NRCA HVAC System Type REFERENCE Document No. ETF-ARP-45-001 Rev/Mod A-0 Release Date 09/01/2015 Page 1 of 13 Tank Farm Alarm Response Procedure Effluent Treatment Facility USQ Not Required ETF is a <Hazard Category 3 Radiological Facility CHANGE HISTORY ( LAST 5 REV-MODS ) Rev-Mod Release Date Justification: Summary of Changes A-0 09/01/2015 Conversion to WRPS Format New Procedure; Supersedes ETF-PRO-AR-51368 (ARP-45-001) NRCA HVAC System Index ALARM PAGE HVAC NRCA OPERATION ATT FAIL-1 ............................................................................................... 2 HVAC NRCA OPERATION ATT FAIL-2 ............................................................................................... 3 HVAC NRCA OPERATION ATT FAIL-3 ............................................................................................... 4 HVAC TAH-45A003 .................................................................................................................................. 5 HVAC TAL-45A003 .................................................................................................................................. 6 HVAC TAH-45A004 .................................................................................................................................. 7 HVAC TAL-45A004 .................................................................................................................................. 8 HVAC TAH-45A005 .................................................................................................................................. 9 HVAC TAL-45A005 ................................................................................................................................ 10 HVAC NRCA 45B-EVU6-A.................................................................................................................... 11 HVAC NRCA 45B-EVU7-A.................................................................................................................... 12 HVAC NRCA 45B-EVU8-A.................................................................................................................... 13 RECORDS No records are generated during the performance of this procedure.

NRCA HVAC System - emcbc.doe.gov Library/011819... · NRCA HVAC System Type REFERENCE Document No. ETF-ARP-45-001 Rev/Mod A-0 Release Date 09/01/2015 Page 2 of 13 HVAC NRCA OPERATION

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Page 1: NRCA HVAC System - emcbc.doe.gov Library/011819... · NRCA HVAC System Type REFERENCE Document No. ETF-ARP-45-001 Rev/Mod A-0 Release Date 09/01/2015 Page 2 of 13 HVAC NRCA OPERATION

NRCA HVAC System

Type

REFERENCE Document No.

ETF-ARP-45-001 Rev/Mod

A-0 Release Date

09/01/2015 Page

1 of 13

Tank Farm Alarm Response Procedure Effluent Treatment Facility

USQ Not Required – ETF is a <Hazard Category 3 Radiological Facility

CHANGE HISTORY ( LAST 5 REV-MODS )

Rev-Mod Release Date Justification: Summary of Changes

A-0 09/01/2015 Conversion to WRPS Format New Procedure; Supersedes ETF-PRO-AR-51368

(ARP-45-001)

NRCA HVAC System Index

ALARM PAGE

HVAC NRCA OPERATION ATT FAIL-1 ............................................................................................... 2

HVAC NRCA OPERATION ATT FAIL-2 ............................................................................................... 3

HVAC NRCA OPERATION ATT FAIL-3 ............................................................................................... 4

HVAC TAH-45A003 .................................................................................................................................. 5

HVAC TAL-45A003 .................................................................................................................................. 6

HVAC TAH-45A004 .................................................................................................................................. 7

HVAC TAL-45A004 .................................................................................................................................. 8

HVAC TAH-45A005 .................................................................................................................................. 9

HVAC TAL-45A005 ................................................................................................................................ 10

HVAC NRCA 45B-EVU6-A .................................................................................................................... 11

HVAC NRCA 45B-EVU7-A .................................................................................................................... 12

HVAC NRCA 45B-EVU8-A .................................................................................................................... 13

RECORDS

No records are generated during the performance of this procedure.

Page 2: NRCA HVAC System - emcbc.doe.gov Library/011819... · NRCA HVAC System Type REFERENCE Document No. ETF-ARP-45-001 Rev/Mod A-0 Release Date 09/01/2015 Page 2 of 13 HVAC NRCA OPERATION

NRCA HVAC System

Type

REFERENCE Document No.

ETF-ARP-45-001 Rev/Mod

A-0 Release Date

09/01/2015 Page

2 of 13

HVAC NRCA OPERATION ATT FAIL-1

HVAC NRCA OPERATION

ATT FAIL-1

Description: HVAC NRCA OPERATION ATT FAIL-1 (Operations area first floor)

Setpoint: Logic permissive(s) not met

Alarm Location: Logic generated alarm

Graphic: Alarm Summary Screen

Indications: N/A

NOTE - Alarm response procedures are not designed for, nor intended to be applied to, “expected”

alarms generated by approved work activities or procedures.

Automatic Actions:

1. Operations Area AHU 45B-EVU-6 will not run.

Immediate Actions:

[1] REQUEST the SOE perform the following actions, as specified:

[1.1] CHECK the fire alarm (fire protection (FP) Zones 3 and 14).

[1.2] (SOE/CRO) IF the alarm is on, RESPOND per ETF-ERP-85B-005.

[1.3] (SOE) ENSURE first floor HVAC is aligned per ETF-45-001.

Possible Causes:

1. Operations area AHU 45B-EVU-6 failed to run.

2. Operations area AHU 45B-EVU-6 not in Auto.

3. Equipment alarm on operations area AHU 45B-EVU-6.

4. Fire Alarm (FP Zones 3 and 14) triggered.

References:

Drawings: H-2-89021, Sheet 2; H-2-89306

Documents: ETF-ERP-85B-005, Fire-Explosion at ETF

ETF-45-001, Operation of Non-RCA HVAC System

Page 3: NRCA HVAC System - emcbc.doe.gov Library/011819... · NRCA HVAC System Type REFERENCE Document No. ETF-ARP-45-001 Rev/Mod A-0 Release Date 09/01/2015 Page 2 of 13 HVAC NRCA OPERATION

NRCA HVAC System

Type

REFERENCE Document No.

ETF-ARP-45-001 Rev/Mod

A-0 Release Date

09/01/2015 Page

3 of 13

HVAC NRCA OPERATION ATT FAIL-2

HVAC NRCA OPERATION

ATT FAIL-2

Description: HVAC NRCA OPERATION ATT FAIL-2 (Electrical Equipment Room HVAC)

Setpoint: Logic permissive(s) not met

Alarm Location: Logic generated alarm

Graphic: Alarm Summary Screen

Indications: N/A

NOTE - Alarm response procedures are not designed for, nor intended to be applied to, “expected”

alarms generated by approved work activities or procedures.

Automatic Actions:

1. Electrical equipment room AHU 45B-EVU-7 will not run.

Immediate Actions:

[1] REQUEST the SOE perform the following actions, unless otherwise specified:

[1.1] CHECK fire alarm (FP Zone 15).

[1.2] (SOE/CRO) IF the alarm is on, RESPOND per ETF-ERP-85B-005.

[1.3] (SOE) ENSURE electrical equipment room HVAC is aligned per ETF-45-001.

Possible Causes:

1. Operations area AHU 45B-EVU-7 failed to run.

2. Operations area AHU 45B-EVU-7 not in Auto.

3. Equipment alarm on operations area AHU 45B-EVU-7.

4. Fire Alarm (FP Zone 15) triggered.

References:

Drawings: H-2-89021, HVAC H-2-89306

Documents: ETF-ERP-85B-005, Fire-Explosion at ETF

ETF-45-001, Operation of Non-RCA HVAC System

Page 4: NRCA HVAC System - emcbc.doe.gov Library/011819... · NRCA HVAC System Type REFERENCE Document No. ETF-ARP-45-001 Rev/Mod A-0 Release Date 09/01/2015 Page 2 of 13 HVAC NRCA OPERATION

NRCA HVAC System

Type

REFERENCE Document No.

ETF-ARP-45-001 Rev/Mod

A-0 Release Date

09/01/2015 Page

4 of 13

HVAC NRCA OPERATION ATT FAIL-3

HVAC NRCA OPERATION

ATT FAIL-3

Description: HVAC NRCA OPERATION ATT FAIL-3 (Control Area HVAC)

Setpoint: Logic permissive(s) not met

Alarm Location: Logic generated alarm

Graphic: Alarm Summary Screen

Indications: N/A

NOTE - Alarm response procedures are not designed for, nor intended to be applied to, “expected”

alarms generated by approved work activities or procedures.

Automatic Actions

1. Control Area AHU 45B-EVU-8 will not run.

Immediate Actions

[1] REQUEST SOE perform the following actions, as specified:

[1.1] CHECK fire alarm (FP Zones 4 and 13).

[1.2] (SOE/CRO) IF the alarm is on, RESPOND per ETF-ERP-85B-005.

[1.3] (SOE) ENSURE control area HVAC is aligned per ETF-45-001.

Possible Causes

1. Control area AHU 45B-EVU-8 failed to run.

2. Control area AHU 45B-EVU-8 not in Auto.

3. Equipment alarm on control area AHU 45B-EVU-8.

4. Fire alarm (FP Zones 4 and 13) triggered.

References Drawings: H-2-89021, Sheet 2; HVAC H-2-89306

Documents: ETF-ERP-85B-005, Fire-Explosion at ETF

ETF-45-001, Operation of Non-RCA HVAC System

Page 5: NRCA HVAC System - emcbc.doe.gov Library/011819... · NRCA HVAC System Type REFERENCE Document No. ETF-ARP-45-001 Rev/Mod A-0 Release Date 09/01/2015 Page 2 of 13 HVAC NRCA OPERATION

NRCA HVAC System

Type

REFERENCE Document No.

ETF-ARP-45-001 Rev/Mod

A-0 Release Date

09/01/2015 Page

5 of 13

HVAC TAH-45A003

HVAC TAH-45A003

Description: HVAC NRCA FIRST FLOOR TEMP HI (TAH-45A003)

Setpoint: 82°F

Alarm Location: TT-45A003

Graphic: Alarm Summary Screen

Indications: N/A

NOTE - Alarm response procedures are not designed for, nor intended to be applied to, “expected”

alarms generated by approved work activities or procedures.

Automatic Actions:

None.

Immediate Actions:

[1] REQUEST the SOE perform the following action, as specified:

[1.1] (SOE) ENSURE first floor HVAC is aligned per ETF-45-001.

Possible Causes:

1. Operations area AHU 45B-EVU-6 failure.

2. Outdoor condensing unit 45B-EVU-3 failure.

3. TE/TT/TIC-45A003-1 failure.

References:

Drawings: H-2-89021, Sheet 2; H-2-89306

Documents: ETF-45-001, Operation of Non-RCA HVAC System

Page 6: NRCA HVAC System - emcbc.doe.gov Library/011819... · NRCA HVAC System Type REFERENCE Document No. ETF-ARP-45-001 Rev/Mod A-0 Release Date 09/01/2015 Page 2 of 13 HVAC NRCA OPERATION

NRCA HVAC System

Type

REFERENCE Document No.

ETF-ARP-45-001 Rev/Mod

A-0 Release Date

09/01/2015 Page

6 of 13

HVAC TAL-45A003

HVAC TAL-45A003

Description: HVAC NRCA FIRST FLOOR TEMP LO (TAL-45A003)

Setpoint: 68°F

Alarm Location: TT-45A003

Graphic: Alarm Summary Screen

Indications: N/A

NOTE - Alarm response procedures are not designed for, nor intended to be applied to, “expected”

alarms generated by approved work activities or procedures.

Automatic Actions:

None.

Immediate Actions:

[1] REQUEST the SOE ensure first floor HVAC is aligned per ETF-45-001.

Possible Causes:

1. Operations area AHU 45B-EVU-6 failure.

2. Heater 45B-E-3 failure.

3. TE/TT/TIC-45A003-1 failure.

References:

Drawings: H-2-89021, Sheet 2; H-2-89306

Documents: ETF-45-001, Operation of Non-RCA HVAC System

Page 7: NRCA HVAC System - emcbc.doe.gov Library/011819... · NRCA HVAC System Type REFERENCE Document No. ETF-ARP-45-001 Rev/Mod A-0 Release Date 09/01/2015 Page 2 of 13 HVAC NRCA OPERATION

NRCA HVAC System

Type

REFERENCE Document No.

ETF-ARP-45-001 Rev/Mod

A-0 Release Date

09/01/2015 Page

7 of 13

HVAC TAH-45A004

HVAC TAH-45A004

Description: HVAC NRCA ELECT EQUIP TEMP HI (TAH-45A004)

Setpoint: 82°F

Alarm Location: TT-45A004

Graphic: Alarm Summary Screen

Indications: N/A

NOTE - Alarm response procedures are not designed for, nor intended to be applied to, “expected”

alarms generated by approved work activities or procedures.

Automatic Actions:

None.

Immediate Actions:

[1] REQUEST the SOE ensure electrical equipment room HVAC is aligned per

ETF-45-001.

Possible Causes:

1. Electrical equipment room AHU 45B-EVU-7 failure.

2. Outdoor condensing unit 45B-EVU-4 failure.

3. TE/TT/TIC-45A004-1 failure.

References:

Drawings: H-2-89021, Sheet 2; H-2-89306

Documents: ETF-45-001, Operation of Non-RCA HVAC System

Page 8: NRCA HVAC System - emcbc.doe.gov Library/011819... · NRCA HVAC System Type REFERENCE Document No. ETF-ARP-45-001 Rev/Mod A-0 Release Date 09/01/2015 Page 2 of 13 HVAC NRCA OPERATION

NRCA HVAC System

Type

REFERENCE Document No.

ETF-ARP-45-001 Rev/Mod

A-0 Release Date

09/01/2015 Page

8 of 13

HVAC TAL-45A004

HVAC TAL-45A004

Description: HVAC NRCA ELECT EQUIP TEMP LO (TAL-45A004)

Setpoint: 68°F

Alarm Location: TT-45A004

Graphic: Alarm Summary Screen

Indications: N/A

NOTE - Alarm response procedures are not designed for, nor intended to be applied to, “expected”

alarms generated by approved work activities or procedures.

Automatic Actions:

None.

Immediate Actions:

[1] REQUEST the SOE ensure electrical equipment room HVAC is aligned per

ETF-45-001.

Possible Causes:

1. Electrical equipment room AHU 45B-EVU-7 failure.

2. Heater 45B-E-4 failure.

3. TE/TT/TIC-45A004-1 failure.

References:

Drawings: H-2-89021, Sheet 2; H-2-89306

Documents: ETF-45-001, Operation of Non-RCA HVAC System

Page 9: NRCA HVAC System - emcbc.doe.gov Library/011819... · NRCA HVAC System Type REFERENCE Document No. ETF-ARP-45-001 Rev/Mod A-0 Release Date 09/01/2015 Page 2 of 13 HVAC NRCA OPERATION

NRCA HVAC System

Type

REFERENCE Document No.

ETF-ARP-45-001 Rev/Mod

A-0 Release Date

09/01/2015 Page

9 of 13

HVAC TAH-45A005

HVAC TAH-45A005

Description: HVAC CONTROL AREA TEMP HI (TAH-45A005)

Setpoint: 76°F

Alarm Location: TT-45A005

Graphic: Alarm Summary Screen

Indications: N/A

NOTE - Alarm response procedures are not designed for, nor intended to be applied to, “expected”

alarms generated by approved work activities or procedures.

Automatic Actions:

None.

Immediate Actions:

[1] REQUEST the SOE ensure control area HVAC is aligned per ETF-45-001.

Possible Causes:

1. Control room AHU 45B-EVU-8 failure.

2. Outdoor condensing unit 45B-EVU-5 failure.

3. TE/TT/TIC-45A005-1 failure.

References:

Drawings: H-2-89021, Sheet 2; H-2-89306

Documents: ETF-45-001, Operation of Non-RCA HVAC System

Page 10: NRCA HVAC System - emcbc.doe.gov Library/011819... · NRCA HVAC System Type REFERENCE Document No. ETF-ARP-45-001 Rev/Mod A-0 Release Date 09/01/2015 Page 2 of 13 HVAC NRCA OPERATION

NRCA HVAC System

Type

REFERENCE Document No.

ETF-ARP-45-001 Rev/Mod

A-0 Release Date

09/01/2015 Page

10 of 13

HVAC TAL-45A005

HVAC TAL-45A005

Description: HVAC NRCA CONTROL AREA TEMP LO (TAL-45A005)

Setpoint: 68°F

Alarm Location: TT-45A005

Graphic: Alarm Summary Screen

Indications: N/A

NOTE - Alarm response procedures are not designed for, nor intended to be applied to, “expected”

alarms generated by approved work activities or procedures.

Automatic Actions:

None.

Immediate Actions:

[1] REQUEST the SOE ensure control area HVAC is aligned per ETF-45-001.

Possible Causes:

1. Control room AHU 45B-EVU-8 failure.

2. Heater 45B-E-5 failure.

3. TE/TT/TIC-45A005-1 failure.

References:

Drawings: H-2-89021, Sheet 2; H-2-89306

Documents: ETF-45-001, Operation of Non-RCA HVAC System

Page 11: NRCA HVAC System - emcbc.doe.gov Library/011819... · NRCA HVAC System Type REFERENCE Document No. ETF-ARP-45-001 Rev/Mod A-0 Release Date 09/01/2015 Page 2 of 13 HVAC NRCA OPERATION

NRCA HVAC System

Type

REFERENCE Document No.

ETF-ARP-45-001 Rev/Mod

A-0 Release Date

09/01/2015 Page

11 of 13

HVAC NRCA 45B-EVU6-A

HVAC NRCA 45B-EVU6-A

Description: OPERATIONS AREA HVAC NRCA EVU-6 (45B-EVU6-A)

Setpoint: Logic permissive(s) not met

Alarm Location: Logic generated alarm

Graphic: Alarm Summary Screen

Indications: N/A

NOTE - Alarm response procedures are not designed for, nor intended to be applied to, “expected”

alarms generated by approved work activities or procedures.

Automatic Actions:

1. Operations area AHU 45B-EVU-6 will not operate.

Immediate Actions:

[1] REQUEST the SOE perform the following actions, as specified:

[1.1] (SOE) ENSURE operations area HVAC is aligned per ETF-45-001.

[1.2] (SOE) CHECK circuit breaker MDP-3-11 is on.

[1.3] (SOE) IF the breaker tripped, REQUEST Maintenance to troubleshoot and reset.

Possible Causes:

1. Circuit breaker MDP-3-11 open/tripped.

2. Local motor overload tripped.

3. Local control fuses blown.

References:

Drawings: H-2-89021, Sheet 2; H-2-89306

Documents: ETF-45-001, Operation of Non-RCA HVAC System

Page 12: NRCA HVAC System - emcbc.doe.gov Library/011819... · NRCA HVAC System Type REFERENCE Document No. ETF-ARP-45-001 Rev/Mod A-0 Release Date 09/01/2015 Page 2 of 13 HVAC NRCA OPERATION

NRCA HVAC System

Type

REFERENCE Document No.

ETF-ARP-45-001 Rev/Mod

A-0 Release Date

09/01/2015 Page

12 of 13

HVAC NRCA 45B-EVU7-A

HVAC NRCA 45B-EVU7-A

Description: ELECTRICAL EQUIPMENT ROOM HVAC NRCA EVU-7 (45B-EVU7-A)

Setpoint: Logic permissive(s) not met

Alarm Location: Logic generated alarm

Graphic: Alarm Summary Screen

Indications: N/A

NOTE - Alarm response procedures are not designed for, nor intended to be applied to, “expected”

alarms generated by approved work activities or procedures.

Automatic Actions:

1. Electrical equipment room AHU 45B-EVU-7 will not operate.

Immediate Actions:

[1] REQUEST the SOE perform the following actions, as specified:

[1.1] (SOE) ENSURE electrical equipment room HVAC is aligned per ETF-45-001.

[1.2] (SOE) CHECK circuit breaker DP-4-19 is on.

[1.3] (SOE) IF the breaker tripped, REQUEST Maintenance to troubleshoot and reset.

Possible Causes:

1. Circuit breaker DP-4-19 open/tripped.

2. Local motor overload tripped.

3. Local control fuses blown.

References:

Drawings: H-2-89021, Sheet 2; H-2-89306

Documents: ETF-45-001, Operation of Non-RCA HVAC System

Page 13: NRCA HVAC System - emcbc.doe.gov Library/011819... · NRCA HVAC System Type REFERENCE Document No. ETF-ARP-45-001 Rev/Mod A-0 Release Date 09/01/2015 Page 2 of 13 HVAC NRCA OPERATION

NRCA HVAC System

Type

REFERENCE Document No.

ETF-ARP-45-001 Rev/Mod

A-0 Release Date

09/01/2015 Page

13 of 13

HVAC NRCA 45B-EVU8-A

HVAC NRCA 45B-EVU8-A

Description: CONTROL AREA HVAC NRCA EVU-8 (45B-EVU8-A)

Setpoint: Logic permissive(s) not met

Alarm Location: Logic generated alarm

Graphic: Alarm Summary Screen

Indications: N/A

NOTE - Alarm response procedures are not designed for, nor intended to be applied to, “expected”

alarms generated by approved work activities or procedures.

Automatic Actions:

1. Control room AHU 45B-EVU-8 will not operate.

Immediate Actions:

[1] REQUEST the SOE perform the following actions, as specified:

[1.1] (SOE) ENSURE control area HVAC is aligned per ETF-45-001.

[1.2] (SOE) CHECK circuit breaker MDP-3-15 is on.

[1.3] (SOE) IF the breaker tripped, REQUEST Maintenance to troubleshoot and reset.

Possible Causes:

1. Circuit breaker MDP-3-15 open/tripped.

2. Local motor overload tripped.

3. Local control fuses blown.

References:

Drawings: H-2-89021, Sheet 2; H-2-89306

Documents: ETF-45-001, Operation of Non-RCA HVAC System