April 6, 2016
Hohmann & Barnard, Inc. 30 Rasons Court Hauppauge Hauppauge, New York 11788 [email protected] RE: Summary Letter on Fire Performance of Polymer Based Brick-ties Exterior Wall Systems for Project F4749.01-121-24. To Whom It May Concern,
This letter is in response to a request for a summary a full scale fire performance test of polymer based brick-ties used in an exterior wall systems by Intertek-Architectural Testing. The core wall components (steel framing, interior and exterior gypsum) were supplied by Intertek-ATI. All other exterior assembly components were provided by the client and Intertek-ATI accepts no responsibilities of any inaccuracies therein. This letter does imply certification of the products by Intertek-ATI. Test Method: Intertek-ATI performed tests on exterior wall systems in accordance with a modified version of NFPA 285-12, Standard Fire Test Method for Evaluation of Fire Propagation Characteristics of
Exterior Non-Load Bearing Wall Assemblies Containing Combustible Components. Modifications included limited instrumentation data, smaller system dimensions, and the observation of anchor integrity.
Test Observations: Test Assembly #1:
Time (min:sec) Observations 00:00 Ignition of the room burner. 02:00 Ignition of the interior gypsum. 05:00 Ignition of the window burner. 15:00 No observations from exterior surface. 30:00 Burners Extinguished.
Post-Test
After the burners were extinguished, the window opening header flashing was removed and the wall assembly was exposed to additional fire exposure from the room burner. The duration of the exposure was also 30 minutes with the calibrated gas flows from the room burner. At the completion of the exposure, it was observed that the “all plastic” thermal wing melted while the steel reinforced thermal wing remained intact. See Photos 6 & 7 in Appendix B.
Summary Letter Project: F4749.01-121-24 Date: 4/06/2016
Test Assembly Construction: Test Assembly #1:
Interior Sheathing – 5/8” Type X Gypsum Board Steel Framing – 3-5/8” 20 Gauge Galvanized Steel Framing Floorline Safing – None Utilized Exterior Insulation – 2” thick Roxul mineral wool insulation Exterior Sheathing – 5/8 inch thick National Gypsum eXP Sheathing Air/Vapor Barrier – None Utilized Exterior Cladding Attachment – Every 24 inches vertically and 16 inches horizontally,
both Hohmann & Barnard 2 Seal Thermal Wing Nut anchors with Hohmann & Barnard 4 inch ties along with nonspecific plastic thermal masonry anchors with 4 inch long metal ties were installed side by side and were fastened through the insulation, through the sheathing, and fastened to the steel studs.
Exterior Cladding System – 3-5/8 in. x 2-1/4 in. x 7-5/8 in. Grade “A” bricks were used for the exterior cladding. The bottom row rested on the level surface of A 4 in. x 4 in. x 1/4 in. thick floating steel lintel at a distance of 2 in. from the exterior surface of the insulation. A mixture of Type S Mortar and Masonry Sand was used for all mortar joints.
130 Derry CourtYork, PA 17406
p. 717.764.7700f. 717.764.4129
www.archtest.com www.intertek.com/building
Summary Letter Project: F4749.01-121-24 Date: 4/06/2016
This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen(s) tested. This report may not be reproduced, except in full, without the written approval of Intertek-ATI. For INTERTEK-ATI: __________________________________ ____________________________________ Ethan Grove Matthew Freeborn Project Manager – Fire Testing Manager – Fire Testing EJG:ddr Appendix-A: Graphical Data (1) Appendix-B: Photographs (4) Appendix-C: Drawings (1)
130 Derry CourtYork, PA 17406
p. 717.764.7700f. 717.764.4129
www.archtest.com www.intertek.com/building
Summary Letter Project: F4749.01-121-24 Date: 4/06/2016
Appendix A
Graphical Data
130 Derry CourtYork, PA 17406
p. 717.764.7700f. 717.764.4129
www.archtest.com www.intertek.com/building
Summary Letter Project: F4749.01-121-24 Date: 4/06/2016
Graph No. 1
Air Cavity TC Data (First 30 Minutes)
Graph No. 2
Air Cavity TC Data (Second 30 Minutes)
0
100
200
300
400
500
600
700
00:00 05:00 10:00 15:00 20:00 25:00 30:00
Tem
pe
ratu
re °
F
Time (Min:Sec)
T/C 1- 1 Ft.
T/C 2- 2 Ft.
T/C 3-3 Ft.
0
200
400
600
800
1000
1200
1400
00:00 05:00 10:00 15:00 20:00 25:00 30:00
Tem
pe
ratu
re °
F
Time (Min:Sec)
T/C 1- 1 Ft.
T/C 2- 2 Ft.
T/C 3-3 Ft.
130 Derry CourtYork, PA 17406
p. 717.764.7700f. 717.764.4129
www.archtest.com www.intertek.com/building
Summary Letter Project: F4749.01-121-24 Date: 4/06/2016
Appendix B
Photographs
130 Derry CourtYork, PA 17406
p. 717.764.7700f. 717.764.4129
www.archtest.com www.intertek.com/building
Summary Letter Project: F4749.01-121-24 Date: 4/06/2016
Photo No. 1
Anchor Installation
Photo No. 2
Anchor Installation
130 Derry CourtYork, PA 17406
p. 717.764.7700f. 717.764.4129
www.archtest.com www.intertek.com/building
Summary Letter Project: F4749.01-121-24 Date: 4/06/2016
Photo No. 3
Complete Test Sample
Photo No. 4
Beginning of Test
130 Derry CourtYork, PA 17406
p. 717.764.7700f. 717.764.4129
www.archtest.com www.intertek.com/building
Summary Letter Project: F4749.01-121-24 Date: 4/06/2016
Photo No. 5
Test #2 End of First 30 Minute Exposure
Photo No. 5
Air Cavity during Second Exposure
130 Derry CourtYork, PA 17406
p. 717.764.7700f. 717.764.4129
www.archtest.com www.intertek.com/building
Summary Letter Project: F4749.01-121-24 Date: 4/06/2016
Photo No. 6
Brick Anchors and Ties (After Exposures)
Photo No. 7
Brick Anchors and Ties (After Exposures)
130 Derry CourtYork, PA 17406
p. 717.764.7700f. 717.764.4129
www.archtest.com www.intertek.com/building
Summary Letter Project: F4749.01-121-24 Date: 4/06/2016
Appendix C
Drawings
130 Derry CourtYork, PA 17406
p. 717.764.7700f. 717.764.4129
www.archtest.com www.intertek.com/building
CL
CL
20 Gauge, 3-5/8 inch thick steel track
20 Gauge, 3-5/8 inch thick steel studs
Typical 5/8 inch Exterior Gypsum SeathingTypical Cored Brick
Typical Mortar Joint
H&B and Additional Anchors and Ties (side x side)
Typical 4x4 angle lintel piece
16 inches on center
36 inches
124 inches
Double stud every 16 inches
2"Mineral Wool Inulation