Asset: P.S. 127 - QUEENS, 98-01 25 AVENUE, New York, 11369
Inspection Id Inspection Type Time In Last Edited
SA : Q127 Architectural - Senior 2019-02-06 7:51 AM 2019-06-05 5:27 PM
AA : Q127 Architectural - Associate 2019-02-06 7:30 AM 2019-02-07 7:50 AM
Asset Data
Question Answer
Was the building fully accessible for inspection Yes
Principal(s) Information
Principal Name Evita Sanabria
Organization P.S. 127 - Queens
Did you meet with this Principal? Yes
Did this Principal provide feedback? Yes
Summary of Principal's Feedback The Principal's comments are as follows:1. The heating controls do not work properly.2. There are pipe leaks in the Pre-K classrooms.3. A 4th Floor Student Toilet Room has deteriorated fixtures andfinishes.
Custodian John Harley
Fireman Hosea Hines
Building Square Footage 94000
Comments on the Area None
Comments on the Stories (Floors) plus Basements 4+B
Comments on the Number of Classrooms 57
Comments on the Year Built 1927
Student Population 1255
Staff Population 150
Weather Fair
Facade Photo
Corner of 25th Avenue and 98th Street -Northeast View
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 1 of 45
Main Entrance Photo
Facade A - 25th Avenue
Roof Photo
Roof 1 - Southwest View
Have any Systems/Major Building Components been upgraded? Yes
Systems: (2) 1st Floor Student Toilet Rooms upgraded to HCcompliance; limited Roofing and Roof Drain repairs
Year: 2018
Systems: Exterior Modernization Project including: Roofing andFlashing replacement at Roofs 3, 5, 7, and 8, newParapets, Coping, Cornice, Leaders/Gutters, Roof DrainStrainers, Roof Vent Louvers, and Roof Barriers, ExteriorMasonry and Chimney repointing and repairs, newBulkhead Roofs, Exterior Guards refurbished, newAreaway Gratings and Walls repaired, Ash Hoist Doorsremoved and sealed
Year: 2016
Systems: New Schoolyard
Year: 2010
Systems: New Windows and Exterior Guards
Year: 2005
Have there been any New Building Additions? Yes
Comments on New Building Additions 1937 (+27,500sf)
Tandem Schools? No
Leased Space? No
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 2 of 45
Priority Condition
PriorityCondition ExistLast Year?
PriorityCategory
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No ProtrudingElements
Protruding metalwith sharp edgeis a potentialsafety hazard.
INTERIOR |AUDITORIUM| Fixed Seating
Seat L/22,M/28, 26, 22
Hosea Hines Fireman
Yes Tripping Hazard Severelydamaged Flooris a PotentialTripping Hazard
INTERIOR |CLASSROOMS/CORRIDORS/ADMINSPACES | FloorFinish
Room 410 Hosea Hines Fireman
Structural Engineer Required
StructuralCondition Type
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Accessibility
Accessibility Status Question Response
Is the primary or secondary entrance on an accessible route? Yes
Is the building a multi-story building? Yes
Are all floors of the building accessible through compliant means? No
Are SOME floors other than the 1st floor and basement accessible through compliantmeans?
No
Do any of the following spaces exist on the First floor? Classroom, Art Room,Auditorium, Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, ScienceLabs
Yes
For the rooms that do exist, are SOME of them accessible on the 1st floor? Yes
Boys and Girls or Unisex accessible toilets exist on the 1st floor? Yes
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
Exterior Entrances & Exits Yes
Exterior H/C Lifts No No
Exterior Ramps and Railings Yes Yes
Interior Routes
Corridor and Lobby H/C Lifts Yes Yes
Interior Corridor Doors and Hardware Yes Yes
Interior Corridors and Lobbies Yes
Interior Elevators No
Interior Lobby Doors and Hardware Yes
Interior Ramps No
Rooms & Spaces
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 3 of 45
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
Rooms & Spaces
Art Rooms No
Auditorium 1st Floor Yes Yes Yes No
Cafeteria 1st Floor Yes Yes Yes No
Classrooms 1st Floor Yes Yes
Computer Rooms No
Gymnasium 3rd Floor Yes No Not on Accessible Route Yes No
Library Room 301 Yes No Not on Accessible Route
Main Office Room 216 Yes No Not on Accessible Route
Multi-purpose Room No
Nurse's Room Room 307 Yes No Not on Accessible Route
Pool No
Science Lab Room 408 Yes No Not on Accessible Route
Toilet Rooms (Boys) 1st Floor Yes Yes
Toilet Rooms (Girls) 1st Floor Yes Yes
Toilet Rooms (Staff) None on Accessible Route Yes No Not on Accessible Route
Building Template
Inspection
Question Response
Architectural
EXTERIOR Inspected
AREAWAY Inspected
InspectedInstance on AW1-AW6
Instance Condition 2 - Between Good and Fair
Instance Quantity 6
Instance Quantity Uom EACH
Deficiency AREAWAY GRATINGS: MAJOR RUSTING / OR BROKEN
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 4 of 45
Question Response
EXTERIOR
AREAWAY
Roof Plan reference
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
AW5
Violations No violations recorded.
AWNINGS AND CANOPIES Does not Exist
CHIMNEY Inspected
Material Type(s) Masonry
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
COPING Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
CORNICE Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
DOORS Inspected
DOORS AND FRAMES Inspected
Condition 3 - Fair
Deficiency METAL CLAD: DETERIORATED DOOR AND FRAME - MINORDETERIORATION
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 5 of 45
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Roof Plan reference
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TRANSOM/SIDE LIGHT Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
EXTERIOR WALLS Inspected
Material Type(s) Masonry
Replacement Quantity 40,000
Replacement Uom S.F.
InspectedInstance on All Facades
Instance Condition 3 - Fair
Instance Quantity 40,000
Instance Quantity Uom S.F.
Deficiency BRICK: DETERIORATED MASONRY SILLS
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 6 of 45
Question Response
EXTERIOR
EXTERIOR WALLS
Elevation
Deficiency Quantity 35
Quantity Uom L.F.
Potential Action REPAIR
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade D
Violations No violations recorded.
Deficiency STONE: CHIPPED/SPALLED/BROKEN PIECES
Roof Plan reference
Elevation
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPAIR
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 7 of 45
Question Response
EXTERIOR
EXTERIOR WALLS
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade H
Violations No violations recorded.
EXTERIOR SOFFITS Does not Exist
LOADING DOCK Does not Exist
LOUVER Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
PARAPETS Inspected
Material Type(s) Masonry
Replacement Quantity 7,000
Replacement Uom C.F.
InspectedInstance on All Roofs
Instance Condition 1 - Good
Instance Quantity 7,000
Instance Quantity Uom C.F.
Deficiency No deficiencies recorded
PLAZA DECK Does not Exist
ROOF Inspected
Roofing Inspected
Replacement Quantity 26,000
Replacement Uom S.F.
ROOF HATCH/SMOKE HATCH Does not Exist
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
ROOF BARRIER Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
ROOF CAGE Does not Exist
ROOF FENCE Does not Exist
ROOFING Inspected
InspectedInstance on IRMA: Roofs 5, 7, 8
Instance Condition 1 - Good
Instance Quantity 400
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 8 of 45
Question Response
EXTERIOR
ROOF
Roofing
ROOFING
Dunnage Steel less than 18" above the Roofing?
Installation Year 2016
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
InspectedInstance on Modified Bitumen: Roof 3
Instance Condition 1 - Good
Instance Quantity 900
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 2016
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
InspectedInstance on Built-Up: Roofs 1, 2, 4, 6, 9, and 10
Instance Condition 3 - Fair
Instance Quantity 24,700
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 2005
Source of Installation Custodial Staff
Deficiency BUILT-UP: ROOFING: MAJOR ACTIVE ROOF LEAKS ININSTRUCTIONAL SPACE
Roof Plan reference
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENTREMOVAL
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 9 of 45
Question Response
EXTERIOR
ROOF
Roofing
ROOFING Inspected
Roof 2 - Room 422 (Roof 4 - Rooms 408, 409, 451, Corridor nearRoom 409, and Roof 10 - Stair J/1 similar)
Violations No violations recorded.
ROOFING DRAINS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Specialties Inspected
BULKHEAD/PENTHOUSE Inspected
Condition 4 - Between Fair and Poor
Deficiency BULKHEAD/PENTHOUSE DOORS: DETERIORATED DOORAND FRAME
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE DOOR AND FRAME
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
BH2
Violations No violations recorded.
Deficiency BULKHEAD/PENTHOUSE WALLS/INTERIOR: PLASTERCRACKS/SPALLING
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 10 of 45
Question Response
EXTERIOR
ROOF
Specialties
BULKHEAD/PENTHOUSE
Roof Plan reference
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
BH1
Violations No violations recorded.
CUPOLA/ SPIRES/ TOWERS Does not Exist
DORMER Does not Exist
DUNNAGE STEEL Does not Exist
SKYLIGHT/ROOF VENT Does not Exist
ROOF/GRAVITY TANK Does not Exist
STAIRS/RAMPS: EXTERIOR Inspected
BUILDING CHEEK/FLANK WALLS Inspected
Condition 3 - Fair
Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR
Roof Plan reference
Deficiency Quantity 10
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 11 of 45
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade H
Violations No violations recorded.
RAILINGS Inspected
Condition 3 - Fair
Deficiency RUST - MINOR
Roof Plan reference
Deficiency Quantity 70
Quantity Uom L.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
STAIRS/RAMPS Inspected
Condition 5 - Poor
Deficiency STONE: CRACKS, SPALLING
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 12 of 45
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
Roof Plan reference
Deficiency Quantity 35
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
WINDOWS Inspected
Replacement Quantity 20,000
Replacement Uom S.F.
EXTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency RUST - MINOR
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 13 of 45
Question Response
EXTERIOR
WINDOWS
EXTERIOR GUARDS
Elevation
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
WINDOWS Inspected
Material Type(s) Aluminum
InspectedInstance on Aluminum - Double Hung: All Facades
Instance Condition 2 - Between Good and Fair
Instance Quantity 17,300
Instance Quantity Uom S.F.
Installation Year 2005
Source of Installation Custodial Staff
Deficiency ALUMINUM - DOUBLE HUNG: INOPERABLE BALANCE
Roof Plan reference
Elevation
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 14 of 45
Question Response
EXTERIOR
WINDOWS
WINDOWS
Deficiency Quantity 20
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
InspectedInstance on Aluminum - Other: Facades A, F, H
Instance Condition 3 - Fair
Instance Quantity 2,700
Instance Quantity Uom S.F.
Installation Year 1995
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
INTERIOR Inspected
POOLS Does not Exist
STRUCTURAL Inspected
COLUMNS/BEAMS/BEARING WALLS Inspected
Condition 3 - Fair
Deficiency STEEL COLUMNS/BEAMS: DETERIORATED CONCRETEFIREPROOFING
Deficiency Location/Instance Basement (Throughout)
Deficiency Quantity 120
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Boiler Room
Violations No violations recorded.
FLOOR STRUCTURE Inspected
Condition 3 - Fair
Deficiency CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED
Deficiency Location/Instance Basement
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 15 of 45
Question Response
INTERIOR
STRUCTURAL
FLOOR STRUCTURE
Deficiency Photo1
Basement Storage Room
Violations No violations recorded.
Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS
Deficiency Location/Instance Basement
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Basement Storage Room
Violations No violations recorded.
Deficiency CONCRETE SLAB ON GRADE: THRU CRACKS
Deficiency Location/Instance Basement
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
Deficiency Photo1
Boiler Room
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 16 of 45
Question Response
INTERIOR
STRUCTURAL
FOUNDATION WALLS Inspected
Material Type(s) Concrete, Masonry
Condition 4 - Between Fair and Poor
Deficiency CONCRETE: CRACKED/SPALLED/REINFORCEMENTEXPOSED
Deficiency Location/Instance Basement
Deficiency Quantity 90
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
Deficiency Photo1
Boiler Room
Violations No violations recorded.
Deficiency BRICK: OPEN JOINTS
Deficiency Location/Instance Basement
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Basement Storage Room
Violations No violations recorded.
Deficiency CONCRETE: WATER INFILTRATION IN ELECTRICAL PANELROOM
Deficiency Location/Instance Electrical Panel Room
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action INSTALL WATERPROOFING
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 17 of 45
Question Response
INTERIOR
STRUCTURAL
FOUNDATION WALLS
Deficiency Photo1
Electrical Panel Room
Violations No violations recorded.
ROOF STRUCTURE Inspected
Condition 4 - Between Fair and Poor
Deficiency CONCRETE: CRACKED/SPALLED/REINFORCEMENTEXPOSED
Deficiency Location/Instance Penthouse
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
Deficiency Photo1
PH
Violations No violations recorded.
VAULTS-BUNKERS Inspected
Foundation Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Slab Structure Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Vault/Ash Hoist Doors and Framing Does not Exist
AUDITORIUM Inspected
InspectedInstance on 1st Floor (585 seats)
Ceiling
InspectedInstance on 1st Floor (585 seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 18 of 45
Question Response
INTERIOR
AUDITORIUM
Door(s)
InspectedInstance on 1st Floor (585 seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed H/C Lift
Does not ExistInstance on 1st Floor (585 seats)
Fixed Seating
InspectedInstance on 1st Floor (585 seats)
Condition 3 - Fair
Deficiency DAMAGED/BROKEN/INOPERABLE
Deficiency Location/Instance Seat L/22, M/28, 27, 26, 22, 19, N/7, R/21, U/5
Deficiency Quantity 9
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Seat R/21
Violations No violations recorded.
Deficiency DAMAGED/BROKEN/INOPERABLE
Deficiency Location/Instance Seat D/28, E/24, G/7, N/26, S/26, and others
Deficiency Quantity 30
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Seat E/24
Violations No violations recorded.
Floor Finish
InspectedInstance on 1st Floor (585 seats)
Condition 2 - Between Good and Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 19 of 45
Question Response
INTERIOR
AUDITORIUM
Floor Finish
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on 1st Floor (585 seats)
Stage
InspectedInstance on 1st Floor (585 seats)
Stage Inspected
InspectedInstance on 1st Floor (585 seats)
Condition 3 - Fair
Deficiency RAILINGS/ BROKEN BRACKET
Deficiency Location/Instance Stage left, Stage right
Deficiency Quantity 2
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stage left
Violations No violations recorded.
Stage Curtain Rigging Inspected
InspectedInstance on 1st Floor (585 seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stage Curtains Inspected
InspectedInstance on 1st Floor (585 seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on 1st Floor (585 seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
InspectedInstance on 1st Floor (585 seats)
Condition 3 - Fair
Deficiency WORN/DAMAGED CURTAINS
Deficiency Location/Instance Left side, Right side
Deficiency Quantity 120
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 20 of 45
Question Response
INTERIOR
AUDITORIUM
Window Curtains/Shades/Blinds
Purpose of Action LEVEL 2
Deficiency Photo1
Right side
Violations No violations recorded.
CAFETERIA Inspected
InspectedInstance on 1st Floor
Ceiling
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Equipment
Does not ExistInstance on 1st Floor
Floor Finish
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Near Kitchen, Center of Room , Near the center Columns
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Kitchen
Violations No violations recorded.
Sliding-folding Partition
Does not ExistInstance on 1st Floor
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 21 of 45
Question Response
INTERIOR
CAFETERIA
Stage
Does not ExistInstance on 1st Floor
Walls
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
Does not ExistInstance on 1st Floor
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency ACOUSTIC TILES ON PLASTER: DAMAGED/MISSING
Deficiency Location/Instance Room 106
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 106
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK
Deficiency Location/Instance Room 105, 408, 409 , 451 Corridor near Room 409
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Room 408
Violations No violations recorded.
Deficiency ACOUSTIC TILES: DAMAGED/MISSING - ACTIVE LEAK
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 22 of 45
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Deficiency Location/Instance Room 422
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Room 422
Violations No violations recorded.
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Room 202, 203, 205, 414, 420, and others
Deficiency Quantity 15
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 205
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: TRIPPING HAZARD - ELECTRICAL OUTLET
Deficiency Location/Instance Room 216
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 23 of 45
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish
Deficiency Photo1
Room 216
Violations No violations recorded.
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Room 216, 408
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 216
Violations No violations recorded.
Deficiency WOOD: DAMAGED/DETERIORATED
Deficiency Location/Instance Room 218
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 218
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 24 of 45
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish
Deficiency CONCRETE: CRACKS
Deficiency Location/Instance Room 451
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 451
Violations No violations recorded.
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Corridor near Room 418, 421 Room 214, 421
Deficiency Quantity 600
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 418
Violations No violations recorded.
Deficiency TERRAZZO: CRACKS
Deficiency Location/Instance Corridor near Room 109, 157
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 25 of 45
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish
Deficiency Photo1
Corridor near Room 157
Violations No violations recorded.
Deficiency WOOD: DETERIORATED SUBSTRATE
Deficiency Location/Instance Room 410
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Room 410
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK
Deficiency Location/Instance Room 408
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 26 of 45
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Walls
Room 408
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Room 454 Corridor near Room 255A, 315
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 315
Violations No violations recorded.
Deficiency SALT GLAZED BRICK: CRACKS/SPALLING
Deficiency Location/Instance Corridor near Room 423
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 423
Violations No violations recorded.
Specialties Does not Exist
GYMNASIUM Inspected
InspectedInstance on 3rd Floor
Ceiling
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 27 of 45
Question Response
INTERIOR
GYMNASIUM
Door(s)
InspectedInstance on 3rd Floor
Condition 3 - Fair
Deficiency WOOD: DETERIORATED DOOR AND FRAME
Deficiency Location/Instance Rear Room
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Rear Room
Violations No violations recorded.
Fixed Equipment
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency WOOD: DAMAGED/DETERIORATED
Deficiency Location/Instance Rear of Room
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Rear of Room
Violations No violations recorded.
Seating
InspectedInstance on 3rd Floor
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 28 of 45
Question Response
INTERIOR
GYMNASIUM
Seating
Condition 3 - Fair
Deficiency DAMAGED FIXED SEATING
Deficiency Location/Instance Near windows
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near windows
Violations No violations recorded.
Sliding-folding Partition
Does not ExistInstance on 3rd Floor
Stage
Does not ExistInstance on 3rd Floor
Walls
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Rear Room
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Rear Room
Violations No violations recorded.
Window Curtains/Shades/Blinds
Does not ExistInstance on 3rd Floor
INTERIOR DOOR HARDWARE Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 29 of 45
Question Response
INTERIOR
INTERIOR DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
INTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
KITCHEN Inspected
InspectedInstance on 1st Floor
Ceiling
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 1st Floor
Condition 3 - Fair
Deficiency METAL: DETERIORATED DOOR AND FRAME
Deficiency Location/Instance Mop Room
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Mop Room
Violations No violations recorded.
Floor Finish
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/MISSING TILES
Deficiency Location/Instance Prep Area
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 30 of 45
Question Response
INTERIOR
KITCHEN
Floor Finish
Deficiency Photo1
Prep Area
Violations No violations recorded.
Walls
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Prep Area
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Prep Area
Violations No violations recorded.
LIBRARY Inspected
InspectedInstance on Room 301
Built-in Furnishing
InspectedInstance on Room 301
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Ceiling
InspectedInstance on Room 301
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Room 301
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 31 of 45
Question Response
INTERIOR
LIBRARY
Floor Finish
InspectedInstance on Room 301
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Center of Room
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Center of Room
Violations No violations recorded.
Walls
InspectedInstance on Room 301
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LOCKER ROOM Inspected
InspectedInstance on 4th Floor
Alternative use Yes
Ceiling
InspectedInstance on 4th Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 4th Floor
Condition 1 - Good
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on 4th Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Locker Room Lockers
Does not ExistInstance on 4th Floor
Walls
InspectedInstance on 4th Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
MULTI-PURPOSE ROOM Does not Exist
SCIENCE DEMO ROOM Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 32 of 45
Question Response
INTERIOR
SCIENCE LAB Inspected
InspectedInstance on Room 408
Alternative use No
Fixed Equipment
InspectedInstance on Room 408
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
SCIENCE PREP ROOM Does not Exist
SHOWER ROOM Inspected
InspectedInstance on 4th Floor
Alternative use Yes
Ceiling
InspectedInstance on 4th Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 4th Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on 4th Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on 4th Floor
Condition 3 - Fair
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Rear of Room
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Rear of Room
Violations No violations recorded.
STAIRS/RAMPS: INTERIOR Inspected
Do Letter Stair Signs Exist? Partially
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 33 of 45
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Ceiling
Deficiency Location/Instance Stair J/1 Exit Vestibule
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Stair J/1 Exit Vestibule
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Stair M/1 Exit Vestibule
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair M/1 Exit Vestibule
Violations No violations recorded.
Door(s) Inspected
Condition 3 - Fair
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Exit Vestibule 9
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 34 of 45
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Door(s)
Deficiency Photo1
Exit Vestibule 9
Violations No violations recorded.
Deficiency METAL CLAD WOOD: DETERIORATED DOOR
Deficiency Location/Instance Stair M/2
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair M/2
Violations No violations recorded.
Partition Does not Exist
Railings Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stairs and Landings Inspected
Condition 2 - Between Good and Fair
Deficiency STONE: BROKEN/MISSING
Deficiency Location/Instance Stair A/1, Exit Vestibule 6
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 35 of 45
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Stairs and Landings
Deficiency Photo1
Stair A/1
Violations No violations recorded.
Deficiency STONE: WORN-OUT TREAD/NOSINGS
Deficiency Location/Instance Stair A/2
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair A/2
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Stair J/2
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 36 of 45
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR Inspected
Walls Inspected
Stair J/2
Violations No violations recorded.
TOILET ROOMS - STAFF Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Room 257
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 257
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency ROLLED ASPHALT: CRACKS
Deficiency Location/Instance Room 460
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 460
Violations No violations recorded.
Stalls Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 37 of 45
Question Response
INTERIOR
TOILET ROOMS - STAFF Inspected
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Room 257, 356
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 356
Violations No violations recorded.
TOILET ROOMS - STUDENTS Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Room 355
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 355
Violations No violations recorded.
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Room 354, 454
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 38 of 45
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Door(s)
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 454
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Room 256, 454
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 256
Violations No violations recorded.
LIFE SAFETY Inspected
F.D. HOLDING AREA Does not Exist
STEEL STAIRS Does not Exist
SITE Inspected
CONTAINERIZATION Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 39 of 45
Question Response
SITE
CONTAINERIZATION
Condition 5 - Poor
Deficiency FENCING MISSING
Deficiency Location/Instance Parking lot
Deficiency Quantity 900
Quantity Uom S.F.
Potential Action INSTALL NEW
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Deficiency CONCRETE PAD MISSING
Deficiency Location/Instance Parking lot
Deficiency Quantity 400
Quantity Uom S.F.
Potential Action INSTALL NEW
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Deficiency CONTAINER DAMAGED
Deficiency Location/Instance Parking lot
Deficiency Quantity 3
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Parking lot
Violations No violations recorded.
Drainage System for Asphalt Inspected
Catch Basins/Manhole - Surrounded by asphalt Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Asphalt Covering Does not Exist
Drainage System for Concrete Inspected
Catch Basins/Manhole - Surrounded by concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Concrete Covering Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 40 of 45
Question Response
SITE
Drainage System for Soil Inspected
Catch Basins/Manhole - Surrounded by Soil Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Soil Covering Does not Exist
DRINKING FOUNTAINS Does not Exist
FENCES Inspected
Condition 4 - Between Fair and Poor
Deficiency CONCRETE CURB: DAMAGED/DETERIORATED
Deficiency Location/Instance 98th Street, Parking lot, 25th Avenue
Deficiency Quantity 140
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
98th Street
Violations No violations recorded.
Deficiency WROUGHT IRON: DAMAGED/DETERIORATED
Deficiency Location/Instance Parking lot, 25th Avenue, 98th Street
Deficiency Quantity 440
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Parking lot
Violations No violations recorded.
IRRIGATION SYSTEM Does not Exist
PAVING Inspected
Student Non-Use Inspected
Gravel Exists? No
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 41 of 45
Question Response
SITE
PAVING
Student Non-Use
Asphalt Inspected
Condition 3 - Fair
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Parking lot
Deficiency Quantity 300
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Parking lot
Violations No violations recorded.
Concrete Inspected
Condition 3 - Fair
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance Parking lot
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Parking lot
Violations No violations recorded.
Pavers Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Student Use Inspected
Gravel Exists? No
Asphalt Does not Exist
Concrete Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 42 of 45
Question Response
SITE
PAVING
Student Use
Concrete
Condition 3 - Fair
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance Schoolyard
Deficiency Quantity 125
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Schoolyard
Violations No violations recorded.
Pavers Does not Exist
Site Sidewalks & Walkways Inspected
Asphalt Inspected
Condition 3 - Fair
Deficiency CRACKS - MAJOR
Deficiency Location/Instance North side
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
North side
Violations No violations recorded.
Concrete Inspected
Condition 3 - Fair
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance Exit to 98th Street, Exit to 25th Avenue
Deficiency Quantity 75
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 43 of 45
Question Response
SITE
PAVING
Site Sidewalks & Walkways
Concrete
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Exit to 98th Street
Violations No violations recorded.
Pavers Does not Exist
DOT Sidewalk Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 4 - Between Fair and Poor
Deficiency DAMAGED CURBS
Deficiency Location/Instance 98th Street, 25th Avenue
Deficiency Quantity 200
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
98th Street
Violations No violations recorded.
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance 98th Street, 25th Avenue
Deficiency Quantity 900
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 44 of 45
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
Deficiency Photo1
98th Street
Violations No violations recorded.
Pavers Does not Exist
PLAYGROUNDS Does not Exist
PLAYING SURFACE Does not Exist
RETAINING WALLS Does not Exist
SEATING Does not Exist
SITE WALLS (NOT RETAINING WALLS) Does not Exist
STAIRS/RAMPS: EXTERIOR Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q127
PB/A&W Print Date: 6/21/2019Page 45 of 45