MANUAL CODE: SYJS-006 -03 Rev.0 .
Haier Group
Auto-Restart function
Group control(with a group controller)
Auto-changeover
The same outdoor unit can match with cassette \convertible\
duct type indoor unit
With new environment friendly refrigerant R407C
Weekly timing(with a weekly timer)
Features
Service Manual
Commercial Air Conditioning
4HP 5HP UniversalOutdoor Unit air conditioning
AC36NACBEA+AU36NAIBEA
AD36NAMBEA+AU36NAIBEA
AB36NACBEA+AU36NAIBEA
Remotoe control and Wired remote control(Optional)
AC42NACBEA+AU42NAIBEA
AD42NAMBEA+AU42NAIBEA
AB42NACBEA+AU42NAIBEA
AP42NACBEA+AU42NAIBEA
AD36NAHBEA+AU36NAIBEA
AD42NAHBEA+AU42NAIBEA
8/11/2019 Op Manual AU42NAIBEA
2/149
CONTENTS
1. Description of Products & Features....2
2. Specifications. ...6
3. Safety precaution...14
4. Net dimensions of indoor and outdoor unit...17
5. Installation instructions . ..20
6. Parts and functions .....48
7. Remote controller functions.50
8. Refrigerant diagram......71
9. Electrical control functions72
10. Diagnostic information(trouble shooting).78
11. Electrical data..........................................85
12. Exploded views and parts lists................ 88
13. Perdormance curves...............................96
14. Noise level charts....................................104
15.Air velocity distribution ...............................106
CONTENTS
Contents.....................................................1
- 1 -
8/11/2019 Op Manual AU42NAIBEA
3/149
1. Description of product code and brief introduction of the series
a) Description of the coding rule of the models
A U 36 N A I B D A
Climate type:T1
Design serial number
Air conditioner
Product series:one-tag-one
Outdoor unit
Product specification:valid digit above kilobi
Adaptive voltage:38
0-400
V/50Hz
Appearance features
Product type: heat pump R407C
A B 36 N A C B D A
Climate type:T1
Design serial number
Air conditioner
Product series:one-tag-one
Product specification:valid digit above kilobi
Adaptive voltage:380-400V/50Hz
Appearance features
Product type: heat pump R407C
Product type:indoor unit
P:Cabinet typeC:Convertible typeB:Cassette type D:Duct type
b). Standard working condition
Operating ModeIndoor Operating Mode Outdoor Operating Mode
Nominal Cooling
Temp. Temp.Humidity
DB:27 WB:19 DB:35
DB:7 WB:6
WB:24
Humidity
DB:20 WB:15Nominal Heating
No.
1
2
Temp.Humidity
DB:27 WB:19 DB:35
DB:7 WB:6
WB:24
Humidity
DB:20 WB:15Nominal Heating
No.
1
2
2
8/11/2019 Op Manual AU42NAIBEA
4/149
c)Brif introduction of the series:
Convertible type:
AC36NACBEA+AU36NAIBEA AC42 NACBDA+AU42NAIBEA
(1).Ceiling convertible,flexible installation,convenient
maintenance,saving the users' expenditures(2).Adopting three-phase power supply,applicable for household
and commercial usage
(3).Dual air outlet design,floor air blowing,accelerating the indoor aircirculation, quick temperature adjustment
(4).Long-distance air blowing,large power,large cooling/heating
ratio
(5).Intelligent remote control,convenient and flexible control
(6).Super-slim indoor unit design,luxury and nice-looking,saving
space,harmonious and unitive with the indoor environment
(7).Adopting screw-fastening for the air inlet grill,firmly
fixed;adopting slipwayinsert-lock fastening method for the
filter screen,convenient cleaning or replacing the filter screen
without opening the air inlet grill.
(8).Group control,units up to 128 sets can be controlled .
Duct type :
AD36NAMBEA+AU36NAIBEA AD42NAMBEA+AU42 NAIBEA
Totally concealed machine body
All the machine body is to be installed inside the ceiling, having no effect on thebeauty of the room and without taking any room space.
Air intake via the rear air intake ductThis new design has changed the former unique pattern of air intake, and a largerdistance between air intake and air return cycles as well as better air quality can beachieved.
Flexible and easier installation
The machine body is to be installed in a totally concealed way,its fan system hasa longer distance coverage so as to supply its airflow to several rooms, and theindoor unit may be installed inside the ceiling of a room or corridor. Theinstallation is simple and flexible, and there is no need to have specified personnel
for management, thus cutting down the expenses; the machine is lighter andsmaller, and convenient for installation, it takes an extremely small building space,thus lower the construction cost; the indoor unit is to be concealed inside theceiling, and hence the usable space can be saved and the room decoration willnot be affected.
3
8/11/2019 Op Manual AU42NAIBEA
5/149
AB36NACBEA+AU36NAIBEA AB42NACBEA+AU42NAIBE A
Products characteristic:
Completely invisible machine body:The whole machine body is completely concealed inside the ceiling. Due to its compact size it neither
breaks the harmonization of indoor decoration nor occupies the indoor spaces. The stylish look of airconditioner allows it to blend right into ceiling.
Superbly efficient healthy filter:
Superbly efficient antibiotic materials are utilized and can prevent germs from
breeding efficiently .
Flexible and easy installationSlim design with machine body, completely ceiling concealing and portable shape, all make it greatly
easier to install. Moreover, it occupies least constructional spaces, which help to reduce constructional
cost prices. It also features a specific drainage system with up to 600mm lift , which allows reducing
installation spaces and ensures to drain smoothly. Thanks to its "smudge-free" mobile outlet grill,the ceiling can be protected from pollution effectively and allow the airflow to fit people's
comfortable need much more.
Compensation function of power failure:When meeting a power failure during running, no matter how long it will be, once the power isrestored, air conditioner will automatic restart with the previous status.
Safety and reliable control due to various signal controls1 Inputting with press buttons on the panel2 Inputting with temperature sensors (indoor ambient temperature sensors, indoor coil pipetemperature sensors,
3 Piping pressure signals4 Compressor current signals5 Testing signals6 System time-shorten signal
7 Water overflowing signal
8 Communication signals between indoor unit and front plate or between indoor unit and outdoorunit .
Silent designThe use of radial outward flow turbine fan produces larger cyde airflow volume and acts tosignificantly decrease operating noise.
When using remote-controlling mode, it is comfortable and convenient to operate.
Cassette type:
4
Advanced wire-controllerand convenient remote-controllerThe new wired controller can connect with 16 indoor units without any device such as detectors.
The new remote controller can be used for single unit or muti-free unit, or H-MRV,very convenient.
In addition, it can be compatible with the old remote controllers.
Low ambient temperature cooling function (optional)Equipped with high/low pressure protection switch
NEW
NEW
8/11/2019 Op Manual AU42NAIBEA
6/149
Climate type
Type of Air Conditioner T1 T2 T3
Cool only 18 43 0 35 21 52
Heat pump -7 43 -7 35 -7 52
Electricity heating 43 35 52
d). Brief Introduction for T1\ T2\ T3 working condition
Climate type
Type of Air Conditioner T1 T2 T3
Cool only 18 43 10 35 21 52
Heat pump -7 43 -7 35 -7 52
Electricity heating 43 35 52
5
8/11/2019 Op Manual AU42NAIBEA
7/149
Function Cooling Heating
Capacity BTU/h 36000 41000
W 4000 3800W 5500 5500
EER or COP BTU/W 9 10.8
Dehumidifying capacity 10m/h
Power cable
Power source NVHzA / A
Start Current A
Unit model (color)
Fan Type Number
Speed(H-M-L) r/min
Fan motor output power kW
Air-flow(H-M-L) m/h
Heat exchanger Type / Diameter mm
Total Area m
Temp. scope
External LWH mmmmmm
Package LWH mmmmmm
Drainage pipe (material , I.D./O.D.) mm
Control type (Remote /wired)
Fresh air hole dimension mm
kW
dB(A)
kg / kg
External LWH mmmmmm
Package LWH mmmmmm
k / kUnit model (color)
Compressor Model / Manufacture
Type
Fan Type Number Speed r/min
Fan motor output power kW
Air-flow(H-M-L) m/h
Heat exchanger Type / Diameter mm
Total area mTemp. scope
External LWH mmmmmm
Package LWH mmmmmm
Drainage pipe (material , I.D./O.D.) mm
Refrigerant control method mm/mm
Volume of Accumulator L
Noise level dB(A)
material of reduce noise
crankcase heater power Wkg / kg
Refrigerant Type / Charge g
Recharge quantity g/m
Liquid mm
Gas mm
Connecting Method
m
m
/
43/41/39
/
/
//
/
/
/
/
Remote
/
2-7
1325920370
PVC 26/32
MAX.Piping length 50
Weight (Net / Shipping) /
Type of Four way valve /
/
Defrosting
PIPING
R407C 3800
65
Pipe 9.52
19.05
Falre
Between I.D &O.MAX.Drop 30
Dimension /
/
//
/
/
/
/
Outdoorunit
/
Weight (Net / Shipping) 46/53
Panel Dimension 134095080
1400995115Weight (Net / Shipping)
/
45
Dimension 1230840280
/
0.06
1980/-/-
Centrifugal*1
590+30/490+40/420+50
TP2M/7
item Model AB36NACBEA(SANYO)
5
/
Total power inputMax. power input
Running /Max.Running
8.4/12
3N~ 380V-400V 50HZ
Indoorunit
AB36NACBEA(WHITE)
Noise level (H-M-L)
Electricity Heater
cooling7.5/9.5heating6.5/9.5
2.Specifications
6
8/11/2019 Op Manual AU42NAIBEA
8/149
Function Cooling Heating
Capacity BTU/h 36000 41000
W 4000 3800
W 5500 5500
EER or COP BTU/W 9 10.8
Dehumidifying capacity 10m/h
Power cable
Power source NVHz
A / A
Start Current A
Unit model (color)
Fan Type Number
Speed(H-M-L) r/min
Fan motor output power kW
Air-flow(H-M-L) m/h
Heat exchanger Type / Diameter mm
Total Area m
Temp. scope
External LWH mmmmmm
Package LWH mmmmmmDrainage pipe (material , I.D./O.D.) mm
Control type (Remote /wired)
Fresh air hole dimension mm
kW
dB(A)
kg / kg
External LWH mmmmmm
Package LWH mmmmmm
kg / kg
Unit model (color)
Compressor Model / Manufacture
TypeFan Type Number
Speed r/min
Fan motor output power kW
Air-flow(H-M-L) m/h
Heat exchanger Type / Diameter mm
Total area m
Temp. scope
External LWH mmmmmm
Package LWH mmmmmm
Drainage pipe (material , I.D./O.D.) mm
Refrigerant control method mm/mm
Volume of Accumulator LNoise level dB(A)
material of reduce noise
crankcase heater power W
kg / kg
Refrigerant Type / Charge g
Recharge quantity g/m
Liquid mm
Gas mm
Connecting Method
m
m
cooling7.5/9.5heating6.5/9.5
45
Dimension
3pH,380V-400V 50HZ
item Model AC36NACBEA(SANYO)
5
/
0.06
1600/1400/1200
Noise level (H-M-L)
Electricity Heater
TP2M/9.52
Weight (Net / Shipping) 62/77
2-7
1980761295PVC 26/32
/
48/-/44
1920715235
/
Between I.D &O.MAX.Drop 30
Outdoorunit
/
/
Dimension /
/
/
Defrosting
Indoorunit
AC36NACBEA(WHITE)
PIPING
R407C 3800
65
Pipe9.52
19.05
Flare
Weight (Net / Shipping) /
Type of Four way valve /
/
/
/
/
Panel Dimension /
/
Weight (Net / Shipping)
MAX.Piping length 50
Remote
/
/
/
/
/
/
/
Total power input
Max. power input
Running /Max.Running
/
/
/
/
/
CentrifugalX4
1350+30/1280+30/1050+30
7
8/11/2019 Op Manual AU42NAIBEA
9/149
Function Cooling Heating
Capacity BTU/h 36000 41000
W 4000 3800
W 5500 5500
EER or COP BTU/W 9 10.8
Dehumidifying capacity 10m/h
Power cable
Power source NVHz
A / A
Start Current A
Unit model (color)
Fan Type Number
Speed(H-M-L) r/min
Fan motor output power kW
Air-flow(H-M-L) m/h
Heat exchanger Type / Diameter mm
Total Area m
Temp. scope
External LWH mmmmmm
Package LWH mmmmmmDrainage pipe (material , I.D./O.D.) mm
Control type (Remote /wired)
Fresh air hole dimension mm
kW
dB(A)
kg / kg
External LWH mmmmmm
Package LWH mmmmmm
kg / kg
Unit model (color)
Compressor Model / Manufacture
TypeFan Type Number
Speed r/min
Fan motor output power kW
Air-flow(H-M-L) m/h
Heat exchanger Type / Diameter mm
Total area m
Temp. scope
External LWH mmmmmm
Package LWH mmmmmm
Drainage pipe (material , I.D./O.D.) mm
Refrigerant control method mm/mm
Volume of Accumulator LNoise level dB(A)
material of reduce noise
crankcase heater power W
kg / kg
Refrigerant Type / Charge g
Recharge quantity g/m
Liquid mm
Gas mm
Connecting Method
m
m
/
MAX.Piping length 50
Wired
/
/
/
/
/
/
/
/
/
/
/
/
Panel Dimension
Weight (Net / Shipping) /
Type of Four way valve /
/
Defrosting
I
ndoorunit
AD36NAMBEA(WHITE)
PIPING
R407C 3800
65
Pipe9.52
19.05
Flare
Between I.D &O.MAX.Drop 30
Outdoorunit
/
/
Dimension /
/
/
/
/
Weight (Net / Shipping) /
CentrifugalX3
1050/ 960/ 870/810
TP2M/9.52
Weight (Net / Shipping) 55/75
2-7
1557800370PVC 26/32
/
43/-/39
1410645350
/
0.06
2040/1800/1600
item Model AD36NAMBEA(SANYO)
5
/
Total power input
Max. power input
Running /Max.Running
/
Noise level (H-M-L)
Electricity Heater
3N 380V-400V 50HZ
cooling7.5/9.5heating6.5/9.5
45
Dimension
8
8/11/2019 Op Manual AU42NAIBEA
10/149
Function cooling heating
Capacity BTU/h 36000 41000
Capacity kW 10.55 12.01
Sensible heat ratio 79% /
W 4000 3800
W 5500 5500
EER or COP W/W 2.64 3.16
Dehumidifying capacity 10m/hPower cable
Power source NVHz
A / A
Start Current A
Unit model (color)
Type Number
Speed(H-M-L) r/min
Fan motor output power kW
Air-flow(H-M-L) m/h
Type / Diameter mm
Total Area m
Temp. scope
External LWH mmmmmm
Package LWH mmmmmm
Drainage pipe (material , I.D./O.D.) mm
Control type (Remote /wired)
Fresh air hole dimension mm
Outlet distribution hole dimension mm
kW
dB(A)
kg / kg
Unit model (color)
Model / Manufacture
Type
Type NumberSpeed r/min
Fan motor output power kW
Air-flow(H-M-L) m/h
Type / Diameter mm
Total area m
Temp. scope
External LWH mmmmmm
Package LWH mmmmmm
Drainage pipe (material , I.D./O.D.) mm
Refrigerant control method mm/mm
Volume of Accumulator L
Noise level dB(A)
material of reduce noise
crankcase heater power W
kg / kg
Type / Charge g
Recharge quantity g/m
Liquid mm
Gas mm
Connecting Method
m
m
/
/
Refrigerant
/
Compressor
Fan
48/46/44
/
/
/
/
wired
/
/
/
/
Type of Four way valve /
/
Defrosting /
/
MAX.Piping length 50
Weight (Net / Shipping) /
PIPING
R407C 3800
65
Pipe9.52
19.05
flared
Between I.D &O.MAX.Drop 30
/
/
Heat exchanger
/
/
/
TP2M/9.52
Outdoorunit
/
Weight (Net / Shipping) 62/77
Dimension/
/
PVC 26/32
1197828355
item Model AD36NAHBEA
5/
Total power input
Max. power input
Running /Max.Running
centrifugal X2
Dimension
/
2580/2070/1560
2-7
1450980530
Fan
Heat exchanger
0.06
Norminal condition: indoor temperature (cooling): 27DB/19WB, indoor temperature (heating): 20DBOutdoor temperature(cooling): 35DB/24WB, outdoor temperature(heating): 7DB/6WB
1090/1000/930
3PH 380V-400V 50HZ
Indoor
unit
AD36NAHBEA (grey)
Noise level (H-M-L)
Electricity Heater
Cooling:7.5/9.5, Heating:6.5/9.5
45
8/11/2019 Op Manual AU42NAIBEA
11/149
Function Cooling Heating
Capacity BTU/h 36000 41000
W 4000 3800
W 5500 5500
EER or COP BTU/W 9 10.8
Dehumidifying capacity 10m/h
Power cable
Power source NVHz
A / A
Start Current A
Unit model (color)
Fan Type Number
Speed(H-M-L) r/min
Fan motor output power kW
Air-flow(H-M-L) m/h
Heat exchanger Type / Diameter mm
Total Area m
Temp. scope
External LWH mmmmmm
Package
LWH mmmmmm
Drainage pipe (material , I.D./O.D.) mm
Control type (Remote /wired)
Fresh air hole dimension mm
kW
dB(A)
kg / kg
External LWH mmmmmm
Package LWH mmmmmm
kg / kg
Unit model (color)
Compressor Model / Manufacture
Type
Fan Type Number Speed r/min
Fan motor output power kW
Air-flow(H-M-L) m/h
Heat exchanger Type / Diameter mm
Total area m
Temp. scope
External LWH mmmmmm
Package LWH mmmmmm
Drainage pipe (material , I.D./O.D.) mm
Refrigerant control method mm/mm
Volume of Accumulator LNoise level dB(A)
material of reduce noise
crankcase heater power W
kg / kg
Refrigerant Type / Charge g
Recharge quantity g/m
Liquid mm
Gas mm
Connecting Method
m
m
Running /Max.Running
/
6000
MAX.Piping length 50
/
/
/
64/-/-
AUTO
/
Capiliary
TP2M/9.52
43-60
0.15
840+30
Scroll
C-SBN303H8A(SANYO)
Panel Dimension /
/
Weight (Net / Shipping) 91/111
Type of Four way valve DHF-12
XPE
Defrosting
Indoorunit
/
PIPING
R407C 3800
65
Pipe9.52
19.05
Flare
Between I.D &O.MAX.Drop 30
Outdoorunit
AU36NAIBEA(WHITE)
Axial-flow2
Dimension 9803401250
10504401375
0.92
Weight (Net / Shipping) /
Weight (Net / Shipping) /
/
//
/
/
/
/
/
item Model AU36NAIBEA(SANYO)
5
/
Total power input
Max. power input
Noise level (H-M-L)
Electricity Heater
3N380V-400V 50HZ
cooling7.5/9.5heating6.5/9.5
45
Dimension /
/
/
/
9
8/11/2019 Op Manual AU42NAIBEA
12/149
Function Cooling Heating
Capacity BTU/h 42000 48000
W 4800 5000W 5700 7200
EER or COP BTU/W 8.75 9.6
Dehumidifying capacity 10m/h
Power cable
Power source NVHz
A / A
Start Current A
Unit model (color)
Fan Type Number
Speed(H-M-L) r/min
Fan motor output power kW
Air-flow(H-M-L) m/h
Heat exchanger Type / Diameter mm
Total Area m
Temp. scope
External LWH mmmmmm
Package LWH mmmmmm
Drainage pipe (material , I.D./O.D.) mm
Control type (Remote /wired)
Fresh air hole dimension mm
kW
dB(A)
kg / kg
External LWH mmmmmm
Package LWH mmmmmm
kg / kgUnit model (color)
Compressor Model / Manufacture
TypeFan Type Number
Speed r/min
Fan motor output power kW
Air-flow(H-M-L) m/h
Heat exchanger Type / Diameter mmTotal area mTemp. scope
External LWH mmmmmm
Package LWH mmmmmm
Drainage pipe (material , I.D./O.D.) mm
Refrigerant control method mm/mm
Volume of Accumulator LNoise level dB(A)
material of reduce noise
crankcase heater power Wkg / kg
Refrigerant Type / Charge gRechar e uantit /mLiquid mm
Gas mm
Connecting Method
m
m
/
/
/
/
/
/
/
PVC 26/32
1400995115
Running /Max.Running
current
/
43/41/39
MAX.Piping length 50
Weight (Net / Shipping) /
Type of Four way valve /
/
Defrosting
PIPING
R407C 4000
65
Pipe 9.52
19.05
Flare
Between I.D &O.MAX.Drop 30
Dimension /
/
/
/
/
0.06
/
/
/
/
Remote control
/
2-7
1325920370
8.4/12Weight (Net / Shipping)
/
/
3N~ 380V-400V 50HZ
Indoorunit
AB42NACBEA(WHITE)
Outdoorunit
/
Weight (Net / Shipping) 46/53
Panel Dimension 134095080
item model AB42NACBEA
5
/
Total power inputMax. power input
Noise level (H-M-L)
Electricity Heater
Cooling8.3/10.2Heating9.5/12.6
59.5
1980/-/-
Centrifugal
590+30/490+40/420+50
TP2M/7
Dimension 1230840280
10
8/11/2019 Op Manual AU42NAIBEA
13/149
Function Cooling Heating
Capacity BTU/h 42000 48000
W 4800 5000
W 5700 7200
EER or COP BTU/W 8.75 9.6
Dehumidifying capacity 10m/h
Power cable
Power source NVHz
A / A
Start Current A
Unit model (color)
Fan Type Number
Speed(H-M-L) r/min
Fan motor output power kW
Air-flow(H-M-L) m/h
Heat exchanger Type / Diameter mm
Total Area m
Temp. scope
External LWH mmmmmm
Package LWH mmmmmmDrainage pipe (material , I.D./O.D.) mm
Control type (Remote /wired)
Fresh air hole dimension mm
kW
dB(A)
kg / kg
External LWH mmmmmm
Package LWH mmmmmm
kg / kg
Unit model (color)
Compressor Model / Manufacture
TypeFan Type Number
Speed r/min
Fan motor output power kW
Air-flow(H-M-L) m/h
Heat exchanger Type / Diameter mm
Total area m
Temp. scope
External LWH mmmmmm
Package LWH mmmmmm
Drainage pipe (material , I.D./O.D.) mm
Refrigerant control method mm/mm
Volume of Accumulator L
Noise level dB(A)
material of reduce noise
crankcase heater power W
kg / kg
Refrigerant Type / Charge g
Recharge quantity g/m
Liquid mm
Gas mm
Connecting Method
mm
Cooling8.3/10.2Heating9.5/12.6
49.5
Dimension
3N380V-400V 50HZ
Item model AC42NACBEA(SANYO)
5
/
0.06
1600/1400/1200
Noise level (H-M-L)
Electricity Heater
TP2M/9.52
Weight (Net / Shipping) 62/77
2-7
1980761295PVC 26/32
/
48/-/44
1920715235
/
Between I.D &O.MAX.Drop 30
Outdoorunit
/
/
Dimension /
/
/
Defrosting
Indoorunit
AC42NACBEA(WHITE)
PIPING
R407C 4000
65
Pipe9.52
19.05
Flare
Weight (Net / Shipping) /
Type of Four way valve /
/
/
/
/
Panel Dimension /
/
Weight (Net / Shipping)
MAX.Piping length 50
Remote
/
/
/
//
/
/
/
Total power input
Max. power input
Running /Max.Running
/
/
/
/
CentrifugalX2
1350+30/1280+30/1050+30
11
8/11/2019 Op Manual AU42NAIBEA
14/149
Function Cooling Heating
Capacity BTU/h 42000 48000
W 4800 5000
W 5700 7200
EER or COP BTU/W 8.75 9.6
Dehumidifying capacity 10m/h
Power cable
Power source NVHz
A / A
Start Current A
Unit model (color)
Fan Type Number
Speed(H-M-L) r/min
Fan motor output power kW
Air-flow(H-M-L) m/h
Heat exchanger Type / Diameter mm
Total Area m
Temp. scope
External LWH mmmmmm
Package LWH mmmmmmDrainage pipe (material , I.D./O.D.) mm
Control type (Remote /wired)
Fresh air hole dimension mm
kW
dB(A)
kg / kg
External LWH mmmmmm
Package LWH mmmmmm
kg / kg
Unit model (color)
Compressor Model / Manufacture
TypeFan Type Number
Speed r/min
Fan motor output power kW
Air-flow(H-M-L) m/h
Heat exchanger Type / Diameter mm
Total area m
Temp. scope
External LWH mmmmmm
Package LWH mmmmmm
Drainage pipe (material , I.D./O.D.) mm
Refrigerant control method mm/mm
Volume of Accumulator L
Noise level dB(A)
material of reduce noise
crankcase heater power W
kg / kg
Refrigerant Type / Charge g
Recharge quantity g/m
Liquid mm
Gas mm
Connecting Method
mm
/
MAX.Piping length 50
Wired
/
/
/
//
/
/
/
/
/
/
/
Panel Dimension
Weight (Net / Shipping) /
Type of Four way valve /
/
Defrosting
Indoorunit
AD42NAMBEA(WHITE)
PIPING
R407C 4000
65
Pipe9.52
19.05
Flare
Between I.D &O.MAX.Drop 30
Outdoorunit
/
/
Dimension /
/
/
/
/
Weight (Net / Shipping) /
Weight (Net / Shipping) 55/75
2-7
14509800530PVC 26/32
/
42/36/30
cooling8.3/10.2heating9.5/12.6
49.5
Dimension 1410645350
/
0.06
2040/1800/1600
CentrifugalX3
1050/960/ 870/810
TP2M/9.52
3N380V-400V 50HZ
Item model AD42NAMBEA(SANYO)
5
5X2.5mm2
Total power input
Max. power input
Running /Max.Running
Noise level (H-M-L)
Electricity Heater
12
8/11/2019 Op Manual AU42NAIBEA
15/149
Function cooling heating
Capacity BTU/h 42000 48000
Capacity kW 12.31 14.06
Sensible heat ratio 79% /
W 4800 5000
W 5700 7200
EER or COP W/W 2.56 2.81
Dehumidifying capacity 10m/hPower cable
Power source NVHz
A / A
Start Current A
Unit model (color)
Type Number
Speed(H-M-L) r/min
Fan motor output power kW
Air-flow(H-M-L) m/h
Type / Diameter mm
Total Area m
Temp. scope
External LWH mmmmmm
Package LWH mmmmmm
Drainage pipe (material , I.D./O.D.) mm
Control type (Remote /wired)
Fresh air hole dimension mm
Outlet distribution hole dimension mm
kW
dB(A)
kg / kg
Unit model (color)
Model / Manufacture
Type
Type NumberSpeed r/min
Fan motor output power kW
Air-flow(H-M-L) m/h
Type / Diameter mm
Total area m
Temp. scope
External LWH mmmmmm
Package LWH mmmmmm
Drainage pipe (material , I.D./O.D.) mm
Refrigerant control method mm/mm
Volume of Accumulator L
Noise level dB(A)
material of reduce noise
crankcase heater power W
kg / kg
Type / Charge g
Recharge quantity g/m
Liquid mm
Gas mm
Connecting Method
m
m
/
/
Refrigerant
/
Compressor
Fan
48/-/44
/
/
/
/
wired
/
/
/
/
Type of Four way valve /
/
Defrosting /
/
MAX.Piping length 50
Weight (Net / Shipping) /
PIPING
R407C 4000
65
Pipe9.52
19.05
flared
Between I.D &O.MAX.Drop 30
/
/
Heat exchanger
/
/
/
TP2M/9.52
Outdoorunit
/
Weight (Net / Shipping) 62/77
Dimension/
/
PVC 26/32
1197828355
item Model AD42NAHBEA
5/
Total power input
Max. power input
Running /Max.Running
centrifugal X2
Dimension
/
2580/-/1560
2-7
1450980530
Fan
Heat exchanger
0.06
Norminal condition: indoor temperature (cooling): 27DB/19WB, indoor temperature (heating): 20DBOutdoor temperature(cooling): 35DB/24WB, outdoor temperature(heating): 7DB/6WB
1090+30/-/930+50
3PH 380V-400V 50HZ
Indoor
unit
AD42NAHBEA (grey)
Noise level (H-M-L)
Electricity Heater
Cooling: 8.3/10.2, Heating: 9.5/12.6
49.5
8/11/2019 Op Manual AU42NAIBEA
16/149
Function coolin heatin
Capacity BTU/h 42000 50000
Capacity kW 12.31 14.65
W 5000 6000
W 6000 7200
EER or COP W/W 2.46 2.44
Dehumidifying capacity 10m/h
Power cable
Power source NVHz
A / A
Start Current A
Unit model (color)
Type Number
Speed(H-M-L) r/min
Fan motor output power kW
Air-flow(H-M-L) m/h
Type / Diameter mm
Total Area m
Temp. scope
External LWH
mmmmmm
Package LWH mmmmmm
Drainage pipe (material , I.D./O.D.) mm
Control type (Remote /wired)
dB(A)
kg / kg
Type / Charge g
Recharge quantity g/m
Liquid mm
Gas mm
Connecting Method
m
m
0.06
Norminal condition: indoor temperature (cooling): 27DB/19WB, indoor temperature (heating): 20DBOutdoor temperature(cooling): 35DB/24WB, outdoor temperature(heating): 7DB/6WB
590/400/350
1PH 380V-400V 50HZ
Indoorunit
AP42NACBEA (white)
Noise level (H-M-L)
Cooling:8.5/10.2 Heating:10.0/12.0
49.5
Dimension
0.338
1560/-/-
2-7
1952660455
PVC 26/32
1820530310
item Model AP42NACBEA
5
/
Total power input
Max. power input
Running /Max.Running
centrifugalX1
TP2M/9.52
Weight (Net / Shipping) 62/77
PIPING
R407C 4000
/
Pipe9.52
19.05
flared
Between I.D &O.MAX.Drop 30
MAX.Piping length 50
wired control
Refrigerant
Fan
Heat exchanger
48/-/44
8/11/2019 Op Manual AU42NAIBEA
17/149
Function Cooling Heating
Capacity BTU/h 42000 48000
W 4800 5000
W 5700 7200
EER or COP BTU/W 8.75 9.6
Dehumidifying capacity 10m/h
Power cable
Power source NVHz
A / A
Start Current A
Unit model (color)
Fan Type Number
Speed(H-M-L) r/min
Fan motor output power kW
Air-flow(H-M-L) m/h
Heat exchanger Type / Diameter mm
Total Area m
Temp. scope
External LWH mmmmmm
Package
LWH mmmmmm
Drainage pipe (material , I.D./O.D.) mm
Control type (Remote /wired)
Fresh air hole dimension mm
kW
dB(A)
kg / kg
External LWH mmmmmm
Package LWH mmmmmm
kg / kg
Unit model (color)
Compressor Model / Manufacture
Type
Fan Type Number Speed r/min
Fan motor output power kW
Air-flow(H-M-L) m/h
Heat exchanger Type / Diameter mm
Total area m
Temp. scope
External LWH mmmmmm
Package LWH mmmmmm
Drainage pipe (material , I.D./O.D.) mm
Refrigerant control method mm/mm
Volume of Accumulator LNoise level dB(A)
material of reduce noise
crankcase heater power W
kg / kg
Refrigerant Type / Charge g
Recharge quantity g/m
Liquid mm
Gas mm
Connecting Method
m
m
Cooling8.3/10.2Heating9.5/12.6
49.5
Dimension
PVC 26/32
3N380V-400V 50HZ
Item model AU42NAIBEA(SANYO)
5
/
/
/
/
Noise level (H-M-L)
Electricity Heater
Weight (Net / Shipping) /
/
//
/
/
/
Between I.D &O.MAX.Drop 30
Outdoorunit
AU42NAIBEA(WHITE)
Axial-flow2
Dimension 9803401225
10504401375
0.92
Defrosting
Indoorunit
/
PIPING
R407C 4000
65
Pipe9.52
19.05
Flare
Weight (Net / Shipping) 91/116
Type of Four way valve DHF-12
XPE
43-60
0.15
1180+30 840+30
Scroll
C-SBN373H8A(SANYO)
Panel Dimension /
MAX.Piping length 50
/
/
42
64/-/-
Auto
/
Capiliary
TP2M/9.52
Total power input
Max. power input
Running /Max.Running
6000
/
Weight (Net / Shipping) /
/
/
/
13
8/11/2019 Op Manual AU42NAIBEA
18/149
WARNING
CAUTION
WARNING
CAUTION
This system should be applied to places of office, restaurant, residence and the like. Appliaction to inferior
environment such as engineering shop could cause equipment malfunction.
Please entrust installation to either the company which sold you the equipment or to a professional contractor.
Defects from improper installations can be the cause of water leakage, electric shocks and fires.
Execute the installation accurately, based on following the installation manual. Again, improper installations can
result in water leakage, electric shocks and fires.
When a large air-conditioning system is installed to a small room, it is necessary to have a prior planned
countermeasure for the rare case of a refrigerant leakage, to prevent the exceeding of threshold concentration.
In regards to preparing this countermeasure, consult with the company from which you purchased the equipment,
and make the installation accordingly. In the rare event that a refrigerant leakage and exceeding of threshold
concentration does occur,there is the danger of a resultant oxygen deficiency accident.
For installation, confirm that the installation site can sufficiently support heavy weight. When strength is insufficient,
injury can result from a falling of the unit.
Execute the prescribed installation construction to prepare for earthquakes and the strong winds of typhoons and
hurricanes, etc. Improper installations can result in accidents due to a violent falling over of the unit.
For electrical work, please see that a licensed electrician executes the work while following the safety standards
related to electrical equipment, and local regulations as well as the installation instructions, and that only exclusive
use circuits are used.
Insufficient power source circuit capacity and defective installment execution can be the cause of electric shocks and
fires.
Accurately connect wiring using the proper cable, and insure that the external force of the cable is not conducted to
the terminal connection part, through properly securing it. Improper connection or securing can result in heat
generation or fire.
Take care that wiring does not rise upward, and accurately install the lid/service panel. Its improper installation can
also result in heat generation or fire.
WARNING
In either case, important safety related information is indicated, so by all means, properly observe all that is mentioned.
After completing the installation, along with confirming that no abnormalities were seen from the operation tests, please
explain operating methods as well as maintenance methods to the user (customer) of this equipment, based on the owner's
manual.
Moreover, ask the customer to keep this sheet together with the owner's manual.
Please read these "Safety Precautions" first then accurately execute the installation work.
Though the precautionary points indicated herein are divided under two headings, and
those points which are related to the strong possibility of an installation done in error
resulting in death or serious injury are listed in the section. However, there is also a
possibility of serious consequences in relationship to the points listed in the section as well.
- 14-
SAFETY PRECAUTIONS
3 SAFETY PRECAUTIONS
8/11/2019 Op Manual AU42NAIBEA
19/149
When setting up or moving the location of the air conditioner, do not mix air etc. or anything other than the designated
refrigerant (please see nameplate) within the refrigeration cycle.
Rupture and injury caused by abnormal high pressure can result from such mixing.
Always use accessory parts and authorized parts for installation construction. Using parts not authorized by this
company can result in water leakage, electric shock, fire and refigerant leakage.
The position of indoor unit must be above the floor 2.5m.
WARNING
Execute proper grounding. Do not connect the ground wire to a gas pipe, water pipe, lightening rod or a telephone
ground wire.
Improper placement of ground wires can result in electric shock.
The installation of an earth leakage breaker is necessary depending on the established location of the unit. Not
installing an earth leakage breaker may result in electric shock.
Do not install the unit where there is a concern about leakage of combustible gas.
The rare event of leaked gas collecting around the unit could result in an outbreak of fire.
For the drain pipe, follow the installation manual to insure that it allows proper drainage and thermally insulate it to
prevent condensation. Inadequate plumbing can result in water leakage and water damage to interior items.
CAUTION
-15
SAFETY PRECAUTIONS
8/11/2019 Op Manual AU42NAIBEA
20/149
185 185
30
52
88Screw Hole
(M10)
580
950
Power wiring Terminal
7018
18
38
340
38
380
1250
25
16
3 Net dimensionsof indoor unit and outdoor unit
1)Outdoor unit
8/11/2019 Op Manual AU42NAIBEA
21/149
1340
9 5 0
840
30
2 2 0
2 0
5 0
2 8 0
260
315270
1 3 5
160 3
0 0
295
1070
7 8 0
8 6 0
- 8 9 0
615
615
1250-1280 (ceiling hole)
over 1
0 0 0
mm
1 5 5
123055 55
2 2 0
over1500
over1500
ove
r1500
ove
r1500
(hanging position)
Model: AB36NACBEA Cassette type Indoor unit
- 17 -
NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT
2)Indoor unit
8/11/2019 Op Manual AU42NAIBEA
22/149
Model: AC36NACBEA Convertible Indoor unit
R15
85
100
19
5
19201800
600
690
630
100
85
310
590
545
4 0
2 3 5
1 5 0
1 8 0
85 150
60
195
600
105
600
300300
555
30
1 1 0
60
8 5
3 0 0
1010
25
6 5
4 5
drainage pipe
NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT
18
8/11/2019 Op Manual AU42NAIBEA
23/149
NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT
A-A
gas
pipe
liquid
pipe
drainage
pipe
Model: AD36NAMBEA AD42NAMBEA
19
8/11/2019 Op Manual AU42NAIBEA
24/149
Model: AD36NAHBEA AD42NAHBEA
8/11/2019 Op Manual AU42NAIBEA
25/149
5.1.1 Installation tools
1. Cross screwdriver 2 .Metal saw 3 .60,70mm drill 4. Inner hexagon spanner,
shifting spanner 5 .Spanner(14, 17, 19,24,27mm diameter) 6. Pipe cutter
7. Pipe expander 8. Knife 9 .Pliers 10. Leak detector or soap liquor
11. Measuring tape 12 .Scraper 13. Refrigeration oil 14 .Vacuum pump
15 .Flat screwdriver
5.1.2 Standard accessories
Part name
QTY
Shape
Clamp
2 Piece
Washer
8 Piece 6 Piece
Clamp Paper pattern
1 Set
6321
3 Piece
Screw(M5 size)
For installationofpaper pattern
Drain hose
1 Piece
Please check if your unit is delivered with following
Part name
QTY
Shape
Dry batteryInsulator Sealing pad Sealing pad Sealing pad7
8 9 12
1 Piece 1 Piece
Insulator
2 Piece 1 Piece 1 Piece 2 Piece
Small sizeMedium sizeLarge sizeFor liquid pipeFor gas pipe R03, 7#
[Other]
OperationManual
Ornamentpanel
Remotecontroller
54
1110
5.1.3 Installation of indoor unit
5.1.3.1 Before installationDetermine the way kto carry unit to installation place.
Don't remove packing until unit reaches installation place.
If unpacking is unkavoidable, protect unit properly.
5.1.3.2 Selection of installation place
(1) Installation place shall meet the following and agreed by customers:
Place where proper air flow can be ensured.
No block to air flow.
Water drainage is smpoth.
Place strong enough to support unit weight.
Place where inclination is not evident on ceiling.
Enough space for mainenance.
Indoor and outdoor unit piping length is within limit. (Refer to Installation Manual for outdoor unit.)Indoor and outdoor unit, power cable, inter unit cable are at least 1 m away fromT.V. radio. Thisis helpful to avoid picture disturbance and noise. (Even if 1 m is kept, noise can still appear if radio
wave is strong)
- 20 -
INSTALLATION INSTRUCTIONS
5 INSTALLATION INSTRUCTIONS
5.1 Cassette type
8/11/2019 Op Manual AU42NAIBEA
26/149
8
260
260
(2) Ceiling heightIndoor unit can be installed on ceiling of 2.5-3m in height. (Refer to Foeld setting and InstallationManual of ornament panel.)
(3) Install suspending bolt. Check if the installation place is strong enough to hold weight. Take
necessary measures in case it is not safe. (Distance between holes are marked on paper pattern. Refer to paper pattern for place need be reinforced)
Installation space
Air inletAir outlet
2500Over
Air ou tle t
1500 Over1500 Over 1500 Over 1500 Over
Air ou tle tAir inlet
Air inlet
5.1.3.3 Preparation
(1) Position of ceiling opening between unit and suspending bolt.Unit: mm
- 21 -
INSTALLATION INSTRUCTIONS
50~100
Roof
Anchor bolt
Long nut
Suspending bolt
Ceiling
(2) Cut an opening in ceiling for installation if necessary. (when ceiling already exists.)
Refer to paper pattern for dimension of ceiling hole.
Connect all pipings (refrigerant, water drainage), wirings (inter unit cable) to indoor unit, before
installation. Cut a hole in ceiling, may be a frame should be used to ensure a smooth surface and to prevent
vibration. Contact your real estate dealer
(3) Install a suspending bolt.
(Use a M10 bolt)
To support the unit weight, anchor bolt shall be used in the case of already exists ceiling. For new
ceiling, use built-in type bolt or parts prepared in the field.
Before going on installing adjust space between ceiling.
Note: All the above mentioned parts shall be prepared in field.
890(Ceiling opening)
( D i s t a n c e b e t w e e n s u s p e n d in g b o l t s )1070515
515
(D
istance
betw
eens
uspendingb
olts)
860(Ceilingop
ening)
780 20 Over
8/11/2019 Op Manual AU42NAIBEA
27/149
5.1.3.4 Installation
4 5
7
(2) As for the dimensions of ceiling hole, see paper pattern. Ask your real estate dealer for details. Center of the hole is marked on the paper pattern. Center of the unit is marked on the card in the unit and on the paper pattern. Mount paper pattern onto unit using 3 screws . Fix the corner of the drain pan at piping outlet.
(1) Install unit temporally
In the case of new ceiling
Put suspending bracket on the suspending bolt. Be sure to use nut and washer at both ends of the bracket.
< After installation on the ceiling >
(3) Adjust unit to its right position. (Refer to preparation for the installation-(1))
(4) Check unit's horizontal level.
Watert pump and flating switch is installed inside indoor unit, check four corners of the unit for its level using
horizontal compartor or PVC tube with water. (If unit is tilting against the direction of water drainage, problem
may occur on floating switch, causing water leakage.)
(5) Remove the washer mounlting , and tighten the nut above.
(6) Remove the paper pattern.
(1) Install unit temporally
Put suspending bracket on the suspending bolt. Be sure to use nut and washer at both ends of the
bracket. Fix the bracket firmly.
(2) Adjust the height and position of the unit. (Refer to preparation for the installation (1) ).
(3) Proceed with and of "In the case of new ceiling".
LevelPolythene pipe
3 4
In the case of ceiling already exists
Scrtews at the piping outlet is fixed at the cornerof drain pan.
Center of ceiling hole Paper pattern 4Paper pattern
5Screw (accessory)5Screw(accessory)
[Fix the paper pattern]
5.1.3.5 Refrigerant piping
As for outdoor piping, please refer to installation Manual of outdoor unit.
6 9
Apple refrigerant oil
Torque spanner
spanner
Piping joing
Flare nut
Medium size seal pad 9 (accessory)
Clip 3
Gas pipe
Liquid pipe
Insulator (accessory)
(For liquid pipe)
Insulator (accessory)
(For gas pipe)
7
6
(Cover the piping joint with seal pad.)R0.4 ~ 0.8
A
Pipesize
Tightentorque
A(mm) Flare shape
9.52 3270~3990N.cm
(333~407kgf.cm)
19.059720~11860N.cm
(990~1210kgf.cm)
12.0~12.4
22.9~23.3
90
0.5
45
2
Outdoor is precharged with refrigerant.Be sure to see the Fig.1, when connecting and removing piping from unit.For the size of the flare nut, please refer to Table 1.
Apply refrigerant oil at both inside and outsid of lflare nut. Tighten it band tight 3-4 turns then tighten it.Use torque specified in Table 1. (Too much force may damage flare nut, causing gas leakage).Check piping joints for gas leakage. Insulate piping as shown in Fig. below.Cover joint of gas piping and insulator with seal .
Table 1
Diameter of PipeLiquid Pipe 9.52mm
Gas Pipe 19.5mm
Tighten Torque42N. m
60N. m
- 22 -
INSTALLATION INSTRUCTIONS
8/11/2019 Op Manual AU42NAIBEA
28/149
5.1.3.6 Installation of drainage pipe
1-1.5m
Use the self-provided stiff pipe and clip with unit. Insert water pipe into water plug until it reaches the white tape.Tighten the clip until head of the screw is less than 4mm from hose.Wind the drain hose to the clip using seal pad 8 .Insulate drain hose in the room.
2
Clip 2
Tape (White) Self-provided stiff pipe
Clip 2
4mm below
(accessory)
(accessory)
Large size seal pad
Clip 2
10
Installation height shall be less than 280mm.There should be a right angle with unit, 300mm from unit.
Waterring can of plastic
(1) Install water drainage pipe
Pipe dia, shall be equal or larger than that of unit piping.(pipe of polyethylent; size: 25mm; O.D:32mm)
Drain pipe should be short, with a downward slope at least 1/100 to prevent air bag from happening.
If downward slope can't be made, take other measures to lift it up.Keep a distance of 1-1.5m between suspending brackets, to make water hose straight.
Slope over 1/100
75below
Self-provided stiff pipe
(accessory)
500below
300mm below 1~1.5m
280below
500below
220
Drain hose 1(accessory) drain water lifting pipe
Suspending bracket
Clip
(accessory)
2
Over100
(Note)
If several water hoses join together, do as per following proceedures.
Connect water hoses with a T joint.
Specifieations of the water hoses shall meet the requirements for the unit running.
The slope of water drain hose (1) shall be within 75mm, don't apply too much force on it.
Method of water charging
11
When wiring is not complete
Charge water fromair outlet
Charge water frominspecting hole
Watering can of plastic
pipe should be about
100 mm long
100mm
Water drainage port formaintenance
(Drain water fromthis hole)
Self-provided stiff pipe Maintenance
Inspecting hole
Cover of controll box
PCB on indoor
Terminal
Terminal blockConnect withoutdoor unit
1 2 3
L N
Power
1 2 3
Indoor
Outdoor
H07RN-F3G 4mm
2
H05RN-F4G 0.75mm
2
1 2 3R S T
1 2 3
N
Indoor
Power Outdoor
H05RN-F4G 0.75mm
2
H07RN-F5G 2.5mm
2
(2) Check if water drainage is smooth after installation.
Charge, through air outlet or inspecting hole, 1200ccd water to see water drainage.
After wiring
Remove cover of control box, short connect "CHECK" terminal of the indoor unit, which is on the uperpart of indoor unit PCB. Connect 1PH power to terminal 1 and 2 on terminal block.Note, in this operation, fan will be running.Upon confirmation of a smooth water drainage, be sure to cut off power supply andremove shortconnection of "CHECK" terminal.
Check water drainage in cooling operation. See also test run.
- 23 -
INSTALLATION INSTRUCTIONS
8/11/2019 Op Manual AU42NAIBEA
29/149
5.1.3.7 Wiring
Terminal block
Clip A
Cover of control box 1
Rubber tube A
Grounding lead
Cover of control box 2
Terminal blockConnect withoutdoor unit
OutIn
Field wiringAttach seal pad
Don't fail to seal it, or, water may come in.
Rubber tube Note: Have it sealed, leaving no space.
Seal pad (small size)( )
(Wind around wire)
12
All supplied parts. materials and wiring operation must in appliance with local code and regulations.
Use copper wire only.
When make wiring, please refer to wiring diagram also.All wiring work must be done by qualified electricians.
A circuit breaker must be installed, which can cut power supply to all system.
See Installation Manual of outdoor unit for specifications of wires, circuit breaker, switches and wiring etc.
Connecting of unitRemove cover of switch box (1) , drag wires into rubber tube A, then, after proper wiring with other wires,tighten clamp A. Connect wires of correct pole to the terminal block inside.Wind seal (12) around wires. (Be sure to do that, or, dew may occur).Upon connecting, replace control box cover (1) and (2).
Obscrve the following when connecting power supply terminal block: Don't connect wires of different specifications to the same terminal block. (Loose wire may cause overheating of circuit)
Connect wires of same specifications as shown in right Fig.
Connect wires of the same
specifications at two sides.
Don't connect wires of the
same specifications at one side.
Don't connect wires of the
different specifications.
5.1.3.8 Wiring example
As for outdoor unit c ircuit, please see Installation Manual of outdoor unit.
Note:All electric wires have their own poles, poles must match that on terminal block.
5.1.3.9 Installation of ornament panel
1. Prepare ornament panel
Handling of ornament panel
Ornament panel shall not be placed face down or against wall, neither on an uneven object.
Don' t bend carelessly the swing flap, or, problem may occur.
(1)Remove air inlet grill from ornament panel:
Push in the bar on inlet grill and lift it up. (Refer to Fig. 1)
Lift it up for about 45 degree and remove it from ornament.Tear off adhesive tape fixing air filter on the back of the air
inlet grill. (Refer to Fig. 2)
Cautions for the installation
Be sure to show customers Operation Manual and guide them how to operate unit correctly. Before installation, read also
the Installation Manual of indoor unit.
With this ornament , 2 or 3 air flow direction is not available. Suitable height is 3 m.
2
Accessory Pad Pad
1
Bar
- 24 -
INSTALLATION INSTRUCTIONS
8/11/2019 Op Manual AU42NAIBEA
30/149
5_ 8mm
3
2
2
1
4
Holding ring
Piping h ole position
Swing flap motor
Fig. 7
SealIndoor unit
Ceiling material
Ornament panel
(2) Remove cover plate at corner
Tear off the adhesive tape,
and slide it off.
(Refer to Fig. 3)
(1)
(2)
2. Install ornament panel on indoor unit.
As shown in Fig . 7, match the position of
swing flap motor with that of the indoor unit
piping hole , so that ormament panel can be
placed on to indoor unit.
Installation of ornament panel
Place the holding ring on swing flao motor
side teporarily on hooks of the indoor unit.
(2 pcs)Put the other two holding rings on the hooks atboth side of the indoor unit. (Care should be
taken not to push wiring of swing flap motor
into seals).
Screw in all 4 screws under holding ring for
about 15mm. (Pancl will rise).
Adjust the ornament panel as per Fig. 7 to
cover opening on the ceiling.
Tighten screws to redrce the thickness of sealsbetween ornament and indoor unit to 5-
8mm.
1
2
3
4
5
If indoor unit is at horizontal leveland water drainage is smooth,
then, indoor unit height can be ad-justed throrgh holes at corners ofornament panel.
If screws are not tighten tight, problems in Fig, 8
might occur. Tighten screws properly.If there are still space after tightening
of screws, please readjust the height
of indoor unit. (Refer to Fig. 9)
Leave no space.Fig. 9
Gas leakage.
Gas leakage from roof.
Contamination Mist exists and drop down.
Fig. 8
45
Fig. 2
Adhesive tape
Slide
Fig. 3
For indoor unit installation, please refer to Installation Manual.Hook
Caution
1
2
Leave no space.
Fig. 6
3. Mounting on high ceiling
(1) Ornament panel can be mounted on ceiling as high as 3 m.
(2) Please install pad as accessary.
Cut open the pad along cutting ling. Use part a only and discard part b . (Refer to Fig. 4)
Install part a of the pad on the place shown in Fig. 5. Refer to Fig. 6.
Fig. 4
(3)Wiring on ornament panel Connecting of wiring of the swing flap motor on ornament panel. (2 places) (Refer to Fit . 10 )
50
Cutting line
100ab
Place it on the frame.
Part a of the padPart a of the pad
Swing flap motor Fig. 5
Side of ornament panel
Fig. 10
Wiring diagramSide of indoor unit
If connecting is not made, error code(A7) appears on remote controller. So,
make proper connecting.
- 25 -
INSTALLATION INSTRUCTIONS
8/11/2019 Op Manual AU42NAIBEA
31/149
1
2
4. Installation of inlet grill and cover plate
Installation of inlet grillInstall in reversed order ofPrepare ornament pandl.Inlet grill can be adjusted into four directions by turning inlet grill. Inlet grill position can be adjusted as
per customers request.
(1)
When installing inlet grill, take care not to twist wiring of swing flap motor.
Install cover plate on the cornerAs shown in Fig. 11 tie thecover plate onto the bolt onornament plate.Install cover plate onto ornament p late. (Refer to Fig. 12)
(2)
Slide all five hold rings
to let them drop in holes
on ornament plate,
Fig. 12Fig. 11
bolt
5.1.3.10 Test running
Refer to
Take special care during installation, check after working
(1)
(2)
(3)(4)
(5)
(6)
Proce-dure Operation
Open check valve on gas pipe.
Open check valve on liquid pipe.
Press ON/OFF button, select Cooling mode.Let it run for 3 min.
Press air flow adjust button to make unit run properly
Confirm unit functions according to Operation Manual.
Upon installation of piping, water drainage and w iringwork, make test run to ensure proper unit operation.
(1)
(2)
(3)
(4)
(5)
Procedure Operation
Open check valve on gas pipe.
Open check valve on liquid pipe.
Press ON/OFF button, select Cooling mode.
Let it run for 3 min.
Cut main power supply after operation.
Conduct test run before installing ornament panel
Note:If unit doesnt run due to certain problem, please seeNote to unit maintenance.
Conduct test run after installation of ornament panel
- 26 -
INSTALLATION INSTRUCTIONS
8/11/2019 Op Manual AU42NAIBEA
32/149
5.1.4 Installation of outdoor unit
580
380
5.1.4.1 Selection of installation place
Place strong enough to support the unit and will not cause vibration and noise.
Place where discharged wind and noise do not cause a nuisance to the neighbors.
Place where is less affected by rain or direct sunlight and is sufficiently ventilated, or to install a shield.
Place with enough space for smooth air flow.
The unit shall not be installed on an unspecifised metal frame (e.g. theft guard net).
If the outdoor unit is installed close to a street, it shall be no less than 2.5m from the ground.
5.1.4.2 Fixing of the unit
Fix outdoor unit using M10 bolt to concrete floor horizontally.
If installed on the wall or on top of a roof, bracket should be fixed securely to resist earthquake or storms.
Use rubber pad during installation against unit vibration.
Install the unit so that the angle of inclination must be less than 3 degrees.
2
Liquid(Thin)
Gas(Thick)
3way V.
2way V.
Vacuum pump
Gaugemanifold
2 Open
3
5.1.4.3 Air purging method: To use vacuum pump
For those models which adopt R407C refriengerant shall only use vacuum pump topurg air.
Detach the service port's cap of 3-way valve, the valve rod'scap for 2-way valve and 3-way's, connect the service portinto the projection of charge hose (low) for gaugemanifold.Then connect the projection of charge hose (center) forgaugemanifold into vacuum pump.
1
Open the handle at low in gaugemanifold, operatevacuum pump. If the scale-moves of gause (low)reach vacuum condition in a moment, check 1 again.
Vacuumize for over 15min. And check the levelgauge which should read -0.1 MPa (-76 cm Hg)at low pressure side. After the completion of
vacuumizing, close the handle 'Lo' in gaugemanifoldand stop the operation of the vacuum pump.Check the condition of the scale and hold it for1-2min. If the scale-moves back in spite of
tightening, make flaring work again, the returnto the beginning of 3 .
185 185
Installation dimension of outdoor unit (mm)
INSTALLATION INSTRUCTIONS
8/11/2019 Op Manual AU42NAIBEA
33/149
4
5
6
8
7
90
3
3way V.
2way V.
6
6
for 6 sec.
Service port
3way V.
2way V.
90
4
If it does not stop gas leakage, discharge whole
refrigerants from the serice port. After flaring workagain and vacuumize, fill up prescribed refrigerant
from the gas cylinder.
Open the valve rod for the 2-way valve to andangle of anticlockwise 90 degree.
After 6 seconds later, close the 2-way valve andmale the inspection of gas leakage.
In case of gas leakage, tightenparts of pipe connection. If leakagestops, then proceed steps.
No gas leakage?6
Detach the charge hose from the service port, open2-way valve and 3-way. Turn the valve rodanticlockwise until hitting lightly.
After attaching the each caps, check the gas leakagearound the caps.
To prevent the gas leakage, turn the service port'scap, the valve rod'd cap for 2-way valve and 3-way'sa lottle more than the point where the torque increasessuddenly.
7 Valve rod cap
7 Valve rod cap
3way V.
2way V.
5 Service port cap
If needing to remove the refrigerant gas when installation or repair , please refer to the
following procedures:
1. Cut off the power
2. (After confirming the power is cut off) pull the power cable plug terminals of the low-pressure
pressure-switch out.
3. (After confirming the power cable terminals of the low-pressure pressure-switch is cut off) After
powering on the unit again and switch to COOLING mode,perform refrigerant gas removing
according to the normal refrigerant gas removing procedure.
4. After finishing refrigerant gas removing , cut off the power , then insert the power cable terminals
of the low-pressure pressure-switch properly.
- 28 -
INSTALLATION INSTRUCTIONS
8/11/2019 Op Manual AU42NAIBEA
34/149
INSTALLATION INSTRUCTIONS
GAS LEAKAGE INSPECTION
After connecting the piping, check the joints for gas leakage with gas leakage detector.
CAUTION
HOW TO CONNECT WIRING TO THE TERMINALSA. For solid core wiring (or F-cable)(Fig.28A)
(1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 25mm of the exposed solid wire.(2) Using a screwdriver, remove the terminal screw(s) on the terminal board.(3) Using pliers, bend the solid wire to form a loop suitable for the terminal screw.(4) Shape the loop wire properly, place it on the terminal board and tighten securely with the terminal screw using a screw driver.
B. For strand wiring(Fig.28B)
(1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 10mm of the exposed strand wiring.(2) Using a screwdriver, remove the terminal screw(s)on the terminal board.(3) Using a round terminal fastener or pliers, securely clamp a round terminal to each stripped wire end.(4) Position the round terminal wire, and replace and tighten the terminal screw using a screw driver.
Fig. 28
Screw withspecial washer
Roundterminal
Wire
Terminalboard
Screw with
special washer
Roundterminal
Wire
A. Solid wire
Insulation
Strip25mm
Loop
B. Strand wire
Strip10mm
Roundterminal
After passing the connection cord and power cable through the insulation tube, fasten it with the cord clamp, as shown in Fig.29
HOW TO FIXED CONNECTION CORD AND POWER CABLE AT THE CORD CLAMP
Fig. 29
Cord clamp
Insulation tube
Use VW-1, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.
Item to the checked
5.5 Pay special care to the following and check after installation
Unproper installation may cause Check
Is indor indoor unit firmly installed?
Is gas leakage dheck performed?
Is unit properly insulated?
Is water drainage smooth?
Is power voltage meet that stipulated on the nameplate?
Is wiring and piping correctly arranged?
Is unit safely grounded?
Is wire size correct?
Are there any obstacles on air inlet and outlet grill of
indoor and outdoor unit?
Is record made for piping length and refrigerant
charging amount?
Unit might fall down, make vibration or noise.
This may lead to gas shortage.
Dew or water drop may occur.
Dew or water drop may occur.
Problem may occur or parts got burned.
Problem may occur or parts got burned.
There might be a danger of electric shock.
Problem may occur or parts got burned.
This may cause poor cooling.
It is hard to control refrigerant charging
amount.
8/11/2019 Op Manual AU42NAIBEA
35/149
(1) If possible, do not install the unit where it will be exposed to direct sunlight.(If necessary, install a blind that does not interfere with the air flow.)
(2) Install the outdoor unit in a place where it will be free from being dirty or getting wet by rain as much as possible.(3) Install the unit where connection to the indoor unit is easy.(4) During heating operation, drain water flows from the outdoor unit. Therefore, install the outdoor unit in a place where the drain water flow will not be obstructed.(Reverse cycle model only)(5) Do not place animals and plants in the path of the warm air.(6) Take the weight of the air conditioner into account and select a place where noise and vibration are small.
(7) Select a place where the warm air and noise from the air conditioner do not disturb neighbors.(8) Provide the space shown in Fig.2 so that the air flow is not blocked. Also for efficient operation, leave open three of the four directions front, rear, and both sides.
For authorized service personnel only
5.2.1SELECTING THE MOUNTING POSITION 2. OUTDOOR UNIT
Decide the m ounting position with the customer
as follows:
1. INDOO R UNIT
(1) Install the indoor unit level on a strong wall, floor, ceiling which is not subject to vibration.(2) The inlet and outlet ports should not be obstructed: the air should be able to blow all over the room.(3) Install the unit near an electric outlet or special branch circuit.(4) Do n ot install the unit where it will be exposed to direct sunlight.(5) Install the unit where connection to the outdoor unit is easy.(6) Install the unit where the drain pipe can be eas ily installed.(7) Take servicing, etc. into consideration and leave the spaces shown in Fig.1. Also install the unit where the filter can be removed.
NOT E: The appearance ma y be dif ferent from m odels.
(1) Install the unit where it will not be tilted by more than 5
(2) When installing the outdoor unit where it may be
exposed to the strong wind, fasten it securely.
Install at a place that can withstand the weight of theindoor and outdoor units and install positively so thatthe units will not topple or fall.
CAUTION(1)Do not install where there is the danger of com-
bustible gas leakage.
(2) Do not install near heat sources.
(3) If children under 10 years old may approach the
unit, take preventive measures so that they can-
not reach the unit.
L2
L3
L1
500
(Servicingspace)
Air outlet
Air inlet
Airinlet
Series 36 42
CaseDistance
L1
L2
L3
open open open open500 500
300 300open open0 0
100 300 150 150 150300
I II III I II III
Be careful not to scratch the room air conditioner when handing it.After installation, explain correct operation to the customer, accord ing to the operating manual.
Let the customer keep this installation manual because it will be used when the room air conditioner is serviced
or moved.
WARNING(1) For the room air conditioner to operate satisfactorily, install it as outlined in this installation manual.
(2) Connect the indoor unit and outdoor un it with the room air conditioner piping and cords available from our
standard parts. This installation manual describes for the correct connections so that the installation set
available from our standard parts should be used.
(3) Installation work must be performed in accordance w ith national wiring standards by authorized personnel only.
(4) Never cut the power cord, lengthen or shorten the cord, or change the plug.
(5) Also, do not use an extension cord.
(6) Plug in the power cord plug firmly. If the receptacle is loose, repair it before using the room air conditioner.
(7) Do not turn on the power until all installation work is done.
WARNINGWARNING
5.2INSTALLATION INSTRUCTIONS--Convertible type
INSTALLATION INSTRUCTIONS
8/11/2019 Op Manual AU42NAIBEA
36/149
Floor console
Fig. 1
2 cmor more
Ceiling
Indoor unit
30 cmor more
30 cmor more
Left
Right
30 cmor more 30 cmor more
1.5m
1.5m
1.5m
Left Right
may be different
For series 36,42
Note: For series 36, 42 no floor console type, the function
below about floor console is invalid to the series.
Fig. 2
Under ceiling
INSTALLATION INSTRUCTIONS
8/11/2019 Op Manual AU42NAIBEA
37/149
Mark Parts name
Adhesive tape
Saddle (L.S) with screws
Connecting electric cablefor indoor and outdoor
Drain hose
Heat insulation material
Piping hole cover
PuttyPlastic clamp
Optional parts
A
B
C
D
E
F
GH
5.2.2 STANDARD PARTSThe following installation parts are furnished.
Use them as required.
ACCESSORIESName and shape Q'ty Application
6
For fixing the wall
bracket.
For series 24,28,36,42
no this part.
Tapping screw( 4x20)
Coupler heat insulator(large)
1For indoor side pipe
join t (Large p ipe)
Coupler heat insulator(small) 1 For indoor side pipejoin t (S mall p ipe)
Nylon fastener1
For fixing the drain
hose
Drain hose
Non-adhesive tape
1
1
VT wire1
For fixing the drain
hose L 280mm
For series 24,28,36,42
VT wire is not available
Remote
controller
Battery
1
2
Use for air conditioner
operation
For remote controller
unit
Name and shape Q'ty Application
1For series 24,28, 36,42
the two cover plate are
not available
Cover plate (left)
Cover plate (right)
Installationtemplate
Anchor bolt
Spring washer
Special nut
Pipe hole cover
Wall hole cover
Main pipes
Connecting cables
1
2
1
4
4
4
1
1
1
1
For positioning the
indoor unit
For under ceiling type.
For suspending the
indoor unit from ceiling
4
Tapping sc rew( 4x10)
Cushion
Drain-elbow1
Only for the heat pump
type
Wall bracket2
For suspending the indoor
unit on the wall.For series
24,28,36,42 no this part.
INSTALLATION INSTRUCTIONS
8/11/2019 Op Manual AU42NAIBEA
38/149
INSTALLATION PROCEDURE
PREPARING INDOOR UNIT INSTALLATION
1. REMOVE THE INTAKE GRILL
Install the room air conditioner as follows:
Open the intake grill and remove the three or four or six screws.
(Fig. 3)
5.2.3CONNECTION PIPE REQUIREMENTTable 1
SeriesDiameter
Liquid side Gas side
Maximum length
Maximum height(between indoor and outdoor)
9.52 mm 19.05mm 50 m 15 m36
Remark: The main unit can be wired before the indoor unit is installed. Select the most appropriate installation order.
For series36,42 not the power plug, but 3-core connecting cable.
Fig. 3Machine screw
Tapping screw
Tapping screw
Intake grill
INSTALLATION INSTRUCTIONS
42 9.52 mm 19.05mm 50 m 15 m
Select piping and drain directions. only have rear side(Fig.13)
A. UN DER CE ILING TYPE-THE ON LY WAY
Using the installation template, drill holes for piping and anchor bolts(forholes).(Fig.12)
1. DRILLING FOR PIPING
Fig. 13
CAUTION
Install the drain hose at the rear; it should not be installed
on the top or right side.
When the directions are selected, drill 80mm and 50mm or 150mm
dia. hole on the wall so that the hole is tilted downward toward the
outdoor for smooth water flow.
AB
40 40
100mm
720mm
87.5mm
147mm
326mm
247mm
85
53
series A B
36
42 1920 1840
18401920
Rear (Install the drain hosein the direction.)
Right
Wall
6mm
60to70mm
12.7mm
Fig. 16
Insert the anchor bolts into the drilled holes, and drive the pins
completely into the anchor bolts with a hammer. (Fig. 16)
2. DRILLING HOLES FOR ANCHOR BOLTS AND
INSTALLING THE ANCHOR BOLTS
Fig. 15
With a concrete drill, drill four 12.7 mm dia. Holes.(Fig.15)
3. INSTALLING BRACKETS
Fig. 17
Install the brackets with nuts, washers and spring
washers.(Fig. 17)
Spring washer
Special nutBracket
8/11/2019 Op Manual AU42NAIBEA
39/149
4. INSTALLING INDOOR UNIT
68 16 21 28
381
232
26.5
26.5
2-R2.510
18
7
.5
4-R
5
68162128
381
232
26.5
26.5
2-R2.510
18
7
.5
4-R5
Reset the hex bolts as shown in Fig.18.
Hex bolt
8 to 13mmIndoor unit
Fig. 18
Apply the indoor unit to the brackets.(Fig.19)
Now, securely tighten the hex bolts in both sides.
Fig. 19
Bolt Bracket
Indoor unit
INSTALLATION INSTRUCTIONS
5. INSTALL THE DRAIN HOSE
Select whether the drain hose will be connected to the left or right
side.(Fig.5)
Insert the drain hose into the drain pan, then secure the drain hose
with a nylon fastener.(Fig.8)
Wrap the insulation (drain hose)around the drain hose connection.
(Fig.9)
Be sure to arrange the drain hose correctly so that it is leveled lower
than the drain hose connecting port of the indoor unit.(Fig.20)
Fig. 20Remove the hole cover.
Fig. 21
When drain hose is arranged backward.Secure the drain hose with
the VT wire. (Fig. 21)
OK
Arrange the drain hoselower than this portion
Drain hose
NO
VT wire hole
Drain hose
Piping hole
5.2.4 GAS LEAKAGE INSPECTION
After connecting the pip ing , ch eck the joints for gas leakage with gas le akage dete ctor.
CAUTION
HOW TO CONNECT WIRING TO THE TERMINALS
A. For solid core wiring (or F-cable )(F ig.28A)
(1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 25mm of the exposed solid wire.(2) Using a screwdriver, remove the terminal screw(s) on the terminal board.(3) Using pliers, bend the solid wire to form a loop suitable for the terminal screw.(4) Shape the loop wire properly, place it on the terminal board an d tighten securely with the terminal screw using a screw driver.
B. For strand wiring(Fig.28B)
(1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 10mm of the exposed strand w iring.(2) Using a screwdriver, remove the terminal screw(s)on the terminal board.(3) Using a round terminal fastener or pliers, securely clamp a round terminal to each stripped wire end.(4) Position the round terminal wire, and replace and tighten the terminal screw using a screw driver.
Fig. 28
8/11/2019 Op Manual AU42NAIBEA
40/149
INSTALLATION INSTRUCTIONS
Fig. 28
Screw withspecial washer
Roundterminal
Wire
Terminalboard
Screw withspecial washer
Roundterminal
Wire
A. So lid wire
InsulationS
trip25mm
Loop
B. Strand wire
Strip10mm
Roundterminal
After passing the connection cord and p ower cable through the insula tion tub e, fas ten it w ith the cord clamp , as shown in Fig .29
HOW TO FIXED CONNECTION CORD AND POWER CABLE AT THE CORD CLAMP
Fig. 29
Cord clamp
Insulation tube
Use VW-1, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.
1. INDOOR UNIT SIDE
(1) Remove the electric component box.
ELECTRICAL REQUIREMENT
Electric wire size and fuse capacity:
Table 5
ELECTRICAL WIRING
Series
Connection
cord (mm2)
Fuse capacity(A)
MA X
MIN
36 42
3.5
2.5
30
CAUTION(1) Match the terminal block numbers and connection cord colors with those of the outdoor unit. Erroneous wiring may cause burning of the electric parts.
(2) Connect the connection cords firmly to the terminal block. Imperfect installation may cause a fire.
(3) Always fasten the outside covering of the connection cord with the cord clamp.(If the insulator is chafed, electric leakage may occur.)
(4) Always connect the ground wire.
3.5
2.5
30
INDOOR UNIT SIDE
Fig. 30
Electric component box
Fig. 31Electric component box
Remove the four tappingscrews.
CAUTION
Do not remove the s crews. If the screwsare removed, the electric componentbox will fall.
8/11/2019 Op Manual AU42NAIBEA
41/149
(2) Pull out the electric component box.
Fig. 32
(3) Remove the e lectric component bo x cover.
Fig. 33
(1) Remove the cord clamp.
(2) Process the end of the connection cords to the
dimensions shown in Fig.34.
(3) Connect the end of the connection cord fully into the
terminal block.
(4) Wiring
CAUTION
Be careful not to pinch the lead wiresbetween the electric component boxand base.
(4) Fasten the connection cord with a cord clamp.(5) Fasten the end of the connection cord with the screw.(6) The power cable and connecting are self-provided
Outdoorunit
Indoorunit
Outdoorunit
1 2 3
1 2 3NTSR
Base
Electric component box cover
Remove the three tapping screws.
Electric component box
INSTALLATION INSTRUCTIONS
5.2.5TEST RUNNING
(1) The power source capacity must be the sum of the
room air conditioner current and the current of other
electrical appliances. When the current contracted
capacity is insufficient, change the contracted capacity.
(2) When the voltage is low and the air conditioner is dif-
ficult to start, contact the power company the voltage
raised.
CAUTION
1. CHECK ITEMS
(1) INDOOR UNIT
(1) Is operation of each button on the remote control unit normal?
(2) Does each lamp light normally?(3) Do not air flow direction louvers operate normally?
(4) Is the drain normal?
(2) OUTDOOR UNIT
(1) Is there any abnormal noise and vibration during operation?
(2) Will noise, wind, or drain water from the unit disturb the neighbors?
(3) Is there any gas leakage?
ELECTRICAL WIRING
(1) Always use a special branch circuit and install a special receptacle to supply power to the room air conditioner.
(2) Use a circuit breaker and receptacle matched to the capacity of the room air conditioner.
(3) The circuit breaker is installed in the permanent wiring. Always use a circuit that can trip all the poles of the wiring and has an isolation distance of at least 3mm between the contacts of each pole.
WARNING
(4) Perform wiring work in accordance with standards so
that the room air conditioner can be operated safely
and positively.
(5) Install a leakage circuit breaker in accordance with the
related laws and regulations and electric company
standards.
5.2.6 CUSTOMER GUIDANCE
Explain the following to the customer in accordance with the
operating manual:
(1) Starting and stopping method, operation switching, temperature
adjustment, timer, air flow switching, and other remote control
unit operations.
(2) Air filter removal and cleaning, and how to use air louvers.
(3) Give the operating and installation manuals to the customer.
8/11/2019 Op Manual AU42NAIBEA
42/149
For inspection and maintenance
When you change your address or the installation place
Electric work
Installation placeAvoid installing the air conditioner
near the place where possibility of
inflammable gas leakage exists.
Install the unit at well ventilated
place.Install the air conditioner firmly
on the foundation that can fully
support the weight of the unit.
If not, it may cause vibration or noise.If some obstacle exist, it may cause
capacity reduction or noise increase.
Explosion (Ignition) may occur.
Select the place so as not toannoy neighbor with the hot air
or noise.
Snow protection work isnecessary where outdoor unit is
blocked up by snow.
It is advisable not to install the air con-ditioner at the following special place.It may cause malfunction, consult thesales dealer when you have to installthe unit on such a place.
The place where corrosive gas generates(Hot spring area etc.)The place where salt breeze blows(Seaside etc.)The place where dense soot smoke existsThe place where humidity is extraordina-rily highThe place where near the machine whichradiates the electromagnetic waveThe place where voltage variation is con-siderably large
For details consult your sales dealer.
The electric work must be burden on the authorized engineer with qualification for electric work and
grounding work, and the work must be conducted in accordance with electric equipment technical standard.
The power source for the unit is to be of exclusive use.
An earth leakage breaker should be installed.(This is necessary to prevent electric shock.)
The unit must be grounded.
Special technology is required for removal or reinstallation of air conditioner, consult the salesdealer. Besides, construction expense is charged for removal or reinstallation.
The capacity of air conditioner will decrease by contamination of inside of unit when it is used for
about three years although depending upon the circumstances under which it is used, and so in
addition to the usual maintenance service, special inspection/maintenance service is necessary.
It is recommended to make a maintenance contract (charged) by consulting your sales dealer.
5.3INSTALLATION INSTRUCTIONS-Duct type
INSTALLATION INSTRUCTIONS
8/11/2019 Op Manual AU42NAIBEA
43/149
a. Remove upper part of wire
Remove upper part of wire controller
b. Install wire
(1) For exposed installation, use 2 wood screws(accessory).
Note: Try as far as possible a flat surface for installation. Don't use excessive
PCB is mounted on lower part of wire
controller, be careful not to damage
Lower part of wire
controller
Upper part of wire
controller
(2) For recessed installation, use 2 wood screws(accessory).
c. Indoor unit wiringConnect terminals (A,B,C,D) on lower
part of wire controller to terminals (A,
B,C,D) on PCB of indoor unit.
Hint:
When make wiring, please
keepa distance between wires
and power supply cord.
Cord kind
Size
Shield wire (4 core) (refer to Hint 3,4)
0.33mm2
Wire size
Use shielede wires for telecommunication
between wire controller and indoor unit;indoor unit and outdoor unit. Ground theshield on one side.Otherwise misoperation because of noisemay occur.Signal wire is self-provided.
Shielded wire
ground
Lower part of
wire controller
A B C D
Upper part of
wire controller
wiring from here
d. Replace the upper part of wire controller
Hint: 1. Switch box and cord for wiring are not supplied.Be careful not to press the wiring.
2. Don't touch PCB with hand.
Hint: Tread surface of the terminal well so that shielding may not contact other part.
INSTALLATION INSTRUCTIONS
5.3.1 Installation of the wired remote controlller
8/11/2019 Op Manual AU42NAIBEA
44/149
Edging
(2) Installation where the area with strong winds.
Install the unit so that the air outlet section of the unit must NOT be faced
toward wind direction.
(1) Open space requirement around the unit
b. Selection of the place of installation
a. Accessories
"Edging" for protection of electric wires from an
opening edge.
Select the place of installation satisfying the following conditions and, at the same time, obtain
a consent from the client or user.
Place where air circulates.Place free from heat radiation from other heat sources.
Place where drain water may be discharged.
Place where noise and hot air may not disturb the neighborhood.
Place where there is not heavy snowfall in the winter time.
Place where obstacles do not exist near the air inlet and air outlet .
Place where the air outlet may not be exposed to a strong wind.
Place surrounded at four sides are not suitable for installation. A 1m or more of overhead
space is needed for the unit.
Mount guide-louvers to place where short-circuit is a possibility.
When installing several units, secure sufficient suction space to avoid short circuiting.
WARNING
BE SURE TO READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGINNINGINSTALLATION. FAILURE TO FOLLOW THESE INSTRUCTIONS COULD CAUSE SERIOUS
INJURY OR DEATH, EQUIPMENT MALFUNCTION AND/OR PROPERTY DAMAGE.
BE SURE TO READ INSTALLATION MANUAL FOR INDOOR UNIT WITH THIS MANUAL.
Unit
Concrete foundationFoundation anchor
Note (1) Give enough room for the
concrete foundation to fix by anchor bolts.
(a)
Note (1) Place the concrete foundation deep
enough.
Install the unit so that the angle of inclination must be less than 3 degrees.
c. Installation of outdoor unit
Fix the unit in a proper way according to the condition of a place where it is installed by referring to the following .
(1) Installation
L2
L3
L1
500
(Servicingspace)
Air