ABB 2CDC 251 048 F0t08 CM-MPS. 2CDC 251 049 F0t08 CM-MPS.2 2CDC 251 050 F0t08 CM-MPS.3 2CDC 251 051 F0t08 CM-MPS.4 Multifunctional three-phase monitoring relays CM-MPS., CM-MPS-2, CM-MPS.3 and CM-MPS.4 Data sheet NEW Features Monitoring of three-phase mains for phase sequence (can be switched off), phase failure, over- and undervoltage as well as phase unbalance Interrupted neutral monitoring possible with CM-MPS. and CM-MPS.2 CM-MPS. and CM-MPS.2 can also be used to monitor single-phase mains Threshold values for phase unbalance, over- and undervoltage are adjustable as absolute values Tripping delay can be adjusted or switched off by means of a logarithmic scale ON-delayed or OFF-delayed tripping delay selectable Powered by the measuring circuit True RMS measuring principle 2 c/o (SPDT) contacts 3 LEDs for status indication J J J J J J J J J J Approvals A UL 508, CAN/CSA C22.2 No.4 C GL D GOST K CB scheme E CCC Marks a CE b C-Tick Order data Type Rated control supply voltage = measuring voltage Interrupted neutral monitoring Order code CM-MPS.11 3x90-70 V AC yes 1SVR 630 885 R1300 CM-MPS.21 3x80-280 V AC yes 1SVR 630 885 R3300 CM-MPS.31 3x60-300 V AC no 1SVR 630 884 R1300 CM-MPS.41 3x300-500 V AC no 1SVR 630 884 R3300 Order data - Accessories Type Description Order code ADP.01 Adapter for screw mounting 1SVR 430 029 R0100 MAR.02 Marker label for devices with DIP switch 1SVR 430 043 R0000 COV.01 Sealable transparent cover 1SVR 430 005 R0100 Application The CM-MPS.x are multifunctional monitoring relays for three-phase mains. They monitor the phase parameters phase sequence, phase failure, over- and undervoltage and phase unbalance. CM-MPS. and CM-MPS.2 also monitor the neutral for interruption. The threshold values for over- and undervoltage and phase unbalance are adjustable. CM-MPS. and CM-MPS.2 are also suitable for monitoring single-phase mains. For this, all three external conductors (L, L2, L3) have to be jumpered and connected as one single conductor. Phase sequence monitoring has to be deactivated and the threshold value for phase unbalance has to be set to the maximum (25 %). R/T: yellow LED - relay status, timing F: red LED - fault message F2: red LED - fault message Adjustment of the tripping delay t V Adjustment of the threshold value for overvoltage 6 Adjustment of the threshold value for undervoltage 7 Adjustment of the threshold value for phase unbalance 8 Function selection (see DIP switch functions) / Marker label

NEW CM-MPS. , CM-MPS-2 , CM-MPS.3 and CM …see DIP switch functions) / Marker label 2 ABB Multifunctional three-phase monitoring relays CM-MPS. , CM-MPS-2 , CM-MPS.3 and CM-MPS.4

  • Upload
    vandung

  • View
    259

  • Download
    4

Embed Size (px)

Citation preview

ABB �

2CD

C 2

51 0

48 F

0t08

��������

CM-MPS.��

2CD

C 2

51 0

49 F

0t08

��������

CM-MPS.2�

2CD

C 2

51 0

50 F

0t08

��������

CM-MPS.3�

2CD

C 2

51 0

51 F

0t08

��������

CM-MPS.4�

Multifunctional three-phase monitoring relaysCM-MPS.��,CM-MPS-2�,CM-MPS.3�andCM-MPS.4�Datasheet

NEW

Features Monitoringofthree-phasemainsforphasesequence(canbeswitchedoff),phasefailure,over-and

undervoltageaswellasphaseunbalance InterruptedneutralmonitoringpossiblewithCM-MPS.��andCM-MPS.2� CM-MPS.��andCM-MPS.2�canalsobeusedtomonitorsingle-phasemains Thresholdvaluesforphaseunbalance,over-andundervoltageareadjustableasabsolutevalues Trippingdelaycanbeadjustedorswitchedoffbymeansofalogarithmicscale ON-delayedorOFF-delayedtrippingdelayselectable Poweredbythemeasuringcircuit TrueRMSmeasuringprinciple 2c/o(SPDT)contacts 3LEDsforstatusindication

J

JJJJJJJJJ

Approvals

A UL508,CAN/CSAC22.2No.�4

C GL

D GOST

K CBscheme

E CCC

Marksa CE

b C-Tick

OrderdataType Ratedcontrolsupplyvoltage=

measuringvoltageInterruptedneutral

monitoringOrder code

CM-MPS.11 3x90-�70VAC yes 1SVR 630 885 R1300

CM-MPS.21 3x�80-280VAC yes 1SVR 630 885 R3300

CM-MPS.31 3x�60-300VAC no 1SVR 630 884 R1300

CM-MPS.41 3x300-500VAC no 1SVR 630 884 R3300

Orderdata-AccessoriesType Description Order code

ADP.01 Adapterforscrewmounting 1SVR 430 029 R0100

MAR.02 MarkerlabelfordeviceswithDIPswitch 1SVR 430 043 R0000

COV.01 Sealabletransparentcover 1SVR 430 005 R0100

ApplicationTheCM-MPS.x�aremultifunctionalmonitoringrelaysforthree-phasemains.Theymonitorthephaseparametersphasesequence,phasefailure,over-andundervoltageandphaseunbalance.CM-MPS.��andCM-MPS.2�alsomonitortheneutralforinterruption.Thethresholdvaluesforover-andundervoltageandphaseunbalanceareadjustable.CM-MPS.��andCM-MPS.2�arealsosuitableformonitoringsingle-phasemains.Forthis,allthreeexternalconductors(L�,L2,L3)havetobejumperedandconnectedasonesingleconductor.Phasesequencemonitoringhastobedeactivatedandthethresholdvalueforphaseunbalancehastobesettothemaximum(25%).

R/T:yellowLED- relaystatus, timing

F�:redLED- faultmessage

F2:redLED- faultmessage

AdjustmentofthetrippingdelaytV

Adjustmentofthethresholdvalueforovervoltage

6 Adjustmentofthethreshold valueforundervoltage

7 Adjustmentofthethreshold valueforphaseunbalance

8 Functionselection (seeDIPswitchfunctions)/ Markerlabel

2 ABB

Multifunctional three-phase monitoring relaysCM-MPS.��,CM-MPS-2�,CM-MPS.3�andCM-MPS.4�Datasheet

NEW

Operatingmode

Configurationofthedevicesismadebymeansofsettingelementsaccessibleonthefrontoftheunitandsignallingismadebymeansoffront-faceLEDs.

Adjustmentpotentiometer

Threshold values

Bymeansofthreeseparatepotentiometerswithdirectreadingscales,thethresholdvaluesforover-andundervoltageaswellasforphaseunbalancecanbeadjustedwithinthemeasuringrange.

Measuring range for overvoltage

Measuring range for undervoltage

Measuring range for phase unbalance

CM-MPS.11 3x�20-�70VAC 3x90-�30VAC 2-25%ofaverageofphasevoltagesCM-MPS.21 3x240-280VAC 3x�80-220VAC

Tripping delay tV

ThetrippingdelaytVcanbeadjustedwithinarangeof0.�-30sbymeansofapotentiometerwithlogaritmicscale.Byturningtotheleftstop,thetrippingdelaycanbeswitchedoff.

DIPswitchesPosition 1 2

ON

OFF

2CD

C 2

52 0

40 F

0b08

DIP switch 1 = Timing function

ON = ON-delayedA OFF = OFF-delayedB

Incaseofafault,thede-energizingoftheout-putrelaysandtherespectivefaultmessagearesuppressedfortheadjustedtrippingdelaytV.

Incaseofafault,theoutputrelaysde-energizeinstantaneouslyandafaultmessageisdisplayedandstoredforthelengthoftheadjustedtrippingdelaytV.Thereby,alsomomentaryundervoltageconditionsarerecognized.

DIP switch 2 = Phase sequence monitoring

ON = Phase sequence monitoring deactivatedl

OFF = Phase sequence monitoring activatedk

Phasesequenceerrorswillnotberecognized. Theoutputrelaysde-energizeassoonasaphasesequenceerroroccurs.Theoutputrelaysre-energizeautomaticallyassoonasthephasesequenceiscorrectagain.

ABB 3

Multifunctional three-phase monitoring relaysCM-MPS.��,CM-MPS-2�,CM-MPS.3�andCM-MPS.4�Datasheet

NEW

LEDs

Function R/T: yellow LED

F1: red LED

F2: red LED

Controlsupplyvoltageapplied,outputrelayenergized

V - -

TrippingdelaytVactive W - -

Phasefailure - V W

Phasesequence - Walternating

Overvoltage - V -

Undervoltage - - V

Phaseunbalance - V V

Interruptionoftheneutral - V W

Adjustmenterror�) W W W

�)Overlappingofthethresholdvalues:Anoverlappingofthethresholdvaluesisgiven,ifthethresholdvalueforovervoltageissettoasmallervaluethanthethresholdvalueforundervoltage.

4 ABB

Multifunctional three-phase monitoring relaysCM-MPS.��,CM-MPS-2�,CM-MPS.3�andCM-MPS.4�Datasheet

NEW

FunctiondiagramlegendGControlsupplyvoltagenotapplied/Outputcontactopen/LEDoffBControlsupplyvoltageapplied/Outputcontactclosed/LEDglowing

Interruptedneutralmonitoring

Theinterruptionoftheneutralinthemaintobemonitoredisdetectedbymeansofphaseunbalanceevaluation.Ifthestarpointisdisplacedbyasymmetricalloadinthethree-phasemain,aninterruptedneutralwillbedetected.Determinedbythesystem,incaseofunloadedneutral,i.e.symmetricalloadbetweenallthreephases,itmayhappenthataninterruptionoftheneutralwillnotbedetected.

PhasesequenceandphasefailuremonitoringApplyingcontrolsupplyvoltagebeginsthefixedstart-updelaytS.WhentSiscompleteandallphasesarepresentwithcorrectvoltage,theoutputrelaysenergizeandtheyellowLEDR/Tglows.

Phase sequence monitoring

Ifphasesequencemonitoringisactivated,theoutputrelaysde-energizeassoonasaphasesequenceerroroccurs.ThefaultisdisplayedbyalternatedflashingoftheLEDsF�andF2.Theoutputrelaysre-energizeautomaticallyassoonasthephasesequenceiscorrectagain.

Phase failure monitoring

Theoutputrelaysde-energizeinstantaneousifaphasefailureoccurs.ThefaultisindicatedbylightningofLEDF�andflashingofLEDF2.Theoutputrelaysre-energizeautomaticallyassoonasthevoltagereturnstothetolerancerange.

25-2625-28

L1, L2, L3

15-1615-18

L1, L2, L3 L1, L2, L3 L1, L2, L3 L1, L2, L3L1, L3, L2 L1, L2 L1

L3 L2, L3ts2C

DC

252

094

F02

07

F1: red LED

F2: red LED

R/T: yellow LED

Measuring value

ts = start-up delay fixed 200 ms

Functiondescriptions/diagrams

ABB 5

Multifunctional three-phase monitoring relaysCM-MPS.��,CM-MPS-2�,CM-MPS.3�andCM-MPS.4�Datasheet

NEW

Over-andundervoltagemonitoringApplyingcontrolsupplyvoltagebeginsthefixedstart-updelaytS.WhentSiscompleteandallphasesarepresentwithcorrectvoltageandwithcorrectphasesequence,theoutputrelaysenergizeandtheyellowLEDR/Tglows.

Type of tripping delay = ON-delay A

Ifthevoltagetobemonitoredexceedsorfallsbelowthesetthresholdvalue,theoutputrelaysde-energizeafterthesettrippingdelaytViscomplete.TheLEDR/Tflashesduringtimingandturnsoffassoonastheoutputrelaysde-energize.Theoutputrelaysre-energizeautomaticallyassoonasthevoltagereturnstothetolerancerange,takingintoaccountafixedhysteresisof5%.TheLEDR/Tglows.

L1, L2, L3

15-1615-18

> U> U - 5 %

< U + 5 %< U

ts tv tv<tv

25-2625-28

2CD

C 2

52 0

90 F

0207

F1: red LED

F2: red LED

R/T: yellow LED

Measuring value

ts = start-up delay fixed 200 mstv = ajdustable tripping delay

Type of tripping delay = OFF-delay B

Ifthevoltagetobemonitoredexceedsorfallsbelowthesetthresholdvalue,theoutputrelaysde-energizeinstantaneouslyandtheLEDR/Tturnsoff.Assoonasthevoltagereturnstothetolerancerange,takingintoaccountafixedhysteresisof5%,theoutputrelaysre-energizeautomaticallyafterthesettrippingdelaytViscomplete.TheLEDR/Tflashesduringtimingandturnssteadywhentimingiscomplete.

25-2625-28

L1, L2, L3

15-1615-18

> U> U - 5 %

< U + 5 %< U

ts <tv<tvtv

2CD

C 2

52 0

91 F

0207

F1: red LED

F2: red LED

R/T: yellow LED

Measuring value

ts = start-up delay fixed 200 mstv = ajdustable tripping delay

6 ABB

Multifunctional three-phase monitoring relaysCM-MPS.��,CM-MPS-2�,CM-MPS.3�andCM-MPS.4�Datasheet

NEW

PhaseunbalancemonitoringApplyingcontrolsupplyvoltagebeginsthefixedstart-updelaytS.WhentSiscompleteandallphasesarepresentwithcorrectvoltageandwithcorrectphasesequence,theoutputrelaysenergizeandtheyellowLEDR/Tglows.

Type of tripping delay = ON-delay A

Ifthevoltagetobemonitoredexceedsorfallsbelowthesetphaseunbalancethresholdvalue,theoutputrelaysde-energizeafterthesettrippingdelaytViscomplete.TheLEDR/Tflashesduringtimingandturnsoffassoonastheoutputrelaysde-energize.Theoutputrelaysre-energizeautomaticallyassoonasthevoltagereturnstothetolerancerange,takingintoaccountafixedhysteresisof20%.TheLEDR/Tglows.

L1, L2, L3

15-1615-18

L1, L2, L3 L1, L2

L3

ts tv tv<tv

25-2625-28

2CD

C 2

52 0

92 F

0207

F1: red LED

F2: red LED

R/T: yellow LED

Measuring value

UnbalanceUnbalance - Hysteresis

Unbalance + HysteresisUnbalance

ts = start-up delay fixed 200 mstv = ajdustable tripping delay

Type of tripping delay = OFF-delay B

Ifthevoltagetobemonitoredexceedsorfallsbelowthesetphaseunbalancethresholdvalue,theoutputrelaysde-energizeinstantaneouslyandtheLEDR/Tturnsoff.Assoonasthevoltagereturnstothetolerancerange,takingintoaccountafixedhysteresisof20%,theoutputrelaysre-energizeautomaticallyafterthesettrippingdelaytViscomplete.TheLEDR/Tflashesduringtimingandturnssteadywhentimingiscomplete.

25-2625-28

L1, L2, L3

15-1615-18

ts <tv<tvtv

L1, L2, L3 L1, L2

L3

2CD

C 2

52 0

93 F

0207

F1: red LED

F2: red LED

R/T: yellow LED

Measuring value

UnbalanceUnbalance - Hysteresis

Unbalance + HysteresisUnbalance

ts = start-up delay fixed 200 mstv = ajdustable tripping delay

ABB 7

Multifunctional three-phase monitoring relaysCM-MPS.��,CM-MPS-2�,CM-MPS.3�andCM-MPS.4�Datasheet

NEW

Connectiondiagrams

L1N

L2

28252618

L3

L3 15

16 18 26 28

25L2

N

L1

16 15

2CD

C 2

52 0

36 F

0b08

L�,L2,L3,N Controlsupplyvoltage=measuringvoltage�5-�6/�8 Outputcontacts-25-26/28 closed-circuitprinciple

CM-MPS.11 and CM-MPS.21

L1 L2

28252618

L3

L3 15

16 18 26 28

25L2L1

16 15

2CD

C 2

52 0

37 F

0b08

L�,L2,L3,N Controlsupplyvoltage=measuringvoltage�5-�6/�8 Outputcontacts-25-26/28 closed-circuitprinciple

CM-MPS.31 and CM-MPS.41

8 ABB

Multifunctional three-phase monitoring relaysCM-MPS.��,CM-MPS-2�,CM-MPS.3�andCM-MPS.4�Datasheet

NEW

DataatTa=25°Candratedvalues,ifnothingelseindicated

Type CM-MPS.11 CM-MPS.21 CM-MPS.31 CM-MPS.41Input circuit = Measuring circuit L1, L2, L3, N L1, L2, L3

RatedcontrolsupplyvoltageUS=measuringvoltage 3x90-�70VAC 3x�80-280VAC 3x�60-300VAC 3x300-500VACRatedcontrolsupplyvoltageUStolerance -�5...+�0%Ratedfrequency 50/60Hz

Frequencyrange 45-65Hz

Typicalcurrent/powerconsumption 25mA/�0VA(��5VAC)

25mA/�8VA(230VAC)

25mA/�0VA(230VAC)

25mA/�8VA(400VAC)

Measuring circuit L1, L2, L3, N L1, L2, L3

Monitoringfunctions Phasefailure J J J JPhasesequence canbeswitchedoff

Automaticphasesequencecorrection - - - -

Over-/undervoltage J J J JPhaseunbalance J J J J

Interruptedneutral J J - -

Measuringrange Overvoltage 3x�20-�70VAC 3x240-280VAC 3x220-300VAC 3x420-500VAC

Undervoltage 3x90-�30VAC 3x�80-220VAC 3x�60-230VAC 3x300-380VAC

Phaseunbalance 2-25%ofaverageofphasevoltages

Thresholds Overvoltage adjustablewithinmeasuringrange

Undervoltage adjustablewithinmeasuringrange

Phaseunbalance(switch-offvalue) adjustablewithinmeasuringrange

Hysteresisrelatedtothethresholdvalue

Over-/undervoltage fixed5%

Phaseunbalance fixed20%

Ratedfrequencyofthemeasuringsignal 50/60Hz

Frequencyrangeofthemeasuringsignal 45-65Hz

Maximummeasuringcycletime �00ms

Measuring error within the rated control supply voltage tolerance 0.5%

Measuringerrorwithinthetemperaturerange 0.06%/°C

Measuringmethod TrueRMS

Timing circuit

Start-updelaytS fixed200ms

TrippingdelaytV ON-orOFF-delay0;0.�-30sadjustable

Repeataccuracy(constantparameters) <w0.2%

Timingerrorwithintheratedcontrolsupplyvoltagetolerance 0.5%

Timingerrorwithinthetemperaturerange 0.06%/°C

Indication of operational states �yellowLED,2redLEDsDetailsseeoperatingmodeandfunctiondescription/diagrams

Output circuits 15-16/18, 25-26/28

Kindofoutput �x2c/o(SPDT)contacts(Relays)

Operatingprinciple�) closed-circuitprinciple

Contactmaterial AgNialloy,Cdfree

Ratedvoltage(VDE0��0,IEC60947-�) 250V

Minimumswitchingpower 24V/�0mA

Maximumswitchingvoltage seeloadlimitcurves

Ratedoperationalcurrent(IEC/EN60947-5-�)

AC�2(resistive)230V 4A

AC�5(inductive)230V 3A

DC�2(resistive)24V 4A

DC�3(inductive)24V 2AACrating(UL508)

Utilization category (Control Circuit Rating Code)

B300

max. rated operational voltage 300VACmax. continuous thermal current at B 300 5A

max. making/breaking apparent power at B 300

3600/360VA

Mechanicallifetime 30x�06switchingcycles

Electricallifetime(AC�2,230V,4A) 0,�x�06switchingcycles

ABB 9

Multifunctional three-phase monitoring relaysCM-MPS.��,CM-MPS-2�,CM-MPS.3�andCM-MPS.4�Datasheet

NEW

DataatTa=25°Candratedvalues,ifnothingelseindicated

Type CM-MPS.11 CM-MPS.21 CM-MPS.31 CM-MPS.41

Short-circuitproof,maximumfuserating

n/ccontact 6Afast-acting

n/ocontact �0Afast-acting

General data

Dutytime �00%

Dimensions(WxHxD) 22.5x78x�00mm(0.89x3.07x3.94inch)

Weight 0.�4kg(0.3�lb) 0.�3kg(0.29lb)

Mounting DINrail(EN607�5),snap-onmountingwithoutanytool

Mountingposition any

Minimumdistancetootherunits lateral �0mm(0.4inch)incaseofcontinuousvoltageof...

>�20V >240V >220V >400V

Degreeofprotection enclosure/terminals IP50/IP20

Electrical connection

Wiresize fine-strandwith(out)wireendferrule 2x0.75-2.5mm²(2x�8-�4AWG)

rigid 2x0.5-4mm²(2x20-�2AWG)

Strippinglength 7mm(0.28inch)

Tighteningtorque 0.6-0.8Nm

Environmental data

Ambienttemperatureranges operation/storage -25...+60°C/-40...+85°C

Dampheat(IEC60068-2-30) 55°C,6cycles

Climaticcategory 3K3

Vibration(sinusoidal)(IEC/EN60255-2�-�) Class2

Shock(IEC/EN60255-2�-2) Class2

Isolation data

RatedinsulationvoltageUi

inputcircuit/outputcircuit 600V

outputcircuit�/outputcircuit2 300V

RatedimpulsewithstandvoltageUimp(VDE0��0,IEC/EN60664)

inputcircuit 6kV;�.2/50µs

outputcircuit 4kV;�.2/50µs

Testvoltagebetweenallisolatedcircuits(typetest) 2.5kV,50Hz,�s

Basisisolation inputcircuit/outputcircuit 600V

Protectiveseparation(VDE0�60part�0�and�0�/A,IEC/EN6��40)

inputcircuit/outputcircuit

yes -

Pollutiondegree(VDE0��0,IEC/EN60664,UL508) 3

Overvoltagecategory(VDE0��0,IEC60664,UL508) III

Standards

Productstandard IEC/EN60255-6,EN50�78

LowVoltageDirective 2006/95/EC

EMCdirective 2004/�08/EC

RoHSdirective 2002/95/EC

Electromagnetic compatibility

Interferenceimmunity EN6�000-6-�,EN6�000-6-2

electrostaticdischarge(ESD) IEC/EN6�000-4-2 Level3(6kV/8kV)

electromagnetic field (HF radiation resistance) IEC/EN6�000-4-3 Level3(�0V/m)

fasttransients(Burst) IEC/EN6�000-4-4 Level3(2kV/2kHz)

powerfulimpulses(Surge) IEC/EN6�000-4-5 Level4(2kVL-N) Level4(2kVL-L)

HFlineemission IEC/EN6�000-4-6 Level3(�0V)

Resistancetoharmonics EN6�000-4-�3 Class3

Interferenceemission EN6�000-6-3,EN6�000-6-4

electromagn. field (HF radiation resistance) IEC/CISPR22,EN50022 ClassB

HFlineemission IEC/CISPR22,EN50022 ClassB�) Closed-circuitprinciple:Outputrelay(s)de-energize(s)ifmeasuredvalueexceedsorfallsbelowtheadjustedthresholdvalue

�0 ABB

Multifunctional three-phase monitoring relaysCM-MPS.��,CM-MPS-2�,CM-MPS.3�andCM-MPS.4�Datasheet

NEW

Technicaldiagrams

Loadlimitcurves

AC load (resistive)

300

200

100 80 60 50 40 30

20

10 1 2 4 6 10

I A

V

2CD

C 2

52 1

94 F

0205

V

0.1 0.2 0.5

DC load (resistive)

300

200

100 80 60 50 40 30

20

10 1 2 4 6 10

I A

V

2CD

C 2

52 1

93 F

0205

V

0.1 0.2 0.5

DeratingfactorF

at inductive AC load

cos ϕ

F

2CD

C 2

52 1

92 F

0205

0.5

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0

0.6

0.7

0.8

0.9

1.0

Contactlifetime

Switching current [A]

250 Vresistive load

Sw

itchi

ng c

ycle

s

2CD

C 2

52 1

48 F

0206

ABB ��

Multifunctional three-phase monitoring relaysCM-MPS.��,CM-MPS-2�,CM-MPS.3�andCM-MPS.4�Datasheet

NEW

Dimensionsinmm

2CD

C 2

52 0

31 F

0b03

Dimensions-Accessoriesinmm

2CD

C 2

52 1

87 F

0005

4,5 62,5

60

1011

,5

22,5

.177

2.46”

2.36”

.394

.886

.453

203A11 8

.315

.787”

2CD

C 2

52 1

86 F

0005

ADP.01 - Adapter for screw mounting MAR.02 - Marker label

2CD

C 2

52 1

85 F

000522,5

68,5

73,5

.886”

2.70

.138”.275”

front-to-backsize 107

COV.01 - Sealable transparent cover

Furtherdocumentation

Document title Document type Document number

ElectronicProductsandRelays Technicalcatalogue 2CDC��0004C020x

CM-MPS.��,CM-MPS.2�,CM-MPS.3�,CM-MPS.4�

Instructionmanual �SVC630520M0000

Youcanfindthedocumentationonlineatwww.abb.com/lowvoltageRControlProductsR...

ABBABB STOTZ-KONTAKT GmbH

EppelheimerStraße82,69�23Heidelberg,GermanyPostfach�0�680,69006Heidelberg,GermanyInternet http://www.abb.com/lowvoltageRControlProducts