 Emergency car lightBattery pack emergency light
with min of 2 hours charging 9 Alarm Bell Battery Operated Alarm Bell
10 Emergency Exits
Provide exit landing doors at
every 3rd floor or at every
11meter as applicable
11 Over load signalAudio visual signal in car with
door open feature
12 Load non stop featureFully loaded car traveling not to
respond hall calls
13 Anti nuisance featureEmpty car not to respond more
than 2 car calls
14 Car ventilation fan2 no axial blow type with side
vents in false ceiling
15 Auto Fan On / Off
Auto Fan Off after 5 minutes
when no load in car. Fan to
switch on automatically once lift
doors open & passengers enter
car
16 Safe landing
to bring car and open door at
slow speed in the event of any
malfunctioning
17 Next landing
In case doors fail to open
during normal stop, lift should
move to immediate next floor
and open doors
18 Remote wiring
Provide piping and wiring
between lift shaft/machine
room/security room
19 BMS Compatibility
Provide potential free contacts
with RS-485 interface &
modbus protocol
20 Car toe guard Provide as safety standard
21 Landing door facia coverProvide at all landing doors as
safety feature
22 Traveling cable
Provide flame and moisture
resistant flat type traveling
cable
23 Wiring
Provide copper wiring of
suitable type and serial link
system
Block A B
Passenger Lifts 6 / 47
PASSENGER LIFTS
Project RequirementSuppliers confirmation
(MANDATORY)Lift specification
24 Warranty
24 month warranty
maintenance with 24x7 call
back service with in 30 minutes
call reporting
25 As built drawing
Provide as built drawing , wiring
diagram, operating instruction
manual and parts ordering
informationSuppliers confirmation
(MANDATORY)
C Car Stopping Zone: ±4mm under any loading condition.
Comply with applicable codes, manufacturer's instructions,
shop drawings and recommendations. Comply with National
Building Code & relevant IS codes for electrical work required
during construction.
1.04 Installation
D. Door Opening Time: Seconds from start of opening to fully
open;
1 Cars: 2.4 seconds. ---
E Door Closing Time: Seconds from start of closing to fully closed;
2 Cars: 5.3 seconds. ----F Car Ride Quality
3 Horizontal acceleration within car during all
riding and door operating conditions. Not more than 15 mg peak
to peak in the 1 - 10 Hz range.
4 Acceleration and Deceleration: Smooth
constant and not more than 1 meter/second² with an initial ramp
between 0.5 and 0.75 second.
5 Sustained Jerk: Not more than 2.44 meters/second³.
G Airborne Noise: Measured noise level of lift equipment
during operation shall not exceed 50 dBA in lift lobbies and 60 dBA
inside car under any condition including door operation and car
ventilation exhaust blower on its highest speed.
Supply, transportation, loading and unloading, keep your
material in secure lockable place, installation with all necessary
scaffolding for erecting of lift, builders work and civil work should
be included in the scope of work. Including light points and fittings
and power socket for each floor in the lift shaft for the
maintenance requirement.
EXECUTION
A. Car Speed: ± 1% of contract speed under any loading
condition.
B Car Capacity: Safely lower, stop and hold 125% of rated load.
1.03 CAR PERFORMANCE
Block A B
Passenger Lifts 7 / 47
PASSENGER LIFTS
Project RequirementSuppliers confirmation
(MANDATORY)Lift specification
1.07
Quote should be net
including supply and
installation of lifts with
scaffolding, minor
builders work and all
steel materials such as
machine beams,
bearing plates, buffer
support ladder, sill
angles, fascias etc.,
and should be inclusive
of all applicable taxes.
Rs
No. of units 6 Rs
Grand Total Rs
Pro-Active Preventive Maintenance for the equipment to facilitate
the following:
1-Consistent safe operation of equipment
AMC - Requirement.
4-Maximum life cycle of equipment
5- Measurement of maintenance hours is the criteria for
achieving all of the above
1.06 Maintenance Specifications INTENT:
Prices
After warranty period for the next consecutive 5 years.
2-Maximum operational performance of equipment
3-Maximum beneficial usage of equipment
Unit Availability: All lifts shall be available for use an average
of 98.7% of property hours of operation over each three (3)
month period. This includes allowance for equipment out of
service time as the result of call-backs, scheduled preventive
maintenance, and repairs. Each three (3) month period which
indicates less than 98% availability for beneficial usage of an
individual unit or group of lifts shall result in a 20% penalty being
assessed against the quarterly amount due to the Contractor for
that individual unit or group of units for the next three (3) month
period. Penalty shall be assessed for each successive three (3)
month period in which Contractor fails to achieve beneficial usage
criteria, i.e. drop first month's results, and add results of month
just completed to previous two (2) months.
1.05 Final Inspection and Test
Comply with IS 14655-latest edition Inspectors' Manual.
Block A B
Passenger Lifts 8 / 47
SERVICE LIFT
1
2
3
4
5
6
7
Project RequirementSuppliers confirmation
(MANDATORY)
A Basic
1 Equipment Source Country of Manufacture
2 No of lifts Two (2) one in each Tower
3 Lift designation SL 01
4 Lift shaft lay outSee plan of architectural
drawings5 Capacity 1360 kgs
6 Speed 1.5 mps
7 No of stops 11
8 No of opening at front All at front
9 No of opening at rear Nil
10 Floors Served G, 1 TO 10 .
11 Travel Height 41.0 Meter
12 Hoist way Size per lift 2200 mm x 3100 mm.
13 Overhead 5200 mm
14 Pit depth Available 1600 mm
15 Lift cabin size 1300 mm W x 2400 mm D
x 2800 mm H
16 Clear entrance sizeTelescopic
1200 mm(w) x 2400 mm(h)
IIT Block A&B SERVICE SL 01
Quoted Prices should be valid for acceptance for 60 days.
PRODUCT1.02 Summary – Traction Lift Equipment
Lift specification
GENERAL
1.01 Quality Assurance
All work shall be performed in accordance with the latest edition of the IS -14655,
PARTS 1, 2, 3, 4, 5, IS 14671, IS-2147 & IS 2332,NBC 2005, state and local codes as
may be applicable
Quote for AMC should be in separate head along with lift BOQ.
All formalities in arranging the Lift License shall be the responsibility of the lift
contractor. Owner shall extend all co operation such as signing the necessary
forms etc.
Following data sheet must be duly filled in along with source of supply. Please
do not indicate as “Standard” the standard must be specified under Suppliers
Confirmation.
Prices should be inclusive of all Taxes & Duties at the prevailing rate.
Delivery / Completion: Delivery of materials 4 months from approval of shop
drawings. Lift to be erected and handed over after inspection & testing within 3
months thereafter. Shop drawings to be furnished within two weeks from date
of LOI.
Prices should be Firm for the Quoted Delivery / Completion period.
Service Lift
Block A & B 9 / 47
SERVICE LIFT
Project RequirementSuppliers confirmation
(MANDATORY)
A Basic
Lift specification
17 Machine Room Above at Terrace Floor 415 Volts, 3Phase, 50 Hertz,
±10%230 Volts, I Phase , 50 Hertz
±10%B Equipment
1 Hoist Machine AC Gearless Traction
2 Roping type 1:1 or 2:1
3 Hoist Motor Permanent Magnet
synchronous motor4 Hoist motor insulation Class ‘F’
5 Hoist motor drive control
Variable Voltage Variable
Frequency with digital
closed loop velocity
encoder
6 Brake systemBuilt in to machine
,electromagnetic ± 3 mm at all load
conditionsWith Releveling Feature
Advance Door Opening
8 Speed variation ± 1% of rated speed
9 Main controller Microprocessor controller.
10 Group controllerBuilt into main controller
with all features ,refer
11 Type of operation control Simplex Collective operation
with all related features,
13 Door motorHigh speed heavy duty A/C
motor
14 Door drive controlVariable Voltage Variable
Frequency control
15 Door controllerProgrammable
microprocessor based
16 Car doors type Telescopic
1200mm(w) x 2400 mm(h)
17 Door Protection
Two dimensional
Panachrome Infra red door
detector covering full height
&width of entrance with
minimum 150 cross beams
with LEDs on edges & with
variable timing , nudging
,limited door reversal,,
recommended Panachrome
manufactured by TL Jones.
18 Landing doors typeTelescopic
1200mm(w) x 2400 mm(h)
19 Car and Landing sills
Polished hard aluminum
extrusion with non slip
grooves
18 Power Characteristics
Leveling accuracy7
Service Lift
Block A & B 10 / 47
SERVICE LIFT
Project RequirementSuppliers confirmation
(MANDATORY)
A Basic
Lift specification
20 Counter weight
Cast iron fillers fitted in steel
channel frame of size and
numbers as per
manufacturers standard
21 Car and cwt guide rails Machined guide rails of
suitable size and fish plates
22 Car and cwt guide shoesSpring loaded sliding /
swivel roller type
23 Load compensationEncapsulated chain with pit
guideC Safety Features
1Emergency manual
release
Provision for manually
releasing of brake and
winding wheel/handle built
in to hoist machine 2 Car safety Flexible guide clamp type
3Counterweight safety if
requiredFlexible guide clamp type
4 Over speed protectionOver speed governor at
machine room
5 Landing door lock safetyEmergency door unlocking
device with key6 Landing door lock Electromechanical
7 Door fire protection One(1) hour
8 Safety buffers Spring / Oil buffers
DOperating &Signal
features
1 no. COP in 3mm thick s/s
plate consists of:-a. Vandal resistant micro
press self illuminating floor
markings using LED’sb. Vandal resistant micro
press door close/open
buttonc. Vandal resistant micro
press door alarm buttone .Attendant /Normal with
removable key and switchf. Car ventilator control
switchg. Inter communication
switch/buttonh. Inbuilt speaker and
microphonei. Capacity plate and
emergency displayj, Scrolling type car
position indicator and
directional arrowsk. All buttons are to be of
Braille type
1
Car
All Pass & Service lifts
except Fireman’s Lift
to be quoted with
option of
Conventional COP &
Touch Screen Panels.
Service Lift
Block A & B 11 / 47
SERVICE LIFT
Project RequirementSuppliers confirmation
(MANDATORY)
A Basic
Lift specification
l. Lockable concealed
service control
buttons/switch box
Hall call station1 riser/ floor( configuration
dependent)
Bottom terminal landing
St / St 2mm thick cover
plate with Vandal resistant
micro press UP button
Intermediate landing
St / St 2mm thick cover
plate with Vandal resistant
micro press UP and DN
buttons
Top terminal landing
St / St 2mm thick cover
plate with Vandal resistant
micro press DN button
3Hall position indicator at
terminal floors
Highly visible horizontal
digital or Scrolling type
position indicator combined
with hall lanterns
E Finishes
Car
1 Car side panels Stainless Still 304 Grade
Hair Line finish
2 Car Rear panel Stainless Still 304 Grade
Hair Line finish
3 Car front return panels Stainless Still 304 Grade
Hair Line finish
4 Car transom Stainless Still 304 Grade
Hair Line finish
5 Car door panels Stainless Still 304 Grade
Hair Line finish
6 Hand rails
45mm dia, Stainless steel
on REAR side- min 16 gauge
grade 304,
7 Flooring25 mm recess for granite or
marble
8 Kick plates3mm(thick) x120mm( w) in
stainless steel on all sides
9 False ceiling
Selection from vendors
options or as directed by
owner / architect
10 LightingIndirect CFL fluorescent
type of 400 lux Landing
1 Landing door panels Stainless Still 304 Grade
Hair Line finish
Landing entrance frames
A. At main lobbywide type (full width of wall)
to match landing door
2
2
Service Lift
Block A & B 12 / 47
SERVICE LIFT
Project RequirementSuppliers confirmation
(MANDATORY)
A Basic
Lift specification
B. At typical
floors
Narrow type in to match
landing door F Other Features
1 Number of start per hour Min 180 start/stops
2 Communication system
Three way communication
between car and 24 hours
security desk and lift
machine room
3Car top inspection
control
Located on car top easily
accessible with common
/up/dn/stop buttons
4 Car top/bottom lightLight fitting with guard and
5 amps socket with switch
5 Car top safety barrier
On three sides of car top to
height of 800mm to as
protection
6 Fireman service featureProvide fireman service
feature
7 Automatic Rescue Device
To bring car and open door
at slow speed in the event
of power failure (Optional)
8 Emergency car light
Battery pack emergency
light with min of 2 hours
charging
9 Alarm Bell Battery Operated Alarm Bell
10 Emergency Exits
Provide exit landing doors at
every 3rd floor or at every
11meter as applicable
11 Over load signalAudio visual signal in car
with door open feature
12 Load non stop featureFully loaded car traveling
not to respond hall calls
13 Anti nuisance featureEmpty car not to respond
more than 2 car calls
14 Car ventilation fan2 no axial blow type with
side vents in false ceiling
15 Auto Fan On / Off
Auto Fan Off after 5 minutes
when no load in car. Fan to
switch on automatically
once lift doors open &
passengers enter car
16 Safe landing
to bring car and open door
at slow speed in the event
of any malfunctioning
Service Lift
Block A & B 13 / 47
SERVICE LIFT
Project RequirementSuppliers confirmation
(MANDATORY)
A Basic
Lift specification
17 Next landing
In case doors fail to open
during normal stop, lift
should move to immediate
next floor and open doors
18 Remote wiring
Provide piping and wiring
between lift shaft/machine
room/security room
19 BMS Compatibility
Provide potential free
contacts with RS-485
interface & modbus protocol
20 Car toe guard Provide as safety standard
21 Landing door facia coverProvide at all landing doors
as safety feature
22 Traveling cable
Provide flame and moisture
resistant flat type traveling
cable
23 Wiring
Provide copper wiring of
suitable type and serial link
system
24 Warranty
24 month warranty
maintenance with 24x7 call
back service with in 30
minutes call reporting
25 As built drawing
Provide as built drawing ,
wiring diagram, operating
instruction manual and parts
ordering informationSuppliers confirmation
(MANDATORY)
F Car Ride Quality
3 Horizontal acceleration within car during all
riding and door operating conditions. Not more than 15 mg
peak to peak in the 1 - 10 Hz range.
4 Acceleration and Deceleration: Smooth
constant and not more than 1 meter/second² with an initial
ramp between 0.5 and 0.75 second.
5 Sustained Jerk: Not more than 2.44 meters/second³.
1.03 CAR PERFORMANCE
A. Car Speed: ± 1% of contract speed under any loading
condition.
B Car Capacity: Safely lower, stop and hold 125% of rated
load.
2 Cars: 3.9 seconds. ----
E Door Closing Time: Seconds from start of closing to fully closed;1 Cars: 2.0 seconds. ---
C Car Stopping Zone: ±4mm under any loading condition.
D Door Opening Time: Seconds from start of opening to fully
open;
Service Lift
Block A & B 14 / 47
SERVICE LIFT
Project RequirementSuppliers confirmation
(MANDATORY)
A Basic
Lift specification
2-Maximum operational performance of equipment
4-Maximum life cycle of equipment
5- Measurement of maintenance hours is the criteria for
achieving all of the above
1.05 Final Inspection and Test
Comply with IS 14655-latest edition Inspectors' Manual.
1.06 Maintenance Specifications INTENT:
3-Maximum beneficial usage of equipment
Unit Availability: All lifts shall be available for use an
average of 98.7% of property hours of operation over each
three (3) month period. This includes allowance for
equipment out of service time as the result of call-backs,
scheduled preventive maintenance, and repairs. Each three
(3) month period which indicates less than 98% availability
for beneficial usage of an individual unit or group of lifts shall
result in a 20% penalty being assessed against the quarterly
amount due to the Contractor for that individual unit or group
of units for the next three (3) month period. Penalty shall be
assessed for each successive three (3) month period in which
Contractor fails to achieve beneficial usage criteria, i.e. drop
first month's results, and add results of month just completed
to previous two (2) months.
AMC - Requirement.
Pro-Active Preventive Maintenance for the equipment to
facilitate the following:
After warranty period for the next consecutive 5 years.
1-Consistent safe operation of equipment
Supply, transportation, loading and unloading, keep your
material in secure lockable place, installation with all
necessary scaffolding for erecting of lift, builders work and
civil work should be included in the scope of work. Including
light points and fittings and power socket for each floor in the
lift shaft for the maintenance requirement.
G Airborne Noise: Measured noise level of lift equipment
during operation shall not exceed 50 dBA in lift lobbies and
60 dBA inside car under any condition including door
operation and car ventilation exhaust blower on its highest
speed.
Comply with applicable codes, manufacturer's instructions,
shop drawings and recommendations. Comply with National
Building Code & relevant IS codes for electrical work required
during construction.
EXECUTION
1.04 Installation
Service Lift
Block A & B 15 / 47
SERVICE LIFT
Project RequirementSuppliers confirmation
(MANDATORY)
A Basic
Lift specification
1.07
Quote should be net
including supply and
installation of lifts
with scaffolding,
minor builders work
and all steel materials
such as machine
beams, bearing
plates, buffer support
ladder, sill angles,
fascias etc., and
should be inclusive of
all applicable taxes.
Rs
No. of units 2 Rs
Grand Total Rs
Prices
Service Lift
Block A & B 16 / 47
PASSENGER LIFTS - BLOCK C
1
2
3
4
5
6
7
Project RequirementSuppliers confirmation
(MANDATORY)
A Basic
1 Equipment Source Country of Manufacture
2 No of lifts Two (2)
3 Lift designation PL 01 to PL 02
4 Lift shaft lay outSee plan of architectural
drawings5 Capacity 1600 kgs
6 Speed 1.75 mps
7 No of stops
Twelve (12) for PLO1.
Eleven (11) for PL02 &
PL03. 8 No of opening at front All at front
9 No of opening at rear Nil
10 Floors ServedPL01- G,1-10, T(terrace)
PL02 -- G,1- 10.
11 Travel Height 45.0 Meter; 41 Meter.
12 Hoist way Size per lift 2500 mm(w) x2500 mm(d)
13 Overhead 5200 mm
14 Pit depth Available 1800 mm
15 Lift cabin size 2000 mm W x 1750 mm D x
2800 mm H
IIT Block C Passenger Lifts PL 01 to PL 02
Quoted Prices should be valid for acceptance for 60 days.
PRODUCT1.02 Summary – Traction Lift Equipment
Lift specification
1.01 Quality Assurance
All work shall be performed in accordance with the latest edition of the IS -14655,
PARTS 1, 2, 3, 4, 5, IS 14671, IS-2147 & IS 2332,NBC 2005, state and local codes as
may be applicable
Quote for AMC should be in separate head along with lift BOQ.
All formalities in arranging the Lift License shall be the responsibility of the lift
contractor. Owner shall extend all co operation such as signing the necessary
forms etc.
Following data sheet must be duly filled in along with source of supply. Please
do not indicate as “Standard” the standard must be specified under Suppliers
Confirmation.
Prices should be inclusive of all Taxes & Duties at the prevailing rate.
Delivery / Completion: Delivery of materials 4 months from approval of shop
drawings. Lift to be erected and handed over after inspection & testing within 3
months thereafter. Shop drawings to be furnished within two weeks from date
of LOI.
Prices should be Firm for the Quoted Delivery / Completion period.
Passenger Lift
Block C 17 / 47
PASSENGER LIFTS - BLOCK C
Project RequirementSuppliers confirmation
(MANDATORY)Lift specification
16 Clear entrance size 1100 mm W x 2400 mm H
C/Opng17 Machine Room Above at Terrace Floor
415 Volts, 3Phase, 50 Hertz,
±10%230 Volts, I Phase , 50 Hertz
±10%B Equipment
1 Hoist Machine AC Gearless Traction
2 Roping type 1:1 or 2:1
3 Hoist Motor Permanent Magnet
synchronous motor4 Hoist motor insulation Class ‘F’
5 Hoist motor drive control
Variable Voltage Variable
Frequency with digital
closed loop velocity
encoder
6 Brake systemBuilt in to machine
,electromagnetic ± 3 mm at all load
conditionsWith Releveling Feature
Advance Door Opening
8 Speed variation ± 1% of rated speed
9 Main controller Microprocessor controller.
10 Group controllerBuilt into main controller
with all features ,refer
11 Type of operation control Group operation with all
related features,
13 Door motorHigh speed heavy duty A/C
motor
14 Door drive controlVariable Voltage Variable
Frequency control
15 Door controllerProgrammable
microprocessor based
16 Car doors type 1100 mm(w) x 2400
mm(h) C/Opng
17 Door Protection
Two dimensional
Panachrome Infra red door
detector covering full height
&width of entrance with
minimum 150 cross beams
with LEDs on edges & with
variable timing , nudging
,limited door reversal,,
recommended Panachrome
manufactured by TL Jones.
18 Landing doors type 1100 mm(w) x 2400
mm(h) C/ Opng
19 Car and Landing sills
Polished hard aluminum
extrusion with non slip
grooves
7 Leveling accuracy
18 Power Characteristics
Passenger Lift
Block C 18 / 47
PASSENGER LIFTS - BLOCK C
Project RequirementSuppliers confirmation
(MANDATORY)Lift specification
20 Counter weight
Cast iron fillers fitted in steel
channel frame of size and
numbers as per
manufacturers standard
21 Car and cwt guide rails Machined guide rails of
suitable size and fish plates
22 Car and cwt guide shoesSpring loaded sliding /
swivel roller type
23 Load compensationEncapsulated chain with pit
guideC Safety Features
1Emergency manual
release
Provision for manually
releasing of brake and
winding wheel/handle built
in to hoist machine 2 Car safety Flexible guide clamp type
3Counterweight safety if
requiredFlexible guide clamp type
4 Over speed protectionOver speed governor at
machine room
5 Landing door lock safetyEmergency door unlocking
device with key6 Landing door lock Electromechanical
7 Door fire protection One(1) hour
8 Safety buffers Spring / Oil buffers
DOperating &Signal
features
1 no. COP in 3mm thick s/s
plate consists of:-a. Vandal resistant micro
press self illuminating floor
markings using LED’sb. Vandal resistant micro
press door close/open
buttonc. Vandal resistant micro
press door alarm buttone .Attendant /Normal with
removable key and switchf. Car ventilator control
switchg. Inter communication
switch/buttonh. Inbuilt speaker and
microphonei. Capacity plate and
emergency displayj, Scrolling type car
position indicator and
directional arrowsk. All buttons are to be of
Braille type
1
Car
All Pass & Service lifts
except Fireman’s Lift
to be quoted with
option of
Conventional COP &
Touch Screen Panels.
Passenger Lift
Block C 19 / 47
PASSENGER LIFTS - BLOCK C
Project RequirementSuppliers confirmation
(MANDATORY)Lift specification
l. Lockable concealed
service control
buttons/switch box
Hall call station1 riser/ floor( configuration
dependent)
Bottom terminal landing
St / St 2mm thick cover
plate with Vandal resistant
micro press UP button
Intermediate landing
St / St 2mm thick cover
plate with Vandal resistant
micro press UP and DN
buttons
Top terminal landing
St / St 2mm thick cover
plate with Vandal resistant
micro press DN button
3Hall position indicator at
terminal floors
Highly visible horizontal
digital or Scrolling type
position indicator combined
with hall lanterns
E Finishes
Car
1 Car side panels Stainless Still 304 Grade
Brush finish
2 Car Rear panel Stainless Still 304 Grade
Brush finish
3 Car front return panels Stainless Still 304 Grade
Brush finish
4 Car transom Stainless Still 304 Grade
Brush finish
5 Car door panels Stainless Still 304 Grade
Brush finish
6 Hand rails
45mm dia, Stainless steel
on REAR side- min 16 gauge
grade 304,
7 Flooring25 mm recess for granite or
marble
8 Kick plates3mm(thick) x120mm( w) in
stainless steel on all sides
9 False ceiling
Selection from vendors
options or as directed by
owner / architect
10 LightingIndirect CFL fluorescent
type of 400 lux Landing
1 Landing door panels Stainless Still 304 Grade
Brush finish
Landing entrance frames
A. At main lobbywide type (full width of wall)
to match landing door 2
2
Passenger Lift
Block C 20 / 47
PASSENGER LIFTS - BLOCK C
Project RequirementSuppliers confirmation
(MANDATORY)Lift specification
B. At typical
floors
Narrow type in to match
landing door F Other Features
1 Number of start per hour Min 180 start/stops
2 Communication system
Three way communication
between car and 24 hours
security desk and lift
machine room
3Car top inspection
control
Located on car top easily
accessible with common
/up/dn/stop buttons
4 Car top/bottom lightLight fitting with guard and
5 amps socket with switch
5 Car top safety barrier
On three sides of car top to
height of 800mm to as
protection
6 Fireman service featureProvide fireman service
feature
7 Automatic Rescue Device
To bring car and open door
at slow speed in the event
of power failure (Optional)
8 Emergency car light
Battery pack emergency
light with min of 2 hours
charging
9 Alarm Bell Battery Operated Alarm Bell
10 Emergency Exits
Provide exit landing doors at
every 3rd floor or at every
11meter as applicable
11 Over load signalAudio visual signal in car
with door open feature
12 Load non stop featureFully loaded car traveling
not to respond hall calls
13 Anti nuisance featureEmpty car not to respond
more than 2 car calls
14 Car ventilation fan2 no axial blow type with
side vents in false ceiling
15 Auto Fan On / Off
Auto Fan Off after 5 minutes
when no load in car. Fan to
switch on automatically
once lift doors open &
passengers enter car
16 Safe landing
to bring car and open door
at slow speed in the event
of any malfunctioning
Passenger Lift
Block C 21 / 47
PASSENGER LIFTS - BLOCK C
Project RequirementSuppliers confirmation
(MANDATORY)Lift specification
17 Next landing
In case doors fail to open
during normal stop, lift
should move to immediate
next floor and open doors
18 Remote wiring
Provide piping and wiring
between lift shaft/machine
room/security room
19 BMS Compatibility
Provide potential free
contacts with RS-485
interface & modbus protocol
20 Car toe guard Provide as safety standard
21 Landing door facia coverProvide at all landing doors
as safety feature
22 Traveling cable
Provide flame and moisture
resistant flat type traveling
cable
23 Wiring
Provide copper wiring of
suitable type and serial link
system
24 Warranty
24 month warranty
maintenance with 24x7 call
back service with in 30
minutes call reporting
25 As built drawing
Provide as built drawing ,
wiring diagram, operating
instruction manual and parts
ordering informationSuppliers confirmation
(MANDATORY)1.03 CAR PERFORMANCE
5 Sustained Jerk: Not more than 2.44 meters/second³.
C Car Stopping Zone: ±4mm under any loading condition.
D Door Opening Time: Seconds from start of opening to fully
open;
1 Cars: 2.4 seconds. --- E Door Closing Time: Seconds from start of closing to fully closed;
2 Cars: 5.3 seconds. ----F Car Ride Quality
3 Horizontal acceleration within car during all
riding and door operating conditions. Not more than 15 mg
peak to peak in the 1 - 10 Hz range.
4 Acceleration and Deceleration: Smooth
constant and not more than 1 meter/second² with an initial
ramp between 0.5 and 0.75 second.
A. Car Speed: ± 1% of contract speed under any loading
condition.
B Car Capacity: Safely lower, stop and hold 125% of rated
load.
Passenger Lift
Block C 22 / 47
PASSENGER LIFTS - BLOCK C
Project RequirementSuppliers confirmation
(MANDATORY)Lift specification
4-Maximum life cycle of equipment
5- Measurement of maintenance hours is the criteria for
achieving all of the above
Comply with applicable codes, manufacturer's
instructions, shop drawings and recommendations. Comply
with National Building Code & relevant IS codes for electrical
work required during construction.
Supply, transportation, loading and unloading, keep your
material in secure lockable place, installation with all
necessary scaffolding for erecting of lift, builders work and
civil work should be included in the scope of work. Including
light points and fittings and power socket for each floor in the
lift shaft for the maintenance requirement.
2-Maximum operational performance of equipment
3-Maximum beneficial usage of equipment
1.06 Maintenance Specifications INTENT:
Unit Availability: All lifts shall be available for use an
average of 98.7% of property hours of operation over each
three (3) month period. This includes allowance for
equipment out of service time as the result of call-backs,
scheduled preventive maintenance, and repairs. Each three
(3) month period which indicates less than 98% availability
for beneficial usage of an individual unit or group of lifts shall
result in a 20% penalty being assessed against the quarterly
amount due to the Contractor for that individual unit or group
of units for the next three (3) month period. Penalty shall be
assessed for each successive three (3) month period in which
Contractor fails to achieve beneficial usage criteria, i.e. drop
first month's results, and add results of month just completed
to previous two (2) months.
1-Consistent safe operation of equipment
Pro-Active Preventive Maintenance for the equipment to
facilitate the following:
EXECUTION
1.04 Installation
G Airborne Noise: Measured noise level of lift equipment
during operation shall not exceed 50 dBA in lift lobbies and
60 dBA inside car under any condition including door
operation and car ventilation exhaust blower on its highest
speed.
1.05 Final Inspection and Test
Comply with IS 14655-latest edition Inspectors' Manual.
Passenger Lift
Block C 23 / 47
PASSENGER LIFTS - BLOCK C
Project RequirementSuppliers confirmation
(MANDATORY)Lift specification
1.07
Quote should be net
including supply and
installation of lifts
with scaffolding,
minor builders work
and all steel materials
such as machine
beams, bearing
plates, buffer support
ladder, sill angles,
fascias etc., and
should be inclusive of
all applicable taxes.
Rs
No. of units 2 Rs
Grand Total Rs
AMC - Requirement.
Prices
After warranty period for the next consecutive 5 years.
Passenger Lift
Block C 24 / 47
MRL LIFTS
1
2
3
4
5
6
7
Suppliers confirmation
MANDATORY
A Basic
1 No of lifts Three (3)
2 Lift designationMRL Lift PL 04 to 05 & PL
07
3 Lift shaft lay outSee plan of architectural
drawings1088 KG.
5 Speed 1.6 mps
6 No of stops PL 04 -05 -Four (4); PL 07 -
Five (5)7 No of opening at front All at front
8 No of opening at rear Nil
9 Floor served PL 04-05 & PL07 -G,1-4
10 Travel Height 17.0 M
11 Hoist way Size lift 2500 mm(W)x 2500 mm(D)
12 Overhead ht5000mm See plan of
architectural drawings
13 Pit depth1800mm See plan of
architectural drawings
14 Lift cabin size1700 mm W x 1500 mm D x
2800 mm H
15 Clear entrance size1100 mm (w) x 2400 mm (h)
C/Opng
IIT Block C Passenger Lifts-MRL PL 04 to 05 & PL 07
1.02 Summary – Traction Lift Equipment
All formalities in arranging the Lift License shall be the responsibility of the lift
contractor. Owner shall extend all co operation such as signing the necessary
forms etc.
Project RequirementLift specification
1.01 Quality Assurance
All work shall be performed in accordance with the latest edition of the IS -
14655, PARTS 1, 2, 3, 4, 5, IS 14671, IS-2147 & IS 2332, and such state and local
codes as may be applicable
Following data sheet must be duly filled in along with source of supply. Please
do not indicate as “Standard” the standard must be specified under Suppliers
Confirmation.
Prices should be inclusive of all Taxes & Duties at the prevailing rate.
Delivery / Completion: Delivery of materials 3 months from approval of shop
drawings. Lift to be erected and handed over after inspection & testing within
2 months thereafter. Shop drawings to be furnished within one weeks from
date of LOI.
Prices should be Firm for the Quoted Delivery / Completion period.
4 Capacity
Quoted Prices should be valid for acceptance for 60 days.
Quote for AMC should be in separate head along with lift BOQ.
PRODUCT
MRL LIFTS
Block C 25 / 47
MRL LIFTS
Suppliers confirmation
MANDATORYProject RequirementLift specification
16 Machine RoomAbove: Within the Lift shaft
(MRL)415 Volts, 3Phase, 50 Hertz,
±10%230 Volts, I Phase , 50 Hertz
±10%B Equipment
1 Hoist Machine AC Geared / Gearless Traction
2 Roping type 1:1 or 2:1
3 Hoist Motor Permanent Magnet
synchronous motor4 Hoist motor insulation Class ‘F’
5 Hoist motor drive control
Variable Voltage Variable
Frequency with digital closed
loop velocity encoder
6 Brake systemBuilt in to machine
,electromagnetic 7 Leveling accuracy ± 3 mm at all load conditions
8 Speed variation ± 1% of rated speed
9 Main controller Built into main controller
9 Group controllerBuilt into main controller with
all features ,refer drawings
10 Type of operation control Duplex Full Collective/simplex
Full Collective( as applicable)
11 Door motorHigh speed heavy duty A/C
motor
12 Door drive controlVariable Voltage Variable
Frequency control
13 Door controllerProgrammable microprocessor
basedTwo panel Center Opening
1100mm x2400mm Maximum 10 kg Weight for
Interior Decor
15 Door Protection
Two dimensional Panachrome
Infra red door detector
covering full height &width of
entrance wit minimum 150
cross beams with LEDs on
edges & with variable timing ,
nudging ,limited door reversal,,
recommended Panachrome
manufactured by TL Jones.
Two panel Center Opening
1100mm x2400mm
17 Car and Landing sillsPolished hard aluminum
extrusion with non slip grooves
Power Characteristics
16 Landing doors type
14 Car doors type
17
MRL LIFTS
Block C 26 / 47
MRL LIFTS
Suppliers confirmation
MANDATORYProject RequirementLift specification
18 Counter weight
Cast iron fillers fitted in steel
channel frame of size and
numbers as per manufacturers
standard
19 Car and cwt guide rails Machined guide rails of
suitable size and fish plates
20 Car and cwt guide shoes Sliding type
21Load compensation ( If
required )
Encapsulated chain with pit
guideC Safety Features
1Emergency manual
release
Provision for manually
releasing of brake and winding
wheel/handle built in to hoist
machine 2 Car safety Flexible guide clamp type
3Counterweight Safety If
RequitrdFlexible guide clamp type
4 Over speed protectionOver speed governor at
machine room
5 Landing door lock safetyEmergency door unlocking
device with key6 Landing door lock Electromechanical
7 Door fire protection One(1) hour
8 Safety buffers Spring / Oil buffers
DOperating &Signal
features1 no. FULL HEIGHT COPs in
hairline St / St 3mm thick
plate consists of:-a. Vandal resistant micro press
self illuminating floor buttons
using LED’sb. Vandal resistant micro press
door close/open buttonc. Vandal resistant micro press
door alarm buttone .Attendant /Normal with
removable key and switch
f. Car ventilator control switch
g. Inter communication
switch/buttonh. Inbuilt speaker and
microphonei. Capacity plate and
emergency displayj, Scrolling type car position
indicator and directional arrowsk. All buttons are to be of
Braille type
l. Digital Temperature Indicator
1 Car
MRL LIFTS
Block C 27 / 47
MRL LIFTS
Suppliers confirmation
MANDATORYProject RequirementLift specification
m. Lockable concealed service
control buttons/switch box
2 Hall call station
# riser floor( configuration
dependent)-minimum 1# per
each lift
Bottom terminal landing
St / St 2mm thick cover plate
with Vandal resistant micro
press UP button
Intermediate landing
St / St 2mm thick cover plate
with Vandal resistant micro
press UP and DN buttons
Top terminal landing
St / St 2mm thick cover plate
with Vandal resistant micro
press DN button
3Hall position indicator at
Terminal floors
Highly visible horizontal digital
or Scrolling type position
indicator combined with hall
lanterns
4Hall lanterns and chimes
at all intermediate floors
St / St 2mm thick cover plate
with hall lantern arrows and
volume adjustable electronic
chime for each lift at every E Finishes
Car
1 Car side panels Stainless Still 304 Grade Brush
finish
2 Car Rear panel Stainless Still 304 Grade Brush
finish
3 Car front return panels Stainless Still 304 Brush finish
4 Car transom Stainless Still 304 Grade Brush
finish
5 Car door panels Stainless Still 304 Grade Brush
finish
6 Hand rails
45mm dia, Stainless steel on
REAR side- min 16 gauge
grade 304,
7 Flooring25 mm recess for granite or
marble
8 Kick plates3 mm(thick) x120mm( w) in
stainless steel on all sides
9 False ceiling Selection form vendors options
10 LightingIndirect fluorescent type of
400 lux lightingLanding
1 Landing door panels Stainless Still 304 Grade Brush
finish
Landing entrance frames
MRL LIFTS
Block C 28 / 47
MRL LIFTS
Suppliers confirmation
MANDATORYProject RequirementLift specification
A. At main lobby
B. At typical floors
wide type (full width of wall) to
match landing door Narrow
type to match landing door
F Other Features
1 Number of start per hour Min 180 start/stops
2 Communication system
Three way communication
between car and 24 hours
security desk and lift machine
room
3Car top inspection
control
Located on car top easily
accessible with common
/up/dn/stop buttons
4 Car top/bottom lightLight fitting with guard and 5
amps socket with switch
5 Car top safety barrier
On three sides of car top to
height of 800mm to as
protection
6 Fireman service feature Provide fireman service feature
7 Automatic Rescue Device
To bring car and open door at
slow speed in the event of
power failure
8 Emergency car lightBattery pack emergency light
with min of 2 hours charging
9Emergency Power
Supply
Provision to operate the Lift on
Emergency / Alternate Power
Supply10 Alarm Bell Battery Operated Alarm Bell
11 MUSIC Provision for Music inside Car
12 Automatic Rescue DeviceTo bring lift to nearest landing
in case of power failure
13 Emergency Exits
Provide exit landing doors at
every 3rd floor or at every
11meter as applicable
14 Over load signalAudio visual signal in car with
door open feature
15 Load non stop featureFully loaded car traveling not
to respond hall calls
16 Anti nuisance featureEmpty car not to respond more
than 2 car calls
17 Car ventilation fan2 no axial blow type with side
vents in false ceiling
18 Auto Fan On / Off
Auto Fan Off after 5 minutes
when no load in car. Fan to
switch on automatically once
lift doors open & passengers
enter car
19 Safe landing
to bring car and open door at
slow speed in the event of any
malfunctioning
2
MRL LIFTS
Block C 29 / 47
MRL LIFTS
Suppliers confirmation
MANDATORYProject RequirementLift specification
20 Next landing
In case doors fail to open
during normal stop, lift should
move to immediate next floor
and open doors
21 CCTV provisionProvide CCTV provision for all
cars
22 Fireman’s service featureProvide fireman’s service
feature
23 BMS Compatibility
Provide potential free contacts
with RS-485 & modbus
protocol
24 Car toe guard Provide as safety standard
25Landing door fascia
cover
Provide at all landing doors as
safety feature
26 Traveling cable
Provide flame and moisture
proof resistance flat type
traveling cable
27 Wiring
Provide copper wiring of
suitable type and serial link
system
28 Steel Material
Steel Items such as M/C
Beams, Buffer support
Channels, Ladder in pit, Fascia
Plates etc to be included.
29 Warranty
24 month warranty
maintenance with 24x7 call
back service with in 30
minutes call reporting
30 As built drawing
Provide as built drawing ,
wiring diagram, operating
instruction manual and parts
ordering informationSuppliers confirmation
(MANDATORY)
A- Car Speed: ± 1% of contract speed under any loading
condition.
Cars: 1.4 seconds.
E- Door Closing Time: Seconds from start of closing to fully
closed;
Cars: 2.0 seconds.
F- Car Ride Quality
1 Horizontal acceleration within car during all
riding and door operating conditions. Not more than 20 mg
peak to peak in the 1 - 10 Hz range.
B- Car Capacity: Safely lower, stop and hold 125% of rated
load.
C- Car Stopping Zone: ±4mm under any loading condition.
D- Door Opening Time: Seconds from start of opening to fully
open;
1.03 CAR PERFORMANCE
MRL LIFTS
Block C 30 / 47
MRL LIFTS
Suppliers confirmation
MANDATORYProject RequirementLift specification
EXECUTION
1.06 Maintenance Specifications INTENT:
Pro-Active Preventive Maintenance for the equipment to
facilitate the following:
G- Airborne Noise: Measured noise level of lift equipment
during operation shall not exceed 50 dBA in lift lobbies and 60
dBA inside car under any condition including door operation and
car ventilation exhaust blower on its highest speed.
2 Acceleration and Deceleration: Smooth constant
and not more than 1 meter/second² with an initial ramp 3 Sustained Jerk: Not more than 2.44 meters/second³.
1- Consistent safe operation of equipment
2-Maximum operational performance of equipment
3- Maximum beneficial usage of equipment
4- Maximum life cycle of equipment
5- Measurement of maintenance hours is the criteria for
achieving all of the above
1.04 Installation
Comply with applicable codes, manufacturer's instructions,
shop drawings and recommendations. Comply with National
Building Code & relevant IS codes for electrical work required
during construction.
Supply, transportation, loading and unloading, keep your
material in secure lockable place. Installation with all necessary
(1)Scaffolding for erecting of lift
(2) Necessary minor builders work and civil work for erection of
lifts
(3) Steel materials such as m/c beams , bearing plates, buffer
support chanels,sill angles, pit laader etc.
(4) Light points and fittings and power socket for each floor in
the lift shaft for the maintenance requirement should be
included in the scope of work..
Comply with IS 14655-latest edition Inspectors' Manual.
1.05 Final Inspection and Test
MRL LIFTS
Block C 31 / 47
MRL LIFTS
Suppliers confirmation
MANDATORYProject RequirementLift specification
1.07
Quote should be net
including supply and
installation of lifts
with scaffolding,
minor builders work
and all steel materials
such as machine
beams, bearing
plates, buffer support
ladder, sill angles,
fascias etc., and
should be inclusive of
all applicable taxes.
Rs
No. of units 3 Rs
Grand Total Rs
Prices
AMC - Requirement.After warranty period for the next consecutive 5 years.
Unit Availability: All lifts shall be available for use an
average of 98.7% of property hours of operation over each
three (3) month period. This includes allowance for equipment
out of service time as the result of call-backs, scheduled
preventive maintenance, and repairs. Each three (3) month
period which indicates less than 98% availability for beneficial
usage of an individual unit or group of lifts shall result in a 20%
penalty being assessed against the quarterly amount due to the
Contractor for that individual unit or group of units for the next
three (3) month period. Penalty shall be assessed for each
successive three (3) month period in which Contractor fails to
achieve beneficial usage criteria, i.e. drop first month's results,
and add results of month just completed to previous two (2)
months.
MRL LIFTS
Block C 32 / 47
PASSENGER LIFT - BLOCK D & E
1
2
3
4
5
6
7
Project RequirementSuppliers confirmation
(MANDATORY)
A Basic
1 Equipment Source Country of Manufacture
2 No of lifts Four (4) Two in each tower
3 Lift designation D PL 01/02 & E PL0 1/03
4 Lift shaft lay outSee plan of architectural
drawings5 Capacity 1088 kgs
6 Speed 1.75 mps
7 No of stops Block D --Nine (9). Block E -
- Seven(7).8 No of opening at front All at front
9 No of opening at rear Nil
10 Floors ServedBlock D PL- 01/02 - B1,G,1-7
.& Block E PL 01/03 - G-7.
11 Travel Height 34.5 Meter & 20.1 Meter
respectively.12 Hoist way Size per lift 2200 mm(w) x2500 mm(d)
13 Overhead 5200 mm
14 Pit depth Available 1800 mm
15 Lift cabin size 1700 mm W x 1500 mm D x
2800 mm H 16 Clear entrance size 900 mm x 2400 mm C/Opng
All formalities in arranging the Lift License shall be the responsibility of the lift
contractor. Owner shall extend all co operation such as signing the necessary
forms etc.
Quoted Prices should be valid for acceptance for 60 days.
Quote for AMC should be in separate head along with lift BOQ.
PRODUCT1.02 Summary – Traction Lift Equipment
Lift specification
All work shall be performed in accordance with the latest edition of the IS -14655,
PARTS 1, 2, 3, 4, 5, IS 14671, IS-2147 & IS 2332,NBC 2005,state and local codes as may
be applicable
BLOCK D & E PASSENGER LIFTS PL-01/03
GENERAL
1.01 Quality Assurance
Following data sheet must be duly filled in along with source of supply. Please do
not indicate as “Standard” the standard must be specified under Suppliers
Confirmation.
Prices should be inclusive of all Taxes & Duties at the prevailing rate.
Delivery / Completion: Delivery of materials 4 months from approval of shop
drawings. Lift to be erected and handed over after inspection & testing within 3
months thereafter. Shop drawings to be furnished within two weeks from date of
LOI.
Prices should be Firm for the Quoted Delivery / Completion period.
PASSENGER LIFT
BLOCK D & E 33 / 47
PASSENGER LIFT - BLOCK D & E
17 Machine Room Above at Terrace Floor 415 Volts, 3Phase, 50 Hertz,
±10%230 Volts, I Phase , 50 Hertz
±10%B Equipment
1 Hoist Machine AC Gearless Traction
2 Roping type 1:1 or 2:1
3 Hoist Motor Permanent Magnet
synchronous motor4 Hoist motor insulation Class ‘F’
5 Hoist motor drive control
Variable Voltage Variable
Frequency with digital closed
loop velocity encoder
6 Brake systemBuilt in to machine
,electromagnetic ± 3 mm at all load conditions
With Releveling Feature
Advance Door Opening
8 Speed variation ± 1% of rated speed
9 Main controller Microprocessor controller.
10 Group controllerBuilt into main controller with
all features ,refer drawings.
11 Type of operation control Group operation with all
related features,
13 Door motorHigh speed heavy duty A/C
motor
14 Door drive controlVariable Voltage Variable
Frequency control
15 Door controllerProgrammable microprocessor
based
16 Car doors type 900 mm(w) x2400 mm(h)
C/OPNG
17 Door Protection
Two dimensional Panachrome
Infra red door detector covering
full height &width of entrance
with minimum 150 cross beams
with LEDs on edges & with
variable timing , nudging
,limited door reversal,,
recommended Panachrome
manufactured by TL Jones.
18 Landing doors type 900 mm(w) x 2400 mm(h) C/
Opng
19 Car and Landing sillsPolished hard aluminum
extrusion with non slip grooves
20 Counter weight
Cast iron fillers fitted in steel
channel frame of size and
numbers as per manufacturers
standard
21 Car and cwt guide rails Machined guide rails of
suitable size and fish plates
18 Power Characteristics
7 Leveling accuracy
PASSENGER LIFT
BLOCK D & E 34 / 47
PASSENGER LIFT - BLOCK D & E
22 Car and cwt guide shoesSpring loaded sliding / swivel
roller type
23 Load compensationEncapsulated chain with pit
guideC Safety Features
1Emergency manual
release
Provision for manually releasing
of brake and winding
wheel/handle built in to hoist
machine 2 Car safety Flexible guide clamp type
3Counterweight safety if
requiredFlexible guide clamp type
4 Over speed protectionOver speed governor at
machine room
5 Landing door lock safetyEmergency door unlocking
device with key6 Landing door lock Electromechanical
7 Door fire protection One(1) hour
8 Safety buffers Spring / Oil buffers
DOperating &Signal
features
1 no. COP in 3mm thick s/s
plate consists of:-a. Vandal resistant micro press
self illuminating floor markings
using LED’sb. Vandal resistant micro press
door close/open buttonc. Vandal resistant micro press
door alarm buttone .Attendant /Normal with
removable key and switchf. Car ventilator control switchg. Inter communication
switch/buttonh. Inbuilt speaker and
microphonei. Capacity plate and emergency
display
j, Scrolling type car position
indicator and directional arrows
k. All buttons are to be of
Braille type l. Lockable concealed service
control buttons/switch box
Hall call station1 riser/ floor( configuration
dependent)
Bottom terminal landing
St / St 2mm thick cover plate
with Vandal resistant micro
press UP button
Intermediate landing
St / St 2mm thick cover plate
with Vandal resistant micro
press UP and DN buttons
1
2
Car
All Pass & Service lifts
except Fireman’s Lift
to be quoted with
option of
Conventional COP &
Touch Screen Panels.
PASSENGER LIFT
BLOCK D & E 35 / 47
PASSENGER LIFT - BLOCK D & E
Top terminal landing
St / St 2mm thick cover plate
with Vandal resistant micro
press DN button
3Hall position indicator at
terminal floors
Highly visible horizontal digital
or Scrolling type position
indicator combined with hall
lanternsE Finishes
Car
1 Car side panels Stainless Still 304 Grade Brush
finish
2 Car Rear panel Stainless Still 304 Grade Brush
finish
3 Car front return panels Stainless Still 304 Grade Brush
finish
4 Car transom Stainless Still 304 Grade Brush
finish
5 Car door panels Stainless Still 304 Grade Brush
finish
6 Hand rails
45mm dia, Stainless steel Brush
finish on REAR side- min 16
gauge grade 304,
7 Flooring25 mm recess for granite or
marble
8 Kick plates3mm(thick) x120mm( w) in
stainless steel on all sides
9 False ceiling
Selection from vendors options
or as directed by owner /
architect
10 LightingIndirect CFL fluorescent type
of 400 lux Landing
1 Landing door panels Stainless Still 304 Grade Brush
finish
Landing entrance frames
A. At main lobbywide type (full width of wall) to
match landing door B. At typical
floors
Narrow type in to match
landing door F Other Features
1 Number of start per hour Min 180 start/stops
2 Communication system
Three way communication
between car and 24 hours
security desk and lift machine
room
3Car top inspection
control
Located on car top easily
accessible with common
/up/dn/stop buttons
4 Car top/bottom lightLight fitting with guard and 5
amps socket with switch
5 Car top safety barrier
On three sides of car top to
height of 800mm to as
protection
2
PASSENGER LIFT
BLOCK D & E 36 / 47
PASSENGER LIFT - BLOCK D & E
6 Fireman service feature Provide fireman service feature
7 Automatic Rescue Device
To bring car and open door at
slow speed in the event of
power failure (Optional)
8 Emergency car lightBattery pack emergency light
with min of 2 hours charging 9 Alarm Bell Battery Operated Alarm Bell
10 Emergency Exits
Provide exit landing doors at
every 3rd floor or at every
11meter as applicable
11 Over load signalAudio visual signal in car with
door open feature
12 Load non stop featureFully loaded car traveling not to
respond hall calls
13 Anti nuisance featureEmpty car not to respond more
than 2 car calls
14 Car ventilation fan2 no axial blow type with side
vents in false ceiling
15 Auto Fan On / Off
Auto Fan Off after 5 minutes
when no load in car. Fan to
switch on automatically once lift
doors open & passengers enter
car
16 Safe landing
to bring car and open door at
slow speed in the event of any
malfunctioning
17 Next landing
In case doors fail to open
during normal stop, lift should
move to immediate next floor
and open doors
18 Remote wiring
Provide piping and wiring
between lift shaft/machine
room/security room
19 BMS Compatibility
Provide potential free contacts
with RS-485 interface &
modbus protocol
20 Car toe guard Provide as safety standard
21 Landing door facia coverProvide at all landing doors as
safety feature
22 Traveling cable
Provide flame and moisture
resistant flat type traveling
cable
23 Wiring
Provide copper wiring of
suitable type and serial link
system
24 Warranty
24 month warranty
maintenance with 24x7 call
back service with in 30 minutes
call reporting
25 As built drawing
Provide as built drawing , wiring
diagram, operating instruction
manual and parts ordering
information
PASSENGER LIFT
BLOCK D & E 37 / 47
PASSENGER LIFT - BLOCK D & E
Suppliers confirmation
(MANDATORY)
Comply with applicable codes, manufacturer's instructions,
shop drawings and recommendations. Comply with National
Building Code & relevant IS codes for electrical work required
during construction.
Supply, transportation, loading and unloading, keep your
material in secure lockable place, installation with all necessary
scaffolding for erecting of lift, builders work and civil work should
be included in the scope of work. Including light point
C Car Stopping Zone: ±4mm under any loading condition.
D. Door Opening Time: Seconds from start of opening to fully
open;
1.05 Final Inspection and Test
Comply with IS 14655-latest edition Inspectors' Manual.
5 Sustained Jerk: Not more than 2.44 meters/second³.
G Airborne Noise: Measured noise level of lift equipment
during operation shall not exceed 50 dBA in lift lobbies and 60
dBA inside car under any condition including door operation and
car ventilation exhaust blower on its highest speed.
EXECUTION
1.04 Installation
3 Horizontal acceleration within car during all
riding and door operating conditions. Not more than 15 mg
peak to peak in the 1 - 10 Hz range.
4 Acceleration and Deceleration: Smooth
constant and not more than 1 meter/second² with an initial ramp
between 0.5 and 0.75 second.
1.03 CAR PERFORMANCE
A. Car Speed: ± 1% of contract speed under any loading
condition.
B Car Capacity: Safely lower, stop and hold 125% of rated load.
2 Cars: 5.3 seconds. ----F Car Ride Quality
1 Cars: 2.4 seconds. ---
E Door Closing Time: Seconds from start of closing to fully
closed;
PASSENGER LIFT
BLOCK D & E 38 / 47
PASSENGER LIFT - BLOCK D & E
1.07
Quote should be net
including supply and
installation of lifts
with scaffolding,
minor builders work
and all steel materials
such as machine
beams, bearing
plates, buffer support
ladder, sill angles,
fascias etc., and
should be inclusive of
all applicable taxes.
Rs
No. of units 4 Rs
Grand Total Rs
Pro-Active Preventive Maintenance for the equipment to facilitate
the following:
3-Maximum beneficial usage of equipment
4-Maximum life cycle of equipment
1-Consistent safe operation of equipment
2-Maximum operational performance of equipment
1.06 Maintenance Specifications INTENT:
Prices
5- Measurement of maintenance hours is the criteria for
achieving all of the above
Unit Availability: All lifts shall be available for use an
average of 98.7% of property hours of operation over each three
(3) month period. This includes allowance for equipment out of
service time as the result of call-backs, scheduled preventive
maintenance, and repairs. Each three (3) month period which
indicates less than 98% availability for beneficial usage of an
individual unit or group of lifts shall result in a 20% penalty
being assessed against the quarterly amount due to the
Contractor for that individual unit or group of units for the next
three (3) month period. Penalty shall be assessed for each
successive three (3) month period in which Contractor fails to
achieve beneficial usage criteria, i.e. drop first month's results,
and add results of month just completed to previous two (2)
months.
AMC - Requirement.After warranty period for the next consecutive 5 years.
PASSENGER LIFT
BLOCK D & E 39 / 47
SERVICE LIFTS
BLOCK D
1
2
3
4
5
6
7
Project RequirementSuppliers confirmation
(MANDATORY)
A Basic
1 Equipment Source Country of Manufacture
2 No of lifts One(1)
3 Lift designation SL 01
4 Lift shaft lay outSee plan of architectural
drawings5 Capacity 1360 kgs
6 Speed 1.5 mps
7 No of stops 11
8 No of opening at front All at front
9 No of opening at rear Nil
10 Floors Served G, 1 TO 10 .
11 Travel Height 41.0 Meter
12 Hoist way Size per lift 2200 mm x 3100 mm.
13 Overhead 5200 mm
14 Pit depth Available 1600 mm
15 Lift cabin size 1300 mm W x 2400 mm D
x 2800 mm H
16 Clear entrance sizeTelescopic
1200 mm(w) x 2400 mm(h)
17 Machine Room Above at Terrace Floor
All formalities in arranging the Lift License shall be the responsibility of the lift
contractor. Owner shall extend all co operation such as signing the necessary
forms etc.
Quoted Prices should be valid for acceptance for 60 days.
Quote for AMC should be in separate head along with lift BOQ.
PRODUCT1.02 Summary – Traction Lift Equipment
Lift specification
All work shall be performed in accordance with the latest edition of the IS -14655,
PARTS 1, 2, 3, 4, 5, IS 14671, IS-2147 & IS 2332,NBC 2005, State and local codes as
may be applicable
Block D SERVICE LIFTS SL-01
GENERAL
1.01 Quality Assurance
Following data sheet must be duly filled in along with source of supply. Please
do not indicate as “Standard” the standard must be specified under Suppliers
Confirmation.
Prices should be inclusive of all Taxes & Duties at the prevailing rate.
Delivery / Completion: Delivery of materials 4 months from approval of shop
drawings. Lift to be erected and handed over after inspection & testing within 3
months thereafter. Shop drawings to be furnished within two weeks from date
of LOI.
Prices should be Firm for the Quoted Delivery / Completion period.
SERVICE LIFTS
BLOCK D 40 / 47
SERVICE LIFTS
BLOCK D
415 Volts, 3Phase, 50 Hertz,
±10%230 Volts, I Phase , 50 Hertz
±10%B Equipment
1 Hoist Machine AC Gearless Traction
2 Roping type 1:1 or 2:1
3 Hoist Motor Permanent Magnet
synchronous motor4 Hoist motor insulation Class ‘F’
5 Hoist motor drive control
Variable Voltage Variable
Frequency with digital
closed loop velocity
encoder
6 Brake systemBuilt in to machine
,electromagnetic ± 3 mm at all load
conditionsWith Releveling Feature
Advance Door Opening
8 Speed variation ± 1% of rated speed
9 Main controller Microprocessor controller.
10 Group controller
Built into main controller
with all features ,refer
drawings.
11 Type of operation control Simplex Collective operation
with all related features,
13 Door motorHigh speed heavy duty A/C
motor
14 Door drive controlVariable Voltage Variable
Frequency control
15 Door controllerProgrammable
microprocessor based
16 Car doors type Telescopic
1200mm(w) x 2400 mm(h)
17 Door Protection
Two dimensional
Panachrome Infra red door
detector covering full height
&width of entrance with
minimum 150 cross beams
with LEDs on edges & with
variable timing , nudging
,limited door reversal,,
recommended Panachrome
manufactured by TL Jones.
18 Landing doors typeTelescopic
1200mm(w) x 2400 mm(h)
19 Car and Landing sills
Polished hard aluminum
extrusion with non slip
grooves
18 Power Characteristics
7 Leveling accuracy
SERVICE LIFTS
BLOCK D 41 / 47
SERVICE LIFTS
BLOCK D
20 Counter weight
Cast iron fillers fitted in steel
channel frame of size and
numbers as per
manufacturers standard
21 Car and cwt guide rails Machined guide rails of
suitable size and fish plates
22 Car and cwt guide shoesSpring loaded sliding /
swivel roller type
23 Load compensationEncapsulated chain with pit
guideC Safety Features
1Emergency manual
release
Provision for manually
releasing of brake and
winding wheel/handle built
in to hoist machine 2 Car safety Flexible guide clamp type
3Counterweight safety if
requiredFlexible guide clamp type
4 Over speed protectionOver speed governor at
machine room
5 Landing door lock safetyEmergency door unlocking
device with key6 Landing door lock Electromechanical
7 Door fire protection One(1) hour
8 Safety buffers Spring / Oil buffers
DOperating &Signal
features
1 no. COP in 3mm thick s/s
plate consists of:-a. Vandal resistant micro
press self illuminating floor
markings using LED’sb. Vandal resistant micro
press door close/open
buttonc. Vandal resistant micro
press door alarm buttone .Attendant /Normal with
removable key and switchf. Car ventilator control
switchg. Inter communication
switch/buttonh. Inbuilt speaker and
microphonei. Capacity plate and
emergency displayj, Scrolling type car
position indicator and
directional arrowsk. All buttons are to be of
Braille type l. Lockable concealed
service control
buttons/switch box
1
Car
All Pass & Service lifts
except Fireman’s Lift
to be quoted with
option of
Conventional COP &
Touch Screen Panels.
SERVICE LIFTS
BLOCK D 42 / 47
SERVICE LIFTS
BLOCK D
Hall call station1 riser/ floor( configuration
dependent)
Bottom terminal landing
St / St 2mm thick cover
plate with Vandal resistant
micro press UP button
Intermediate landing
St / St 2mm thick cover
plate with Vandal resistant
micro press UP and DN
buttons
Top terminal landing
St / St 2mm thick cover
plate with Vandal resistant
micro press DN button
3Hall position indicator at
terminal floors
Highly visible horizontal
digital or Scrolling type
position indicator combined
with hall lanterns
E Finishes
Car
1 Car side panels Stainless Still 304 Grade
Hair Line finish
2 Car Rear panel Stainless Still 304 Grade
Hair Line finish
3 Car front return panels Stainless Still 304 Grade
Hair Line finish
4 Car transom Stainless Still 304 Grade
Hair Line finish
5 Car door panels Stainless Still 304 Grade
Hair Line finish
6 Hand rails
45mm dia, Stainless steel
on REAR side- min 16 gauge
grade 304,
7 Flooring25 mm recess for granite or
marble
8 Kick plates3mm(thick) x120mm( w) in
stainless steel on all sides
9 False ceiling
Selection from vendors
options or as directed by
owner / architect
10 LightingIndirect CFL fluorescent
type of 400 lux Landing
1 Landing door panels Stainless Still 304 Grade
Hair Line finish
Landing entrance frames
A. At main lobbywide type (full width of wall)
to match landing door
B. At typical
floors
Narrow type in to match
landing door F Other Features
1 Number of start per hour Min 180 start/stops
2
2
SERVICE LIFTS
BLOCK D 43 / 47
SERVICE LIFTS
BLOCK D
2 Communication system
Three way communication
between car and 24 hours
security desk and lift
machine room
3Car top inspection
control
Located on car top easily
accessible with common
/up/dn/stop buttons
4 Car top/bottom lightLight fitting with guard and
5 amps socket with switch
5 Car top safety barrier
On three sides of car top to
height of 800mm to as
protection
6 Fireman service featureProvide fireman service
feature
7 Automatic Rescue Device
To bring car and open door
at slow speed in the event
of power failure (Optional)
8 Emergency car light
Battery pack emergency
light with min of 2 hours
charging
9 Alarm Bell Battery Operated Alarm Bell
10 Emergency Exits
Provide exit landing doors at
every 3rd floor or at every
11meter as applicable
11 Over load signalAudio visual signal in car
with door open feature
12 Load non stop featureFully loaded car traveling
not to respond hall calls
13 Anti nuisance featureEmpty car not to respond
more than 2 car calls
14 Car ventilation fan2 no axial blow type with
side vents in false ceiling
15 Auto Fan On / Off
Auto Fan Off after 5 minutes
when no load in car. Fan to
switch on automatically
once lift doors open &
passengers enter car
16 Safe landing
to bring car and open door
at slow speed in the event
of any malfunctioning
17 Next landing
In case doors fail to open
during normal stop, lift
should move to immediate
next floor and open doors
18 Remote wiring
Provide piping and wiring
between lift shaft/machine
room/security room
SERVICE LIFTS
BLOCK D 44 / 47
SERVICE LIFTS
BLOCK D
19 BMS Compatibility
Provide potential free
contacts with RS-485
interface & modbus protocol
20 Car toe guard Provide as safety standard
21 Landing door facia coverProvide at all landing doors
as safety feature
22 Traveling cable
Provide flame and moisture
resistant flat type traveling
cable
23 Wiring
Provide copper wiring of
suitable type and serial link
system
24 Warranty
24 month warranty
maintenance with 24x7 call
back service with in 30
minutes call reporting
25 As built drawing
Provide as built drawing ,
wiring diagram, operating
instruction manual and parts
ordering information
Suppliers confirmation
(MANDATORY)
C Car Stopping Zone: ±4mm under any loading condition.
D Door Opening Time: Seconds from start of opening to fully
open;
5 Sustained Jerk: Not more than 2.44 meters/second³.
G Airborne Noise: Measured noise level of lift equipment
during operation shall not exceed 50 dBA in lift lobbies and
60 dBA inside car under any condition including door
operation and car ventilation exhaust blower on its highest
speed.
3 Horizontal acceleration within car during all
riding and door operating conditions. Not more than 15 mg
peak to peak in the 1 - 10 Hz range.
4 Acceleration and Deceleration: Smooth
constant and not more than 1 meter/second² with an initial
ramp between 0.5 and 0.75 second.
1.03 CAR PERFORMANCE
A. Car Speed: ± 1% of contract speed under any loading
condition.
B Car Capacity: Safely lower, stop and hold 125% of rated
load.
2 Cars: 3.9 seconds. ----F Car Ride Quality
1 Cars: 2.0 seconds. --- E Door Closing Time: Seconds from start of closing to fully closed;
SERVICE LIFTS
BLOCK D 45 / 47
SERVICE LIFTS
BLOCK D
Pro-Active Preventive Maintenance for the equipment to
facilitate the following:
3-Maximum beneficial usage of equipment
4-Maximum life cycle of equipment
1-Consistent safe operation of equipment
2-Maximum operational performance of equipment
1.06 Maintenance Specifications INTENT:
Comply with applicable codes, manufacturer's
instructions, shop drawings and recommendations. Comply
with National Building Code & relevant IS codes for electrical
work required during construction.
Supply, transportation, loading and unloading, keep your
material in secure lockable place, installation with all
necessary scaffolding for erecting of lift, builders work and
civil work should be included in the scope of work. Including
light point
1.05 Final Inspection and Test
Comply with IS 14655-latest edition Inspectors' Manual.
5- Measurement of maintenance hours is the criteria for
achieving all of the above
Unit Availability: All lifts shall be available for use
an average of 98.7% of property hours of operation over
each three (3) month period. This includes allowance for
equipment out of service time as the result of call-backs,
scheduled preventive maintenance, and repairs. Each three
(3) month period which indicates less than 98% availability
for beneficial usage of an individual unit or group of lifts shall
result in a 20% penalty being assessed against the quarterly
amount due to the Contractor for that individual unit or group
of units for the next three (3) month period. Penalty shall be
assessed for each successive three (3) month period in which
Contractor fails to achieve beneficial usage criteria, i.e. drop
first month's results, and add results of month just completed
to previous two (2) months.AMC - Requirement.After warranty period for the next consecutive 5 years.
EXECUTION
1.04 Installation
SERVICE LIFTS
BLOCK D 46 / 47
SERVICE LIFTS
BLOCK D
1.07
Quote should be net
including supply and
installation of lifts
with scaffolding,
minor builders work
and all steel materials
such as machine
beams, bearing
plates, buffer support
ladder, sill angles,
fascias etc., and
should be inclusive of
all applicable taxes.
Rs
No. of units 1 Rs
Grand Total Rs
Prices
SERVICE LIFTS
BLOCK D 47 / 47