Overcurent Very Inverse Relay

Embed Size (px)

Citation preview

  • 8/2/2019 Overcurent Very Inverse Relay

    1/4

    Overcurent Very Inverse Relay.qcm. .Test Object - Device Settings

    . . .Substation/Bay:

    Substation: Omicron Office Substation address: Vikaspuri

    Bay: Bay address:

    . . .Device:

    Name/description: Overcurrent relay Manufacturer: English Electric

    Device type: Very Inverse Device address:Serial/model number: 13OS001/CDG13AF8012MCH

    Additional info 1: Additional info 2:

    . . .Nominal Values:

    f nom: 50.00 Hz Number of phases: 3

    V nom (secondary): 110.0 V V primary: 110.0 kV

    I nom (secondary): 5.000 A I primary: 1.000 kA

    . . .Residual Voltage/Current Factors:

    VLN / VN: 1.732 IN / I nom: 1.000

    . . .Limits:

    V max: 200.0 V I max: 50.00 A

    . . .Debounce/Deglitch Filters:

    Debounce time: 3.000 ms Deglitch time: 0.000 s

    . . .Overload Detection:

    Suppression time: 50.00 ms

    Hardware Configuration.Test EquipmentType Serial Number CMC256plus JJ348B

    . .Hardware Check Performed At Result Details3/7/2012 5:40:19 PM Passed

    .Analog OutputsTest Equipment Test Object Signal

    Device Connector Display Name ConnectionTerminal

    CMC256plus IA JJ348B

    1 I L1 9 , 10(Neutral) I L1

    N

    .Binary/Analog InputsTest Equipment Test Object SignalDevice Connector Display Name Connection

    Terminal

    CMC256plus 1+ Binary Input 1 3 & 4 Trip

  • 8/2/2019 Overcurent Very Inverse Relay

    2/4

    JJ348B

    1- 2+ Bin. In. 2 2- 3+ Bin. In. 3 3- 4+ Bin. In. 4 4- 5+ Bin. In. 5 5- 6+ Bin. In. 6 6- 7+ Bin. In. 7 7- 8+ Bin. In. 8 8- 9+ Bin. In. 9 9- 10+ Bin. In. 10 10-

    1 Bin. In. 11 2 Bin. In. 12 N

    .Binary OutputsTest Equipment Test Object SignalDevice Connector Display Name Connection

    Terminal

    CMC256plusJJ348B

    1+ Bin. out 1 Bin. out 1

    1- 2+ Bin. out 2 Bin. out 2

    2- 3+ Bin. out 3 Bin. out 3

    3- 4+ Bin. out 4 Bin. out 4

    4- 11 Bin. Out 5 12 Bin. Out 6 13 Bin. Out 7 14 Bin. Out 8 N

    . .Test Module

    Name: OMICRON QuickCMC Version: 2.40 SR 1

    Test Start: 07-Mar-2012 18:08:25 Test End: 07-Mar-2012 18:30:15

    User Name: Manager: Company:

    Test ResultsTitle: Test @10A

    .Fault Calculator:Table Inputmode Parameters (All values are secondary)Direct I L1 10.00 A 0.00 50.000 Hz

  • 8/2/2019 Overcurent Very Inverse Relay

    3/4

    Generator Settings I L1 10.000A 0.00 +90

    -90

    180 0

    10.0 A

    I L1

    Binary InputsBinary Input 1 Overload0->1 1->03.830s n/a

    Analog Inputs VDCin IDCin-0.0000V 0.0642mA

    .Comment TMS=1 I pick up= 2.5 Plug Setting Multiplier= Fault Current/I Pickup =10/2.5=4 From the Relay

    nameplate PSM(4) corresponds to between 3 & 4 seconds

    . . . .Assessment

    Passed 07-Mar-2012 18:05:49

    Title: Test @10A

    .Fault Calculator:Table Inputmode Parameters (All values are secondary)Direct I L1 10.00 A 0.00 50.000 Hz

    Generator Settings I L1 10.000A 0.00 +90

    -90

    180 0

    10.0 A

    I L1

    Binary InputsBinary Input 1 Overload0->1 1->03.833s n/a

    Analog Inputs VDCin IDCin-0.0000V 0.0642mA

    .Comment TMS=1 I pick up= 2.5 Plug Setting Multiplier= Fault Current/I Pickup =10/2.5=4 From the Relay

    nameplate PSM(4) corresponds to between 3 & 4 seconds Conditions: - On trigger Switch off is checked - BinaryInputs/Trigger is checked Observation: - Binary Input 1 LED shows the continuous state. - Initially it was NO - Aftergetting the trip time it is again NO. Conclusion: Since we have checked the On Trigger Switch off box, once the faultcurrent is applied after 3.883s contacts change their state however since after trigger the kit is immediately switchedoff the momentarily NC state will not be visible

  • 8/2/2019 Overcurent Very Inverse Relay

    4/4

    . . . .Assessment

    Passed 07-Mar-2012 18:26:16

    Comment

    Summary 2 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed

    Test passed