Over head transmission line fault detection system

Embed Size (px)

Citation preview

Prashant Das Tauruspowertronics Pvt. Ltd

[email protected] www.tauruspowertronics.com

CIGRE INDIA

1

Transmission lines

Prashant Das Tauruspowertronics Pvt. Ltd

[email protected] www.tauruspowertronics.com 2

• Transmission lines constitute more than 60% of asset of power transmission.

• They traverse an incredible range of kilometer in harsh environments, climates and terrains.

• In India many of the Transmission lines currently in service were built in the 1960s and 70s and are subject to many problems including ageing.

• With growing demands, there is huge expectations from transmission companies to keep the transmission line uptime near to 100%.

• Hence accurate fault location, health check / monitoring the same is very much essential.

Type of common faults in overhead Transmission lines

Prashant Das Tauruspowertronics Pvt. Ltd

[email protected] www.tauruspowertronics.com 3

All Types of Open & Short Category faults

Overhead Transmissionline fault locator & Analyzer

Prashant Das Tauruspowertronics Pvt. Ltd

[email protected] www.tauruspowertronics.com 4

• Pre-Commissioning Check of EHV Lines –Continuity, Phase Sequence, line length verification.

• Ascertaining line healthiness before re-Charging.

• For Preventive & Predictive Maintenance of existing EHV Lines.

• Restore the EHV lines ASAP to maintain UP TIME.

Fault Locator and types of fault locator

Prashant Das Tauruspowertronics Pvt. Ltd

[email protected] www.tauruspowertronics.com

OVER HEADTRANSMISSIONLINE FAULT LOCATOR (OHFL)

• Online• Offline

5

OHFLBasic Principals of working

Prashant Das Tauruspowertronics Pvt. Ltd

[email protected] www.tauruspowertronics.com 6

• ONLINE-Systems works on the principal of powersystem Parameters & Data is taken during stressedbreakdown condition and this data is in percentageaccuracy depending on the residual impedance ofthe line.

• OFFLINE-Systems works on the principal of Multiplepulse Eco Co-relation technique & doesn't requireany input parameters for accurate fault finding.

Online method some of it’s limitations

Prashant Das Tauruspowertronics Pvt. Ltd

[email protected] www.tauruspowertronics.com 7

• Each Line require one dedicated equipment.

• It is not helpful for spur lines.• Open Circuit faults can’t locate through

online systems.• Fault locating accuracy may vary in

percentage. (+/_ 10% or more)• Pre-Commissioning tests are not possible.

Offline method

Prashant Das Tauruspowertronics Pvt. Ltd

[email protected] www.tauruspowertronics.com 8

• Advanced high frequency multiple pulseco-relation technique

• How it works:- High frequency Coded pulse sent in to

the powerline- picks up different types of disturbance

and location- Information Decoded- Generates User Friendly Report and gives

complete vision of the line end to end

Offline methods and it’s advantages

Prashant Das Tauruspowertronics Pvt. Ltd

[email protected] www.tauruspowertronics.com 9

• It’ is accurate up to +/- 100Mtr.• One equipment is enough for whole sub station.• It can be used for Spur line fault locating.• Pre –Commissioning tests are possible.• Offline system can identify the secondary faults

before re charging the line.• It can find out Open Circuit faults.• Does not require any complimentary system at other

end of the sub station.• It can Locate faults up to 2500KM.

Offline OHFL Diagnostic outputs

Prashant Das Tauruspowertronics Pvt. Ltd

[email protected] www.tauruspowertronics.com 10

• Fault Locator(Breakdown): For finding the faults at accurate distance.

• Line Signature Analysis: for understanding the healthiness of the line.

Overhead transmission

line fault locator benefits

Prashant Das Tauruspowertronics Pvt. Ltd

[email protected] www.tauruspowertronics.com 11

• Apart from finding dead faults , useful for predictive and preventive maintenance-

i) It can detect developing faults .ii) It can detect nature of the fault(Open/Short)iii) It can indicate severity of the fault (Level of the

Faults).

• Less time to find faults and its location. • Healthiness check up for the entire line .

Case Studies

Prashant Das Tauruspowertronics Pvt. Ltd

[email protected] www.tauruspowertronics.com 12

• Short circuit Fault• De-capping• All jumpers not through in Quad line• Leaky Insulators• Clearance related problems• High frequency effects on transmission lines

CASE STUDIES

Short circuit FaultDe-cappingAll jumpers not through in Quad lineLeaky InsulatorsClearance related problemsHigh frequency effects on transmission lines

Prashant Das Tauruspowertronics Pvt. Ltd

[email protected] www.tauruspowertronics.com 13

SHORT CIRCUIT FAULT at 112 KM

CASE STUDIES

Short circuit FaultDe-cappingAll jumpers not through in Quad lineLeaky InsulatorsClearance related problemsHigh frequency effects on transmission linesPrashant Das Tauruspowertronics Pvt. Ltd

[email protected] www.tauruspowertronics.com 14

Decapping Fault at 69 Km in B Phase

Decapping

Fault

CASE STUDIES

Short circuit FaultDe-cappingAll jumpers not through in Quad lineLeaky InsulatorsClearance related problemsHigh frequency effects on transmission linesPrashant Das Tauruspowertronics Pvt. Ltd

[email protected] www.tauruspowertronics.com 15

ALL JUMPERS NOT THROUGH AT 55 KM

CASE STUDIES

Short circuit FaultDe-cappingAll jumpers not through in Quad lineLeaky InsulatorsClearance related problemsHigh frequency effects on transmission linesPrashant Das Tauruspowertronics Pvt. Ltd

[email protected] www.tauruspowertronics.com 16

Corona due to loose jumper

CASE STUDIES

Short circuit FaultDe-cappingAll jumpers not through in Quad lineLeaky InsulatorsClearance related problemsHigh frequency effects on transmission linesPrashant Das Tauruspowertronics Pvt. Ltd

[email protected] www.tauruspowertronics.com 17

SIGNATURE AFTER THROUGH JUMPER

CASE STUDIES

Short circuit FaultDe-cappingAll jumpers not through in Quad lineLeaky InsulatorsClearance related problemsHigh frequency effects on transmission linesPrashant Das Tauruspowertronics Pvt. Ltd

[email protected] www.tauruspowertronics.com 18

Flashover insulator at 5.8 and 5.3 KM

CASE STUDIES

Short circuit FaultDe-cappingAll jumpers not through in Quad lineLeaky InsulatorsClearance related problemsHigh frequency effects on transmission linesPrashant Das Tauruspowertronics Pvt. Ltd

[email protected] www.tauruspowertronics.com 19

CASE STUDIES

Short circuit FaultDe-cappingAll jumpers not through in Quad lineLeaky InsulatorsClearance related problemsHigh frequency effects on transmission linesPrashant Das Tauruspowertronics Pvt. Ltd

[email protected] www.tauruspowertronics.com 20

Trees very close to Transmission Line in B-phase

CASE STUDIES

Short circuit FaultDe-cappingAll jumpers not through in Quad lineLeaky InsulatorsClearance related problemsHigh frequency effects on transmission linesPrashant Das Tauruspowertronics Pvt. Ltd

[email protected] www.tauruspowertronics.com 21

After Removal of trees

CASE STUDIES

Short circuit FaultDe-cappingAll jumpers not through in Quad lineLeaky InsulatorsClearance related problemsHigh frequency effects on transmission linesPrashant Das Tauruspowertronics Pvt. Ltd

[email protected] www.tauruspowertronics.com 22

• Line Signature Analyser could identify the stress of the linecaused by high frequency noise flowing on the surface ofinsulators and flashover.

• Line Signature Analyser printout with and without filtersreveal the presence of several kV’s of high frequency noiseand really a cause for flash over of insulators

• The noise was later found due to parallel HVDC lines andthyristor switching action

CASE STUDIES

Short circuit FaultDe-cappingAll jumpers not through in Quad lineLeaky InsulatorsClearance related problemsHigh frequency effects on transmission linesPrashant Das Tauruspowertronics Pvt. Ltd

[email protected] www.tauruspowertronics.com 23

Annexure –A without filterPadghe – BBLR – gain 1 without filter-Lots of noise

CASE STUDIES

Short circuit FaultDe-cappingAll jumpers not through in Quad lineLeaky InsulatorsClearance related problemsHigh frequency effects on transmission linesPrashant Das Tauruspowertronics Pvt. Ltd

[email protected] www.tauruspowertronics.com 24

Annexure – B with HVDC filterPadghe – BBLR– Gain1 No noise observed

CASE STUDIES

OFFLINE OVERHEAD LINE FAULT LOCATOR

Prashant Das Tauruspowertronics Pvt. Ltd

[email protected] www.tauruspowertronics.com 25

Case Studies of 25 lines taken in a Transmission ZONE during 2011-2012 . Statistics are based on the OnM internal record maintained for 365 days

Line Lengths in

KMs

Without OHFL time

taken to rectify the fault in a line (Hrs)

With OHFL time

taken to rectify

fault in a line (Hrs)

No. Of Lines in

the Zone (Total

Sample 25 lines)

Average No. of

Tripping in a

Year/Line

Total Trippings in a Year

Ideally with OHFLtime

would have taken

OHFL used

at

Time taken to

find fault with

OHFL in ( Hrs)

OHFL not

used

Time taken to find fault in

HRS without

OHFL (Hrs)

Total

time take

n

EXTRA HOUR

S

0 to 150 KMs

15 3 19 3 57171 hrs

30 places

90 hrs

27 places

405 hrs

495 hrs

324 hrs

150 to 250 Kms

19 4 4 2 832 hrs

5 Places

20 hrs

3 Places

95 hrs

115 hrs

83 hrs

250 to 350 Kms

23 4 2 2 416 hrs

1 places

4 hrs

1 place

23 hrs

27 hrs

11 hrs

Case Studies

OFFLINE OHFL

Line Signature

Prashant Das Tauruspowertronics Pvt. Ltd

[email protected] www.tauruspowertronics.com 26

Case Studies of 73 new lines in a Utility Transmission company in India

KV of the line No.of LinesNo of Tripping Without Line

Signature test

No.of Lines signature test was done

No. of lines successfully charged

after Signature Analyzer

132KV 5 3 3 3

220KV 20 11 9 9

400KV 40 16 14 14

765KV 8 3 3 3

Important parameters-while choosing an overheadtransmis

sion line fault locator

Prashant Das Tauruspowertronics Pvt. Ltd

[email protected] www.tauruspowertronics.com 27

• Equipment should be Portable & Battery operated. • Induction Voltage Suppression capability.• Auto Impedance matching facility for the kit to be

used in any EHV Lines.• Instrument should be EMI/EMC Compliance.

PAPER

Presented by

POWERGRID IN CBIP – INTERNATIONAL CONFERENCE

Using Offline Fault Locator

TO DIAGNOSE THE TRANSMISSION LINE

Prashant Das Tauruspowertronics Pvt. Ltd

[email protected] www.tauruspowertronics.com 28

29