Asset: P.S. 114 - QUEENS, 134-01 CRONSTON AVE, New York, 11694
Inspection Id Inspection Type Time In Last Edited
SA : Q114 Architectural - Senior 2019-03-06 7:32 AM 2019-06-04 12:29 PM
AA : Q114 Architectural - Associate 2019-03-06 9:11 AM 2019-03-06 5:54 PM
Asset Data
Question Answer
Was the building fully accessible for inspection No
Inspection Access Comment 1st Floor Locker and Shower Room (no key)
Principal(s) Information
Principal Name Elizabeth Welsome
Organization P.S. 114 - Queens
Did you meet with this Principal? Yes
Did this Principal provide feedback? Yes
Summary of Principal's Feedback The Principal's comments are as follows:1. The playground equipment is deteriorated and damaged presenting ahazard.2. Student toilet flush valves are too difficult to operate by youngerstudents.3. Auditorium seating operates poorly.
Custodian James Kennedy
Fireman John Bobby
Building Square Footage 62000
Comments on the Area None
Comments on the Stories (Floors) plus Basements 3+B
Comments on the Number of Classrooms 34
Comments on the Year Built 1926
Student Population 687
Staff Population 86
Weather Fair
Facade Photo
Corner of Cronston Avenue and Beach135th Street - Southeast View
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 1 of 39
Main Entrance Photo
Facade A - Beach 135th Street
Roof Photo
Roof 1 - View
Have any Systems/Major Building Components been upgraded? Yes
Systems: Complete Exterior Doors replacement
Year: 2018
Systems: Auditorium upgrade including new Curtains and StageFlooring
Year: 2013
Systems: Exterior Modernization Project including: new PerimeterRoofing, Flashing, Parapets, Coping, Cornice,Leaders/Gutters, Skylight, Roof Hatch, Roof Barriers,Door and Window Lintels, and Exterior Guards; ExteriorMasonry repointing
Year: 2010
Systems: New Science Lab (Room 313)
Year: 2009
Systems: New Elevator; Student Toilet Rooms upgraded at 1st and3rd Floors
Year: 2007
Systems: New Roofing, Windows, and Exterior Guards
Year: 1998
Have there been any New Building Additions? Yes
Comments on New Building Additions 1953 (+30,000sf)
Tandem Schools? No
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 2 of 39
Leased Space? No
Priority Condition
PriorityCondition ExistLast Year?
PriorityCategory
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No Potential FallingDebris
A steel beam hascracked andspallingconcretefireproofingpresenting ahazard.
INTERIOR |STRUCTURAL|COLUMNS/BEAMS/BEARING WALLS
BasementCrawlspace (atVacuum Pump)
James Kennedy Custodian
No ProtrudingElements
Severelydamaged playequipment withsharp edge is apotential safetyhazard.
SITE |PLAYGROUNDS | PlayEquipment
PlaygroundNear Beach134th Street
James Kennedy Custodian
Yes Potential FallingDebris
Deterioratedconcrete floorstructure is apotential fallingdebris hazard.
INTERIOR |STRUCTURAL| FLOORSTRUCTURE
Boiler Room James Kennedy Custodian
Structural Engineer Required
StructuralCondition Type
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Accessibility
Accessibility Status Question Response
Is the primary or secondary entrance on an accessible route? Yes
Is the building a multi-story building? Yes
Are all floors of the building accessible through compliant means? Yes
Accessible classrooms exists on each floor? Yes
Boys and Girls or Unisex accessible toilets exist on at least every other floor? No
Is there at least one Boys and Girls or Unisex toilet accessible in the building? Yes
If the following spaces exist, are SOME accessible? Art Room, Auditorium,Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs
Yes
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
Exterior Entrances & Exits Yes
Exterior H/C Lifts No No
Exterior Ramps and Railings Yes Yes
Interior Routes
Corridor and Lobby H/C Lifts Yes Yes
Interior Corridor Doors and Hardware Yes Yes
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 3 of 39
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
Interior Routes
Interior Corridors and Lobbies No Change in Elevation
Interior Elevators Yes Yes
Interior Lobby Doors and Hardware Yes
Interior Ramps Yes Yes
Rooms & Spaces
Art Rooms Room 104 Yes Yes
Auditorium 1st Floor Yes Yes Yes Yes
Cafeteria 1st Floor Yes Yes Yes Yes
Classrooms 1st Floor Yes Yes
Computer Rooms Room 103 Yes Yes
Gymnasium 1st Floor Yes Yes Yes Yes
Library Room 307 Yes Yes
Main Office Room 160 Yes Yes
Multi-purpose Room No
Nurse's Room Room 154 Yes Yes
Pool No
Science Lab Room 313 Yes Yes
Toilet Rooms (Boys) 1st-3rd Floors Yes Yes
Toilet Rooms (Girls) 1st Floor Yes Yes
Toilet Rooms (Staff) 1st Floor Yes Yes
Building Template
Inspection
Question Response
Architectural
EXTERIOR Inspected
AREAWAY Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 4 of 39
Question Response
EXTERIOR
AWNINGS AND CANOPIES Does not Exist
CHIMNEY Inspected
Material Type(s) Masonry
Condition 2 - Between Good and Fair
Deficiency BRICK: OPEN JOINTS
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Chimney
Violations No violations recorded.
COPING Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CORNICE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
DOORS Inspected
DOORS AND FRAMES Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
DOOR HARDWARE Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TRANSOM/SIDE LIGHT Inspected
Condition 5 - Poor
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 5 of 39
Question Response
EXTERIOR
DOORS
TRANSOM/SIDE LIGHT
Deficiency WOOD: EXCESSIVELY WEATHERED
Roof Plan reference
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
Deficiency METAL: BROKEN GLASS
Roof Plan reference
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 6 of 39
Question Response
EXTERIOR
DOORS
TRANSOM/SIDE LIGHT
Deficiency Photo1
Facade B
Violations No violations recorded.
EXTERIOR WALLS Inspected
Material Type(s) Masonry
Replacement Quantity 38,000
Replacement Uom S.F.
InspectedInstance on All Facades
Instance Condition 2 - Between Good and Fair
Instance Quantity 38,000
Instance Quantity Uom S.F.
Deficiency No deficiencies recorded
EXTERIOR SOFFITS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LOADING DOCK Does not Exist
LOUVER Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
PARAPETS Inspected
Material Type(s) Masonry
Replacement Quantity 14,000
Replacement Uom C.F.
InspectedInstance on All Roofs
Instance Condition 2 - Between Good and Fair
Instance Quantity 14,000
Instance Quantity Uom C.F.
Deficiency No deficiencies recorded
PLAZA DECK Does not Exist
ROOF Inspected
Roofing Inspected
Replacement Quantity 34,800
Replacement Uom S.F.
ROOF HATCH/SMOKE HATCH Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected
Condition 2 - Between Good and Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 7 of 39
Question Response
EXTERIOR
ROOF
Roofing
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected
Deficiency No deficiencies recorded
ROOF BARRIER Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF CAGE Does not Exist
ROOF FENCE Does not Exist
ROOFING Inspected
InspectedInstance on Built-Up: All Roofs
Instance Condition 3 - Fair
Instance Quantity 34,800
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 1998
Source of Installation Custodial Staff
Deficiency BUILT-UP: ROOFING: BEYOND USEFUL LIFE
Deficiency Location/Instance Built-Up: All Roofs
Deficiency Quantity 34,800
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 1
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
ROOFING DRAINS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Specialties Inspected
BULKHEAD/PENTHOUSE Inspected
Condition 3 - Fair
Deficiency BULKHEAD/PENTHOUSE WALLS/INTERIOR: PLASTERCRACKS/SPALLING
Roof Plan reference
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 8 of 39
Question Response
EXTERIOR
ROOF
Specialties
BULKHEAD/PENTHOUSE
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Deficiency BULKHEAD/PENTHOUSE WALLS/EXTERIOR: WATERINFILTRATION
Roof Plan reference
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
BH2
Violations No violations recorded.
CUPOLA/ SPIRES/ TOWERS Does not Exist
DORMER Does not Exist
DUNNAGE STEEL Does not Exist
SKYLIGHT/ROOF VENT Inspected
Material Type(s) Glass
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF/GRAVITY TANK Does not Exist
STAIRS/RAMPS: EXTERIOR Inspected
BUILDING CHEEK/FLANK WALLS Inspected
Condition 3 - Fair
Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MINOR
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 9 of 39
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
RAILINGS Inspected
Condition 4 - Between Fair and Poor
Deficiency RUST - MAJOR
Roof Plan reference
Deficiency Quantity 20
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade B
Violations No violations recorded.
STAIRS/RAMPS Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 10 of 39
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
Condition 3 - Fair
Deficiency STONE: OPEN JOINTS
Roof Plan reference
Deficiency Quantity 30
Quantity Uom L.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade C
Violations No violations recorded.
WINDOWS Inspected
Replacement Quantity 8,500
Replacement Uom S.F.
EXTERIOR GUARDS Inspected
Condition 3 - Fair
Deficiency DETERIORATED/TORN-OUT/MISSING
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 11 of 39
Question Response
EXTERIOR
WINDOWS
EXTERIOR GUARDS
Elevation
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 5 - Room 215
Violations No violations recorded.
Deficiency RUST - MINOR
Roof Plan reference
Elevation
Deficiency Quantity 180
Quantity Uom S.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 12 of 39
Question Response
EXTERIOR
WINDOWS
EXTERIOR GUARDS
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
WINDOWS Inspected
Material Type(s) Aluminum
InspectedInstance on Aluminum - Double Hung: All Facades
Instance Condition 3 - Fair
Instance Quantity 8,500
Instance Quantity Uom S.F.
Installation Year 1998
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
INTERIOR Inspected
POOLS Does not Exist
STRUCTURAL Inspected
COLUMNS/BEAMS/BEARING WALLS Inspected
Condition 4 - Between Fair and Poor
Deficiency STEEL COLUMNS/BEAMS: DETERIORATED/MISSINGPLASTER FIREPROOFING
Deficiency Location/Instance Boiler Room Entry Stair
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Boiler Room Entry Stair
Violations No violations recorded.
Deficiency STEEL COLUMNS/BEAMS: MINOR RUSTING
Deficiency Location/Instance Gas Meter Room
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPAIR AND REPAINT
Urgency of Action PRIORITY 3
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 13 of 39
Question Response
INTERIOR
STRUCTURAL
COLUMNS/BEAMS/BEARING WALLS
Purpose of Action LEVEL 5
Deficiency Photo1
Gas Meter Room
Violations No violations recorded.
Deficiency STEEL COLUMNS/BEAMS: DETERIORATED/MISSINGSPRAY-ON FIREPROOFING
Deficiency Location/Instance Basement Crawlspace
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Basement Crawlspace
Violations No violations recorded.
Deficiency STEEL COLUMNS/BEAMS: DETERIORATED CONCRETEFIREPROOFING
Deficiency Location/Instance Basement Crawlspace (similar throughout Basement)
Deficiency Quantity 370
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 14 of 39
Question Response
INTERIOR
STRUCTURAL
COLUMNS/BEAMS/BEARING WALLS
Basement Crawlspace
Violations No violations recorded.
Deficiency STEEL COLUMNS/BEAMS: DETERIORATED CONCRETEFIREPROOFING
Deficiency Location/Instance Basement Crawlspace (at Vacuum Pump)
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Basement Crawlspace
Violations No violations recorded.
FLOOR STRUCTURE Inspected
Condition 4 - Between Fair and Poor
Deficiency CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED
Deficiency Location/Instance Boiler Room
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Boiler Room
Violations No violations recorded.
Deficiency CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED
Deficiency Location/Instance Basement Corridor
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 15 of 39
Question Response
INTERIOR
STRUCTURAL
FLOOR STRUCTURE
Purpose of Action LEVEL 5
Deficiency Photo1
Basement Corridor
Violations No violations recorded.
Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS
Deficiency Location/Instance Boiler Room
Deficiency Quantity 220
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Boiler Room
Violations No violations recorded.
Deficiency CONCRETE SLAB ON GRADE: THRU CRACKS
Deficiency Location/Instance Boiler Room
Deficiency Quantity 170
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
Deficiency Photo1
Boiler Room
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 16 of 39
Question Response
INTERIOR
STRUCTURAL
FLOOR STRUCTURE Inspected
Violations No violations recorded.
FOUNDATION WALLS Inspected
Material Type(s) Concrete
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF STRUCTURE Inspected
Condition 3 - Fair
Deficiency CONCRETE: CRACKED/SPALLED/REINFORCEMENTEXPOSED
Deficiency Location/Instance Auditorium Fan Room
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Auditorium Fan Room
Violations No violations recorded.
VAULTS-BUNKERS Does not Exist
AUDITORIUM Inspected
InspectedInstance on 1st Floor (388 Seats)
Ceiling
InspectedInstance on 1st Floor (388 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 1st Floor (388 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed H/C Lift
InspectedInstance on 1st Floor (388 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Seating
InspectedInstance on 1st Floor (388 Seats)
Condition 1 - Good
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on 1st Floor (388 Seats)
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 17 of 39
Question Response
INTERIOR
AUDITORIUM
Floor Finish
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on 1st Floor (388 Seats)
Stage
InspectedInstance on 1st Floor (388 Seats)
Stage Inspected
InspectedInstance on 1st Floor (388 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stage Curtain Rigging Inspected
InspectedInstance on 1st Floor (388 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stage Curtains Inspected
InspectedInstance on 1st Floor (388 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on 1st Floor (388 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
InspectedInstance on 1st Floor (388 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CAFETERIA Inspected
InspectedInstance on 1st Floor
Ceiling
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency ACOUSTIC TILES ON PLASTER: DAMAGED/MISSING
Deficiency Location/Instance Right Side
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 18 of 39
Question Response
INTERIOR
CAFETERIA
Ceiling
Right Side
Violations No violations recorded.
Door(s)
InspectedInstance on 1st Floor
Condition 3 - Fair
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Entrance Near Stair D
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Entrance Near Stair D
Violations No violations recorded.
Fixed Equipment
Does not ExistInstance on 1st Floor
Floor Finish
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Near Windows, Center
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Center
Violations No violations recorded.
Sliding-folding Partition
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 19 of 39
Question Response
INTERIOR
CAFETERIA
Sliding-folding Partition
Does not ExistInstance on 1st Floor
Stage
Does not ExistInstance on 1st Floor
Walls
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
Does not ExistInstance on 1st Floor
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Room 310, Corridor near Room 316
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 310
Violations No violations recorded.
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Rooms 103, 112, 162, 213, 308, and others
Deficiency Quantity 7
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 20 of 39
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Door(s) Inspected
Deficiency Photo1
Room 308
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency WOOD: DAMAGED/DETERIORATED
Deficiency Location/Instance Rooms 208, 209
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 208
Violations No violations recorded.
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Corridor near Room 256, Room 204
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 21 of 39
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish Inspected
Corridor near Room 256
Violations No violations recorded.
Deficiency TERRAZZO: CRACKS
Deficiency Location/Instance Corridor near Room 148
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 148
Violations No violations recorded.
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Room 206, Corridor near Rooms 211, 263, 312, 360, and others
Deficiency Quantity 1,000
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 360
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Specialties Does not Exist
GYMNASIUM Inspected
InspectedInstance on 1st Floor
Ceiling
InspectedInstance on 1st Floor
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 22 of 39
Question Response
INTERIOR
GYMNASIUM
Ceiling
Condition 3 - Fair
Deficiency METAL PAN: DAMAGED/MISSING
Deficiency Location/Instance Right Side, Left Side, Center
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Right Side
Violations No violations recorded.
Door(s)
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Equipment
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Seating
InspectedInstance on 1st Floor
Condition 3 - Fair
Deficiency DAMAGED FIXED SEATING
Deficiency Location/Instance Center
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 23 of 39
Question Response
INTERIOR
GYMNASIUM
Seating
Deficiency Photo1
Center
Violations No violations recorded.
Sliding-folding Partition
Does not ExistInstance on 1st Floor
Stage
Does not ExistInstance on 1st Floor
Walls
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
Does not ExistInstance on 1st Floor
INTERIOR DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
INTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
KITCHEN Inspected
InspectedInstance on 1st Floor
Ceiling
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 1st Floor
Condition 3 - Fair
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Store Room
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 24 of 39
Question Response
INTERIOR
KITCHEN
Door(s)
Deficiency Photo1
Store Room
Violations No violations recorded.
Floor Finish
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LIBRARY Inspected
InspectedInstance on Room 307
Built-in Furnishing
InspectedInstance on Room 307
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Ceiling
InspectedInstance on Room 307
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Room 307
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on Room 307
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Near Entrance
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 25 of 39
Question Response
INTERIOR
LIBRARY
Floor Finish
Deficiency Photo1
Near Entrance
Violations No violations recorded.
Walls
InspectedInstance on Room 307
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LOCKER ROOM Inspected
InaccessibleInstance on 1st Floor
MULTI-PURPOSE ROOM Does not Exist
SCIENCE DEMO ROOM Does not Exist
SCIENCE LAB Inspected
InspectedInstance on Room 313
Alternative use No
Fixed Equipment
InspectedInstance on Room 313
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
SCIENCE PREP ROOM Does not Exist
SHOWER ROOM Inspected
InaccessibleInstance on 1st Floor
STAIRS/RAMPS: INTERIOR Inspected
Do Letter Stair Signs Exist? Yes
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 5 - Poor
Deficiency METAL: DETERIORATED DOOR AND FRAME
Deficiency Location/Instance Stair D/1 Vestibule
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 26 of 39
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Door(s)
Deficiency Photo1
Stair D/1 Vestibule
Violations No violations recorded.
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Stair B/1
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair B/1
Violations No violations recorded.
Partition Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Railings Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stairs and Landings Inspected
Condition 3 - Fair
Deficiency TERRAZZO: CRACKS
Deficiency Location/Instance Stair B/1
Deficiency Quantity 45
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 27 of 39
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Stairs and Landings
Deficiency Photo1
Stair B/1
Violations No violations recorded.
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Stairs C/1,2,3, D/1,2,3
Deficiency Quantity 150
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair D/3
Violations No violations recorded.
Deficiency CONCRETE: CRACKS/SPALLING - MAJOR
Deficiency Location/Instance Stair A/Bulkhead
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair A/Bulkhead
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 28 of 39
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR Inspected
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TOILET ROOMS - STAFF Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Room 148
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 148
Violations No violations recorded.
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Rooms 257, 357
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 357
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 29 of 39
Question Response
INTERIOR
TOILET ROOMS - STAFF Inspected
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Rooms 257, 357
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 357
Violations No violations recorded.
TOILET ROOMS - STUDENTS Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Rooms 262, 263
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 263
Violations No violations recorded.
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: MISSING DOOR
Deficiency Location/Instance Rooms 262, 263, 362, 364
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 30 of 39
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Door(s)
Deficiency Quantity 4
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 362
Violations No violations recorded.
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Room 255, Near Room 102
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 255
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/MISSING TILES
Deficiency Location/Instance Room 256, Inside Room 166
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 31 of 39
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Floor Finish
Deficiency Photo1
Room 256
Violations No violations recorded.
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Rooms 255, 256, 362, 264
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 256
Violations No violations recorded.
LIFE SAFETY Inspected
F.D. HOLDING AREA Does not Exist
STEEL STAIRS Does not Exist
SITE Inspected
CONTAINERIZATION Inspected
Condition 5 - Poor
Deficiency CONTAINER DAMAGED
Deficiency Location/Instance Near Beach 134th Street
Deficiency Quantity 3
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 32 of 39
Question Response
SITE
CONTAINERIZATION
Deficiency Photo1
Near Beach 134th Street
Violations No violations recorded.
Drainage System for Asphalt Inspected
Catch Basins/Manhole - Surrounded by asphalt Inspected
Condition 3 - Fair
Deficiency DAMAGED COVER
Deficiency Location/Instance Schoolyard Near Beach 134th Street
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Schoolyard Near Beach 134th Street
Violations No violations recorded.
Culverts - Asphalt Covering Does not Exist
Drainage System for Concrete Does not Exist
Drainage System for Soil Inspected
Catch Basins/Manhole - Surrounded by Soil Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Soil Covering Does not Exist
DRINKING FOUNTAINS Inspected
Condition 5 - Poor
Deficiency INOPERABLE
Deficiency Location/Instance Schoolyard
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 33 of 39
Question Response
SITE
DRINKING FOUNTAINS Inspected
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
FENCES Inspected
Condition 3 - Fair
Deficiency CHAIN LINK: MISSING SECTIONS
Deficiency Location/Instance Along Beach 134th Street
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Along Beach 134th Street
Violations No violations recorded.
Deficiency CONCRETE CURB: DAMAGED/DETERIORATED
Deficiency Location/Instance Along Beach 135th Street, Along Cronston Avenue
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Along Beach 135th Street
Violations No violations recorded.
IRRIGATION SYSTEM Does not Exist
PAVING Inspected
Student Non-Use Inspected
Gravel Exists? No
Asphalt Inspected
Condition 3 - Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 34 of 39
Question Response
SITE
PAVING
Student Non-Use
Asphalt
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Near Beach 134th Street
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Beach 134th Street
Violations No violations recorded.
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Pavers Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
Student Use Inspected
Gravel Exists? No
Asphalt Inspected
Condition 4 - Between Fair and Poor
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Schoolyard
Deficiency Quantity 600
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Schoolyard
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 35 of 39
Question Response
SITE
PAVING
Student Use
Concrete Inspected
Condition 3 - Fair
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Schoolyard
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Schoolyard
Violations No violations recorded.
Pavers Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Site Sidewalks & Walkways Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance Near Beach 135th Street
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Beach 135th Street
Violations No violations recorded.
Pavers Does not Exist
DOT Sidewalk Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 36 of 39
Question Response
SITE
PAVING
DOT Sidewalk
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance Beach 135th Street, Beach 134th Street
Deficiency Quantity 150
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Beach 135th Street
Violations No violations recorded.
Deficiency DAMAGED CURBS
Deficiency Location/Instance Beach 135th Street, Beach 134th Street
Deficiency Quantity 95
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Beach 135th Street
Violations No violations recorded.
Pavers Does not Exist
PLAYGROUNDS Inspected
InspectedInstance on Along Beach 135th Street
InspectedInstance on Along Beach 134th Street
Benches
InspectedInstance on Along Beach 135th Street
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 37 of 39
Question Response
SITE
PLAYGROUNDS
Benches
InspectedInstance on Along Beach 134th Street
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fence
InspectedInstance on Along Beach 134th Street
Condition 3 - Fair
Deficiency CHAIN LINK: DAMAGED/DETERIORATED
Deficiency Location/Instance North Side
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
North Side
Violations No violations recorded.
Pavement
InspectedInstance on Along Beach 135th Street
Condition 4 - Between Fair and Poor
Deficiency ASPHALT: CRACKS - MAJOR
Deficiency Location/Instance South Side, North Side
Deficiency Quantity 400
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
South Side
Violations No violations recorded.
Play Equipment
InspectedInstance on Along Beach 134th Street
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 38 of 39
Question Response
SITE
PLAYGROUNDS
Play Equipment
Condition 5 - Poor
Deficiency BROKEN/DETERIORATED/MISSING
Deficiency Location/Instance Playground Near Beach 134th Street
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Playground Near Beach 134th Street
Violations No violations recorded.
Safety Surfacing
InspectedInstance on Along Beach 134th Street
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on Along Beach 135th Street
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Unpaved Area
InspectedInstance on Along Beach 135th Street
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Does not ExistInstance on Along Beach 134th Street
PLAYING SURFACE Does not Exist
RETAINING WALLS Inspected
Are there any Retaining Walls 6' OR higher facing publicstreet/sidewalk?
No
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
SEATING Inspected
Benches Inspected
Concrete Does not Exist
Metal/Wood/Plastic Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Bleachers Does not Exist
SITE WALLS (NOT RETAINING WALLS) Does not Exist
STAIRS/RAMPS: EXTERIOR Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q114
PB/A&W Print Date: 6/20/2019Page 39 of 39