MSX1410-OCP Rev. 1.3 SwitchX®-2 based 10GbE/40GbE, 1U Open Ethernet switch with 48 SFP+ ports and 12 QSFP+ ports Author: Shy Zimmerman Rev 1.3

Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

Embed Size (px)

Citation preview

Page 1: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

MSX1410-OCP

Rev. 1.3

SwitchX®-2 based 10GbE/40GbE, 1U Open Ethernet switch with 48 SFP+ ports and 12 QSFP+ ports

Author: Shy Zimmerman

Rev 1.3

Page 2: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

Revision History

Revision Date Description of Change

1.3 April 2015 Added Table 1

Added Sections 3.1.3.1, 3.1.3.2

1.2 May 2014 Updated port speed to 10GbE and 40GbE in figures

Added Abbreviations

Minor editing of Figure 15

1.1 May 2014 Updated System Figures

Added Long Switch Dimensions

Updated Sx Layout Diagram

Updated Main Block Diagram

Added Split Configurations

Updated I²C Tree

Updated to 3 CPLD’s (instead of 4)

Updated CPLD Field Upgrade

Updated Red LED to Amber LED

Added Operating Temperature

Added CCC Support

Added Measured Units in Power

Added CPU Basic Configuration

1.0 January 2014 Initial release

Page 3: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

Open Compute Project

3 April 2015

Scope

This document defines the technical specifications for the MSX1410-OCP switch used in Open Compute Project

Contents

Revision History ............................................................................................................................. 2

Scope .............................................................................................................................................. 3

Contents ......................................................................................................................................... 3

Overview ......................................................................................................................................... 5

License ............................................................................................................................................ 5

1 Abbreviations ........................................................................................................................... 7

2 Mechanical Drawings ............................................................................................................. 8

2.1 Mechanical System Overview ............................................................................................... 8

2.2 Switch Dimensions (in mm) ................................................................................................... 9

2.3 Fan Unit Dimensions (in mm) ............................................................................................... 9

2.4 Power Supply Dimensions (in mm) .................................................................................... 10

2.5 SFP+ Port Assembly ............................................................................................................ 11

3 MSX1410-OCP Features ..................................................................................................... 12

3.1 Electrical Features ................................................................................................................ 12

3.1.1 Port Configurations – Based on SwitchX-2™ .......................................................... 12

3.1.2 Management I/O Interfaces ........................................................................................ 14

3.1.3 Field Replaceable Units - FRU ................................................................................... 14

3.1.4 Management ................................................................................................................. 15

4 SX1410-OCP Blocks ............................................................................................................ 16

4.1 Main Block Diagram ............................................................................................................. 16

4.2 SwitchX-2™Block ................................................................................................................. 17

4.2.1 SFP+ Interface .............................................................................................................. 19

4.2.2 QSFP Interface ............................................................................................................. 20

4.2.3 Port over Current Protection ....................................................................................... 21

4.2.4 Port I²C Interface .......................................................................................................... 21

4.3 I²C ............................................................................................................................................ 22

4.4 CPLD ...................................................................................................................................... 24

4.4.1 CPLD Features ............................................................................................................. 24

Page 4: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

4 April 2015

4.4.2 CPLD Field Upgrade .................................................................................................... 24

4.5 SPI and Safe BIOS Mechanism ......................................................................................... 26

4.6 Ethernet .................................................................................................................................. 28

4.7 RS232 Interface .................................................................................................................... 29

4.8 USB ......................................................................................................................................... 30

4.9 LPC ......................................................................................................................................... 31

4.10 SATA .............................................................................................................................. 32

4.11 PCIe ................................................................................................................................ 33

5 Power ...................................................................................................................................... 34

5.1 Power Consumption ............................................................................................................. 34

5.2 Power Monitoring and Distribution ..................................................................................... 36

5.3 FRU Control ........................................................................................................................... 40

5.3.1 Fan Control .................................................................................................................... 40

5.3.2 Power Supply Control .................................................................................................. 40

5.4 Reset ...................................................................................................................................... 42

5.5 Temperature Monitor ............................................................................................................ 44

5.6 Clock Distribution .................................................................................................................. 45

5.6.1 Switch Clock Distribution ............................................................................................. 45

5.6.2 MGMT Clocks ............................................................................................................... 46

5.7 LEDs ....................................................................................................................................... 47

5.8 Power ...................................................................................................................................... 49

5.8.1 Power Consumption ..................................................................................................... 49

5.8.1.1 Celeron Based CPU, 48xDAC+12xSR4 ............................................................... 49

5.8.1.2 Celeron based CPU, 48xSR+12xLR4 ................................................................... 49

5.8.2 Power Distribution – Switch ........................................................................................ 50

5.8.3 Power Monitoring – Switch ......................................................................................... 51

5.8.4 Power Distribution and Monitoring – Management ................................................. 52

5.8.5 System Voltages and Currents Sensing ................................................................... 53

6 JTAG ....................................................................................................................................... 54

6.1 Testing I²C GPIO .................................................................................................................. 54

7 Compliancy ............................................................................................................................ 55

Page 5: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

Open Compute Project

5 April 2015

Overview

The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE for non-blocking throughput between rack and aggregation layer. Based on advanced hardware design, this switch packs 48 SFP+ and 12 QSFP interfaces in an ultra-dense 1U form factor. The MSX1410-OCP features latency of 250ns and power efficiency, while providing optimal performance for open rack based enterprise data centers, financial services, Web 2.0, high performance computing and cloud computing applications.

License

As of May 25, 2015, the following persons or entities have made this Specification available under the Open Compute Project Hardware License (Copyleft) Version 1.0 (OCPHL-R), which is available at http://www.opencompute.org/community/get-involved/spec-submission-process/

Mellanox, Inc.

Your use of this Specification may be subject to other third party rights. THIS SPECIFICATION IS PROVIDED "AS IS." The contributors expressly disclaim any warranties (express, implied, or otherwise), including implied warranties of merchantability, non-infringement, fitness for a particular purpose, or title, related to the Specification. The entire risk as to implementing or otherwise using the Specification is assumed by the Specification implementer and user. IN NO EVENT WILL ANY PARTY BE LIABLE TO ANY OTHER PARTY FOR LOST PROFITS OR ANY FORM OF INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES OF ANY CHARACTER FROM ANY CAUSES OF ACTION OF ANY KIND WITH RESPECT TO THIS SPECIFICATION OR ITS GOVERNING AGREEMENT, WHETHER BASED ON BREACH OF CONTRACT, TORT (INCLUDING NEGLIGENCE), OR OTHERWISE, AND WHETHER OR NOT THE OTHER PARTY HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGE.

Page 6: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

6 April 2015

Semiconductor Devices Licenses

All semiconductor devices that may be referred to in this specification, or required to manufacture products described in this specification, will be considered referenced only, and no intellectual property rights embodied in or covering such semiconductor devices shall be licensed as a result of this specification or such references.

Notwithstanding anything to the contrary in the CLA, the licenses set forth therein do not apply to the intellectual property rights included in or related to the semi without limitation the reference to devices listed below. For clarity, no patent claim that reads on such semiconductor devices will be considered a “Granted Claim” under the applicable Contributor License Agreement for this specification.

Manufacturer Description

Mellanox SwitchX-2, 36 Port 40GbE Switch IC

MT51136A2-CLCR-B

Lattice CPLD 4320LUT 3.3V

LCMXO2-4000HC-4BG332CCA2

Intel C QM77 EXPRESS CHIPSET

BD82QM77-SLJ8A

Intel IC CPU 1047UE 2M 1.40GHZ

AV8063801116300-SR10E

Intel IC GIGABIT ETHERNET CONTROLLER 82583

WG82583V-SLGVD

Windbond MEMORY FLASH SPI SERIAL 32MBIT 4KBYTEX1024 W25Q32FVSSIGT

Windbond MEMORY FLASH SPI SERIAL 64MBIT 4KBYTEX2048 W25Q64FVSSIGT

Windbond SUPER IO LPC INTERFACE WITH UART

NCT5577D

Intel LHA5 "LEWISVILLE" GIGABIT ETHERNET LAN CONTROLLER HURON

WG82579LM-SLHA6

INNODISK MODULE MSATA SSD 16GB MLC 0..70

DEMSR-16GD07SC2DC-92

APACER MODULE SO-DIMM DDR3 ECC 4GB 1600MBS 800MHZ SDRAM 204PIN

78.B2GCS.AT00C

Page 7: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

Open Compute Project

7 April 2015

1 Abbreviations

ToR – Top of Rack Switch

MNG – Management

SWB – Switch Board

FRU – Field Replaceable Unit

PWR – Power

HS – High Speed

SE – Single Ended

OCP – Open Compute Project

WD – Watch Dog

Page 8: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

8 April 2015

2 Mechanical Drawings

2.1 Mechanical System Overview

Switch Board

MNG Board

PSU 2 Ext. PSU 1 Ext.

IO BoardFan Board x 4

LED Board

Figure 1 – Main Components

Table 1: PCB Layer Dimensions

PCB Function PCB Layer Dimension (mm x mm)

Switch Board 18 413 x 184

MNG Board 16 250 x 134

IO Board 4 51 x 80.7

FAN Board 2 40.2 x 18.7

PSU Extender 4 127 x 25

LED Board 8 37.6 x 26.85

Page 9: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

Open Compute Project

9 April 2015

2.2 Switch Dimensions (in mm)

Figure 2 – Short Depth 17’’ Switch Dimensions

2.3 Fan Unit Dimensions (in mm)

Figure 3: Fan Unit Dimensions

Page 10: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

10 April 2015

2.4 Power Supply Dimensions (in mm)

Figure 4: Power Supply Dimensions

Page 11: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

Open Compute Project

11 April 2015

2.5 SFP+ Port Assembly

Figure 5: SFP+ Assembly on MSX1410-OCP

Page 12: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

12 April 2015

3 MSX1410-OCP Features

3.1 Electrical Features

3.1.1 Port Configurations – Based on SwitchX-2™

With each new generation of technology, server sizes shrink. Whereas in the past all servers occupied the entire rack width (19”), it is quite common today to find different racking solutions that allow fitting two servers on the same rack shelf, yielding a total of 56, 60 or more servers in the same rack.

Since most commercially available ToR switches have 48 10GbE ports, connecting more than 48 servers in this rack would require two ToR switches. These two switches increase the rack cost, latency and energy consumption, and occupy space that could have been allocated for servers.

This problem is solved by the port flexibility of the MSX1410-OCP switch. By simple configuration, its 40GbE ports can be configured to 10GbE and support more servers. For example, the MSX1410-OCP can be configured with 60 ports of 10GbE and 4 ports of 40GbE. This configuration connects 60 servers with an uplink of 160Gb/s, or oversubscription of 3.75:1. If configuring the four uplink ports to operate at 56GbE, the oversubscription ratio improves to 2.68:1. Alternatively, the MSX1410-OCP can be configured with 56 ports of 10GbE and 8 ports of 40GbE. This configuration connects 56 servers with an uplink of 320Gb/s, or oversubscription of 1.75:1.

A listing of all possible port configurations can be found in Table 2.

Table 2: MSX1410-OCP Ports Configuration

Possible Port

Configurations

40GbE/56GbE

ports

12 10 8 6 4 2 0

10GbE ports 48 52 56 58 60 62 64

Page 13: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

Open Compute Project

13 April 2015

Figure 6: MSX1410-OCP Ports Panel

3.1.1.1 Cables Support

SR

SR4

LR4

DAC

3.1.1.2 Split Capabilities

1 x 4x

Split 4

1 x 1x

41

52

63

107

118

129

1613

1714

1815

2219

2320

2421

2825

2926

3027

3431

3532

3633

4037

4138

4239

4643

4744

4845

5149

5250

5553

5654

5957

6058Blocked

48 x 10GbE + 12 x 40GbE

Split 2

1 x 4x

Split 4

1 x 1x

41

52

63

107

118

129

1613

1714

1815

2219

2320

2421

2825

2926

3027

3431

3532

3633

4037

4138

4239

4643

4744

4845

5149

5250

5553

5654

5957

6058Blocked

52 x 10GbE + 10 x 40GbE

Split 2

1 x 4x

Split 4

1 x 1x

41

52

63

107

118

129

1613

1714

1815

2219

2320

2421

2825

2926

3027

3431

3532

3633

4037

4138

4239

4643

4744

4845

5149

5250

5553

5654

5957

6058Blocked

64 x 10GbE

Split 2

Figure 7: Port Split Configurations

Page 14: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

14 April 2015

3.1.2 Management I/O Interfaces

2x 10/100/1000BASE-T RJ-45 Ethernet port

1x RS232/I²C RJ-45 Console connector

1x USB connector

Figure 8: Management I/O interfaces

3.1.3 Field Replaceable Units - FRU

3+1 redundant fan field replaceable modules. Can support a dual fan pack in each module

1+1 redundant field replaceable power supplies. Two optional power supplies:

o AC/DC 90-240Vac inlet - 460W

o DC/DC 48vdc inlet - 800W

3.1.3.1 AC Power Supply Units

The AC power supply units (DPS-460KBJ_REV.03) offer the following features:

Input voltage: 100 to 240 VAC

Frequency: 50 to 60 Hz

Efficiency: 89 to 91% at 220V

Table 3 describes the power supply connector pinout.

Pin # Description Pin # Description

A1~9 GND B1~9 GND

A10~18 +12V B10~18 +12V

A19 PMBus SDA B19 A0 (SMBus Address)

A20 PMBus SCL B20 N/A

A21 PSON B21 12VSB

Page 15: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

Open Compute Project

15 April 2015

Table 3: Power Supply Connector Pinout

3.1.3.2 Fan Units

The fan FRU is Delta Module P/N FA121A04-D40. Table 4 describes the fan unit connector pinout. Figure 18 is a mechanical drawing of the unit.

Table 4: Fan Unit Connector Pinout

3.1.4 Management

CPU: Intel Ivy Bridge

o Supports all flavors:

Celeron

i3

i5

i7

Chipset: Intel QM77 (Panther Point)

Up to two 1600MTs, 8GB (Each), DDR3, ECC SO-DIMM modules

Supports up to two SATA-slim 4/8/16/64GB SLC or MLC SSD modules

BIOS Field upgrade with fail safe

Real time clock 24H-SuperCap (optional battery)

3x CPLDs with field upgrade and fails safe capabilities

A22 SMBAlert# B22 Smart)on

A23 Return Sense B23 12VLS

A24 +12V Remote

Sense B24 No Connect

A25 PWOK B25 N/A

Pin # Description Pin # Description

1 12V 9 12V

2 12V 10 12V

3 Fan PWM 11 FAN TACH

4 Fan PWM 12 FAN TACH

5 GND 13 GND

6 GND 14 GND

7 FAN Present 15 I2C SCL

8 3.3V 16 I2C SDA

Page 16: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

16 April 2015

Default configuration: Celeron / Single DDR3 4GB SO-DIMM / Single SSD 16GB MLC

4 SX1410-OCP Blocks

4.1 Main Block Diagram

The following block diagram specifies the main blocks in the MSX1410-OCP switch:

12 QSFP 40GbE

LR4

12

QSFP

po

rts

SWB

CPLD1

SX I2

C

Front

Panel LED

Board

SWB

CPLD2

SwitchX-2

12V

3.3

V A

ux

CPUPCH

DMI

FDIMNG CPLD

LPC

BU

S

HS Harness

PC

Ie 4

x Up

To G

en

2

SX I2

C

I2C Tree

12V 3.3V_AUX

IO board connector

RS-2

32

ETH0

ETH1

USB

PS connectorsFAN connectors

Co

ntro

l/Sync b

us

12

V

CP

U I2

C

I2C Tree

0.9V 1.2V1.8V3.3V

LPC

BU

S

Co

ntro

ls / INT

PC

Ie 4

X

CP

U I2

C

I2C Tree

Power Block

+ Power

Monitor

PSU I2C x 2

FAN

I2C

x 4

FAN

s C

trl

PSUs Ctrl

LEDs

SX Ctrl+LEDS

Po

rts I2C

48

SFP+ P

orts

Status &

SFP+ LED

s

12

V

Panel I2C

SE HarnessPWR

Harness

MNG Board

Switch Board

48 SFP+

10GbE

SX Ctrl

Figure 9: MSX1410-OCP Main Block Diagram

Page 17: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

Open Compute Project

17 April 2015

4.2 SwitchX-2™Block

There are 12x40GbE QSFP ports and 48x10GbE SFP+ ports towards the panel from the SwitchX-2. The following diagrams show SwitchX-2 breakout capabilities and the general fan-out of ETH signals on the MSX1410-OCP accordingly:

Figure 10: SwitchX-2 Breakout Capabilities and Layout

Page 18: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

18 April 2015

Table 5 : Port Mapping

HW

Port Panel Port

QSFP/SFP+ HW Port Panel Port QSFP/SFP+

1 56 QSFP 20 53 QSFP

2 58 QSFP 21 54 QSFP

3 60 QSFP 22 51 QSFP

4 55 QSFP 23 52 QSFP

5 57 QSFP 24 43 SFP+

6 59 QSFP 24 44 SFP+

7 1 SFP+ 24 45 SFP+

8 2 SFP+ 25 40 SFP+

8 3 SFP+ 25 41 SFP+

9 4 SFP+ 25 42 SFP+

9 5 SFP+ 26 49 QSFP

10 21 SFP+ 27 50 QSFP

10 22 SFP+ 28 23 SFP+

11 20 SFP+ 28 24 SFP+

12 18 SFP+ 29 25 SFP+

12 19 SFP+ 30 26 SFP+

13 16 SFP+ 30 27 SFP+

13 17 SFP+ 31 28 SFP+

14 14 SFP+ 31 29 SFP+

14 15 SFP+ 32 30 SFP+

15 12 SFP+ 32 31 SFP+

15 13 SFP+ 33 32 SFP+

16 10 SFP+ 33 33 SFP+

16 11 SFP+ 34 34 SFP+

17 8 SFP+ 34 35 SFP+

17 9 SFP+ 35 36 SFP+

18 6 SFP+ 35 39 SFP+

18 7 SFP+ 36 38 SFP+

19 46 SFP+

36 37 SFP+ 19 47 SFP+

Page 19: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

Open Compute Project

19 April 2015

4.2.1 SFP+ Interface

48 ports of the MSX1410-OCP have SFP+ connectors. Each SFP+ connector supports the following:

Table 6 : SFP+ Interface

A single SFP+ interface on the MSX1410-OCP switch is illustrated in Figure 11.

SFP+ Port

22

uF

0.1

uF

22

uF

0.1

uF

VCCR

VCCT

SwitchX

CPLD

I2C Tree

Tx_FAULT

Tx_DISABLE

MOD_ABS

RX_LOS

RS0/RS1

Mod_Select

2 SCL/SDA I2C Buffer

2 Sx_to_sFP+_[P..N]

2 SFP+_to_Sx_[P..N]

SCL/SDA2

Power Enable

Shared fuse for 6 ports

0x50 / 0x51

EEPROM

SFP_PWR_EN

SFP_OC

Figure 11 : SFP+ Interface

Signal Name Description Type

TD+/TD- High Speed Transmission pair CML from SX to connector

RD+/RD- High Speed Receive pair CML from connector to SX

SCL/SDA I²C slave interface

address 0x50 or 0x51

Open Drain from SX to connector

TX Fault Module transmitter fault LVTTL from connector to CPLD

TX Disable Turn off transmitter output (optical) LVTTL from CPLD to connector

Mod ABS Module absent (logic high) Short to GND in module

RS0/RS1 RS0 – Receiver rate select

RS1 – Transmitter rate select

LVTTL from CPLD to connector

(short together)

RX LOS Receiver loss of signal indication LVTTL from connector to CPLD

Page 20: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

20 April 2015

4.2.2 QSFP Interface

12 ports of the MSX1410-OCP are QSFP connectors.

Each QSFP connector supports the following:

Table 7 : QSFP Interface

A single QSFP interface in the MSX1410-OCP board is presented in Figure 12.

QSFP Port

SwitchX

CPLD

I2C Tree

ResetL

LPMpde

IntL

MODPrsL

Mod_Select

2 SCL/SDA I2C Buffer

8 Sx_to_QSFP_[A..D][P..N]

8 QSFP_to_Sx_[A..D][P..N]

SCL/SDA2 0x50 / 0x51

EEPROM

Power Enable

3.3V

VCCTXVCCRXVCC1

22

uF

0.1

uF

22

uF

0.1

uF

22

uF

0.1

uF

22

uF

0.1

uF

QSFP_PWR_EN

QSFP_OC

Figure 12 : QSFP Interface

Signal Name Description Type

TD+/TD- High Speed Transmission pairs (x4) CML from SX to connector

RD+/RD- High Speed Receive pairs (x4) CML from connector to SX

SCL/SDA I²C slave interface

address 0x50 or 0x51

Open Drain from SX to

connector

ModSel Module select for I²C communication to prevent

bus conflicts

LVTTL from CPLD to connector

ResetL Module reset use to reset all user module settings

to their default state

LVTTL from CPLD to connector

IntL Use to indicate the host for a fault or status critical. OC from Connector to CPLD

ModPrsL Module present Short to GND in module

LPMod When the module is in a low power mode it has a

maximum power consumption of 1.5W

LVTTL from CPLD to connector

Page 21: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

Open Compute Project

21 April 2015

4.2.3 Port over Current Protection

The power for every 4 QSFP/ 6 SFP modules is controlled by a current limited power distribution switch. All of these power limiting switches are controlled by QSFP_PWR_EN signals (default enabled), originated from the CPLD. When the output load exceeds the current limit threshold, the power switch limits the current to a safe level. In addition, the SFP/QSFP_OC signals are asserted low and create an interrupt event towards the CPU from the CPLD.

4.2.4 Port I²C Interface

CPLD controls the I²C switch and connected to SwitchX-2 secondary I²C bus. 60 different I²C buses are connected from I²C switch to the 60 MSX1410-OCP ports. MOD_SEL register selects which I²C bus will be open– each time only one bus can be open.

The main reason for using this CPLD buffering method is that all the QSFP modules have the same address (0x50). By separating the buses in the CPLD, Switch-X2 can select a specific module to communicate with. Another reason for selecting a different bus for each port is to isolate problematic modules from the others. This way, if a specific port is corrupted, it does not affect the other ports.

Page 22: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

22 April 2015

4.3 I²C

MSX1410-OCP I²C tree has 4 optional masters:

1. SW (LPC to I²C module)

2. FW (SwitchX2)

3. External connector

4. BIOS (SMbus)

The PCH does not support I²C, therefore, LPC to I²C module was implemented inside

the MGMT CPLD.

I²C switching is done by external switch devices. These devices are controlled by an I²C

machine inside the CPLD. I²C channel access is controlled via relevant CPLD registers.

The CPU and the I²C external connector are sharing the same switches.

The I²C external connector is not connected directly to the head of the CPU I²C tree.

Access to CPU I²C is granted by request to CPLD 0x80.

When connection between the I²C external connector and the head of the tree is

enabled, the CPU I²C connection to the head of the tree is disabled.

In case of collision between masters, the following hierarchy will be implemented

(decreasing order):

1. Connector

2. SW I²C register

3. SW LPC register

4. FW

The I²C and the RS232 are sharing a single RJ45 connector.

Page 23: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

23 May 2014

The following diagram illustrates an I²C tree on MSX1410-OCP:

Figure 13: I²C Tree

Page 24: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

24 May 2014

4.4 CPLD

Three CPLD devices on the MSX1410-OCP provide monitoring and controlling

capabilities:

1. MGMT CPLD: located on the MGMT board. Controls fans, PS, power sequence,

software register map, software interrupt controller, firmware interrupt controller,

reset controller, I²C switching, LEDs, CPU power and safe BIOS.

2. Ports CPLDs (1-2): controls LEDs, SwitchX-2 reset logic, power monitor,

SwitchX-2 power sequence, I²C switching and ports control and monitor signals.

All CPLDs are powered from the auxiliary power; therefore, they are still functioning

during main 12V rail shutdown.

4.4.1 CPLD Features

Lattice XO2 CABGA332 device

4320 Logic elements

271 I/Os in four banks

96K bit UFM User flash memory

332-Pin FineLine BGA

Fail-safe mechanism using SPI flash memory

4.4.2 CPLD Field Upgrade

All Three CPLD devices can be field upgraded via SwitchX-2 JTAG emulation. Fail safe

feature is supported in case of field upgrade failure for all CPLDs.

Page 25: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

Open Compute Project

25 April 2015

TDI_CPLD1

TDO_CPLD1

Switch Board

CPLD1

CP

LD

Hea

der

SwitchX_FU_REQ

MNG Board

CPLD

CPLD MNG TDI

CPLD MNG TDO

TMS/TCK_SX_GPIO

TDI_SX_GPIO

TDO_SX_GPIO

SwitchX

SX_FU_EN

TDO_CPLD_LOOP

TMS/TCK_CPLD

Switch Board

CPLD2

JTAG Testing Connector

On Fan FRU

TDO_CPLD2

Tes

tin

g T

DO

SW Board

TMS/TCK_CPLD

TMS/TCK_CPLD

TDI

TDO

TDI

TDO

TDI

TDO

TMS/TCK

TMS/TCK

TMS/TCK

Single Ended Harness

Tes

tin

g T

MS

/TC

K

Buffer

Buffer

Buffer

Jumper

Buffer

EN

Tes

tin

g T

DI

Buffer

Jumper

BufferEN

2

2

2Buffer

Buffer

MGMT

Board

Figure 14: CPLD Field Upgrade

.

Page 26: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

26 April 2015

4.5 SPI and Safe BIOS Mechanism

The Serial Peripheral Interface on the chipset supports two 64MB (each) flash devices,

storing a Unified BIOS Code.

The MGMT board has two pairs of SPI flash devices: one serves as the default pair

and the other serves as the safe BIOS pair.

The BIOS SPI interface is described in Figure 15.

ISPDediprog

Conn.

PCH

SPIFlash

1

SPIFlash

0

Known Good Image

SPIFlash

1

SPIFlash

0

Current Image

3

CS#_0

CS#_1

CPLDBoot successful

PWRBTN_N

PLTRST_NKGI WP

CI WP BIOS setup mode

Figure 15: Safe BIOS Mechanism

The system has two SPI Flash pairs:

Known Good Image (KGI) pair

Current Image (CI) pair

Both of these pairs are loaded with identical images at the factory. The factory

programmed images are the KGI images. The KGI image is never intended for update.

The KGI provides an image to always recover the system.

The system always chooses the CI as the default boot device after power up. This

selection is made by the CPLD.

Page 27: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

Open Compute Project

27 April 2015

Safe BIOS Events flow:

1. Initial boot: the default is CI.

2. When PLTRST_N is asserted (logic low) and then de-asserted, a timer starts

inside the CPLD (this timer value can be a variable, based upon boot time of

the system).

3. The CPLD then waits for “Boot Successful” bit driven by the BIOS.

4. If Boot Successful is high before the timer has been expired, then this is a normal

boot.

5. If not, the mechanism starts working.

6. CPLD selects the KGI pair.

7. Then PWRBTN_N is asserted for 6 seconds, de-asserted for 5 seconds,

asserted for 1 second and then released. This will power cycle the platform

(PCH and CPU).

8. The system then boots from KGI.

9. After a successful boot, the CPLD selects the CI again.

10. At this stage, it is possible to recover the CI using BIOS FU mechanism.

In addition to the BOOT_SUCCESS signals, two other signals are connecting the PCH

to the CPLD:

i. BIOS_SETUP_MODE - Asserted high by the PCH in case the user entered the

setup menu. As long as this signal is high, the CPLD counter for boot success is

paused.

ii. BIOS_STARTED - Asserted high by the PCH once BIOS load was started.

BOOT_SUCCESS and BIOS_STARTED are used for status LED control.

Page 28: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

28 April 2015

4.6 Ethernet

The MSX1410-OCP provides two Ethernet MDI 10/100/1000MB/s ports. One port is connected through internal PCH MAC and Intel 82579 PHY (port 1). The other port is connected through Intel 82583 MAC/PHY (port 2).

These two MDI ports are routed to two RJ45 ports on the FRU panel.

The Ethernet interface is displayed in Figure 16.

GbE PHY

Intel 82579

GbE PHY

Intel 82583

PCH

8 la

ne

s P

CI-e

GE

N2

inte

rface

1

2

3

4

5

6

7

8

RJ45

RJ45MDI

MDI

Figure 16: Ethernet Interface

Page 29: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

Open Compute Project

29 April 2015

4.7 RS232 Interface

The 8-pin RJ-45 connector provides CLI connectivity (RS-232) to the CPU. The I²C and

the RS232 are sharing the same RJ45 connector. The RS-232 interface is shown in

Figure 17.

RS232

transceiverSIOPCH LPC

RJ45

Connector

(Shared with I2C)

Figure 17: RS-232 Interface

Page 30: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

30 April 2015

4.8 USB

The system has one external USB 2.0 host interface for general use. The USB port can

supply 500mA @ 5V and has internal current limiter with fault signal. Figure 18

describes the USB interface.

PCH

USB ports

0

1

2

3

4

5

6

7

.

.

Over Current protection PowerSwitch

CPLD

5V

OC1External

USB

connector

Figure 18: USB Interface

Page 31: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

Open Compute Project

31 April 2015

4.9 LPC

The PCH implements an LPC interface, as described in the Low Pin Count Interface

Specification, Revision 1.1. The LPC interface from the PCH is shown in Figure 19.

Super

IO

LPC busPCH

CPLD

Ports

CPLD1

Figure 19: LPC Interface

Page 32: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

32 April 2015

4.10 SATA

Up to two mSATA SSD (Solid State Drive) modules are supported in the system. Each SSD supports 4-64GB SLC or MLC.

On power down sequence, both of the SSD modules are powered from Super capacitor, in order to perform a graceful shutdown. The super capacitors provide power to the SSD modules while the rest of the system is in shutdown mode.

The SATA interface is described in Figure 20.

0

1

SA

TA

6G

b/s

PCH

2 3

4 5

SA

TA

3G

b/s

mSATA

module

mSATA

module

Figure 20: SATA Interface

Page 33: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

Open Compute Project

33 April 2015

4.11 PCIe

MSX1410-OCP implements 4 PCIe interfaces:

1. 1X from PCH to 82579

2. 1X from PCH to 82583

3. 8X (gen 2 for Celeron/i3, Gen3 for i5/i7) from CPU to 8X slot

4. 4X gen 2 connection between CPU and SwitchX -2.

The PCIe interface is shown in Figure 21.

82579

Eth PHY

82583

Eth

MAC/PHY

CPU

X16 PCIe

1 x16 or2 x8 or

1 x8 and 2 x4

Configured with

strapping resistors

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

8 la

ne

s P

CI-e

inte

rfac

e

1

2

3

4

5

6

7

8

PCH

X8 PCIe GEN2

Ports 1-4 and Ports 5–8 can be

independently configured as

four x1s, two x2s, one x2 and

2 x1s, or one x4 port widths

In order to change

configuration ME must be

updated

X8 PCIeslot

SwitchXPCIe/IB MNG port

Figure 21: PCIe Interface

Page 34: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

34 April 2015

5 Power

5.1 Power Consumption

5.1.1 Switch Board Max Power Consumption

Table 8: Switch Board Max Power Consumption

Configuration 3.3_SX

(3.3V)[W]

1.8_SX

(1.8V) [W]

1.2_SX

(1.2V) [W]

VCORE_SX

(0.9V) [W]

Total 12v

Including

DC/DC

Efficiency

36 Copper

(0W per port) 5.9 9.5 20.6 41.2 85.8

36 SR4

(3.5W per port) 77.9 9.5 20.6 41.2 165.8

36 LR4

(2W per port) 131.9 9.5 20.6 41.2 225.8

36 Active cables

(1.5W per port) 59.9 9.5 20.6 41.2 145.8

Page 35: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

Open Compute Project

35 April 2015

5.1.2 MGMT Board Power Consumption

voltage voltage 0.90 1.23 1.05 1.05 1.35 0.675 0.85 5.00 3.30 1.90 1.05 1.80 0.90 1.20 1.80

Device Qty. CPU Core CPU GFX CPU VCCIO PCH Vtt Vddq DDR3 Vtt DDR3 VCCSA 5V 3.3V 1.9V 1.05 CPU PLL ADIR Core ADIR ADIR

CPU 1 47.700 0.000 8.925 0.000 6.750 0.000 5.400 0.000 0.000 0.000 0.000 2.160 0.000 0.000 0.000 35.000

PCH 1 0.000 0.000 0.000 6.152 0.225 0.000 0.000 0.010 0.878 0.000 0.000 0.004 0.000 0.000 0.000 4.000

82583 1 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.017 0.505 0.205 0.000 0.000 0.000 0.000 0.727

82579 1 0.000 0.000 0.000 0.320 0.000 0.000 0.000 0.000 0.310 0.000 0.000 0.000 0.000 0.000 0.000 0.630

CPLD 1 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.330 0.000 0.000 0.000 0.000 0.000 0.000 0.330

SODIMM 1 0.000 0.000 0.000 0.000 4.050 0.506 0.000 0.000 0.017 0.000 0.000 0.000 0.000 0.000 0.000 4.573

mSATA 1 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.990 0.000 0.000 0.000 0.000 0.000 0.000 0.990

ConnectX-3 1 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.957 0.000 0.000 0.000 2.124 1.032 0.504 4.617

PCIe slot 0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000

USB 1 0.000 0.000 0.000 0.000 0.000 0.000 0.000 2.500 0.000 0.000 0.000 0.000 0.000 0.000 0.000 2.500

CRT 0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000

SPI f lash 2 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.132 0.000 0.000 0.000 0.000 0.000 0.000 0.132

SIO 1 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.132 0.000 0.000 0.000 0.000 0.000 0.000 0.132

OSC 4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.264 0.000 0.000 0.000 0.000 0.000 0.000 0.264

LEDs 15 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.594 0.000 0.000 0.000 0.000 0.000 0.000 0.594

3.3->1.9V

(Integrated in

82583) 1 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.878 0.000 0.000 0.000 0.000 0.000 0.000 0.878

3.3->1.05V

(Integrated in

82583) 1 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.644 0.000 0.000 0.000 0.000 0.000 0.000 0.644

3.3-> 1.8V CPU 1 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 3.967 0.000 0.000 0.000 0.000 0.000 0.000 3.967

3.3V-> 1.8 ADIR 1 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.924 0.000 0.000 0.000 0.000 0.000 0.000 0.924

Total 47.70 0.00 8.93 6.47 11.03 0.51 5.40 2.51 11.03 0.51 0.20 2.16 2.12 1.03 0.50

Power[W]

12V (including

90%

efficiency) 51.6612V_AUX

(including 90%

efficiency) 12.26

12V PCIe slot 0.00

Total 63.91

CPU power [W]

t> 2sec 35

10ms<t<2s 45

t<10mS 71

Current (Amp) Power[Watt] Total pow er

consumption

per part

Table 9: MGMT Board Power Consumption

5.1.3 System Power Consumption

Table 10: System Max Power Consumption

Part Power Current Comments

Fans 92.2 7.7 ---

MNG Board 51.7 4.3 ---

SWB 225.8 (with 36 LR4) 18.8 ---

12V Total 369.6 30.8 From 460W

12V AUX MNG 12.3 1.0 ---

12V AUX SWB 3.5 0.3 ---

12 AUX Total 15.7 1.3 From 24W

Page 36: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

36 April 2015

5.2 Power Monitoring and Distribution

5.2.1 Switch Board Power Monitoring and Distribution

12V to 0.9V

UCD74120

Phase 1A

12V to 1.2V

UCD74120

Phase 2A

15.26A

Sx Vcore12V to 0.9V

UCD74120

Phase 1B

Sx VDDHS

12V to 1.8V

UCD74120

Phase 2A

17.2A

Sx VDDO5.3A

1.27A

1.91A

0.44A

36 x LR4, QSFP LEDs, Sx

Peripherals

SX VDDPLL, VDDA

12V to 3.3V

UCD74120

Phase 1A

20A6.11A

0.64A

I2C GPIO

UCD

CPLD +

SPI Flash

VPD

Thermal

Sensors

UCD9224

0x27

12V to 3.3V

UCD74120

Phase 1B

UCD9224

0x41

45.8A

39.9A

6.11A

18.8A

B2

B

Po

we

r

Co

n.

VBATA

12V

3.3V_Aux

12V to 0.9V

UCD74120

Phase 3A

15.26A

15.26A

1.27A

1.27A

B2

B S

E

Co

n.

12V to 1.2V

UCD74120

Phase 3A

0.44A

20A

8.6A

8.6A

Figure 22: Switch Board Power Distribution

CPLD 0xXX

UCD’s

&

DC2DC

Comparators

PWR_OFF

PG_UCD[1..2]

12V_PG

PG_3.3V_AUX

UCD_ALERT#[1..2]

9 QSFP OC limiterOC_QSFP[1..9] 9

PWR_EN_QSFP[1..9] 9

2

PG_1.8V

VCORE_PG

1.2V_PG

3.3V_PG

2

3.3V Aux

Vcore 3.3V SX 1.2V 1.8V

Figure 23: Switch Board Power Monitor and Power Sequence

Page 37: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

Open Compute Project

37 April 2015

5.2.2 MGMT Board Power Monitoring and Distribution

4.42A

3.75A

12V to

1.05V

PCH

POW000080

VCC1P05_LAN

1.48A

8.5A

VCCP1P05_S

6A

VCC0P85_S

0.5A

53A

VCC_CORE

33A

VCC_GFXCORE

VCC3P3_A

FUSE 40A

VBATA

12V_PS1

12V_PS2 FUSE 40A

4XFUSE

12V_FANS

VCC5_A

VCC1P35

12A

VCC1P5_S

0.17A

VCC1P8_S

1.4A

1_2V_CX30.86A

1_8V_CX3

CX3_VDD_CORE

2.36A

PM_SLP_LAN_N

VCC1P05_M

PM_SLP_M_N

VCC1P05_S

PM_SLP_S3_N

VCC12_S

VCC5_S

PM_SLP_S3_N

3.3V to 1.8V

POW000066

PM_SLP_S3_N

VCC3P3_S

PM_SLP_S3_N

PM_SLP_LAN_N

VCC3P3_M

82579

PCH:VCCASW

PCH:VCCPLLPCH:VCCCORE

PCH:VCCIO

PCH

VCC_IMVPUSBNCP5212AISL62872HRUZPOW000096

PCIe SLOT

82579PCH:VCCSPISPI

RS232 TransiverSIO

PCIe SLOTSATADIMM SPDPCH

VCC3P3_A_PG

PWRGD_VCC1P05_LAN

PG12V to 5V

POW000059

PCH:VCCVRM

CPU:VCCPLLPCH:VCCDFT

3.3V to 1.8V

POW000010PM_SLP_S3_N

ConnectX3

CPU:VCCDQDIMM

PWRGD_1_2V_CX3

ConnectX3

ConnectX3

ALL_SYS_PWRGD

DELAY_VR_PWRGOOD

IMVP7

IC000234 GTVR_PWRGOOD

CPU

CPU:VAXG

CPU:VCCIOPCH:VCCDMISIO

VCC1P05S_VCCP_PWRGD V0P85_S_PWRGD

12V to

0.85V

CPU

POW000071

CPU:VCCSA

SWBTSEEPROMsADCCPLDConnectX-3 PCH:VCCSUSIO Board

SWB

12V to 1.2V

POW000075

12V to 0.9V

POW000075

PM_SLP_S4_NPM_SLP_S3_N

3.3V to 1.5V

POW000066PM_SLP_S3_N

VCC0P675_S

1.5A DIMM

DDRQ_VR_PWRGD

12V to

1.35V

POW000096 VTTREF

DIMM

VCC1P05S_VCCP_PWRGDV0P85_S_PWRGD

PM_SLP_S3_N

DDRQ_VR_PWRGD

PM_SYS_PWRGD

V1P8_S_PWRGD

1P05_PWRGD

PWRGD_CX3_VDD_CORE

VCC3P3_S PGVCC5_S PG

VCC1P5_S PG

1P8_S COMP

PWRGD_VCC1P05_LAN

VCC1P05_M_PWRGD

PM_SLP_M_N

VRPWRGD_3P3M_WOL

PM_M_PWRGD

1P05_S COMP

1P05_M COMP

3P3_M COMP

0.1A

1A

1A

28A

8A

0.3A

1A

5.34A

5.6A12V to 3.3V

POW000059

0.5A

3.6A

1.5A

PM_1P5_SMPWRGD

PM_1P5_SMPWRGD

VCCP1P05S

COMP

FUSE 3A

12V_SB1

FUSE 3A

12V_SB2

Current Measure

Current Measure

Power

sequence

AC/DC PS 1

AC/DC PS 2

PS2_ON_N

VCC3P3_A_PG150msdelay

PS1_ON_N

12V_SB1

12V_SB2

0.28A

Figure 24: System and MGMT Board Power Distribution, Monitoring and Sequence

Page 38: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

38 April 2015

5.2.3 System and MGMT Board Voltages and Currents Sensing

Certain voltages and currents in the system can be read by SW/FW via an 8-channel

I²C analog to digital converter. Voltage/current inputs to the A2D channels 2-7 are

MUXed by 1:2 MUX. Therefore, two values can be read per channel. The MUX select

signal is derived by the CPLD and can be controlled by SW and FW. The main 12V

voltages and currents can be read directly from the AC/DC PS.

The following table describes the voltage rail in each channel and the expected

reading.

The acceptable range for each rail is +-10% from nominal value.

Table 11: A/D Channels

A/D Channel MUX Select

Signal Monitored Voltage/Current “B” Parameter

0 NA DDR3 VTT 0.675V

(VCC0P675_S) 0.008 (See note 2)

1

NA

VCC0P85_S

(See Note 1)

Rail Level [VID0,VID1]

0.008 (See note 2)

0.675 [1,1]

0.725 [1,0]

0.8 [0,1]

0.9 [0,0]

2 0 12V_AUX1 (12VSB1 current) 0.008 (See note 2)

1 12V_AUX2 (12VSB2 current) 0.008 (See note 2)

3 0 3.3V (VCC3P3_A) 0.016 (See note 2,3)

1 5V (VCC5_A) 0.024 (See note 2,3)

4 0 CPU 1.8V (VCC1P8_S) 0.008 (See note 2)

1 CX3 1.2V (1_2V_CX3) 0.008 (See note 2)

5 0

CPU/PCH 1.05V

(VCC1P05_LAN) 0.008 (See note 2)

1 CPU 1.5V (VCC1P5_S) 0.008 (See note 2)

6 0 CPU 1.05V (VCCP1P05_S) 0.008 (See note 2)

1 CX3 1.8V (1_8V_CX3) 0.008 (See note 2)

7 0 DDR3 1.35V (VCC1P35) 0.008 (See note 2)

1 CX3 0.9V (CX3_VDD_CORE) 0.008 (See note 2)

Page 39: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

Open Compute Project

39 April 2015

Notes:

1. This rail has 4 valid values controlled by the CPU, using 2 lines which are connected to

the voltage regulator - VCCSA_SEL[0:1].

In order to allow the testing of all 4 levels in JTAG tests, these two controls are routed

through the CPLD (CPLD_VCCSA_SEL[0:1]).

2. The B parameter is used to calculate the real voltage/current from I²C reading, using the

following formula: V=B*R, where V is the real voltage and R is the I²C reading.

3. This voltage is divided by voltage divider before it is sampled; therefore its B parameter

contains the divider value as well.

Page 40: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

40 April 2015

5.3 FRU Control

5.3.1 Fan Control

The MGMT CPLD includes a fan controller which is controlled by the SwitchX-2 FW.

The fans speed is controlled by 8 PWM signals from the MGMT CPLD to the fans and

they are monitored by 8 Tacho signals from the fans towards the CPLD.

PWM:

A single PWM output signal from SwitchX-2 is connected to the MGMT CPLD.

This signal is reflected to all 8 fans as default.

8 PWM registers (register per fan) are available via the FW I²C (part of the FW

register map). Writing into one of these registers will override the PWM signal

into the specific mated fan

Tacho:

8 Tacho RO registers will be available via the FW I²C (part of the FW register

map).

FW will be interrupted in case PWM ≠ Tacho.

Fan present signal can be monitored by SW and FW via the CPLD.

Inside the FRU, I²C is connected only to one EEPROM. FW and SW can accesses the

fans I²C buses.

5.3.2 Power Supply Control

The PS is controlled via PMbus and a few signals. SW and FW can access the PMbus.

PS fans can be controlled via the PMbus. By default, PS fans are controlled

automatically by the PS. PS fans speed can only be increased through FW/SW, but

can never be decreased.

All other PS control signals can be controlled (for PS inputs) and monitored (for PS

outputs) via FW and SW registers maps.

Page 41: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

Open Compute Project

41 April 2015

The MSX1410-OCP FRU control is illustrated in Figure 25.

Fuse

MNG CPLDSwitchX

Fuse

PS

U 1

12V

PS1_PWOK

Fa

n C

on

ne

cto

r

PS1_SMBAlert#

PS1_I2C 2

PS2_PWOK

PS2_SMBAlert#

PS2_PSON

SX_I2C 2

Fa

n C

on

ne

cto

rF

an

Co

nn

ecto

rF

an

Co

nn

ecto

r

FAN1_I2CPWM1TACH1

FAN1 PRSNT

2

Fuse

Fuse

3.3V

3.3V

3.3V

3.3V

FAN2_I2C

PWM2TACH2

FAN2 PRSNT

2

FAN3_I2C2PWM3TACH3

FAN3 PRSNT

PS

U 2

FAN4_I2C

PWM4TACH4

FAN4 PRSNT

2

PS1_PSON

2

2

2

2

2

PS1_12V_Sense

PS2_12V_Sense

2

2

2

2

PS2_I2C

PWM 1

Figure 25: MSX1410-OCP FRU Control

Page 42: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

42 April 2015

5.4 Reset Table 12 specifies the reset scenarios and power monitoring in the system:

Table 12: MSX1410-OCP Reset Matrix

# Cause Source Target Description

1. Power monitor

circuit indication

CPLD Entire system The power monitor circuit verifies that

the local voltages are in the range of

±10% of the nominal value.

2. External push button

Short assertion

Push

Button

Entire system User reset from panel.

Assertion of more than ½ sec and

less than 12sec.

3. External push button

Long assertion

Push

Button

Entire system User reset from panel. Restores CPU

factory defaults.

Assertion of more than 12sec.

4. SW RST SW Entire system

SW has the ability to

reset specific

components via CPLD

SW request RST.

5. FW RST FW Entire system

SW has the ability to

reset specific

components CPLD

FW request RST

6. WD expired

CPLD Entire system

WD is disabled as

default.

WD mechanism is implemented in the

CPLD device. The CPU periodically

writes counter value via LPC to 4 WD

registers in the SW board 0xXX CPLD

– if the CPLD does not recognize a

counter value change, board reset is

initiated.

7. I²C Reset request CPU\SX I²C tree CPU\SX requests the CPLD to reset

the internal I²C Switches.

Page 43: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

Open Compute Project

43 April 2015

The MSX1410-OCP reset mechanism is displayed in Figure 26.

PCH

MNG CPLD

CPU

SIO

PLT_RST#

82579

PWR MON

XDP CPU

X86_RST_N

CPU XDP

Sus power OKSignals

RSMRST

150ms delay

82583

CPU

DIMM_A

DIMM_B

SM_DRAMRST_N

LPC RST_NPCH

I2C block

LPC block

PCIe Slot

PORTS CPLD 1

UCD’s&

DC2DCSx

SX_RST#

PORTS CPLD 2,3

CPLD2_RST#

UCD_RESET# [1..2]

PO

RT_R

ST# [1..6

0]

SFP/QSFP ports

FW_I2C_RST_CPLD2#

FW_I2C_RST#

SX_PRE_RST#

2

RST 2 SWITCH

FW I2C RST#

Mezz CPLD RST_N

LPC block

Back Panel PB on IO

board

RST PUSH BUTTON#

PORTS CPLD 2,3

LPC RST_N

Figure 26: MSX1410-OCP Reset Tree

Page 44: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

44 April 2015

5.5 Temperature Monitor

The following temperature sensors can be read by SW, FW or both:

Two external sensors provide temperature sensing:

o In front of fan FRUs: sense the ambient temperature when fans are pushing air into the system (Air in system)

o In front of the ports panel: sense the ambient temperature when fans are sucking air from the system (Air out system)

The Switch-X2 has an internal temperature sensing diode. The temperature sensed by the diode is processed and according to it, two signals may be asserted: Over Thermal Warning and Over Thermal Shutdown. The temperature above / below which these signals are activated /deactivated is controlled by firmware via the INI file, and it must be within the operational temperature range of the device.

The CPU has an internal sensor that can be monitored only by SW. The CPU can reduce its power (the performance might be reduced as well) in order to prevent from reaching its maximum value.

The PCH has an internal sensor that can be monitored only by SW.

Each SODIMM has one module thermal sensor that can be monitored only by SW.

Page 45: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

Open Compute Project

45 April 2015

5.6 Clock Distribution

5.6.1 Switch Clock Distribution

Figure 27 specifies the clock distribution in the switch board.

Figure 27: Switch Clock Distribution

Page 46: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

46 April 2015

5.6.2 MGMT Clocks

Most of the MGMT clocks are generated from two crystals and distributed by the PCH.

In addition, one 25MHz oscillator is buffered and distributed to the ETH PHYs and to

the CPLD.

Figure 28 describes the clock distribution for the MGMT.

CPU

Ivy Bridge ECC

DM

I 1

00M

Hz

DP

12

0 M

Hz

2X DDR3 Clocks

CPU XDP

32.768KHz

TIM000054

25MHz

TIM000053

SPI_CLK

8257925MHz

Crystal

TIM000053

PCH

PANTHER

POINT

QM77

CLK_FBRTCXTAL_25

CPLD

Ch. A DDR3+ECC

Ch. B DDR3+ECC2X DDR3 Clocks

100MHz ITP XDP

4x BIOS

SPI Flash

0 1

2 3

4

33

MH

z PC

I CL

K

0 1

2

3

Co

nfi

gu

rab

le C

LK

82583

82583

LPC CLK MGT CPLD

LPC CLK SIO

48MHz SIOSIO LPC CLK SW CPLD

82579

SwitchX

X8 PCIe slot

Buffer

0 1

2 3

4 5

6 7

A B

10

0M

Hz P

CIe C

LK

Gen

3

CPLD

CPLD

Figure 28: MGMT Clock Distribution

Page 47: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

Open Compute Project

47 April 2015

5.7 LEDs

T

Table 13 describes the indication LEDs on the MSX1410-OCP.

LED Qty. Color Description Originator Driver Location

QSFP

LEDs

12 Green/

Amber

Ethernet:

Off – Link down

Solid Green – Link up ,no traffic Blinking Green – Traffic (Received packet)

Blinking Amber – Physical errors

Switch-X2 Above

QSFP

Ports

QSFP

LEDs

SFP 12 Green/

Amber

Ethernet:

Off – Link down

Solid Green – Link up ,no traffic Blinking Green – Traffic (Received packet)

Blinking Amber – Physical errors

Switch-X2 Above

SFP

Ports

SFP

Status

LED

1 Amber /

Green

Off – No power

Solid Amber – Fault

Solid Green – Normal operation

Blinking Green – Boot

CPU On

Ports

Side

and on

FRU

side

Status

LED

General

Fans

LED

1 Amber /

Green

Off – No power

Green – All fans are operating

Amber – Fan failure

CPLD On

Ports

Side

General

Fans LED

Fans 1-4

LEDs

4 Amber /

Green

Off – No power

Green – Fan# is operating

Amber – Fan failure

CPLD FRU

side

Fans 1-4

LEDs

UID LED 1 Blue Static – The operator has activated this LED to identify this module.

Blinking – The Operator is instructing to

replace this module

SwitchX-2 Ports

Side

UID LED

Bad Port

indication

1 Green /

Amber

Blinking Amber – Bad port indication

Switch-X2 Ports

Side

Bad Port

indication

PSU

LED

1 Green/

Amber

Green – Both PSU OK

Amber –PSU is Faulty

CPLD Ports

Side

PSU LED

PSU

LED

1 per

PS

Green/

Amber

Output ON and OK GREEN PS PS PS FRU

No AC power to all OFF

Page 48: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

48 April 2015

T

Table 13: MSX1410-OCP LEDs

FRU power supplies

AC present / Only

12VSB on (PS off) or PS

in Smart on state

1Hz Blink

GREEN

AC cord unplugged or

AC power lost; with a

second power supply in

parallel still with AC input

power. AMBER

Power supply warning

events where the power

supply continues to

operate; high temp, high

power, high current, slow

fan.

1Hz Blink

Amber

Power supply critical

event causing a

shutdown;

failure, OCP, OVP, Fan

Fail AMBER

Power Supply FW

updating

2Hz Blink

GRENN

Page 49: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

Open Compute Project

49 April 2015

5.8 Power

5.8.1 Power Consumption

5.8.1.1 Celeron Based CPU, 48xDAC+12xSR4

Voltage

[V]

Current

[A]

Power

[W]

Fans (normal speed) 12V 3.2 38.4

CPU + periphery 12V 4.3 51.7

Switch + periphery 12V 6.4 76.6

SFP – DAC 12V 0 0

QSFP – SR4 12V 2.2 26.6

Total 12V power 12V 16.1 193.3

Auxilary power 12VSB 1.3 15.6

Table 14: Celeron, 48xDAC, 12xSR4

5.8.1.2 Celeron based CPU, 48xSR+12xLR4

Voltage

[V]

Current

[A]

Power

[W]

Fans (high speed) 12V 4.8 57.6

CPU + periphery 12V 4.3 51.7

Switch + periphery 12V 6.4 76.6

SFP – SR 12V 4.4 53.3

QSFP – LR4 12V 3.9 46.6

Total 12V power 12V 22.2 285.8

Auxilary power 12VSB 1.3 15.6

Table 15: Celeron, 48xSR, 12xLR4

Page 50: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

50 April 2015

5.8.2 Power Distribution – Switch

The power rails of SwitchX-2 and its periphery are driven from TI UCD9224 with UCD74120 power stages.

Figure 29 specifies the power distribution of the Switch power:

Figure 29: Power Distribution - Switch

Page 51: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

Open Compute Project

51 April 2015

5.8.3 Power Monitoring – Switch

Power monitoring on SwitchX-2 power rails is done in Port CPLD 1.

Figure 30 specifies Switch power monitoring.

Figure 30: Power Monitoring and Power Sequence- Switch

Page 52: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

52 April 2015

5.8.4 Power Distribution and Monitoring – Management

Figure 31 specifies power distribution on CPU, chipset, and fans.

12V to

1.05V

PCH

VCC1P05_LAN

VCCP1P05_S

VCC0P85_S

VCC_CORE

VCC_GFXCORE

VCC3P3_A

FUSE 40A

VBATA

12V_PS1

12V_PS2 FUSE 40A

FUSE

12V_FANS

VCC5_A

VCC1P35

VCC1P5_S

VCC1P8_S

PM_SLP_LAN_N

VCC1P05_M

PM_SLP_M_N

VCC1P05_S

PM_SLP_S3_N

VCC12_S

VCC5_S

PM_SLP_S3_N

PM_SLP_S3_N

VCC3P3_S

PM_SLP_S3_N

PM_SLP_LAN_N

VCC3P3_M

82579

PCH:VCCASW

PCH:VCCPLLPCH:VCCCORE

PCH:VCCIO

PCH

VCC_IMVPUSBNCP5212AISL62872HRUZPOW000096

PCIe SLOT

82579PCH:VCCSPISPI

RS232 TransiverSIO

PCIe SLOTSATADIMM SPDPCH

PG

PWRGD_VCC1P05_LAN

PG12V to 5V

PCH:VCCVRM

CPU:VCCPLLPCH:VCCDFT3.3V to 1.8V

PM_SLP_S3_N

CPU:VCCDQDIMM

ALL_SYS_PWRGD

DELAY_VR_PWRGOOD

IMVP7GTVR_PWRGOOD

CPU

CPU:VAXG

CPU:VCCIOPCH:VCCDMISIO

VCC1P05S_VCCP_PWRGD V0P85_S_PWRGD

12V to

0.85V

CPU

CPU:VCCSA

TSEEPROMsADCCPLDPCH:VCCSUSIO

SWB

PM_SLP_S4_NPM_SLP_S3_N

3.3V to 1.5VPM_SLP_S3_N

VCC0P675_S

DIMM

DDRQ_VR_PWRGD

12V to

1.35V VTTREF

DIMM

VCC1P05S_VCCP_PWRGDV0P85_S_PWRGD

PM_SLP_S3_N

DDRQ_VR_PWRGD

PM_SYS_PWRGD

V1P8_S_PWRGD

1P05_PWRGD

VCC3P3_S PGVCC5_S PG

VCC1P5_S PG

1P8_S COMP

PWRGD_VCC1P05_LAN

VCC1P05_M_PWRGD

PM_SLP_M_N

VRPWRGD_3P3M_WOL

PM_M_PWRGD

1P05_S COMP

1P05_M COMP

3P3_M COMP

12V to 3.3V

PM_1P5_SMPWRGD

PM_1P5_SMPWRGD

VCCP1P05S

COMP

FUSE 3A

12V_SB1

FUSE 3A

12V_SB2

Current Measure

Current Measure

Power

sequence

Figure 31: Management Power Distribution and Monitoring

Page 53: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

Open Compute Project

53 April 2015

5.8.5 System Voltages and Currents Sensing

System voltages and currents are accessible by SW/FW via an 8 channel I²C analog to

digital converter. Voltage/current inputs to the A2D channels 2-7 are MUXed by 1:2

MUX. Therefore, two values can be read per channel. The MUX select signal is derived

by the CPLD and can be controlled by SW and FW. The main 12V voltages and

currents can be read directly from the AC/DC PS. The following table describes the

voltage rail at each channel and the expected reading.

Acceptable range for each rail is +-10% from nominal value.

Table 16: A/D Channels

A/D Channel MUX Select

Signal Monitored Voltage/Current “B” Parameter

0 NA DDR3 VTT 0.675V (VCC0P675_S) 0.008

1

NA

VCC0P85_S

(See Note 1)

Rail level [VID0,VID1]

0.008

0.675 [1,1]

0.725 [1,0]

0.8 [0,1]

0.9 [0,0]

2 0 12V_AUX1 (12VSB1 current) 0.0586

1 12V_AUX2 (12VSB2 current) 0.0586

3 0 3.3V (VCC3P3_A) 0.016

1 5V (VCC5_A) 0.024

4 0 CPU 1.8V (VCC1P8_S) 0.008

1 --- 0.008

5 0 CPU/PCH 1.05V (VCC1P05_LAN) 0.008

1 CPU 1.5V (VCC1P5_S) 0.008

6 0 CPU 1.05V (VCCP1P05_S) 0.008

--- --- 0.008

7 0 DDR3 1.35V (VCC1P35) 0.008

--- --- 0.008

Page 54: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

54 April 2015

Notes:

Parameter B is used to calculate the real voltage/current from I²C reading, using the

following formula: V=B*R, where V is the real voltage and R is the I²C reading. This

voltage is divided by voltage divider before it is sampled; therefore, its parameter B

contains the divider.

6 JTAG

The system’s MGMT board has standalone JTAG support; in addition, the system

allows JTAG support via a special fan FRU, while the top cover is assembled.

In order to connect to the MGMT JTAG chain, a special extension card is required (no

on-board connectors).

For lab CPLD burning, a few jumpers might have to be assembled, depending on the

board and on the system structure. For CPLD JTAG chain, please refer t o Error!

Reference source not found..

The SwitchX chain and the MGMT board chain are described in the following figure.

PCIe slot ConnectX-3 3.3V ó 1.05V CPU PCHTesting

Connector

To special

FAN FRU

Buffer

on SW

board

JTAG

header

Single

ended

harness

CPU XDP

SWB

SwitchX

3.3V ó 1.05V

Testing

Connector

To special

FAN FRU

Figure 32: MGMT Board and Switch Board JTAF Chains

6.1 Testing I²C GPIO

Each of the two boards has a dedicated I²C GPIOs for testing. This GPIO is for use only

during JTAG tests. The CPLD emulates I²C (using JTAG) to control this GPIO.

The GPIO allows control on critical signals during the JTAG test.

In addition, the I²C GPIO on the MGMT board is connected to the "Safe BIOS"

mechanism. This will allow switching between the 2 sets of SPI flash (Know Good

Image and Current Image) without the need of a jumper during the burning process.

Page 55: Open Compute MSX1410OCP 01 - Circle B · Open Compute Project 5 April 2015 Overview The MSX1410-OCP switch is a top of rack switch with 48 ports of 10GbE and 12 uplink ports of 40GbE

Open Compute Project

55 April 2015

7 Compliancy

Shock & Vibration: ETSI EN 300 019-2-2: 1999-09

Humidity operating: 5% - 95% non-condensing

Operating temperature 0C-45C

Safety:

US/Canada: cTUVus

EU: IEC60950

International: CB

CCC

EMC (Emissions):

USA: FCC, Class A

Canada: ICES, Class A

EU: EN55022, Class A

EU: EN55024, Class A

EU: EN61000-3-2, Class A

EU: EN61000-3-3, Class A

Japan: VCCI, Class A

Environmental

EU: IEC 60068-2-64: Random Vibration

EU: IEC 60068-2-29: Shocks Type I /II

EU: IEC 60068-2-32: Fall Test

Acoustics:

ISO 7779

ETS 300 753