CAR
T ST
OP
CAR
T ST
OP
CAR
T ST
OP
CLIENT
REVISIONS
PROJECT NO. HIN-19000FILENAMECHECKED BYDRAWN BYSCALEDATE 04. 13. 2020
X:\P
roje
cts\
HIN\
HIN-
1900
0\04
-Pro
duct
ion\
Engi
neer
ing\
Cons
truc
tion
Draw
ings
\Cur
rent
Dra
win
gs\H
IN19
000-
CD-O
AU1.
dwg,
4/2
4/20
20 4
:10:
08 P
M, W
eave
r, Le
e
The John R. McAdams Company, Inc.2905 Meridian Parkway
Durham, NC 27713
phone 919. 361. 5000fax 919. 361. 2269
license number: C-0293
www.mcadamsco.com
SHEET
PLAN INFORMATION
USEF HCG FENTON, LLCFIVE RAVINIA DRIVEATLANTA, GEORGIA 30346
FINAL DRAWING - RELEASED FOR CONSTRUCTION
INDEX MAP
AREA "B"AREA "A" AREA "C" AREA "D"
AREA "F"AREA "E" AREA "G" AREA "H"
AREA "J"AREA "I" AREA "K"
AREA "L"
SEE SHEET C0.00 FOR ALL PROJECT, SITE,GRADING, STORM DRAINAGE AND UTILITYNOTES
ALL CONSTRUCTION SHALL BE INACCORDANCE WITH THE CURRENT TOWN OFCARY ENGINEERING DESIGN ANDCONSTRUCTION STANDARDS
DEVE
LOPM
ENT
PLAN
- 20
-DP-
1205
855
CARY
TOW
NE B
OULE
VARD
CARY
, NOR
TH C
AROL
INA,
275
11
N0. DATE
WEGMANS
3A
3B
4A
4B
2
5
6
10A 10B
23A
22A
23B 24
17 18 19 20
22B
C4.00
HIN19000-CD-OAU1LAWJLB1"=100'
UTILITY PLANOVERALL
7
4C
12
11A(1)
11A(2)
11A(3)
SHEET C4.02SHEET C4.01 SHEET C4.03 SHEET C4.04
SHEET C4.06SHEET C4.05 SHEET C4.07 SHEET C4.08
SHEET C4.10SHEET C4.09 SHEET C4.11
SHEET C4.12
UTILITY LEGEND
TRINITY ROAD(126' PUBLIC R/W)
EXISTING
CARY TOWNE BOULEVARD-SR 1497
(VARIABLE WIDTH PUBLIC R/W
)
QUINARD ROAD
(70' PUBLIC R/W)
GRAPHIC SCALE0 50 100 200
1 inch = 100 ft.
NOTES: 1. THE DESIGN MEETS ALL CURRENT TOWN OF CARY STANDARD SPECIFICATIONS
AND DETAILS EXCEPT WHERE SPECIFICALLY NOTED BELOW.
A. NONE
FDC
NOTEA METAL SIGN WITH RAISED LETTERS AT LEAST 1 INCH IN SIZE SHALL BE MOUTED ON ALLFIRE DEPARTMENT CONNECTIONS SERVING AUTOMATIC SPRINKLERS. FDC SIGNS SHALLINCLUDE THE BUILDING ADDRESS BEING SERVED.
FDC SIGN DETAIL
"FDC" ALL SIGNS
BUILDING ADDRESS
BUILDING STREETNAME
FENTON BUILDING NEEDED FIRE-FLOW
2
3A
BUILDING
6,500
3B
4A
BUILDING #
4B
4C
5
YES
(SF) (TYPE) (GPM)
IFC REQUIREDFIRE-FLOW SPRINKLERED?
IFC REQUIREDFIRE-FLOW W/
REDUCTIONMIN.
FIRE-FLOW
(GPM) (GPM) (GPM)
95,000 IIB 1,625 1,625
2,000 YES8,681 IIB 500 1,500
2,250 YES12,323 IIB 563 1,500
1,500 YES3,300 IIB 375 1,500
1,500 YES3,300 IIB 375 1,500
1,500 YES3,400 IIB 375 1,500
2,750 YES18,385 IIB 688 1,500
6 4,750 YES49,200 IIB 1,188 1,500
7 1,500 YES4,452 IIB 375 1,500
10A/10B 8,000 YES167,698 IA/IIB 2,000 2,000
11A-1 1,500 YES3,004 IIB 375 1,500
11A-2 4,000 YES35,916 IIB 1,000 1,500
11A-3 1,500 YES3,632 IIB 375 1,500
12 5,500 YES67,400 IIB 1,375 1,500
17 1,500 YES1,593 IIB 375 1,500
18 1,500 YES1,456 IIB 375 1,500
19 1,500 YES750 IIB 375 1,500
20 1,500 YES2,128 IIB 375 1,500
22A/22B/23A/23B/24 6,000 YES505,839 IA/IIIA 1,500 1,500
PARKING DECK D1 4,000 YES (DRY RISER)137,325 IA 1,000 1,500
2,25039,663 IA N/A 2,250PARKING DECK D5 NO
WALNUT CREEK
WAL
NUT CRE
EK
WALNUT CREEK
FENTON MAIN ST.
LOWER GARDEN LANE
RIDGEVIEW WALK DR.
MARKET WALK DR.
UPPER PLAZA LANE
WALNUT SLOPE LANE
RIDGEVIEWWALK DR.
FENTONGATEWAYDR.
APPROVED by the Town of CaryDevelopment Review Committee
04/28/2020
By: Kevin A. Hales
20-DP-1205