UK83059300fUK – Translation of the original operating manual
Accessories for heat pumps
Operating ManualHydraulic Station
2 Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
Table of contents
1 About this operating manual .........................31.1 Validity ..............................................................31.2 Reference documents ...................................31.3 Symbols and markings ..................................31.4 Contact ............................................................4
2 Safety .......................................................................42.1 Intended use ...................................................42.2 Personnelqualifications ................................42.3 Personal protective equipment ....................42.4 Residual risks .................................................42.5 Avoid damage to property ............................4
3 Operation and care ............................................53.1 Energy and environmentally conscious
operation ..........................................................53.2 Maintenance ...................................................5
4 Scope of supply ...................................................64.1 Accessories.....................................................64.2 Components of the device ............................6
5 Transport, installation and assembly .........75.1 Unpacking and transport ..............................75.2 Making transport easier ................................75.3 Carrying the device and transporting
with handcart ..................................................75.4 Installation .......................................................85.5 Installation / hydraulic connection to the
heating circuit and the domestic hot water .....85.6 Safety module .................................................95.7 Expansion vessel ...........................................95.8 Hydraulic connection for the
domestic hot water tank ................................9
6 Electrical installation .........................................9
7 Installing the control device ......................... 11
8 Flushing,fillingandventing ..........................128.1 Heating water quality ...................................128.2 Flushandfilltheheatingand
domestic hot water charging circuit ...........128.3 Flushing,fillingandventing
the domestic hot water tank .......................13
9 Insulate hydraulic connections ...................14
10 Settheoverflowvalve ....................................14
11 Commissioning ..................................................14
12 Faults ......................................................................1412.1 Unlock the safety temperature limiter .......14
13 Dismantling and Disposal .............................1513.1 Dismantling ...................................................1513.2 Disposal and Recycling ...............................15
Technical data / Scope of supply ..............16HSV ........................................................................16HSDV .....................................................................18
Free pressing ......................................................20HSV 9M1/3 ..............................................................20HSDV 9M1/3 ...........................................................20HSV 12M3, HSV 12.1M3 .......................................20HSDV 12M3, HSDV 12.1M3 .................................20
Dimensioned drawings...................................21HS(D)V 9M1/3 .........................................................21HS(D)V 12M3 ..........................................................22HS(D)V 12.1M3 .......................................................23
Installation plans ...............................................24HS(D)V 9M1/3 .........................................................24HS(D)V 12M3, HS(D)V 12.1M3 ............................25
Terminal diagrams ............................................26HSV ........................................................................26HSDV .....................................................................27Terminal diagram, mains connection
heat pump 1~230V + electric heating element 3~400V ...........28
Terminal diagram, mains connection heat pump 1~230V + electric heating element 1~230V ............29
Terminal diagram, mains connection heat pump 3~400V + electric heating element 3~400V ...........30
Circuit diagrams ................................................31HSV ........................................................................31HSDV .....................................................................33
3Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
1 About this operating manualThis operating manual is part of the device.
► Before working on or with the device, read the op-erating manual carefully and follow it for all activi-ties at all times, especially the warnings and safe-ty instructions.
► Keep the operating manual to hand at the de-vice and hand over to the new owner if the device changes hands.
► If you have any questions or anything is unclear, ask the local partner of the manufacturer or the factory's customer service.
► Note and follow all reference documents.
1.1 ValidityThis operating manual exclusively refers to the device identifiedbytheratingplate.
1.2 Reference documentsThe following documents contain additional informa-tion to this operating manual:
● Planning & design manual, hydraulic integration
● Operating manual of the heating and heat pump controller
● Brief description of the heat pump controller
● Operating manual of the expansion board (acces-sories)
● Log book
● Heat pump manual
1.3 Symbols and markings
Identificationofwarnings
Symbol MeaningSafety-relevant information. Warning of physical injuries.
DANGER Indicates imminent danger resulting in severe injuries or death.
WARNING Indicates a potentially dangerous situation, which can result in severe injuries or death.
CAUTION Indicates a potentially dangerous situation, which can result in moderate or minor injuries.
IMPORTANT Indicates a potentially dangerous situation, which can result in property damage.
Symbols in the document
Symbol MeaningInformationforqualifiedpersonnel
Information for the owner/operator
Requirement for action Single step action prompt1., 2., 3., … Numbered step within a multi-step
action prompt. Keep to the given order.Additional information, e.g. a tip on making work easier, information on standards
Reference to further information elsewhere in the operating manual or in another document
● Listing
4 Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
1.4 ContactAddresses for purchasing accessories, for service cases or for answers to questions about the device and this operating manual can be found on the internet and are kept up-to-date:
● www.ait-deutschland.eu
2 SafetyOnly use the device when it is in flawless technicalcondition and only use it as intended, safely and aware of the hazards, and follow this operating manual.
2.1 Intended useThe device is solely intended for the following func-tions:
● Heating
● Domestic hot water preparation
► Proper use includes complying with the operating conditions ( „Technical data / Scope of sup-ply“, from page 16) and the operating manu-al and noting and following the reference docu-ments.
► When using the local regulations note: laws, standards, guidelines, directives.
All other uses of the device are not as intended.
2.2 PersonnelqualificationsAll instructional information in this operating manual is solelydirectedatqualified,skilledpersonnel.
Only qualified, skilled personnel is able to carry outthe work on the device safety and correctly. Interfer-encebyunqualifiedpersonnelcancauselife-threaten-ing injuries and damage to property.
► Ensure that the personnel is familiar with the lo-cal regulations, especially those on safe and haz-ard-aware working.
► Allowqualifiedpersonnelwith"electrical"trainingonly to carry out work on the electrics and elec-tronics.
► Allow qualified, skilled personnel only to do anyother work on the system, e.g.
● Heating installer
● Plumbing installer
● Refrigeration system installer (maintenance work)
During the warranty and guarantee period, service work and repairs may only be carried out by personnel authorised by the manufacturer.
2.3 Personal protective equipmentThere is a risk of cutting your hands on sharp edges of the device.
► Wear cut-resistant protective gloves during trans-port.
2.4 Residual risks
Electric shockComponents in the device are energised with life-threatening voltage. Before opening the device panelling:
► Disconnect the device from power supply.
► Protect the device against being switched back on again.
2.5 Avoid damage to property
Improper actionRequirements for minimum scale and corrosion dam-age in hot water heating systems:
● Proper planning, design and commissioning
● Closed system with regard to corrosion
● Integration of an adequately dimensioned pres-sure maintaining device
● Use of deionised heating water (VE water) or VDI 2035 water
● Regular servicing and maintenance
If a system is not planned, designed, started up and operated according to the given requirements, there is a risk that the following damage and faults will occur:
● Malfunctions and the failure of components, e.g. pumps, valves
● Internal and external leaks, e.g. from heat ex-changers
5Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
● Cross-section reduction and blockages in compo-nents, e.g. heat exchanger, pipes, pumps
● Material fatigue
● Gas bubbles and gas cushion formation (cavita-tion)
● Negativeeffectonheattransfer,e.g.formationofcoatings, deposits, and associated noises, e.g. boilingnoises,flownoises
► Note and follow the information in this operating manual for all work on and with the device.
Unsuitablequalityofthefillandmake-upwater in the heating circuitTheefficiencyofthesystemandtheservicelifeoftheheat generator and the heating components depend decisively on the quality of the heating water.
Whenthesystemisfilledwithuntreateddrinkingwa-ter, calcium precipitates as scale. Lime scale deposits form on the heat transfer surfaces of the heating. The efficiencydropsandenergycostsrise.Inextremecas-es, the heat exchangers will be damaged.
► Fill the system exclusively with deionised heating water (VE water) or VDI 2035 water.
3 Operation and care
NOTEThe device is operated via the control panel of the heating and heat pump controller ( operating manual of the heating and heat pump controller).
3.1 Energy and environmentally conscious operation
The generally accepted requirements for energy con-scious and environmentally conscious operation of a heating system also apply to use of a heat pump. The most important measures include:
● Nounnecessarilyhighflowtemperature
● No unnecessarily high domestic hot water tem-perature (note and follow local regulations)
● Do not open windows with just a gap or tilt open (continuous ventilation), but instead open wide for a short time (shock ventilation)
● Always ensure that the controller settings are cor-rect
3.2 MaintenanceWipe down the outside of the device only using a damp cloth or cloth with mild cleaning product (wash-ing up liquid, neutral cleaning product). Do not use any harsh, abrasive, acid or chlorine-based cleaning prod-ucts.
6 Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
4 Scope of supplyExample of scope of supply arrangementExample HS(D)V 9M1/3
1 Compact device (domestic hot water tank and buffertank,withoutheatpump)
2 Accompanying parts package: safety module, pump ball valves, outdoor temperature sensor, adjustable feet
3 Accompanying parts package: control panel for the heating and heat pump controller
1. Inspect the delivery for outwardly visible signs of damage.
2. Inspect the scope of supply for completeness. Any defects or incorrect deliveries must be report-ed immediately.
4.1 AccessoriesThe following accessories are available for the device through the manufacturer's local partner:
● Expansion circuit printed board with various addi-tional functions
● Room control panel for controlling the main func-tions from the living room
● Electrical connection kit
4.2 Components of the deviceExample HS(D)V 9M1/3
1 Shut-offvalvewithdrainvalve (withfillanddrainvalveinthecaseof HS(D)V 12…)
2 Shut-offvalvewithfillanddrainvalve3 Heating circuit recirculating pump (HUP)4 Domestic hot water tank5 Overflowvalve6 Electric heating element behind shielding
panel7 Switchover valve domestic hot water8 Heating circuit safety module (insulated)9 Protection anode10 Controller11 Switch box12 Expansion tank13Buffertank14Drainingoffbuffertank15 Feet for adjusting screws
7Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
5 Transport, installation and assembly
5.1 Unpacking and transport
Notes on safe transportThe device is heavy ( „Technical data / Scope of supply“, from page 16). There is a risk of injuries or damage to property if the device falls or overturns.
There is a risk of cutting your hands on sharp edges of the device.
► Wear cut resistant protective gloves.
The hydraulic connections are not designed for me-chanical loads.
► Do not lift or transport the device by the hydraulic connections.
Transport the device preferably with a pallet truck, al-ternatively with a handcart or by carrying.
Transport with a pallet truck ► Transport the device to the place of installation
packaged and secured on a wooden pallet.
Unpacking1. Removeplasticfilms.Ensurethatyoudonotdam-
age the device.
2. Dispose of the transport and packaging material in an environmentally friendly way and in accord-ance with local regulations.
3. Remove the film from the plastic element of thefront panel at the place of installation.
If the device is to be carried, then it is recommended that the wooden pallet is not removed yet.
5.2 Making transport easierIn order to make the transport simpler and easier, the whole hydraulic system(including the controller with switch box) can be unscrewed beforehand.
The hydraulic system is fastened to the tank with 3 hexagonal bolts.
Beispiel HS(D)V 9M1/3
1 4 union nuts, which must be loosened when unscrewing
2 3 hexagonal bolts
First loosen the union nuts (1) on the pipework to the tank, then the 3 hexagonal bolts (2) and then remove the whole hydraulic system from the tank.
5.3 Carrying the device and transporting with handcart
Carrying the hydraulic stationIn order to make it easier to carry, a T-piece with two doublenipplescanbefittedonthedomestichotwateroutlet. It is recommended that the wooden pallet is on-ly removed after carrying is complete.
► Carry the hydraulic station to the installation site with 3 – 4 people.
8 Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
Transporting the hydraulic station with a handcart1. Load the hydraulic station with the underside of
the device on the handcart.
2. Secure the hydraulic station to the handcart with lashing straps.
3. Transport the hydraulic station to the installation site.
5.4 Installation
Installation site
IMPORTANTOnly ever install the device inside buildings.
The installation area must be frost-free and dry. It must fulfiltherelevantlocalregulations.
„Installation plans“, from page 24 and „Dimen-sioned drawings“, from page 21, for the respec-tive model
1. Place the device on a stable and horizontal sur-face, preferably decoupled from structure-borne noise.
2. Tilt the device slowly and carefully to one side.
3. Secure the tilted device to ensure that it cannot tip back to its initial position.
4. Fit the adjusting screws to all 3 feet.
Screw-in the adjusting feet
5. Tilt the device slowly and carefully back to its ini-tial position.
6. Level out the three adjusting screws.
7. If the hydraulic system was dismantled for trans-port reasons, then it must be screwed back into place on the tank!
5.5 Installation / hydraulic connection to the heating circuit and the domestic hot water
NOTEBefore connection to the heating system, the heatingcircuitmustbethoroughlyflushed.
„Dimensioned drawings“, from page 21
IMPORTANTDamage to the copper pipes due to unacceptable loading!
► Secure all connections against twisting.
Cross-sections and lengths of the pipes for the heating circuit are adequately dimensioned. In do-ing so, ensure that the connection pipework be-tween the heat pump and hydraulic station are also taken into account.
Freely pressing the recirculating pump produces at least the minimum throughput required for the device type ( “Free pressing”, page 20).
Thecablesfortheheatingarefixedtothewallorceilingviaafixedpoint.
► Insert the vent at the highest point of the heating circuit.
► Lift up the hood at the front of the hydraulic sta-tion.
9Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
1. There are 3 grooves located on the left and right on the inside of the hood. There are 3 correspond-ing studs on the tower housing to lock the hood.
2. This enables it to be dismantled and re-assem-bled with a single manual action.
5.6 Safety moduleThe safety module for the heating circuit is in the ex-tra box.Install the safety module at the connection provided on the top of the device.The safety discharge of the safety valve must be dis-charged into the drain via a funnel waste trap in accord-ance with the respective valid standards, guidelines and directives.
5.7 Expansion vesselThe expansion vessel for the heating circuit is integrated.Always inspect whether the size of the expansion ves-sel is large enough for the system. If necessary, an ad-ditional expansion vessel must be installed on site in accordance with the relevant valid standards.
NOTEThe admission pressure of the expansion vessel must be adjusted to the system (ap-prox.0.5barlessthanthesystemfillingpres-sure) in accordance with calculation accord-ing to the relevant standards (EN 12828).
5.8 Hydraulic connection for the domestic hot water tank
Connect the domestic hot water tank according to DIN 1988 and DIN 4753 Part 1 (or the standards and direc-tives applicable locally).The working overpressure cited on the rating plate must not be exceeded. Install a pressure reducer if re-quired.The sensor for the domestic hot water preparation is already connected in the switch box.
IMPORTANTThe electrical conductivity of the domestic hot wa-ter must be > 100 µS/cm and must lie within the drinkable water quality limits.
6 Electrical installation
6.1 Connect the electrical cables
IMPORTANTIrreparable damage to the compressor due to wrongrotatingfield!
► Ensurethat there isaclockwiserotatingfieldforthe compressor load infeed.
Basic information on the electrical connection ● The specifications of the local energy supply
company may apply to electrical connections
● Fit the power supply for the heat pump with an all-pole circuit breaker with at least 3 mm contact spacing (per IEC 60947-2)
● Note the level of the tripping current ( „Technical data / Scope of supply“, from page 16))
● Comply with the electromagnetic compatibility regulations (EMC regulations)
● Lay unshielded power supply cables and shielded cables(buscable)sufficientlyfarapart(>100mm)
● Maximum line length: 30m
Cable extension details see heat pump manual
10 Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
5. Carry out electrical connections in accordance with the terminal diagram.
„Terminal diagram“ for the respective model, from page 26
1 Contactor2 Control panel3 Bus cable connection4 Electrical switch box5 Strain relief
The hydraulic station is connected on site to the sub-distribution according to the following scheme:
5
1 Heat pump2 Load Compressor3 Bus (shielded)4 Control voltage (for dual heat pump only)5 Hydraulic station6 Heating element load line7 Control voltage8 Load Compressor9 Sub-distribution
Establish the electrical connections between the heat pump and the hydraulic station1. Route the two plug-in connections of the load and
bus cables from the hydraulic station to the plug-in points on the heat pump.
NOTE.For dual output-controlled heat pumps, the lines (8 m) are already connected to the heat pump.
2. Couple the connections together.
3. Fit cover for plug-in connections.
6.2 Electrical connectionThe electrical connection is established via the switch box.
1. Strip the sheathing of all cables to the external loads before laying in the cable gland of the con-trol box.
2. Feed the cable on the rear of the hydraulic station through the cable gland into the switch box.
3. Open the switch box in the device. Only slightly undo the top two screws of the cov-
er plate. Remove the remaining screws. Unhook cover panel.
4. Feed the control and sensor cable as well as the cable for the EVU blocking time through the glands on the rear of the device and into the interi-or of the device. Lay the cables through the cable gland to the terminals in the switch box.
11Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
NOTEThe control panel for the heating and heat pump controller can be connected to a com-puter or network using a suitable network ca-ble, enabling the heating and heat pump con-troller to be controlled remotely from there.If such a connection is required, install a shielded network cable (category 6, with RJ45 connector) through the device and par-allel to the existing control cable of the heat-ing and heat pump controller during the elec-trical connection work.
NOTEIn devices with integrated electric heat-ing element, the electric heating element is connected for 9 kW (6 kW) in the factory. At contactor Q, it is possible to select 6 kW (4 kW) = 2 phase operation. Disconnect Q5/6 for this. Or 3 kW (2 kW) = 1 phase op-eration. Disconnect Q5/6 and Q5/4 for this. The values in brackets are for the 6 kW heat-ing element. Disconnected cables must be furnished with screw terminals. Only the phases cited above may be disconnected (safety temperature limiter).
7 Installing the control device1. Lift up the hood at the front of the hydraulic tower.
Four cut-outs in the switchgear compartment panel
12 Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
2. There are 4 hooks at the rear of the control panel, which are used to hook the control panel onto the switchgear compartment panel.
3. Press the hooked in control panel downwards un-til it latches into position.
4. Plug the control cable into the bottom of the con-trol panel.
1 Room control panel RBE RS 485 (accessory) connection
2 Network cable connection3 LIN-bus cable connection to the controller
board4 Modbus cable to Modbus distributor
connection
8 Flushing,fillingandventing
8.1 Heating water quality
NOTE ● Detailed information is also provided in VDI
Guideline 2035 “Vermeidung von Schäden in Warmwasserheizanlagen” (Avoiding damage to hot water heating systems)
● Required pH value: 8.2 … 10 ● For aluminium materials:
pH value: 8.2 … 8.5 ► Fill the system with deionised heating water
(VE water) or with water corresponding to VDI 2035 only (low-salt operation of the system).
Advantages of low-salt operation:
● Low corrosion-promoting properties
● No formation of mineral scale
● Ideal for closed heating circuits
● IdealpHvalueduetoself-alkalisationafterfillingthe system
● If necessary, simple alkalisation to pH value 8.2 by adding chemicals
8.2 Flushandfilltheheatinganddomestic hot water charging circuit
Outlet pipe of the safety valve is connected.
► Ensure that the set pressure of the safety valve is not exceeded.
NOTEThe venting programme on the controller can alsobeusedtosupporttheflushingandvent-ing process. It is possible to control individual recirculating pumps and also the switchover valve via the venting programme. As a result, it is not necessary to remove the valve motor.
1. PulltheU-clip(2)offthebaseofthevalvemotor(1).
2. Pullthevalvemotorcarefullyoffthe3-wayswitch-ing valve (3).
13Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
9. Ensure that the U-clip has latched into position correctly:
● Valve motor sits securely on the 3-way switching valve.
● Both prongs of the U-clip sit on the lug.
● The tips of the U-clip are visible by approx. 2 mm (notsignificantlymore!).
8.3 Flushing,fillingandventing the domestic hot water tank
IMPORTANTBefore flushing and filling the domestic hot wa-ter tank, the outlet pipe of the safety valve must be connected. The set pressure of the safety valve must not be exceeded.
1. Open the domestic cold water supply valve on the domestic hot water tank.
2. Open the domestic hot water valves at the tapping points.
3. Flush the domestic hot water tank until no more air discharges from the valves at the tapping points.
4. Close the domestic hot water valves at the tap-ping points.
3. Turn the spindle of the 3-way switching valve so that the rounded side of the spindle points in the direction of marking A of the connections of the 3-way switching valve.
A
B
4. Flush the domestic hot water charging circuit for approx. 1 minute.
5. Turn the spindle so that the rounded side of the spindle points in the direction of marking B of the connections of the 3-way switching valve.
6. Flush heating circuit thoroughly, until no more air is discharged.
7. Position the valve motor (1) on the 3-way switch-ing valve (3).
8. Insert the U-clip (2) into the base of the valve mo-tor.
14 Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
9 Insulate hydraulic connectionsInsulate hydraulic lines in accordance with local regu-lations.
1. Openshut-offdevices.
2. Perform a pressure test and check for leaks.
3. Insulate external piping on site.
4. Insulateallconnections,fittingsandpipes.
10 Settheoverflowvalve Heat pump manual
11 CommissioningCheck that
● The water supply to the domestic hot water tank is open.
● Thedomestichotwatertankisfilled.
● If the heat pump is switched on whilst the tank is empty, the control panel indicates a fault.
Operating manual of the heating and heat pump controller
Heat pump manual
12 Faults ► Read out the cause of the fault via the diagnostics
programme of the heating and heat pump control-ler.
► Contact the local partner of the manufacturer or the factory's customer service. Have the fault message and device number to hand.
12.1 Unlock the safety temperature limiter
A safety temperature limiter (2) is installed in the elec-tric heating element (3). If the heat pump fails or there is air in the system:
► Check whether the reset knob (1) in the centre of the safety temperature limiter (2) has jumped out (located underneath the cover).
► Press the reset button back in again.
1 Reset knob2 safety temperature limiter3 Electric heating element
► If the safety temperature limiter trips again, con-tact the local partner of the manufacturer or the factory's customer service.
15Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
13 Dismantling and Disposal
13.1 Dismantling The device is safely disconnected from the power
supply and protected against being switched back on again.
► Separate components by their materials.
13.2 Disposal and Recycling ► Recycle or ensure proper disposal of device com-
ponents and packaging materials in accordance with local regulations.
Buffer(standby)battery1. Useascrewdriver topushout thebufferbattery
on the processor circuit board of the control ele-ment.
2. Disposeof thebufferbattery inaccordancewithlocal regulations.
16 Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
Accessories for heat pump type HSV 9M1/3 HSV 12M3Air/water 8 kW output-controlled | Air/water 12 kW output-controlled • yes – no • | – • | •
Air/water dual output-controlled • yes – no – | – – | –
Air/water 7 kW to 8 kW output-controlled | Air/water 10 kW to 18 k Outdoor installation • yes – no – | – – | –
Air/water 9 kW to 14 kW RX Outdoor installation • yes – no – | – – | –
Air/water dual Outdoor installation • yes – no – | – – | –
Air/water dual RX Outdoor installation • yes – no – | – – | –
Installation locationRoom temperature min. | max. °C 5 | 35 5 | 35
Relative humidity % 60 60
SoundSound pressure level at 1 m distance inside dB(A) 36 36
Sound power level inside dB(A) 44 44
Heating circuitFlow rate: minimum | maximum (see heat pump for pipe dimensioning) l/h | l/h 600 | 1200 600 | 1900
Free pressing | Pressure loss | Flow rate bar | bar | l/h 0,63 | – | 1200 0,55 | – | 1900
Max. allowable operating pressure bar 3 3
Circulation pump control range min. | max. l/h 600 ı 1200 600 ı 1900
General unit dataTotal weight kg 150 220
Weight of individual components kg | kg | kg – | – | – – | – | –
Domestic hot water tankNet volume l 180 303
Magnesium sacrificial anode Impressed current | Magnesium • yes – no – | • – | •
Domestic hot water temperature, heating pump mode | Electric heating element up to °C | up to °C 60 | 65 60 | 65
Mixed water quantity according to ErP: 2009/125/EC (at 40 °C, draw-off of 10 l/min) l 230 400
Standing loss according to ErP: 2009/125/EC (at 65 °C) W 55 74
Maximum pressure | Operating pressure bar | bar 6 | 10 | 13 6 | 10 | 13
ElectricsVoltage code | all-pole fuse protection for heat pump *)**) 1 phase … | A 1~N/PE/230V/50Hz | B16 1~N/PE/230V/50Hz | B16
Voltage code | all-pole fuse protection for heat pump *)**) 3 phases … | A – | – 3~N/PE/400V/50Hz | B16
Voltage code | Control voltage fuse protection **) … | A 1~N/PE/230V/50Hz | B10 1~N/PE/230V/50Hz | B10
Voltage code | Electric heating element fuse protection **) 1 phase … | A 1~N/PE/230V/50Hz | B32 – | –
Voltage code | Electric heating element fuse protection **) 3 phases … | A 3~N/PE/400V/50Hz | B10 3~N/PE/400V/50Hz | B16
Degree of protection IP 20 20
Residual current circuit breaker if required type B B
Electric heating element output 3 | 2 | 1 phase kW | kW | kW 6 | 4 | 2 9 | 6 | 3
Circulation pump power consumption, heating circuit min. | max. W 4 | 75 4 | 75
Other unit informationSafety valve Heating circuit | Response pressure included in scope of supply: • yes – no | bar • | 3 • | 3
Buffer tank | Volume included in scope of supply: • yes – no | l • | 62 • | 82
Diaphragm expansion vessel Heating circuit | Volume | Prepressure incl. in scope of supply: • yes – no | l | bar • | 12 | 1,5 • | 18 | 1,5
Overflow valve | Changeover valve, heating -Domestic hot water integrated: • yes – no • | • • | •
Vibration decoupling, Heating circuit | Heat source included in scope of supply or integrated: • yes – no – –
Controller | Heat quantity recording | Extension board included in scope of supply or integrated: • yes – no • | • | – • | • | –813320a 813321a*) compressor only, **) note local regulations
HSV Technical data / Scope of supply
17Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
Accessories for heat pump type HSV 12.1M3Air/water 8 kW output-controlled | Air/water 12 kW output-controlled • yes – no • | •
Air/water dual output-controlled • yes – no – | –
Air/water 7 kW to 8 kW output-controlled | Air/water 10 kW to 18 k Outdoor installation • yes – no – | –
Air/water 9 kW to 14 kW RX Outdoor installation • yes – no – | –
Air/water dual Outdoor installation • yes – no – | –
Air/water dual RX Outdoor installation • yes – no – | –
Installation locationRoom temperature min. | max. °C 5 | 35
Relative humidity % 60
SoundSound pressure level at 1 m distance inside dB(A) 36
Sound power level inside dB(A) 44
Heating circuitFlow rate: minimum | maximum (see heat pump for pipe dimensioning) l/h | l/h 600 | 1900
Free pressing | Pressure loss | Flow rate bar | bar | l/h 0,55 | – | 1900
Max. allowable operating pressure bar 3
Circulation pump control range min. | max. l/h 600 ı 1900
General unit dataTotal weight kg 161
Weight of individual components kg | kg | kg – | – | –
Domestic hot water tankNet volume l 279
Magnesium sacrificial anode Impressed current | Magnesium • yes – no – | •
Domestic hot water temperature, heating pump mode | Electric heating element up to °C | up to °C 55 | 65
Mixed water quantity according to ErP: 2009/125/EC (at 40 °C, draw-off of 10 l/min) l 365
Standing loss according to ErP: 2009/125/EC (at 65 °C) W 66
Maximum pressure | Operating pressure bar | bar 6 | 10 | 13
ElectricsVoltage code | all-pole fuse protection for heat pump *)**) 1 phase … | A 1~N/PE/230V/50Hz | B16
Voltage code | all-pole fuse protection for heat pump *)**) 3 phases … | A 3~N/PE/400V/50Hz | B16
Voltage code | Control voltage fuse protection **) … | A 1~N/PE/230V/50Hz | B10
Voltage code | Electric heating element fuse protection **) 1 phase … | A – | –
Voltage code | Electric heating element fuse protection **) 3 phases … | A 3~N/PE/400V/50Hz | B16
Degree of protection IP 20
Residual current circuit breaker if required type B
Electric heating element output 3 | 2 | 1 phase kW | kW | kW 9 | 6 | 3
Circulation pump power consumption, heating circuit min. | max. W 4 | 75
Other unit informationSafety valve Heating circuit | Response pressure included in scope of supply: • yes – no | bar • | 3
Buffer tank | Volume included in scope of supply: • yes – no | l • | 83
Diaphragm expansion vessel Heating circuit | Volume | Prepressure incl. in scope of supply: • yes – no | l | bar • | 18 | 1,5
Overflow valve | Changeover valve, heating -Domestic hot water integrated: • yes – no • | •
Vibration decoupling, Heating circuit | Heat source included in scope of supply or integrated: • yes – no –
Controller | Heat quantity recording | Extension board included in scope of supply or integrated: • yes – no • | • | –813326*) compressor only, **) note local regulations
HSVTechnical data / Scope of supply
18 Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
Accessories for heat pump type HSDV 9M1/3 HSDV 12M3Air/water 8 kW output-controlled | Air/water 12 kW output-controlled • yes – no – | – – | –
Air/water dual output-controlled • yes – no • •
Air/water 7 kW to 8 kW output-controlled | Air/water 10 kW to 18 k Outdoor installation • yes – no – | – – | –
Air/water 9 kW to 14 kW RX Outdoor installation • yes – no – –
Air/water dual Outdoor installation • yes – no – –
Air/water dual RX Outdoor installation • yes – no – –
Installation locationRoom temperature min. | max. °C 5 | 35 5 | 35
Relative humidity % 60 60
SoundSound pressure level at 1 m distance inside dB(A) 33 33
Sound power level inside dB(A) 46 46
Heating circuitFlow rate: minimum | maximum (see heat pump for pipe dimensioning) l/h | l/h 700 | 1600 700 | 1600
Free pressing | Pressure loss | Flow rate bar | bar | l/h 0,65 | – | 1150 0,81 | – | 1150
Max. allowable operating pressure bar 3 3
Circulation pump control range min. | max. l/h 600 ı 1200 600 ı 1900
General unit dataTotal weight kg 150 220
Weight of individual components kg | kg | kg – | – | – – | – | –
Domestic hot water tankNet volume l 180 303
Magnesium sacrificial anode Impressed current | Magnesium • yes – no – | • – | •
Domestic hot water temperature, heating pump mode | Electric heating element up to °C | up to °C 60 | 65 60 | 65
Mixed water quantity according to ErP: 2009/125/EC (at 40 °C, draw-off of 10 l/min) l 230 400
Standing loss according to ErP: 2009/125/EC (at 65 °C) W 55 74
Maximum pressure | Operating pressure bar | bar 6 | 10 | 13 6 | 10 | 13
ElectricsVoltage code | all-pole fuse protection for heat pump *)**) 1 phase … | A 1~N/PE/230V/50Hz | B16 1~N/PE/230V/50Hz | B16
Voltage code | all-pole fuse protection for heat pump *)**) 3 phases … | A – | – – | –
Voltage code | Control voltage fuse protection **) … | A 1~N/PE/230V/50Hz | B16 1~N/PE/230V/50Hz | B16
Voltage code | Electric heating element fuse protection **) 1 phase … | A 1~N/PE/230V/50Hz | B25 – | –
Voltage code | Electric heating element fuse protection **) 3 phases … | A 3~N/PE/400V/50Hz | B10 3~N/PE/400V/50Hz | B16
Degree of protection IP 20 20
Residual current circuit breaker if required type B B
Electric heating element output 3 | 2 | 1 phase kW | kW | kW 6 | 4 | 2 9 | 6 | 3
Circulation pump power consumption, heating circuit min. | max. W 4 | 75 4 | 75
Other unit informationSafety valve Heating circuit | Response pressure included in scope of supply: • yes – no | bar • | 3 • | 3
Buffer tank | Volume included in scope of supply: • yes – no | l • | 62 • | 82
Diaphragm expansion vessel Heating circuit | Volume | Prepressure incl. in scope of supply: • yes – no | l | bar • | 12 | 1,5 • | 18 | 1,5
Overflow valve | Changeover valve, heating -Domestic hot water integrated: • yes – no • | • • | •
Vibration decoupling, Heating circuit | Heat source included in scope of supply or integrated: • yes – no – –
Controller | Heat quantity recording | Extension board included in scope of supply or integrated: • yes – no • | • | – • | • | –813324a 813325a*) compressor only, **) note local regulations
HSDV Technical data / Scope of supply
19Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
Accessories for heat pump type HSDV 12.1M3Air/water 8 kW output-controlled | Air/water 12 kW output-controlled • yes – no – | –
Air/water dual output-controlled • yes – no •
Air/water 7 kW to 8 kW output-controlled | Air/water 10 kW to 18 k Outdoor installation • yes – no – | –
Air/water 9 kW to 14 kW RX Outdoor installation • yes – no –
Air/water dual Outdoor installation • yes – no –
Air/water dual RX Outdoor installation • yes – no –
Installation locationRoom temperature min. | max. °C 5 | 35
Relative humidity % 60
SoundSound pressure level at 1 m distance inside dB(A) 33
Sound power level inside dB(A) 46
Heating circuitFlow rate: minimum | maximum (see heat pump for pipe dimensioning) l/h | l/h 700 | 1600
Free pressing | Pressure loss | Flow rate bar | bar | l/h 0,81 | – | 1150
Max. allowable operating pressure bar 3
Circulation pump control range min. | max. l/h 600 ı 1900
General unit dataTotal weight kg 161
Weight of individual components kg | kg | kg – | – | –
Domestic hot water tankNet volume l 279
Magnesium sacrificial anode Impressed current | Magnesium • yes – no – | •
Domestic hot water temperature, heating pump mode | Electric heating element up to °C | up to °C 60 | 65
Mixed water quantity according to ErP: 2009/125/EC (at 40 °C, draw-off of 10 l/min) l 365
Standing loss according to ErP: 2009/125/EC (at 65 °C) W 66
Maximum pressure | Operating pressure bar | bar 6 | 10 | 13
ElectricsVoltage code | all-pole fuse protection for heat pump *)**) 1 phase … | A 1~N/PE/230V/50Hz | B16
Voltage code | all-pole fuse protection for heat pump *)**) 3 phases … | A – | –
Voltage code | Control voltage fuse protection **) … | A 1~N/PE/230V/50Hz | B16
Voltage code | Electric heating element fuse protection **) 1 phase … | A – | –
Voltage code | Electric heating element fuse protection **) 3 phases … | A 3~N/PE/400V/50Hz | B16
Degree of protection IP 20
Residual current circuit breaker if required type B
Electric heating element output 3 | 2 | 1 phase kW | kW | kW 9 | 6 | 3
Circulation pump power consumption, heating circuit min. | max. W 4 | 75
Other unit informationSafety valve Heating circuit | Response pressure included in scope of supply: • yes – no | bar • | 3
Buffer tank | Volume included in scope of supply: • yes – no | l • | 82
Diaphragm expansion vessel Heating circuit | Volume | Prepressure incl. in scope of supply: • yes – no | l | bar • | 18 | 1,5
Overflow valve | Changeover valve, heating -Domestic hot water integrated: • yes – no • | •
Vibration decoupling, Heating circuit | Heat source included in scope of supply or integrated: • yes – no –
Controller | Heat quantity recording | Extension board included in scope of supply or integrated: • yes – no • | • | –813327*) compressor only, **) note local regulations
HSDVTechnical data / Scope of supply
20 Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
Bezeichnung:
Datei: 823284 Freie Pressung HSV 9M1_3
Seite: 1/1
Zeichnungsnummer:
Legende:“” Volumenstrom Heizwasser in m3/h∆pmax maximale freie Pressung
Freie Pressung HV 9-1/3
823284
Änd./ÄM/Ersteller/Datum
- /PEP 015-2016 / Döring / 17.07.2017
823284
0,0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
0,0 0,5 1,0 1,5 2,0 2,5 3,0
Δpm
ax [b
ar]
Δpmax
Δp
“ ” [m3/h]
Bezeichnung:
Datei: 823288 Freie Pressung HSDV 9M-1_3
Seite: 1/1Zeichnungsnummer:
Legende:“” Volumenstrom Heizwasser in m3/h∆pmax maximale freie Pressung
Freie Pressung HSDV 9M1/3
823288
Änd./ÄM/Ersteller/Datum
-/PEP015-2016/Bornmann/10.04.2018
823288
0,0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
0,0 0,5 1,0 1,5 2,0 2,5 3,0
Δpm
ax [b
ar]
Δpmax
Δp
“ ” [m3/h]
Bezeichnung:
Datei: 823285 Freie Pressung HSV 12M3
Änd./ÄM/Ersteller/Datum
- /PEP 016-2016 / Döring / 17.07.2017
823285
Seite: 1/1
Zeichnungsnummer:
Legende:“” Volumenstrom Heizwasser in m3/h∆pmax maximale freie Pressung
Freie Pressung HSV 12M3
823285
0,0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
1,0
0,0 0,5 1,0 1,5 2,0 2,5 3,0
Δpm
ax [b
ar]
Δpmax
Δp
“ ” [m3/h]
Bezeichnung:
Datei: 823289 Freie Pressung HSDV 12M-3
Änd./ÄM/Ersteller/Datum
-/PEP016-2016/Bornmann/10.04.2018
823289
Seite: 1/1Zeichnungsnummer:
Legende:“” Volumenstrom Heizwasser in m3/h∆pmax maximale freie Pressung
Freie Pressung HSDV 12M3
823289
0,0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
0,0 0,5 1,0 1,5 2,0 2,5 3,0
Δpm
ax [b
ar]
Δpmax
Δp
“ ” [m3/h]
Keys: UK823284 / UK823288
“” Volumetric flow of hot water∆pmax Maximum free pressing
Keys: UK823285 / UK823289
“” Volumetric flow of hot water∆pmax Maximum free pressing
Free pressing
HSDV 9M1/3HSV 9M1/3
HSDV 12M3, HSDV 12.1M3HSV 12M3, HSV 12.1M3
21Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
97 180 323
291 83 226
600
0
217 290
1547
<1800
23
1
5
67
4
639
0
649
5
99
834
30 300
0
547
1163
1651
508
216
11
8
9
10
A EB
Technische Änderungen vorbehalten.
87654321
www.ait-deutschland.euD - 95359 Kasendorf
Industriestraße 3ait-deutschland GmbH
1
1
Ers. d. Ers. f.
A
B
C
D
E
F F
E
D
C
B
A
4321
Benennung
a
Zust. Änderungstext
PEP 015/2016
Datum
21.8.2017
Von
RA Blatt
von
Werkstoff Gewicht
Maßstab 1:20 Det. Maßstab
Datum NameErstelltGepr.Norm.
21.8.2017 Aepfelbach
toleranzAllgemein- Oberflächen
ArtikelNr.
Schu
tzverm
erk IS
O 16
016 b
each
ten
DIN ISO 2768 -c
Aepfelbach21.8.2017Aepfelbach31.5.2012
RARA
21.8.201725.9.2012
PEP 015/2016
PEP 015/2011-a
819417
152063, 152067 , 150713, 150714Maßbild Hydraulikstation HS(D)V 9M1/3, HTD
Keys: UK819417aAll dimensions in mm.
Pos. Name Dim.A Front viewB Side view from leftE Rear view1 Safety module2 Heating water inlet (return) Rp1ʺinternalthread3 Heatingwateroutlet(flow) Rp1ʺinternalthread4 Control panel5 Emptying,buffertank G1/2ʺ6 Hot water inlet (from heat pump) Rp1ʺinternalthread7 Hot water outlet (to heat pump) Rp1ʺinternalthread8 Domestic hot water R1ʺexternalthread9 Circulation pump R3/4ʺexternalthread10 Cold water R1ʺexternalthread11 Penetrations for electric/sensor cables
HS(D)V 9M1/3Dimensioned drawings
22 Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
272 102 330
99 230 374 703
0 99 233
1557
<1844 1
3
4
6
5
7
2
352
0
469 496
1079
1732
212
E
8
9
10
11
740
0
26
687
7
73
995
A B
Technische Änderungen vorbehalten.
87654321
www.ait-deutschland.euD - 95359 Kasendorf
Industriestraße 3ait-deutschland GmbH
1
1
Ers. d. Ers. f.
A
B
C
D
E
F F
E
D
C
B
A
4321
Benennung
Zust. Änderungstext
Datum
Von
Blatt
von
Werkstoff Gewicht
Maßstab 1:20 Det. Maßstab
Datum NameErstelltGepr.Norm.
toleranzAllgemein- Oberflächen
ArtikelNr.
Schu
tzverm
erk IS
O 16
016 b
each
ten
DIN ISO 2768 -cL
Gruosso20.6.2017
NG
5.7.2017
PEP 016/2016-
819489
152064, 152068Maßbild Hydraulikstation Variabel 12kW HS(D)V
Keys: UK819489All dimensions in mm.
Pos. Name Dim.A Front viewB Side view from leftE Rear view1 Safety module2 Heating water inlet (return) Rp1ʺinternalthread3 Heatingwateroutlet(flow) Rp1ʺinternalthread4 Control panel5 Emptying,buffertank G1/2ʺ6 Hot water inlet (from heat pump) Rp1ʺinternalthread7 Hot water outlet (to heat pump) Rp1ʺinternalthread8 Domestic hot water R1ʺexternalthread9 Circulation pump R3/4ʺexternalthread10 Cold water R1ʺexternalthread11 Penetrations for electric/sensor cables
Dimensioned drawingsHS(D)V 12M3
23Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
0
EBA
5
67
1
4
32
101 0
11
10
9
8
12
0
Technische Änderungen vorbehalten.
64321
1
1
A
B
C
D
E
F
A
4321
Schu
tzverm
erk IS
O 16
016 b
each
ten
Keys: UK819511All dimensions in mm.
Pos. Name Dim.A Front viewB Side view from leftE Rear view1 Safety module2 Heating water inlet (return) Rp1ʺinternalthread3 Heatingwateroutlet(flow) Rp1ʺinternalthread4 Control panel5 Emptying,buffertank Rp1/2ʺinternalthread6 Hot water inlet (from heat pump) Rp1ʺinternalthread7 Hot water outlet (to heat pump) Rp1ʺinternalthread8 Domestic hot water R1ʺexternalthread9 Circulation pump R3/4ʺexternalthread10 Cold water R1ʺexternalthread11 Penetrations for electric/sensor cables12 Adjusting foot M12 (3x) variable height, additional 15-30mm
HS(D)V 12.1M3Dimensioned drawings
24 Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
>100 >500
>1200
>40
0
FS
OKF
>15
50
>50
0 >
200
FS
Legende: 819418 -Technische Änderungen vorbehalten.Alle Maße in mm.
OKF Oberkante FertigfussbodenFS Freiraum für Servicezwecke
87654321
www.alpha-innotec.deD - 95359 Kasendorf
Industriestraße 3Alpha-InnoTec GmbH
1
1
Ers. d. Ers. f.
A
B
C
D
E
F F
E
D
C
B
A
4321
Benennung
Aufstellungsplan, MindestabständeHydrauliktower Dual HTD
819418 -Zust. Änderungstext
PEP015/2011
Datum14.6.2012
RAVon
Blatt
von
Werkstoff Gewicht
Maßstab 1:50 1:25Det. Maßstab
Datum NameErstelltGepr.Norm.
5.6.2012 Aepfelbach14.6.2012 Aepfelbach
toleranzAllgemein-
DIN ISO 2768 -c
Oberflächen
ArtikelNr.
Schu
tzverm
erk IS
O 16
016 b
each
ten
Keys: UK819418All dimensions in mm.
Pos. NameFS Free space for service purposesOKF Topedgeoffinishedfloor
Installation planHS(D)V 9M1/3
25Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
>500 >100 >1300
>40
0
FS
>60
0
>18
10
>20
0
FS
Legende: 819490 -Alle Maße in mm.
OKF Oberkante FertigfußbodenFS Freiraum für Servicezwecke
Technische Änderungen vorbehalten.
OKF
87654321
www.ait-deutschland.euD - 95359 Kasendorf
Industriestraße 3ait-deutschland GmbH
1
1
Ers. d. Ers. f.
A
B
C
D
E
F F
E
D
C
B
A
4321
Benennung
Zust. Änderungstext
Datum
Von
Blatt
von
Werkstoff Gewicht
Maßstab 1:50 1:25Det. Maßstab
Datum NameErstelltGepr.Norm.
toleranzAllgemein- Oberflächen
ArtikelNr.
Schu
tzverm
erk IS
O 16
016 b
each
ten
DIN ISO 2768 -cL
Gruosso21.6.2017
NG
5.7.2017
PEP 016/2016-
819490
Hydraulikstation Variabel 12kW HS(D)VAufstellungsplan, Mindestabstände
Keys: UK819490
All dimensions in mm.
Pos. NameFS Free space for service purposesOKF Topedgeoffinishedfloor
HS(D)V 12M3, HS(D)V 12.1M3Installation plan
26 Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
HSV 9M
-1/3 - 12-M3
-a
Legend:Equipem
ent
A1A3EVUK11X20X200Term
inalsO
UT1
OU
T2O
UT3
OU
T4O
UT5
OU
T6O
UT7
OU
T8IN
3IN
4N
TC2N
TC3N
TC4N
TC5N
TC6N
TC8N
TC9
HU
P/(FP1) BUPacronymZW
1ZIP/BLPZW
2/FP1M
Z1/MIS
MA1/M
ISZU
PBU
PH
UP/(FP1)
EVU1
EVU2
TATBWTB1TRL ext.TVLTRLCW
ZUP
-X3-1
MISU
KFunction
Controller board; Attention: I-max =
6,3A/230VACSub-distribution unit internal installationEnergy supplier Control U
nitTerm
inal board, Modbus
Plug Mod-Bus
Control signal of additional heat generator 1circulation pum
p / Dom
estic Water charge pum
pControl signal of additional heat generator 2 (alternative is general m
alfunction) / Pump for m
ixing circuit 1 (Flex Config)Charge/discharge/cooling m
ixer 1 closedCharge/discharge/cooling m
ixer 1 openAuxiliary circulation pum
pD
iverting valve for domestic hot w
aterH
eating circuit circulating pump / (Pum
p for mixing circuit 1)
Energy supplier contact; closed on release; bridge if no blocking intervalEnergy supplier contact; closed on release; bridge if no blocking intervalExternal sensorAccessories: Process w
ater sensor/thermostat
Dew
point monitor bridge; cooling interrupted if contact open / Sensor M
K1External return sensorFlow
sensorReturn sensorEncoding resistor
ZW2/SST
831218a
FP1
ZIP
-X3-2-X4
EVU
-X5-1-X5-2
-X9
-X20
-X200
-K111
23
45
67
8
12
8
ABCDEF
ABCDEF
BlattBl.
113
45
67
AIT831218
Stromlaufplan
ait-deutschland Gm
bH
PEP015-2016ÄM
029/201818.04.201717.07.2018
AP OUT8OUT7OUT6OUT5OUT4OUT3OUT2OUT1
NN
LIN1IN2IN3IN4IN5
L12
L1L1
A1A2
NTC1GND1NTC2
TAGND2NTC3
TBWGND3NTC4
TB1GND4NTC5
TRL ext.GND5NTC6
TVLGND6
NTC7GND7NTC8
TRL
GND8NTC9CW
GND9
AGP1AIN1AGP2AIN2
AGND1AOUT1AGND2AOUT2
-X11-X10-X6
X1X5
X6X4 X3 X2
A/B/.../+12V/G
ND
-A3
-A1
ÄnderungD
atum
Datum
BearbeiterG
eprüftN
ormN
ame
18.04.2017Pfleger
R.
12V 1234561234
bluewhite
12
34
12
34
12
34
12
34
12
34
1
white / bluegreen
brownbrown
yellowyellow
12
35
4
1234 RJ45
MM
HSV Terminal diagram
27Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
HSD
V 9M-1/3 - 12-M
3-a
HU
P/(FP1)
Legend:Equipem
entA1A3EVUK11X20X200X300Term
inalsO
UT1
OU
T2O
UT3
OU
T4O
UT5
OU
T6O
UT7
OU
T8IN
3IN
4N
TC2N
TC3N
TC4N
TC5N
TC6N
TC8N
TC9 BUP
-X3-1
ZUPacronymZW
1ZIP/BLPZW
2/FP1M
Z1/MIS
MA1/M
ISZU
PBU
PH
UP/(FP1)
EVU1
EVU2
TATBWTB1TRL ext.TVLTRLCW
MIS
ZW"/SSTU
KFunctionController board; Attention: I-m
ax = 6,3A/230VAC
Sub-distribution unit internal installationEnergy supplier Control U
nitTerm
inal board, Modbus
Plug Lin-BusControl connector
Control signal of additional heat generator 1circulation pum
p / Dom
estic Water charge pum
pControl signal of additional heat generator 2 (alternative is general m
alfunction) / Pump for m
ixing circuit 1 (Flex Config)Charge/discharge/m
ixer 1 closedCharge/discharge/m
ixer 1 openAuxiliary circulation pum
pD
iverting valve for domestic hot w
aterH
eating circuit circulating pump / (Pum
p for mixing circuit 1)
Energy supplier contact; closed on release; bridge if no blocking intervalEnergy supplier contact; closed on release; bridge if no blocking intervalExternal sensorAccessories: Process w
ater sensor/thermostat
Sensor mixing circuit 1
External return sensorFlow
sensorReturn sensorEncoding resistor
831219a
FP1
-X3-2
ZIP
-X4
EVU
-X5-1-X5-2
-X9-X20
-X200
LIN
-K11
-X300
1~N
/PE/230V/50Hz
X10
-X10
12
34
56
78
12
8
ABCDEF
ABCDEF
BlattBl.
113
45
67
AIT831219
Stromlaufplan
ait-deutschland Gm
bH
PEP015-2016ÄM
029/201809.05.201717.07.2018
APAP
OUT8OUT7OUT6OUT5OUT4OUT3OUT2OUT1
NN
LIN1IN2IN3IN4IN5
L12
L1L1
A1A2
NTC1GND1NTC2
TAGND2NTC3
TBWGND3NTC4
TB1GND4NTC5
TRL ext.GND5NTC6
TVLGND6
NTC7GND7NTC8
TRL
GND8NTC9CW
GND9
AGP1AIN1AGP2AIN2
AGND1AOUT1AGND2AOUT2
-X11-X10-X6
X1X5
X6X4 X3 X2
GN
D/.../LIN
/12V
GN
D/.../LIN
/12V1~
N/PE/230V/50H
z
NPE
L
LN
PE
-A3
-A1
ÄnderungD
atum
Datum
BearbeiterG
eprüftN
ormN
ame
09.05.2017Pfleger
R.
blue
12
34
12
34
12
34
12
34
12
34
1
12Vwhite / blue 1234561234
brown
yellow
brown
12
34
12
34
32
1PE
green
white
1234 RJ45
LN
PE
LPE
N
blPE
br
MM
Terminal diagramHSDV
28 Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
Netz W
P1~230V +
DLE3~
400V-
-F10
-X9
-F11
-X8
-F13 -X100
-X10
Legend:Equipem
ent
A3F10F11F13
X8X9X10X100
UK
Function
Sub-distribution unit internal installationCut out auxiliary heatingCut out com
pressorCut out controller unit
Terminal in the sw
itch box for compressor output
Terminal in the sw
itch box; power supply additional heating output
Terminal strip in the sw
itch box; N/PE distribution for external 230V devices
Power supply W
P
831222
12
34
56
78
12
8
ABCDEF
ABCDEF
BlattBl.
113
45
67
AIT831222
Stromlaufplan
ait-deutschland Gm
bH
PEP018-201611.05.2017
AP
Information on fuses can be found in the technical data
PE3~N/PE/400V/50Hz
NL1L2L3
PE1~N/PE/230V/50Hz
NL1L2L3
1~N/PE/230V/50Hz
LNN
PEPE
-X9
-A3 -X8-X10
ÄnderungD
atum
Datum
BearbeiterG
eprüftN
ormN
ame
14.02.2017Pfleger
R.
L1L2
NPE
L3
Terminal diagram, mains connection heat pump 1~230V + electric heating element 3~400V
HS(D)V 9M1/3 HSDV 12M3, HSDV 12.1M3
29Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
Netz W
P1~230V +
DLE1~
230V-
-F10
-X9
-F11
-X8
-F13 -X100
-X10
Legend:Equipem
ent
A3F10F11F13
X8X9X10X100
UK
Function
Sub-distribution unit internal installationCut out auxiliary heatingCut out com
pressorCut out controller unit
Terminal in the sw
itch box for compressor output
Terminal in the sw
itch box; power supply additional heating output
Terminal strip in the sw
itch box; N/PE distribution for external 230V devices
Power supply W
P
831223
12
34
56
78
12
8
ABCDEF
ABCDEF
BlattBl.
113
45
67
AIT831223
Stromlaufplan
ait-deutschland Gm
bH
PEP018-201611.05.2017
AP
Information on fuses can be found in the technical data
PE1~N/PE/230V/50Hz
NL1L2L3
PE1~N/PE/230V/50Hz
NL1L2L3
1~N/PE/230V/50Hz
LNN
PEPE
-X9
-A3 -X8-X10
ÄnderungD
atum
Datum
BearbeiterG
eprüftN
ormN
ame
14.02.2017Pfleger
R.
L1L2
NPE
L3
HS(D)V 9M1/3 Terminal diagram, mains connection heat pump 1~230V + electric heating element 1~230V
30 Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
Netz W
P3~400V +
DLE3~
400V-
-F10
-X9
-F11
-X8
-F13 -X100
-X10
Legend:Equipem
ent
A3F10F11F13
X8X9X10X100
UK
Function
Sub-distribution unit internal installationCut out auxiliary heatingCut out com
pressorCut out controller unit
Terminal in the sw
itch box for compressor output
Terminal in the sw
itch box; power supply additional heating output
Terminal strip in the sw
itch box; N/PE distribution for external 230V devices
Power supply W
P
831221
12
34
56
78
12
8
ABCDEF
ABCDEF
BlattBl.
113
45
67
AIT831221
Stromlaufplan
ait-deutschland Gm
bH
PEP018-201611.05.2017
AP
Information on fuses can be found in the technical data
PE3~N/PE/400V/50Hz
NL1L2L3
PE3~N/PE/400V/50Hz
NL1L2L3
1~N/PE/230V/50Hz
LNN
PEPE
-X9
-A3 -X8-X10
ÄnderungD
atum
Datum
BearbeiterG
eprüftN
ormN
ame
14.02.2017Pfleger
R.
L1L2
NPE
L3
Terminal diagram, mains connection heat pump 3~400V + electric heating element 3~400V
HSV 12M3 HSV 12.1M3
31Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
HSV9M
-1/3 u. HSV12M
-3 Tower
-a
Legend:Equipem
entE22K10K11Q
5X8X9X20X400CableX100X200X400
-X93~N
/PE/400V/50Hz
ZW1
-Q5
-X400
-E22
UK
FunctionAuxiliary heatingController board; Attention: I-m
ax = 6,3A/230VAC
Control Unit
Contactor for auxiliary heatingD
istribution box power supply output com
pressorPow
er supply, output, additional heatingTerm
inal board, Modbus
Additional heating output connector, inputU
nit connectionPow
er supply WP
connector MO
D-Bus
Additional heating output connector, input
817444a
-X83~N
/PE/400V/50Hz-X100
3~N
/PE/400V/50Hz
-K10
-X200
-X10
-X20
-X6-X11
-K111
23
45
67
8
12
8
ABCDEF
ABCDEF
BlattBl.
123
45
67
AIT817444
Stromlaufplan
ait-deutschland Gm
bH
PEP015/2016ÄM
999/201709.12.201618.04.2017
APAP\z21
/2.B4
135
246
1359246
A/B/.../+12V/G
ND
12
X1X5
X6X4 X3 X2
34
12V
123456
ÄnderungD
atum
Datum
BearbeiterG
eprüftN
ormN
ame
09.12.2016Pfleger
R.
PEN
L1L2
L3
sw
ZW1
12
34
56
PE
sw
brbr
ws
ws
PEN
L1L2
L3
L1L2
NPE
L3
12
35
4
bluewhite
12
34
12
34
12
34
12
34
12
34
1
white / bluegreen
brownbrown
yellowyellow
1234 RJ45
HSV Circuit diagram 1/2
32 Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
HSV9M
-1/3 u. HSV12M
-3 Tower
-a
Legend:Equipem
entEVUB2K10M
5Q
5R3R4R5R9R20STBX10X400Y1
HU
PZW
1TBWTRLTVLCWBU
P
-X0
-X10
UK
FunctionEnergy supplier contact; closed on release; bridge if no blocking intervalFlow
sensorController board; Attention: I-m
ax = 6,3A/230VAC
Heating pum
p energy efficiencyContactor for auxiliary heatingD
omestic hot w
ater sensorReturn sensorFlow
sensorEncoding resistorResistorSafety tem
perature limiter, additional heating
Power supply controller 230V
Additional heating output connector, inputD
iverting valve for domestic hot w
ater
817444a
-X4
EVU4,64kOhm
-X3-2
HD
T6 - 13,3kOhm
; HD
T9 - 14,7kOhm
;
-Q5
-X3-1
-X400
-STB
-X400
-Q5
1~
-M5
-Y1 -X3-1-X6
-X10-R20
-X9-X5-1
-R3-R5
-X5-2
-R4-R9
12
34
56
78
12
8
ABCDEF
ABCDEF
BlattBl.
223
45
67
AIT817444
Stromlaufplan
ait-deutschland Gm
bH
PEP015/2016ÄM
999/201709.12.201618.04.2017
APAP\z21 LLNNPEPE
LLL
IN1
IN2
B4
1413
IN3
OUT178A1A2
ZW1
brbl
HU
P
PE
BUP
Out7
GND1A2
3
AIN1AOUT14
TBWTVL
TRLCW
-K10
M
ÄnderungD
atum
Datum
BearbeiterG
eprüftN
ormN
ame
09.12.2016Pfleger
R.
bl
br
bk
brsw
gr
NTC3
GND3
NTC6
GND6
NTC8
GND8
NTC9
GND9
Circuit diagram 2/2 HSV
33Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
HSD
V9M-1/3 u. H
SDV12M
-3 Tower
-ab
Legend:Equipem
entE22K10K11Q
5X8X9X20X400CableX100X200X400
-X93~N
/PE/400V/50Hz
ZW1
-Q5
-X400
-E22
UK
FunctionAuxiliary heatingController board; Attention: I-m
ax = 6,3A/230VAC
Control Unit
Contactor for auxiliary heatingD
istribution box power supply output com
pressorPow
er supply, output, additional heatingTerm
inal board, Modbus
Additional heating output connector, inputU
nit connectionPow
er supply WP
connector LIN-Bus
Additional heating output connector, input
817446b
-X83~N
/PE/400V/50Hz-X100
1~N
/PE/230V/50Hz
-K10-X10
-X20
-X6-X11
-X200
-K111
23
45
67
8
12
8
ABCDEF
ABCDEF
BlattBl.
123
45
67
AIT817446
Stromlaufplan
ait-deutschland Gm
bH
PEP015/2016ÄM
999/2017ÄM
999/2018
01.12.201618.04.201712.01.2018
APAPAP
/2.B4
135
246
1359246
12
X1X5
X6X4 X3 X2
34
12V
1
GN
D/.../LIN
/12V
23456
ÄnderungD
atum
Datum
BearbeiterG
eprüftN
ormN
ame
01.12.2016Pfleger
R.
PEN
L1L2
L3
sw
ZW1
12
34
56
PE
sw
brbr
ws
ws
PEN
L1L2
L3
L1L2
NPE
L3
blue
12
34
12
34
12
34
12
34
12
34
1
white / blue
brown
yellow
brown
12
34
green
white
1234 RJ45
HSDV Circuit diagram 1/2
34 Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
HSD
V9M-1/3 u. H
SDV12M
-3 Tower
-ab
Legend:Equipem
entEVUB2K10M
5Q
5R3R4R5R9STBX10X300X400Y1
HU
PZW
1TBWTRLTVLCWBU
P
-X0
-X10
UK
FunctionEnergy supplier contact; closed on release; bridge if no blocking intervalFlow
sensorController board; Attention: I-m
ax = 6,3A/230VAC
Heating pum
p energy efficiencyContactor for auxiliary heatingD
omestic hot w
ater sensorReturn sensorFlow
sensorEncoding resistorSafety tem
perature limiter, additional heating
Power supply controller 230V
Control connectorAdditional heating output connector, inputD
iverting valve for domestic hot w
ater
817446b
-X4
EVU -X3-2
HD
T6LWD
- 14,0kOhm
; HD
T9LWD
- 15,4kOhm
;
-Q5
-X300
1~N
/PE/230V/50Hz
-X3-1
-X400
-STB
-X400
-Q5
1~
-M5
-Y1 -X3-1-X6
-B2 -X9-X5-1
-R3-R5
-X5-2
-R4-R9
12
34
56
78
12
8
ABCDEF
ABCDEF
BlattBl.
223
45
67
AIT817446
Stromlaufplan
ait-deutschland Gm
bH
PEP015/2016ÄM
999/2017ÄM
999/2018
01.12.201618.04.201712.01.2018
APAPAP LLNNPEPE
LLL
IN1
IN2
B4
1413
IN3
OUT178A1A2
ZW1
brbl
HU
P
PE
BUP
Out7
GNDA
yellowwhitegreenbrown
AIN1AGND1AOUT1
TBWTVL
TRLCW
-K10
M
ÄnderungD
atum
Datum
BearbeiterG
eprüftN
ormN
ame
01.12.2016Pfleger
R.
LN
PE
bl
br
bk
brsw
gr
NTC3
GND3
NTC6
GND6
NTC8
GND8
NTC9
GND9
Circuit diagram 2/2 HSDV
35Subject to change without notice | 83059300fUK – Translation of the original operating manual | ait-deutschland GmbH
UK
ait-deutschland GmbHIndustriestraße 3D-95359 Kasendorf
www.ait-deutschland.eu