Asset: SHIRLEY CHISHOLM CAMPUS - K, 965 EAST 107TH STREET, New York, 11236
Inspection Id Inspection Type Time In Last Edited
SA : K366 Architectural - Senior 2019-12-03 8:08 AM 2019-12-12 12:22 PM
AA : K366 Architectural - Associate 2019-12-03 7:35 AM 2019-12-03 3:29 PM
Asset Data
Question Answer
Was the building fully accessible for inspection No
Inspection Access Comment Playground Safety Surface due to snow
Principal(s) Information
Principal Name Dennis Herring Jr.
Organization The Science and Medicine Middle School - Brooklyn
Did you meet with this Principal? Yes
Did this Principal provide feedback? Yes
Summary of Principal's Feedback The Principal's comments are as follows: 1. The climate control is notworking properly and requires frequent repairs. 2. There is waterinfiltration through the door into Room 206. 3. The a/c unit in theTelcom Room on the 2nd Floor is not working.
Custodian Was not present
Fireman Was not present
Building Square Footage 67000
Comments on the Area None
Comments on the Stories (Floors) plus Basements 4+B+PH
Comments on the Number of Classrooms 27
Comments on the Year Built 2009
Student Population 403
Staff Population 60
Weather Fair
Facade Photo
East 107th Street - Northeast view
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 1 of 34
Main Entrance Photo
Facade A - East 107th Street
Roof Photo
Roof 1 - Northwest view
Have any Systems/Major Building Components been upgraded? Yes
Systems: New Science Demo Room 114
Year: 2019
Systems: Limited Window repairs
Year: 2016
Have there been any New Building Additions? No
Tandem Schools? No
Leased Space? No
Priority Condition
PriorityCondition ExistLast Year?
PriorityCategory
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No ProtrudingElements
Severelydamagedbleacher plankwith protrudingmetal supportexposing is apotentialtripping hazard.
INTERIOR |GYMNASIUM |Seating
Across from theentrance
AlexanderFrancisco
Handyman
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 2 of 34
Structural Engineer Required
StructuralCondition Type
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Accessibility
Accessibility Status Question Response
Is the primary or secondary entrance on an accessible route? Yes
Is the building a multi-story building? Yes
Are all floors of the building accessible through compliant means? Yes
Accessible classrooms exists on each floor? Yes
Boys and Girls or Unisex accessible toilets exist on at least every other floor? Yes
If the following spaces exist, are they ALL accessible? Art Room, Auditorium,Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs
Yes
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
Exterior Entrances & Exits Yes
Exterior H/C Lifts No No
Exterior Ramps and Railings No No
Interior Routes
Corridor and Lobby H/C Lifts No No
Interior Corridor Doors and Hardware No No
Interior Corridors and Lobbies Yes
Interior Elevators Yes Yes
Interior Lobby Doors and Hardware Yes
Interior Ramps Yes Yes
Rooms & Spaces
Art Rooms Room 322 Yes Yes
Auditorium No
Cafeteria Basement Yes Yes Yes Yes
Classrooms 1st - 4th Floors Yes Yes
Computer Rooms No
Gymnasium Basement Yes Yes Yes Yes
Library Room 419 Yes Yes
Main Office Room 101 Yes Yes
Multi-purpose Room No
Nurse's Room Room 105C Yes Yes
Pool No
Science Lab Room 402 Yes Yes
Toilet Rooms (Boys) Basement, 1st - 4th Floors Yes Yes
Toilet Rooms (Girls) Basement, 1st - 4th Floors Yes Yes
Toilet Rooms (Staff) Basement, 1st - 4th Floors Yes Yes
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 3 of 34
Building Template
Inspection
Question Response
Architectural
EXTERIOR Inspected
AREAWAY Does not Exist
AWNINGS AND CANOPIES Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CHIMNEY Does not Exist
COPING Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CORNICE Does not Exist
DOORS Inspected
DOORS AND FRAMES Inspected
Condition 3 - Fair
Deficiency METAL: AIR AND WATER INFILTRATION, OPEN JOINTS WITHDAMAGED CAULKING
Roof Plan reference
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 4 of 34
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Purpose of Action LEVEL 2
Deficiency Photo1
Facade E - Room 206
Violations No violations recorded.
Deficiency METAL: DETERIORATED DOOR AND FRAME - MINORDETERIORATION
Roof Plan reference
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade B
Violations No violations recorded.
DOOR HARDWARE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TRANSOM/SIDE LIGHT Inspected
Condition 2 - Between Good and Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 5 of 34
Question Response
EXTERIOR
DOORS Inspected
TRANSOM/SIDE LIGHT
Deficiency No deficiencies recorded
EXTERIOR WALLS Inspected
Material Type(s) Masonry, Concrete, Steel
Replacement Quantity 22,000
Replacement Uom S.F.
InspectedInstance on All Facades
Instance Condition 3 - Fair
Instance Quantity 22,000
Instance Quantity Uom S.F.
Deficiency BRICK: MINOR CRACKS AND SPALLING
Roof Plan reference
Elevation
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action RESTITCH
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade F
Violations No violations recorded.
Deficiency BRICK: OPEN JOINTS
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 6 of 34
Question Response
EXTERIOR
EXTERIOR WALLS Inspected
Roof Plan reference
Elevation
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade F
Violations No violations recorded.
Deficiency CAST IN PLACE / PRE-CAST CONCRETE: MAJORCRACKS/SPALLING
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 7 of 34
Question Response
EXTERIOR
EXTERIOR WALLS
Elevation
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade B
Violations No violations recorded.
Deficiency BRICK: DETERIORATED MASONRY SILLS
Roof Plan reference
Elevation
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action REPAIR
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 8 of 34
Question Response
EXTERIOR
EXTERIOR WALLS
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade B
Violations No violations recorded.
EXTERIOR SOFFITS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LOADING DOCK Does not Exist
LOUVER Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
PARAPETS Inspected
Material Type(s) Masonry, Concrete
Replacement Quantity 2,200
Replacement Uom C.F.
InspectedInstance on All Facades
Instance Condition 3 - Fair
Instance Quantity 2,200
Instance Quantity Uom C.F.
Deficiency CONCRETE: MINOR CRACKS, SPALLING
Roof Plan reference
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 9 of 34
Question Response
EXTERIOR
PARAPETS
Deficiency Photo1
Roof 1 Facade A
Violations No violations recorded.
PLAZA DECK Inspected
InspectedInstance on Pavers: Roofs 1, 2
Instance Condition 2 - Between Good and Fair
Instance Quantity 7,500
Instance Quantity Uom S.F.
Installation Year 2009
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
InspectedInstance on Concrete: Roof 3
Instance Condition 2 - Between Good and Fair
Instance Quantity 3,000
Instance Quantity Uom S.F.
Installation Year 2009
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
ROOF Inspected
Roofing Inspected
Replacement Quantity 11,000
Replacement Uom S.F.
ROOF HATCH/SMOKE HATCH Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected
Condition 3 - Fair
Deficiency DAMAGED/MISSING
Roof Plan reference
Deficiency Quantity 20
Quantity Uom L.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 10 of 34
Question Response
EXTERIOR
ROOF
Roofing
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 7 Facade E
Violations No violations recorded.
ROOF BARRIER Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF CAGE Inspected
Condition 3 - Fair
Deficiency STEEL FRAME: MINOR RUSTING
Roof Plan reference
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 11 of 34
Question Response
EXTERIOR
ROOF
Roofing
ROOF FENCE Inspected
Condition 2 - Between Good and Fair
Deficiency RAILING/PANELS: DETERIORATED, MINOR RUSTING
Roof Plan reference
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 2
Violations No violations recorded.
ROOFING Inspected
InspectedInstance on IRMA: Roofs 4-6
Instance Condition 3 - Fair
Instance Quantity 10,000
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 2009
Source of Installation Custodial Staff
Deficiency IRMA: ROOFING: MINOR LEAKAGE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 12 of 34
Question Response
EXTERIOR
ROOF
Roofing
ROOFING
Roof Plan reference
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 4 - Room 417
Violations No violations recorded.
InspectedInstance on Metal: Roof 7
Instance Condition 1 - Good
Instance Quantity 1,000
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 2009
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
ROOFING DRAINS Inspected
Condition 3 - Fair
Deficiency DETERIORATED
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 13 of 34
Question Response
EXTERIOR
ROOF
Roofing
ROOFING DRAINS
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 5
Violations No violations recorded.
Specialties Inspected
BULKHEAD/PENTHOUSE Inspected
Condition 3 - Fair
Deficiency BULKHEAD/PENTHOUSE WALLS/EXTERIOR:EFFLORESCENCE
Roof Plan reference
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 1
Purpose of Action LEVEL 1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 14 of 34
Question Response
EXTERIOR
ROOF
Specialties
BULKHEAD/PENTHOUSE
Deficiency Photo1
Roof 1 PH
Violations No violations recorded.
Deficiency BULKHEAD/PENTHOUSE DOORS: AIR/WATER INFILTRATIONWITH DAMAGED CAULKING
Roof Plan reference
Deficiency Quantity 30
Quantity Uom L.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 BH2
Violations No violations recorded.
Deficiency BULKHEAD/PENTHOUSE WALLS/EXTERIOR:CRACKS/SPALLING - MINOR
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 15 of 34
Question Response
EXTERIOR
ROOF
Specialties
BULKHEAD/PENTHOUSE
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 BH2
Violations No violations recorded.
CUPOLA/ SPIRES/ TOWERS Does not Exist
DORMER Does not Exist
DUNNAGE STEEL Does not Exist
SKYLIGHT/ROOF VENT Does not Exist
ROOF/GRAVITY TANK Does not Exist
STAIRS/RAMPS: EXTERIOR Inspected
BUILDING CHEEK/FLANK WALLS Does not Exist
RAILINGS Inspected
Condition 3 - Fair
Deficiency RUST - MINOR
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 16 of 34
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
RAILINGS
Deficiency Quantity 15
Quantity Uom L.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade F
Violations No violations recorded.
STAIRS/RAMPS Inspected
Condition 3 - Fair
Deficiency CONCRETE: CRACKS/SPALLING - MINOR
Roof Plan reference
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade F
Violations No violations recorded.
WINDOWS Inspected
Replacement Quantity 3,500
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 17 of 34
Question Response
EXTERIOR
WINDOWS
Replacement Uom S.F.
EXTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
WINDOWS Inspected
Material Type(s) Aluminum
InspectedInstance on Aluminum - Other: All Facades
Instance Condition 3 - Fair
Instance Quantity 3,500
Instance Quantity Uom S.F.
Installation Year 2009
Source of Installation Custodial Staff
Deficiency ALUMINUM - OTHER: AIR/WATER INFILTRATION
Roof Plan reference
Elevation
Deficiency Quantity 60
Quantity Uom L.F.
Potential Action REPLACE TRIM, SILLS OR WEATHERSTRIPPING
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 18 of 34
Question Response
EXTERIOR
WINDOWS
WINDOWS
Deficiency Photo1
Facade F - Corridor by Room 321
Violations No violations recorded.
Deficiency ALUMINUM - OTHER: DETERIORATED
Roof Plan reference
Elevation
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPLACE WINDOW
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A Room 417
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 19 of 34
Question Response
EXTERIOR
WINDOWS
WINDOWS
Deficiency ALUMINUM - OTHER: BROKEN PANE
Roof Plan reference
Elevation
Deficiency Quantity 90
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A -Room 321 shown, Rooms 307, 403 similar
Violations No violations recorded.
INTERIOR Inspected
POOLS Does not Exist
STRUCTURAL Inspected
COLUMNS/BEAMS/BEARING WALLS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
FLOOR STRUCTURE Inspected
Condition 3 - Fair
Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS
Deficiency Location/Instance Basement Rooms B03, B05, B17D
Deficiency Quantity 30
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 20 of 34
Question Response
INTERIOR
STRUCTURAL
FLOOR STRUCTURE
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Room B03
Violations No violations recorded.
Deficiency METAL DECK AND CONCRETE: DETERIORATED
Deficiency Location/Instance Roof 1 PH
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Elevator Machine Room
Violations No violations recorded.
FOUNDATION WALLS Inspected
Material Type(s) Concrete
Condition 2 - Between Good and Fair
Deficiency CONCRETE: CRACKED/SPALLED/REINFORCEMENTEXPOSED
Deficiency Location/Instance Basement
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 21 of 34
Question Response
INTERIOR
STRUCTURAL
FOUNDATION WALLS
Deficiency Photo1
Room B17D
Violations No violations recorded.
ROOF STRUCTURE Inspected
Condition 2 - Between Good and Fair
Deficiency STEEL COLUMNS/BEAMS: DETERIORATED/MISSINGSPRAY-ON FIREPROOFING
Deficiency Location/Instance Roof 1 PH
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Elevator Machine Room
Violations No violations recorded.
VAULTS-BUNKERS Does not Exist
AUDITORIUM Does not Exist
CAFETERIA Inspected
InspectedInstance on Basement
Ceiling
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Equipment
Does not ExistInstance on Basement
Floor Finish
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 22 of 34
Question Response
INTERIOR
CAFETERIA
Floor Finish
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on Basement
Stage
Does not ExistInstance on Basement
Walls
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Near the students toilet, Drinking Fountain, by the vending machines
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near the students toilets
Violations No violations recorded.
Window Curtains/Shades/Blinds
Does not ExistInstance on Basement
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency ACOUSTIC TILES: DAMAGED/MISSING
Deficiency Location/Instance Corridor near Room 402
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 23 of 34
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Deficiency Photo1
Corridor near Room 402
Violations No violations recorded.
Deficiency ACOUSTIC TILES: DAMAGED/MISSING - ACTIVE LEAK
Deficiency Location/Instance Room 417, Corridor near Room B400
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room B400
Violations No violations recorded.
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Rooms 206, 217, 321, Main Entrance Vestibules (3 doors)
Deficiency Quantity 6
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 24 of 34
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Door(s) Inspected
Main Entrance Vestibule
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Rooms 112, 321, 417
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 321
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency WALL PADDING: DETERIORATED
Deficiency Location/Instance 4th Floor Roof - Plaza Deck playing area
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 4
Deficiency Photo1
4th Floor Roof - Plaza Deck playing area
Violations 35383729N
Deficiency GYPSUM BOARD: DETERIORATED
Deficiency Location/Instance Corridor near Rooms B15A, 105C, 205, 321, 404, and others
Deficiency Quantity 120
Quantity Uom S.F.
Potential Action REPLACE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 25 of 34
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Walls
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 321
Violations No violations recorded.
Specialties Does not Exist
GYMNASIUM Inspected
InspectedInstance on Basement
Ceiling
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Equipment
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Seating
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency DAMAGED BLEACHERS
Deficiency Location/Instance Across from the entrance
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 26 of 34
Question Response
INTERIOR
GYMNASIUM
Seating
Deficiency Photo1
Across from the entrance
Violations No violations recorded.
Sliding-folding Partition
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stage
InspectedInstance on Basement
Stage Inspected
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stage Curtain Rigging Inspected
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stage Curtains Inspected
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency WALL PADDING: DETERIORATED
Deficiency Location/Instance Along the entrance, left side wall
Deficiency Quantity 160
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 27 of 34
Question Response
INTERIOR
GYMNASIUM
Walls
Deficiency Photo1
Left side wall
Violations No violations recorded.
Window Curtains/Shades/Blinds
Does not ExistInstance on Basement
INTERIOR DOOR HARDWARE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
INTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
KITCHEN Inspected
InspectedInstance on Basement
Ceiling
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LIBRARY Inspected
InspectedInstance on Room 419
Built-in Furnishing
InspectedInstance on Room 419
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Ceiling
InspectedInstance on Room 419
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 28 of 34
Question Response
INTERIOR
LIBRARY
Door(s)
InspectedInstance on Room 419
Condition 3 - Fair
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Main Entrance
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Main Entrance
Violations No violations recorded.
Floor Finish
InspectedInstance on Room 419
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on Room 419
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LOCKER ROOM Does not Exist
MULTI-PURPOSE ROOM Does not Exist
SCIENCE DEMO ROOM Inspected
InspectedInstance on Room 114
Alternative use No
Fixed Equipment
InspectedInstance on Room 114
Condition 1 - Good
Deficiency No deficiencies recorded
SCIENCE LAB Inspected
InspectedInstance on Room 402
Alternative use No
Fixed Equipment
InspectedInstance on Room 402
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
SCIENCE PREP ROOM Inspected
InspectedInstance on Room 402A
Alternative use No
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 29 of 34
Question Response
INTERIOR
SCIENCE PREP ROOM
Fixed Equipment
InspectedInstance on Room 402A
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
SHOWER ROOM Does not Exist
STAIRS/RAMPS: INTERIOR Inspected
Do Letter Stair Signs Exist? Partially
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency GYPSUM BOARD: DAMAGED/DETERIORATED
Deficiency Location/Instance Stairs A/4, B/4
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair B/4
Violations No violations recorded.
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Partition Does not Exist
Railings Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stairs and Landings Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency GYPSUM BOARD: DETERIORATED
Deficiency Location/Instance Stair A/1 (Lobby level),3, B/4
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 30 of 34
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Walls
Deficiency Photo1
Stair B/4
Violations No violations recorded.
TOILET ROOMS - STAFF Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Does not Exist
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TOILET ROOMS - STUDENTS Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DAMAGED LOUVER
Deficiency Location/Instance Rooms B20A, B20B
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 31 of 34
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Door(s) Inspected
Room B20B
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LIFE SAFETY Inspected
F.D. HOLDING AREA Does not Exist
STEEL STAIRS Does not Exist
SITE Inspected
CONTAINERIZATION Does not Exist
Drainage System for Asphalt Does not Exist
Drainage System for Concrete Inspected
Catch Basins/Manhole - Surrounded by concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Concrete Covering Does not Exist
Drainage System for Soil Does not Exist
DRINKING FOUNTAINS Does not Exist
FENCES Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
IRRIGATION SYSTEM Does not Exist
PAVING Inspected
Student Non-Use Inspected
Gravel Exists? No
Asphalt Does not Exist
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Pavers Does not Exist
Student Use Does not Exist
Site Sidewalks & Walkways Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance E.107th Street, near the Playground, North walkway
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 32 of 34
Question Response
SITE
PAVING
Site Sidewalks & Walkways
Concrete
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
E.107th Street
Violations No violations recorded.
Pavers Does not Exist
DOT Sidewalk Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance E.107th Street
Deficiency Quantity 125
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
E.107th Street
Violations No violations recorded.
Deficiency DAMAGED CURBS
Deficiency Location/Instance E.107th Street
Deficiency Quantity 20
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 33 of 34
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
Deficiency Photo1
E.107th Street
Violations No violations recorded.
Pavers Does not Exist
PLAYGROUNDS Inspected
InspectedInstance on 1st Floor Plaza Deck - East side of the building
Benches
Does not ExistInstance on 1st Floor Plaza Deck - East side of the building
Fence
InspectedInstance on 1st Floor Plaza Deck - East side of the building
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Pavement
Does not ExistInstance on 1st Floor Plaza Deck - East side of the building
Play Equipment
InspectedInstance on 1st Floor Plaza Deck - East side of the building
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Safety Surfacing
InaccessibleInstance on 1st Floor Plaza Deck - East side of the building
Unpaved Area
Does not ExistInstance on 1st Floor Plaza Deck - East side of the building
PLAYING SURFACE Does not Exist
RETAINING WALLS Inspected
Are there any Retaining Walls 6' OR higher facing publicstreet/sidewalk?
No
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
SEATING Does not Exist
SITE WALLS (NOT RETAINING WALLS) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
STAIRS/RAMPS: EXTERIOR Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K366
PB/A&W Print Date: 9/14/2020Page 34 of 34