Asset: GRAND STREET CAMPUS (OLD E.D.HS)-K, 850 GRAND STREET, New York, 11225
Inspection Id Inspection Type Time In Last Edited
SA : K450 Architectural - Senior 2019-04-03 7:37 AM 2019-06-04 5:05 PM
AA : K450 Architectural - Associate 2019-04-03 7:44 AM 2019-06-03 9:30 AM
Asset Data
Question Answer
Was the building fully accessible for inspection No
Inspection Access Comment Dunnage Steel, Window Lintels, Roof Fence, Areaways, Railings,Fence, Student Use Asphalt, Security Lights due to Scaffolding,Netting, Sidewalk Bridge.Boys, Girls Shower Rooms Sealed Off.
Principal(s) Information
Principal Name Dr. Jasmine Pena
Organization Progress High School for Professional Careers - Brooklyn
Did you meet with this Principal? Yes
Did this Principal provide feedback? Yes
Summary of Principal's Feedback The Principal's commented as follows: 1. The Staff Toilet Rooms needto be upgraded.
Principal Name Rosemary Vega
Organization East Williamsburg Scholars Academy - Brooklyn
Did you meet with this Principal? Yes
Did this Principal provide feedback? Yes
Summary of Principal's Feedback The Principal's comments are as follows: 1. The Corridor Ceiling Tilesneed to be replaced.2. The Science Rooms need to be upgraded.
Principal Name Holger Carrillo
Organization High School for Enterprise, Business and Technology - Brooklyn
Did you meet with this Principal? Yes
Did this Principal provide feedback? Yes
Summary of Principal's Feedback The Principal had no comments about the physical condition of thebuilding at this time.
Principal Name Kara Ahmed
Organization L.Y.F.E. Center - Brooklyn
Did you meet with this Principal? No
Did this Principal provide feedback? No
Custodian Abe DaSilva
Fireman John Chung
Building Square Footage 480000
Comments on the Area None
Comments on the Stories (Floors) plus Basements 4+B+PH
Comments on the Number of Classrooms 107
Comments on the Year Built 1980
Student Population 1820
Staff Population 213
Weather Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 1 of 51
Facade Photo
Corner of Grand Street and BushwickAvenue - Southeast view
Main Entrance Photo
Facade A - Grand Street
Roof Photo
Roof 1 - Southwest view
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 2 of 51
Have any Systems/Major Building Components been upgraded? Yes
Systems: New L.Y.F.E. Center.
Year: 2014
Systems: Partial (4) Exterior Doors replacement; Partial PerimeterWindows re-caulking.
Year: 2009
Systems: Exterior Walls repointing and repairs; Science Labupgrade; Roofing and Soffits repairs.
Year: 2008
Systems: Auditorium Roofing repairs: Partial Perimeter Windowsre-caulking; Plaza Deck Roofing and Flashingreplacement.
Year: 2000
Have there been any New Building Additions? No
Tandem Schools? No
Leased Space? No
Priority Condition
PriorityCondition ExistLast Year?
PriorityCategory
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No Potential FallingDebris
Severelydamaged plasterceiling withloose particle isa potentialsafety hazard.
INTERIOR |CLASSROOMS/CORRIDORS/ADMINSPACES |Ceiling
Room 450A John Chung Fireman
No ProtrudingElements
Severelydamage seatwith protrudingmetal is apotential safetyhazard.
INTERIOR |AUDITORIUM| Fixed Seating
Seat BB/103 John Chung Fireman
Yes ProtrudingElements
Severelydamagedbleacher plasticseats withprotruding metalis a potentialsafety hazard.
INTERIOR |GYMNASIUM |Seating
Along theperimeter onboth side
John Chung Fireman
Structural Engineer Required
StructuralCondition Type
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Accessibility
Accessibility Status Question Response
Is the primary or secondary entrance on an accessible route? Yes
Is the building a multi-story building? Yes
Are all floors of the building accessible through compliant means? Yes
Accessible classrooms exists on each floor? Yes
Boys and Girls or Unisex accessible toilets exist on at least every other floor? Yes
If the following spaces exist, are they ALL accessible? Art Room, Auditorium,Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs
Yes
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 3 of 51
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
Exterior Entrances & Exits Yes
Exterior H/C Lifts No No
Exterior Ramps and Railings Yes Yes
Interior Routes
Corridor and Lobby H/C Lifts No No
Interior Corridor Doors and Hardware Yes Yes
Interior Corridors and Lobbies No Change in Elevation
Interior Elevators Yes Yes
Interior Lobby Doors and Hardware Yes
Interior Ramps Yes Yes
Rooms & Spaces
Art Rooms Rooms 158, 162, 326, 353, 365 Yes Yes
Auditorium 2nd Floor Yes No No Stage Access No Yes
Cafeteria 1st Floor - Staff, Students A, B Yes Yes No Yes
Classrooms 1st-4th Floor Yes Yes
Computer Rooms Rooms G297, G298, 330, 360C, 450A,450D, 462
Yes Yes
Gymnasium 1st Floor - BGA, BGC, GGA, GGC Yes Yes No Yes
Library Room 235 Yes Yes
Main Office Room 198 (L.Y.F.E. Center); Room 258B(Progress High School for ProfessionalCareers); Room A362 (East WilliamsburgScholar Academy); Room 414 (HighSchool for Enterprise, Business,Technology)
Yes Yes
Multi-purpose Room No
Nurse's Room Rooms 102, 106 Yes Yes
Pool No
Science Lab Rooms G280, G283, A369, A375, A377,453, 457
Yes Yes
Toilet Rooms (Boys) 1st-4th Floor Yes Yes
Toilet Rooms (Girls) 1st-4th Floor Yes Yes
Toilet Rooms (Staff) 1st-4th Floor Yes Yes
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 4 of 51
Building Template
Inspection
Question Response
Architectural
EXTERIOR Inspected
AREAWAY Inspected
InaccessibleInstance on AW1-AW2
Instance Quantity 2
Instance Quantity Uom EACH
AWNINGS AND CANOPIES Inspected
Condition 4 - Between Fair and Poor
Deficiency CONCRETE: WATER PENETRATION
Roof Plan reference
Deficiency Quantity 130
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 5 of 51
Question Response
EXTERIOR
AWNINGS AND CANOPIES
Deficiency Photo1
Facade E
Violations No violations recorded.
CHIMNEY Under Construction
COPING Under Construction
CORNICE Does not Exist
DOORS Inspected
DOORS AND FRAMES Inspected
Condition 5 - Poor
Deficiency METAL: DETERIORATED DOOR AND FRAME - MAJORDETERIORATION
Roof Plan reference
Deficiency Quantity 14
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade P
Violations No violations recorded.
Deficiency METAL: DETERIORATED DOOR AND FRAME - MINORDETERIORATION
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 6 of 51
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Roof Plan reference
Deficiency Quantity 12
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TRANSOM/SIDE LIGHT Inspected
Condition 4 - Between Fair and Poor
Deficiency METAL: DENTED, MAJOR RUSTING
Roof Plan reference
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 7 of 51
Question Response
EXTERIOR
DOORS
TRANSOM/SIDE LIGHT
Deficiency Photo1
Facade C
Violations No violations recorded.
EXTERIOR WALLS Inspected
Material Type(s) Masonry, Concrete
Replacement Quantity 120,000
Replacement Uom S.F.
Under ConstructionInstance on All Brick Facades
Instance Quantity 93,900
Instance Quantity Uom S.F.
Under ConstructionInstance on All Concrete Facades C, D, E
Instance Quantity 26,100
Instance Quantity Uom S.F.
EXTERIOR SOFFITS Inspected
Condition 2 - Between Good and Fair
Deficiency CONCRETE: MINOR CRACKS/SPALLING
Roof Plan reference
Elevation
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 8 of 51
Question Response
EXTERIOR
EXTERIOR SOFFITS
Purpose of Action LEVEL 2
Deficiency Photo1
Facade P
Violations No violations recorded.
LOADING DOCK Does not Exist
LOUVER Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
PARAPETS Inspected
Material Type(s) Concrete, Masonry
Replacement Quantity 17,000
Replacement Uom C.F.
Under ConstructionInstance on All Brick Facades
Instance Quantity 11,900
Instance Quantity Uom C.F.
Under ConstructionInstance on All Concrete Facades A, C, D, E, I, R, S, T, U
Instance Quantity 5,100
Instance Quantity Uom C.F.
PLAZA DECK Inspected
InspectedInstance on Concrete: General Office Balcony
Instance Condition 2 - Between Good and Fair
Instance Quantity 2,600
Instance Quantity Uom S.F.
Installation Year 2000
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
ROOF Inspected
Roofing Inspected
Replacement Quantity 154,000
Replacement Uom S.F.
ROOF HATCH/SMOKE HATCH Does not Exist
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Under Construction
ROOF BARRIER Does not Exist
ROOF CAGE Does not Exist
ROOF FENCE Inaccessible
ROOFING Inspected
Under ConstructionInstance on IRMA: All Roofs
Instance Quantity 154,000
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 9 of 51
Question Response
EXTERIOR
ROOF
Roofing Inspected
ROOFING Inspected
Instance Quantity Uom S.F.
ROOFING DRAINS Under Construction
Specialties Inspected
BULKHEAD/PENTHOUSE Under Construction
CUPOLA/ SPIRES/ TOWERS Does not Exist
DORMER Does not Exist
DUNNAGE STEEL Inaccessible
SKYLIGHT/ROOF VENT Does not Exist
ROOF/GRAVITY TANK Does not Exist
STAIRS/RAMPS: EXTERIOR Inspected
BUILDING CHEEK/FLANK WALLS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
RAILINGS Inaccessible
STAIRS/RAMPS Inspected
Condition 3 - Fair
Deficiency CONCRETE: WORN-OUT TREAD/RISER/NOSING
Roof Plan reference
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade P
Violations No violations recorded.
Deficiency CONCRETE: CRACKS/SPALLING - MINOR
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 10 of 51
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
Roof Plan reference
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade P
Violations No violations recorded.
WINDOWS Inspected
Replacement Quantity 35,000
Replacement Uom S.F.
EXTERIOR GUARDS Under Construction
LINTELS Inaccessible
WINDOWS Inspected
Material Type(s) Aluminum
Under ConstructionInstance on Aluminum - Double Hung: All Facades except Facades O, N
Instance Quantity 32,300
Instance Quantity Uom S.F.
Under ConstructionInstance on Aluminum - Other: Facades O, N
Instance Quantity 2,700
Instance Quantity Uom S.F.
INTERIOR Inspected
POOLS Does not Exist
STRUCTURAL Inspected
COLUMNS/BEAMS/BEARING WALLS Inspected
Condition 2 - Between Good and Fair
Deficiency CONCRETE COLUMNS/BEAMS:CRACKED/SPALLED/REINFORCEMENT EXPOSED
Deficiency Location/Instance Basement - Shop
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 11 of 51
Question Response
INTERIOR
STRUCTURAL
COLUMNS/BEAMS/BEARING WALLS
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Basement - Shop
Violations No violations recorded.
FLOOR STRUCTURE Inspected
Condition 3 - Fair
Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS
Deficiency Location/Instance Basement - Corridor, Fan Room, Storage
Deficiency Quantity 300
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Basement - Fan Room
Violations No violations recorded.
Deficiency CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED
Deficiency Location/Instance Basement - Gas Meter Room, Fan Room
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 12 of 51
Question Response
INTERIOR
STRUCTURAL
FLOOR STRUCTURE
Deficiency Photo1
Basement - Gas Meter Room
Violations No violations recorded.
FOUNDATION WALLS Inspected
Material Type(s) Concrete
Condition 3 - Fair
Deficiency CONCRETE: CRACKED/SPALLED/REINFORCEMENTEXPOSED
Deficiency Location/Instance Basement - Corridor
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Basement - Corridor
Violations No violations recorded.
ROOF STRUCTURE Inspected
Condition 3 - Fair
Deficiency STEEL COLUMNS/BEAMS: MINOR RUSTING
Deficiency Location/Instance Gymnasium 2
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPAIR AND REPAINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1 No photo recorded
Violations No violations recorded.
VAULTS-BUNKERS Does not Exist
AUDITORIUM Inspected
InspectedInstance on 2nd Floor (14,000 SF, 1000 Seats)
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 13 of 51
Question Response
INTERIOR
AUDITORIUM
Ceiling
InspectedInstance on 2nd Floor (14,000 SF, 1000 Seats)
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Near the side entrance by Seat T/18 side
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near the side entrance by Seat T/18 side
Violations No violations recorded.
Deficiency TECTUM: DAMAGED/MISSING
Deficiency Location/Instance Near right Stage
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near right Stage
Violations No violations recorded.
Door(s)
InspectedInstance on 2nd Floor (14,000 SF, 1000 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed H/C Lift
Does not ExistInstance on 2nd Floor (14,000 SF, 1000 Seats)
Fixed Seating
InspectedInstance on 2nd Floor (14,000 SF, 1000 Seats)
Condition 2 - Between Good and Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 14 of 51
Question Response
INTERIOR
AUDITORIUM
Fixed Seating
Deficiency DAMAGED/BROKEN/INOPERABLE
Deficiency Location/Instance Seat BB/103
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Seat BB/103
Violations No violations recorded.
Deficiency DAMAGED/BROKEN/INOPERABLE
Deficiency Location/Instance Seats E/1, F/15,17, N/3, Q/5, and others
Deficiency Quantity 23
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Seat F/15
Violations No violations recorded.
Floor Finish
InspectedInstance on 2nd Floor (14,000 SF, 1000 Seats)
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Near the Sliding-Folding Partition, by Seat A/103,108, B/3
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 15 of 51
Question Response
INTERIOR
AUDITORIUM
Floor Finish
Deficiency Photo1
Near Seat A/108
Violations No violations recorded.
Sliding-folding Partition
InspectedInstance on 2nd Floor (14,000 SF, 1000 Seats)
Condition 5 - Poor
Deficiency MOTOR: INOPERABLE
Deficiency Location/Instance Between the upper and lower seats
Deficiency Quantity 2
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Stage
InspectedInstance on 2nd Floor (14,000 SF, 1000 Seats)
Stage Inspected
InspectedInstance on 2nd Floor (14,000 SF, 1000 Seats)
Condition 2 - Between Good and Fair
Deficiency DAMAGED STEPS
Deficiency Location/Instance Right Stage
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Right Stage
Violations No violations recorded.
Stage Curtain Rigging Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 16 of 51
Question Response
INTERIOR
AUDITORIUM
Stage
Stage Curtain Rigging Inspected
InspectedInstance on 2nd Floor (14,000 SF, 1000 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stage Curtains Inspected
InspectedInstance on 2nd Floor (14,000 SF, 1000 Seats)
Condition 3 - Fair
Deficiency WORN/DETERIORATED
Deficiency Location/Instance Side curtain
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Side curtain
Violations No violations recorded.
Walls
InspectedInstance on 2nd Floor (14,000 SF, 1000 Seats)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
Does not ExistInstance on 2nd Floor (14,000 SF, 1000 Seats)
CAFETERIA Inspected
InspectedInstance on 1st Floor - Staff (1,500 SF)
InspectedInstance on 1st Floor - Students A
InspectedInstance on 1st Floor - Students B
Ceiling
InspectedInstance on 1st Floor - Students A
Condition 2 - Between Good and Fair
Deficiency ACOUSTIC TILES ON PLASTER: DAMAGED/MISSING
Deficiency Location/Instance Toward the main entrance (Tectum on plaster)
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 17 of 51
Question Response
INTERIOR
CAFETERIA
Ceiling
Deficiency Photo1
Toward the main entrance (Tectum on plaster)
Violations No violations recorded.
Deficiency TECTUM: DAMAGED/MISSING
Deficiency Location/Instance Near the entrance, by Cafeteria B
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near the entrance
Violations No violations recorded.
InspectedInstance on 1st Floor - Students B
Condition 2 - Between Good and Fair
Deficiency TECTUM: DAMAGED/MISSING
Deficiency Location/Instance Near the entrance
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 18 of 51
Question Response
INTERIOR
CAFETERIA
Ceiling
Near the entrance
Violations No violations recorded.
InspectedInstance on 1st Floor - Staff (1,500 SF)
Condition 2 - Between Good and Fair
Deficiency ACOUSTIC TILES: DAMAGED/MISSING
Deficiency Location/Instance Near the window, rear
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near the window
Violations No violations recorded.
Door(s)
InspectedInstance on 1st Floor - Students B
Condition 4 - Between Fair and Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Main Entrance
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Main Entrance
Violations No violations recorded.
Fixed Equipment
Does not ExistInstance on 1st Floor - Staff (1,500 SF)
Does not ExistInstance on 1st Floor - Students A
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 19 of 51
Question Response
INTERIOR
CAFETERIA
Fixed Equipment
Does not ExistInstance on 1st Floor - Students B
Floor Finish
InspectedInstance on 1st Floor - Students B
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Near the vending machine
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near the vending machine
Violations No violations recorded.
Sliding-folding Partition
Does not ExistInstance on 1st Floor - Staff (1,500 SF)
InspectedInstance on 1st Floor - Students A
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 1st Floor - Students B
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stage
Does not ExistInstance on 1st Floor - Staff (1,500 SF)
Does not ExistInstance on 1st Floor - Students A
Does not ExistInstance on 1st Floor - Students B
Walls
InspectedInstance on 1st Floor - Staff (1,500 SF)
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance On the columns
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 20 of 51
Question Response
INTERIOR
CAFETERIA
Walls
Deficiency Photo1
On the column
Violations No violations recorded.
Window Curtains/Shades/Blinds
Does not ExistInstance on 1st Floor - Students A
Does not ExistInstance on 1st Floor - Students B
Does not ExistInstance on 1st Floor - Staff (1,500 SF)
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Room 450A
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Room 450A
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Rooms 326, 359, 406, Corridor near Room 460C
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 21 of 51
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Deficiency Photo1
Room 326
Violations No violations recorded.
Deficiency ACOUSTIC TILES: DAMAGED/MISSING
Deficiency Location/Instance Rooms G297/G298, 357, A362, 435, 437, and others
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room G298 side
Violations No violations recorded.
Deficiency TECTUM: DAMAGED/MISSING
Deficiency Location/Instance Corridor near Rooms 254, 305, 423, 437, by Stair G/4, and others
Deficiency Quantity 1,200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 254
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 22 of 51
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Door(s) Inspected
Condition 3 - Fair
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Rooms 220, 320, 420, 450A
Deficiency Quantity 4
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 450A
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency EPOXY FLOORING: CRACKS/SPALLING
Deficiency Location/Instance Rooms G280, G283
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room G283
Violations No violations recorded.
Deficiency VINYL TILES: TRIPPING HAZARD - ELECTRICAL OUTLET
Deficiency Location/Instance Rooms G298, 330, 342, 354, 360C, 360D, 450E
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 23 of 51
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish
Deficiency Photo1
Room 450E
Violations No violations recorded.
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Rooms G298, A377, 460A, 450D, Corridor near Room 230, and others
Deficiency Quantity 120
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 230
Violations No violations recorded.
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Corridor near Rooms 156, A362
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room A362
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 24 of 51
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency MASONRY: CRACKS/SPALLING
Deficiency Location/Instance Corridor near Rooms 450, 450E
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 450E
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Rooms 351, 354, 437, 440, 456, and others
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 440
Violations No violations recorded.
Specialties Inspected
Classroom Locker(s) Inspected
Condition 2 - Between Good and Fair
Deficiency DAMAGED UNITS
Deficiency Location/Instance (Total: 2,500 Lockers) Corridor near Rooms G293, 350
Deficiency Quantity 2
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 25 of 51
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Specialties
Classroom Locker(s)
Deficiency Photo1
Corridor near Room 350
Violations No violations recorded.
Fixed Seating Does not Exist
GYMNASIUM Inspected
InspectedInstance on 1st Floor - BGA
InspectedInstance on 1st Floor - BGC
InspectedInstance on 1st Floor - GGA
InspectedInstance on 1st Floor - GGC
Ceiling
InspectedInstance on 1st Floor - BGC
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Near the center
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near the center
Violations No violations recorded.
InspectedInstance on 1st Floor - BGA
Condition 2 - Between Good and Fair
Deficiency TECTUM: DAMAGED/MISSING
Deficiency Location/Instance Near the Sliding-Folding Partition
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 26 of 51
Question Response
INTERIOR
GYMNASIUM
Ceiling
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near the Sliding-Folding Partition
Violations No violations recorded.
InspectedInstance on 1st Floor - GGA
Condition 2 - Between Good and Fair
Deficiency TECTUM: DAMAGED/MISSING
Deficiency Location/Instance Near the Sliding-Folding Partition
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near the Sliding-Folding Partition
Violations No violations recorded.
Door(s)
InspectedInstance on 1st Floor - GGA
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 1st Floor - GGC
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 1st Floor - BGC
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 1st Floor - BGA
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Equipment
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 27 of 51
Question Response
INTERIOR
GYMNASIUM
Fixed Equipment
InspectedInstance on 1st Floor - GGC
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 1st Floor - BGA
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 1st Floor - BGC
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 1st Floor - GGA
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on 1st Floor - BGC
Condition 2 - Between Good and Fair
Deficiency WOOD: DAMAGED/DETERIORATED
Deficiency Location/Instance Near the center (minor heaving)
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near the center (minor heaving)
Violations No violations recorded.
Seating
InspectedInstance on 1st Floor - BGA
Condition 4 - Between Fair and Poor
Deficiency INOPERABLE BLEACHERS
Deficiency Location/Instance Gymnasium 2
Deficiency Quantity 360
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Deficiency DAMAGED BLEACHERS
Deficiency Location/Instance Along the perimeter on both side
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 28 of 51
Question Response
INTERIOR
GYMNASIUM
Seating
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Along the perimeter wall
Violations No violations recorded.
Sliding-folding Partition
InspectedInstance on 1st Floor - BGA
Condition 3 - Fair
Deficiency MOVABLE PANELS: DAMAGED
Deficiency Location/Instance Rear wall
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Rear wall
Violations No violations recorded.
Stage
Does not ExistInstance on 1st Floor - BGA
Does not ExistInstance on 1st Floor - BGC
Does not ExistInstance on 1st Floor - GGA
Does not ExistInstance on 1st Floor - GGC
Walls
InspectedInstance on 1st Floor - GGC
Condition 2 - Between Good and Fair
Deficiency WALL PADDING: DETERIORATED
Deficiency Location/Instance Near the entrance
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 29 of 51
Question Response
INTERIOR
GYMNASIUM
Walls
Deficiency Quantity 120
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near the entrance
Violations No violations recorded.
InspectedInstance on 1st Floor - BGC
Condition 2 - Between Good and Fair
Deficiency WALL PADDING: DETERIORATED
Deficiency Location/Instance On the column
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
On the column
Violations No violations recorded.
InspectedInstance on 1st Floor - GGA
Condition 4 - Between Fair and Poor
Deficiency WALL PADDING: DETERIORATED
Deficiency Location/Instance Left, right, rear wall
Deficiency Quantity 480
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 30 of 51
Question Response
INTERIOR
GYMNASIUM
Walls
Deficiency Photo1
Left wall side
Violations No violations recorded.
InspectedInstance on 1st Floor - BGA
Condition 2 - Between Good and Fair
Deficiency WALL PADDING: DETERIORATED
Deficiency Location/Instance Near the entrance
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near the entrance
Violations No violations recorded.
InspectedInstance on 1st Floor - GGA
Condition 4 - Between Fair and Poor
Deficiency MASONRY: CRACKS/SPALLING
Deficiency Location/Instance Near the Sliding-Folding Partition
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 31 of 51
Question Response
INTERIOR
GYMNASIUM
Walls
Deficiency Photo1
Near the Sliding-Folding Partition
Violations No violations recorded.
Window Curtains/Shades/Blinds
Does not ExistInstance on 1st Floor - BGC
Does not ExistInstance on 1st Floor - GGA
Does not ExistInstance on 1st Floor - GGC
Does not ExistInstance on 1st Floor - BGA
INTERIOR DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
INTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
KITCHEN Inspected
InspectedInstance on 1st Floor (3,000 SF)
Ceiling
InspectedInstance on 1st Floor (3,000 SF)
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Mop Room
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Mop Room
Violations No violations recorded.
Door(s)
InspectedInstance on 1st Floor (3,000 SF)
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 32 of 51
Question Response
INTERIOR
KITCHEN
Door(s)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on 1st Floor (3,000 SF)
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/MISSING TILES
Deficiency Location/Instance Food preparation area, Mop Room
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Food preparation area
Violations No violations recorded.
Walls
InspectedInstance on 1st Floor (3,000 SF)
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Near the Mop Room, column, by the teacher servery
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Food preparation area
Violations No violations recorded.
LIBRARY Inspected
InspectedInstance on Room 235 (3,000 SF)
Built-in Furnishing
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 33 of 51
Question Response
INTERIOR
LIBRARY
Built-in Furnishing
Does not ExistInstance on Room 235 (3,000 SF)
Ceiling
InspectedInstance on Room 235 (3,000 SF)
Condition 2 - Between Good and Fair
Deficiency ACOUSTIC TILES: DAMAGED/MISSING
Deficiency Location/Instance Near the circulation desk, by the computer/media room area
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near the circulation desk
Violations No violations recorded.
Door(s)
InspectedInstance on Room 235 (3,000 SF)
Condition 3 - Fair
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Rear entrance
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Rear entrance
Violations No violations recorded.
Floor Finish
InspectedInstance on Room 235 (3,000 SF)
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 34 of 51
Question Response
INTERIOR
LIBRARY
Floor Finish
Deficiency Location/Instance Media/Computer Room, Storage Room
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Computer/Media Room
Violations No violations recorded.
Walls
InspectedInstance on Room 235 (3,000 SF)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LOCKER ROOM Inspected
InspectedInstance on Basement - Boys (1,914 Lockers)
Alternative use No
InspectedInstance on Basement - Girls (1,914 Lockers)
Alternative use No
Ceiling
InspectedInstance on Basement - Boys (1,914 Lockers)
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Near Locker 687
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Locker 687
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 35 of 51
Question Response
INTERIOR
LOCKER ROOM
Door(s)
InspectedInstance on Basement - Boys (1,914 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on Basement - Girls (1,914 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on Basement - Boys (1,914 Lockers)
Condition 3 - Fair
Deficiency CONCRETE: CRACKS
Deficiency Location/Instance Near Locker 1777
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Locker 1777
Violations No violations recorded.
InspectedInstance on Basement - Girls (1,914 Lockers)
Condition 2 - Between Good and Fair
Deficiency CONCRETE: CRACKS
Deficiency Location/Instance Near locker 595
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near locker 595
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 36 of 51
Question Response
INTERIOR
LOCKER ROOM
Locker Room Lockers
InspectedInstance on Basement - Boys (1,914 Lockers)
Condition 5 - Poor
Deficiency DAMAGED UNITS
Deficiency Location/Instance Near lockers 76, 101, 140, 152, 511, and others
Deficiency Quantity 500
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near locker 511
Violations No violations recorded.
InspectedInstance on Basement - Girls (1,914 Lockers)
Condition 2 - Between Good and Fair
Deficiency DAMAGED UNITS
Deficiency Location/Instance Lockers 124, 448, 745, 1319
Deficiency Quantity 4
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Locker 124
Violations No violations recorded.
Walls
InspectedInstance on Basement - Boys (1,914 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on Basement - Girls (1,914 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 37 of 51
Question Response
INTERIOR
MULTI-PURPOSE ROOM Does not Exist
SCIENCE DEMO ROOM Inspected
InspectedInstance on Rooms 352, 356
Alternative use Yes
InspectedInstance on Rooms 354, 452
Alternative use Yes
InspectedInstance on Rooms 357, 435, 437, 438, 440, 454, 456
Alternative use No
InspectedInstance on Room 305
Alternative use No
Fixed Equipment
InspectedInstance on Rooms 357, 435, 437, 438, 440, 454, 456
Condition 5 - Poor
Deficiency CABINETRY: MISSING/DAMAGED
Deficiency Location/Instance Rooms 357, 435, 437, 438, 440, 454, 456
Deficiency Quantity 34
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 454
Violations No violations recorded.
InspectedInstance on Rooms 352, 356
Condition 3 - Fair
Deficiency CABINETRY: MISSING/DAMAGED
Deficiency Location/Instance Rooms 352, 356
Deficiency Quantity 8
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
SCIENCE LAB Inspected
InspectedInstance on Rooms A369, A375, A377, 453, 457
Alternative use No
InspectedInstance on Rooms G280, G283
Alternative use No
Fixed Equipment
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 38 of 51
Question Response
INTERIOR
SCIENCE LAB
Fixed Equipment
InspectedInstance on Rooms A369, A375, A377, 453, 457
Condition 5 - Poor
Deficiency CABINETRY: MISSING/DAMAGED
Deficiency Location/Instance Rooms A369, A375, A377, 453, 457
Deficiency Quantity 96
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 457
Violations No violations recorded.
SCIENCE PREP ROOM Inspected
InspectedInstance on Rooms A371/A373, 455
Alternative use No
InspectedInstance on Room G280A
Alternative use No
Fixed Equipment
InspectedInstance on Rooms A371/A373, 455
Condition 4 - Between Fair and Poor
Deficiency CABINETRY: MISSING/DAMAGED
Deficiency Location/Instance Rooms A371/A373, 455
Deficiency Quantity 16
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 455
Violations No violations recorded.
SHOWER ROOM Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 39 of 51
Question Response
INTERIOR
SHOWER ROOM Inspected
InaccessibleInstance on Basement - Boys
InaccessibleInstance on Basement - Girls
STAIRS/RAMPS: INTERIOR Inspected
Do Letter Stair Signs Exist? Partially
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Partition Does not Exist
Railings Inspected
Condition 2 - Between Good and Fair
Deficiency METAL: MISSING
Deficiency Location/Instance Room BGE (Weight Room)
Deficiency Quantity 6
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Room BGE (Weight Room)
Violations No violations recorded.
Stairs and Landings Inspected
Condition 2 - Between Good and Fair
Deficiency CONCRETE: CRACKS/SPALLING - MAJOR
Deficiency Location/Instance Stair B/Basement,1
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 40 of 51
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR Inspected
Stairs and Landings Inspected
Deficiency Photo1
Stair B/1
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TOILET ROOMS - STAFF Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Room 113T
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 113T
Violations No violations recorded.
Door(s) Inspected
Condition 5 - Poor
Deficiency METAL: DAMAGED LOUVER
Deficiency Location/Instance Rooms G190B, A261M, 229T, 415T
Deficiency Quantity 4
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 41 of 51
Question Response
INTERIOR
TOILET ROOMS - STAFF
Door(s)
Deficiency Photo1
Room 415T
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: DETERIORATED SUBSTRATE
Deficiency Location/Instance Room A261
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room A261
Violations No violations recorded.
Stalls Inspected
Condition 5 - Poor
Deficiency RUST - MAJOR
Deficiency Location/Instance Rooms 113T, A261M, 215T, 331T, inside Room 115G
Deficiency Quantity 5
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 42 of 51
Question Response
INTERIOR
TOILET ROOMS - STAFF
Stalls
Deficiency Photo1
Room 331T
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Rooms 113T, 142T,213T, 331T, 415T, and others
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 415T
Violations No violations recorded.
TOILET ROOMS - STUDENTS Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 5 - Poor
Deficiency METAL: DAMAGED LOUVER
Deficiency Location/Instance Rooms 142G, A261M, 329B, 429B, toilet inside the Boys LockerRoom, and others
Deficiency Quantity 11
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 43 of 51
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Door(s)
Deficiency Photo1
Room 429B
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Inspected
Condition 5 - Poor
Deficiency BROKEN/MISSING
Deficiency Location/Instance Toilet inside the Boys Locker Room
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Toilet inside the Boys Locker Room
Violations No violations recorded.
Deficiency RUST - MAJOR
Deficiency Location/Instance Rooms 142G, 229B, 231G, 413G, 429B
Deficiency Quantity 12
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 44 of 51
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Stalls
Deficiency Photo1
Room 429B
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Rooms 142G, A261M, 313G, 413G, 429B, and others
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 313G
Violations No violations recorded.
LIFE SAFETY Inspected
F.D. HOLDING AREA Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
STEEL STAIRS Does not Exist
SITE Inspected
CONTAINERIZATION Inspected
Condition 5 - Poor
Deficiency FENCING MISSING
Deficiency Location/Instance Waterbury Street
Deficiency Quantity 1,200
Quantity Uom S.F.
Potential Action INSTALL NEW
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 45 of 51
Question Response
SITE
CONTAINERIZATION
Deficiency Photo1
Waterbury Street
Violations No violations recorded.
Deficiency CONTAINER DAMAGED
Deficiency Location/Instance Waterbury Street
Deficiency Quantity 4
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Waterbury Street
Violations No violations recorded.
Drainage System for Asphalt Inspected
Catch Basins/Manhole - Surrounded by asphalt Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Asphalt Covering Does not Exist
Drainage System for Concrete Inspected
Catch Basins/Manhole - Surrounded by concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Concrete Covering Does not Exist
Drainage System for Soil Does not Exist
DRINKING FOUNTAINS Does not Exist
FENCES Inaccessible
IRRIGATION SYSTEM Does not Exist
PAVING Inspected
Student Non-Use Inspected
Gravel Exists? No
Asphalt Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 46 of 51
Question Response
SITE
PAVING
Student Non-Use
Asphalt
Condition 4 - Between Fair and Poor
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Parking area between the school and Athletic Field
Deficiency Quantity 800
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Parking area between the school and Athletic Field
Violations No violations recorded.
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Pavers Does not Exist
Student Use Inspected
Gravel Exists? No
Asphalt Inaccessible
Concrete Does not Exist
Pavers Does not Exist
Site Sidewalks & Walkways Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 4 - Between Fair and Poor
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance Waterbury, Grand Avenue
Deficiency Quantity 700
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 47 of 51
Question Response
SITE
PAVING
Site Sidewalks & Walkways
Concrete
Deficiency Photo1
Grand Avenue
Violations No violations recorded.
Pavers Inspected
Condition 3 - Fair
Deficiency DAMAGED/MISSING
Deficiency Location/Instance Bushwich Avenue
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Bushwich Avenue
Violations No violations recorded.
DOT Sidewalk Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 4 - Between Fair and Poor
Deficiency DAMAGED CURBS
Deficiency Location/Instance Grand Street, Bushwick Avenue, Waterbury Street
Deficiency Quantity 100
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 48 of 51
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
Deficiency Photo1
Bushwick Avenue
Violations No violations recorded.
Deficiency HEAVING
Deficiency Location/Instance Bushwick Avenue
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Bushwick Avenue
Violations No violations recorded.
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance Grand Street, Bushwick Avenue, Waterbury Street
Deficiency Quantity 2,700
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Bushwick Avenue
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 49 of 51
Question Response
SITE
PAVING Inspected
DOT Sidewalk
Concrete Inspected
Violations No violations recorded.
Pavers Does not Exist
PLAYGROUNDS Does not Exist
PLAYING SURFACE Does not Exist
RETAINING WALLS Inspected
Are there any Retaining Walls 6' OR higher facing publicstreet/sidewalk?
Yes
Condition 3 - Fair
Deficiency BRICK: DETERIORATED JOINT AT COPING STONE
Deficiency Location/Instance Corner of Grand Avenue and Bushwick Avenue
Deficiency Quantity 30
Quantity Uom L.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corner of Grand Avenue and Bushwick Avenue
Violations No violations recorded.
Deficiency BRICK: CRACKS/SPALLING - MAJOR
Deficiency Location/Instance Grand Avenue
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Grand Avenue
Violations No violations recorded.
SEATING Does not Exist
SITE WALLS (NOT RETAINING WALLS) Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450
PB/A&W Print Date: 6/20/2019Page 50 of 51
Question Response
SITE
SITE WALLS (NOT RETAINING WALLS) Does not Exist
STAIRS/RAMPS: EXTERIOR Inspected
Railings Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Site Cheek/flank Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stairs/ramps Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K450