DescriptionThe
SR
L2 uses
infrared optics
to create
aportable refrigerant leak detector technology thathas a superior com
bination of sensitivity, speed,sensor life, battery life, portability, and ease of use.
Gas is pum
ped through the tip of the wand into
the sensor
within
the S
RL2
body. The
sensordetects changes in concentration, not absolute con-centration, m
aking it easy to detect leaks even inareas w
ith refrigerant in the air. The S
RL2 detects leaks as sm
all as 0.1 oz/year,w
hich exceeds the toughest SA
E J1627 standards.
The SR
L2 comes w
ith wall and car chargers for its
ultra-compact Li-ion polym
er battery which pow
ersthe S
RL2 for 8hrs of continuous operation before a
recharge is needed. That’s long enough to last yourentire w
orkday.U
nlike many leak detectors, oil vapor does not
trigger the SR
L2.The S
RL2 has vari-
able sensitivity
set-tings,
keeping ‘nui-
sance tripping’
to a
minim
um. A
quick andautom
atic 30 second self-calibration upon power-up
ensures optimal perform
ance. Abuilt in replaceable
filter blocks moisture and harm
ful particulates. TheS
RL2 also has a m
ute button and a peak hold func-tion.
Specifications Sensing elem
ent:Enhanced infrared photo optics
Sensor life: 10 yearsR
efrigerants:HFC
, CFC
, HC
FC, and blends
Sensitivity level (per SAEJ1627):
HIG
H: 0.1 oz/year and higher
ME
D:
0.5 oz/year and higherLO
W:
1.0 oz/year and higherR
esponse time: 0.5 to 1 second
Auto off:10 m
inutes after no activityB
attery:7.4VD
C(nom
inal), 900mA
h rechargeablelithium
ion polymer (m
odel H702550-2S
) techni-cian-replaceable battery.
Battery life:8 hours continuous use prior toneeding a charge. D
egradation (10-5%) after
500 charge/discharge cycles or two years,
whichever com
es first.Low
battery LED: Illum
inated when approxim
ate-ly 1 hour of battery life rem
ains.C
harge time: Less than 4 hours w
ith either sup-plied charger.
Operating environm
ent:32ºF (0°C) to 122ºF
(50°C) at <75%
RH
Storage environment:<80%
RH
meter and batt.
For 80% battery recovery:
-4ºF (-20°C) to 140ºF (60°C
) less than 1 month
-4ºF (-20°C) to 113ºF (45°C
) less than 3 months
-4ºF (-20°C) to 68ºF (20°C
) less than 1 yearPatents: #6,791,088 and #7,022,993
Accessories included:w
all charger, car charger,case, 10 extra filters, 5 spare O
-ring rubber gas-kets, battery (installed), and operator’s m
anual.
Quick Tips
1.K
eep the wand tip m
oving past suspected leaklocations.
2.O
nce a leak is detected, sweep the w
and backover to pinpoint.
3.To pinpoint larger leaks adjust sensitivity.
T2 T2P
EA
K
MU
TE
ON
/OFF
ON
/OFF
L/M/H
SENSITIV
ITYHML
PEAK
LOW-BA
TT
PRESS FO
R1 SEC
ON
D
SR
L2
InfraredR
efrigerantLeak D
etectorSEN
SITIVITY
HML
PEAK
LOW-BA
TT
WA
RN
ING
DO
NO
Topen battery com
partment or m
etercase. B
attery must be replaced by Fieldpiece.
DO
NO
Tcharge battery w
ith any other charg-er than those that cam
e with the instrum
ent!D
ON
OT
use the SR
L2 without the proper fil-
ter correctly installed. R
ead and follow the Lithium
Battery C
aresection in this m
anual.
!!
Operation
ON
/OFF Protection
To turn on/off the SR
L2 press and hold theO
N/O
FF button for one second. This slight delayprotects against inadvertant pressing. If you forgetto turn it off, it w
ill automatically go off in 10 m
inutes.
LEDB
ar Graph D
isplayThe eight segm
ent LED
display indicates thedegree of change
in refrigerant concentration. As
the concentration of refrigerant in the air increases,so does the num
ber of lit bars on the display.
L/M/H
Button (Sensitivity)
Set the sensitivity level by pressing the L/M
/H but-
ton. Low(L), m
edium(M
), or high(H) sensitivity w
illbe indicated by their respective LE
D.
Use the highest sensitivity that w
ill not give youfalse indications of a leak. The higher the concen-tration of refrigerant in the am
bient air, the lower the
sensitivity setting should be to minim
ize false trips.
Mute B
uttonP
ressing the MU
TE button toggles the sound of
the SR
L2 on and off.
Peak Button
The PE
AK
function holds the highest change inconcentration achieved w
hile continuing to detect
leaks. Press P
EA
K to toggle this function on and off.
Turning the PE
AK
function off will clear the peak
change. The PE
AK
LED
will light w
hen PE
AK
func-tion is on.
Leak Detection Procedure
Keep the S
RL2 aw
ay from any areas of potential
refrigerant leakage until the warm
-up and calibrationperiod
is over.
The w
arm-up
and calibration
sequence lasts about 30 seconds after ON
/OFF is
pressed. On startup, m
eter defaults to high sensitiv-ity.The m
ost likely points for refrigerant leaks are atthe soldered joints in refrigerant lines and changesin cross section or direction of these lines.
The SR
L2 detects changesin concentration of
refrigerant, not the absolute concentration of refrig-erant. This lets the user easily detect leaks in placesthat m
ay have refrigerant in the air, such as a refrig-erator leaking into an enclosed space. B
ecause theS
RL2 detects change, there is a specific “double-
pass” method used to find leaks.
1. The tip of the wand should be fairly close to the
line. You may need to be w
ithin 1/4” of a small
leak to detect it. In this case, using a secondhand to guide the tip along refrigerant lines m
aybe helpful.
2. Keep the tip m
oving along refrigerant lines at arate of 1-3 inches per second.
3. Once the S
RL2 indicates a change in concentra-
tion, note the spot on the line and keep the tipm
oving past the potential leak to refresh the airspace w
ithin the SR
L2 with clean air. (N
ote: Ifthe S
RL2 w
and moves through a very high con-
centration of refrigerant, you may need to use in
fresh air for 4 seconds before moving to step 4
in order to clear the refrigerant within the S
RL2.)
4. Return the tip back to, and past, the spot first
indicated. When the S
RL2 indicates a second
change, note the spot on the line. The source ofthe leak w
ill be near the midpoint betw
een thetw
o noted spots of indication. 5. Very high concentrations of refrigerant can
cause an overload which can take a few
sec-onds to clear.
Warranty and Service
The product is warranted to the original purchas-
er against defects in material or w
orkmanship for a
period of one (1) year from the date of purchase.
During the w
arranty period, Fieldpiece Instruments
will, at its option, replace or repair the defective unit. This w
arranty does not apply to defects resultingfrom
abuse, neglect, accident, unauthorized repair,alteration, or unreasonable use of the instrum
ent.A
ny implied w
arranty arising out of the sale ofFieldpiece's products including but not lim
ited toim
plied warranties of m
erchantability and fitness forpurpose are lim
ited to the above. Fieldpiece shallnot be liable for incidental or consequential dam
-ages.
Any
defective S
RL2
should be
returned to
Fieldpiece Instruments for w
arranty service alongw
ith proof of purchase. Call Fieldpiece for a return
material authorization (R
MA
). For out of warranty
service, send the SR
L2 meter w
ith battery installedalong w
ith an RM
Anum
ber. Your SR
L2 will be
repaired or replaced at Fieldpiece's option. Repair
price for SR
L2 meter is $155. R
epair price for SR
L2battery is $45. Fieldpiece Instrum
ents, Inc.580 W
est Central Ave. S
uite AB
rea, CA
92821P
hone: (714) 257-9060 Fax: (714) 257-9069w
ww
.fieldpiece.comS
RL2 testing an A
-coil in an evaporator, 1/4” from the line.
1/4”
More Products From
Fieldpiece
Modular
Expandability
Modular
expandability is
ability for
accessoryheads
and m
eters to
change configurations
tom
atch the various needs of an HVA
C/R
technician.A
ccessory heads (the sensors) send out a mV
signal, which represents the value of the m
easure-m
ent, to whatever m
eter is attached to it. Heads can
attach directly to the top of a Stick meter, D
L2 datalogger, or E
HD
L1. They can also plug into any meter
with m
V ranges using A
SLS
2 leads.
Stick Meter
This is the heart of modular expandability. In addi-
tion to being a full functioning multim
eter, any acces-sory head can be used w
ith it.
Model H
S36
Non contact voltage
Magnetic hanger
Autoranging
Backlight
Temperature
Volts, amps, ohm
sFrequency
Microfarads
Includes:H
S36 M
eterA
CH
4 Current C
lamp
ATB1 K
-type TCouple
AD
LS2 D
eluxe LeadsA
NC
1 Case
Accessory H
eadsA
ccessory heads are the sensors of multiple
parameters m
easured by technicians every day.They plug into a m
V range (depending on the head)
of a multim
eter. The multim
eter will display w
hatev-er the head is m
easuring. Instead of having to pur-chase and carry a separate instrum
ent for eachparam
eter, a technician can use multiple heads and
a single multim
eter to do the job.
Here are four of the m
any heads available:A
AV3 A
ir Velocity and Temperature
AD
MN
2 Dual-P
ort Manom
eterAV
G2 D
igital Vacuum G
augeA
OX
2 Com
bustion Check
Standalone Instruments
The SR
L2 is a standalone instrument for leak
detection. Accessory heads do not hook up to it.
Below
is a sampling of other standalone (non-m
od-ular) instrum
ents available from Fieldpiece.
SM
G5 M
egohm M
eterS
T4 Dual Tem
perature Thermom
eterS
RP
M2 O
ptical Laser Tachometer
SS
X34 S
uperheat and Subcooling for A
C &
Ref.
CA
T.III
300V
400A
CL
AM
P
AC
H4
AC
Current
Clam
p1A
AC
/ 1mVA
C400A
AC
MA
X
!
AirVelocity
&Tem
perature
Head
English
READ
LOBATT
ON
LCD
X100
Average(16
sec)
MetricReal
time
AAV3
AUTO-OFF
English
Metric
Ft/min
M/sKM/hr
MPHºF
ºCOFF
AOX2
CombustionCheck
%O%COTEMP
ON
GAS
OIL
Lo Batt
°C °FAUTOOFF
STABLE
Fuel Type
2
2
T/CCAL
AUTO-
OFFT/CCal
STA
BLE
Pr essure
Temp
SHor
SC
ONLO
BATT
Refriger
a tion
Superheat
andSubcooling
ENGLISHMETRIC
R134A
R404A
SetATM
ASX24
SH
SC
Air
Velo
city
&Tem
pera
ture
Head
En
glis
h
RE
AD
LO
BA
TT
ON
LC
DX
10
0
Av
era
ge
(16
se
c)
Me
tricR
ea
ltim
e
AA
V3
AU
TO
-O
FF
En
glis
hM
etric
Ft/m
inM
/s
KM
/hr
MP
HºFºC
OF
F
AD
MN
2
Dual-Port
Manom
eterA
ccessoryH
ead
P1
P2
P1-P
2
ON
0.1
EN
GL
ISH
ME
TR
IC0.0
1
(LC
D/1
0)
Lo
Ba
tt
Resolution
ZERO
AU
TO
OFF
P1
P2
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
AO
X2
Com
bustionC
heck
%O
%C
OT
EM
P
ON
GA
S
OIL
Lo
Ba
tt
°C °F
AU
TO
OFF
STA
BL
E
Fuel Type
22
T/CC
AL
Laser Digital Tachom
eter
Mode
Mem
ON
SR
PM
2 TEST
T2 T2A
TM
ON
/OFF
TY
PE
TE
MP.
UN
IT
KSHSC
ST
4
T1
T2
OFFS
ET
ON
OFF
T1-T
2
T1
T2
T2
1/0
.1º
ºT
2º
ºC
/F
Min
/Max
T2
HO
LD
ºFT
1
v17
Lithium
Battery C
areThe S
RL2 contains a very pow
erful two-cell lithi-
um ion polym
er battery. For a long battery life andsafe operation you m
ust observe the following:
Cautions
1. Charge only w
hile battery is inside the SR
L2w
ith a Fieldpiece supplied charger. Do not
charge externally. 2. D
o not expose the battery to temperatures high-
er than 140ºF. 3. D
o not charge the battery in or nearby heatedplaces, such as fire, hot vehicles, or direct sun-light.
4. Do not directly connect the battery to any bat-
tery charger. The included chargers connect tothe S
RL2, not the S
RL2 battery.
5. Do not solder directly on battery.
6. Do not use the battery for unspecified equip-
ment.
7. Do not expose the battery to direct im
pact orthrow
it. If the protection circuit on the battery isbroken, do not continue to use the battery.
8. Do not get the battery w
et.9. D
o not deform or pierce the battery in any w
ay. 10. If there is any battery leakage, do not touch
the battery. In the case that electrolyte gets intothe eyes, flush w
ith fresh water, do not rub, and
see a physician imm
ediately. 11. S
end in for replacement im
mediately if there is
any deformity, bad sm
ell, color change, or otherabnorm
ality.12. D
o not dissassemble or try to repair battery or
protective circuitry.13.The battery is technician-replaceable and m
ustbe sent to Fieldpiece Instrum
entsif a replace-
ment is needed. It is not user-replaceable.
ChargingTw
o chargers are included with the S
RL2. The
AC
charger plugs into a wall outlet (110-120 VA
C,
60Hz) and the car charger plugs into a car cigarette
lighter DC
plug.1. The battery is partially charged w
hen packaged.Fully charge the battery before first use.
2. The LOW
-BATT
LED
will light red w
hen the bat-tery is low
. 3. To recharge the S
RL2, plug one end of the
charger into the top of the SR
L2 and the otherinto the pow
er source. LOW
-BATT
will blink
while charging until the battery is fully charged.
When the S
RL2 battery is fully charged, LO
W-
BATT
turns off. 4. C
harge within operating environm
ent specifiedin the Specifications section in this m
anual. 5. Avoid frequent full discharges. S
everal partialdischarges w
ith frequent recharges are betterfor lithium
-ion batteries. Unlike nickel-based bat-
teries they have no charge mem
ory, and do notneed to be discharged before charging.
StorageThe battery should have a 40%
-50% charge dur-
ing prolonged storage of a month or longer. S
eeSpecifications section in this m
anual for proper stor-age environm
ent. B
attery life is dramatically reduced if the battery
is stored fully charged and/or at high temperatures.
Carrying C
ase W
hile both chargers fit in the included case, thecarrying case is intended to carry the leak detectoralone. M
ost users leave the chargers near thepow
er supply and carry around just the meter.
Larger cases, to hold both chargers plus extraaccessories, are available such as the A
NC
8 (seeO
ptional Accessories).
FilterAssessm
ent & R
eplacement
The filter blocks moisture and other contam
inantsfrom
the sensor. When it gets w
et, it constricts flowof air and it w
ill have to be replaced.Unscrew
thesensor tip and replace the w
hite filter so that therounded end is closest to the tip of the w
and. Use
only the Fieldpiece supplied filter. E
xtra bags of replacement parts (m
odel RFL2)
are available from Fieldpiece w
hich contain 10filters and 5 O
-rings.
Optional A
ccessoriesU
se model R
RE
2 when detecting in tight spaces,
such as through a condensor grille. Model R
FE2
extends the wand to 25.5”. The m
idsize case,m
odel AN
C8, holds everything w
ith room to spare.
9” Needle Tip P
robem
odel RR
E2
9” Flex Extension
model R
FE2
4 Pocket M
idsize Case
model A
NC
8