Asset: SHIRLEY CHISHOLM CAMPUS - K, 965 EAST 107TH STREET, New York, 11236 Inspection Id Inspection Type Time In Last Edited SA : K366 Architectural - Senior 2019-12-03 8:08 AM 2019-12-12 12:22 PM AA : K366 Architectural - Associate 2019-12-03 7:35 AM 2019-12-03 3:29 PM Asset Data Question Answer Was the building fully accessible for inspection No Inspection Access Comment Playground Safety Surface due to snow Principal(s) Information Principal Name Dennis Herring Jr. Organization The Science and Medicine Middle School - Brooklyn Did you meet with this Principal? Yes Did this Principal provide feedback? Yes Summary of Principal's Feedback The Principal's comments are as follows: 1. The climate control is not working properly and requires frequent repairs. 2. There is water infiltration through the door into Room 206. 3. The a/c unit in the Telcom Room on the 2nd Floor is not working. Custodian Was not present Fireman Was not present Building Square Footage 67000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4+B+PH Comments on the Number of Classrooms 27 Comments on the Year Built 2009 Student Population 403 Staff Population 60 Weather Fair Facade Photo East 107th Street - Northeast view NYC Department of Education Architectural Inspection Building Condition Assessment Survey 2019 - 2020 K366 PB/A&W Print Date: 9/14/2020 Page 1 of 34

NYC Department of EducationK366 PB/A&W Page 15 of 34 Print Date: 9/14/2020 Question Response EXTERIOR ROOF Specialties BULKHEAD/PENTHOUSE Roof Plan reference Deficiency Quantity 10

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

  • Asset: SHIRLEY CHISHOLM CAMPUS - K, 965 EAST 107TH STREET, New York, 11236

    Inspection Id Inspection Type Time In Last Edited

    SA : K366 Architectural - Senior 2019-12-03 8:08 AM 2019-12-12 12:22 PM

    AA : K366 Architectural - Associate 2019-12-03 7:35 AM 2019-12-03 3:29 PM

    Asset Data

    Question Answer

    Was the building fully accessible for inspection No

    Inspection Access Comment Playground Safety Surface due to snow

    Principal(s) Information

    Principal Name Dennis Herring Jr.

    Organization The Science and Medicine Middle School - Brooklyn

    Did you meet with this Principal? Yes

    Did this Principal provide feedback? Yes

    Summary of Principal's Feedback The Principal's comments are as follows: 1. The climate control is notworking properly and requires frequent repairs. 2. There is waterinfiltration through the door into Room 206. 3. The a/c unit in theTelcom Room on the 2nd Floor is not working.

    Custodian Was not present

    Fireman Was not present

    Building Square Footage 67000

    Comments on the Area None

    Comments on the Stories (Floors) plus Basements 4+B+PH

    Comments on the Number of Classrooms 27

    Comments on the Year Built 2009

    Student Population 403

    Staff Population 60

    Weather Fair

    Facade Photo

    East 107th Street - Northeast view

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 1 of 34

  • Main Entrance Photo

    Facade A - East 107th Street

    Roof Photo

    Roof 1 - Northwest view

    Have any Systems/Major Building Components been upgraded? Yes

    Systems: New Science Demo Room 114

    Year: 2019

    Systems: Limited Window repairs

    Year: 2016

    Have there been any New Building Additions? No

    Tandem Schools? No

    Leased Space? No

    Priority Condition

    PriorityCondition ExistLast Year?

    PriorityCategory

    ConditionDescription

    ComponentAffected

    LocationDescription

    Person(s)Notified

    Person(s) Title PhotoImage

    No ProtrudingElements

    Severelydamagedbleacher plankwith protrudingmetal supportexposing is apotentialtripping hazard.

    INTERIOR |GYMNASIUM |Seating

    Across from theentrance

    AlexanderFrancisco

    Handyman

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 2 of 34

  • Structural Engineer Required

    StructuralCondition Type

    ConditionDescription

    ComponentAffected

    LocationDescription

    Person(s)Notified

    Person(s) Title PhotoImage

    No condition recorded

    Accessibility

    Accessibility Status Question Response

    Is the primary or secondary entrance on an accessible route? Yes

    Is the building a multi-story building? Yes

    Are all floors of the building accessible through compliant means? Yes

    Accessible classrooms exists on each floor? Yes

    Boys and Girls or Unisex accessible toilets exist on at least every other floor? Yes

    If the following spaces exist, are they ALL accessible? Art Room, Auditorium,Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs

    Yes

    Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

    FireAlarmStrobe

    FUNCTIONAL ACCESSIBILITY

    Exterior Routes

    Exterior Entrances & Exits Yes

    Exterior H/C Lifts No No

    Exterior Ramps and Railings No No

    Interior Routes

    Corridor and Lobby H/C Lifts No No

    Interior Corridor Doors and Hardware No No

    Interior Corridors and Lobbies Yes

    Interior Elevators Yes Yes

    Interior Lobby Doors and Hardware Yes

    Interior Ramps Yes Yes

    Rooms & Spaces

    Art Rooms Room 322 Yes Yes

    Auditorium No

    Cafeteria Basement Yes Yes Yes Yes

    Classrooms 1st - 4th Floors Yes Yes

    Computer Rooms No

    Gymnasium Basement Yes Yes Yes Yes

    Library Room 419 Yes Yes

    Main Office Room 101 Yes Yes

    Multi-purpose Room No

    Nurse's Room Room 105C Yes Yes

    Pool No

    Science Lab Room 402 Yes Yes

    Toilet Rooms (Boys) Basement, 1st - 4th Floors Yes Yes

    Toilet Rooms (Girls) Basement, 1st - 4th Floors Yes Yes

    Toilet Rooms (Staff) Basement, 1st - 4th Floors Yes Yes

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 3 of 34

  • Building Template

    Inspection

    Question Response

    Architectural

    EXTERIOR Inspected

    AREAWAY Does not Exist

    AWNINGS AND CANOPIES Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    CHIMNEY Does not Exist

    COPING Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    CORNICE Does not Exist

    DOORS Inspected

    DOORS AND FRAMES Inspected

    Condition 3 - Fair

    Deficiency METAL: AIR AND WATER INFILTRATION, OPEN JOINTS WITHDAMAGED CAULKING

    Roof Plan reference

    Deficiency Quantity 10

    Quantity Uom L.F.

    Potential Action MAINTENANCE

    Urgency of Action PRIORITY 5

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 4 of 34

  • Question Response

    EXTERIOR

    DOORS

    DOORS AND FRAMES

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Facade E - Room 206

    Violations No violations recorded.

    Deficiency METAL: DETERIORATED DOOR AND FRAME - MINORDETERIORATION

    Roof Plan reference

    Deficiency Quantity 2

    Quantity Uom EACH

    Potential Action MAINTENANCE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Facade B

    Violations No violations recorded.

    DOOR HARDWARE Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    LINTELS Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    TRANSOM/SIDE LIGHT Inspected

    Condition 2 - Between Good and Fair

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 5 of 34

  • Question Response

    EXTERIOR

    DOORS Inspected

    TRANSOM/SIDE LIGHT

    Deficiency No deficiencies recorded

    EXTERIOR WALLS Inspected

    Material Type(s) Masonry, Concrete, Steel

    Replacement Quantity 22,000

    Replacement Uom S.F.

    InspectedInstance on All Facades

    Instance Condition 3 - Fair

    Instance Quantity 22,000

    Instance Quantity Uom S.F.

    Deficiency BRICK: MINOR CRACKS AND SPALLING

    Roof Plan reference

    Elevation

    Deficiency Quantity 10

    Quantity Uom S.F.

    Potential Action RESTITCH

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Facade F

    Violations No violations recorded.

    Deficiency BRICK: OPEN JOINTS

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 6 of 34

  • Question Response

    EXTERIOR

    EXTERIOR WALLS Inspected

    Roof Plan reference

    Elevation

    Deficiency Quantity 20

    Quantity Uom S.F.

    Potential Action REPOINT

    Urgency of Action PRIORITY 4

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Facade F

    Violations No violations recorded.

    Deficiency CAST IN PLACE / PRE-CAST CONCRETE: MAJORCRACKS/SPALLING

    Roof Plan reference

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 7 of 34

  • Question Response

    EXTERIOR

    EXTERIOR WALLS

    Elevation

    Deficiency Quantity 40

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 4

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Facade B

    Violations No violations recorded.

    Deficiency BRICK: DETERIORATED MASONRY SILLS

    Roof Plan reference

    Elevation

    Deficiency Quantity 10

    Quantity Uom L.F.

    Potential Action REPAIR

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 8 of 34

  • Question Response

    EXTERIOR

    EXTERIOR WALLS

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Facade B

    Violations No violations recorded.

    EXTERIOR SOFFITS Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    LOADING DOCK Does not Exist

    LOUVER Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    PARAPETS Inspected

    Material Type(s) Masonry, Concrete

    Replacement Quantity 2,200

    Replacement Uom C.F.

    InspectedInstance on All Facades

    Instance Condition 3 - Fair

    Instance Quantity 2,200

    Instance Quantity Uom C.F.

    Deficiency CONCRETE: MINOR CRACKS, SPALLING

    Roof Plan reference

    Deficiency Quantity 80

    Quantity Uom S.F.

    Potential Action REPAIR

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 9 of 34

  • Question Response

    EXTERIOR

    PARAPETS

    Deficiency Photo1

    Roof 1 Facade A

    Violations No violations recorded.

    PLAZA DECK Inspected

    InspectedInstance on Pavers: Roofs 1, 2

    Instance Condition 2 - Between Good and Fair

    Instance Quantity 7,500

    Instance Quantity Uom S.F.

    Installation Year 2009

    Source of Installation Custodial Staff

    Deficiency No deficiencies recorded

    InspectedInstance on Concrete: Roof 3

    Instance Condition 2 - Between Good and Fair

    Instance Quantity 3,000

    Instance Quantity Uom S.F.

    Installation Year 2009

    Source of Installation Custodial Staff

    Deficiency No deficiencies recorded

    ROOF Inspected

    Roofing Inspected

    Replacement Quantity 11,000

    Replacement Uom S.F.

    ROOF HATCH/SMOKE HATCH Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected

    Condition 3 - Fair

    Deficiency DAMAGED/MISSING

    Roof Plan reference

    Deficiency Quantity 20

    Quantity Uom L.F.

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 10 of 34

  • Question Response

    EXTERIOR

    ROOF

    Roofing

    LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS

    Potential Action REPLACE

    Urgency of Action PRIORITY 4

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Roof 7 Facade E

    Violations No violations recorded.

    ROOF BARRIER Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    ROOF CAGE Inspected

    Condition 3 - Fair

    Deficiency STEEL FRAME: MINOR RUSTING

    Roof Plan reference

    Deficiency Quantity 100

    Quantity Uom S.F.

    Potential Action MAINTENANCE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Roof 1

    Violations No violations recorded.

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 11 of 34

  • Question Response

    EXTERIOR

    ROOF

    Roofing

    ROOF FENCE Inspected

    Condition 2 - Between Good and Fair

    Deficiency RAILING/PANELS: DETERIORATED, MINOR RUSTING

    Roof Plan reference

    Deficiency Quantity 20

    Quantity Uom S.F.

    Potential Action REPAIR

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Roof 2

    Violations No violations recorded.

    ROOFING Inspected

    InspectedInstance on IRMA: Roofs 4-6

    Instance Condition 3 - Fair

    Instance Quantity 10,000

    Instance Quantity Uom S.F.

    Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

    No

    Installation Year 2009

    Source of Installation Custodial Staff

    Deficiency IRMA: ROOFING: MINOR LEAKAGE

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 12 of 34

  • Question Response

    EXTERIOR

    ROOF

    Roofing

    ROOFING

    Roof Plan reference

    Deficiency Quantity 50

    Quantity Uom S.F.

    Potential Action REPAIR

    Urgency of Action PRIORITY 5

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Roof 4 - Room 417

    Violations No violations recorded.

    InspectedInstance on Metal: Roof 7

    Instance Condition 1 - Good

    Instance Quantity 1,000

    Instance Quantity Uom S.F.

    Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

    No

    Installation Year 2009

    Source of Installation Custodial Staff

    Deficiency No deficiencies recorded

    ROOFING DRAINS Inspected

    Condition 3 - Fair

    Deficiency DETERIORATED

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 13 of 34

  • Question Response

    EXTERIOR

    ROOF

    Roofing

    ROOFING DRAINS

    Roof Plan reference

    Deficiency Quantity 1

    Quantity Uom EACH

    Potential Action REPLACE

    Urgency of Action PRIORITY 4

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Roof 5

    Violations No violations recorded.

    Specialties Inspected

    BULKHEAD/PENTHOUSE Inspected

    Condition 3 - Fair

    Deficiency BULKHEAD/PENTHOUSE WALLS/EXTERIOR:EFFLORESCENCE

    Roof Plan reference

    Deficiency Quantity 30

    Quantity Uom S.F.

    Potential Action MAINTENANCE

    Urgency of Action PRIORITY 1

    Purpose of Action LEVEL 1

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 14 of 34

  • Question Response

    EXTERIOR

    ROOF

    Specialties

    BULKHEAD/PENTHOUSE

    Deficiency Photo1

    Roof 1 PH

    Violations No violations recorded.

    Deficiency BULKHEAD/PENTHOUSE DOORS: AIR/WATER INFILTRATIONWITH DAMAGED CAULKING

    Roof Plan reference

    Deficiency Quantity 30

    Quantity Uom L.F.

    Potential Action MAINTENANCE

    Urgency of Action PRIORITY 5

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Roof 1 BH2

    Violations No violations recorded.

    Deficiency BULKHEAD/PENTHOUSE WALLS/EXTERIOR:CRACKS/SPALLING - MINOR

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 15 of 34

  • Question Response

    EXTERIOR

    ROOF

    Specialties

    BULKHEAD/PENTHOUSE

    Roof Plan reference

    Deficiency Quantity 10

    Quantity Uom S.F.

    Potential Action REPAIR

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Roof 1 BH2

    Violations No violations recorded.

    CUPOLA/ SPIRES/ TOWERS Does not Exist

    DORMER Does not Exist

    DUNNAGE STEEL Does not Exist

    SKYLIGHT/ROOF VENT Does not Exist

    ROOF/GRAVITY TANK Does not Exist

    STAIRS/RAMPS: EXTERIOR Inspected

    BUILDING CHEEK/FLANK WALLS Does not Exist

    RAILINGS Inspected

    Condition 3 - Fair

    Deficiency RUST - MINOR

    Roof Plan reference

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 16 of 34

  • Question Response

    EXTERIOR

    STAIRS/RAMPS: EXTERIOR

    RAILINGS

    Deficiency Quantity 15

    Quantity Uom L.F.

    Potential Action MAINTENANCE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Facade F

    Violations No violations recorded.

    STAIRS/RAMPS Inspected

    Condition 3 - Fair

    Deficiency CONCRETE: CRACKS/SPALLING - MINOR

    Roof Plan reference

    Deficiency Quantity 15

    Quantity Uom S.F.

    Potential Action REPAIR

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Facade F

    Violations No violations recorded.

    WINDOWS Inspected

    Replacement Quantity 3,500

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 17 of 34

  • Question Response

    EXTERIOR

    WINDOWS

    Replacement Uom S.F.

    EXTERIOR GUARDS Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    LINTELS Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    WINDOWS Inspected

    Material Type(s) Aluminum

    InspectedInstance on Aluminum - Other: All Facades

    Instance Condition 3 - Fair

    Instance Quantity 3,500

    Instance Quantity Uom S.F.

    Installation Year 2009

    Source of Installation Custodial Staff

    Deficiency ALUMINUM - OTHER: AIR/WATER INFILTRATION

    Roof Plan reference

    Elevation

    Deficiency Quantity 60

    Quantity Uom L.F.

    Potential Action REPLACE TRIM, SILLS OR WEATHERSTRIPPING

    Urgency of Action PRIORITY 5

    Purpose of Action LEVEL 2

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 18 of 34

  • Question Response

    EXTERIOR

    WINDOWS

    WINDOWS

    Deficiency Photo1

    Facade F - Corridor by Room 321

    Violations No violations recorded.

    Deficiency ALUMINUM - OTHER: DETERIORATED

    Roof Plan reference

    Elevation

    Deficiency Quantity 60

    Quantity Uom S.F.

    Potential Action REPLACE WINDOW

    Urgency of Action PRIORITY 4

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Facade A Room 417

    Violations No violations recorded.

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 19 of 34

  • Question Response

    EXTERIOR

    WINDOWS

    WINDOWS

    Deficiency ALUMINUM - OTHER: BROKEN PANE

    Roof Plan reference

    Elevation

    Deficiency Quantity 90

    Quantity Uom S.F.

    Potential Action MAINTENANCE

    Urgency of Action PRIORITY 5

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Facade A -Room 321 shown, Rooms 307, 403 similar

    Violations No violations recorded.

    INTERIOR Inspected

    POOLS Does not Exist

    STRUCTURAL Inspected

    COLUMNS/BEAMS/BEARING WALLS Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    FLOOR STRUCTURE Inspected

    Condition 3 - Fair

    Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS

    Deficiency Location/Instance Basement Rooms B03, B05, B17D

    Deficiency Quantity 30

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 20 of 34

  • Question Response

    INTERIOR

    STRUCTURAL

    FLOOR STRUCTURE

    Quantity Uom S.F.

    Potential Action REPAIR

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 5

    Deficiency Photo1

    Room B03

    Violations No violations recorded.

    Deficiency METAL DECK AND CONCRETE: DETERIORATED

    Deficiency Location/Instance Roof 1 PH

    Deficiency Quantity 20

    Quantity Uom S.F.

    Potential Action REPAIR

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 5

    Deficiency Photo1

    Elevator Machine Room

    Violations No violations recorded.

    FOUNDATION WALLS Inspected

    Material Type(s) Concrete

    Condition 2 - Between Good and Fair

    Deficiency CONCRETE: CRACKED/SPALLED/REINFORCEMENTEXPOSED

    Deficiency Location/Instance Basement

    Deficiency Quantity 20

    Quantity Uom S.F.

    Potential Action REPAIR

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 5

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 21 of 34

  • Question Response

    INTERIOR

    STRUCTURAL

    FOUNDATION WALLS

    Deficiency Photo1

    Room B17D

    Violations No violations recorded.

    ROOF STRUCTURE Inspected

    Condition 2 - Between Good and Fair

    Deficiency STEEL COLUMNS/BEAMS: DETERIORATED/MISSINGSPRAY-ON FIREPROOFING

    Deficiency Location/Instance Roof 1 PH

    Deficiency Quantity 10

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 5

    Deficiency Photo1

    Elevator Machine Room

    Violations No violations recorded.

    VAULTS-BUNKERS Does not Exist

    AUDITORIUM Does not Exist

    CAFETERIA Inspected

    InspectedInstance on Basement

    Ceiling

    InspectedInstance on Basement

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Door(s)

    InspectedInstance on Basement

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Fixed Equipment

    Does not ExistInstance on Basement

    Floor Finish

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 22 of 34

  • Question Response

    INTERIOR

    CAFETERIA

    Floor Finish

    InspectedInstance on Basement

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Sliding-folding Partition

    Does not ExistInstance on Basement

    Stage

    Does not ExistInstance on Basement

    Walls

    InspectedInstance on Basement

    Condition 2 - Between Good and Fair

    Deficiency CERAMIC TILE: BROKEN/ MISSING

    Deficiency Location/Instance Near the students toilet, Drinking Fountain, by the vending machines

    Deficiency Quantity 15

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Near the students toilets

    Violations No violations recorded.

    Window Curtains/Shades/Blinds

    Does not ExistInstance on Basement

    CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected

    Ceiling Inspected

    Condition 2 - Between Good and Fair

    Deficiency ACOUSTIC TILES: DAMAGED/MISSING

    Deficiency Location/Instance Corridor near Room 402

    Deficiency Quantity 10

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 23 of 34

  • Question Response

    INTERIOR

    CLASSROOMS/CORRIDORS/ADMIN SPACES

    Ceiling

    Deficiency Photo1

    Corridor near Room 402

    Violations No violations recorded.

    Deficiency ACOUSTIC TILES: DAMAGED/MISSING - ACTIVE LEAK

    Deficiency Location/Instance Room 417, Corridor near Room B400

    Deficiency Quantity 20

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 5

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Corridor near Room B400

    Violations No violations recorded.

    Door(s) Inspected

    Condition 5 - Poor

    Deficiency WOOD: DETERIORATED DOOR

    Deficiency Location/Instance Rooms 206, 217, 321, Main Entrance Vestibules (3 doors)

    Deficiency Quantity 6

    Quantity Uom EACH

    Potential Action MAINTENANCE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 24 of 34

  • Question Response

    INTERIOR

    CLASSROOMS/CORRIDORS/ADMIN SPACES

    Door(s) Inspected

    Main Entrance Vestibule

    Violations No violations recorded.

    Floor Finish Inspected

    Condition 2 - Between Good and Fair

    Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

    Deficiency Location/Instance Rooms 112, 321, 417

    Deficiency Quantity 30

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Room 321

    Violations No violations recorded.

    Walls Inspected

    Condition 2 - Between Good and Fair

    Deficiency WALL PADDING: DETERIORATED

    Deficiency Location/Instance 4th Floor Roof - Plaza Deck playing area

    Deficiency Quantity 100

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 4

    Purpose of Action LEVEL 4

    Deficiency Photo1

    4th Floor Roof - Plaza Deck playing area

    Violations 35383729N

    Deficiency GYPSUM BOARD: DETERIORATED

    Deficiency Location/Instance Corridor near Rooms B15A, 105C, 205, 321, 404, and others

    Deficiency Quantity 120

    Quantity Uom S.F.

    Potential Action REPLACE

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 25 of 34

  • Question Response

    INTERIOR

    CLASSROOMS/CORRIDORS/ADMIN SPACES

    Walls

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Corridor near Room 321

    Violations No violations recorded.

    Specialties Does not Exist

    GYMNASIUM Inspected

    InspectedInstance on Basement

    Ceiling

    InspectedInstance on Basement

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Door(s)

    InspectedInstance on Basement

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Fixed Equipment

    InspectedInstance on Basement

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Floor Finish

    InspectedInstance on Basement

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Seating

    InspectedInstance on Basement

    Condition 2 - Between Good and Fair

    Deficiency DAMAGED BLEACHERS

    Deficiency Location/Instance Across from the entrance

    Deficiency Quantity 10

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 5

    Purpose of Action LEVEL 6

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 26 of 34

  • Question Response

    INTERIOR

    GYMNASIUM

    Seating

    Deficiency Photo1

    Across from the entrance

    Violations No violations recorded.

    Sliding-folding Partition

    InspectedInstance on Basement

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Stage

    InspectedInstance on Basement

    Stage Inspected

    InspectedInstance on Basement

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Stage Curtain Rigging Inspected

    InspectedInstance on Basement

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Stage Curtains Inspected

    InspectedInstance on Basement

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Walls

    InspectedInstance on Basement

    Condition 2 - Between Good and Fair

    Deficiency WALL PADDING: DETERIORATED

    Deficiency Location/Instance Along the entrance, left side wall

    Deficiency Quantity 160

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 27 of 34

  • Question Response

    INTERIOR

    GYMNASIUM

    Walls

    Deficiency Photo1

    Left side wall

    Violations No violations recorded.

    Window Curtains/Shades/Blinds

    Does not ExistInstance on Basement

    INTERIOR DOOR HARDWARE Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    INTERIOR GUARDS Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    KITCHEN Inspected

    InspectedInstance on Basement

    Ceiling

    InspectedInstance on Basement

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Door(s)

    InspectedInstance on Basement

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Floor Finish

    InspectedInstance on Basement

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Walls

    InspectedInstance on Basement

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    LIBRARY Inspected

    InspectedInstance on Room 419

    Built-in Furnishing

    InspectedInstance on Room 419

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Ceiling

    InspectedInstance on Room 419

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 28 of 34

  • Question Response

    INTERIOR

    LIBRARY

    Door(s)

    InspectedInstance on Room 419

    Condition 3 - Fair

    Deficiency WOOD: DETERIORATED DOOR

    Deficiency Location/Instance Main Entrance

    Deficiency Quantity 1

    Quantity Uom EACH

    Potential Action MAINTENANCE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Main Entrance

    Violations No violations recorded.

    Floor Finish

    InspectedInstance on Room 419

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Walls

    InspectedInstance on Room 419

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    LOCKER ROOM Does not Exist

    MULTI-PURPOSE ROOM Does not Exist

    SCIENCE DEMO ROOM Inspected

    InspectedInstance on Room 114

    Alternative use No

    Fixed Equipment

    InspectedInstance on Room 114

    Condition 1 - Good

    Deficiency No deficiencies recorded

    SCIENCE LAB Inspected

    InspectedInstance on Room 402

    Alternative use No

    Fixed Equipment

    InspectedInstance on Room 402

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    SCIENCE PREP ROOM Inspected

    InspectedInstance on Room 402A

    Alternative use No

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 29 of 34

  • Question Response

    INTERIOR

    SCIENCE PREP ROOM

    Fixed Equipment

    InspectedInstance on Room 402A

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    SHOWER ROOM Does not Exist

    STAIRS/RAMPS: INTERIOR Inspected

    Do Letter Stair Signs Exist? Partially

    Ceiling Inspected

    Condition 2 - Between Good and Fair

    Deficiency GYPSUM BOARD: DAMAGED/DETERIORATED

    Deficiency Location/Instance Stairs A/4, B/4

    Deficiency Quantity 20

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    Stair B/4

    Violations No violations recorded.

    Door(s) Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Partition Does not Exist

    Railings Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Stairs and Landings Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Walls Inspected

    Condition 2 - Between Good and Fair

    Deficiency GYPSUM BOARD: DETERIORATED

    Deficiency Location/Instance Stair A/1 (Lobby level),3, B/4

    Deficiency Quantity 50

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 30 of 34

  • Question Response

    INTERIOR

    STAIRS/RAMPS: INTERIOR

    Walls

    Deficiency Photo1

    Stair B/4

    Violations No violations recorded.

    TOILET ROOMS - STAFF Inspected

    Ceiling Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Door(s) Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Floor Finish Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Stalls Does not Exist

    Walls Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    TOILET ROOMS - STUDENTS Inspected

    Ceiling Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Door(s) Inspected

    Condition 5 - Poor

    Deficiency WOOD: DAMAGED LOUVER

    Deficiency Location/Instance Rooms B20A, B20B

    Deficiency Quantity 2

    Quantity Uom EACH

    Potential Action MAINTENANCE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 31 of 34

  • Question Response

    INTERIOR

    TOILET ROOMS - STUDENTS

    Door(s) Inspected

    Room B20B

    Violations No violations recorded.

    Floor Finish Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Stalls Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Walls Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    LIFE SAFETY Inspected

    F.D. HOLDING AREA Does not Exist

    STEEL STAIRS Does not Exist

    SITE Inspected

    CONTAINERIZATION Does not Exist

    Drainage System for Asphalt Does not Exist

    Drainage System for Concrete Inspected

    Catch Basins/Manhole - Surrounded by concrete Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Culverts - Concrete Covering Does not Exist

    Drainage System for Soil Does not Exist

    DRINKING FOUNTAINS Does not Exist

    FENCES Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    IRRIGATION SYSTEM Does not Exist

    PAVING Inspected

    Student Non-Use Inspected

    Gravel Exists? No

    Asphalt Does not Exist

    Concrete Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Pavers Does not Exist

    Student Use Does not Exist

    Site Sidewalks & Walkways Inspected

    Asphalt Does not Exist

    Concrete Inspected

    Condition 3 - Fair

    Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

    Deficiency Location/Instance E.107th Street, near the Playground, North walkway

    Deficiency Quantity 200

    Quantity Uom S.F.

    Potential Action REPLACE

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 32 of 34

  • Question Response

    SITE

    PAVING

    Site Sidewalks & Walkways

    Concrete

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    E.107th Street

    Violations No violations recorded.

    Pavers Does not Exist

    DOT Sidewalk Inspected

    Asphalt Does not Exist

    Concrete Inspected

    Condition 3 - Fair

    Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

    Deficiency Location/Instance E.107th Street

    Deficiency Quantity 125

    Quantity Uom S.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    Deficiency Photo1

    E.107th Street

    Violations No violations recorded.

    Deficiency DAMAGED CURBS

    Deficiency Location/Instance E.107th Street

    Deficiency Quantity 20

    Quantity Uom L.F.

    Potential Action REPLACE

    Urgency of Action PRIORITY 3

    Purpose of Action LEVEL 2

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 33 of 34

  • Question Response

    SITE

    PAVING

    DOT Sidewalk

    Concrete

    Deficiency Photo1

    E.107th Street

    Violations No violations recorded.

    Pavers Does not Exist

    PLAYGROUNDS Inspected

    InspectedInstance on 1st Floor Plaza Deck - East side of the building

    Benches

    Does not ExistInstance on 1st Floor Plaza Deck - East side of the building

    Fence

    InspectedInstance on 1st Floor Plaza Deck - East side of the building

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Pavement

    Does not ExistInstance on 1st Floor Plaza Deck - East side of the building

    Play Equipment

    InspectedInstance on 1st Floor Plaza Deck - East side of the building

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    Safety Surfacing

    InaccessibleInstance on 1st Floor Plaza Deck - East side of the building

    Unpaved Area

    Does not ExistInstance on 1st Floor Plaza Deck - East side of the building

    PLAYING SURFACE Does not Exist

    RETAINING WALLS Inspected

    Are there any Retaining Walls 6' OR higher facing publicstreet/sidewalk?

    No

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    SEATING Does not Exist

    SITE WALLS (NOT RETAINING WALLS) Inspected

    Condition 2 - Between Good and Fair

    Deficiency No deficiencies recorded

    STAIRS/RAMPS: EXTERIOR Does not Exist

    NYC Department of Education

    Architectural Inspection

    Building Condition Assessment Survey 2019 - 2020

    K366

    PB/A&W Print Date: 9/14/2020Page 34 of 34