Commissioning Test and P521/EN RS/B21 Record Sheets MiCOM P521
COMMISSIONING TEST AND RECORD SHEETS
Date: 8th November 2005
Software Version: 2
Connection Diagrams: 10P52101
P521/EN RS/B21 Commissioning Test and Record Sheets MiCOM P521
Commissioning Test and P521/EN RS/B21 Record Sheets MiCOM P521 Page 1/26
CONTENTS
1. COMMISSIONING TEST RECORD 3
2. SETTING RECORD 13
2.1 OP Parameters 13
2.2 Configuration 13
2.2.1 Display 13
2.2.2 CT ratios 14
2.2.3 LED 14
2.2.4 Group select 15
2.2.5 Alarms 15
2.2.6 Configuration inputs 15
2.2.7 Phase rotation 15
2.3 Communication 15
2.3.1 Ctrl comms (MODBUS protocol) 15
2.3.2 Ctrl comms (IEC60870-5-103 protocol) 16
2.3.3 Protection 16
2.4 Protection G1/G2 16
2.4.1 [87] Current diff 16
2.4.2 [50/51] Phase O/C 17
2.4.3 [50N/51N] E/Gnd 17
2.4.4 [46] Neg seq OC 18
2.4.5 [49] Therm OL 19
2.4.6 [37] Undercurrent 19
2.5 Automat. ctrl 19
2.5.1 Trip commands 19
2.5.2 Latch functions 20
2.5.3 I-Trip commands 20
2.5.4 Blocking logic 1/2 21
2.5.5 Logic select 1/2 21
2.5.6 Output relays 22
P521/EN RS/B21 Commissioning Test and Record Sheets Page 2/26 MiCOM P521
2.5.7 Latch output relays 22
2.5.8 Invert output relays 23
2.5.9 Inputs 1/2/3/4/5 23
2.5.10 Brkn. cond 24
2.5.11 Cold load pu 24
2.5.12 CB fail 24
2.5.13 CB supervision 25
2.6 Records 25
2.6.1 Disturb record 25
2.6.2 Disturb record 25
2.6.3 Time peak value 25
2.6.4 Rolling demand 25
Commissioning Test and P521/EN RS/B21 Record Sheets MiCOM P521 Page 3/26
1. COMMISSIONING TEST RECORD
Date: Engineer:
Station: Circuit:
System Frequency:
Front Plate Information
Current differential protection relay P521
Model number
Serial number
Auxiliary voltage Vx
Test Equipment Used
This section should be completed to allow future identification of protective devices that have been commissioned using equipment that is later found to be defective or incompatible but may not be detected during the commissioning procedure.
Overcurrent test set Model:
Serial No:
Optical power meter Model:
Serial No:
Insulation tester Model:
Serial No:
Setting software: Type:
Version:
P521/EN RS/B21 Commissioning Test and Record Sheets Page 4/26 MiCOM P521
Have all relevant safety instructions been followed? Yes No
4. PRODUCT CHECKS
4.1 With the relay de-energized
4.1.1 Visual inspection
Relay damaged? Yes No Rating information correct for installation? Yes No Case earth installed? Yes No
Current transformer shorting contacts close? Yes No Not checked
4.1.2 Insulation resistance >100M at 500V dc Yes No Not tested
4.1.3 External wiring
Wiring checked against diagram? Yes No
Test block connections checked? Yes No N/A
4.1.4 Watchdog contact (auxiliary supply off)
Terminals 35 and 36 Contact closed? Yes No
Contact resistance Not measured
Watchdog Contact (auxiliary supply on)
Terminals 35 and 36 Contact open? Yes No
4.1.5 Measured auxiliary supply V ac/dc
4.2 With the relay energized
4.2.1 Date and time
Clock set to local time? Yes No
Time maintained when auxiliary supply removed? Yes No
Commissioning Test and P521/EN RS/B21 Record Sheets MiCOM P521 Page 5/26
4.2.2 Light emitting diodes
4.2.2.1 Relay healthy (green) LED working? Yes No Warning (orange) LED working? Yes No Alarm (yellow) LED working? Yes No Trip (red) LED working? Yes No All 4 programmable (red) LEDs working? Yes No
4.2.3 Input opto-isolators
Opto input 1 working? Yes No Opto input 2 working? Yes No Opto input 3 working? Yes No Opto input 4 working? Yes No Opto input 5 working? Yes No
4.2.4 Output relays
Relay 1 Working? Yes No
Contact resistance (N/C) Not measured
(N/O) Not measured
Relay 2 Working? Yes No
Contact resistance (N/C) Not measured
(N/O) Not measured
Relay 3 Working? Yes No
Contact resistance Not measured
Relay 4 Working? Yes No
Contact resistance Not measured
P521/EN RS/B21 Commissioning Test and Record Sheets Page 6/26 MiCOM P521
Relay 5 Working? Yes No
Contact resistance Not measured
Relay 6 Working? Yes No
Contact resistance Not measured
Relay 7 Working? Yes No
Contact resistance Not measured
Relay 8 Working? Yes No N/A
Contact resistance Not measured
4.2.5 Communication standard
MODBUS
IEC60870-5-103
DNP 3.0
Communications established? Yes No
Protocol converter tested? Yes No N/A
4.2.6 Current differential protection communications
Type of communications:
Dedicated fiber
Via P59x
EIA(RS)485
EIA(RS)232
Modem
4.2.6.1 Direct fiber communication
Communication working? Yes No N/A
Commissioning Test and P521/EN RS/B21 Record Sheets MiCOM P521 Page 7/26
4.2.6.2 Direct EIA(RS)485
Communication working? Yes No N/A
4.2.6.3 EIA(RS)232
Communication working? Yes No N/A
4.2.6.4 Communication using modems
Unit damaged? Yes No
Communication working? Yes No N/A
4.2.6.5 Communication using P595
Unit damaged? Yes No
Communication working? Yes No N/A
4.2.6.x.1 Visual inspection (P59x units only)
Unit damaged?
Channel 1 unit Yes No
N/A
Rating information correct?
Channel 1 unit Yes No
N/A
Case earth installed?
Channel 1 unit Yes No
N/A
4.2.6.x.2 Insulation resistance (P59x units only)
Channel 1 unit
Yes No
Not tested
N/A
P521/EN RS/B21 Commissioning Test and Record Sheets Page 8/26 MiCOM P521
4.2.6.x.3 External wiring (P59x units only)
Wiring checked against diagram?
Channel 1 unit Yes No
N/A
4.2.6.x.4 Measured auxiliary supply (P59x units only)
Channel 1 unit
V dc
V ac
N/A
All LEDs working?
Channel 1 unit Yes No
N/A
4.2.6.x.5 Loopback test
Signal strength received by P59x
Channel 1 unit dBm
N/A
Signal strength transmitted by P59x
Channel 1 unit dBm
N/A
Signal Strength within tolerance Yes No
N/A
Loopback test applied?
Channel 1 unit Yes No
N/A
Communications working Yes No
N/A
4.2.7 Current inputs
Displayed Current Primary
Secondary Phase CT Ratio N/A
Earth Fault CT Ratio N/A
CT Correction Ratio N/A
Commissioning Test and P521/EN RS/B21 Record Sheets MiCOM P521 Page 9/26
Input CT Applied value Displayed value
A A A B A A C A A N A A
5. SETTING CHECKS
5.1 Application-specific function settings applied? Yes No
5.2.1.2 Current differential lower slope pickup A
5.2.1.3 Current differential upper slope pickup A
5.2.2 Current differential operating time
Current Differential Phase A trip time s
Current Differential Phase B trip time s
Current Differential Phase C trip time s
5.2.3 Backup phase overcurrent protection enabled? Yes No 5.2.3.2 Applied current A
5.2.3.3 Expected operating time s
Measured operating time s
6. END TO END TESTS
6.1 Remove the loopback test
Communications alarms? Yes No Loopback test removed? Yes No All connections restored? Yes No Application-specific settings applied? Yes No Cover replaced? (P59x units only) Yes No
6.2 Verify communications between relays
6.2.1 Optical port type
850nm
1300nm multi
1300nm single
Signal strength received by P521 dBm
N/A
P521/EN RS/B21 Commissioning Test and Record Sheets Page 10/26 MiCOM P521
Signal strength transmitted by P521 dBm
N/A
Signal Strength within tolerance Yes No
N/A
Optical fibers reconnected? Yes No Alarms reset? Yes No
6.2.2 Metallic communications
Direct EIA(RS)485
P595
EIA(RS)232
Modem
Transmit and receive leads reconnected? Yes No Alarms reset? Yes No
7. ON-LOAD CHECKS
Test wiring removed? Yes No N/A
Disturbed customer wiring re-checked? Yes No N/A
On-load test performed? Yes No
7.1 Confirm current transformer wiring
CT wiring checked? Yes No N/A
CT polarities correct? Yes No Phase CT ratio N/A
Earth fault CT ratio N/A
Currents: Applied value Displayed value
A A A B A A C A A N A N/A A N/A
Commissioning Test and P521/EN RS/B21 Record Sheets MiCOM P521 Page 11/26
7.2 Capacitive charging current
Measured capacitive charging current
A phase A
B phase A
C phase A
Differential setting S1 A
7.3 Differential current checked? Yes No
7.4 Consistency of current transformer polarity
Polarity at each end consistent? A phase Yes No
B phase Yes No
C phase Yes No
8. FINAL CHECKS
Test wiring removed? Yes No N/A
Disturbed customer wiring re-checked? Yes No N/A
Commissioning test mode disabled? Yes No
Circuit breaker operations counter reset? Yes No N/A
Current counters reset? Yes No N/A
Event records reset? Yes No Fault records reset? Yes No Disturbance records reset? Yes No Alarms reset? Yes No LEDs reset? Yes No
Front cover replaced? Yes No N/A
P521/EN RS/B21 Commissioning Test and Record Sheets Page 12/26 MiCOM P521
Commissioning Engineer Customer Witness
Date: Date:
Commissioning Test and P521/EN RS/B21 Record Sheets MiCOM P521 Page 13/26
2. SETTING RECORD
Date: Engineer:
Station: Circuit:
System Frequency:
Front Plate Information
Current Differential Protection Relay P521
Model Number
Serial Number
Auxiliary Voltage Vx
*Delete as appropriate
Setting Groups Used
Group 1 Yes No
Group 2 Yes No
2.1 OP Parameters
Description
Reference
Model Number
Software Version
Frequency
2.2 Configuration
2.2.1 Display
Default Display
Phase A Text
Phase B Text
Phase C Text
E/Gnd Text
P521/EN RS/B21 Commissioning Test and Record Sheets Page 14/26 MiCOM P521
2.2.2 CT ratios
Line CT primary
Line CT sec
E/Gnd CT primary
E/Gnd CT sec
CT Correct Ratio
Vector Comp.
2.2.3 LED
Functions LED 5 LED 6 LED 7 LED 8
diff Yes No Yes No Yes No Yes No diff Fail Yes No Yes No Yes No Yes No B/up Prot Yes No Yes No Yes No Yes No
Comms Fail Yes No Yes No Yes No Yes No
Direct I-Trip Yes No Yes No Yes No Yes No
C-Diff I-Trip Yes No Yes No Yes No Yes No
PT Yes No Yes No Yes No Yes No > Yes No Yes No Yes No Yes No t> Yes No Yes No Yes No Yes No >> Yes No Yes No Yes No Yes No t>> Yes No Yes No Yes No Yes No >>> Yes No Yes No Yes No Yes No t>>> Yes No Yes No Yes No Yes No >>>> Yes No Yes No Yes No Yes No t>>>> Yes No Yes No Yes No Yes No e> Yes No Yes No Yes No Yes No te> Yes No Yes No Yes No Yes No e>> Yes No Yes No Yes No Yes No te>> Yes No Yes No Yes No Yes No e>>> Yes No Yes No Yes No Yes No te>>> Yes No Yes No Yes No Yes No e>>>> Yes No Yes No Yes No Yes No te>>>> Yes No Yes No Yes No Yes No Therm Trip Yes No Yes No Yes No Yes No
Brkn. Cond. Yes No Yes No Yes No Yes No
CB Fail Yes No Yes No Yes No Yes No
t2> Yes No Yes No Yes No Yes No t2>> Yes No Yes No Yes No Yes No
Commissioning Test and P521/EN RS/B21 Record Sheets MiCOM P521 Page 15/26
Functions LED 5 LED 6 LED 7 LED 8
Input 1 Yes No Yes No Yes No Yes No
Input 2 Yes No Yes No Yes No Yes No
Input 3 Yes No Yes No Yes No Yes No
Input 4 Yes No Yes No Yes No Yes No
Input 5 Yes No Yes No Yes No Yes No
tAux 1 Yes No Yes No Yes No Yes No
tAux 2 Yes No Yes No Yes No Yes No
CB Alarm Yes No Yes No Yes No Yes No
2.2.4 Group select
Change Group Input
2.2.5 Alarms
Inst. Self-reset? Alarm Battery
2.2.6 Configuration inputs
Inputs
Voltage Input
2.2.7 Phase rotation
Phase rotation
2.3 Communication
2.3.1 Ctrl comms (MODBUS protocol)
Ctrl Comms? Baud Rate
Parity
Stop Bits
Relay Address
Date format
P521/EN RS/B21 Commissioning Test and Record Sheets Page 16/26 MiCOM P521
2.3.2 Ctrl comms (IEC60870-5-103 protocol)
Ctrl Comms? Data Bits
Relay Address
2.3.3 Protection
Protocol
Data Rate
Relay Address
Clock Source Ch1
Comm Fail Timer
Comms Delay Tol
Char Mod Time
2.4 Protection G1/G2
2.4.1 [87] Current diff
Functions Group 1 Group 2
Current Diff? s1 s2 K1
K2
Diff Delay Type tdiff Diff Curve Diff Tms Diff Time Dial PT Time PT Disable DIT Rx tDwell
Inrush Restraint
High Set
Commissioning Test and P521/EN RS/B21 Record Sheets MiCOM P521 Page 17/26
2.4.2 [50/51] Phase O/C
Functions Group 1 Group 2
>? > > Delay Type > Curve > Tms t> Reset Type
K
tReset
Time Dial
>>? >> t>> Delay Type >> Curve >> Tms t>> Reset Type
K
tReset
Time Dial
>>>? >>> t>>> >>>>? >>>> t>>>>
2.4.3 [50N/51N] E/Gnd
Functions Group 1 Group 2
e>? e> e> Delay Type e> Curve e> Tms
P521/EN RS/B21 Commissioning Test and Record Sheets Page 18/26 MiCOM P521
Functions Group 1 Group 2
te> Reset Type
K
tReset
Time Dial
e>>? e>> te>> Delay Type e> Curve e>> Tms te>> Reset Type
K
tReset
Time Dial
e>>>? e>>> te>>> e>>>>? e>>>> te>>>>
2.4.4 [46] Neg seq OC
Functions Group 1 Group 2
2>? 2> 2> Delay Type 2> Curve 2> Tms t2> Reset Type
K
tReset
Time Dial
t Reset
Commissioning Test and P521/EN RS/B21 Record Sheets MiCOM P521 Page 19/26
Functions Group 1 Group 2
2>>? 2>> t2>>
2.4.5 [49] Therm OL
Functions Group 1 Group 2
Therm OL? > Te
k
Trip Alarm? Alarm
2.4.6 [37] Undercurrent
Functions Group 1 Group 2
P521/EN RS/B21 Commissioning Test and Record Sheets Page 20/26 MiCOM P521
Trip t< Yes No Trip t2> Yes No Trip t2>> Yes No Trip Thermal Yes No Trip Brkn. Cond. Yes No
Trip tAux1 Yes No
Trip tAux1 Yes No
2.5.2 Latch functions
Latch diff Yes No Latch Direct -Trip Yes No Latch C Diff -Trip Yes No Latch PT Yes No Latch t> Yes No Latch t>> Yes No Latch t>>> Yes No Latch t>>>> Yes No Latch te> Yes No Latch te>> Yes No Latch te>>> Yes No Latch te>>>> Yes No Latch t< Yes No Latch t2> Yes No Latch t2>> Yes No Latch Thermal Yes No Latch Brkn. Cond. Yes No
Latch tAux1 Yes No
Latch tAux1 Yes No
2.5.3 I-Trip commands
I-Trip tI> Yes No
I-Trip tI>> Yes No
I-Trip tI>>> Yes No
I-Trip tI>>>> Yes No
I-Trip tIe> Yes No
Commissioning Test and P521/EN RS/B21 Record Sheets MiCOM P521 Page 21/26
I-Trip tIe>> Yes No
I-Trip tIe>>> Yes No
I-Trip tIe>>>> Yes No
I-Trip tI< Yes No
I-Trip tI2> Yes No
I-Trip tI2>> Yes No
I-Trip Thermal Yes No I-Trip Brkn. Cond Yes No
I-Trip tAux1 Yes No
I-Trip tAux2 Yes No
I-Trip CB Fail Yes No
2.5.4 Blocking logic 1/2
Functions Blocking Logic 1 Blocking Logic 2
Block diff Yes No Yes No Block t> Yes No Yes No Block t>> Yes No Yes No Block t>>> Yes No Yes No Block t>>>> Yes No Yes No Block te> Yes No Yes No Block te>> Yes No Yes No Block te>>> Yes No Yes No Block te>>>> Yes No Yes No Block t2> Yes No Yes No Block t2>> Yes No Yes No Block Thermal Yes No Yes No Block Brkn. Cond. Yes No Yes No
Block tAux 1 Yes No Yes No
Block tAux 2 Yes No Yes No
2.5.5 Logic select 1/2
Functions Logic Select 1 Logic Select 2
Sel t>> Yes No Yes No Sel t>>> Yes No Yes No Sel t>>>> Yes No Yes No Sel te>> Yes No Yes No
P521/EN RS/B21 Commissioning Test and Record Sheets Page 22/26 MiCOM P521
Functions Logic Select 1 Logic Select 2
Sel te>>> Yes No Yes No Sel te>>>> Yes No Yes No tSel 1
2.5.6 Output relays
Functions Setting Functions Setting
Trip te>> Diff e>>> Back-up Prot. te>>> Comms Fail e>>>> Direct -Trip te>>>> C-Diff -Trip t< PT t2> > t2>> t> Therm Alarm >> Therm Trip t>> CB Alarm >>> 52 Fail t>>> Brkn. Cond. >>>> CB fail t>>>> CB Close e> tAux1 te> tAux2 e>> Active Group
2.5.7 Latch output relays
Output 2 Yes No
Output 3 Yes No
Output 4 Yes No
Output 5 Yes No
Output 6 Yes No
Output 7 Yes No
Output 8 Yes No
Commissioning Test and P521/EN RS/B21 Record Sheets MiCOM P521 Page 23/26
2.5.8 Invert output relays
Output 2 Yes No
Output 3 Yes No
Output 4 Yes No
Output 5 Yes No
Output 6 Yes No
Output 7 Yes No
Output 8 Yes No
2.5.9 Inputs 1/2/3/4/5
None Blk Log 1 Reset Unlatch Blk Log 2 Trip circ
52a Start Dist Strt tBF
52b Cold L PU Permiss IT
Comms RST Log sel 1 Direct IT
Aux 1 Log sel 2 Log Trip
Input 1
Aux 2 Change Set Log Close
None Blk Log 1 Reset Unlatch Blk Log 2 Trip circ
52a Start Dist Strt tBF
52b Cold L PU Permiss IT
Comms RST Log sel 1 Direct IT
Aux 1 Log sel 2 Log Trip
Input 2
Aux 2 Change Set Log Close
None Blk Log 1 Reset Unlatch Blk Log 2 Trip circ
52a Start Dist Strt tBF
52b Cold L PU Permiss IT
Comms RST Log sel 1 Direct IT
Aux 1 Log sel 2 Log Trip
Input 3
Aux 2 Change Set Log Close
None Blk Log 1 Reset Unlatch Blk Log 2 Trip circ
52a Start Dist Strt tBF
52b Cold L PU Permiss IT
Comms RST Log sel 1 Direct IT
Aux 1 Log sel 2 Log Trip
Input 4
Aux 2 Change Set Log Close
P521/EN RS/B21 Commissioning Test and Record Sheets Page 24/26 MiCOM P521
None Blk Log 1 Reset Unlatch Blk Log 2 Trip circ
52a Start Dist Strt tBF
52b Cold L PU Permiss IT
Comms RST Log sel 1 Direct IT
Aux 1 Log sel 2 Log Trip
Input 5
Aux 2 Change Set Log Close
Aux 1 Time tAux1
Aux 2 Time tAux2
2.5.10 Brkn. cond
Brkn. Cond? Brkn. Cond. Time tBC
Ratio 2/1
2.5.11 Cold load pu
Cold Load PU? Yes No t>? Yes No t>>? Yes No t>>>? Yes No t>>>>? Yes No te>? Yes No te>>? Yes No te>>>? Yes No te>>>>? Yes No t2>? Yes No t2>>? Yes No t Therm? Yes No Cold Load PU Level
Cold Load tCL
2.5.12 CB fail
CB Fail? < = CB Fail Time tBF
Block >
Commissioning Test and P521/EN RS/B21 Record Sheets MiCOM P521 Page 25/26
Block e>
2.5.13 CB supervision
TC Supervision? t tripcircuit tSUP
CB Open Svision
CB Open Time
CB Close Svision
CB Close Time
CB Close Alarm? CB Open NB
Amps(n)? Amps(n) n
t Open Pulse
t Close Pulse
CB Man Trip Dly
CB Man Close Dly
2.6 Records
2.6.1 Disturb record
Pre-time
Post-time
Disturb Rec Trig
2.6.2 Disturb record
Pre-time
Post-time
Disturb Rec Trig
2.6.3 Time peak value
Time Window
2.6.4 Rolling demand
Sub Period
Num of Sub Per
P521/EN RS/B21 Commissioning Test and Record Sheets Page 26/26 MiCOM P521
Commissioning Engineer Customer Witness
Date: Date:
P521_EN_RS_B211. COMMISSIONING TEST RECORD2. SETTING RECORD 2.1 OP Parameters2.2 Configuration2.2.1 Display2.2.2 CT ratios2.2.3 LED2.2.4 Group select2.2.5 Alarms2.2.6 Configuration inputs2.2.7 Phase rotation
2.3 Communication2.3.1 Ctrl comms (MODBUS protocol)2.3.2 Ctrl comms (IEC60870-5-103 protocol)2.3.3 Protection
2.4 Protection G1/G22.4.1 [87] Current diff2.4.2 [50/51] Phase O/C2.4.3 [50N/51N] E/Gnd2.4.4 [46] Neg seq OC2.4.5 [49] Therm OL2.4.6 [37] Undercurrent
2.5 Automat. ctrl2.5.1 Trip commands2.5.2 Latch functions2.5.3 I-Trip commands2.5.4 Blocking logic 1/22.5.5 Logic select 1/22.5.6 Output relays2.5.7 Latch output relays2.5.8 Invert output relays2.5.9 Inputs 1/2/3/4/52.5.10 Brkn. cond2.5.11 Cold load pu2.5.12 CB fail2.5.13 CB supervision
2.6 Records2.6.1 Disturb record2.6.2 Disturb record2.6.3 Time peak value2.6.4 Rolling demand