T Check Valve Circulator Pressure Relief Valve Expansion Tank Aquastat Full-port Ball Valve Mixing Valve Storage Vessel DHW Circulator w/Aquastat & Check Valve These drawing are intended as a guide only and not as a replacement for professionally engineered project drawings. These concept system drawings do not imply compliance with local building codes. Actual installations may vary depending on installation location & parameters and it must be done in accordance with all local building codes. Verify with Guide Only NPE Series Application Drawings C H G NPE-240S C H G NPE-210S C H G NPE-180S 20 Goodyear Irvine, CA 92618 800-519-8794

NPE Series Application Drawings · 2016. 1. 30. · 1. Use Navien Cord P #30011612A 2. Set DIP Switches on Integrated Controller #1 – OFF, #2 – OFF, #3 – ON 3. Select External

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: NPE Series Application Drawings · 2016. 1. 30. · 1. Use Navien Cord P #30011612A 2. Set DIP Switches on Integrated Controller #1 – OFF, #2 – OFF, #3 – ON 3. Select External

T

Check Valve Circulator

Pressure

Relief

Valve Expansion

Tank

AquastatFull-port

Ball Valve

Mixing

Valve

Storage

Vessel

DHW Circulator

w/Aquastat & Check Valve

These drawing are intended as a guide only and not as a replacement for professionally engineered project drawings. These concept system drawings do not imply compliance with local building codes. Actual installations may vary depending on installation location & parameters and it must be done in accordance with all local building codes. Verify with

Guide Only

NPE Series Application Drawings

CHG

NPE-240S

CHG

NPE-210S

CHG

NPE-180S

20 GoodyearIrvine, CA 92618

800-519-8794

Page 2: NPE Series Application Drawings · 2016. 1. 30. · 1. Use Navien Cord P #30011612A 2. Set DIP Switches on Integrated Controller #1 – OFF, #2 – OFF, #3 – ON 3. Select External

20 GoodyearIrvine, CA 92618

800-519-8794www.Navien.com T

Check Valve Circulator

PressureReliefValve Expansion

Tank

AquastatFull-portBall Valve

Mixing Valve

StorageVessel

DHW Circulatorw/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.This concept system drawing does not imply compliance with local building codes. Actual installation may vary depending on installation location & parameters and it must be done in accordance to all local building codes. Verify with local building officials before commencement of system installation.

Drawn By: B. Fenske NPE-S-1-BF02 August 1, 2013

One NPE-S Tankless(Includes NPE-A, Internal Circulation Mode)

NPE-S Series Tankless Water Heater

CHG

Gas

Domestic Cold Water

CondensateDomestic Hot Water

Page 3: NPE Series Application Drawings · 2016. 1. 30. · 1. Use Navien Cord P #30011612A 2. Set DIP Switches on Integrated Controller #1 – OFF, #2 – OFF, #3 – ON 3. Select External

20 GoodyearIrvine, CA 92618

800-519-8794www.Navien.com T

Check Valve Circulator

PressureReliefValve Expansion

Tank

AquastatFull-portBall Valve

Mixing Valve

StorageVessel

DHW Circulatorw/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.This concept system drawing does not imply compliance with local building codes. Actual installation may vary depending on installation location & parameters and it must be done in accordance to all local building codes. Verify with local building officials before commencement of system installation.

Drawn By: B. Fenske NPE-S-2-I-BF02 August 1, 2013

Two NPE-S Tankless (Includes NPE-A Internal Circulation Mode)

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater

CHG

Gas

Domestic Cold Water

Condensate

CHG

Domestic Hot Water

CommunicationCable

Page 4: NPE Series Application Drawings · 2016. 1. 30. · 1. Use Navien Cord P #30011612A 2. Set DIP Switches on Integrated Controller #1 – OFF, #2 – OFF, #3 – ON 3. Select External

20 GoodyearIrvine, CA 92618

800-519-8794www.Navien.com T

Check Valve Circulator

PressureReliefValve Expansion

Tank

AquastatFull-portBall Valve

Mixing Valve

StorageVessel

DHW Circulatorw/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.This concept system drawing does not imply compliance with local building codes. Actual installation may vary depending on installation location & parameters and it must be done in accordance to all local building codes. Verify with local building officials before commencement of system installation.

Drawn By: B. Fenske NPE-S-2LT-I-BF02 August 1, 2013

Two NPE-S Tankless With Two Temperature Operation

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater

CHG

Gas

Domestic Cold Water

Condensate

CHG

High Temp Domestic Hot Water

CommunicationCable

Low TempDomestic Hot Water

M

CH

Page 5: NPE Series Application Drawings · 2016. 1. 30. · 1. Use Navien Cord P #30011612A 2. Set DIP Switches on Integrated Controller #1 – OFF, #2 – OFF, #3 – ON 3. Select External

20 GoodyearIrvine, CA 92618

800-519-8794www.Navien.com T

Check Valve Circulator

PressureReliefValve Expansion

Tank

AquastatFull-portBall Valve

Mixing Valve

StorageVessel

DHW Circulatorw/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.This concept system drawing does not imply compliance with local building codes. Actual installation may vary depending on installation location & parameters and it must be done in accordance to all local building codes. Verify with local building officials before commencement of system installation.

Drawn By: B. Fenske NPE-S-3-I-BF02 August 1, 2013

Three NPE-S Tankless (Includes NPE-A Internal Circulation Mode)

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater

CHG

Gas

Domestic Cold Water

Condensate

CHG

Domestic Hot Water

CommunicationCable

CHG

CommunicationCable

Page 6: NPE Series Application Drawings · 2016. 1. 30. · 1. Use Navien Cord P #30011612A 2. Set DIP Switches on Integrated Controller #1 – OFF, #2 – OFF, #3 – ON 3. Select External

20 GoodyearIrvine, CA 92618

800-519-8794www.Navien.com T

Check Valve Circulator

PressureReliefValve Expansion

Tank

AquastatFull-portBall Valve

Mixing Valve

StorageVessel

DHW Circulatorw/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.This concept system drawing does not imply compliance with local building codes. Actual installation may vary depending on installation location & parameters and it must be done in accordance to all local building codes. Verify with local building officials before commencement of system installation.

Drawn By: B. Fenske NPE-S-4-I-BF02 August 1, 2013

Four NPE-S Tankless (Includes NPE-A, Internal Circulation Mode)

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater

CHG

Gas

Domestic Cold Water

Condensate

CHG

Domestic Hot Water

CommunicationCable

CHG

CommunicationCable

CHG

CommunicationCable

Page 7: NPE Series Application Drawings · 2016. 1. 30. · 1. Use Navien Cord P #30011612A 2. Set DIP Switches on Integrated Controller #1 – OFF, #2 – OFF, #3 – ON 3. Select External

20 GoodyearIrvine, CA 92618

800-519-8794www.Navien.com T

Check Valve Circulator

PressureReliefValve Expansion

Tank

AquastatFull-portBall Valve

Mixing Valve

StorageVessel

DHW Circulatorw/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.This concept system drawing does not imply compliance with local building codes. Actual installation may vary depending on installation location & parameters and it must be done in accordance to all local building codes. Verify with local building officials before commencement of system installation.

Drawn By: B. Fenske NPE-S-5-I-BF02 August 1, 2013

Five NPE-S Tankless (Includes NPE-A, Internal Circulation Mode)

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater

CHG

Gas

Domestic Cold Water

Condensate

CHG

Domestic Hot Water

CommunicationCable

CHG

CommunicationCable

CHG

CommunicationCable

CHG

CommunicationCable

Page 8: NPE Series Application Drawings · 2016. 1. 30. · 1. Use Navien Cord P #30011612A 2. Set DIP Switches on Integrated Controller #1 – OFF, #2 – OFF, #3 – ON 3. Select External

20 GoodyearIrvine, CA 92618

800-519-8794www.Navien.com T

Check Valve Circulator

PressureReliefValve Expansion

Tank

AquastatFull-portBall Valve

Mixing Valve

StorageVessel

DHW Circulatorw/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.This concept system drawing does not imply compliance with local building codes. Actual installation may vary depending on installation location & parameters and it must be done in accordance to all local building codes. Verify with local building officials before commencement of system installation.

Drawn By: B. Fenske NPE-S-6P-I-BF02 August 1, 2013

Six Plus NPE-S Tankless (Includes NPE-A, Internal Circulation Mode)

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater

CHG

GasDomestic Cold Water

Condensate

CHG

Domestic Hot Water

CommunicationCable

CHG

CommunicationCable

CHG

CommunicationCable

CHG

CommunicationCable

CommunicationCable

CHG

Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Unit 6 - 16. . . . .

Page 9: NPE Series Application Drawings · 2016. 1. 30. · 1. Use Navien Cord P #30011612A 2. Set DIP Switches on Integrated Controller #1 – OFF, #2 – OFF, #3 – ON 3. Select External

20 GoodyearIrvine, CA 92618

800-519-8794www.Navien.com T

Check Valve Circulator

PressureReliefValve Expansion

Tank

AquastatFull-portBall Valve

Mixing Valve

StorageVessel

DHW Circulatorw/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.This concept system drawing does not imply compliance with local building codes. Actual installation may vary depending on installation location & parameters and it must be done in accordance to all local building codes. Verify with local building officials before commencement of system installation.

Drawn By: B. Fenske NPE-A-10-E-BF02 August 1, 2013

Ten NPE-S Tankless (Includes NPE-A, Internal Circulation Mode)

Alternative Mounting Shown

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater

Gas

Domestic Cold Water

Condensate

Domestic Hot Water

Page 10: NPE Series Application Drawings · 2016. 1. 30. · 1. Use Navien Cord P #30011612A 2. Set DIP Switches on Integrated Controller #1 – OFF, #2 – OFF, #3 – ON 3. Select External

20 GoodyearIrvine, CA 92618

800-519-8794www.Navien.com T

Check Valve Circulator

PressureReliefValve Expansion

Tank

AquastatFull-portBall Valve

Mixing Valve

StorageVessel

DHW Circulatorw/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.This concept system drawing does not imply compliance with local building codes. Actual installation may vary depending on installation location & parameters and it must be done in accordance to all local building codes. Verify with local building officials before commencement of system installation.

Drawn By: B. Fenske NPE-S-1-PW-EC-BF02 August 1, 2013

One NPE-S Tankless Using External Pump for Recirculation

with Part #30011612A External Pump Wire

NPE-S Series Tankless Water Heater

Notes:1. Use Navien Cord P #30011612A2. Set DIP Switches on Integrated Controller

#1 – OFF, #2 – OFF, #3 – ON3. Select External Circulator Performance

to be 2 GPM Minimum, 4 GPM Maximum basedon 11 Psi drop @ 4 GPM at tankless

* Refer to NPE Installation Manual for further details

CHG

Gas

Domestic Cold Water

CondensateDomestic Hot Water

Page 11: NPE Series Application Drawings · 2016. 1. 30. · 1. Use Navien Cord P #30011612A 2. Set DIP Switches on Integrated Controller #1 – OFF, #2 – OFF, #3 – ON 3. Select External

20 GoodyearIrvine, CA 92618

800-519-8794www.Navien.com T

Check Valve Circulator

PressureReliefValve Expansion

Tank

AquastatFull-portBall Valve

Mixing Valve

StorageVessel

DHW Circulatorw/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.This concept system drawing does not imply compliance with local building codes. Actual installation may vary depending on installation location & parameters and it must be done in accordance to all local building codes. Verify with local building officials before commencement of system installation.

One NPE-S with Storage to meet Flow/Temp Rise Requirements

Drawn By: B. Fenske August 1, 2013NPE-S-1-ST-BF02

NPE-S Series Tankless Water Heater

Domestic Cold Water

Insulated Storage

Tank

T

¾” Min

Domestic Hot Water to Fixtures

Optional DHW

Recirculation

3 or 4TapTank

(A) Tankless Circulator (Bronze or S.S) Selected Shall be 4 GPM Max @ 23' Total Head (10 PSI) + pipe, valves, fittings & tank.

(A)

GasCondensate

CHG

Page 12: NPE Series Application Drawings · 2016. 1. 30. · 1. Use Navien Cord P #30011612A 2. Set DIP Switches on Integrated Controller #1 – OFF, #2 – OFF, #3 – ON 3. Select External

20 GoodyearIrvine, CA 92618

800-519-8794www.Navien.com T

Check Valve Circulator

PressureReliefValve Expansion

Tank

AquastatFull-portBall Valve

Mixing Valve

StorageVessel

DHW Circulatorw/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.This concept system drawing does not imply compliance with local building codes. Actual installation may vary depending on installation location & parameters and it must be done in accordance to all local building codes. Verify with local building officials before commencement of system installation.

Two NPE-S with Storage to meet Flow/Temp Rise Requirements

Drawn By: B. Fenske August 1, 2013NPE-S-2-ST-BF02

(A) Tankless Circulator (Bronze or S.S) Selected Shall be 8 GPM Max (4 Per Tankless) @ 23' Total Head (10 PSI) + pipe, valves, fittings & tank.(B) Install Circuit Setters to Maintain Flow into Units @ 4 GPM Maximum

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater

(A)Domestic Cold Water

Insulated Storage

Tank

T

Domestic Hot Water to Fixtures

Optional DHW

Recirculation

3 or 4TapTank

CHG

Gas

Condensate

CHG

CommunicationCable

(B) (B)

Page 13: NPE Series Application Drawings · 2016. 1. 30. · 1. Use Navien Cord P #30011612A 2. Set DIP Switches on Integrated Controller #1 – OFF, #2 – OFF, #3 – ON 3. Select External

20 GoodyearIrvine, CA 92618

800-519-8794www.Navien.com T

Check Valve Circulator

PressureReliefValve Expansion

Tank

AquastatFull-portBall Valve

Mixing Valve

StorageVessel

DHW Circulatorw/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.This concept system drawing does not imply compliance with local building codes. Actual installation may vary depending on installation location & parameters and it must be done in accordance to all local building codes. Verify with local building officials before commencement of system installation.

Three NPE-S with Storage to meet Flow/Temp Rise Requirements

Drawn By: B. Fenske August 1, 2013NPE-S-3-ST-BF02

(A) Tankless Circulator (Bronze or S.S) Selected Shall be 12 GPM Max (4 Per Tankless) @ 23' Total Head (10 PSI) + pipe, valves, fittings & tank.(B) Install Circuit Setters to Maintain Flow into Units @ 4 GPM Maximum

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater

(A)Domestic Cold Water

Insulated Storage

Tank

T

Domestic Hot Water to Fixtures

Optional DHW

Recirculation

3 or 4TapTank

CHG

Gas

Condensate

CHG

CommunicationCable

CHG

CommunicationCable

(B) (B) (B)

Page 14: NPE Series Application Drawings · 2016. 1. 30. · 1. Use Navien Cord P #30011612A 2. Set DIP Switches on Integrated Controller #1 – OFF, #2 – OFF, #3 – ON 3. Select External

20 GoodyearIrvine, CA 92618

800-519-8794www.Navien.com T

Check Valve Circulator

PressureReliefValve Expansion

Tank

AquastatFull-portBall Valve

Mixing Valve

StorageVessel

DHW Circulatorw/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.This concept system drawing does not imply compliance with local building codes. Actual installation may vary depending on installation location & parameters and it must be done in accordance to all local building codes. Verify with local building officials before commencement of system installation.

Four NPE-S with Storage to meet Flow/Temp Rise Requirements

Drawn By: B. Fenske August 1, 2013NPE-S-4-ST-BF02

(A) Tankless Circulator (Bronze or S.S) Selected Shall be 16 GPM Max (4 Per Tankless) @ 23' Total Head (10 PSI) + pipe, valves, fittings & tank.(B) Install Circuit Setters to Maintain Flow into Units @ 4 GPM Maximum

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater

(A)

Domestic Cold Water

Insulated Storage

Tank

T

Domestic Hot Water to Fixtures

Optional DHW

Recirculation

3 or 4TapTank

CHG

Gas

Condensate

CHG

CommunicationCable

CHG

CommunicationCable

CHG

CommunicationCable

(B) (B) (B) (B)

Page 15: NPE Series Application Drawings · 2016. 1. 30. · 1. Use Navien Cord P #30011612A 2. Set DIP Switches on Integrated Controller #1 – OFF, #2 – OFF, #3 – ON 3. Select External

20 GoodyearIrvine, CA 92618

800-519-8794www.Navien.com T

Check Valve Circulator

PressureReliefValve Expansion

Tank

AquastatFull-portBall Valve

Mixing Valve

StorageVessel

DHW Circulatorw/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.This concept system drawing does not imply compliance with local building codes. Actual installation may vary depending on installation location & parameters and it must be done in accordance to all local building codes. Verify with local building officials before commencement of system installation.

Two NPE-S with Two Storage Tanks to meet Flow/Temp Rise Requirements

Drawn By: B. Fenske August 1, 2013NPE-S-2-2ST-BF02

(A) Tankless Circulator (Bronze or S.S) Selected Shall be 8 GPM Max (4 Per Tankless) @ 23' Total Head (10 PSI) + pipe, valves, fittings & tank.(B) Install Circuit Setters to Maintain Flow into Units @ 4 GPM Maximum

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater

(A)Domestic Cold Water

Domestic Hot Water to Fixtures

CHG

Gas

Condensate

CHG

CommunicationCable

InsulatedStorage

Tank

InsulatedStorage

Tank

T T

Optional DHW Recirculation

(B) (B)

Page 16: NPE Series Application Drawings · 2016. 1. 30. · 1. Use Navien Cord P #30011612A 2. Set DIP Switches on Integrated Controller #1 – OFF, #2 – OFF, #3 – ON 3. Select External

20 GoodyearIrvine, CA 92618

800-519-8794www.Navien.com T

Check Valve Circulator

PressureReliefValve Expansion

Tank

AquastatFull-portBall Valve

Mixing Valve

StorageVessel

DHW Circulatorw/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.This concept system drawing does not imply compliance with local building codes. Actual installation may vary depending on installation location & parameters and it must be done in accordance to all local building codes. Verify with local building officials before commencement of system installation.

Three NPE-S with Two Storage Tanks to meet Flow/Temp Rise Requirements

Drawn By: B. Fenske August 1, 2013NPE-S-3-2ST-BF02

(A) Tankless Circulator (Bronze or S.S) Selected Shall be 12 GPM Max (4 Per Tankless) @ 23' Total Head (10 PSI) + pipe, valves, fittings & tank.(B) Install Circuit Setters to Maintain Flow into Units @ 4 GPM Maximum

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater

(A)Domestic Cold Water

Domestic Hot Water to Fixtures

CHG

Gas

Condensate

CHG

CommunicationCable

InsulatedStorage

Tank

InsulatedStorage

Tank

T T

Optional DHW Recirculation

CHG

CommunicationCable

(B) (B) (B)

Page 17: NPE Series Application Drawings · 2016. 1. 30. · 1. Use Navien Cord P #30011612A 2. Set DIP Switches on Integrated Controller #1 – OFF, #2 – OFF, #3 – ON 3. Select External

20 GoodyearIrvine, CA 92618

800-519-8794www.Navien.com T

Check Valve Circulator

PressureReliefValve Expansion

Tank

AquastatFull-portBall Valve

Mixing Valve

StorageVessel

DHW Circulatorw/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.This concept system drawing does not imply compliance with local building codes. Actual installation may vary depending on installation location & parameters and it must be done in accordance to all local building codes. Verify with local building officials before commencement of system installation.

Four NPE-S with Two Storage Tanks to meet Flow/Temp Rise Requirements

Drawn By: B. Fenske August 1, 2013NPE-S-4-2ST-BF02

(A) Tankless Circulator (Bronze or S.S) Selected Shall be 16 GPM Max (4 Per Tankless) @ 23' Total Head (10 PSI) + pipe, valves, fittings & tank.(B) Install Circuit Setters to Maintain Flow into Units @ 4 GPM Maximum

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater

Condensate

(A)

Domestic Cold Water

Domestic Hot Water to Fixtures

CHG

Gas

CHG

CommunicationCable

InsulatedStorage

Tank

InsulatedStorage

Tank

T T

Optional DHW Recirculation

CHG

CommunicationCable

CHG

CommunicationCable

(B) (B) (B) (B)

Page 18: NPE Series Application Drawings · 2016. 1. 30. · 1. Use Navien Cord P #30011612A 2. Set DIP Switches on Integrated Controller #1 – OFF, #2 – OFF, #3 – ON 3. Select External

20 GoodyearIrvine, CA 92618

800-519-8794www.Navien.com T

Check Valve Circulator

PressureReliefValve Expansion

Tank

AquastatFull-portBall Valve

Mixing Valve

StorageVessel

DHW Circulatorw/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.This concept system drawing does not imply compliance with local building codes. Actual installation may vary depending on installation location & parameters and it must be done in accordance to all local building codes. Verify with local building officials before commencement of system installation.

Two NPE-S with Storage to meet Flow/Temp Rise Requirements

Two Temperature System

Drawn By: B. Fenske August 1, 2013NPE-S-2-STLT-BF02

(A) Tankless Circulator (Bronze or S.S) Selected Shall be 8 GPM Max (4 Per Tankless) @ 23' Total Head (10 PSI) + pipe, valves, fittings & tank.(B) Install Circuit Setters to Maintain Flow into Units @ 4 GPM Maximum

Recommended Pipe Size/Heater Count 1 Unit - ¾” 2 Units - 1" 3 Units - 1-¼” 4 to 5 Units - 1-½” 6 to 8 Units - 2" 9 to 14 Units - 2-½” 15 to 16 Units - 3"

NPE-S Series Tankless Water Heater

(A)Domestic Cold Water

Insulated Storage

Tank

T

Domestic Hot Water to Fixtures

Optional DHW

Recirculation

3 or 4TapTank

CHG

Gas

Condensate

CHG

CommunicationCable

(B) (B)

Low TempDomestic Hot Water

M

CH

Page 19: NPE Series Application Drawings · 2016. 1. 30. · 1. Use Navien Cord P #30011612A 2. Set DIP Switches on Integrated Controller #1 – OFF, #2 – OFF, #3 – ON 3. Select External

20 GoodyearIrvine, CA 92618

800-519-8794www.Navien.com T

Check Valve Circulator

PressureReliefValve Expansion

Tank

AquastatFull-portBall Valve

Mixing Valve

StorageVessel

DHW Circulatorw/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.This concept system drawing does not imply compliance with local building codes. Actual installation may vary depending on installation location & perameters and it must be done in accordance to all local building codes. Verify with local building officials before commencement of system installation.

One Navien NPE-S Dishwasher ApplicationWith Storage to meet Flow/Temp

Rise Requirements

1. Tankless circulator selected should beapproved for domestic water (S.S. or Bronze).

2. Tankless circulator selected shall be 4 GPM@ 23' H (10 PSI) + pipe, valves, fittings & tank.

3. Storage tank volume size selections:

High Temp (180°F) 6 X dishwasher GPM requirements

Low Temp (140°F) 4 X dishwasher GPM requirements

Drawn By: B. Fenske August 1, 2013NPE-S-1-DW-BF02

NPE-S Series Tankless Water Heater

Opt. Recirculation

Domestic Cold Water

Vacuum Breaker

Insulated Storage

Tank

T

¾” Min

CHG

GasCondensate

Page 20: NPE Series Application Drawings · 2016. 1. 30. · 1. Use Navien Cord P #30011612A 2. Set DIP Switches on Integrated Controller #1 – OFF, #2 – OFF, #3 – ON 3. Select External

20 GoodyearIrvine, CA 92618

800-519-8794www.Navien.com T

Check Valve Circulator

PressureReliefValve Expansion

Tank

AquastatFull-portBall Valve

Mixing Valve

StorageVessel

DHW Circulatorw/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.This concept system drawing does not imply compliance with local building codes. Actual installation may vary depending on installation location & perameters and it must be done in accordance to all local building codes. Verify with local building officials before commencement of system installation.

Drawn By: B. Fenske August 1, 2013

Two Navien NPE-S Dishwasher ApplicationWith Storage to meet Flow/Temp

Rise Requirements

NPE-S-2-DW-DHW-BF02

NPE-S Series Tankless Water Heater

(A) Tankless Circulator (Bronze or S.S) Selected Shall be 4 GPM Max per Tankless @ 23' Total Head (10 PSI) + pipe, valves, fittings & tank.(B) Install Circuit Setters to Maintain Flow into Units @ 4 GPM Maximum.

Storage tank volume size selections:High Temp (180°F)

6 X dishwasher GPM requirements Low Temp (140°F)

4 X dishwasher GPM requirements

Opt. Recirculation

Vacuum Breaker

Insulated Storage

Tank

T

1” Min

Domestic Water

To Fixtures

(A)

CHG

Gas

Domestic Cold Water

Condensate

CHG

CommunicationCable

(B) (B)M

CH

Page 21: NPE Series Application Drawings · 2016. 1. 30. · 1. Use Navien Cord P #30011612A 2. Set DIP Switches on Integrated Controller #1 – OFF, #2 – OFF, #3 – ON 3. Select External

20 GoodyearIrvine, CA 92618

800-519-8794www.Navien.com T

Check Valve Circulator

PressureReliefValve Expansion

Tank

AquastatFull-portBall Valve

Mixing Valve

StorageVessel

DHW Circulatorw/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.This concept system drawing does not imply compliance with local building codes. Actual installation may vary depending on installation location & perameters and it must be done in accordance to all local building codes. Verify with local building officials before commencement of system installation.

(A) Tankless Circulator (Bronze or S.S) Selected Shall be 4 GPM Max per Tankless @ 23' Total Head (10 PSI) + pipe, valves, fittings & tank.(B) Install Circuit Setters to Maintain Flow into Units @ 4 GPM Maximum.

Storage tank volume size selections:High Temp (180°F)

6 X dishwasher GPM requirements Low Temp (140°F)

4 X dishwasher GPM requirements

Drawn By: B. Fenske August 1, 2013

Two Navien NPE-S Dishwasher ApplicationWith Storage to meet Flow/Temp

Rise Requirements

NPE-S-2-DW-BF02

NPE-S Series Tankless Water Heater

Opt. Recirculation

Vacuum Breaker

Insulated Storage

Tank

T

1” Min

(A)

CHG

Gas

Domestic Cold Water

Condensate

CHG

CommunicationCable

(B) (B)

Page 22: NPE Series Application Drawings · 2016. 1. 30. · 1. Use Navien Cord P #30011612A 2. Set DIP Switches on Integrated Controller #1 – OFF, #2 – OFF, #3 – ON 3. Select External

20 GoodyearIrvine, CA 92618

800-519-8794www.Navien.com T

Check Valve Circulator

PressureReliefValve Expansion

Tank

AquastatFull-portBall Valve

Mixing Valve

StorageVessel

DHW Circulatorw/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.This concept system drawing does not imply compliance with local building codes. Actual installation may vary depending on installation location & perameters and it must be done in accordance to all local building codes. Verify with local building officials before commencement of system installation.

(A) Tankless Circulator (Bronze or S.S) Selected Shall be 4 GPM Max per Tankless @ 23' Total Head (10 PSI) + pipe, valves, fittings & tank.(B) Install Circuit Setters to Maintain Flow into Units @ 4 GPM Maximum.

Storage tank volume size selections:High Temp (180°F)

6 X dishwasher GPM requirements Low Temp (140°F)

4 X dishwasher GPM requirements

Drawn By: B. Fenske August 1, 2013

Three Navien NPE-S Dishwasher ApplicationWith Storage to meet Flow/Temp

Rise Requirements

NPE-S-3-DW-DHW-BF02

NPE-S Series Tankless Water Heater

Gas

Condensate

Opt. Recirculation

Vacuum Breaker

Insulated Storage

Tank

T

1-1/4” Min

Domestic Water

To Fixtures

(A)

CHG

Domestic Cold Water

CHG

CommunicationCable

(B) (B)

CHG

CommunicationCable

(B)M

CH

Page 23: NPE Series Application Drawings · 2016. 1. 30. · 1. Use Navien Cord P #30011612A 2. Set DIP Switches on Integrated Controller #1 – OFF, #2 – OFF, #3 – ON 3. Select External

20 GoodyearIrvine, CA 92618

800-519-8794www.Navien.com T

Check Valve Circulator

PressureReliefValve Expansion

Tank

AquastatFull-portBall Valve

Mixing Valve

StorageVessel

DHW Circulatorw/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.This concept system drawing does not imply compliance with local building codes. Actual installation may vary depending on installation location & parameters and it must be done in accordance to all local building codes. Verify with local building officials before commencement of system installation.

NPE-S-Combi-AH-BF02 August 1, 2013Drawn By: B. Fenske

Navien NPE-S Series TanklessCombi Use Application with Air Handler

NPE-S Series Tankless Water Heater

AIRFLOW

Opt. AC COILGas

Domestic Cold Water

Domestic Hot Water

ToFixtures

Circulator Requirement:Bronze or Stainless Steel

Select & Set - 4 GPM max @ 23 ft head. (Alternate pump location shown inside AHU)

Condensate

CHGM

CH

Page 24: NPE Series Application Drawings · 2016. 1. 30. · 1. Use Navien Cord P #30011612A 2. Set DIP Switches on Integrated Controller #1 – OFF, #2 – OFF, #3 – ON 3. Select External

20 GoodyearIrvine, CA 92618

800-519-8794www.Navien.com T

Check Valve Circulator

PressureReliefValve Expansion

Tank

AquastatFull-portBall Valve

Mixing Valve

Air Elimination

DHW Circulatorw/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.This concept system drawing does not imply compliance with local building codes. Actual installation may vary depending on installation location & parameters and it must be done in accordance to all local building codes. Verify with local building officials before commencement of system installation.

NPE-S-Combi-SS-BF02 August 1, 2013Drawn By: B. Fenske

Navien NPE-S Series TanklessCombi Use Application with Required

SS Heat Exchanger

NPE-S Series Tankless Water Heater

Gas

Domestic Cold Water

Domestic Hot Water

ToFixtures

(A) Circulator Requirement: Bronze or Stainless Steel

Select & Set - 4 GPM max @ 23 ft head.(B) Maximum 30 MBTU’s/Hour & 135°F

Maximum Heating System Temperature with NPE tankless set at 140°F.

Condensate

CH

Closed Loop Heating Fill

SS Heat Exchanger

(B)

FieldSuppliedCirculator

Zone PanelT

(A)

GM

CH

Page 25: NPE Series Application Drawings · 2016. 1. 30. · 1. Use Navien Cord P #30011612A 2. Set DIP Switches on Integrated Controller #1 – OFF, #2 – OFF, #3 – ON 3. Select External

20 GoodyearIrvine, CA 92618

800-519-8794www.Navien.com T

Check Valve Circulator

PressureReliefValve Expansion

Tank

AquastatFull-portBall Valve

Mixing Valve

StorageVessel

DHW Circulatorw/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.This concept system drawing does not imply compliance with local building codes. Actual installation may vary depending on installation location & parameters and it must be done in accordance to all local building codes. Verify with local building officials before commencement of system installation.

NPE-S-G-BF02 August 1, 2013Drawn By: B. Fenske

NPE-S Domestic Hot Water Standard Installation with Geothermal or

Desuperheater

Notes:1. For Storage Tank/Geothermal Operation; DIP Switch #6of 10 located on Integrated Display Panel should be set ON (UP).2. With Storage Tank/Geothermal Operation Enabled, NPETankless DHW setting may be set at or near storage tank thermostatic mixing valve temperature output.

Domestic Cold Water

NPE-S Series Tankless Water Heater

DHWSupply

To Fixtures

GasCondensate

CH

DomesticStorage

TankGeothermal Unit

orDesuperheater

G

(A)

(A) Follow GeoThermal Unit and Tank Manufacturer Recommendations and Requirements

Page 26: NPE Series Application Drawings · 2016. 1. 30. · 1. Use Navien Cord P #30011612A 2. Set DIP Switches on Integrated Controller #1 – OFF, #2 – OFF, #3 – ON 3. Select External

20 GoodyearIrvine, CA 92618

800-519-8794www.Navien.com T

Check Valve Circulator

PressureReliefValve Expansion

Tank

AquastatFull-portBall Valve

Mixing Valve

StorageVessel

DHW Circulatorw/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.This concept system drawing does not imply compliance with local building codes. Actual installation may vary depending on installation location & parameters and it must be done in accordance to all local building codes. Verify with local building officials before commencement of system installation.

NPE-S-S-BF02 August 1, 2013Drawn By: B. Fenske

NPE-S Domestic Hot Water Standard Installation with Solar Application

Notes:1. For Storage Tank/Solar Operation; DIP Switch #6 of 10located on Integrated Display Panel should be set ON (UP).2. With Storage Tank/Solar Operation Enabled, NPETankless DHW setting may be set at or near storage tank thermostatic mixing valve temperature output.

Domestic Cold Water

NPE-S Series Tankless Water Heater

GasCondensate

CHG

Solar Fill

DHWSupply

To Fixtures