NEW DUCT

Embed Size (px)

Citation preview

  • 7/27/2019 NEW DUCT

    1/122

    1

    Ducted Type Air Conditioner

    Indoor unit with round air outlet

    Indoor unit with rectangle air outlet

    Indoor unit with high static pressure(with filter in return air inlet

  • 7/27/2019 NEW DUCT

    2/122

    2

    Outdoor unit (2.6kw~10kw)

    Outdoor unit (12kw~16kw)

  • 7/27/2019 NEW DUCT

    3/122

    3

    1. Summary and Features

    1.1 Model Designation

    FG / N-

    Unit type

    Power type

    Refrigerant type

    Static pressure type

    Cooling capacity

    Product type

    Ducted type air conditioning

    Meaning of standard model before/

    Meaning FG Product type Cooling capacity Static pressure type

    Cooling only type-omitted Common type-omitted

    Heat pump auxiliary

    electric heat type-R

    High static pressure-H

    Expression

    method

    Ducted type air

    conditioning

    Nominal cooling

    capacity (kW)

    The outdoor unit is not

    expressed.

    Meaning of supplementation code after /

    Meaning Refrigerant Power supply type Indoor and outdoor unit code

    R22-omitted 1Ph-220~230V-50Hz-o

    mitted

    Outdoor unit-O

    R407-N 1Ph-220~230V-50Hz

    below 10kw-E

    Indoor unit-I

    Expression

    method

    R410a-Na 3Ph-380~420V-50Hz-M The entire unit is notexpressed.

    Example1FGR2.6/NIt refers to the ducted air conditioning unit with a nominal cooling capacity of 2.6kW. Its

    refrigerant is R407C, power supply is 1Ph-220~230V-50Hz.

    2FGR10/N-MIt refers to the ducted air conditioning unit with a nominal cooling capacity of 10kW. Its

    refrigerant is R407C, power supply is Ph-380~420V-50Hz.

    1.2 Product feature

  • 7/27/2019 NEW DUCT

    4/122

    4

    GREE FG Series Ducted type Air-conditioning Units has combined the comfort, top grade from the central

    air conditioners as well as the convenient installation and facility from the mini type of the split air conditioners. It

    could be divided into the ordinary units and high static pressure units can satisfy with the different requirements

    from customers. The FG Series Ducted Air-conditioning Units can be widely used in small supermarkets,

    chain stores, hotels, restaurants, offices and meeting rooms etc. Is especially fit for the small commercial

    and industrial application.

    a) Flexible installationair-supply or air-return type, condensation water exit direction, andmodes of twyer(adopting neither air back or rear air back) etc can be selected flexibly;

    b) Energy effectivelyquality compressor, hydrophilic aluminum sheet and inner groovecopper pipe are adopted, so as to improve the efficiency of units greatly;

    c) Long-distance duct air supply : it adopt high static pressure design, so air is centralized

    handling in the indoor unit and implant long-distance duct air supply.

    d) Good indoor air quality: it can connect many supply-air outlet to the duct, so that it can

    make the temperature and humidity of the whole room equality, meanwhile, it can lead in

    fresh air, makes well indoor unit air quality

    e) Reliably operation: it has perfect safe protection function, and powerful malfunction

    self-diagnosis function;

    f) Convenient operation: Simple controller and intelligent remote controller make unit

    more convenient operation.

    1.3 Microcomputer control system, as shown in table 1-1.

    Table 1-1

    Control function Protection function Display function

    Memory function High/low pressure protection Timing ON/OFF display

    Remote control function Overload protection Fan speed display

    Timing function Over current protection Function model display

    Self-diagnosis with alarm

    function

    Discharge high temperature

    protection Defrosting display

    Sleep function Reverse (open) phase protection Testing display

    Automatic functionAnti-freeze temperature

    sensorSleep mode display

    Cool air proof functionAnti-high temperature

    protectionTemperature display

    Blow residual heat function Sensor malfunction alarm Malfunction code display

    Sub-room control function

    Centralization control

    function

  • 7/27/2019 NEW DUCT

    5/122

    5

    Control function Memory function: when unit restart after power off, it will run on former status, the mode and parameter are

    kept the same

    Remote control function: wireless controller and remote controller can be opted, and the maximum control

    distance of remote controller is 10m.

    Timing function: it can timing ON/ OFF separately, meanwhile, it can also can timing on circularly

    Self-diagnosis with alarm function : once unit has malfunction, the malfunction code will be indicated and

    alarm ring immediately

    Energy efficiency: it can self control for saving energy in energy saving mode.

    Automatic model function: the fan of indoor unit can adjust fan speed automatically based on actual demand

    when cooling or heating under automatic mode

    Cool air proof function: the fan starts only when the temperature of indoor unit heat exchanger is higher than

    indoor temperature under heating mode

    Sub-room control function: it can control the unit by controlling each sub-room

    Blow residual heat function: under heating mode, fan of indoor unit will work for a period after compressor

    stops

    Protection function

    High/low pressure protection: when suction pressure is too low or discharge pressure is too high, compressor

    will stop and unit display malfunction code

    Overload protection: compressor has its own overheat protection, once the temperature of compressor is

    higher than allowable level, compressor will stop and only when temperature recovery, compressor restart

    Over current protection: once the current of compressor is higher that normal level, compressor will stop and

    unit display malfunction code

    Discharge high temperature protection: once the discharge temperature of compressor is higher than

    allowable value, compressor will stop and unit display malfunction code

    Reverse (open) phase protection: once the phase sequence of power supply is incongruent or the phase is

    absent, unit cant work and display malfunction code (Remark: this function is only available for

    FG(R)10/N-M and FG(R)12/N-M)

    Anti-freeze temperature protection: once the heat exchanger temperature of indoor unit is

    too low, compressor will stop and unit display malfunction code.

    Anti-high temperature protection: once the heat exchanger temperature of indoor unit is too

  • 7/27/2019 NEW DUCT

    6/122

    6

    high, compressor stop and unit display malfunction code.

    Sensor malfunction alarm: once the sensor short out or shutdown, unit will display malfunction code.

    Display function Time display: display and set real time

    Timing turn ON/OFF display: display and timing turn ON/OFF time.

    Cancel timing display: display the cancel of timing

    Fan speed display: display the speed (highmediumlow) of fan

    Function mode display: cooling modedehumidifying modeheating modefan mode

    Defrost display: display defrosting status under deforst mode

    Testing display: display testing mode

    Energy efficiency display: display energy saving mode

    Temperature display: display room temperature and set temperature

    Malfunction code display

    Centralization control system (optional function)Ducted Type Air Conditionerhas centralization control function, each centralization controller can

    control 16 set of main units simultaneously and control each main unit separately, this function

    can make you more convenient for controlling main units. The centralization controller of

    Ducted type air conditioner communicate with wire controller of each unit by 485 mode, the

    longest distance is 1200m; centralization controller can display the code of each unit that is

    delimited by the different dial-up location of each unit. The connection of centralization

    controller and wire controller is as follow fig:

  • 7/27/2019 NEW DUCT

    7/122

    7

    Remark: if you need this function, please notify us before ordering.

  • 7/27/2019 NEW DUCT

    8/122

    2. Specification and technical parameter

    2.1 Nominal work condition and working temperature rangeas shown in table 2.1-1

    Table 2.1-1

    Work condition Temperature Indoor air temperature Outdoor air temperature

    Nominal 27 DB / 19 WB 35 DB / 24 WB

    Max. 32 DB / 23 WB 43 DB / 26 WBCooling

    Min. 18 DB / 14 WB 18 DB /

    Nominal 20 DB / 7 DB / 6 WB

    Max. 24 DB / 18 WB 27 DB /Heating

    Min. 15 DB / 7 DB / -8 WB

    2.2 Specification and technical parameter

  • 7/27/2019 NEW DUCT

    9/122

    2.2.2 Technical parameter of FG(R)2.6/NFG(R)3.5/NFG(R)5/NFG(R)7/N-E

    COOLING HEATING COOLING HEATING COOLING HEATING COOLING HEATING

    2600 2900 3500 3700 5000 5800 7000 8200

    930 998 1340 1217 1935 1849 3000 3000

    1300 1300 1850 1850 2750 2750 4050 4050

    4.5 5 6.8 6.1 8.9 8.54 14.6 13.5

    2.796 2.906 2.612 3.04 2.584 3.137 2.3 2.7

    Model of Indoor Unit

    Fan Motor Speed (r/min) (H/M/L)

    Output of Fan Motor (w)

    Fan Motor Capacitor (uF)

    Fan Type-Piece

    Diameter-Length (mm)

    Evaporator

    Pipe Diameter (mm)

    Row - Fin Gap (mm)

    Working Area (m2)

    Swing Motor Model

    Output of Swing Motor (W)

    Fuse (A)

    Sound Pressure Level dB (A) (H/M/L)

    Dimension (W/D/H)( mm)

    Dimension of Package (W/D/H)( mm)

    Net Weight /Gross Weight (kg)

    Model of Outdoor Unit

    Compressor Model

    L.R.A. (A)

    Overload Protector

    Throttling Method

    Starting Method

    Working Temp Range ()

    Condenser

    Pipe Diameter (mm)

    Rows - Fin Gap (mm)

    Working Area (m2)

    Fan Motor Speed (rpm) (H/M/L)

    Output of Fan Motor (W)

    Fan Motor Capacitor (uF)

    Air Flow Volume of Outdoor unit(m3 /H)

    Fan Type-Piece

    Fan Diameter (mm)

    Defrosting Method

    Sound Pressure Level dB (A) (H/M/L)

    Dimension (W/D/H)( mm)

    Dimension of Package (W/D/H)( mm)

    Net Weight /Gross Weight (kg)

    Refrigerant Charge (kg)

    Length (m)

    Liquid Pipe 1/4" Liquid Pipe 1/4" Liquid Pipe 1/4" Liquid Pipe 3/8"

    Gas Pipe 3/8" Gas Pipe 1/2" Gas Pipe 1/2" Gas Pipe 5/8"

    Height (m) 15 Height (m) 15 Height (m) 15 Height (m) 15

    Length (m) 20 Length (m) 20 Length (m) 20 Length (m) 25

    5 5

    950x412x700

    1100x450x905

    75/80

    2.8 (R407C)2.1 (R407C)

    59/64

    Axial fan1

    450

    Auto defrost

    59

    780

    60

    3

    2600

    Aluminum fin-copper tube

    9.52

    2-1.8

    0.56

    3HM

    Capillary

    PSC

    -7DB43DB

    55/59

    FG(R)7/N-E(O)

    C-RN220H5B

    75

    3.15A

    46/44/42

    1108x756x300

    1245x785x360

    3-1.8

    0.24

    ----

    ----

    Centrifugal fan -3

    190x200

    Aluminum fin-copper tube

    9.52

    FG(R)7/N-E

    230V ~

    50Hz

    1200

    2.7

    FG(R)7/N-E(I)

    1050/1000/750

    150

    8

    57

    760x250x530

    878x360x590

    2200

    Axial fan1

    450

    Auto defrost

    0.44

    780

    60

    3

    -7DB43DB

    Aluminum fin-copper tube

    9.52

    2-1.7

    55

    UP3-07

    Capillary

    PSC

    1068x766x320

    36/39

    FG(R)5/N(O)

    CHW33TC4-U

    ----

    3.15A

    42/41/40

    980x736x276

    9.52

    3-1.8

    0.18

    ----

    4

    Centrifugal fan -2

    155x175

    Aluminum fin-copper tube

    2

    FG(R)5/N (I)

    1250/1150/1050

    70

    FG(R)5/N

    230V ~

    50Hz

    840

    Model FG(R)2.6/N

    Function

    Rated Voltage 230V ~

    Rated Frequency 50Hz

    Capacity (W)

    Power Input (W)

    Rated Input (W)

    Rated Current (A)

    Air Flow Volume (m3/h) 450

    Dehumidifying Volume (Kg/h) 1.01

    C.O.P / EER (W/W)

    Indoorunit

    FG(R)2.6/N (I)

    770/570/500

    20

    1.5

    Centrifugal fan -2

    155x175

    Aluminum fin-copper tube

    6

    2-1.6

    0.15

    ----

    ----

    3.15A

    38/37/36

    913x680x220

    1012x708x275

    27/31

    Outdoorunit

    FG(R)2.6/N (O)

    C-RV167H01AA

    23

    MST20ALU-9201

    Capillary

    PSC

    -7DB43DB

    Aluminum fin-copper tube

    9.52

    1-1.6

    0.31

    805

    30

    2.5

    1200

    Axial fan1

    400

    Auto defrost

    Conn

    ectio

    n

    Pipe

    Outer Diameter

    Max Distance

    55

    760x250x530

    878x360x590

    32/37

    FG(R)3.5/N

    230V ~

    50Hz

    520

    1.4

    FG(R)3.5/N (I)

    1100/870/720

    20

    2.5

    Centrifugal fan -2

    155x175

    Aluminum fin-copper tube

    6

    3-1.6

    0.14

    ----

    ----

    3.15A

    40/39/38

    913x680x220

    1012x708x275

    27/31

    FG(R)3.5/N (O)

    C-RV227H01AA

    31

    MRA98619-9200

    Capillary

    PSC

    -7DB43DB

    Aluminum fin-copper tube

    9.52

    1-1.4

    0.31

    885

    48

    3

    2200

    Axial fan1

    450

    Auto defrost

    0.9 (R407C)

    5 5

    56

    760x250x530

    878x360x590

    32/37

    0.95 (R407C)

  • 7/27/2019 NEW DUCT

    10/122

    2.2.3 FG(R)10/N-EFG(R)10/N-MFG(R)12/N-MFGR16/NC-M technical parameter

    COOLING HEATING COOLING HEATING COOLING HEATING HEATING

    10000 11000 10000 11000 12000 13200 16000 18000

    4200 4200 4200 4200 5200 5200 5900 6000

    5670 5670 5670 5670 7020 7020 10980 14580

    19.6 19.6 7.3 7.3 8.7 8.7 13 12.5

    2.4 2.6 2.4 2.6 2.3 2.5 2.71 3

    Model of Indoor Unit

    Fan Motor Speed (r/min) (H/M/L)

    Output of Fan Motor (w)

    Fan Motor Capacitor (uF)

    Fan T ype-Piece

    Diameter-Length (mm )

    Evaporator

    Pipe Diameter (mm)

    Row - Fin Gap (mm)

    Working Area (m2)

    Swing Motor Model

    Output of Swing Motor (W)

    Fuse (A)

    Sound Pressure Level dB (A) (H/M/L)

    Dimension (W/D/H)( mm)

    Dimension of Package (W/D/H)( mm)

    Net Weight /Gross Weight (kg)

    Model of Outdoor Unit

    Compressor Model

    L.R.A. (A)

    Overload Protector

    Throttling Method

    Starting Method

    Working Temp Range ()

    Condenser

    Pipe Diameter (mm)

    Rows - Fin Gap (mm)

    Working Area (m2)

    Fan Motor Speed (rpm) (H/M/L)

    Output of Fan Motor (W)

    Fan Motor Capacitor (uF)

    Air Flow Volume of O utdoo r unit(m3 /H )

    Fan T ype-Piece

    Fan Diameter (mm)

    Defrosting Method

    Sound Pressure Level dB (A) (H/M/L)

    Dimension (W/D/H)( mm)

    Dimension of Package (W/D/H)( mm)

    Net Weight /Gross Weight (kg)

    Refrigerant Charge (kg)

    Length (m)

    Liquid Pipe 1/2" Liquid Pipe 1/2" Liquid Pipe 1/2" Liquid Pipe 1/2"

    Gas Pipe 3/4" Gas Pipe 3/4" Gas Pipe 3/4" Gas Pipe 3/4"

    Height (m) 25 Height (m) 25 Height (m) 25 Height (m) 25

    Length (m) 35 Length (m) 35 Length (m) 35 Length (m) 35

    123/134

    1110x450x1280

    5

    3.8 (R407C)

    112/123

    Axia l fan2

    450

    Auto defrost

    63

    950X 412X 1250

    5

    5 (R407C)

    940

    92

    4

    6000

    Alum inum fin-copper tube

    9.52

    2-1.8

    0.83

    UO-10-16A

    Capillary

    PSC

    -7DB43DB

    95/100

    FGR16/NC-M(O)

    C-SB453H8A

    48

    3.65A

    53/49/46

    1463x 756x370

    1514x785x430

    3-1.8

    0.318

    ----

    ----

    Centrifugal fan -3

    190x200

    Alum inum fin-copper tube

    9.52

    FGR16/NC-M

    400V 3N ~

    50Hz

    3500

    5.2

    FGR16/NC-M(I)

    1100/1000/900

    180/80

    10/5

    62

    950x340x1250

    1110x450x1280

    5200

    Axial fan2

    450

    Auto defrost

    0.83

    840

    68

    3.5

    -7DB43DB

    Alum inum fin-copper tube

    9.52

    2-1.8

    48

    34HM500-B

    Capillary

    PSC

    1514x785x360

    72/76

    FG(R)12/N-M(O)

    C-SBN373H8A

    ----

    3.15A

    48/46/44

    1463x756x300

    9.52

    3-1.80.318

    ----

    8/5

    Centrifugal fan -3

    190x200

    Alum inum fin-copper tube

    4.8

    FG(R)12/N-M (I)

    1050/1000/750

    150/75

    FG(R)12/N-M

    400V 3N ~

    50Hz

    2000

    Model FG(R)10/N-E

    Function

    Rated Voltage 230V ~

    Rated Frequency 50Hz

    Capacity (W)

    Power Input (W)

    Rated Input (W)

    Rated Current (A)

    Air Flow Volume (m3/h) 2000

    Dehumidifying Volume (Kg/h) 4

    C.O.P / EER (W/W)

    Indoor

    unit

    FG(R)10/N-E (I)

    1050/1000/750

    150/75

    8/5

    Centrifugal fan -3

    190x200

    Alum inum fin-copper tube

    9.52

    3-1.80.318

    ----

    ----

    3.15A

    48/46/44

    1463x756x300

    1514x785x360

    72/76

    Outdoorunit

    FG(R)10/N-E (O)

    C-SBN301H5A

    48

    UP16RC1210-Z1

    Capillary

    PSC

    -7DB43DB

    Alum inum fin-copper tube

    9.52

    2-1.8

    0.56

    840

    68

    3.5

    5200

    Axial fan2

    450

    Auto defrost

    Conn

    ectio

    n

    Pipe

    Outer Diameter

    Max Distance

    62

    950x340x1250

    1110x450x1280

    112/123

    FG(R)10/N-M

    400V 3N ~

    50Hz

    2000

    4

    FG(R)10/N-M(I)

    1050/1000/750

    150/75

    8/5

    Centrifugal fan -3

    190x200

    Alum inum fin-copper tube

    9.52

    3-1.8

    0.318

    ----

    ----

    3.15A

    48/46/44

    1463x756x300

    1514x785x360

    72/76

    FG(R)10/N-M (O)

    C-SBN303H8A

    48

    34HM500-B

    Capillary

    PSC

    -7DB43DB

    Alum inum fin-copper tube

    9.52

    2-1.8

    0.83

    840

    68

    3.5

    5200

    Axial fan2

    450

    Auto defrost

    3.55 (R407C)

    5 5

    62

    950x340x1250

    1110x450x1280

    112/123

    3.55 (R407C)

  • 7/27/2019 NEW DUCT

    11/122

    3. Characteristic chart

    3.1 The relationship between low pressure of air conditioner and temperatureas shown inchart 3-1

    Cooling mode: the working condition of indoor and outdoor is the same.

    Heating mode: the working condition of indoor is: 21 DB/15.5 WB

    50 60 70 80(%)

    2

    3

    4

    5

    6

    7

    15 20 25 30 35

    DB()/Humidity(%)

    Lowp

    ressure(ab

    solutedate)bar

    2

    3

    4

    5

    6

    7

    0 5 10 15 20

    DB()/Humidity(%)

    Lowp

    ressure(absolutedate)bar

    (a) Cooling mode (b)Heating mode

    chart 3-1

    3.2 Performance chart ( as shown in chart 3-2)

    (a) Cooling (b)Heating

    chart 3-2

  • 7/27/2019 NEW DUCT

    12/122

    3.3 The relationship between cooling capacitycharge of refrigerant and the length of connectpipeas shown in chart 3-3

    92%

    94%

    30 40

    90%

    30

    20

    96%

    98%

    10

    0 100%

    -30

    -20

    -10

    10 20

    (m)

    (m)

    (a) relationship between cooling capacity (b) relationship between charge of refrigerant

    and length of pipe and length of pipe

    chart 3-3

  • 7/27/2019 NEW DUCT

    13/122

    4. Main parts name4.1 Indoor unit and outdoor unit structure schematic plan

    fig. 4-1Indoor unit

    Remark1round air outtake 2rectangular air outtake

    3condensate water pipe 4return air intake

    Fig. 4-2 Outdoor unit

    Remark4air intake 5air outtake

  • 7/27/2019 NEW DUCT

    14/122

    5. Outlines and dimensions of the units5.1 Outlines and dimensions of indoor unit (as shown in chart. 5-1)

    (a)FGR2.6/NFGR3.5/N

  • 7/27/2019 NEW DUCT

    15/122

    bFG(R)5/N(I)~ FG(R)16/NC-M(I)

    chart 5-1Outlines and dimensions of indoor unit

    5.2 Outlines and dimensions of outdoor unitas shown in chart.5-2

    E

    A

    D

    B

    chart 5-2

    Item

    ModelA B C D E F G H I J

    FG(R)5/N(I) 932 430 738 904 980 736 738 207 207 266

    FG(R)7/N-E(I) 1112 420 918 1070 1155 756 1008 207 250 300

    FG(R)10/N-M(I) 1382 420 1155 1340 1425 756 1278 207 250 300

    FG(R)10/N-E(I) 1382 420 1155 1340 1425 756 1278 207 250 300

    FG(R)12/N-M(I) 1382 420 1155 1340 1425 756 1278 207 250 300

    FG(R)16/NC-M(I) 1382 420 1155 1340 1425 756 1278 273 320 370

  • 7/27/2019 NEW DUCT

    16/122

    ModelItem

    FG(R)2.6/N(O)FG(R)3.5/N(O)FG(R)5/N(O)

    FG(R)7/N-E(O)FG(R)10/N-E(O)FG(R)10/N-M(O)FG(R)12/N-M(O)FG(R)16/NC-M(O)

    A 760 950

    B 320 412

    C 530 700 1250

    D 540 572

    E 286 378

  • 7/27/2019 NEW DUCT

    17/122

    6. Air conditioner working principle

    Cooling cycleLow temperature and low pressure refrigerant gas goes from evaporator,then be suction into compressor and compressed into high temperature and high pressure gas by

    compressor and discharge to condenser; in condenser, the high temperature and high pressure gas

    exchange heat with outdoor fresh air, then the gas becomes high temperature and high pressure

    liquid; then it is cooled and decompressed by capillary and go into evaporator. In the evaporator, the

    liquid refrigerant and gas refrigerant are mixed and evaporated, the heat which is demanded for

    evaporation is supplied by indoor air, so the indoor air is cooled at the same time. Then the gas from

    evaporator goes into compressor again, so the cooling cycle begins. And the cooled air is supplied

    into air conditioning area through duct by fan.Heating cycle: The heating cycle is inverse cycle to cooling cycle. Four-way valve changes

    its direction, so refrigerant change the direction. It means the high temperature and high pressure

    refrigerant gas goes from compressor and into indoor heat exchanger, after the refrigerant is

    condensed by condenser and throttled by capillary, it goes into outdoor heat exchanger and be

    evaporated, then be suctioned by compressor again, so the heating cycle begins. And the warm air is

    supplied into air conditioning area through duct by fan.

    Working principle schematic for cooling only unit

  • 7/27/2019 NEW DUCT

    18/122

    Working principle schematic for heat pump unit

  • 7/27/2019 NEW DUCT

    19/122

    1

    7. Electric schematic diagram

    7.1 Indoor unit static-pressure adjustment wiring diagramMulti-static pressure indoor unit can adjust its static pressure by changing wire

    connection mode. There are two unit type: standard static pressure mode and high

    static pressure mode, their wiring diagram is as follows(refer to fig. 7.1-1)

    XT2

    XT3

    2

    2

    1

    1

    FH

    FM

    FL FL

    FH

    FM

    XT2

    1

    2

    1

    XT3

    2

    High static pressure typeStandard static pressure type

    (omitted type from factory)

    Contr

    olpanel

    white

    black

    yellow

    blue

    blue

    blue

    yellow

    yellow

    blackblack

    white

    white

    Contr

    olpanel

    white

    black

    yellow

    blue

    blue

    blue

    yellow

    yellow

    blackblack

    white

    white

    (a)double-motor high static pressure type

    FL

    FH

    FM

    XT2

    1

    2

    1

    XT3

    2

    XT2

    FL

    FM

    FH

    1

    2

    1

    2

    XT3

    Standard static pressure type(omitted type from factory)

    High static pressure type

    Controlpanel

    Controlpanel

    white (yellow)

    black (red)

    yellow (blue)

    blue (black)

    white (yellow)

    black (red)

    yellow (blue)

    blue (black)

    white (yellow)

    black (red)

    yellow (blue)

    blue (black) blue (black)

    yellow (blue)

    black (red)

    white (yellow)

    (b) single-motor high static pressure type

    fig. 7.1-1

  • 7/27/2019 NEW DUCT

    20/122

    2

    7.2 Electric wiring diagram of units

    Electric wiring diagram of FG2.6/N, FG3.5/N

  • 7/27/2019 NEW DUCT

    21/122

    3

    Electric wiring diagram of FGR2.6/N, FGR3.5/N

  • 7/27/2019 NEW DUCT

    22/122

    4

    Electric wiring diagram of FG5/N

  • 7/27/2019 NEW DUCT

    23/122

    5

    Electric wiring diagram of FGR5/N

  • 7/27/2019 NEW DUCT

    24/122

    6

    Electric wiring diagram of FG7/N-E

  • 7/27/2019 NEW DUCT

    25/122

    7

    Electric wiring diagram of FGR7/N-E

  • 7/27/2019 NEW DUCT

    26/122

    8

    Electric wiring diagram of FG10/N-E

    5F

    8F

  • 7/27/2019 NEW DUCT

    27/122

    9

    Electric wiring diagram of FGR10/N-E

    5F

    8F

  • 7/27/2019 NEW DUCT

    28/122

    10

    Electric wiring diagram of FG10/N-M, FG12/N-M

  • 7/27/2019 NEW DUCT

    29/122

    11

    Electric wiring diagram of FGR10/N-M, FGR12/N-M

    8F

    5F

  • 7/27/2019 NEW DUCT

    30/122

    12

    Electric wiring diagram of FGR16/NC-M

  • 7/27/2019 NEW DUCT

    31/122

    8. Wire controller function and operation

    8.1 Composition and function of wire controllertype one as shown in fig 8.1-1

    88:88

    8888

    LCDDisplay information.

    ON/OFF buttonpress one time, unitturn on; press once

    again, unit turn off

    Automatichighmediumlow

    Fan speed control button:every

    press, speed adjust as follows:

    Sleep mode button:press

    one time, enter sleep

    mode, press once again,

    exit sleep mode

    Timing button: set timing turn

    OFF/ON under ON/OFF status.press every time, the timing willadd half an hour.

    The circle mode is as follows:0--24hours

    cancel timing

    Temperature buttonpress

    every time , settedtemperature rises 1pressevery time , setted timereduce 1

    Mode button: pressevery time, mode

    change as follows:

    dehumidifyheatingblow

    Automaticcooling

    ON/OFF

    Sleep

    Timing

    Fan speed

    Mode

    Temperature adjust

    ON/OFF

    Timing

    AM PM Hour Swing

    Sleep

    Auto

    Setting EnvironmentDefrost

    Test

    Fan speed

    Auto Cool Dry

    HeatBlowMode

    Fig 8.1-1

    8.2 Operation of wire controller1) Cooling operation methodas shown in fig 8.2-1

    Micro-computer can select cool mode ON or OFF according to the temperature

    differential between set temperature-Tsetand indoor air temperature- Tindoor that

    is detected by temperature sensor.

    When Tindoor is higher than Tset, the unit start to work in cool mode.

    When Tindoor is lower than Tset, the cool mode turn off, only the fan of indoor unit

    works.

  • 7/27/2019 NEW DUCT

    32/122

    The set temperature rang is in the range of 1630

    ModeSwing

    Sleep

    Temperature adjust

    Hour

    ON/OFFTiming

    AM PM

    Fan speed

    Auto

    ON/OFF

    Fan speed

    Test

    88

    BlowMode

    CoolAuto

    Sleep

    Timing

    Setting Defrost Environment

    Dry

    Heat

    88

    88:88

    1.Make sure

    power is supplied,

    press this button,

    unit starts work.

    2.Press this button

    to choose operate

    mode-cool

    3.Press this button

    to set fan speed 4.Press this buttonto set temperature

    Fig 8.2-1

    2) Heating operation methodas shown in fig8.2-2When Tindoor is lower than Tset, compressor start to work, and heating mode operate.

    When Tindoor is higher than Tset, compressor and fan of outdoor unit stop, only thefan of indoor unit still works.

    When heating mode is in operation, if the outdoor temperature is low and humidity

    is low, the outdoor unit will frost and then heating efficiency reduces. In such

    a case, unit will begin the defrost cycle automatically. And the controller panel

    will display Defrost.

    The set temperature range is 1630

  • 7/27/2019 NEW DUCT

    33/122

    ModeSwing

    Sleep

    Temperature adjust

    Hour

    ON/OFF

    Timing

    AM PM

    Fan speed

    Auto

    ON/OFF

    Fan speed

    Test

    88

    BlowMode

    CoolAuto

    Sleep

    Timing

    Setting Defrost Environment

    Dry

    Heat

    88

    88:88

    1.Make surepower is supplied,press this button,unit starts work.

    3.Press this button

    to set fan speed 4.Press this buttonto set temperature

    2.Press this buttonto choose operatemode-heat

    8.2-2

    3) Dry mode operation method, as shown in fig8.2-3When Tindoor is in the range of Tset,2the unit work in cool mode. When Tindoor is

    higher than Tset, the unit start to work in cool mode, and the speed of indoor unit

    fan can be adjusted.

    The set temperature range is 1630

    1.Make sure

    power is supplied,

    press this button,

    unit starts work.

    88:88

    88

    Heat

    Dry

    EnvironmentDefrostSetting

    Timing

    Sleep

    Auto Cool

    Mode Blow

    88Test

    Fan speed

    ON/OFF

    Auto

    Fan speed

    AM PM

    Timing

    ON/OFF

    Hour

    Temperature adjust

    Sleep

    SwingMode

    2.Press this button to choose

    operate mode-Dry( theindoor unit fan speed can't

    adjust under this mode).

    3.Press this buttonto set temperature

  • 7/27/2019 NEW DUCT

    34/122

    Fig. 8.2-3

    4) Auto mode operation methodas shown in figure8.2-4When the unit run in auto mode, the standard set temperature for cooling is 26, and the

    standard set temperature for heating is 20.

    ModeSwing

    Sleep

    Temperature adjust

    Hour

    ON/OFF

    Timing

    AM PM

    Fan speed

    Auto

    ON/OFF

    Fan speed

    Test

    88

    BlowMode

    CoolAuto

    Sleep

    Timing

    Setting Defrost Environment

    Dry

    Heat

    88

    88:88

    1.Make sure

    power is supplied,

    press this button,

    unit starts work.

    2.Press this button to choose

    operate mode-Auto, then

    microcomputer will choose

    operation status-coolingheatingdryingautomatically for the mostcomfortable condition.

    8.2-4

    5) Sleep mode operation method, as shown in figure8.2-5

    When the unit runs in Cool mode or Dry mode, press Sleep button and after it operates for 1

    hour, the pre-set temperature will increase by 1. After 2 hours, the pre-temperature will increase

    by another 1. Then based on this set temperature, the cool mode or Dry mode operation is

    performed.

    When the unit runs in Heat mode, press Sleep button and after it operates for 1 hour, the

    pre-set temperature will reduce by 1. After 2 hours, the pre-temperature will reduce by another 1

    . Then based on this set temperature, the Heat mode operation is performed.

  • 7/27/2019 NEW DUCT

    35/122

    ModeSwing

    Sleep

    Temperature adjust

    Hour

    ON/OFF

    Timing

    AM PM

    Fan speed

    Auto

    ON/OFF

    Fan speed

    Test

    88

    BlowMode

    CoolAuto

    Sleep

    Timing

    Setting Defrost Environment

    Dry

    Heat

    88

    88:88

    1.Make sure

    power is supplied,

    press this button,

    unit starts work.

    4.Press this button

    to set temperature

    3.Press this button

    to set fan speed

    5.Press this button,

    unit runs in sleep

    mode, and press

    once again, unit exit

    sleep mode.

    2.Press this button to

    choose operate

    mode-CoolDry orHeat.

    Fig.8.2-5

    8.3 Wire controller malfunction displayWhen there is malfunction existing in the system running, malfunction code will be displayed

    on the controller panel. The meaning of malfunction codes are as shown in table 8.3-1

    Table 8.3-1

    Malfunction code Malfunction

    E1 Compressor high pressure protection

    E2 Indoor unit anti-freezing protection

    E3 Compressor low pressure protection

    E4Compressor air discharge high temperatur

    protection

    E5 Compressor overload protection

    E6 Communication malfunction

    F0 Indoor unit tube sensor malfunction

    F1 Evaporator temperature sensor malfunction

    F2 Condensor temperature sensor malfunction

    F3 Outdoor unit tube sensor malfunction

    F4 Air discharge temperature sensor malfunction

  • 7/27/2019 NEW DUCT

    36/122

    8.4 Name and function of wire controllertype two as shown in fig 8.4-1

    Fig.8.4-1

    Composition of wire controller

    1 Timing display 10 Display of sleep mode

    2Fan speed display (auto, high speed,

    middle speed, low speed)11 Mode button

    3 Display of defrost mode 12 Button for increasing the set temperature

    4 Display of energy-saving mode 13 Button for reducing the set temperature

    5 Display of set temperature 14 Fan speed button(can set fresh air)

    6 Display of room temperature 15Button of sleep mode(for require the

    ambient temperature)

    7 Display of fresh air mode 16 Button for timing

    8Display of operation modeautomatic,

    cooling, dry, heating, fan17 ON/OFF button

    9 Display of malfunction status

  • 7/27/2019 NEW DUCT

    37/122

  • 7/27/2019 NEW DUCT

    38/122

    Auto -------- 1630

    Fan -------- No temperature setting function

    Fig.8.5-4 Fig.8.5-5 Fig.8.5-6

    8.5.4 Sleep function setting (as shown in figure 8.5-4

    When the unit runs in Cool mode or Dry mode, press Sleep button and after it operates for 1hour, the pre-set temperature will increase by 1. After 2 hours, the pre-temperature will increase

    by another 1. Then based on this set temperature, the cool mode or Dry mode operation is

    performed.

    When the unit runs in Heat mode, press Sleep button and after it operates for 1 hour, the pre-set temperature

    will reduce by 1. After 2 hours, the pre-temperature will reduce by another 1. Then based on this set

    temperature, the Heat mode operation is performed.

    8.5.5 Operation mode setting (as shown in figure 8.5-5)

    NoteThe auto mode of this air-conditioning unit can only be controlled by the wire controller but not the

    remote controller.

    If this button is pressed consecutively, the operating mode shall change as per the following sequence

    CoolingDehumidifyingFanHeatingAuto

    When the unit operates under cooling mode, the Cool word shall be displayed. Now the set temperature

    must be lower than the ambient temperature, or else, the unit shall not run in cooling mode but only in fan

    mode.

    When the unit operates under dehumidifying mode, the DRY word shall be displayed. Now the fan of

    indoor unit shall operate in low speed within a certain range of temperature. The dehumidifying effort under

    this mode is better than that under cooling mode and saves more energy.

    When the unit operates under heating mode, the Heat word shall be displayed. Now the set temperature

    must be higher than the ambient temperature, or else, the unit shall not run in heating mode but only in fan

  • 7/27/2019 NEW DUCT

    39/122

    mode.

    When the unit operates under fan mode, the Fan word shall be displayed. When the unit operates under

    auto mode, the Auto word shall be displayed and the unit shall adjust its speed automatically according to the

    ambient temperature.

    When the unit operates under heat mode and the ambient temperature is low and humidity is high, frost shall

    generate at the outdoor unit and the heating efficiency shall be decreased. When frosting happens, the unit shall

    runs in defrost mode automatically, and Defrost word shall be displayed.

    Note: The cooling only type unit does not have heat mode, and once the energy mode is set, the auto mode

    shall be invalidated.

    8.5.6 Timing setting (as shown in figure8.5-6)

    When the unit is turn off, timing start can be set; after the unit is turn on, timing turnoff can be set. Press the

    Time button, the unit enters the timing status and the word TIME flashed on the display. Now user can

    press or to increase or reduce the set time. Press the TIME button again and then the timing shall go

    into effect. Now the unit starts to count the time passed. When the unit is under timing status, you can cancel

    timing set by pressing the TIME button.

    The range of set time is between 0.5 to 24 hours.

    Fig.8-.5-7 Fig. 8.5-8 Fig.8.5-9

    8.5.7 Fresh air valve setting (as shown in figure8.5-7)

    When the unit is turn off, you can enter the fresh air setting by pressing the FAN button for 5 seconds. The

    word FRESH shall flash on the LCD and the set temperature area shall display the current fresh air setting. User

    can adjust the fresh air set by pressing the button or button.

    Definitions of the code:

    00 always turn off.

    01the unit operate continually for 60 minutes, and the fresh air valve opens for 6 minutes.

  • 7/27/2019 NEW DUCT

    40/122

  • 7/27/2019 NEW DUCT

    41/122

    the last button input, and the normal shutoff status interface shall be displayed.

    After the above setting are completed, the system shall display SAVE when the unit turn on the next time.

    Now the set temperature shall not exceed the temperature range of the energy saving setting before. For example,

    the lower cooling limit temperature is set as 23 and the upper cooling limit temperature is set as 27 for the

    energy saving temperature setting as shown in fig.8.5-8, so the cooling temperature can only be selected in the

    range of 23 to 27 by using the remote controller or the wire controller later.

    If the upper limit temperature is the same as the lower limit temperature, the system can only operate at such

    temperature under relevant modes.

    Remove of energy saving setting: To remove the energy saving setting after it takes into effect, you can

    press the FAN button and the button simultaneously for 5 consecutive seconds when the unit turn off. But

    the data set before will not be cleared but as the initial set temperature for the next energy saving setting.

    After the unit is disconnected to power supply, the energy saving setting shall be stored. The

    setting still functions when the unit is connected to power supply again.

    If the energy saving mode is set, the sleep mode and the auto mode shall be invalidated.

    8.5.9 Display of outdoor ambient temperature (as shown in figure 8.5-9)

    Under normal condition, the OUT ENV area shall only display the indoor temperature. Press the SLEEP

    button for 5 consecutive seconds when the unit is turn off or turn on, the LCD shall display OUT ENV. After

    the outdoor temperature is display for 10 seconds, the system shall return to the display interface of indoor

    temperature. Note: if the unit is not equipped with an outdoor ambient temperature sensor, the unit shall not have

    this function.

    Fig.8.5-10 Fig.8.5-11 Fig.8.5-12

    8.5.10 Power-fail memory function setting (as shown in figure8.5-10)

    Press and hold the MODE button for 10 seconds when the unit is turn off to switch set values so as to

  • 7/27/2019 NEW DUCT

    42/122

    decide if the unit operating status for shutoff status shall be memorized after a power fail. If the set temperature

    area display 01, it means the unit operating status or shutoff status shall be memorized after a power fail; 02

    means the operating status or shutoff status shall not be memorized. Press the ON/OFF button to store the set

    value and exit the setting.

    8.5.11 Debug function (as shown in figure8.5-11)

    When the unit is turn off, press the FAN button and the SLEEP button simultaneously for

    10 seconds to activate the debug menu. Now the LCD displays DEBUG. Press the MODE

    button to select setting item and the button and the button to set actual value.

    Setting of ambient temperature sensor.

    Under the debug mode, press the MODE button so as to display 01 on the set temperature area (at the

    left of the word DEBUG). The OUT ENV area (at the right of the word DEBUG) displays setting status. Now

    use the button and the button to select from the following two setting:

    The indoor room temperature is measured at the return-air intake (Now the OUT ENV area display

    01).

    The indoor room temperature is measured at the wire controller (Now the OUT ENV area display 02).

    The default room temp. sensor is located at the return-air intake.

    8.6 Malfunction display(as shown is figure.8.5-12)

    When there is malfunction in the unit operation, the word ERROR will flash on the LCD of the wire

    controller and the malfunction code will also be displayed. When there are multiple malfunction at the same time,

    the malfunction codes will be displayed on the wire controller one by one. The first digit of the code denotes the

    system number. When there is only one system, the system number will not displayed. The last two digits denote

    the detailed malfunction code. For example, the code in Fig. 8.5-11 means low pressure protection of compressor

    of system 1.

  • 7/27/2019 NEW DUCT

    43/122

    The malfunction codes definition are as follows:

    Cod Malfunction Code Malfunction

    E0 Pump malfunction F0 Malfunction of indoor room temp.

    sensor at air intake

    E1 High pressure protection of compressor F1 Malfunction of evaporator tem.

    sensor

    E2 Indoor frost-proof protection F2 Malfunction of condenser tem.

    sensor

    E3 Low pressure protection of compressor F3 Malfunction of outdoor ambient

    temperature sensor

    E4 Exhaust high temperature protection of

    compressor

    F4 Malfunction of exhaust gas

    temperature sensor

    E5 Overload protection of compressor F5 Malfunction of indoor room sensor

    at wire controller

    E6 Communication malfunction EH Malfunction of auxiliary

    E8 Indoor unit fan protection EE Buttons are locked (not malfunction)

    E9 Full water protection CC The unit is remotely monitored or

    controlled by centralized controller

    and the wire controllers function are

    invalidated (not malfunction)

  • 7/27/2019 NEW DUCT

    44/122

    1

    9.Disassembly Procedures

    9.1 Disassembly procedures for FG(R)2.6/N, FG(R)3.5/N,FG(R)5/N indoor

    unit

    Operation procedure Fig.

    1Disassemble outsidecasing plate

    1) Disassemble the filter of rear return

    air inlet

    pull out two filters of rear return air

    inlet, as shown in fig.1

    2) Disassemble side plate of rear return

    air inlet

    Screw off the fastening screw of the

    rear air return inlet, take down the side

    plate of the rear air return inlet (as shown

    in fig.2)

    3) Disassemble cover plate of return airinlet

    Screw off the fastening screw of the air

    return inlet, take down cover plate of the

    air return inlet (as shown in fig.3)

    filter of rear return air inlet

    Fig.1

    Fig. 2

    cover plate of return air inlet

    Fig. 3

  • 7/27/2019 NEW DUCT

    45/122

    2

    Operation procedure Fig.

    4) Disassemble bottom cover plate

    Screw off the fastening screw of the

    bottom cover plate, take down the bottomcover plate (as shown in fig.4)

    2Disassemble the watertray

    Screw off the fastening screw of the

    water tray, then take down the water tray

    (as shown in fig.5)

    3 Disassemble fan and

    motor1disassemble the front and rear volute

    Screw off the fastening screw of the

    front and rear volute, then take down the

    front and rear volute (as shown in fig.6)

    the bottom cover plate

    Fig. 4

    water tray

    Fig. 5

    the front and rear volute

    Fig. 6

  • 7/27/2019 NEW DUCT

    46/122

    3

    Operation procedure Fig.

    2disassemble centrifugal fan

    Screw off the fastening screw between

    the fan and motor, then take down thecentrifugal fan wheel (as shown in fig.7)

    3Disassemble the motor support frame

    Screw off the fastening screw of the

    motor support frame, then take down the

    frame (as shown in fig.8).

    Loosen the connection plug of motor

    wire in the electric box, and take down the

    motor (as shown in fig. 9)

    centrifugal fan wheel

    Fig. 7

    motor support frame

    Fig. 8

    Fig. 9

    support frame for fan

    Fig. 10

  • 7/27/2019 NEW DUCT

    47/122

    4

    Operation procedure Fig.

    4Disassemble evaporator1

    Disassemble right side plate Screw off the fastening screw of the

    right side plate, then take down the

    plate(as shown in fig.11)

    2Disassemble left side plate

    Screw off the fastening screw of the

    left side plate, then take down the

    plate(as shown in fig.12)

    3Disassemble evaporator

    Screw off the fastening screw of the

    evaporator.

    Take down the evaporator (as shown

    in fig.13)

    4Disassemble the evaporator support

    frame

    Screw off the fastening screw of the

    evaporator support frame, then take

    down the frame (as shown in fig.14).

    Fig. 11

    Fig. 12

    Fig. 13

    Fig. 14

  • 7/27/2019 NEW DUCT

    48/122

    5

    9.2 Disassembly procedures for FG(R)2.6/N, FG(R)3.5/N,FG(R)5/N outdoor

    unit

    Operation procedure Fig.

    1Disassemble outside casingplate

    1) Disassemble the front side plate

    Screw off the fastening screw of the front

    side plate

    Push the front side plate downwards.(there

    is hook behind the plate) as shown in fig. 2

    2) Disassemble the top cover plate

    Screw off the fastening screw of the top

    cover plate, then take down the plate. (asshown in fig.3)

    3Disassemble the protection grill

    Screw off the fastening screw of the

    protection grill, then take down the protection

    grill. (as shown in fig.3)

    Fig. 1

    Fig. 2

    Fig. 3

  • 7/27/2019 NEW DUCT

    49/122

    6

    Operation procedure Fig.

    4

    Disassemble the outer shellScrew off the fastening screw of the outer

    shell, then take down the shell. (as shown in

    fig.4)

    (2) Disassemble hte axial flow

    fan

    Screw off the spheric nuts fastening the

    axial flow fan, then take down the external

    gear locking ring. (as shown in fig.5)

    Take down the axial flow fan. (as shown in

    fig. 5)

    (3) Disassemble the motor of

    fan

    Screw off the fastening screw of the motor

    support frame, then take down the frame. (as

    shown in fig.6)

    Fig. 4

    Fig. 5

    Fig. 6

  • 7/27/2019 NEW DUCT

    50/122

    7

    Operation procedure Fig.

    Screw off the fastening screw between

    the motor and the motor support frame,

    then take down the motor backwards (asshown in fig.7)

    Loosen the connection plug of the

    motor wire and lead the motor wire

    through the wire hole.

    (4) Disassemble the four-way

    vale and capillary

    1. Disassemble the four-way valve

    Screw off the fastening screw on

    four-way valve for fastening the magnet

    coil.

    Take down the magnet coil.

    Unsolder welding spot between the

    four-way valve and another pipes.

    Take down the four-way valve. (as

    shown in fig. 8)

    Notes: please be careful when you the

    capillary and other pipes, make sure fire

    cant touch another parts, meanwhile, the

    valve should be packaged by wet cloth for

    fear the valve is hurt by high temperature.

    2.Disassemble the capillary

    Unsolder the two welding spot among

    the capillary and other pipes.

    Take down the capillary (as shown in

    fig. 8).

    Fig. 7

    four-way valve capillary

    Fig. 8

  • 7/27/2019 NEW DUCT

    51/122

  • 7/27/2019 NEW DUCT

    52/122

  • 7/27/2019 NEW DUCT

    53/122

    1

    9.3 Disassembly procedures for FG(R)7/N-E indoor unit

    Operation procedure Fig.

    1 Disassemble outsidecasing plate

    1) Disassemble side plate of supply-air

    outlet

    screw off the fastening bolts on the

    supply-air outlet, then take down the side

    plate of supply-air outlet. (as shown in fig

    1)

    2) Disassemble the filter of rear return

    air inlet

    pull out two filters of rear return air

    inlet, as shown in fig.2

    3) Disassemble side plate of return-airoutlet

    screw off the fastening bolts on the

    return-air outlet, then take down the side

    plate of return-air outlet. (as shown in fig

    3)

    side plate of supply-air outlet

    Fig. 1

    filter of rear return air inlet

    Fig.2

    Fig.3

  • 7/27/2019 NEW DUCT

    54/122

    2

    Operation procedure Fig.

    4) Disassemble cover plate of return air

    inlet

    Screw off the fastening screw of the airreturn inlet, take down cover plate of the

    air return inlet (as shown in fig.4)

    5) Disassemble bottom cover plate

    Screw off the fastening screw of the

    bottom cover plate, take down the bottom

    cover plate (as shown in fig 5)

    2Disassemble the water

    tray Screw off the fastening screw of the

    water tray, then take down the water tray

    (as shown in fig.6)

    cover plate of return air inlet

    Fig.4

    bottom cover plate

    Fig.5

    water tray

    Fig.6

  • 7/27/2019 NEW DUCT

    55/122

    3

    Operation procedure Fig.

    3Disassemble fan

    Screw off the fastening screw of thefan. (as shown in fig.7)

    Screw off the fastening screw between

    fan and motor, then take down the fan. (as

    shown in fig. 8)

    2Disassemble the motor support frame

    Screw off the fastening screw of the

    motor support frame. then take down the

    frame (as shown in fig. 9)

    Loosen the connection plug of motor

    wire in the electric box, and take down the

    motor (as shown in fig. 10)

    the fastening screw of the fan

    Fig.7

    fastening screw

    Fig.8

    motor support frame

    Fig.9

    Fig.10

  • 7/27/2019 NEW DUCT

    56/122

    4

    Operation procedure Fig.

    4Disassemble evaporator1

    Disassemble right side plate Screw off the fastening screw of the

    right side plate, then take down the

    plate(as shown in fig.11)

    2Disassemble left side plate

    Screw off the fastening screw of the

    left side plate, then take down the

    plate(as shown in fig.12)

    3Disassemble the pipe clamp

    Screw off the fastening screw of pipe

    clamp. (as shown in fig. 12)

    4Disassemble evaporator

    Screw off the fastening screw of the

    evaporator.

    Take down the evaporator (as shown

    in fig.13)

    5Disassemble the evaporator support

    frame

    Screw off the fastening screw of the

    evaporator support frame, then take

    down the frame (as shown in fig.13).

    Fig. 11

    Fig. 12

    Fig. 13

  • 7/27/2019 NEW DUCT

    57/122

    5

    9.4 Disassembly procedures for FG(R)7/N-E outdoor unit

    Operation procedure Fig.

    1Disassemble outside casingplate

    1) Disassemble the front side plate

    Screw off the fastening screw of the front

    side plate

    Push the front side plate downwards.(there

    is hook behind the plate) as shown in fig. 2

    2) Disassemble the top cover plate

    Screw off the fastening screw of the top

    cover plate, then take down the plate. (asshown in fig.3)

    Fig. 1

    Fig. 2

    Fig. 3

  • 7/27/2019 NEW DUCT

    58/122

    6

    Operation procedure Fig.

    3Disassemble the outer shell

    Screw off the fastening screw of the outershell, then take down the shell. (as shown in

    fig.4)

    4Disassemble the protection grill

    Screw off the fastening screw of the

    protection grill, then take down the protection

    grill. (as shown in fig.5 and fig. 6)

    protection grill

    Fig. 4

    Fig. 5

    Fig. 6

  • 7/27/2019 NEW DUCT

    59/122

    7

    Operation procedure Fig.

    (2) Disassemble axial flow fan

    Screw off the spheric nuts fastening theaxial flow fan, then take down the

    external gear locking ring. (as shown in

    fig.7)

    Take down the axial flow fan. (as

    shown in fig. 7)

    (3) Disassemble the motor of

    fan

    Screw off the fastening screw of the

    motor support frame, then take down the

    frame. (as shown in fig.8)

    spheric nuts

    Fig.7

    motor support frame

    Fig. 8

    Fig. 9

  • 7/27/2019 NEW DUCT

    60/122

    8

    Operation procedure Fig.

    Screw off the fastening screw between themotor and the motor support frame, then

    take down the motor backwards (as shown

    in fig.10)

    Loosen the connection plug of the motor

    wire and lead the motor wire through the

    wire hole.

    (4) Disassemble the four-way

    vale and capillary

    1. Disassemble the four-way valve

    Screw off the fastening screw on four-way

    valve for fastening the magnet coil.

    Take down the magnet coil.

    Unsolder the welding spot between the

    four-way valve and another pipes.

    Take down the four-way valve. (as shown

    in fig. 11)

    Notes: please be careful when you the

    capillary and other pipes, make sure

    fire cant touch another parts,

    meanwhile, the valve should be

    packaged by wet cloth for fear the

    valve is hurt by high temperature.

    2.Disassemble the capillary

    Unsolder the two welding spots among

    the capillary and other pipes.

    Take down the capillary (as shown in fig.

    12).

    Fig.10

    Fig.11

    Fig.12

  • 7/27/2019 NEW DUCT

    61/122

  • 7/27/2019 NEW DUCT

    62/122

    10

    Operation procedure Fig.

    (7) Disassemble the gas

    valve and liquid valve

    1. Disassemble the gas valve

    screw off the 2 screw bolts that

    fasten the valve.

    Unsolder the two welding spots

    between the valve and the gas return

    pipe, then take down the gas valve. (as

    shown in fig. 12)

    Notes: the valve should be packaged

    by wet cloth for fear the valve is hurt

    by high temperature when you

    unsoldering.

    2. Disassemble the liquid valve

    screw off the 2 screw bolts that

    fasten the valve.

    Unsolder the spot weld between the

    valve and the gas return pipe, then

    take down the liquid valve. (as

    shown in fig. 13)

    Notes: the valve should be packaged

    by wet cloth for fear the valve

    is hurt by high temperature

    when you unsoldering.

    Gas valve

    screw bolt

    Fig.15

    Liquid valve

    screw bolt

    Fig.16

  • 7/27/2019 NEW DUCT

    63/122

    1

    9.5 Disassembly procedures for FG(R)10/N-E, FG(R)10/N-MFG(R)12/N-MFGR16/NC-M indoor unit

    Operation procedure Fig.

    1 Disassemble outsidecasing plate

    1) Disassemble side plate of supply-air

    outlet

    screw off the fastening bolts on the

    supply-air outlet, then take down

    the side plate of supply-air outlet.

    (as shown in fig 1)

    2) Disassemble the filter of rear return

    air inlet

    pull out two filters of rear return air

    inlet, as shown in fig.2

    3) Disassemble side plate of return-airoutlet

    screw off the fastening bolts on the

    return-air outlet, then take down

    the side plate of return-air outlet.

    (as shown in fig 3)

    Fig. 1

    Fig. 2

    Fig. 3

  • 7/27/2019 NEW DUCT

    64/122

    2

    Operation procedure Fig.

    4) Disassemble cover plate of return air

    inlet Screw off the fastening screw of the

    air return inlet, take down cover plate of

    the air return inlet (as shown in fig.4)

    5) Disassemble bottom cover plate

    Screw off the fastening screw of the

    bottom cover plate, take down the bottom

    cover plate (as shown in fig 5)

    2Disassemble the watertray

    Screw off the fastening screw of the

    water tray, then take down the water tray

    (as shown in fig.6)

    Fig. 4

    bottom cover plate

    Fig. 5

    water tray

    Fig. 6

  • 7/27/2019 NEW DUCT

    65/122

    3

    Operation procedure Fig.

    3 Disassemble fan andmotor

    Screw off the fastening screw of the

    fan. (as shown in fig.7)

    2Disassemble the motor support frame

    Screw off the fastening screw of the

    motor support frame, then take down the

    frame (as shown in fig. 8)

    3Disassemble the wire plug of motor

    Loosen the connection plug of motor

    wire in the electric box, and take down the

    motor (as shown in fig. 9)

    Fig. 7

    Fig. 8

    Fig. 9

  • 7/27/2019 NEW DUCT

    66/122

    4

    Operation procedure Fig.

    4) Disassemble motor wiringLoosen the connection plug of motor,

    and lead the wire through the wire hole

    (as shown in fig.10)

    5) Disassemble the fan

    Screw off the fastening screw between

    fan and motor, then take down the fan.

    (as shown in fig. 11)

    6Disassemble the motor

    Screw off the fastening screw that

    fasten the motor, then take down the

    motor. (as shown in fig. 12)

    Fig. 10

    fastening screw

    Fig. 11

    Fig. 12

  • 7/27/2019 NEW DUCT

    67/122

    5

    Operation procedure Fig.

    4 disassemble theauxiliary electric heater

    Notice: only the heat pump (cooling

    capacity is up to 16kw) has auxiliary electric

    heater, the other type dont need this

    procedure.

    Loose the connection wire of high

    temperature protector. (as shown in

    fig.13)

    Screw off the fastening bolts for the

    auxiliary electric heater clamp.(as shown

    in fig. 14)

    Take down the connection wire of the

    auxiliary electric heater, then take down

    the auxiliary electric heater.(as shown in

    fig. 15)

    high temperature protector

    Fig. 13

    Fig. 14

    Fig. 15

  • 7/27/2019 NEW DUCT

    68/122

    6

    Operation procedure Fig.

    5Disassemble evaporator

    1Disassemble right side plate

    Screw off the fastening screw of the

    right side plate, then take down the

    plate(as shown in fig.16)

    2Disassemble the tube temperature

    sensor

    Pull out the tube temperature sensor of

    evaporator.(as shown in fig. 17)

    3Disassemble the pipe clamp

    Screw off the fastening bolts of pipe

    clamp.(as shown in fig. 18)

    Fig. 16

    tube temperature sensor

    Fig. 17

    pipe clamp

    Fig. 18

  • 7/27/2019 NEW DUCT

    69/122

    7

    Operation procedure Fig.

    4) Disassemble evaporator

    Screw off the fastening screw of theevaporator.

    Take down the evaporator (as shown

    in fig.19)

    5Disassemble the evaporator support

    frame

    Screw off the fastening screw of the

    evaporator support frame, then take

    down the frame (as shown in fig.20).

    Fig. 19

    Fig. 20

  • 7/27/2019 NEW DUCT

    70/122

  • 7/27/2019 NEW DUCT

    71/122

  • 7/27/2019 NEW DUCT

    72/122

    10

    Operation procedure Fig.

    (2) Disassemble axial flow fan

    Screw off the spheric nuts fastening theaxial flow fan, then take down the

    external gear locking ring. (as shown

    in fig.6)

    Pull out the axial flow fan. (as shown in fig.

    6)

    Fig. 5

    Fig. 6

  • 7/27/2019 NEW DUCT

    73/122

    11

    Operation procedure Fig.

    (3) Disassemble the motor of

    fan

    Screw off the fastening screw of the

    motor support frame, then take down

    the frame. (as shown in fig. 7)

    Screw off the fastening screw between

    the motor and the motor support

    frame, then take down the motor

    backwards (as shown in fig.8)

    Loosen the connection plug of the motor

    wire and lead the motor wire through the

    wire hole.

    Fig. 7

    Fig. 8

    Fig. 9

  • 7/27/2019 NEW DUCT

    74/122

    12

    Operation procedure Fig.

    (4) Disassemble the four-way

    vale and capillary

    1. Disassemble the four-way valve

    Screw off the fastening screw on

    four-way valve for fastening the magnet

    coil.

    Take down the magnet coil.

    Unsolder the four-way valve and another

    pipes.

    Take down the four-way valve. (as shown

    in fig. 10)

    Notes: please be careful when you the

    capillary and other pipes, make sure fire

    cant touch another parts, meanwhile, the

    valve should be packaged by wet cloth for

    fear the valve is hurt by high temperature.

    2.Disassemble the capillary

    Unsolder the two connected spot weld

    among the capillary and other pipes.

    Take down the capillary (as shown in

    fig. 11).

    magnet coil

    Fig. 10

    Fig. 11

  • 7/27/2019 NEW DUCT

    75/122

    13

    Operation procedure Fig.

    (5) Disassemble electric box

    Screw off the fastening screw on theelectric box, then pull it up and take down

    the electric box. (as shown in fig. 12)

    2Disassemble environment temperature

    sensor

    Pull out the environment temperature

    sensor in condenser, then take down the

    sensor with communication line. (as shown

    in fig.13 and fig. 14)

    Fig. 12

    environment temperature sensor

    Fig. 13

    Fig. 14

  • 7/27/2019 NEW DUCT

    76/122

    14

    Operation procedure Fig.

    3 Disassemble the discharge gas

    temperature sensor

    Pull out the temperature sensor on thedischarge pipe, then take down the sensor

    with communication line. (as shown in

    fig.15)

    4Disassemble high pressure switch

    Pull out the high pressure switch on the

    discharge pipe, then take down the switch

    with communication line. (as shown in

    fig.16)

    5Disassemble low pressure switch

    Pull out the low pressure switch on the

    suction pipe, then take down the switch

    with communication line. (as shown in

    fig.17)

    6) Disassemble the defrost temperature

    sensor

    Pull out the temperature sensor on the

    condenser, then take down the sensor with

    communication line. (as shown in fig.18)

    discharge gas temperature sensor

    Fig. 15

    high pressure switch

    Fig. 16

    Fig. 17

    defrost temperature sensor

    Fig. 18

  • 7/27/2019 NEW DUCT

    77/122

    15

    Operation procedure Fig.

    (6) Disassemble compressor and

    the gas-liquid separator

    1 Disassemble compressor

    Loosen the connection wire on the blinding

    post of compressor. (as shown in fig. 19)

    Loosen the fastening elastic spring and

    connection wire between the compressor and

    auxiliary electrical heater. (as shown in fig.

    20)

    Unsolder the suction pipe and discharge pipe

    of compressor. (as shown in fig. 21)

    Screw off the fastening nut on the

    compressor and take down the compressor.

    Fig. 19

    fastening elastic spring

    Fig. 20

    Fig. 21

  • 7/27/2019 NEW DUCT

    78/122

    16

    Operation procedure Fig.

    2 Disassemble the gas-liquid separator

    Screw off the fastening nut on the

    gas-liquid separator and take down theseparator.(as shown in fig. 22)

    (7) Disassemble the gas valve

    and liquid valve

    1. Disassemble the gas valve

    screw off the 2 screw bolts that fasten

    the valve.

    Unsolder the spot weld between the

    valve and the gas return pipe, then

    take down the gas valve. (as shown in

    fig. 23)

    Notes: the valve should be packaged by

    wet cloth for fear the valve is hurt

    by high temperature when you

    unsoldering.

    2. Disassemble the liquid valve

    screw off the 2 screw bolts that fasten

    the valve.

    Unsolder the spot weld between the

    valve and the gas return pipe, then

    take down the liquid valve. (as shown

    in fig. 24)

    Notes: the valve should be packaged by

    wet cloth for fear the valve is hurt

    by high temperature when you

    unsoldering.

    fastening nut

    Fig. 22

    Gas valve

    screw bolt

    Fig. 23

    Liquid valve

    screw bolt

    Fig. 24

  • 7/27/2019 NEW DUCT

    79/122

    10.Explosive view and parts detailed list

    10.1 Explosive view and parts detailed list for FG(R)2.6/N FG(R)3.5/N10.1.1 Explosive view and parts detailed list for FG(R)2.6/N(I) FG(R)3.5/N(I)

  • 7/27/2019 NEW DUCT

    80/122

    FG(R)2.6/N(I) FG(R)3.5/N(I)No Description

    Qty Part Code Qty Part Code

    1 Top Cover 1 01259051 1 01259051

    2 Evaporator Parts 1 01039051 1 01039062

    3 Liquid Inlet Pipe 1 032390521 1 036324561

    4 Collecting Gas Pipe 1 03638704 1 03639090

    5 Left Side Plate 1 01309051 1 01309051

    6 Left Support of Evaporator 1 01079055 1 01079055

    7 Seal of Connection Pipe1 1 01499051 1 01499051

    8 Seal of Connection Pipe 1 01499054 1 01499054

    9 Electric Box 1 01408627 1 01408627

    10 Room Temp Sensor 1 390000451 1 390000451

    11 Tube Temp Sensor 1 3900018717 1 3900018717

    12 Main PCB2 1Heat pump:30224405

    Cooling only:302244031

    Heat pump: 30224405

    Cooling only: 30224403

    13 Transformer SC39 1 43110209 1 43110209

    14 Remote Controller ZY512A 1 305050031 1 305050031

    15 Capacitor 1 33010020 1 33010027

    17 Terminal Board 1 420111562 1 420111562

    18 Isolation plate C 1 70410523 1 70410523

    19 Wire Clamp 3 71010102 2 71010102

    20 Terminal Board 2-8 2 42011103 2 42011103

    21 Hook 2 02112446 2 02112446

    22 Right Side Plate 1 01309055 1 01309055

    23 Right Support Frame of Evaporator 1 01079056 1 01079056

    24 Hook 2 02112446 2 02112446

    25 Water Tray 1 01279051 1 01279051

    26 Fan Fixed Plate 1 01339095 1 01339062

    27 Motor Support Frame 2 01709058 2 01709058

    28 Fan parts 1 150024011 1 150024011

    29 Motor FG20C 1 15019053 1 15019522

    30 Fan parts 1 150024011 1 150024011

    31 Bottom Cover 1 01259086 1 01259055

    32 Bottom Cover parts 1 01259054 1 01259054

    33 Cover of Air-return inlet 1 01259056 1 01259056

    34 Side Plate of Air-return inlet 1 01499055 1 01499055

    35 Display Panel 1Heat pump: 30294403

    Cooling only: 302944021

    Heat pump:30294403

    Cooling only:30294402

  • 7/27/2019 NEW DUCT

    81/122

    10.1.2 Explosive view and parts detailed list for FG(R)2.6/N(O), FG(R)3.5/N(O)

  • 7/27/2019 NEW DUCT

    82/122

    FG(R)2.6/N(O) FG(R)3.5/N(O)NO Description

    Qty Part Code Qty Part Code

    1 Panel Grill 1 22413431 1 22413431

    2 Front side plate 1 01533012 1 01533012

    3 Axial Flow Fan 1 10333413 1 103334134 Motor FW30K 1 15013067 1 15013066

    5 Motor Support Frame 1 01703069 1 01703069

    6 Condenser Parts 1 011032023 1 011032002

    7 Top Cover 1 01253443 1 01253443

    8 Protection Grill 1 01473030 1 01473030

    9Capacitor CBB65

    22.5uF/450V(VDE/TUV)1 33000002 1 33000017

    10 Electric Box 1 01409070 1 01409070

    11 Isolation Plate D 1 70410525 1 70410525

    12 4-way Valve 1430004021

    Only for FGR2.6/N(O)1

    430004021

    Only for FGR3.5/N(O)

    13 Wire Clamp 1 71010103 1 71010103

    14 Discharge Pipe 1Heat pump: 03613129

    Cooling only: 036131281

    Heat pump:03613105

    Cooling only:03619081

    15 Right Side Plate 1 01302004 1 01302004

    16 Handle 1 26233433 1 26233433

    17 Valve (R407C) # 1 07100134 1 07100149

    18 Valve Support Frame 1 01713041 1 01713041

    19 Compressor and parts 1 00100355 1 00100352

    20 Isolation plate 1 01239052 1 01239052

    21 Bottom plate 1 01213429 1 01203008

    22 Temp sensor 13900012125

    Only for FGR2.6/N(O)1

    3900012125

    Only for FGR3.5/N(O)

    23 Main PCB1 1Heat pump:30224404

    Cooling only: 302244021

    Heat pump:30224404

    Cooling only:30224402

    24 Transformer SC39 1 43110209 1 43110209

    25 Terminal Board (2 bit) 1 420111531 1 420111531

    26 AC Contactor CJX9B-25S/D 1 44010245 1 44010245

    27 Terminal Board 2-8 142011103

    Only for FGR2.6/N(O)1

    42011103

    Only for FGR3.5/N(O)

    28 4-way Valve parts 1430004002

    Only for FGR2.6/N(O)1

    430004002

    Only for FGR3.5/N(O)

    29 Capacitor 1 33010026 1 33010027

    30 Valve (R407C) # 1 07100135 1 07100133

    31 Overload Protector for compressor 1 Fitting parts for compressor 1 Fitting parts for compressor

    32 Compressor Gasket 3 Fitting parts for compressor 3 Fitting parts for compressor

  • 7/27/2019 NEW DUCT

    83/122

  • 7/27/2019 NEW DUCT

    84/122

    FG(R)5/N(I)No. Description

    Qty Part Code

    1 Top Cover 1 01259064

    2 Evaporator Parts 1 01038623

    3 Liquid Inlet Pipe 1 032391094 Collecting Gas Pipe 1 03639072

    5 Left Side Plate 1 01308668

    6 Left Support Frame of Evaporator 1 01078629

    7 Seal of Connection Pipe1 1 01498640

    8 Seal of Connection Pipe2 1 01498644

    9 Electric Box 1 01409204

    10 Tube Temp Sensor 1 3900018717

    11 Room Tube Temp Sensor 1 390000451

    12 Main PCB2 1 Heat pump: 30224405Cooling only30224403

    13 Transformer SC39 1 43110209

    15Capacitor CBB61 4F/450V

    133010011

    17 Terminal Board (5 bits) 1 420111562

    18 Isolation plate C 1 70410523

    19 Wire Clamp 2 71010102

    20 Terminal Board 2-8 1 42011103

    21 Hook 2 0211246622 Right Side Plate 1 01308670

    23 Right Support Frame of Evaporator 1 01078625

    24 Hook 2 02112466

    25 Water Tray 1 01278633

    26 Fan Fixed Plate 1 01339058

    27 Remote Controller ZY512A 1 305050031

    28 Motor Parts 1 15002401

    29 Motor FG70B 1 15018322

    30 Motor Parts 1 15002401

    31 Display Panel 1Heat pump: 30294403

    Cooling only: 30294402

    32 Bottom Cover 1 01258649

    33 Cover of Air-return inlet 1 01258650

    34 Side Plate of Air-return inlet 1 01499061

    35 Air-return inlet parts 1 01498641

  • 7/27/2019 NEW DUCT

    85/122

    10.2.2 Explosive view and parts detailed list for FG(R)5/N(O)

  • 7/27/2019 NEW DUCT

    86/122

  • 7/27/2019 NEW DUCT

    87/122

  • 7/27/2019 NEW DUCT

    88/122

    FG(R)7/N-EINo Description

    Qty Part Code

    1 Top Cover 1 01258651

    2 Evaporator Parts 1 010086281

    3 Left Side Plate 1 01308676

    4 Left Support Frame of Evaporator 101078603

    5 Seal of Connection Pipe1 1 01308680

    6 Seal of Connection Pipe 2 1 01498610

    7 Electric Box 1 01408628

    8 Room Temperature Sensor 1 390000451

    9 Tube Temperature Sensor 1 3900018717

    10 Main PCB2 Z4415_M 1 30224403

    11 Transformer SC39 1 43110209

    12 Capacitor CBB61 8F/450V 1 33010014

    13 Terminal Board 2-8 2 42011103

    14 Terminal Board (3 bits) 1 420111591

    15 Isolation Plate C 1 70410523

    16 Wire Clamp 2 71010102

    17 Right Side Plate 1 01308677

    18 Right Support Frame of Evaporator 101078604

    19 Water Tray 1 01278612

    20 Fan Fixed Plate 1 01338631

    21 Fan (right)SYP-200/190J-1 1 15018604

    22 Motor FG150B 1 15018612

    23 Fan (left)SYP-200/190J-1 115018603

    24 Bottom Cover 1 012586121

    25 Cover of Air-return inlet 1 01258614

    26 Side Plate of Air-return inlet 1 01499074

    27 Side Plate of Air-supply outlet 1 0149861228 Hook 4 02118504

    29 Remote controller ZY512A 1 305050031

    30 Display Panel Z44351_M 1Heat pump: 30294403

    Cooling only:30294402

    31 Capillary 3 81020149

  • 7/27/2019 NEW DUCT

    89/122

    10.3.2 Explosive view and parts detailed list for FG(R)7/N-E(O)

    10 9 8

    1

    3

    2

    4

    1711

    7

    20

    19

    18

    13

    12

    5

    6

    14

    15

    16

  • 7/27/2019 NEW DUCT

    90/122

    FG(R)7/N-E(O)No Description

    Qty Part Code

    1 Panel Grill 1 22265251

    2 Front side plate 1 01435254

    3 Protection Grill 1 01475252

    4 Top Cover 1 01255262

    5 Back Side Plate 1 01305261

    6 Handle 2 26235253

    7 Valve Support Frame 1 01715001

    8 Bottom cover 1 01203066

    9 Front Side Plate 1 01305247

    11 Axial Flow Fan 1 10335253

    12 Condenser Parts 1Heat pump: 01109063

    Cooling only: 01103468

    13 Motor Support Frame 1 01705252

    14 Motor FW60T 1 15013703

    15 Isolation Plate 1 01235253

    16 4-way Valve 1430004031

    Only for FGR7/N-E(O)

    17 Compressor C-RN220H5B 1 00100063

    18 Gas Valve 1 07105007

    19 Liquid Valve 1 07105002

    20 Temp Sensor 13900012125

    Only for FGR7/N-E(O)

    21 Electric Box 1 01409092

    22 Terminal Board (4 bits) 1 42011201

    23 Transformer SC39 1 43110209

    24 Terminal Board 2-8 1 42011103

    25 Main PCB1 Z4435_M 1 30224404

    26 Capacitor CBB61 3.0F/450V 1 33010027

    27 AC Contactor CJX9B-25S/01 1 44010222

    28 Capacitor CBB65 40F/440V 1 33000022

    29 Capacitor Clamp 1 02143401

    30 Isolation plate D 2 70410523

    31 Wire Clamp 2 71010102

    32 4-way Valve1

    430004002

    Only for FGR7/N-E(O)

    33 Compressor Gasket 527-0116-00 4 Fitting parts for compressor

  • 7/27/2019 NEW DUCT

    91/122

    10.4 Explosive view and parts detailed list for FG(R)10/N-EFG(R)10/N-MFG(R)12/N-M10.4.1 Explosive view and parts detailed list for FG(R)10/N-EIFG(R)10/N-MIFG(R)12/N-MI

  • 7/27/2019 NEW DUCT

    92/122

    FG(R)10/N-EI FG(R)10/N-MI FG(R)12/N-MINo Description

    Qty Part Code Qty Part Code Qty Part Code

    1 Top Cover 1 01258606 1 01258606 1 01258606

    2 Evaporator Parts 1 01009069 1 01009060 1 010090603 Left Side Plate 1 01308676 1 01308676 1 01308676

    4 Left Support Frame of Evaporator 1 01078603 1 01078603 1 01078603

    5 Seal of Connection Pipe 1 1 01308672 1 01308672 1 01308672

    6 Seal of Connection Pipe 2 1 01498601 1 01498601 1 01498601

    7 Electric Box 1 01408628 1 01408628 1 01408628

    8 Room Temperature Sensor 1 3900012123 1 3900012123 1 3900012123

    9 Tube Temperature Sensor 1 3900018717 1 3900018717 1 3900018717

    10 Main PCB2 Z4435_M 1

    Heat pump:

    30224405

    Cooling only:

    30224403

    1

    Heat pump:

    30224405

    Cooling only:

    30224403

    1

    Heat pump:

    30224405

    Cooling only:

    30224403

    11 Transformer SC39 1 43110209 1 43110209 1 43110209

    12 Capacitor CBB61 8F/450V 1 33010014 1 33010014 1 33010014

    13 Capacitor CBB61 5F/450V(TUV/VDE) 1 33010064 1 33010064 1 33010064

    14 Terminal Board 2-8 2 42011103 2 42011103 2 42011103

    15 Terminal Board (3 bits) 1 420111591 1 420111591 1 420111591

    16 Isolation Plate C 1 70410523 1 70410523 1 70410523

    17 Wire Clamp 2 71010102 2 71010102 2 71010102

    18 Right Side Plate 1 01308677 1 01308677 1 01308677

    19 Left Support Frame of Evaporator 1 01078604 1 01078604 1 01078604

    20 Water Tray 1 01278620 1 01278620 1 01278620

    21 Fan Fixed Plate 1 01338630 1 01338630 1 01338630

    22 Fan (right)SYP-200/190J 1 15019058 1 15019058 1 15019058

    23 Motor FG150B 1 15018612 1 15018612 1 15018612

    24 Fan (left)SYP-200/190J 2 15019059 2 15019059 2 15019059

    25 Motor FG75B 1 15018613 1 15018613 1 15018613

    26 Bottom Cover 1 01258604 1 01258604 1 01258604

    27 Cover of Air-return inlet 1 01258602 1 01258602 1 01258602

    28 Side Plate of Air-return inlet 1 01499066 1 01499066 1 01499066

    29 Side Plate of Air-supply outlet 1 01498607 1 01498607 1 01498607

    30 Hook 4 02118504 4 02118504 4 02118504

    31 Remote Controller ZY512A 1 305050031 1 305050031 1 305050031

    32 Display Panel Z44351_M 1

    Heat pump:

    30294403

    Cooling only:

    30294402

    1

    Heat pump:

    30294403

    Cooling only:

    30294402

    1

    Heat pump:

    30294403

    Cooling only:

    30294402

    33 Capillary 5 81020069 5 81020069 5 81020069

  • 7/27/2019 NEW DUCT

    93/122

    10.4.2 Explosive view and parts detailed list for FG(R)10/N-EOFG(R)10/N-MOFG(R)12/N-M(O)

    FG(R)10/N-EO FG(R)10/N-MO FG(R)12/N-MONo. Description

    Qty Part Code Qty Part Code Qty Part Code

    1 Panel Grill 2 22265251 2 22265251 2 22265251

    2 Front side plate 1 01435433 1 01435433 1 01435433

    3 Protection Grill 1 01475432 1 01475432 1 01475432

    4 Top Cover 1 01255262 1 01255262 1 01255262

  • 7/27/2019 NEW DUCT

    94/122

  • 7/27/2019 NEW DUCT

    95/122

    10.5 Explosive view and parts detailed list for FGR16/NC-M

    10.5.1 Explosive view and parts detailed list for FGR16/NC-M(I)

  • 7/27/2019 NEW DUCT

    96/122

    FGR16/NC-M(O)No Description

    Qty Part Code

    1 Top Cover 1 01259074

    2 Evaporator Parts 1 01039057

    3 Gas Piping Parts 1 036390794 Left Side Plate 1 01309060

    5 Left Support Frame of Evaporator 1 01079067

    6 Seal of Connection Pipe 1 1 01308672

    7 Seal of Connection Pipe 2 1 01498601

    8 Electric Box 1 01418601

    9 Room Temp Sensor 1 3900018717

    10 Tube Temp Sensor 1 3900012123

    11 Main PCB2 Z4435_M 1 30224405

    12 Display Panel 1 Z443513 1 30294407

    13 Transformer SC39 1 43110209

    14 Capacitor CBB61 (1A) 10F/450V AC 1 33010056

    15 Capacitor CBB61 5F/450V(TUV/VDE) 1 33010064

    16 AC Contactor 1 44010199

    17 Terminal Board (5 bits) 1 420111563

    18 Isolation Plate F 1 70410524

    19 Wire Clamp 3 71010102

    20 Terminal Board 2-8 2 42011103

    21 Hook 2 02118504

    22 Right Side Plate 1 01309063

    23 Left Support Frame of Evaporator 1 01079068

    24 Hook 2 02118504

    25 Water Tray 1 01279065

    26 Fan Fixed Plate 1 01339065

    27 Fan Support Frame 2 01709060

    28 Fan (right) 1 15018604

    29 Motor FG180A 1 15019056

    30 Fan (left) 2 15018603

    31 Motor FG80A 1 15019057

    32 Bottom Cover 1 01259071

    33 Cover of Air-return inlet 1 01259073

    34 Side Plate of Air-return inlet 1 01499068

    35 Side Plate of Air-supply outlet 1 01499070

    36 Electric Heater 3 32018614

    37 Electric Heater Support Frame 1 01228635

    38 Electric Heater Fixer 3 01222401

    39 Signal Control wire 1 401101403

    40 Capillary Parts (Cooling) 1 03009063

    41 Capillary Parts (Heating) 1 030090632

  • 7/27/2019 NEW DUCT

    97/122

    10.5.2 Explosive view and parts detailed list for FGR16/NC-M(O)

  • 7/27/2019 NEW DUCT

    98/122

    FGR16/NC-M(O)No Description

    Qty Part Code

    1 Support leg 2 01795251

    2 Bottom cover 1 01205472

    3 Valve Support Frame 1 017152564 Compressor 1 00100176

    5 Compressor Gasket 4 76710219

    6 Condenser Parts 1 01109064

    7 Gas-Liquid Separator 1 07225479

    8 Motor Support Frame 1 01705472

    9 Motor 2 15015451

    10 Axial Flow Fan 2 10335253

    11 4-way Valve 1 430004051

    12 4-way Valve Parts 1 430004005

    13 Electrical Box 1 01419056

    14 Isolation Plate 1 01235473

    15 Liquid Valve 1 07103457

    16 Gas Valve 1 07103456

    17 Back Side Plate 1 01305434

    18 Protection Grill 1 01475431

    19 Protection Grill Gasket 1 76315251

    20 Front Side Plate 1 01305431

    21 Front Plate 1 01435432

    22 Front Grill 2 22265251

    23 Top Cover 1 01255472

    24 Handle 3 26235252

    25 Overload Protector for compressor 1 46020103

    26 Capacitor of Fan 2 33010013

    27 Terminal Board (4 bits) 1 42011044

    28 Terminal Board 2-8 2 42011103

    29 AC Contactor 1 44010213

    30 Transformer SC39 1 43110209

    31 Phase Reverse Protector 1 46020052

  • 7/27/2019 NEW DUCT

    99/122

    11. Maintenance

    11.1 Clean the air filter1) Take down the air filter before clean it, or else it will cause malfunction.2) If there is too much dust in air conditioner operation environment, you should

    clean the filter more frequently.(usually every two weeks one time)

    Notice: Before you clean the filter, you should pay attention to some item as

    follows:

    a) Cut off all the power supply before you contact the wiring device.

    b) Turn off the air conditioner and cut off the power supply before you clean

    the air conditioner, or else you maybe get an electric shock or be hurt.

    c) Dont clean the air conditioner with water, or else you maybe get an electric

    shock.

    d) Take care when you clean the air conditioner, and please use steady platform.

    11.2 Maintenance before the operation season1) Check whether the inlet and outlet of the indoor and that of outdoor units are blocked

    2) Check whether the earth lead is reliable.

    3) Check whether the connection of wire is appropriate.

    4) Check whether there is word appear on the display panel of wired controller when the power is on.

    Notice: Once there is any abnormity of the units, please contact the service people after sale to supply help.

    11.3 Maintenance after usage season1) When it is fine, operate the unit in the air supply mode for half a day to dry the inside of the unit

    2) If the air conditioner is not used for a long time, shut down the power to save energy. After the power is off,

    texts on the wired controller display panel will disappear.

  • 7/27/2019 NEW DUCT

    100/122

    12. Instruction of Unit Installation

    12.1 The installation accessory list, as shown in table 12.1-1

    Table 12.1-1

    Name Qty. Remark

    Specification for usage and

    installation1

    gas pipe insulation material 1 use for connecting to gas pipe of indoor unit

    liquid pipe insulation material 1use for connecting to liquid pipe of indoor

    unitcondensate water drainage pipe

    insulaiton material2

    use for packing the condensate water pipe and

    latex plug

    nut with gasket M8 8 use for fastening the hook

    nut with gasket M10 4

    nut and spring gasket 44 sets, for hanging on the indoor unit

    hook 4 use for hanging on the indoor unit

    electric coil 4 or 8 nos. 2HP type:4nos.;others:8 nos.

    wired controller 1

    remote controller 1

    battery 2

    corrugated pipe 0,2 or 4 piece2HP type:0 piece;2.53HP type:2 piece4

    5HP:4 piece

    connection wire 23 piece 45HP type:3 piece; others:2 piece

    12.2 Dimension requirement of the installation space of indoor unit, as shown in fig. 12.2-1

  • 7/27/2019 NEW DUCT

    101/122

    (a) indoor unit

    boutdoor unit

    Fig. 12.2-1

    12.3 Installation of indoor unit

    12.3.1 Selection of installation site

    1) Ensure the top hanging piece has strong strength to withstand the weight of unit.2) It is convenient for draining the condensate water.

    3) There is no obstacle blocking the air intake and exhaust outtake, so as to ensure appropriate

    air circulation.

    4) The installation spaces required by the above drawing must be ensured, so as to provide

    enough space for the service and maintenance.

    5) The installation site must be far away from heat source, leakage of inflammable gas or

    smoke.

    6) The indoor unit is of ceiling mount(indoor unit is hidden inside the ceiling).

  • 7/27/2019 NEW DUCT

    102/122

    7) The indoor and outdoor units, the power cable and the connecting electrical wiring must be

    at least 1 meter from any TV set or radio. This is to avoid image interference or noise of the

    TV set or radio. (Even if the distance is 1 meter, noise can also exist if there is strong

    electric wave.)

    12.3.2 Installation of indoor unit

    1) Installation of expansion bolt

    Drill 4 hole (diameter is about 10mm) on the ceiling, the distance between every hole is refer

    to the fig. 3-1. then insert a M10 expansion bolt into the hole, and drive a nail into the bolt,

    as shown in fig. 12.3-1

    Fig.12.3-1 Fig.12.3-2

    2) Install the hanger onto the indoor unit, as shown in fig. 12.3-2

    3) Install the indoor unit at the ceiling, as shown in fig. 12.3-3

    48mm

    12.3-3

    4) Level check of the indoor unitAfter the indoor unit is installed, it is required to be check the level of the whole unit, so that

  • 7/27/2019 NEW DUCT

    103/122

    the whole unit is placed horizontally, as shown in fig.

    12.3-4.

    Fig. 12.3-4

    12.3.3 Installation of duct

    1) Installation of rectangular duct, as shown in fig.12.3-5

    2

    4

    3

    1

    5 7

    63

    No. Name No. Name

    1 Hanger 5 Filter

    2 Air return duct 6 Main air supply duct3 Canvas air duct 7 Air outtake

    4 Air intake

    Fig.12.3-5

    2) Installation of circular duct, as shown in fig.12.3-6

  • 7/27/2019 NEW DUCT

    104/122

    4

    3

    2

    5

    1

    876 9

    No. Name No. Name

    1 Hanger 6 Transition duct

    2 Air return duct 7 Air supply duct

    3 Canvas air duct 8 Diffuser

    4 Air return grill 9 Diffuser joint

    5 Air intake

    Fig.12.3-6

    Notice: The above two fig are only show the installation of rear air back type, but in fact, you also

    can adopt nether air back type according to actual demand, and the installation of two type are

    similar; among all the air outtake, one outtake must be opened; and you also can adopt the

    circular air duct type in which the air will be supplied by circular flexible conduit to rooms;

    and the air-supply duct and air-return duct are all need be covered by insulation material.

    12.3.4 Installation of fresh air duct( only for the high static pressure type whose cooling

    capacity is up to 6000W).

    1) Before connect the fresh air duct, you should cut off the baffle plate for fresh air first, as shown

    in fig.12.3-7a. if you dont use the fresh air duct, please seal the gap at fresh air baffle plate

    with sponge.

    2) Install circular flange for connecting the fresh air duct, as shown in fig.12.3-7(b).

    3) The duct and circular flange are all need be sealed and insulated well.

    4) The fresh air is the clean air that have been filtered by air filter.

  • 7/27/2019 NEW DUCT

    105/122

    (a) (b)

    Fig.12.3-7

    12.3.5 Installation of air-return duct1) When the unit leave factory, the rectangular flange is acquiescently installed at the backside of

    unit and the air-return cover is installed at the bottom of unit, as shown in fig.12.3-8.

    Fig. 12.3-8

    2) If you adopt nether air back type, you only need change the position of rectangular flange and

    air-return plate.

    3) Connect one end of the air-return duct to the air-return intake of indoor unit with rivetthe other

    end is connected to air-return grill. For adjusting the height freely, you can make a length of

    canvas duct which is strengthened by 8# iron wire and shaped rugous duct. You can adopt

    optimum installation mode according to the situation of building and maintenance, as shown in

    fig.12.3-9.

  • 7/27/2019 NEW DUCT

    106/122

  • 7/27/2019 NEW DUCT

    107/122

    installation is ad