Orion-Mi Multi-loop Control System
• Configuration & Setup Worksheets
version 1.0
Note: this pdf file has an active table of contents when viewed with Adobe Viewer
This Excel Configuration Tool is assigned version number below
Version: v1.0Date 29-Apr-10
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 1
Orion-M Software Version
The software version levels for the Orion-M Control system can be viewed in the Setup\Offline Section,from the Help drop down menu; select “About Orion-M”.
Both the HMI (Human Machine Interface – color touchscreen) and Control Module firmware andsoftware versions will be displayed.
When obtaining replacement parts or to get assistance for setup and/or troubleshooting purposes, it isimportant to have this information available to insure that your request is processed properly and in atimely manner. It is recommended that this information be written down and kept in a readily accessiblelocation along with this manual, so that it is available when required.
HMI Version:CE Net Version: CM Firmware Version:
CM Program Version:
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 1
OEM Number of Loops-Monitors
Min-Max # Number000 - 15000 - 6
Max Digital Out 000 - 32000 - 30000 - 14000 - 16000 - 32
Configuration Name:Configured by:
Date Configured:
Max System Events
DescriptionMax Control LoopsMax Analog Out
Max Process AlarmsMax Analog In Max Digital In
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 1
OEM Loop Configuration
√√
TemperatureRH
(Wetbulb) ProcessSource
Loop (RH)Engr
Units*Decimal Point**
Low SP Limit
High SP Limit SP AM AT
1
2
3
4
5
6
7
8
9
10
1112131415
* Engineering Units: up to 3 characters** Decimal Point: temperature and RH (wetbulb) = 0 or 1; process = 0, 1, 2 or 3*** Loop Tag Name: up to 16 Characters
Disabled Deviation ProcessSource Loop
1 √2 √3 √4 √5 √6 √7 √8 √9 √10 √11 √12 √13 √14 √15 √
**** Loop Tagnames imported from sheet 1 above
Loop # Tagname ****Cascade Configuration
Loop #Input Type Selection
Loop 12Loop 13
Loop 10
Loop 14Loop 15
Permissions
Loop Tagnames are limited to 16 characters. The tagnames are exported to the following sheets:
Common Configuration Settings
Loop 9
Loop 1
Loop 3Loop 4
Loop 2
Loop 6Loop 7
Loop 11
Configuration Name:Configured by:
Date Configured:
Loop 8
Tagname ***
Loop 5
Loop 1Loop 2Loop 3Loop 4Loop 5Loop 6
Loop 12Loop 13
Loop 7Loop 8Loop 9Loop 10
Loop 15
"Setup Setpoint Limits""Setup Alarms""Single Loop BarGraph Config""Profile Config-Global Profile""Profile Config-Steps""Profle Config Wait For""Profile Config Step Events"
Loop 11
Loop 14
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 1
OEM Monitor Input Configuration
* Decimal Point: TC/RTD = 0 or 1; analog/loop 2 input 2 = 0-3** Engineering Units: up to 3 characters*** Monitor Tag Name: up to 16 characters
Thermocouple (max of 8)Analog Input (max of 8)RTD Input (max of 6) √Loop #2 Input (max # of loops) √
1 Mon 1 1 0 02 Mon 2 1 0 03 Mon 3 1 0 04 Mon 4 1 0 05 Mon 5 1 0 06 Mon 6 1 0 07 Mon 7 1 0 08 Mon 8 1 0 09 Mon 9 1 0 010 Mon 10 1 0 011 Mon 11 1 0 012 Mon 12 1 0 013 Mon 13 1 0 014 Mon 14 1 0 015 Mon 15 1 0 0
Enter Tagnames for either the 8 or 6-channel input card OR Loop Control Input #2Tagnames are exported to the following sheets:
Number Tagname*** Engr Units**
Decimal Position*
"Offline Setup-Monitor Offset" "Setup Alarms""Profile Config Steps Wait For"
Total # of Inputs
Line Frequency (50 thru 60 HZ)
Max# Number of Input Type
Low Scale High Scale
Analog InputMonitor Inputs Detail Configuration
Input Type Selection
Configuration Name:Configured by:
Date Configured:
Type B
Type JType K
Thermocouple Type
Type TType E
Type N
PT100Ni120
PT1000
RTD Type
Analog Input
Loop Control Input 2
Ni1000-DINNi1000-Landys&Gyr
10-400 ohms10-4000 ohms
Type D
60
Type G-100 to 100mV
Type SType R
0-50mVType C
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 1
OEM Profile Type Configuration
Profile Setup Selected√
* (Degrees/Hr)
Ramp in TimeRamp Rate*
Configuration Name:Configured by:
Date Configured:
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 1
OEM Splash Screen Configuration
The Orion splash screen will shown company information each time the sytsem is started
Company:Address:Phone:
Configuration Name:Configured by:
Date Configured:
Maximum of 26 Characters per line
Default Company Name is Future Design Controls
Enter Company Name, Address & Phone
Enter Company Name, Address (City, State & Zip) & Phone
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 1
OEM Functions-Startup Config
Configuration Name:Configured by:
Date Configured:
Main View Selection Selected
Single Loop View √ √Dual Loop View √All Loops ViewLoop/Monitor TrendsSystem Event ControlAlarm Monitor ViewAlarn History ViewDigital Input MonitorDigital Output Monitor
(only one may be selected)
Note: Confirm the Main View selected is available from the Orion Functions / Menu List
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 2
OEM Functions-Startup Config
Orion Function / Menu Item Runtime Menu Location SelectedSingle Loop View View/Single Loop View √ √Dual Loop View View/Dual Loop View √ √All Loops View View/All Loop Views √Loop/Monitor Trends View/Loop/Monitor Trends √System Event Conrtol View/System Event Control √Alarm Monitor View View/Alarm Monitor View √Alarm History View View/Alarm History View √Digital Input & Output Monitor View/Digital Input & Output Monitor √not used not used √Profile Control Profiles √System Security Security √Data Logging Log/Data Logger √Data Log Viewer Log/DataLogging √USB File Utilities Log/Edit/File Utilities √FTP File Transfer Log/Edit/FTP/WAN Setup √Loop Alarm Settings Setup/Alarm Security √Email/SMTP Setup/Email √System Event Names Setup/Event Tagnames √Web Server/VNC Setup/Web Server/Modbus/VNC √Degrees C/F Offline/Setup/Degrees C/F √Maintenance Items Offline/Setup/Maintenance Items √Monitor Input Offset Offline/I/O/Monitor Input Offset √Analog Input Setup Offline/I/O/Analog Input Setup √Analog Output Setup Offline/I/O/Analog Output Setup √Digital Input Setup Offline/I/O/Digital Input Setup √Digital Output Setup Offline/I/O/Digital Output Setup √Operator Events Log/Edit/Add Operator Events √Digital Signatures Log/Edit/Add Digital Signatures √DI/DO Monitor - Force Offline/I/O/ Montior & Force Digital Output √not used not used √Barcode Setup Setup/Barcode Setup √not used not used √Profile GS Events Profiles/Profile Entry √Profile Wait For Profiles/Profile Entry √Profile GS Soak Limits Profiles/Screens/GS Soak Limits √Profile Auto Start Profiles/Screens/Auto Start Profile √Loops Not Used In Profile Profiles/Screens/Loops Not Used in Profile √Profile Jump Step Profiles/Profile Entry √Profile Jump Count Profiles/Profile Entry √Import / Export Setup Offline/Setup/Export Setup √Exit Application Offline/Setup/Exit Application √
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 2 of 2
OEM Event-DIO Tagnames Config
Configuration Name:Configured by:
Date Configured:
# System Event Names Digital Output Names Digital Input Names0 System Events Start at #1 DIGITAL OUT0 DIG INPUT 01 EVT1 DIG OUT0 DIGITAL OUT1 DIG INPUT 12 EVT2 DIG OUT1 DIGITAL OUT2 DIG INPUT 23 EVT3 DIG OUT2 DIGITAL OUT3 DIG INPUT 34 EVT4 DIG OUT3 DIGITAL OUT4 DIG INPUT 45 EVT5 DIG OUT4 DIGITAL OUT5 DIG INPUT 56 EVT6 DIG OUT5 DIGITAL OUT6 DIG INPUT 67 EVT7 DIG OUT6 DIGITAL OUT7 DIG INPUT 78 EVT8 DIG OUT7 DIGITAL OUT8 DIG INPUT 89 EVT9 DIG OUT8 DIGITAL OUT9 DIG INPUT 910 EVT10 DIG OUT9 DIGITAL OUT10 DIG INPUT 1011 EVT11 DIG OUT10 DIGITAL OUT11 DIG INPUT 1112 EVT12 DIG OUT11 DIGITAL OUT12 DIG INPUT 1213 EVT13 DIG OUT12 DIGITAL OUT13 DIG INPUT 1314 EVT14 DIG OUT13 DIGITAL OUT14 DIG INPUT 1415 EVT15 DIG OUT14 DIGITAL OUT15 DIG INPUT 1516 EVT16 DIG OUT15 DIGITAL OUT1617 EVT17 DIG OUT16 DIGITAL OUT1718 EVT18 DIG OUT17 DIGITAL OUT1819 EVT19 DIG OUT18 DIGITAL OUT1920 EVT20 DIG OUT19 DIGITAL OUT2021 EVT21 DIG OUT20 DIGITAL OUT2122 EVT22 DIG OUT21 DIGITAL OUT2223 EVT23 DIG OUT22 DIGITAL OUT2324 EVT24 DIG OUT23 DIGITAL OUT2425 EVT25 DIG OUT24 DIGITAL OUT2526 EVT26 DIG OUT25 DIGITAL OUT2627 EVT27 DIG OUT26 DIGITAL OUT2728 EVT28 DIG OUT27 DIGITAL OUT2829 EVT29 DIG OUT28 DIGITAL OUT2930 EVT30 DIG OUT29 DIGITAL OUT3031 EVT31 DIG OUT30 DIGITAL OUT3132 EVT32 DIG OUT31 Digital Outputs 0-31 (32 max)
Dig
ital I
nput
s lim
ited
to 0
- 15
(16
max
imum
)
(up to 20 characters for each name)
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 1
OEM System Events Config
Configuration Name:Configured by: √
Date Configured: √
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 311 EVT1 DIG OUT02 EVT2 DIG OUT13 EVT3 DIG OUT24 EVT4 DIG OUT35 EVT5 DIG OUT46 EVT6 DIG OUT57 EVT7 DIG OUT68 EVT8 DIG OUT79 EVT9 DIG OUT8
10 EVT10 DIG OUT911 EVT11 DIG OUT1012 EVT12 DIG OUT1113 EVT13 DIG OUT1214 EVT14 DIG OUT1315 EVT15 DIG OUT1416 EVT16 DIG OUT1517 EVT17 DIG OUT1618 EVT18 DIG OUT1719 EVT19 DIG OUT1820 EVT20 DIG OUT1921 EVT21 DIG OUT2022 EVT22 DIG OUT2123 EVT23 DIG OUT2224 EVT24 DIG OUT2325 EVT25 DIG OUT2426 EVT26 DIG OUT2527 EVT27 DIG OUT2628 EVT28 DIG OUT2729 EVT29 DIG OUT2830 EVT30 DIG OUT2931 EVT31 DIG OUT3032 EVT32 DIG OUT31
Event # System Event Output Configuration - Select Event Outputs per System Event *System Event Name (refer to OEM Event-DIO Tagnames Config)
Events can be assigned to one or more outputs allowing different events to control the same outputs or combination of outputs as required.
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 1
Offline Setup-Monitor Offset
Configuration Name:Configured by:
Date Configured:
Monitor Number Monitor Tagname * + / - Offset
1 Mon 1 02 Mon 2 03 Mon 3 04 Mon 4 05 Mon 5 06 Mon 6 07 Mon 7 08 Mon 8 0
Refer to: * The Monitor Input Tagnames are for reference only.
Monitor Inputs Offset
- Offset for Input #2 of loop controls should be made at the loop control.
OEM Monitor Input Configuration
- T/C and Analog inputs have up to 8-channels- RTD inputs have up to 6-channels
Note Input #2 of Loop Controls:
Note:
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 1
Offline Setup-Analog In Config
√√
012345678910111213
0-10Vdc 4-20mA Input Minimum
Date Configured:
Configuration Name:Configured by:
Loop Setpoint/Input UseLoop
Selection
The Input Use selections, ‘None’ and ‘Remote SP’ enable and disable the analog input.This allows the input configuration to be maintained, but disable its operation until required.
Input Maximum
Input TypeAnalog Input
Number None Remote SP
Input Range
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 1
Offline Setup-Analog Out Config
None SP PV %Out0 √1 √23456
Source Loop
Input/Loop Source for OutputRetransmit Selection
4-20mA Output Minimum
Output Maximum
Configuration Name:Configured by:
The output will retransmit this source linearly from the minimum to maximum range. The minimum and maxaimum values of the output can be set to correspond to a specific value of the retransmitted source.The analog outputs can be configured to retransmit signals either in a 0-10V or 4-20mA range.
Date Configured:
Analog Output Number
Output Type Output Range
0-10Vdc
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 1
Offline Setup-DI Config
√√
Off
to O
n
On
to O
ff
0123456789101112131415
"OEM Config SysEvent-DO-DI Names"
DIG INPUT 4
Dis
able
All
Loop
C
omm
unic
atio
ns
Rem
ote
Ala
rm S
ilenc
e
Adv
ance
Pre
viou
s St
ep
Adv
ance
Nex
t Ste
p
Dig
ital O
utpu
t Con
trol
Dig
ital I
nput
*
Digital Input Tagname
Wai
t for
Eve
nt
Dis
able
Loo
p SP
C
omm
unic
atio
ns
Term
inat
e Pr
ofile
Ala
rm In
put *
*
Star
t Pro
file
Paus
e Pr
ofile
Configuration Name:Configured By:
Date Configured:
DIG INPUT 15
DIG INPUT 9
Dig
ital O
utpu
t Def
eat *
*
Star
t Dat
a Lo
ggin
g
DIG INPUT 11
DIG INPUT 13
DIG INPUT 1
DIG INPUT 3
DIG INPUT 5
DIG INPUT 7
** Reference 'Offline Setup-DI Output Defeat' for output defeat selections.
DIG INPUT 0
DIG INPUT 2
Res
ume
Prof
ileTran
sitio
n
DIG INPUT 6
DIG INPUT 8
DIG INPUT 10
DIG INPUT 12
DIG INPUT 14
* Digital Input Voltage Specifications: (Refer to Manual for details)Digital Input Tagnames are imported from sheet
- Digital Inptuts 8-15 (optional) are either 24VDC sink/source or 120VAC- Digital Inputs 0-7 (standard) are 24VDC sink/source input signal
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 1
Offline Setup-DI Output Defeat
√√
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 310123456789101112131415
DIG INPUT 2DIG INPUT 3DIG INPUT 4
Configuration Name:Configured by:
Date Configured:
Digital Input *
Output Defeat SelectionsDigital Input Tagname *
DIG INPUT 0
DIG INPUT 15
DIG INPUT 11DIG INPUT 12DIG INPUT 13DIG INPUT 14
DIG INPUT 9DIG INPUT 10
DIG INPUT 1
DIG INPUT 5DIG INPUT 6DIG INPUT 7DIG INPUT 8
* Digital Input Voltage Specifications: (Refer to Manual for details)- Digital Inputs 0-7 (standard) are 24VDC sink/source input signal
Digital Input & Referenced Output Tagnames are imported from sheet"OEM Config SysEvent-DO-DI Names"
- Digital Inptuts 8-15 (optional) are either 24VDC sink/source or 120VAC
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 1
Offline Setup-DO Config
Configuration Name:Configured By: √
Date Configured: √
0 DIGITAL OUT01 DIGITAL OUT12 DIGITAL OUT23 DIGITAL OUT34 DIGITAL OUT45 DIGITAL OUT56 DIGITAL OUT67 DIGITAL OUT78 DIGITAL OUT89 DIGITAL OUT910 DIGITAL OUT1011 DIGITAL OUT1112 DIGITAL OUT1213 DIGITAL OUT1314 DIGITAL OUT1415 DIGITAL OUT1516 DIGITAL OUT1617 DIGITAL OUT1718 DIGITAL OUT1819 DIGITAL OUT1920 DIGITAL OUT2021 DIGITAL OUT2122 DIGITAL OUT2223 DIGITAL OUT2324 DIGITAL OUT2425 DIGITAL OUT2526 DIGITAL OUT2627 DIGITAL OUT2728 DIGITAL OUT2829 DIGITAL OUT2930 DIGITAL OUT3031 DIGITAL OUT31
* Digital Output Voltage Specifications: (Refer to Manual for details)
Prof
ile R
unni
ng
Prof
ile H
old
Rem
ote
Ala
rm (N
C)
Prof
ile S
tep
Cha
nge
Digital Output Tagname
Dig
ital O
utpu
t *
Output Delay Settings ** Output Function Selection
Dig
ital I
nput
Con
trol
** Digital Output Delay Settings: settings in seconds except for cycle time (X.X seconds)
Digital Output Tagnames are imported from sheet OEM Event-DIO Tagnames Config
- Digital Outputs 0-1 (standard) are transistor source output (24Vdc - 0.3 amp)- Digital Ouptuts 2-7 (standard) are relay rated 240VAC 2 amp (resistive)- Digital Ouptuts 8-31 (optional) are relay or transistor. Outputs are specified as 8 or 16 point cards with each.
Dig
ital I
nput
Num
ber
Sele
cted
for C
ontr
ol
Syst
em R
ingB
ack
(Ala
rm F
unct
ions
Onl
y)
On
Del
ay
Off
Del
ay
Cyc
le T
ime
Syst
em/A
udib
le A
larm
Proc
ess
Ala
rm
Dig
ital I
nput
Ala
rm
Syst
em E
vent
Out
put
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 1
Offline Setup - Degrees C-F
oooF √oooC √
NOTE:
The temperature units selection only effects control loops and monitor inputs configured as temperature, i.e., controllers or monitor input cards with a temperature input device such as a thermocouple or RTD. The units display for loop controls and monitor input cards configured with linear inputs (mA or Vdc) will not be effected by this selection.
Date Configured:
Select F or C
When changing display units, profile set points will not be converted between units. Separate profiles are required for each temperature range. Operating the Orion-M with profiles that have been written using alternate units, could cause property damage or personal injury.
Configuration Name:Configured by:
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 1
Offline Setup-Maint Items
DO #
01234567890111213141516171819202122232425262728293031
On Off√
OEM Event-DIO Tagnames Config
DIGITAL OUT31
DIGITAL OUT27DIGITAL OUT28DIGITAL OUT29DIGITAL OUT30
DIGITAL OUT23DIGITAL OUT24DIGITAL OUT25DIGITAL OUT26
DIGITAL OUT19DIGITAL OUT20DIGITAL OUT21DIGITAL OUT22
DIGITAL OUT15DIGITAL OUT16DIGITAL OUT17DIGITAL OUT18
DIGITAL OUT11DIGITAL OUT12DIGITAL OUT13DIGITAL OUT14
DIGITAL OUT7DIGITAL OUT8DIGITAL OUT9DIGITAL OUT10
DIGITAL OUT3DIGITAL OUT4DIGITAL OUT5DIGITAL OUT6
DIGITAL OUT0DIGITAL OUT1DIGITAL OUT2
Configuration Name:
Digital Output Names Cycle Count Setpoint
Configured by:Date Configured:
Maintenance Item Counter Setpoint Configuration
Run Hours Setpoint
Maintenance Alarms
Output names are imported from sheet
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 1
Offline Setup-Set Time & Date
Set Date \ Time
Year Day Month
Hour Minute Seconds
Year Day MonthStart
Year Day MonthEnd
√ √√
Daylight Savings is Enabled
Daylight Savings Settings
NTS Sever (National Time Server)tick.usno.nave.mil
time-b.nist.gov
Time Options
Configuration Name:Configured by:
Date Configured:
DOW (Sun-Sat = 0 - 6)
The daylight savings time options allow the user to set the start date and end date for daylight savings time.
nist1.dc.certifiedtime.com
The date and time can be adjusted by selecting ‘Set Date\Time’ from the offline Setup menu.The current date and time will be displayed in the field entry windows under the ‘set time’ tab.
time-a.nist.gov
The ‘Time Options’ tab is used to configure the National Time Server & Time Zone clock settings.
nist1.nyc.certifiedtime.comnist1.sjc.certifiedtime.com
time-a.timefreq.bldrdoc.govtime-b.timefreq.bldrdoc.govtime-c.timefreq.bldrdoc.govutcnist.colorado.edutime.nist.govtime-nw.nist.govnist1.datum.com
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 2
Offline Setup-Set Time & Date
Pakistan Standard TimeMauritius Standard Time
Korea Standard Time
E. Australia Standard Time
Vladivostok Standard TimeWest Pacific Standard Time
ASU Central Standard TimeCen. Austalia Standard Time
Ekaterinburg Standard Time
Middle East Standard TimeNamibia Standard TimeGeorgian Standard TimeAzerbaijan Standard Time
Pacific Standard Time (Mexico)
Caucasus Standard Time
Tasmania Standard Time
North Asia Standard Time
India Standard TimeNepal Standard TimeCentral Asia Standard Time
West Asia Standard Time
Taipei Standard Time
Sri Lanka Standard TimeMyanmar Standard TimeSE Asia Standard Time
new Zealand Standard Time
W. Australia Standard TimeNorth Asia East Standard Time
Central Pacific Standard TimeFiji Standard Time
AUS Eastern Standard Time
China Standard Time
Tokyo Standard TimeYakutsk Standard Time
Argentina Standard TimeW. Europe Standard TimeW. Central Africa Standard Time
Mid-Atlantic Standard Time
Central European Standard Time
Cape Verde Standard TimeGMT Standard Time
Tonga Standard Time
Greenland Standard Time
Montevideo Standard TimeVenezuela Standard TimeCentral Brazilian Standard TimeMorocco Standard TimeJordan Standard Time
E. Africa Standard TimeArabic Standard TimeIran Standard TimeArabian Standard Time
South Africa Standard TimeRussian Standard TimeArab Standard Time
Egypt Standard TimeFLE Standard TimeGTB Standard TimeJerusalem Standard Time
Romance Standard Time
E. Euope Standard Time
Alaskan Standard Time
Samoa Standard TimeHawaiian Standard Time
Dateline Standard Time
Time OptionsThe ‘Time Options’ tab is used to configure the National Time Server & Time Zone clock settings.
Afghanistan Standard Time
Azores Standard Time
Pacific Standard TimeMountain Standard Time
Eastern Standard TimeUS Eastern Standard Time
Central Standard Time (Mexico)Central America Standard Time
SA Pacific Standard TimeAtlantic Standard Time
Pacific SA Standard TimeNewfoundland Standard TimeE. South America Standard TimeSA Eastern Standard Time
Mountain Standard Time (Mexico)
SA Western Standard Time
US Mountain Standard TimeCentral Standard TimeCanada Central Standard Time
Time Zone Selection - select one (USA contiguous 48 states time zones in BOLD) (choices are embedded within standard Windows CE OS & uses Microsoft standards)
Greenwich Standard TtimeCentral Europe Standard Time
Malay Peninsular Standard Time
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 2 of 2
Offline Setup-Help Voice Asst
English √ √Espanol √Francais
OnOff √
Select the desired language for text help & voice assisted Help
Language
Voice Assistance
Configuration Name:Configured by:
Date Configured:
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 1
Setup Email
Configuration Name:Configured by:
Date Configured:
Login NameReturn Address
PasswordSMTP ServerEmail Subject
Email Address # (1 - 30) 1
NameEmail AddressSMS Address
√Email Alarms √
SMS Alarms
Email Address # (1 - 30) 2
NameEmail AddressSMS Address
√Email Alarms √
SMS Alarms
Email Address # (1 - 30) 3
NameEmail AddressSMS Address
√Email Alarms √
SMS Alarms
Confirgure Email and/or SMS on Alarm
maximum characters = 50
Create New Email Address (30 addresses maximum)
maximum characters = 50
Confirgure Email and/or SMS on Alarm
Create New Email Address (30 addresses maximum)
Email Settings
maximum characters = 50
Create New Email Address (30 addresses maximum)
Confirgure Email and/or SMS on Alarm
maximum characters = 50
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 1
Setup Profile Power Recovery
Profile Recovery
configure from 0 to 32,760 seconds
Off √Hold √
ContinueRestart
Resume
Recovery State on Power up when Power Out Time is Exceeded
Power Out Time (seconds)
Configuration Name:Configured by:
Date Configured:
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 1
Setup Setpoint Limits
Loop Number
OEM Set Lower
Setpoint Limit
OEM Set Upper
Setpoint Limit
User Set Lower
Setpoint Limit
User Set Upper
Setpoint Limit
1 0 02 0 03 0 04 0 05 0 06 0 07 0 08 0 09 0 0
10 0 011 0 012 0 013 0 014 0 015 0 0
The OEM Set Lower & Upper settings are imported from "OEM Loop Configuration" sheet. Enter appropriate User Set Lower & Upper setpoint limits within the OEM range. This excel file will allow User settings outside the OEM settings; Orion-M firmware will not allow User settings outside the OEM settings.
Configuration Name:Configured by:
Date Configured:
Loop 7Loop 8Loop 9
Loop Tagname
Loop 3Loop 4Loop 5Loop 6
Loop 1Loop 2
Loop 10
Loop Tagnames and OEM set Lower & Upper Setpoint limits are imported from sheet:"OEM Loop configuration"
Loop 15
Loop 11Loop 12Loop 13Loop 14
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 1
Setup Event Tagnames
1234567891011121314151617181920212223242526272829303132
OEM Assigned Event Names User Assigned Event Names
EVT31 DIG OUT30EVT32 DIG OUT31
EVT28 DIG OUT27EVT29 DIG OUT28EVT30 DIG OUT29
EVT21 DIG OUT20EVT22 DIG OUT21
EVT15 DIG OUT14
System Event Names
Note: System Event Tagnames 20 Characters Maximum; space provided below is 20+ characters
Event #
EVT27 DIG OUT26
EVT23 DIG OUT22EVT24 DIG OUT23EVT25 DIG OUT24EVT26 DIG OUT25
EVT19 DIG OUT18EVT20 DIG OUT19
EVT17 DIG OUT16EVT18 DIG OUT17
EVT11 DIG OUT10EVT12 DIG OUT11EVT13 DIG OUT12EVT14 DIG OUT13
EVT8 DIG OUT7EVT9 DIG OUT8EVT10 DIG OUT9
EVT16 DIG OUT15
EVT4 DIG OUT3EVT5 DIG OUT4EVT6 DIG OUT5EVT7 DIG OUT6
EVT1 DIG OUT0EVT2 DIG OUT1EVT3 DIG OUT2
Configuration Name:Configured by:
Date Configured:
EVT1 DIG OUT0EVT2 DIG OUT1EVT3 DIG OUT2EVT4 DIG OUT3EVT5 DIG OUT4EVT6 DIG OUT5EVT7 DIG OUT6EVT8 DIG OUT7
EVT15 DIG OUT14EVT16 DIG OUT15
EVT9 DIG OUT8EVT10 DIG OUT9EVT11 DIG OUT10EVT12 DIG OUT11
EVT32 DIG OUT31
EVT25 DIG OUT24EVT26 DIG OUT25EVT27 DIG OUT26EVT28 DIG OUT27
EVT30 DIG OUT29
EVT22 DIG OUT21EVT23 DIG OUT22EVT24 DIG OUT23
EVT31 DIG OUT30
EVT29 DIG OUT28
EVT17 DIG OUT16EVT18 DIG OUT17EVT19 DIG OUT18EVT20 DIG OUT19
EVT13 DIG OUT12EVT14 DIG OUT13
EVT21 DIG OUT20
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 1
Setup Alarms
Configuration Name:Configured by: √
Date Configured: √
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
Ala
rm #
Inhibit On or
Off
On
Output Assignment"None" or
Output #0-31O
ff
Self Clear or Latching
Output Close or
Open
Ope
n
Clo
se
Latc
h
Silent On or
Off
On
Off
Hig
h
Low
Bot
h
Self
Cle
ar
Hig
hLoop
or
Mon
itor #
Alarm Tagname/Message *
* Alarm Tagname / Message may be up to 24 characters
Alarm TypeProcess Alarm
Bot
h
Low
Bot
h
Bot
h
Deviation Alarm
Hig
h
Low
ROC Alarm
Hig
h
Low
%Out Alarm
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 2
Setup Alarms
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
Alarm Inhibit Delay (seconds)Deadband On Delay
(seconds)
High Alarm
Setpoint
Low Alarm SetpointA
larm
#
Loop
or
Mon
itor #
Alarm Tagname / Message **
Alarm Setpoionts, Deadband & On Delay Duration
** Alarm Tagname / Message directly below auto inserted from page 1Alarm Delay & Alarm Inhibit Delay Duration is 0 - 32,760 seconds
See
"Set
up A
larm
s-O
utpu
t Def
eats
" w
orks
heet
.
Alarm Output Defeat
Select Outputs
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 2 of 2
Setup Alarms-Output Defeats
Configuration Name:Configured by: √
Date Configured: √
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 311 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
* Alarm Tagname / Message Auto inserted from "Setup Alarms" worksheet.
Alarm Tagname/Message *
Ala
rm #
Alarm Output Defeat Selections
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 1
Setup Webserver-VNC-Modbus
1
none
On Off√ √√ √
* The name entered here will be used on the VNC header window on a PC, so that if multiple VNC clients are open to different systems, each one can be identified.
Web & VNC Server Web VNC
VNC Password (up to 28 characters)
VNC Device Name * (up to 35 characters)
Date Configured:
VNC Address (0 to 255)VNC Password (none or pwd)
Modbus Slave Address (1 to 31)
Configuration Name:Configured by:
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 1
Security Configuration
Configuration Name:Configured by:
Date Configured:
Security Options ConfigurationNumber of Days before
Password renewal is required(1 - 365)
1
Re-authenticate User duringProcess Changes
Enable\Disable Audit Trail √Enable\Disable Security √
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 3
Security Configuration
User Rights Configuration √√
User Rights Sys Oper Super AdminTrend Setup √ √ √ √Email Settings √ √ √ √Change Setpoints √ √ √ √Open Files √ √ √ √Save Files √ √ √ √Delete Files √ √ √ √Edit Profile √ √ √ √Edit Barcode Setup √ √ √ √Adjust Setpoint Limits √ √ √ √Adjust Alarms √ √ √ √System Event Control √ √ √ √Touch Calibration √ √ √ √Silence Alarms √ √ √ √Clear Alarms √ √ √ √Data Logging & Settings √ √ √ √Start/Stop/Hold Profiles √ √ √ √Power Recovery √ √ √ √Access Security √ √ √ √Exit Application √ √ √ √Edit Event Names √ √ √ √Edit Bar Graphs √ √ √ √Set/Clear Maints Counters √ √ √ √File Utilities √ √ √ √Offline Mode √ √ √ √Change Units √ √ √ √Maints Setup √ √ √ √Set Date/Time √ √ √ √Not used √ √ √ √Monitor Points Offset √ √ √ √Analog Outputs √ √ √ √Web/Modbus/VNC Settings √ √ √ √FTP Settings √ √ √ √NTS Clock Settings √ √ √ √DST Settings √ √ √ √Config Analog Inputs √ √ √ √Config Digital Inputs √ √ √ √Config Digital Outputs √ √ √ √Help/Voice Assist √ √ √ √Import/Export Setup √ √ √ √Auto-Man Enable/Disable √ √ √ √Auto Tune Enable/Disable √ √ √ √Offline DO Force √ √ √ √User Composed Email √ √ √ √Add Operator Events √ √ √ √Add Digital Signatures √ √ √ √Verify Digital Signatures √ √ √ √
View/Single Loop, Dual & All loop ViewsOpen Alarm, Profile, Audit Trail & Historical files
Menu LocationView/Loop Monitor TrendsSetup/Email/Email Settings
Applicable to Profile "save" & "save as"
Profiles/Edit Profile
Setup/Setpoint Limits
View/System Event ControlSetup/Alarm Settings
Setup/Barcode Reader Setup
View/Alarm Monitor View; Silence button
Log/ (applies to all Data Logging functions)View/Alarm Monitor View; Clear button
Setup/Offline/Calibrate Touch Screen
Profiles/Run, Hold, Stop actions
Log/Edit/File UtilitiesSetup/Offline
Setup/Profile Recovery
Setup/Offline/Exit Application
View/Single Loop ViewSetup/Offline/Maintenance Items
Setup/Event Tagnames
Security/Setup
Setup/Web Server-Modbus-VNC
Setup/Offline/Degrees C\FSetup/Offline/Maintenance Items SetupSetup/Offline/Set Date\Timenot usedSetup/Offline/I-O/Input OffsetsSetup/Offline/I-O/Analog Output Setup
Log/Edit/Add Digital SignatureLog/Edit/Verify Digital Signatures
Applicacable to Profile & Historical Data files
Single Loop ViewSingle Loop ViewSetup/Offline/Force System OutputsSetup/Email/New Email Message
Setup/Offline/I-O/Digital Input SetupSetup/Offline/I-O/Digital Output Setup
Log/Edit/Add Operator Events
Single Loop View
Log/Edit/FTP\WAN SetupSetup/Offline: Set Date/TimeSetup/Offline: Set Date/TimeSetup/Offline/I-O/Analog Input Setup
Setup/Offline/Help-Voice Setup
User Groups
Note: Refer to Manual for detail on each User Right
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 2 of 3
Security Configuration
Users List√
User Number (1 to 30): 1
User Group Configuration System Operator Supervisor AdministratorSelect User Group
User ID *Full Name *Password *
Password Aging
User Number (1 to 30): 2
User Group Configuration System Operator Supervisor AdministratorSelect User Group
User ID *Full Name *Password *
Password Aging
User Number (1 to 30): 3
User Group Configuration System Operator Supervisor AdministratorSelect User Group
User ID *Full Name *Password *
Password Aging
User Number (1 to 30): 4
User Group Configuration System Operator Supervisor AdministratorSelect User Group
User ID *Full Name *Password *
Password Aging select for password aging* Minimum of 4 characters & maximum of 10
Note: Printing is set to first 4 user entries. Adjust settings as necessary.
Add Users Configuration (up to 30 users maximum)
select for password aging
select for password aging* Minimum of 4 characters & maximum of 10
* Minimum of 4 characters & maximum of 10
Add Users Configuration (up to 30 users maximum)
* Minimum of 4 characters & maximum of 10 select for password aging
Add Users Configuration (up to 30 users maximum)
Add Users Configuration (up to 30 users maximum)
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 3 of 3
Single Loop BarGraph Config
Low High1 0 1002 0 1003 0 1004 0 1005 0 1006 0 1007 0 1008 0 1009 0 100
10 0 10011 0 10012 0 10013 0 10014 0 10015 0 100
Configuration Name:Configured by:
Date Configured:
Scale Value
Loop 7Loop 8
Loop 1
Loop 15
Loop 11Loop 12Loop 13Loop 14
Loop 2Loop 3
Loop Tagnames are imported from sheet "OEM Loop Configuration""OEM Loop Configuration"
Single Loop Display - configure Bar Graph Low & High values for Setpoint & Process Value
Loop 9Loop 10
Loop Number Loop Tagname *
Loop 4Loop 5Loop 6
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 1
Loop-Monitor Trends Setup
√√
Zero Span Mins PV SP %Out1 0 100 60 √ √ √2 0 100 60 √ √ √3 0 100 60 √ √ √4 0 100 60 √ √ √5 0 100 60 √ √ √6 0 100 60 √ √ √7 0 100 60 √ √ √8 0 100 60 √ √ √9 0 100 60 √ √ √
10 0 100 60 √ √ √11 0 100 60 √ √ √12 0 100 60 √ √ √13 0 100 60 √ √ √14 0 100 60 √ √ √15 0 100 60 √ √ √
Zero Span Mins PV1 0 100 60 √2 0 100 60 √3 0 100 60 √4 0 100 60 √5 0 100 60 √6 0 100 60 √7 0 100 60 √8 0 100 60 √9 0 100 60 √
10 0 100 60 √11 0 100 60 √12 0 100 60 √13 0 100 60 √14 0 100 60 √15 0 100 60 √
"OEM Loop Configuration"Loop / Monitor Tagnames are imported from sheets:
"OEM Monitor Input Configuration"
Monitor # Monitor Tagname Trend Settings
Mon 3Mon 4Mon 5Mon 6
Plot Selections
Plot Selections
Mon 1Mon 2
Loop 1
Loop 15
Loop 11Loop 12Loop 13Loop 14
Mon 7Mon 8Mon 9Mon 10Mon 11Mon 12Mon 13Mon 14Mon 15
Loop 9Loop 10
Loop # Loop Tagname
Loop 4Loop 5Loop 6Loop 7Loop 8
Loop 2Loop 3
Configuration Name:Configured by:
Date Configured:
Trend Settings
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 1
Profile Config-Global Profile
0 Loop Tagnames are imported from sheet:
1 √2 √3 4 5 6 Month Day of Week*7 Day Hour8 Year Minute9
10 11 12 13 14 15
Auto Start by DateAuto Start by Time
* Day of Week: Sun-Sat = 0 to 6
Profile Start Date / Time Entry
"OEM Loop Configuration"
- Each Profile has Global Settings as shown on this page.
Guaranteed Soak (dwell), Ramp Limits (GS) and Loops NOT Profiling
Configured by:
Auto Start Off
Number of Steps (maximum of 99)
Loops NOT Profiling
Date Configured:
Loop Tagname
Configuration Name:
- Profile Config-Global Profile- Each Profile has four pages to document configuration;
Loop 3
Loop 1
Profile Name
Loop Number Profile Auto Start Logic
GS Setpoint *
Loop 2
Loop 9
Loop 10
Loop 15
Loop 4Loop 5Loop 6Loop 7
* GS Setpoint is value above or below that the Step Timer will stop
- Profile Config-Steps- Profile Config Steps Wait For- Profile Config Step Events
Loop 11Loop 12Loop 13Loop 14
(16 characters maximum)
Loop 8
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 1
Profile Config-Steps
- Profile Config-Global Profile- Profile Config-Steps- Profile Config Steps Wait For- Profile Config Step Events
√ hours 0√ minutes 0
seconds 0
1 2 3 4 5 6 7 8 9
10
11
12
13
14 15
- Jump Count sets the # of jumps that will be made from the step; with 10 cycles within a profile - set jump count = 9, 10 minus the 1 preformed prior to first jump. Once all jumps are complete, the profile will continue to the next step. Jumps are disabled on the step when the Jump Count is zero regardless of the Jump Step number (it is ignored).
- Each Profile has four pages:
Loop Tagnames are imported from sheet:
Note 1: Step Events, GS Active, Step Jump To and the Wait For menu functions may not be avaialable based upon OEM Configuration.
Note 2: Number of Loop Controls and Digital Inputs available is dependent upon OEM Configuration; maxium of 15 loop controls dependent upon configuration.
See
Step
Eve
nt S
elec
tion
Tabl
e
Loop 2Loop 3Loop 4Loop 5Loop 6Loop 7Loop 8Loop 9
0Jump Step
Loop 13Loop 14Loop 15
Jump Count1
Profile Name
Configuration Name:Configured by:
Date Configured:
- Jump Step sets the step # that the profile will jump to upon completetion fo the step.
GS
Act
ive
Loop
Num
ber
Loop Tagname
Loop 10
See
Jum
p St
eps
Sele
ctio
n B
elow
Loop 12
Loop 1
"OEM Loop Configuration"
Loop 11
Step Time
Loop
s N
OT
Prof
iling
(r
efer
ece-
Glo
bal S
et)
Targ
et S
etpo
int
Jum
p St
eps
Step
Eve
nts
Step Number
1Total # of Steps
0
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 1
Profile Config Steps Wait For
- Profile Config-Global Profile
1 1 02 2 13 3 24 4 35 5 46 6 57 7 68 8 79 9 810 10 911 11 1012 12 1113 13 1214 14 1315 15 14
√ √ 15
Loop/Monitor PV RisingOEM Event-DIO Tagnames Config
- Each Profile has four pages;
OEM Loop ConfigurationOEM Monitor Input Configuration
Digital Input Tagname
DIG INPUT 1DIG INPUT 0
DIG INPUT 12
Dig
ital I
nput
W
ait F
or
DIG INPUT 13
DIG INPUT 4Mon 4Mon 5
Tagnames imported from:
- Profile Config-Steps- Profile Config Steps Wait For- Profile Config Step Events
Monitor Tagname
Mon 1Mon 2Mon 3
Loop 4Loop 5Loop 6Loop 7
Mon 6
Mon 12
Mon 7
Loop 10Loop 11Loop 12
Mon 8Loop 8Loop 9
Loop 2
Configuration Name:Configured by:
Date Configured:
Loop 3
Digital Input #
Mon
tiors
to
Wai
t For
Step Timer "Wait For" - Loop/Monitor Points
Loo
ps to
W
ait F
or
Loop
s U
nder
D
elta
Con
trol
Mon
titor
N
umbe
r
Loop # Loop Tagname
Loop 1
Step Number1
Profile NameTotal # of Steps
0
Loop & Monitor Setpoint
Mon 15
Mon 9Mon 10Mon 11
Loop 13Loop 14Loop 15
DIG INPUT 5DIG INPUT 6
DIG INPUT 2DIG INPUT 3
Delta SetpointDelta Setpoint
DIG INPUT 9DIG INPUT 10DIG INPUT 11
Loop & Monitor Wait For Setpoint
DIG INPUT 14
Wait Type (select one) (applies to Loop & Monitor Setpoint)
Mon 13Mon 14
DIG INPUT 15
Auto (Edge Detect
DIG INPUT 7DIG INPUT 8
Loop/Monitor PV Falling
Orion-M_Configuration_and_Setup_Worksheet_v1.0_04-29-10 1 of 1
Profile Config Step Events
Configuration Name: - Each Profile has four pages; Configured by: - Profile Config-Global Profile
Date Configured: - Profile Config-Steps- Profile Config Steps Wait For- Profile Config Step Events
1 2 3 4 5 6 7 8 91234567891011121314151617181920212223242526272829303132
Notes:√√
Step Step Step Step StepSystem Event Names
Profile Name
Event #
EVT2 DIG OUT1EVT3 DIG OUT2EVT4 DIG OUT3
EVT1 DIG OUT0
EVT5 DIG OUT4EVT6 DIG OUT5EVT7 DIG OUT6EVT8 DIG OUT7EVT9 DIG OUT8EVT10 DIG OUT9EVT11 DIG OUT10EVT12 DIG OUT11EVT13 DIG OUT12EVT14 DIG OUT13EVT15 DIG OUT14EVT16 DIG OUT15EVT17 DIG OUT16EVT18 DIG OUT17EVT19 DIG OUT18EVT20 DIG OUT19EVT21 DIG OUT20EVT22 DIG OUT21EVT23 DIG OUT22EVT24 DIG OUT23
EVT30 DIG OUT29EVT31 DIG OUT30EVT32 DIG OUT31
EVT25 DIG OUT24EVT26 DIG OUT25EVT27 DIG OUT26EVT28 DIG OUT27
OEM Number of Loops-Monitors- System Event names imported from sheet:OEM Event-DIO Tagnames Config
This sheet contains spaces for event selections for up to 9 steps (default 1 - 9). Additional steps 10-99 are shown below in groups of 9. Printing is defaulted to Steps 1-9.
Step Step
- The number of System Events is dependent upon OEM Configuration (maximum of 32); see sheet:
Step Step
EVT29 DIG OUT28
Return to Top of Sheet