New Chapel & Parish Rectory @ Nativity Catholic Church I. GENERAL INFORMATION Overall Site Analysis PROPOSED LAND USAGE A. TOTAL ACREAGE = 34,848 SF = 0.80 AC B. BUILDING COVERAGE = 9,750 SF = 0.22 AC 28% C. TOTAL ASPHALT & WALKS= 16,250 SF = 0.37 AC 47% D. TOTAL IMPERVIOUS = 26,000 SF = 0.60 AC 75% E. % WATER QUALITY IMPERVIOUS = 64% F. PERVIOUS AREA = 9,012 SF= 0.21 AC 26% 100% II. WATER QUALITY CRITERIA A. COMPUTE FIRST INCH OF RUNOFF FROM TOTAL SITE 1"/12 Total Acreage = 0.07 AC-FT= 0.80 AC-IN B. COMPUTE 2.5 TIMES THE % OF "WATER QUALITY" IMPERVIOUS 2.5" x % Imperv. = 0.11 AC-FT= 1.28 AC-IN Munson Design Consulting, Inc. (MDC)

New Chapel & Parish Rectory @ Nativity Catholic Church

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: New Chapel & Parish Rectory @ Nativity Catholic Church

New Chapel & Parish Rectory @ Nativity Catholic Church

I. GENERAL INFORMATION

Overall Site Analysis

PROPOSED LAND USAGE

A. TOTAL ACREAGE = 34,848 SF = 0.80 AC

B. BUILDING COVERAGE = 9,750 SF = 0.22 AC 28%

C. TOTAL ASPHALT & WALKS= 16,250 SF = 0.37 AC 47%

D. TOTAL IMPERVIOUS = 26,000 SF = 0.60 AC 75%

E. % WATER QUALITY IMPERVIOUS = 64%

F. PERVIOUS AREA = 9,012 SF= 0.21 AC 26%

100%

II. WATER QUALITY CRITERIA

A. COMPUTE FIRST INCH OF RUNOFF FROM TOTAL SITE

1"/12 Total Acreage = 0.07 AC-FT= 0.80 AC-IN

B. COMPUTE 2.5 TIMES THE % OF "WATER QUALITY" IMPERVIOUS

2.5" x % Imperv. = 0.11 AC-FT= 1.28 AC-IN

Munson Design Consulting, Inc. (MDC)

Page 2: New Chapel & Parish Rectory @ Nativity Catholic Church

New Chapel & Parish Rectory @ Nativity Catholic Church

Hollywood, Fl.

Lowest CB rim ele=7.00

E1 = 7.00 ft. NAVDNAVD k1 = 1.30E-04 cfs / ft2 - ft. head (Hydraulic Conductivity)

E2 = 5.00 ft. NAVDNAVD k2 = 1.70E-04 cfs / ft2 - ft. head (Hydraulic Conductivity)

E3 = 3.75 ft. NAVDNAVD k2 = 1.50E-04 cfs / ft2 - ft. head (Hydraulic Conductivity)

E4 = 2.50 ft. NAVDNAVD

E5 = 1.52 ft. NAVDNAVD K = (k1 + k2 + K3)/3 = 1.50E-04 cfs / ft2 - ft. head

Water Table = 0.52 ft. NAVDNAVD

Width (W) = 6.00 ft. NAVD

L = Length Required (lineal feet) (To be solved for)

K = 1.50E-04 cfs / ft2 - ft. head (Hydraulic Conductivity)

DU = 3.48 ft. (Non-Saturated Trench Depth) DU = E2 - (The Shallower of Water Table or E5)

DS = 0.00 ft. (Saturated Trench Depth) DS = (The Shallower of Water Table or E5) - E5

H2 = 5.48 ft. (Depth to water table) H2 = E1 - (The Shallower of Water Table or E5)

W = 6.00 ft. (Width of Trench)

Vwq = 1.280 ac-in (Volume to be treated)

Vadd= 0.000 ac-in (Additional Volume to be treated)

L = FS[(%WQ)(Vwq)+Vadd] = 1.28 = 109 LF

K(H2W + 2H2DU - DU2 + 2H2DS) + (0.000139)WDU 0.0088 + 0.0029

L = 147 Length Provided; lineal feet of trench provided for water quality

V = L x [K(H2W + 2H2DU - DU2 + 2H2DS) + (0.000139)WDU] = 147 x ( 0.0088 + 0.0029 )

= 1.73 acre-inches treated

= 0.144 acre-feet treated

Summary: All of the water quality is provided within the exfiltration trenches

Prepared: 6/5/2016

Page 3: New Chapel & Parish Rectory @ Nativity Catholic Church

GLEON GALLEON LED

1-10 Light Squares

Solid State LED

AREA/SITE LUMINAIRE

McGraw-Edison

SPECIFICATION FEATURES

ConstructionExtruded aluminum driver enclosure thermally isolated from Light Squares for optimal thermal performance. Heavy-wall, die-cast aluminum end caps enclose housing and die-cast aluminum heat sinks. A unique, patent pending interlocking housing and heat sink provides scalability with superior structural rigidity. 3G vibration tested. Optional tool-less hardware available for ease of entry into electrical chamber. Housing is IP66 rated.

OpticsPatented, high-efficiency injection-molded AccuLED Optics technology. Optics are precisely designed to shape the distribution maximizing efficiency and application spacing. AccuLED Optics create consistent distributions with the scalability to meet customized application requirements. Offered standard in 4000K (+/- 275K) CCT 70 CRI. Optional 6000K CCT and 3000K CCT.

ElectricalLED drivers are mounted to removable tray assembly for ease of maintenance. 120-277V 50/60Hz, 347V 60Hz or 480V 60Hz operation. 480V is compatible for use with 480V Wye systems only. Standard with 0-10V dimming. Shipped standard with Eaton proprietary circuit module designed to withstand 10kV of transient line surge. The Galleon LED luminaire is suitable for operation in -40°C to 40°C ambient environments. For applications with ambient temperatures exceeding 40°C, specify the HA (High Ambient) option. Light Squares are IP66 rated. Greater than 90% lumen maintenance expected at 60,000 hours. Available in standard 1A drive current and optional 530mA and 700mA drive currents.

MountingSTANDARD ARM MOUNT: Extruded aluminum arm includes internal bolt guides allowing for easy positioning of fixture during assembly. When mounting two or more luminaires at 90° and 120° apart, the EA extended arm may be required. Refer to the arm mounting requirement table.

Round pole adapter included. For wall mounting, specify wall mount bracket option. 3G vibration rated. QUICK MOUNT ARM: Arm is bolted directly to the pole and the fixture slides onto the quick mount arm and is secured via a single fastener, facilitating quick and easy installation. The versatile, patent pending, quick mount arm accommodates multiple drill patterns ranging from 1-1/2” to 4-7/8”. Removal of the door on the quick mount arm enables wiring of the fixture without having to access the driver compartment. A knock-out enables round pole mounting.

FinishHousing finished in super durable TGIC polyester powder coat paint, 2.5 mil nominal thickness for superior protection against fade and wear. Heat sink is powder coated black. Standard colors include black, bronze, grey, white, dark platinum and graphite metallic. RAL and custom color matches available.

WarrantyFive-year warranty.

TD500020EN2016-01-29 10:56:52

The Galleon™ LED luminaire delivers exceptional performance in a highly scalable, low-profile design. Patented, high-efficiency AccuLED Optics™ system provides uniform and energy conscious illumination to walkways, parking lots, roadways, building areas and security lighting applications. IP66 rated and UL/cUL Listed for wet locations.

DESCRIPTION

*www.designlights.org

S

YSTEMS

C

E RT I F I E

D

C E R T I F I C A T I O N D A T AUL/cUL Wet Location ListedISO 9001LM79 / LM80 Compliant3G Vibration RatedIP66 RatedDesignLights ConsortiumTM Qualified*

E N E R G Y D A T AElectronic LED Driver>0.9 Power Factor<20% Total Harmonic Distortion120V-277V 50/60Hz347V & 480V 60Hz-40°C Min. Temperature40°C Max. Temperature50°C Max. Temperature (HA Option)

Catalog # Type

Date

Project

Comments

Prepared by

TY P E " N "3/4" [19mm]

DiameterHole

(2) 9/16" [14mm]Diameter

Holes

1-3/4"[44mm]

7/8" [22mm]

2"[51mm]

DRILLING PATTERN

“A”

3-15/16" [100mm]

21-3/4" [553mm] "B"

DIMENSION DATA

Number of Light Squares

“A” Width

“B” Standard

Arm Length

“B” Optional Arm

Length 1

Weightwith Arm

(lbs.)

EPA with Arm 2

(Sq. Ft.)

1-4 15-1/2" (394mm)

7" (178mm)

10" (254mm)

33 (15.0 kgs.) 0.96

5-6 21-5/8" (549mm)

7" (178mm)

10" (254mm)

44 (20.0 kgs.) 1.00

7-8 27-5/8" (702mm)

7" (178mm)

13" (330mm)

54 (24.5 kgs.) 1.07

9-10 33-3/4" (857mm)

7" (178mm)

16" (406mm)

63 (28.6 kgs.) 1.12

NOTES: 1. Optional arm length to be used when mounting two fi xtures at 90° on a single pole. 2. EPA calculated with optional arm length.

DIMENSIONS

Page 4: New Chapel & Parish Rectory @ Nativity Catholic Church

Specifications and dimensions subject to change without notice.

Eaton 1121 Highway 74 SouthPeachtree City, GA 30269P: 770-486-4800www.eaton.com/lighting

GLEON GALLEON LED

TD500020EN2016-01-29 10:56:52

2 @ 180° Triple1

4 @ 90°

2 @ 90° Triple2 2 @ 120°

NOTES: 1 Round poles are 3 @ 120°. Square poles are 3 @ 90°. 2 Round poles are 3 @ 90°.

“A”

QM Quick Mount Arm (Standard) QMEA Quick Mount Arm (Extended)

21-3/4" [553mm]21-3/4" [553mm]8-7/16"

[215mm]16-9/16" [421mm]

3-15/16"[100mm]

QUICK MOUNT ARM DATA

Number of Light Squares 1, 2

“A” Width

Weight with QM Arm(lbs.)

Weight with QMEA Arm(lbs.)

EPA(Sq. Ft.)

1-4 15-1/2" (394mm) 35 (15.91 kgs.) 38 (17.27 kgs.)

1.115-6 3 21-5/8" (549mm) 46 (20.91 kgs.) 49 (22.27 kgs.)

7-8 27-5/8" (702mm) 56 (25.45 kgs.) 59 (26.82 kgs.)

NOTES: 1 QM option available with 1-8 light square confi gurations. 2 QMEA option available with 1-6 light square confi gurations. 3 QMEA arm to be used when mounting two fi xtures at 90° on a single pole.

Con� guration 90° Apart 120° Apart

GLEON-AE-017" Arm

(Standard)7" Arm

(Standard)

GLEON-AE-02 7" Arm(Standard)

7" Arm(Standard)

GLEON-AE-03 7" Arm(Standard)

7" Arm(Standard)

GLEON-AE-04 7" Arm(Standard)

7" Arm(Standard)

GLEON-AE-05 10" Extended Arm(Required)

7" Arm(Standard)

GLEON-AE-06 10" Extended Arm(Required)

7" Arm(Standard)

GLEON-AE-07 13" Extended Arm(Required)

13" Extended Arm(Required)

GLEON-AE-08 13" Extended Arm(Required)

13" Extended Arm(Required)

GLEON-AE-0916" Extended Arm

(Required)16" Extended Arm

(Required)

GLEON-AE-10 16" Extended Arm(Required)

16" Extended Arm(Required)

ARM MOUNTING REQUIREMENTS

8-1/8" [206mm]

1-13/16"[47mm]

(2) 27/64"[11mm]

Dia. Hole

3"[76mm]

3-13/16"[97mm]

3-13/64"[82mm]

MAST ARM MOUNT

4-15/16"[125mm]

3-3/4"[96mm]

6-15/16"[177mm]

4"[102mm]

4-7/8"[124mm]

1-1/4" [32mm]

9/16"[15mm]

Dia. Hole

QUICK MOUNT ARM (INCLUDES FIXTURE ADAPTER)

10-5/32" [256mm]

6-3/16" [157mm]

21-3/4"[553mm]

7"[178mm]

2-7/16"[61mm]

STANDARD WALL MOUNT

Page 5: New Chapel & Parish Rectory @ Nativity Catholic Church

Specifications and dimensions subject to change without notice.

Eaton 1121 Highway 74 SouthPeachtree City, GA 30269P: 770-486-4800www.eaton.com/lighting

GLEON GALLEON LED

TD500020EN2016-01-29 10:56:52

Standard

Street Side

House Side

Street Side

House Side

Street Side

House Side

Optics Rotated Left @ 90° [L90] Optics Rotated Right @ 90° [R90]

OPTIC ORIENTATION

Asymmetric Area Distributions

Symmertric Distributions

T3(Type III)

SL2(Type II with Spill Control)

SL3(Type III with Spill Control)

T4FT(Type IV Forward Throw)

T4W(Type IV Wide)

SL4(Type IV with Spill Control)

Specialized Distributions

Asymmetric Roadway Distributions

AFL(Automotive Frontline)

SLL(90° Spill Light Eliminator Left)

SLR(90° Spill Light Eliminator Right)

T2R(Type II Roadway)

RW(Rectangular Wide Type I)

T3R(Type III Roadway)

5NQ(Type V Square Narrow)

5MQ(Type V Square Medium)

5WQ(Type V Square Wide)

T2(Type II)

OPTICAL DISTRIBUTIONS

Page 6: New Chapel & Parish Rectory @ Nativity Catholic Church

Specifications and dimensions subject to change without notice.

Eaton 1121 Highway 74 SouthPeachtree City, GA 30269P: 770-486-4800www.eaton.com/lighting

GLEON GALLEON LED

TD500020EN2016-01-29 10:56:52

Number of Light Squares 1 2 3 4 5 6 7 8 9 10

Drive Current 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A

Nominal Power (Watts) 56 107 157 213 264 315 370 421 475 528

Input Current @ 120V (A) 0.47 0.90 1.31 1.79 2.21 2.64 3.09 3.51 3.96 4.41

Input Current @ 208V (A) 0.28 0.51 0.74 1.02 1.25 1.48 1.76 1.99 2.22 2.50

Input Current @ 240V (A) 0.25 0.45 0.65 0.90 1.10 1.30 1.55 1.75 1.95 2.20

Input Current @ 277V (A) 0.23 0.41 0.59 0.82 1.00 1.18 1.41 1.59 1.77 2.00

Optics

T2Lumens 5,272 10,303 15,373 20,313 25,168 30,118 35,618 40,357 45,018 49,842

BUG Rating B1-U0-G1 B2-U0-G2 B2-U0-G2 B3-U0-G3 B3-U0-G4 B3-U0-G4 B3-U0-G4 B3-U0-G5 B4-U0-G5 B4-U0-G5

T2RLumens 5,597 10,938 16,321 21,565 26,719 31,974 37,813 42,844 47,792 52,914

BUG Rating B1-U0-G1 B2-U0-G2 B2-U0-G2 B3-U0-G3 B3-U0-G3 B3-U0-G4 B3-U0-G4 B3-U0-G4 B4-U0-G4 B4-U0-G5

T3Lumens 5,374 10,501 15,669 20,704 25,652 30,697 36,303 41,134 45,884 50,802

BUG Rating B1-U0-G2 B2-U0-G2 B2-U0-G3 B3-U0-G3 B3-U0-G4 B3-U0-G4 B3-U0-G5 B3-U0-G5 B4-U0-G5 B4-U0-G5

T3RLumens 5,493 10,735 16,017 21,164 26,222 31,379 37,110 42,048 46,904 51,930

BUG Rating B1-U0-G2 B1-U0-G2 B2-U0-G3 B2-U0-G4 B3-U0-G4 B3-U0-G4 B3-U0-G5 B3-U0-G5 B3-U0-G5 B3-U0-G5

T4FTLumens 5,405 10,562 15,760 20,824 25,801 30,875 36,514 41,372 46,150 51,096

BUG Rating B1-U0-G2 B2-U0-G2 B2-U0-G3 B3-U0-G4 B3-U0-G4 B3-U0-G5 B3-U0-G5 B3-U0-G5 B3-U0-G5 B3-U0-G5

T4WLumens 5,335 10,426 15,556 20,555 25,468 30,476 36,042 40,838 45,554 50,436

BUG Rating B1-U0-G2 B2-U0-G2 B2-U0-G3 B3-U0-G4 B3-U0-G4 B3-U0-G5 B3-U0-G5 B4-U0-G5 B4-U0-G5 B4-U0-G5

SL2Lumens 5,263 10,285 15,347 20,278 25,124 30,066 35,556 40,288 44,940 49,756

BUG Rating B1-U0-G2 B2-U0-G2 B2-U0-G3 B3-U0-G3 B3-U0-G4 B3-U0-G4 B3-U0-G5 B3-U0-G5 B4-U0-G5 B4-U0-G5

SL3Lumens 5,373 10,500 15,667 20,701 25,649 30,693 36,298 41,128 45,878 50,794

BUG Rating B1-U0-G2 B2-U0-G3 B2-U0-G3 B3-U0-G4 B3-U0-G4 B3-U0-G4 B3-U0-G5 B3-U0-G5 B3-U0-G5 B3-U0-G5

SL4Lumens 5,105 9,976 14,886 19,669 24,370 29,163 34,488 39,078 43,591 48,262

BUG Rating B1-U0-G2 B1-U0-G3 B1-U0-G3 B2-U0-G4 B2-U0-G4 B2-U0-G5 B3-U0-G5 B3-U0-G5 B3-U0-G5 B3-U0-G5

5NQLumens 5,542 10,830 16,160 21,352 26,455 31,658 37,439 42,421 47,320 52,392

BUG Rating B2-U0-G1 B3-U0-G1 B3-U0-G2 B4-U0-G2 B4-U0-G2 B5-U0-G2 B5-U0-G3 B5-U0-G3 B5-U0-G3 B5-U0-G4

5MQLumens 5,644 11,029 16,457 21,745 26,942 32,241 38,128 43,202 48,191 53,356

BUG Rating B3-U0-G1 B4-U0-G2 B4-U0-G2 B5-U0-G3 B5-U0-G3 B5-U0-G4 B5-U0-G4 B5-U0-G4 B5-U0-G4 B5-U0-G5

5WQLumens 5,659 11,059 16,501 21,803 27,014 32,327 38,230 43,317 48,320 53,498

BUG Rating B3-U0-G1 B4-U0-G2 B4-U0-G2 B5-U0-G3 B5-U0-G4 B5-U0-G4 B5-U0-G4 B5-U0-G5 B5-U0-G5 B5-U0-G5

SLL/SLRLumens 4,722 9,227 13,767 18,191 22,539 26,971 31,897 36,141 40,315 44,635

BUG Rating B1-U0-G2 B1-U0-G3 B2-U0-G3 B2-U0-G3 B3-U0-G4 B3-U0-G4 B3-U0-G5 B3-U0-G5 B3-U0-G5 B3-U0-G5

RWLumens 5,492 10,732 16,014 21,159 26,216 31,372 37,101 42,038 46,893 51,918

BUG Rating B2-U0-G1 B3-U0-G1 B4-U0-G2 B4-U0-G2 B4-U0-G2 B5-U0-G3 B5-U0-G3 B5-U0-G3 B5-U0-G4 B5-U0-G4

AFLLumens 5,512 10,771 16,072 21,236 26,311 31,486 37,236 42,191 47,063 52,107

BUG Rating B1-U0-G1 B1-U0-G1 B2-U0-G2 B2-U0-G2 B3-U0-G3 B3-U0-G3 B3-U0-G3 B3-U0-G3 B3-U0-G3 B3-U0-G4

* Nominal data for 4000K CCT.

NOMINAL POWER AND LUMENS (1A)

Ambient Temperature

Lumen Multiplier

0°C 1.02

10°C 1.01

25°C 1.00

40°C 0.99

50°C 0.97

LUMEN MULTIPLIER

Ambient Temperature

TM-21 LumenMaintenance

(60,000 Hours)

Theoretical L70(Hours)

25°C > 94% > 350,000

40°C > 93% > 250,000

50°C* > 90% > 170,000

* 50°C lumen maintenance data applies to 530mA and 700mA drive currents.

LUMEN MAINTENANCE

Page 7: New Chapel & Parish Rectory @ Nativity Catholic Church

Specifications and dimensions subject to change without notice.

Eaton 1121 Highway 74 SouthPeachtree City, GA 30269P: 770-486-4800www.eaton.com/lighting

Number of Light Squares 1 2 3 4 5 6 7 8 9 10

Drive Current 700mA 700mA 700mA 700mA 700mA 700mA 700mA 700mA 700mA 700mA

Nominal Power (Watts) 38 72 105 138 176 210 243 276 314 348

Input Current @ 120V (A) 0.32 0.59 0.86 1.14 1.45 1.72 2 2.28 2.58 2.86

Input Current @ 208V (A) 0.21 0.36 0.51 0.67 0.87 1.02 1.18 1.34 1.53 1.69

Input Current @ 240V (A) 0.19 0.32 0.45 0.59 0.77 0.90 1.04 1.18 1.35 1.49

Input Current @ 277V (A) 0.20 0.29 0.40 0.51 0.69 0.80 0.91 1.02 1.20 1.31

Optics

T2Lumens 3,854 7,531 11,237 14,847 18,395 22,013 26,033 29,497 32,904 36,430

BUG Rating B1-U0-G1 B1-U0-G2 B2-U0-G2 B2-U0-G2 B3-U0-G3 B3-U0-G3 B3-U0-G4 B3-U0-G4 B3-U0-G4 B3-U0-G4

T2RLumens 4,091 7,995 11,929 15,762 19,529 23,370 27,638 31,316 34,932 38,676

BUG Rating B1-U0-G1 B1-U0-G2 B2-U0-G2 B2-U0-G2 B3-U0-G3 B3-U0-G3 B3-U0-G3 B3-U0-G4 B3-U0-G4 B3-U0-G4

T3Lumens 3,928 7,676 11,453 15,133 18,750 22,437 26,534 30,065 33,537 37,132

BUG Rating B1-U0-G1 B1-U0-G2 B2-U0-G2 B2-U0-G3 B3-U0-G3 B3-U0-G4 B3-U0-G4 B3-U0-G4 B3-U0-G4 B3-U0-G5

T3RLumens 4,015 7,846 11,707 15,469 19,166 22,936 27,124 30,733 34,283 37,957

BUG Rating B1-U0-G1 B1-U0-G2 B2-U0-G2 B2-U0-G3 B2-U0-G3 B3-U0-G4 B3-U0-G4 B3-U0-G4 B3-U0-G5 B3-U0-G5

T4FTLumens 3,951 7,720 11,519 15,221 18,858 22,567 26,688 30,240 33,732 37,347

BUG Rating B1-U0-G1 B1-U0-G2 B2-U0-G2 B2-U0-G3 B2-U0-G4 B3-U0-G4 B3-U0-G4 B3-U0-G5 B3-U0-G5 B3-U0-G5

T4WLumens 3,900 7,620 11,370 15,024 18,615 22,276 26,343 29,849 33,296 36,864

BUG Rating B1-U0-G1 B1-U0-G2 B2-U0-G2 B2-U0-G3 B3-U0-G4 B3-U0-G4 B3-U0-G4 B3-U0-G5 B3-U0-G5 B3-U0-G5

SL2Lumens 3,847 7,518 11,217 14,821 18,364 21,975 25,988 29,447 32,847 36,368

BUG Rating B1-U0-G1 B1-U0-G2 B2-U0-G3 B2-U0-G3 B3-U0-G3 B3-U0-G4 B3-U0-G4 B3-U0-G4 B3-U0-G4 B3-U0-G5

SL3Lumens 3,927 7,675 11,451 15,131 18,747 22,434 26,531 30,061 33,533 37,126

BUG Rating B1-U0-G1 B1-U0-G2 B2-U0-G3 B2-U0-G3 B2-U0-G3 B3-U0-G4 B3-U0-G4 B3-U0-G4 B3-U0-G5 B3-U0-G5

SL4Lumens 3,731 7,292 10,880 14,376 17,812 21,315 25,208 28,562 31,861 35,275

BUG Rating B1-U0-G2 B1-U0-G2 B1-U0-G3 B1-U0-G3 B2-U0-G4 B2-U0-G4 B2-U0-G4 B2-U0-G5 B2-U0-G5 B3-U0-G5

5NQLumens 4,051 7,916 11,811 15,606 19,336 23,139 27,365 31,006 34,587 38,294

BUG Rating B2-U0-G1 B3-U0-G1 B3-U0-G1 B3-U0-G2 B4-U0-G2 B4-U0-G2 B4-U0-G2 B5-U0-G2 B5-U0-G3 B5-U0-G3

5MQLumens 4,125 8,062 12,029 15,894 19,692 23,565 27,869 31,577 35,224 38,999

BUG Rating B2-U0-G1 B3-U0-G2 B4-U0-G2 B4-U0-G2 B4-U0-G2 B5-U0-G3 B5-U0-G3 B5-U0-G3 B5-U0-G4 B5-U0-G4

5WQLumens 4,136 8,083 12,061 15,936 19,745 23,628 27,943 31,661 35,318 39,103

BUG Rating B3-U0-G1 B3-U0-G2 B4-U0-G2 B4-U0-G2 B5-U0-G3 B5-U0-G3 B5-U0-G4 B5-U0-G4 B5-U0-G4 B5-U0-G4

SLL/SLRLumens 3,451 6,744 10,063 13,296 16,474 19,714 23,314 26,416 29,467 32,625

BUG Rating B1-U0-G1 B1-U0-G2 B1-U0-G3 B2-U0-G3 B2-U0-G3 B2-U0-G4 B3-U0-G4 B3-U0-G4 B3-U0-G5 B3-U0-G5

RWLumens 4,014 7,844 11,704 15,465 19,162 22,930 27,118 30,726 34,274 37,948

BUG Rating B2-U0-G1 B3-U0-G1 B3-U0-G2 B4-U0-G2 B4-U0-G2 B4-U0-G2 B4-U0-G2 B5-U0-G3 B5-U0-G3 B5-U0-G3

AFLLumens 4,029 7,873 11,747 15,522 19,231 23,014 27,216 30,838 34,399 38,086

BUG Rating B1-U0-G1 B1-U0-G1 B2-U0-G2 B2-U0-G2 B2-U0-G2 B3-U0-G2 B3-U0-G3 B3-U0-G3 B3-U0-G3 B3-U0-G3

* Nominal data for 4000K CCT.

NOMINAL POWER AND LUMENS (700MA)

GLEON GALLEON LED

TD500020EN2016-01-29 10:56:52

Ambient Temperature

Lumen Multiplier

0°C 1.02

10°C 1.01

25°C 1.00

40°C 0.99

50°C 0.97

LUMEN MULTIPLIER

Ambient Temperature

TM-21 LumenMaintenance

(60,000 Hours)

Theoretical L70(Hours)

25°C > 94% > 350,000

40°C > 93% > 250,000

50°C* > 90% > 170,000

* 50°C lumen maintenance data applies to 530mA and 700mA drive currents.

LUMEN MAINTENANCE

Page 8: New Chapel & Parish Rectory @ Nativity Catholic Church

Specifications and dimensions subject to change without notice.

Eaton 1121 Highway 74 SouthPeachtree City, GA 30269P: 770-486-4800www.eaton.com/lighting

TD500020EN2016-01-29 10:56:52

GLEON GALLEON LED

Number of Light Squares 1 2 3 4 5 6 7 8 9 10

Drive Current 530mA 530mA 530mA 530mA 530mA 530mA 530mA 530mA 530mA 530mA

Nominal Power (Watts) 30 54 80 105 130 159 184 209 234 259

Input Current @ 120V (A) 0.25 0.45 0.66 0.86 1.07 1.32 1.52 1.72 1.93 2.14

Input Current @ 208V (A) 0.17 0.28 0.39 0.51 0.63 0.78 0.9 1.02 1.14 1.26

Input Current @ 240V (A) 0.17 0.25 0.35 0.45 0.55 0.70 0.80 0.90 1.00 1.10

Input Current @ 277V (A) 0.19 0.24 0.32 0.40 0.49 0.64 0.72 0.80 0.89 0.98

Optics

T2Lumens 3,079 6,017 8,978 11,862 14,697 17,588 20,800 23,567 26,289 29,106

BUG Rating B1-U0-G1 B1-U0-G2 B2-U0-G2 B2-U0-G2 B2-U0-G2 B3-U0-G3 B3-U0-G3 B3-U0-G3 B3-U0-G4 B3-U0-G4

T2RLumens 3,269 6,388 9,531 12,593 15,603 18,672 22,082 25,020 27,909 30,900

BUG Rating B1-U0-G1 B1-U0-G1 B1-U0-G2 B2-U0-G2 B2-U0-G2 B2-U0-G2 B3-U0-G3 B3-U0-G3 B3-U0-G3 B3-U0-G4

T3Lumens 3,138 6,133 9,150 12,091 14,980 17,926 21,200 24,021 26,795 29,667

BUG Rating B1-U0-G1 B1-U0-G2 B2-U0-G2 B2-U0-G2 B2-U0-G3 B3-U0-G3 B3-U0-G3 B3-U0-G4 B3-U0-G4 B3-U0-G4

T3RLumens 3,208 6,269 9,354 12,359 15,313 18,325 21,671 24,555 27,390 30,326

BUG Rating B1-U0-G1 B1-U0-G2 B1-U0-G2 B2-U0-G2 B2-U0-G3 B2-U0-G3 B2-U0-G4 B3-U0-G4 B3-U0-G4 B3-U0-G4

T4FTLumens 3,156 6,168 9,203 12,161 15,067 18,030 21,323 24,160 26,950 29,839

BUG Rating B1-U0-G1 B1-U0-G2 B1-U0-G2 B2-U0-G2 B2-U0-G3 B2-U0-G3 B3-U0-G4 B3-U0-G4 B3-U0-G4 B3-U0-G5

T4WLumens 3,116 6,088 9,084 12,004 14,872 17,797 21,047 23,848 26,602 29,453

BUG Rating B1-U0-G1 B1-U0-G2 B2-U0-G2 B2-U0-G2 B2-U0-G3 B3-U0-G3 B3-U0-G4 B3-U0-G4 B3-U0-G4 B3-U0-G5

SL2Lumens 3,074 6,006 8,962 11,842 14,672 17,558 20,764 23,527 26,244 29,056

BUG Rating B1-U0-G1 B1-U0-G2 B2-U0-G2 B2-U0-G3 B2-U0-G3 B3-U0-G3 B3-U0-G3 B3-U0-G4 B3-U0-G4 B3-U0-G4

SL3Lumens 3,138 6,132 9,149 12,089 14,978 17,924 21,197 24,018 26,791 29,662

BUG Rating B1-U0-G1 B1-U0-G2 B1-U0-G2 B2-U0-G3 B2-U0-G3 B2-U0-G3 B3-U0-G4 B3-U0-G4 B3-U0-G4 B3-U0-G4

SL4Lumens 2,981 5,826 8,693 11,486 14,231 17,030 20,140 22,820 25,456 28,184

BUG Rating B0-U0-G1 B1-U0-G2 B1-U0-G3 B1-U0-G3 B1-U0-G3 B2-U0-G3 B2-U0-G4 B2-U0-G4 B2-U0-G4 B2-U0-G5

5NQLumens 3,236 6,324 9,437 12,469 15,449 18,487 21,863 24,773 27,634 30,595

BUG Rating B1-U0-G0 B2-U0-G1 B3-U0-G1 B3-U0-G2 B3-U0-G2 B4-U0-G2 B4-U0-G2 B4-U0-G2 B4-U0-G2 B5-U0-G2

5MQLumens 3,296 6,441 9,610 12,698 15,733 18,828 22,266 25,229 28,142 31,158

BUG Rating B2-U0-G1 B3-U0-G1 B3-U0-G2 B4-U0-G2 B4-U0-G2 B4-U0-G2 B5-U0-G3 B5-U0-G3 B5-U0-G3 B5-U0-G3

5WQLumens 3,305 6,458 9,636 12,732 15,775 18,878 22,325 25,296 28,217 31,241

BUG Rating B2-U0-G1 B3-U0-G2 B4-U0-G2 B4-U0-G2 B4-U0-G2 B5-U0-G3 B5-U0-G3 B5-U0-G3 B5-U0-G4 B5-U0-G4

SLL/SLRLumens 2,757 5,388 8,040 10,623 13,162 15,751 18,627 21,105 23,543 26,066

BUG Rating B1-U0-G1 B1-U0-G2 B1-U0-G2 B1-U0-G3 B2-U0-G3 B2-U0-G3 B2-U0-G3 B2-U0-G4 B3-U0-G4 B3-U0-G4

RWLumens 3,207 6,267 9,351 12,356 15,309 18,320 21,666 24,549 27,384 30,319

BUG Rating B2-U0-G1 B3-U0-G1 B3-U0-G1 B3-U0-G2 B4-U0-G2 B4-U0-G2 B4-U0-G2 B4-U0-G2 B4-U0-G2 B5-U0-G3

AFLLumens 3,219 6,290 9,385 12,401 15,365 18,387 21,745 24,638 27,484 30,429

BUG Rating B1-U0-G1 B1-U0-G1 B1-U0-G1 B2-U0-G2 B2-U0-G2 B2-U0-G2 B2-U0-G2 B3-U0-G2 B3-U0-G3 B3-U0-G3

* Nominal data for 4000K CCT.

NOMINAL POWER AND LUMENS (530MA)

Ambient Temperature

Lumen Multiplier

0°C 1.02

10°C 1.01

25°C 1.00

40°C 0.99

50°C 0.97

LUMEN MULTIPLIER

Ambient Temperature

TM-21 LumenMaintenance

(60,000 Hours)

Theoretical L70(Hours)

25°C > 94% > 350,000

40°C > 93% > 250,000

50°C* > 90% > 170,000

* 50°C lumen maintenance data applies to 530mA and 700mA drive currents.

LUMEN MAINTENANCE

Page 9: New Chapel & Parish Rectory @ Nativity Catholic Church

Specifications and dimensions subject to change without notice.

Eaton 1121 Highway 74 SouthPeachtree City, GA 30269P: 770-486-4800www.eaton.com/lighting

TD500020EN2016-01-29 10:56:52

Sample Number: GLEON-AE-04-LED-E1-T3-GM-700

Product Family 1, 2 Light EngineNumber of Light Squares 3 Lamp Type Voltage Distribution Color Mounting

GLEON=Galleon AE= 1A Drive Current

01= 102=203=304=405=506=607=7 4

08=8 4

09=9 5

10=10 5

LED= Solid State Light Emitting Diodes

E1=(120-277V)347=347V 6

480=480V 6, 7

T2=Type IIT2R=Type II RoadwayT3=Type IIIT3R=Type III RoadwayT4FT=Type IV Forward ThrowT4W=Type IV Wide5NQ=Type V Narrow5MQ=Type V Square Medium5WQ=Type V Square WideSL2=Type II w/Spill ControlSL3=Type III w/Spill ControlSL4=Type IV w/Spill ControlSLL=90° Spill Light Eliminator LeftSLR=90° Spill Light Eliminator Right RW=Rectangular Wide Type IAFL=Automotive Frontline

AP=GreyBZ=BronzeBK=BlackDP= Dark PlatinumGM= Graphite MetallicWH=White

[Blank]= Arm for Round or Square Pole

EA= Extended Arm 8

MA= Mast Arm Adapter 9

WM= Wall MountQM= Quick Mount

Arm (Standard Length) 10

QMEA= Quick Mount Arm (Extended Length) 11

Options (Add as Suffi x) Accessories (Order Separately)

2L=Two Circuits 12, 13

7030=70 CRI / 3000K 14

8030=80 CRI / 3000K 15

7050=70 CRI / 5000K 15

7060=70 CRI / 6000K 14

530= Drive Current Factory Set to 530mA 16

700= Drive Current Factory Set to 700mA 16

P=Button Type Photocontrol (120, 208, 240 or 277V)PER7= NEMA 7-PIN Twistlock Photocontrol ReceptacleR= NEMA Twistlock Photocontrol ReceptacleHA=50°C High Ambient 13, 17

MS/DIM-L08= Motion Sensor for Dimming Operation, Maximum 8' Mounting Height 18, 19, 20, 21, 22

MS/DIM-L20= Motion Sensor for Dimming Operation, 9' - 20' Mounting Height 18, 19, 20, 21, 22

MS/DIM-L40= Motion Sensor for Dimming Operation, 21' - 40' Mounting Height 18, 19, 20, 21

MS/DIM-L40W= Motion Sensor for Dimming Operation, 21' - 40' Mounting Height (Wide Range) 18, 19, 20, 21, 25

MS/X-L08= Bi-Level Motion Sensor, Maximum 8' Mounting Height 18, 19, 20, 21, 22, 26

MS/X-L20= Bi-Level Motion Sensor, 9' - 20' Mounting Height 18, 19, 20, 21, 23, 26

MS/X-L40= Bi-Level Motion Sensor, 21' - 40' Mounting Height 18, 19, 20, 21, 24, 26 MS/X-L40W= Bi-Level Motion Sensor, 21' - 40' Mounting Height (Wide Range) 18, 19, 20, 21, 25, 26 MS-L08= Motion Sensor for ON/OFF Operation, Maximum 8' Mounting Height 18, 19, 20, 21, 22

MS-L20= Motion Sensor for ON/OFF Operation, 9' - 20' Mounting Height 18, 19, 20, 21, 23

MS-L40=Motion Sensor for ON/OFF Operation, 21' - 40' Mounting Height 18, 19, 20, 21, 24 MS-L40W= Motion Sensor for ON/OFF Operation, 21' - 40' Mounting Height (Wide Range) 18, 19, 20, 25

DIMRF-LW= LumaWatt Wireless Sensor, Wide Lens for 8' - 16' Mounting Height 27

DIMRF-LN= LumaWatt Wireless Sensor, Narrow Lens for 16' - 40' Mounting Height 27

L90=Optics Rotated 90° LeftR90=Optics Rotated 90° RightMT=Factory Installed Mesh TopTH=Tool-less Door HardwareLCF=Light Square Trim Plate Painted to Match Housing 28

HSS=Factory Installed House Side Shield 29

CE=CE Marking 30

OA/RA1016=NEMA Photocontrol Multi-Tap - 105-285VOA/RA1027=NEMA Photocontrol - 480VOA/RA1201=NEMA Photocontrol - 347VOA/RA1013=Photocontrol Shorting CapOA/RA1014=120V PhotocontrolMA1252=10kV Surge Module ReplacementMA1036-XX=Single Tenon Adapter for 2-3/8" O.D. TenonMA1037-XX=2 @ 180° Tenon Adapter for 2-3/8" O.D. TenonMA1197-XX=3 @ 120° Tenon Adapter for 2-3/8" O.D. TenonMA1188-XX=4 @ 90° Tenon Adapter for 2-3/8" O.D. TenonMA1189-XX=2 @ 90° Tenon Adapter for 2-3/8" O.D. TenonMA1190-XX=3 @ 90° Tenon Adapter for 2-3/8" O.D. TenonMA1191-XX=2 @ 120° Tenon Adapter for 2-3/8" O.D. TenonMA1038-XX=Single Tenon Adapter for 3-1/2" O.D. TenonMA1039-XX=2 @ 180° Tenon Adapter for 3-1/2" O.D. TenonMA1192-XX=3 @ 120° Tenon Adapter for 3-1/2" O.D. TenonMA1193-XX=4 @ 90° Tenon Adapter for 3-1/2" O.D. TenonMA1194-XX=2 @ 90° Tenon Adapter for 3-1/2" O.D. TenonMA1195-XX=3 @ 90° Tenon Adapter for 3-1/2" O.D. TenonFSIR-100=Wireless Confi guration Tool for Occupancy Sensor 31

GLEON-MT1=Field Installed Mesh Top for 1-4 Light SquaresGLEON-MT2=Field Installed Mesh Top for 5-6 Light SquaresGLEON-MT3=Field Installed Mesh Top for 7-8 Light SquaresGLEON-MT4=Field Installed Mesh Top for 9-10 Light Squares GLEON-QM=Quick Mount Arm Kit 10

GLEON-QM-EA=Quick Mount Extended Length Arm Kit 11

LS/HSS=Field Installed House Side Shield 29, 32

NOTES: 1. Customer is responsible for engineering analysis to confi rm pole and fi xture compatibility for all applications. Refer to our white paper WP513001EN for additional support information.2. DesignLights ConsortiumTM Qualifi ed. Refer to www.designlights.org Qualifi ed Products List under Family Models for details. 3. Standard 4000K CCT and minimum 70 CRI.4. Not compatible with extended quick mount arm (QMEA).5. Not compatible with standard quick mount arm (QM) or extended quick mount arm (QMEA).6. Requires the use of a step down transformer when combined with MS/DIM, MS/X or DIMRF.7. Only for use with 480V Wye systems. Per NEC, not for use with ungrounded systems, impedance grounded systems or corner grounded systems (commonly known as Three Phase Three Wire Delta, Three Phase

High Leg Delta and Three Phase Corner Grounded Delta systems).8. May be required when two or more luminaires are oriented on a 90° or 120° drilling pattern. Refer to arm mounting requirement table.9. Factory installed.10. Maximum 8 light squares.11. Maximum 6 light squares. 12. 2L is not available with MS/X or MS/DIM at 347V or 480V. 2L in AE-02 through AE-04 requires a larger housing, normally used for AE-05 or AE-06. Extended arm option may be required when mounting two or more

fi xtures per pole at 90° or 120°. Refer to arm mounting requirement table.13. Not available with LumaWatt wireless sensors. 14. Extended lead times apply. Use dedicated IES fi les for 3000K and 6000K when performing layouts. These fi les are published on the Galleon luminaire product page on the website.15. Extended lead times apply. For 8030, factor 7030 IES fi les x .92 (8% lumen loss). For 7050, use 7060 IES fi les.16. 1 Amp standard. Use dedicated IES fi les for 530mA and 700mA when performing layouts. These fi les are published on the Galleon luminaire product page on the website. 17. 50°C lumen maintenance data applies to 530mA and 700mA drive currents.18. Consult factory for more information.19. Utilizes internal step-down transformer when 347V or 480V is selected.20. The FSIR-100 accessory is required to adjust parameters including high and low modes, sensitivity, time delay, cutoff and more. Consult your lighting representative at Eaton for more information.21. Not available with HA option.22. Approximately 22' detection diameter at 8' mounting height.23. Approximately 40' detection diameter at 20' mounting height.24. Approximately 60' detection diameter at 40' mounting height.25. Approximately 100' detection diameter at 40' mounting height.26. Replace X with number of light squares operating in low output mode.27. LumaWatt wireless sensors are factory installed only requiring network components RF-EM-1, RF-GW-1 and RF-ROUT-1 in appropriate quantities. See www.eaton.com/lighting for LumaWatt application information.28. Not available with house side shield (HSS).29. Only for use with SL2, SL3, SL4 and AFL distributions. The Light Square trim plate is painted black when the HSS option is selected.30. CE is not available with the DIMRF, MS, MS/X, MS/DIM, P, R or PER7 options. Available in 120-277V only.31. This tool enables adjustment of parameters including high and low modes, sensitivity, time delay, cutoff and more. Consult your lighting representative at Eaton for more information.32. One required for each Light Square.

ORDERING INFORMATION

GLEON GALLEON LED

Page 10: New Chapel & Parish Rectory @ Nativity Catholic Church

Client:

Project:

Type:

Order Code:

Quantity:

ACCLAIMLIGHTING

D y n a F l o o d S O

Total Lumens

1176 @ 4000K, 7º

Efficacy (lm/W)

47

CRI

Lumen Maintenance

70% @ 50,000 hours

80

Color Temperature 2700k, 3000K, 3500K, 4000k

Power Consumption 25W

Beam Angle 7º Standard, 20º, 40º, 10º x 60º, 60º via LSF Filter

Drive Current 500ma

Operating Temperature

-40°F to 122°F (-40°C to 50°C)

90-135VAC / 200-300VAC

ELV, TRIAC

2 Conductor, Bare Wire Leads

Operating Voltage

Fixture Connections

Housing

Die Cast Aluminum

Rating IP 66, Wet Location

Dimming

Warranty 5 Years

6 lbs (2.7 kg)Weight Dimensions

W 9.6” x H 13.9” x D 5.9’

(245 mm x 221 mm x 149.5mm)

SPECIFICATIONS

DynaFlood SO is a high powered flood fixture designed for exterior illumination and outdoor signage.It’s integral power supply is universal voltage and can be dimmed via ELV or TRIAC. The head pivots 180º to help you get the exact angle needed for your application.

DIMENSIONS

8.7”

5.9”

9.6”

Page 11: New Chapel & Parish Rectory @ Nativity Catholic Church

DFA . 1 _ 1. A _ _ _

- Black*

www.acclaimlighting.com Lumen measurements comply with IES LM-79-08 provided by a recognized, independent testing lab. LM79 Photometry, LM80 LED source compliance documents, and IES files are available at www.acclaimlighting.com

ORDER CODES *special order

WIRING

1- White*- Grey

24

- 2700K*ABDE

- 3000K- 3500K*- 4000K

- 90-135VACU- 200-300VACEH

ousi

ng

Beam

Colo

r Input Voltage

Client:

Project:

Type:

Order Code:

Quantity:

AC Input 90-135 or 200-300VAC(Fixture Dependant)

4” IP Rated Junction Box (Round)

- 7º- 20º

BE

- 40º- 10º x 60º - 60º

HPK

ACCLAIMLIGHTING

D y n a F l o o d S O

DYNAFEB6 Dyna Flood Extender Bar 6”

DYNAFEB12 Dyna Flood Extender Bar 12”

DYNAFEB36 Dyna Flood Extender Bar 36”

DYNAFGS Dyna Flood Glare Shield

DYNAFSWG Dyna Flood SO Wire Guard

RELATED COMPONENTS

Page 12: New Chapel & Parish Rectory @ Nativity Catholic Church
Page 13: New Chapel & Parish Rectory @ Nativity Catholic Church
Page 14: New Chapel & Parish Rectory @ Nativity Catholic Church
Page 15: New Chapel & Parish Rectory @ Nativity Catholic Church
Page 16: New Chapel & Parish Rectory @ Nativity Catholic Church
Page 17: New Chapel & Parish Rectory @ Nativity Catholic Church
Page 18: New Chapel & Parish Rectory @ Nativity Catholic Church
Page 19: New Chapel & Parish Rectory @ Nativity Catholic Church
Page 20: New Chapel & Parish Rectory @ Nativity Catholic Church
Page 21: New Chapel & Parish Rectory @ Nativity Catholic Church
Page 22: New Chapel & Parish Rectory @ Nativity Catholic Church
Page 23: New Chapel & Parish Rectory @ Nativity Catholic Church
Page 24: New Chapel & Parish Rectory @ Nativity Catholic Church
Page 25: New Chapel & Parish Rectory @ Nativity Catholic Church
Page 26: New Chapel & Parish Rectory @ Nativity Catholic Church
Page 27: New Chapel & Parish Rectory @ Nativity Catholic Church
Page 28: New Chapel & Parish Rectory @ Nativity Catholic Church
Page 29: New Chapel & Parish Rectory @ Nativity Catholic Church
Page 30: New Chapel & Parish Rectory @ Nativity Catholic Church
Page 31: New Chapel & Parish Rectory @ Nativity Catholic Church
Page 32: New Chapel & Parish Rectory @ Nativity Catholic Church
Page 33: New Chapel & Parish Rectory @ Nativity Catholic Church
Page 34: New Chapel & Parish Rectory @ Nativity Catholic Church

TITLE SEARCH REPORT

Rev. 12/10 Page 1 of 4

Fund File Number: 235089 The information contained in this title search is being furnished by Attorneys' Title Fund Services, LLC. If this report is to be used by a title insurance agent for evaluation and determination of insurability by the agent prior to the issuance of title insurance, then the agent shall have liability for such work. Provided For: J Patrick Fitzgerald & Associates P.A. Agent's File Reference: 1-298 After an examination of this search the Agent must: A. Evaluate all instruments, plats and documents contained in the report. B. Include in the Commitment under Schedule B, any additional requirements and/or exceptions

you find necessary from your analysis of the surveys, prior title evidence or other relevant information from the transaction.

C. Verify the status of corporations and limited partnerships and other business entities with the

appropriate governmental agency or other authority. D. Determine whether the property has legal access. E. Determine if any unpaid municipal taxes or assessments exist, which are not recorded in the

Official Records Books of the county. F. Determine whether any portion of the property is submerged or artificially filled, if the property

borders a body of water, and if riparian or littoral rights exist. G. The information provided herein does not include a search of federal liens and judgment liens

filed with the Florida Department of State pursuant to Sec. 713.901, et seq., F.S., and Sec. 55.201, et seq., F.S., respectively, which designate the Florida Department of State as the place for filing federal liens and judgment liens against personal property. For insuring purposes:

(a) Pursuant to Sec. 713.901, et seq., F.S., personal property includes, but is not limited to, mortgages, leaseholds, mortgages on leaseholds, interests in cooperative associations, vendees’ interests, and options when those interests are held by a partnership, corporation, trust or decedent’s estate; and

(b) Pursuant to Sec. 55.201, et seq., F.S., personal property includes, but is not limited to,

leaseholds, interests in cooperative associations, vendees’ interests, and options regardless of the type of entity holding such interests, including individuals. (Note: Mortgages have been specifically excluded from the personal property interests in which a judgment lien may be acquired under the provisions of Sec. 55.201, et seq., F.S.)

Prepared Date: 7/1/2016 Attorneys' Title Fund Services, LLC Prepared by: Manny Proano, Examiner Phone Number: (800) 929-5791 x6247 Email Address: [email protected]

Page 35: New Chapel & Parish Rectory @ Nativity Catholic Church

DEED SEARCH Fund File Number: 235089

Rev. 12/10 Page 2 of 4

Effective Date of approved base title information: from 1925 to November 30 1959 Effective Date of Search: at 11:00 PM Description of real property to be insured/foreclosed situated in Broward County, Florida. Muniments of Title, including bankruptcy, foreclosure, quiet title, probate, guardianship and incompetency proceedings, if any, recorded in the Official Records Books of the county:

1. Warranty Deed from The Highway Construction Company of Ohio, Inc. to Hollywood Inc. recorded in Deed Book 221, Page 175

2. Deed form________to Home Seekers Realty, Inc., recorded in 02-14-1931, in Instrument Number 144196, ( COPY NOT AVAILABLE)

3. Warranty Deed form Leonard Robbins and Virginia Robbins, his wife to Hollywood Land Company, Inc., recorded in O.R. .Book 843, Page 440.

4. Quit Claim Deed from State of Florida through the Trustees of the Internal Improvement Fund to Sherwood Investment co., a Florida corporation recorded in O.R. Book 1727, Page 234.

A 20-year name search was not performed on the proposed insured. It is the agent’s responsibility to obtain a name search if a loan policy to be issued based on this product is other than a 100% purchase money mortgage.

STANDARD EXCEPTIONS Unless satisfactory evidence is presented to the agent eliminating the need for standard exceptions, the following should be made a part of any commitment or policy. 1. General or special taxes and assessments required to be paid in the year 2016 and subsequent

years. 2. Rights or claims of parties in possession not shown by the public records. 3. Encroachments, overlaps, boundary line disputes, and any other matters which would be

disclosed by an accurate survey and inspection of the premises. 4. Easements or claims of easements not shown by the public records.

Page 36: New Chapel & Parish Rectory @ Nativity Catholic Church

DEED SEARCH Fund File Number: 235089

Rev. 12/10 Page 3 of 4

5. Any lien, or right to a lien, for services, labor, or material heretofore or hereafter furnished,

imposed by law and not shown by the public records. 6. Any owner policy issued pursuant hereto will contain under Schedule B the following exception:

Any adverse ownership claim by the State of Florida by right of sovereignty to any portion of the lands insured hereunder, including submerged, filled and artificially exposed lands, and lands accreted to such lands.

7. Federal liens and judgment liens, if any, filed with the Florida Department of State pursuant to

Sec. 713.901, et seq., F.S., and Sec. 55.201, et seq., F.S., respectively, which designate the Florida Department of State as the place for filing federal liens and judgment liens against personal property. For insuring purposes:

(a) Pursuant to Sec. 713.901, et seq., F.S., personal property includes, but is not limited to,

mortgages, leaseholds, mortgages on leaseholds, interests in cooperative associations, vendees’ interests, and options when those interests are held by a partnership, corporation, trust or decedent’s estate; and

(b) Pursuant to Sec. 55.201, et seq., F.S., personal property includes, but is not limited to,

leaseholds, interests in cooperative associations, vendees’ interests, and options regardless of the type of entity holding such interests, including individuals. (Note: Mortgages have been specifically excluded from the personal property interests in which a judgment lien may be acquired under the provisions of Sec. 55.201, et seq., F.S.)

8. Any lien provided by County Ordinance or by Chapter 159, Florida Statutes, in favor of any city,

town, village or port authority, for unpaid service charges for services by any water systems, sewer systems or gas systems serving the land described herein; and any lien for waste fees in favor of any county or municipality.

The report does not cover bankruptcies or other matters filed in the Federal District Courts of Florida. In foreclosure proceedings, title should be examined between the effective date of this report and the recording of the lis pendens to assure that all necessary and proper parties are joined. Consideration should be given to joining as defendants any persons in possession, other than the record owner, and any parties, other than those named herein, known to the plaintiff or the plaintiff's attorney and having or claiming an interest in the property. Prior to issuance of any policy of title insurance underwritten by Old Republic National Title Insurance Company, the agent must obtain and evaluate a title search for the period between the effective date of this Title Search Report and the recording date(s) of the instrument(s) on which the policy is based. If this product is not used for the purpose of issuing a policy, then the maximum liability for incorrect information is $1,000. Note: The Agent is responsible for obtaining underwriting approval on any commitment prepared from this product in the amount of $1,000,000.00 or more.

Page 37: New Chapel & Parish Rectory @ Nativity Catholic Church

DEED SEARCH Fund File Number: 235089

Rev. 12/10 Page 4 of 4

Page 38: New Chapel & Parish Rectory @ Nativity Catholic Church

July 05, 2016 Application Number: City of Hollywood, Florida RE: Nativity Catholic Church

5220 Johnson Street Hollywood, FL 33021

Technical Advisory Committee Report.

A. APPLICATION SUBMITTALS Karina da Luz, Planning Administrator 954-921-3471 1. The Ownership and Encumbrance (O&E) Report shall:

a. Indicate that it was researched from time of platting or 1953 (earliest of the two). Acknowledged.

b. Name of all current owners shall be included in the Ownership & Encumbrance Report (O&E). Names of all current owners are included in the attached O & E report.

c. Provide hard copies of all recorded and unrecorded encumbrances (with O.R. or plat book(s) and page number(s) provided) lying within/on the property boundaries (i.e. easements, rights-of-way, non-vehicular access lines, etc.). Copies of all recorded and unrecorded encumbrances are attached to the submittal.

1. ALTA survey shall be based on O&E (and vice versa) with a note indicating as such. Work with the Engineering Division to ensure the survey is accurate. Acknowledged.

2. ALTA survey shall provide net property size in square feet and acreage. Requested information has been included in the revised survey. Refer to sheet 1

3. Indicate current and future meeting dates (not submittal dates) on Cover Sheet and Title Block. Dates have been revised, refer to revision/ submission index sheet T-1

4. Index of Drawings should follow the Planning and Development Board checklist provided by Planning Division. Acknowledged .

5. Tabular data information shall be updated with correct Land Use designation, and Broward County code must be removed. Information has been updated, Broward county designation removed. Refer to sheets T-1 & SP-1

6. Tabular data "Site Information" shall; a. Include required and proposed height.

Page 39: New Chapel & Parish Rectory @ Nativity Catholic Church

Tabular data was updated, including required and proposed height. Refer to sheet SP-1

b. Include note stating the maximum foot-candle level at all property lines (maximum 0.5 if adjacent to residential). Note included in the tabular data, sheet SP-1.

7. General Application shall be completed; signed and notarized if applicable. Acknowledged.

8. Staff encourages Applicant to meet with surrounding homeowner's associations prior to submitting for any Board. Provide update with next submittal. Acknowledged. Owner representative and owner are working on the schedule, they will provide possible dates to the team for coordination.

9. Provide written responses to all comments with next submittal. Acknowledged.

B. ZONING Karina da Luz, Planning Administrator 954-921-3471

1. Work with Staff on the format and requirements for parking data. Required parking should reflect and satisfy additional building area. Spaces with enclosed residence garage shall be reflected. Parking data has been modified per Planning department recommendations.

2. Required landscaping for paved vehicular use areas should be calculated as a percentage of the paved vehicular use area and not the lot area; and shall not include required parking lot setbacks, buffers, or parking overhangs. Landscape area was recalculated accordingly. Updated site data provided on sheet SP-1

3. Indicate location of mechanical equipment. Include Roof Plan if located on the roof and how it will be accessed. If not, include note stating that all mechanical equipment shall be properly screened from public view. Mechanical equipment will be located on top of the electrical room of the residence, refer to sheet A-2. Also, roof plan is included in this submittal; refer to sheet A-3.

4. Provide dimensions and areas of terminal landscape islands. All terminal islands shall be a minimum of 190 square feet and have a length equal to that of the adjacent parking stall. Terminal Landscape Islands have been dimensioned; refer to sheet SP-2.

5. Include Dumpster Enclosure details. Are there any provisions for recycling? Trash is managed by the maintenance team of the school. The pick up the trash from the residence/ office and take it to the school dumpster for proper disposal.

6. Provide method of mail delivery. Mail is delivered to the desk of the office receptionist.

7. Provide location and height/size of fences, walls, dumpster enclosures and signage. Information of the fences and site walls have been included, refer to sheet SP-2

8. Provide overhang projection setback for the west side of proposed structure. Proposed roof was modified; overhang on the west side of the building is 2’-0”, as permitted per code. Refer to sheets A-3 Roof plan.

Page 40: New Chapel & Parish Rectory @ Nativity Catholic Church

9. Clarify purpose of catering kitchen shown on Floor Plan; typo shall also be fixed.

The catering kitchen in the meeting hall is a warming kitchen; not cooking in this area, only will keep warm the food for the special events.

10. Provide current and proposed number of residences. Existing (1) residence – proposed (1) residence.

11. Elevations sheets shall provide median height of structure as well as elevation mark to the highest point of church spire. Acknowledged . Requested information has been added to the proposed elevations, refer to sheets A-4 & A-5

12. Provide height of all projections; mark and calculation for the 25 percent projection shall be included. Proposed roof was modified; overhang of the building is 2’-0” & 5’-0” in some areas, but none over the permitted per code. Refer to sheets A-3 Roof plan.

C. DESIGN Karina da Luz, Planning Administrator 954-921-3471

1. Provide material legend on Elevation sheets. Acknowledged . Requested information has been added to the proposed elevations, refer to sheets A-4 & A-5

Terrence Comiskey, Architect, 954-921 -3930

1. Sheet A-3 & A-4: Exterior Elevations - Material selections not called out in the drawings. Acknowledged . Requested information has been added to the proposed elevations, refer to sheets A-4 & A-5

2. Sheet A-3 & A-4: What type of roofing is proposed? Without a roof plan it is hard to understand the roof slopes on the "Residence" and the 'Office/Meeting Hall". Do they physically connect to the "Chapel"? The roof proposed is standing seam metal roof. A roof plan is included in the attached submittal. Refer to sheet A-3.

3. Sheet A-2: One of the bedrooms and bathrooms in the "Residence" is ADA compliant. That is correct, a room in the second floor of the residence is proposed as ADA bedroom and bathroom.

4. How is trash service handled on site? Trash is managed by the maintenance team of the school. The pick up the trash from the residence/ office and take it to the school dumpster for proper disposal.

5. How will the building meet the City's Green Building Ordinance? List of proposed green building ordinances to be implemented in the project, was added on sheet A-1.

D. LANDSCAPING Dale Bryant, Landscape Architect 954-921-3997

Page 41: New Chapel & Parish Rectory @ Nativity Catholic Church

1. Tree Disposition and Landscape Plans are well-prepared and appear to meet or exceed

Code requirements. Acknowledged.

2. The cost to relocate large trees can be immense, but consider relocation of Royal and Coconut Palms elsewhere on the property. Acknowledged.

3. Final mitigation requirements for removals will be determined at time of Building Permit. Acknowledged.

E. SIGNAGE Karina da Luz, Planning Administrator 954-921-3471

1. For review, full signage package shall be provided, including signage details, signs illustrated on Elevations, dimensions on Site Plan, etc. Monument sign information has been added on sheet A-6.

2. Provide setback of proposed monument sign. Setback required per code has been provide, refer to sheet SP-2-

3. Include note indicating all signage shall be in compliance with the Zoning and Land Development Regulations. Acknowledged.

4. All signs, which are electrically illuminated by neon or other means, shall require a separate electrical permit and inspection. Separate permits are required for each sign. Acknowledged.

F. LIGHTING Karina da Luz, Planning Administrator 954-921 -3471

1. Provide note stating the maximum foot-candle level at all property lines (maximum 0.5 if adjacent to residential) on Site Plan. Tabular data was updated, including maximum foot-candle level. Refer to sheet SP-1

2. Provide detail on lighting to be provided and consistency with existing development on property. Proposed lighting cut sheets are attached to this submittal. Existing luminairs notes have been added to the photometric plan. Reefer to sheet E-1

G. GREEN BUILDING Karina da Luz, Planning Administrator 954-921-3471

1. Project shall provide 10 Green Building Practices in accordance with the City's Green Building Regulations. Indicate compliance on Site Plan and list practices to be implemented. List of proposed green building ordinances to be implemented in the project, was added on sheet A-1.

Page 42: New Chapel & Parish Rectory @ Nativity Catholic Church

H. ENVIRONMENTAL SUSTAINABILITY Lindsey Nieratka, Environmental Sustainability Coordinator 954-921-3201

1. Reduce urban heat island effect through using cool roofs and greater than required tree canopy. Acknowledged .

2. Reduce stormwater pollution through using landscaped areas in the parking lot as bioswales and utilizing pervious pavement. It is the intent of drainage swales north of new parking, swales utilitize raised rims to achieve portion of water quality volume. We will meet the water quality volume requirements, pervious pavement is expensive and will not perform as designed over time. Refer to sheets C-1 to C-4

I. UTILITIES James Rusnak, Engineer 954-921 -3302 Wilford Zephyr, Engineer 954-924-2985

Drainage 1. Application is substantially compliant.

Sewer

1. Application is substantially compliant. J. BUILDING Philip Sauer, Structural Inspector 954-921-3025

1. Provide occupancy type, occupant load and construction type for each building, assuming each is a separate building. Building data was updated with the requested information. Refer to sheet A-1.

2. Provide distance separation requirements of Florida Building Code table 602 and opening protection of FBC table 705.8 for each building. Building is

3. Do the buildings have a fire sprinkler? Yes, building (residence, chapel, office and meeting hall) has fire sprinklers.

4. Explain the use of the second floor of the business office and residence, Handicap Accessibility may be required. The parish schedule different activities with community, such as religious education, adoration, etc.; the proposed meeting hall will allow then to have different meetings with different groups at the same time.

5. More comments may follow when answering the above questions. Acknowledged .

Page 43: New Chapel & Parish Rectory @ Nativity Catholic Church

K. ENGINEERING Jonathan M. Vogt, Deputy Director Public Works/City Engineer 954-921-3251 Clarissa lp, Engineering Support Services Manager 954-921-3915

1. On Sheet SC-1, please verify the computation for the total number of teachers and the total number of staff. Data has been revised, and calculations corrected.

L. FIRE Janet A. Washburn, Fire Prevention Officer Ill 954-921-3263

1. This review is limited to water supply and fire department access. At time of formal submittal to the building department a complete review wi ll be done using the 5th edition Florida Fire Prevention code, NFPA 13,2010 edition, NFPA 72, 2010 edition. Acknowledged.

2. The new building must meet the fire flow requirements found in the 5th edition of the Florida Fire Prevention code, chapter 18 of NFPA 1. A reduction may be taken for the fire sprinkler system. You may schedule a hydrant flow test through underground utilities at 954-921-3046 to determine if new hydrants are needed etc. Once test is complete, have civil engineer calculate fire flow requirements, and show them on the plan and update the civil drawings if necessary. Acknowledged, owner will schedule hydrant flow tests for fire flow building requirements per NFPA code.

3. On pg. C1 show the nearest fire hydrants on 35th Ave. and Johnson St. New fire service for the ‘New Chapel & Parish Rectory’ is proposed from N. 53rd Avenue. Nearest existing hydrants to project are not within NFPA code for proposed new fire connection to new buildings. A proposed fire hydrant has been added adjacent to FDC south of service drive off of N. 53rd Avenue. Existing hydrants located at 35th Ave. / Johnson St. & approximately 165’ south of project along N. 53rd Avenue will be utilized for the proposed hydrant flow tests. Existing hydrants were not located on initial topographic survey .

4. Fire department access must be maintained around the parking lot. The minimum width of the roads are 20' per NFPA 1, 18 Our turning radius is as follows: 28' .5" interior radius, 38' centerline of the turning radius, and 45' exterior. Please show FD access into the parking lot in the event of a car fire. Requested information has been added on sheet SP-2.

M. COMMUNITY DEVELOPMENT Clay Milan, Special Projects Manager 954-921 -3271

1. Sheet A-2: Clarify function of "Cathering Kitchen." The catering kitchen in the meeting hall is a warming kitchen; not cooking in this area, only will keep warm the food for the special events.-

2. It is suggested to inform Hollywood Hills Civic Association about the proposed project. Acknowledged.

Page 44: New Chapel & Parish Rectory @ Nativity Catholic Church

N. PARKS, RECREATION AND CULTURAL ARTS David Vazquez, Assistant Director 954-921-3404 Eric Brown, Recreation Supervisor 954-921-3404

1. Application is substantially compliant. 0 . POLICE DEPARTMENT Tracey Thomas, Police 954-967-4549 Doreen Avitabile, Police 954-967-4371

1. No comments received. P. PARKING Tamika Bacon, Parking Operations Manager 954-921-3448

1. Application is substantially compliant. Q. PUBLIC WORKS Charles Lassiter, Environmental Services Supervisor 954-967-4207 Karen Arndt, Assistant Director 954-967-4264

1. Show previsions for garbage and recycling collection. Trash is managed by the maintenance team of the school. The pick up the trash from the residence/ office and take it to the school dumpster for proper disposal.

R. DOWNTOWN AND BEACH CRA Jorge Camejo, Executive Director 954-924-2980 Susan Goldberg, Deputy Director 954-924-2980

1. Not Applicable. S. ADDITIONAL COMMENTS Karina da Luz, Planning Administrator 954-921-3471

1. None at this time. Thank you for your review, if you have any additional questions or comments please call me directly at (954) 917-5781. Thank you, Architect Bruce Celenski, Inc.