P63X

Embed Size (px)

Citation preview

  • 7/31/2019 P63X

    1/525

    MiCOM

    P631/P632/P633/P634

    Transformer Differential Protection

    P631 -301/302 -401/402 -301/602/603

    P632 -301/302 -401/402 -301/602/603

    P633 -301/302 -401/402/403 -301/602/603

    P634 -301/302 -401/402 -301/602/603

    Technical Manual

    P63X/EN M/C32

    Contains:Technical Manual for

    Software Version 601 P63X/EN M/C11

    Software Update 602 P63X/EN AD/B22

    Software Update 603 P63X/EN AD/C32

  • 7/31/2019 P63X

    2/525

  • 7/31/2019 P63X

    3/525

    MiCOM

    P631/P632/P633/P634

    Transformer Differential Protection

    Version -301 -401 -601

    Technical Manual

    P63X/EN M/C11

    (AFSV.12.06661 EN)

  • 7/31/2019 P63X

    4/525

  • 7/31/2019 P63X

    5/525

    WarningWhen electrical equipment is in operation, dangerous voltage will be present in certain parts of theequipment. Failure to observe warning notices, incorrect use, or improper use may endangerpersonnel and equipment and cause personal injury or physical damage.

    Before working in the terminal strip area, the device must be isolated. Where stranded conductorsare used, wire end ferrules must be employed.

    Proper and safe operation of this device depends on appropriate shipping and handling, properstorage, installation and commissioning, and on careful operation, maintenance and servicing.

    For this reason only qualified personnel may work on or operate this device.

    Qualified Personnelare individuals who

    o are familiar with the installation, commissioning, and operation of the device and of the system to which it is beingconnected;

    o are able to perform switching operations in accordance with safety engineering standards and are authorized toenergize and de-energize equipment and to isolate, ground, and label it;

    o are trained in the care and use of safety apparatus in accordance with safety engineering standards;

    o are trained in emergency procedures (first aid).

    NoteThe operating manual for this device gives instructions for its installation, commissioning, and operation. However, themanual cannot cover all conceivable circumstances or include detailed information on all topics. In the event ofquestions or specific problems, do not take any action without proper authorization. Contact the appropriate AREVA

    technical sales office and request the necessary information.

    Any agreements, commitments, and legal relationships and any obligations on the part of AREVA,including settlement of warranties, result solely from the applicable purchase contract, which is not affected bythe contents of the operating manual.

  • 7/31/2019 P63X

    6/525

  • 7/31/2019 P63X

    7/525

  • 7/31/2019 P63X

    8/525

    Modifications After Going to Press

  • 7/31/2019 P63X

    9/525

    Contents

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 7

    1 ApplicationandScope 1-1

    2 TechnicalData 2-1

    2.1 Conformity 2-12.2 General Data 2-12.3 Tests 2-22.3.1 Type Tests 2-22.3.2 Routine Tests 2-42.4 Climatic Conditions 2-42.5 Inputs and Outputs 2-52.6 Interfaces 2-62.7 Information Output 2-8

    2.8 Settings 2-82.9 Deviations 2-82.9.1 Deviations of the Operate Values 2-82.9.2 Deviations of the Timer Stages 2-92.9.3 Deviations of Measured Data Acquisition 2-102.10 Recording Functions 2-112.11 Power supply 2-122.12 Dimensioning of Current Transformers 2-13

  • 7/31/2019 P63X

    10/525

    Contents(continued)

    8 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    3 Operation 3-13.1 Modular Structure 3-13.2 Operator-Machine Communication 3-33.3 Configuration of the Measured

    Value Panels(function group LOC) 3-4

    3.4 Serial Interfaces 3-73.4.1 PC interface (function group PC) 3-73.4.2 Communication interface (function group COMM1) 3-93.5 Time synchronization via the

    IRIG-B interface(function group IRIGB) 3-16

    3.6 Configuration and operating modeof the binary inputs

    (function group INP) 3-17

    3.7 Measured data input (function group MEASI) 3-183.7.1 Direct current input 3-193.7.2 Input for Connection of a

    Resistance Thermometer3-22

    3.8 Configuration, operating mode andblocking of the output relays

    (function group OUTP) 3-23

    3.9 Measured data output (function group MEASO) 3-263.9.1 BCD-coded measured data output 3-293.9.2 Analog measured data output 3-313.9.3 Output of external measured data 3-353.10 Configuration and operating mode

    of the LED indicators(function group LED) 3-36

    3.11 Main functions of the P63x (function group MAIN) 3-383.11.1 Conditioning of the measured

    variables3-38

    3.11.2 Selection of the residual current tobe monitored

    3-42

    3.11.3 Operating data measurement 3-453.11.4 Configuring and enabling the

    protection functions3-57

    3.11.5 Activation of dynamic parameters 3-593.11.6 Multiple blocking 3-593.11.7 Blocked / faulty 3-613.11.8 Starting signals and starting logic 3-623.11.9 Time tag and clock synchronization 3-663.11.10 Resetting mechanisms 3-673.11.11 Test mode 3-68

  • 7/31/2019 P63X

    11/525

    Contents(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 9

    3.12 Parameter subset selection (function group PSS) 3-693.13 Self-monitoring (function group SFMON) 3-713.14 Operating data recording (function group OP_RC) 3-733.15 Monitoring signal recording (function group MT_RC) 3-743.16 Overload data acquisition (function group OL_DA) 3-753.17 Overload recording (function group OL_RC) 3-783.18 Fault data acquisition (function group FT_DA) 3-813.19 Fault recording (function group FT_RC) 3-893.20 Differential protection (function group DIFF) 3-953.21 Ground differential protection

    (Br: Restricted earth fault protection)(function groupsREF_1 to REF_3)

    3-116

    3.22 Definite-time overcurrentprotection

    (function groupsDTOC1 to DTOC3)

    3-123

    3.23 Inverse-time overcurrent protection (function groupsIDMT1 to IDMT3)

    3-133

    3.24 Thermal overload protection (function groupsTHRM1 and THRM2)

    3-149

    3.25 Time-voltage protection (function group V) 3-1583.26 Over-/ underfrequency protection (function group f) 3-1613.27 Limit value monitoring (function group LIMIT) 3-1663.28 Limit value monitoring 1 to 3 (function groups

    LIM_1 to LIM_3)3-169

    3.29 Programmable logic (function group LOGIC) 3-172

  • 7/31/2019 P63X

    12/525

    Contents(continued)

    10 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    4 Design 4-1

    4.1 Designs 4-24.2 Modules 4-8

    5 Installationandconnection 5-1

    5.1 Unpacking and packing 5-15.2 Checking the nominal data and the design type 5-15.3 Location requirements 5-25.4 Installation 5-35.5 Protective grounding 5-145.6 Connection 5-15

    5.6.1 Connecting the measuring and auxiliary circuits 5-155.6.2 Connecting the IRIG-B interface 5-185.6.3 Connecting the serial interfaces 5-18

    6 Local control panel 6-1

    6.1 Display and keypad 6-26.2 Changing between display levels 6-66.3 Illumination of the display 6-76.4 Control at the Panel level 6-76.5 Control at the menu tree level 6-86.5.1 Navigation in the menu tree 6-86.5.2 Switching between address mode and plain text mode 6-96.5.3 Change-enabling function 6-106.5.4 Changing parameters 6-136.5.5 Setting a list parameter 6-146.5.6 Memory readout 6-156.5.7 Resetting 6-196.5.8 Password-protected control actions 6-206.5.9 Changing the password 6-21

    7 Settings 7-1

    7.1 Parameters 7-17.1.1 Device identification 7-27.1.2 Configuration parameters 7-67.1.3 Function parameters 7-30

    7.1.3.1 Global 7-307.1.3.2 General functions 7-337.1.3.3 Parameter subsets 7-46

    8 Information and control functions 8-1

    8.1 Operation 8-18.1.1 Cyclic values 8-18.1.1.1 Measured operating data 8-18.1.1.2 Physical state signals 8-108.1.1.3 Logic state signals 8-158.1.2 Control and testing 8-308.1.3 Operating data recording 8-32

    8.2 Events 8-338.2.1 Event counters 8-338.2.2 Measured fault data 8-348.2.3 Fault recording 8-37

  • 7/31/2019 P63X

    13/525

    Contents(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 11

    9 Commissioning 9-1

    9.1Safety instructions

    9-1

    9.2Commissioning tests

    9-3

    10 Troubleshooting 10-1

    11 Maintenance 11-1

    12 Storage 12-1

    13 Accessoriesandspareparts 13-1

    14 Order information 14-1

    14.1 Order information for P631 in case 40T 14-114.2 Order information for P632 in case 40T 14-214.3 Order information for P633 in case 40T or 84T 14-314.4 Order information for P634 in case 84T 14-4

    Appendix

  • 7/31/2019 P63X

    14/52512 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

  • 7/31/2019 P63X

    15/525

    1 Application and Scope

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 1-1

    1 Application and Scope

    The P63x differential protection devices are designed for the fast and selective short-circuit protection of transformers, motors and generators and of other two-, three- or four-winding arrangements. Four models are available. The P631 and P632 are designed forthe protection of two-winding arrangements, the P633 and P634 for the protection ofthree- or four-winding arrangements, respectively.

    Main functionsThe P63x differential protection devices have the following main functions:

    Three-system differential protection for protected objects with up to four windings

    Amplitude and vector group matching Zero-sequence current filtering for each winding, may be deactivated

    Triple-slope tripping characteristic

    Inrush restraint with second harmonic, optionally with or without global effects;may be deactivated

    Overfluxing restraint with fifth harmonic component, may be deactivated

    Through-stabilization with saturation discriminator

    Ground differential protection (Am) ; (Br: Restricted earth fault protection)(This function is not available in the P631.)

    Definite-time overcurrent protection (three stages, phase-selective,

    separate measuring systems for phase currents, negative-sequence currentand residual current)

    Inverse-time overcurrent protection (single-stage, phase-selective,separate measuring systems for phase currents, negative-sequence currentand residual current)

    Thermal overload protection, choice of relative or absolute thermal replica

    Over-/ underfrequency protection

    Over-/ undervoltage protection (time-voltage protection)

    Limit value monitoring

    Programmable logic

    The user can select all main functions individually for inclusion in the device configurationor cancel them as desired. By means of a straightforward configuration procedure, theuser can adapt the device flexibly to the scope of protection required in each particularapplication. The units powerful, freely configurable logic also makes it possible toaccommodate special applications.

  • 7/31/2019 P63X

    16/525

    1 Application and Scope(continued)

    1-2 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    Global functionsIn addition to the features listed above, the P63x models provide comprehensive self-monitoring as well as the following global functions:

    Parameter subset selection

    Operating data recording (time-tagged signal logging)

    Overload data acquisition

    Overload recording (time-tagged signal logging)

    Fault data acquisition

    Fault signal recording (time-tagged signal logging with fault value recording of the

    phase currents for each winding)

    Extended fault recording (fault recording of the neutral-point current for each windingas well as the voltage)

  • 7/31/2019 P63X

    17/525

    1 Application and Scope(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 1-3

    The following function groups are provided in the P63x differential protection devices. Fora detailed description of these function groups, see Chapter 3.

    P631 P632 P633 P634

    COMM1: Communication link

    DIFF: Differential protection

    DTOC1: Definite-time overcurrent protection 1

    DTOC2: Definite-time overcurrent protection 2

    DTOC3: Definite-time overcurrent protection 3 - -

    DVICE: Device

    f: Over-/underfrequency protection -

    FT_DA: Fault data acquisition

    FT_RC: Fault recording

    IDMT1: Inverse-time overcurrent protection 1

    IDMT2: Inverse-time overcurrent protection 2

    IDMT3: Inverse-time overcurrent protection 3 - -

    INP: Binary inputs

    IRIGB: IRIG-B interface

    LED: LED indicators

    LIM_1: Limit value monitoring 1

    LIM_2: Limit value monitoring 2 LIM_3: Limit value monitoring 3 - -

    LIMIT: Limit value monitoring

    LOC: Local control panel

    LOGIC: Logic

    MAIN: Main functions

    MEASI: Measured data input

    MEASO: Measured data output

    MT_RC: Monitoring signal recording

    OL_DA: Overload data acquisition

    OL_RC: Overload recording

    OP_RC: Operating data recording

    OUTP: Binary outputs

    PC: PC link

    PSS: Parameter subset selection

    REF_1: Ground differential protection 1 (Am) ;(Br: Restricted earth fault protection 1)

    -

    REF_2: Ground differential protection 2 -

    REF_3: Ground differential protection 3 - -

    SFMON: Self-monitoring

    THRM1: Thermal overload protection 1

    THRM2: Thermal overload protection 2 - -

    V: Time-voltage protection -

  • 7/31/2019 P63X

    18/525

    1 Application and Scope(continued)

    1-4 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    DesignThe P63x is modular in design. The plug-in modules are housed in a robust aluminumcase and electrically connected via one analog and one digital bus module.

    Inputs and outputsThe P63x models have the following inputs/outputs:

    P631 P632 P633 P634

    Phase current inputs 6 6 9 12

    Inputs for residual or neutral current - 2 3 3

    Voltage inputs - 1 1 1

    Optical coupler inputs for binary signals(freely configurable function assignment)

    4 4 to 10(perorder)

    4 to 16(perorder)

    4 to 10(perorder)

    Additional optical coupler inputs (optional) - 24 24 24

    Output relays(freely configurable function assignment)

    8 to 14(perorder)

    8 to 22(perorder)

    8 to 30(perorder)

    8 to 22(perorder)

    Analog input, 0 to 20 mA - 1 1 1

    PT 100 input - 1 1 1

    Analog output, 0 to 20 mA - 2 2 2

    The nominal voltage range of the optical coupler inputs is 24 to 250 V DC without internalswitching. The auxiliary voltage inputfor the power supply is also a wide-range design.The nominal voltage ranges are 48 to 250 V DC and 100 to 230 V AC. A 24 V DCversion is also available. All output relays are suitable for both signals and commands.

    The optional PT 100 input is lead-compensated, balanced and linearized for PT-100resistance thermometers per IEC 751.

    The optional 0 to 20 mA input provides open-circuit and overload monitoring, zerosuppression defined by a setting, plus the option of linearizing the input variable via 20adjustable interpolation points.

    Two freely selected measured variables (cyclically updated measured operating data,stored overload data and stored measured fault data) can be output as a load-independent direct current via the two optional 0 to 20 mA outputs. The characteristicsare defined via 3 adjustable interpolation points allowing a minimum output current(4 mA, for example) for receiver-side open-circuit monitoring, knee-point definition for finescaling and a limitation to lower nominal currents (10 mA, for example). Where sufficientoutput relays are available, a freely selected measured variable can be output in BCD-coded form via contacts.

    InterfacesLocal control and display:

  • 7/31/2019 P63X

    19/525

    1 Application and Scope(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 1-5

    Local control panel with LCD display

    17 LED indicators, 13 of which allow freely configurable function assignment

    PC interface

    Communication interface for connection to a substation control system (optional)

    Information exchange is via the local control panel, the PC interface, or the optionalcommunication interface.

    The communication interface complies with the international IEC 60870-5-103 standardor alternatively, with IEC 870-5-101, MODBUS or DNP 3.0. Using the communicationinterface, the P63x can be integrated with a substation control system.

  • 7/31/2019 P63X

    20/5251-6 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

  • 7/31/2019 P63X

    21/525

    2 Technical Data

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 2-1

    2 Technical Data

    2.1 Conformity

    NoticeApplicable to P631/P632/P633/P634, version 301-401-601.

    Declaration of conformity(Per Article 10 of EC Directive 72/73/EC.)The products designated P631, P632, P633 and P634 Transformer DifferentialProtection Devices have been designed and manufactured in conformance with theEuropean standards EN 60255-6 and EN 60010-1 and with the EMC Directive and theLow Voltage Directive issued by the Council of the European Community.

    2.2 General Data

    General device dataDesignSurface-mounted case suitable for wall installation or flush-mounted case for19 cabinets and for control panels.

    Installation PositionVertical 30.

    Degree of ProtectionPer DIN VDE 0470 and EN 60529 or IEC 529.IP 52; IP 20 for rear connection space with flush-mounted case.

    WeightCase 40 T: approx. 7 kgCase 84 T: approx. 11 kg

    Dimensions and ConnectionsSee Dimensional Drawings (Chapter 4) and Terminal Connection Diagrams (Chapter 5).

    Terminals

    PC Interface (X6):DIN 41652 connector, type D-Sub, 9-pin.

    Communication Interface:Optical fibers (X7 and X8): F-SMA optical fiber connector

    per IEC 874-2 or DIN 47258orBFOC (ST

    ) optical fiber connector 2.5

    per IEC 874-10 or DIN 47254-1(ST

    is a registered trademark of AT&T

    Lightguide Cable Connectors)orLeads (X9 and X10): M2 threaded terminal ends for wire cross-sections

    up to 1.5 mm2.

    IRIG-B Interface (X11): BNC plug

  • 7/31/2019 P63X

    22/525

    2 Technical Data(continued)

    2-2 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    Current-Measuring Inputs:M5 threaded terminal ends, self-centering with wire protection for conductor cross

    sections 4 mm2.

    Other Inputs and Outputs:M3 threaded terminal ends, self-centering with wire protection for conductor cross

    sections from 0.2 to 2.5 mm2.

    Creepage Distances and ClearancesPer EN 61010-1

    and IEC 664-1.

    Pollution degree 3, working voltage 250 V,overvoltage category III, impulse test voltage 5 kV.

    2.3 Tests

    2.3.1 Type Tests

    Type testsAll tests per EN 60255-6

    or IEC 255-6.

    Electromagneticcompatibility (EMC)

    Interference SuppressionPer EN 55022

    or IEC CISPR 22, Class A.

    1 MHz Burst Disturbance TestPer IEC 255 Part 22-1

    or IEC 60255-22-1, Class III.

    Common-mode test voltage: 2.5 kVDifferential test voltage: 1.0 kV

    Test duration: > 2 s, source impedance: 200

    Immunity to Electrostatic DischargePer EN 60255-22-2

    or IEC 60255-22-2, severity level 3.

    Contact discharge, single discharges: > 10Holding time: > 5 sTest voltage: 6 kV

    Test generator: 50 to 100 M, 150 pF / 330

    Immunity to Radiated Electromagnetic Energy

    Per EN 61000-4-3

    and ENV 50204

    , severity level 3.Antenna distance to tested device: > 1 m on all sidesTest field strength, frequency band 80 to 1000 MHz: 10 V / mTest using AM: 1 kHz / 80 %Single test at 900 MHz AM 200 Hz / 100 %

    _______________________________________________________________

    For this EN, ENV or IEC standard, the DIN EN, DINV ENV or DIN IEC edition,

    respectively, was used in the test.

  • 7/31/2019 P63X

    23/525

    2 Technical Data(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 2-3

    Electrical Fast Transient or Burst RequirementsPer EN 61000-4-4

    or IEC 60255-22-4, severity levels 3 and 4.

    Rise time of one pulse: 5 ns,Impulse duration (50% value): 50 ns,Amplitude: 2 kV / 1 kV or 4 kV / 2 kVBurst duration: 15 ms,Burst period: 300 msBurst frequency: 5 kHz or 2.5 kHz

    Source impedance: 50

    Current/Voltage Surge Immunity TestPer EN 61000-4-5

    or IEC 61000-4-5, insulation class 4.

    Testing of circuits for power supply and unsymmetrical or symmetrical lines.

    Open-circuit voltage, front time / time to half-value: 1.2 / 50 sShort-circuit current, front time / time to half-value: 8 / 20 sAmplitude: 4 / 2 kV,Pulse frequency: > 5 / min

    Source impedance: 12 / 42

    Immunity to Conducted Disturbances Induced by Radio Frequency FieldsPer EN 61000-4-6

    or IEC 61000-4-6, severity level 3.

    Test voltage: 10 V

    Power Frequency Magnetic Field ImmunityPer EN 61000-4-8

    or IEC 61000-4-8, severity level 4.

    Frequency: 50 Hz

    Test field strength: 30 A / m

    Alternating Component (Ripple) in DC Auxiliary Energizing QuantityPer IEC 255-11.12 %

    InsulationVoltage TestPer EN 61010-1

    or IEC 255-5.

    2 kV AC, 60 sDirect voltage (2.8 kV DC) must be used for the voltage test of the power supply inputs.The PC interface must not be subjected to the voltage test.

    Impulse Voltage Withstand TestPer IEC 255-5Front time: 1.2 sTime to half-value: 50 sPeak value: 5 kV

    Source impedance: 500

  • 7/31/2019 P63X

    24/525

    2 Technical Data(continued)

    2-4 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    Mechanical robustnessVibration TestPer EN 60255-21-1

    or IEC 255-21-1, test severity class 1.

    Frequency range in operation: 10 to 60 Hz, 0.035 mm, 60 to 150 Hz, 0.5 gFrequency range during transport: 10 to 150 Hz, 1 g

    Shock Response and Withstand Test, Bump TestPer EN 60255-21-2

    or IEC 255-21-2, test severity class 1.

    Acceleration: 5 g / 15 gPulse duration: 11 ms

    Seismic TestPer EN 60255-21-3

    , test procedure A, class 1

    Frequency range:5 to 8 Hz, 3.5 mm / 1.5 mm, 8 to 35 Hz, 10 / 5 m/s2, 3 1 cycle

    2.1.2 Routine Tests

    All tests per EN 60255-6

    or IEC 255-6.and DIN 57435 part 303

    Voltage TestPer IEC 255-5.2.5 kV AC, 1 s.Direct voltage (2.8 kV DC) must be used for the voltage test of the power supply inputs.The PC interface must not be subjected to the voltage test.

    Additional Thermal Test100% controlled thermal endurance test, inputs loaded.

    2.4 Climatic Conditions

    EnvironmentTemperaturesRecommended temperature range: -5C to +55C or +23F to +131F.Limit temperature range: -25C to +70C or -13F to +158F.

    Humidity

    75 % relative humidity (annual mean),

    56 days at 95 % relative humidity and 40C or 104F, condensation not permissible.

    Solar RadiationDirect solar radiation on the front of the device must be avoided.

  • 7/31/2019 P63X

    25/525

    2 Technical Data(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 2-5

    2.5 Inputs and Outputs

    Measurement inputsCurrentNominal current: 1 or 5 A AC (adjustable).Nominal consumption per phase: < 0.1 VA at InomLoad rating:continuous: 4 Inomfor 10 s: 30 Inomfor 1 s: 100 InomNominal surge current: 250 Inom

    Voltage

    Nominal voltage Vnom: 50 to 130 V AC (adjustable)Nominal consumption per phase: < 0.3 VA at Vnom = 130 V AC

    Load rating: continuous 150 V AC

    FrequencyNominal frequency fnom: 50 Hz and 60 Hz (adjustable)

    Frequency protection function:Operating range: 40 to 70 Hz

    All other protection functions:Operating range: 0.95 to 1.05 fnom.

    Binary signal inputsNominal voltage Vin,nom: 24 to 250 V DC.

    Operating range: 0.8 to 1.1 Vin,nom with a residual ripple of up to 12 % Vin,nomPower consumption per input:Vin = 19 to 110 V DC: 0.5 W 30 %,

    Vin > 110 V DC: 5 mA 30 %.

    Direct current inputInput current: 0 to 26 mAValue range: 0.00 to 1.20 IDC,nom (IDC,nom = 20 mA)Maximum permissible continuous current: 50 mAMaximum permissible input voltage: 17 V

    Input load: 100 Open-circuit monitoring: 0 to 10 mA (adjustable)Overload monitoring: > 24.8 mAZero suppression: 0.000 to 0.200 IDC,nom (adjustable)

    Resistance thermometerResistance thermometer: only PT 100 permitted,Mapping curve per IEC 751

    .

    Value range: -40.0C to +215.0C (-40F to +419F)

    3-wire configuration: max. 20 per conductor.Open and short-circuited input permitted

    Open-circuit monitoring: > +215C and < -40C ( > +419F and < -40F)

  • 7/31/2019 P63X

    26/525

    2 Technical Data(continued)

    2-6 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    Output relaysRated voltage: 250 V DC, 250 V ACContinuous current: 5 AShort-duration current: 30 A for 0.5 sMaking capacity: 1000 W (VA) at L/R = 40 msBreaking capacity: 0.2 A at 220 V DC and L/R = 40 ms

    4 A at 230 V AC and cos = 0.4

    BCD-coded measured dataoutput

    Maximum numerical value that can be displayed: 399

    Analog measured data

    outputValue range: 0 to 20 mA

    Permissible load: 0 to 500 Maximum output voltage: 15 V

    2.6 Interfaces

    Local control panelInput or output:via seven keys and a LCD display of 4 x 20 characters

    State and fault signals:17 LED indicators (4 permanently assigned, 13 freely configurable)

    PC interfaceTransmission rate: 300 to 115 200 baud (adjustable)

    Communication interfaceSettable communications protocols:Per IEC 60870-5-103, IEC 870-5-101, MODBUS and DNP 3.0 (user selection)

    Wire LeadsPer RS 485 or RS 422, 2 kV isolationDistance to be bridged:Point-to-point connection: max. 1.200 mMultipoint connection: max. 100 m

    Module Transmission Rate Communication Protocol

    A 0336 426 300 to 19,200 baud (adjustable) IEC 60870-5-103

    A 9650 356 300 to 64,000 baud (adjustable) adjustable

  • 7/31/2019 P63X

    27/525

    2 Technical Data(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 2-7

    Plastic Fiber ConnectionOptical wavelength: typically 660 nmOptical output: min. 7.5 dBmOptical sensitivity: min. -20 dBmOptical input: max. -5 dBmDistance to be bridged:

    1)max. 45 m

    Module Transmission Rate Communication Protocol

    A 0336 428 300 to 38,400 baud (adjustable) IEC 60870-5-103

    A 9650 355 300 to 64,000 baud (adjustable) adjustable

    Glass Fiber Connection G 50/125Optical wavelength: typically 820 nmOptical output: min. -19.8 dBmOptical sensitivity: min. -24 dBmOptical input: max. -10 dBmDistance to be bridged:

    1)max. 400 m

    Module Transmission Rate Communication Protocol

    A 9650 107 300 to 38,400 baud (adjustable) IEC 60870-5-103

    A 9650 354 300 to 64,000 baud (adjustable) adjustable

    Glass Fiber Connection G 62.5/125Optical wavelength: typically 820 nmOptical output: min. -16 dBmOptical sensitivity: min. -24 dBmOptical input: max. -10 dBmDistance to be bridged:

    1)max. 1400 m

    Module Transmission Rate Communication Protocol

    A 9650 107 300 to 38,400 baud (adjustable) IEC 60870-5-103

    A 9650 354 300 to 64,000 baud (adjustable) adjustable

    IRIG-B interfaceB122 formatAmplitude-modulated1 kHz carrier signalBCD time-of-year code

    ____________________________________________________________________

    1)

    Distance to be bridged given identical optical outputs and inputs at both ends,a system reserve of 3 dB, and typical fiber attenuation.

  • 7/31/2019 P63X

    28/525

    2 Technical Data(continued)

    2-8 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    2.7 Information Output

    Counters, measured data, signals and indications: see Address List

    2.8 Settings

    Typical characteristic dataMain FunctionMinimum output pulse for a trip command: 0.1 to 10 s (adjustable)

    Differential ProtectionOperating time at Id = 10Idiff> with harmonic blocking disabled or at Id > Idiff>>>:

    min. 13 ms / typ. 15 ms

    Operating time at Id = 2.5Idiff> with harmonic blocking disabled:min. 19 ms / typ. 21 ms

    Operating time at Id = 2.5Idiff> with harmonic blocking enabled:min. 30 ms / typ. 33 ms

    Definite-Time and Inverse-Time Overcurrent ProtectionOperate time including output relay (measured variable from 0 to 2-fold operate value):

    40 ms, approx. 30 msRelease time (measured variable from 2-fold operate value to 0):

    40 ms, approx. 30 msDisengaging ratio for starting: approx. 0.95

    2.9 Deviations

    2.9.1 Deviations of the Operate Values

    DefinitionsReference Conditions

    Sinusoidal signals at nominal frequency fnom, total harmonic distortion 2 %, ambient

    temperature 20 C (68F), and nominal auxiliary voltage VA,nom.

    DeviationDeviation relative to the setting under reference conditions.

    Differential protectionMeasuring System

    Deviation for Idiff 0.2 Iref: 5 %

    Inrush StabilizationDeviation: 10 %

    Ground differentialprotection

    Measuring System

    Deviation for Idiff 0.2 Iref: 5 %

  • 7/31/2019 P63X

    29/525

    2 Technical Data(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 2-9

    Definite-time and inverse-time overcurrent protection

    Deviation: 5 %

    Thermal overloadprotection

    Deviation: 5 %

    Frequency protectionDeviation: 3 %

    Voltage protectionDeviation: 3 %

    Direct current inputDeviation: 1 %

    Resistance thermometerDeviation: 2 or 1 %

    Analog measured dataoutput

    Deviation: 1 %Output residual ripple for max. load: 1 %

    2.1.2 Deviations of the Timer Stages

    DefinitionsReference Conditions

    Sinusoidal signals at nominal frequency fnom, total harmonic distortion 2 %, ambienttemperature 20 C (68F), and nominal auxiliary voltage VA,nom.

    DeviationDeviation relative to the setting under reference conditions.

    Definite-time stages

    Deviation: 1 % + 20 to 80 msSoftware version -603 and up:

    Deviation: 1 % + 20 to 40 ms

    Inverse-time stages

    Deviation for I 2 Iref: 5 % +10 to 25 ms

    For IEC characteristic extremely inverse: 7.5 % +10 to 20 ms

    Limit value monitoringstages

    Limit Value Monitoring is not a fast protection function and is intended to be used forsignalling purposes. This function is processed about once a second only, hence it is notpossible to make meaningful accuracy claims.

  • 7/31/2019 P63X

    30/525

    2 Technical Data(continued)

    2-10 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    2.9.3 Deviations of Measured Data Acquisition

    DefinitionsReference Conditions

    Sinusoidal signals at nominal frequency fnom, total harmonic distortion 2 %, ambienttemperature 20 C, and nominal auxiliary voltage VA,nom.

    DeviationDeviation relative to the corresponding nominal value under reference conditions.

    Operating datameasurement

    Measuring Input Currents

    Deviation: 1 %

    Measuring Input VoltageDeviation: 0.5 %

    Restraining and Differential Currents Formed InternallyDeviation: 2 %

    FrequencyDeviation: 10 mHz

    Direct Current of Measured Data Input and OutputDeviation: 1 %

    TemperatureDeviation: 2 C

    Fault data acquisitionShort-Circuit Current and VoltageDeviation: 3 %

    Restraining and Differential CurrentsDeviation: 5 %

    Internal clockWith free running internal clock:Deviation: < 1min/month

    With external synchronization (with a synchronization interval 1 min):Deviation: < 10 ms

  • 7/31/2019 P63X

    31/525

    2 Technical Data(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 2-11

    2.10 Recording Functions

    Organization of the Recording Memories

    Operating data memoryScope: All operation-relevant signals from a total of 1024 different logic

    state signals (see Address List: "Operating Data Memory")Depth: The 100 most recent signals

    Monitoring signal memoryScope: All signals relevant for self-monitoring from a total of 1024 different

    logic state signals (see Address List: "Monitoring Signal Memory")Depth: Up to 30 signals

    Overload memoryNumber: The 8 most recent overload eventsScope: All signals relevant for an overload event from a total of 1024 different

    logic state signals (see Address List: "Overload Memory")Depth: 200 entries per overload event

    Fault memoryNumber: The 8 most recent faults

    Scope: Signals:All fault-relevant signals from a total of 1024 different logic state signals(see Address List: "Fault Memory")

    Fault Values:Sampled values for all measured currents and voltages

    Depth: Signals:200 entries per fault

    Fault Values:max. number of periods per fault can be set by user; a total of820 periods for all faults, i.e., 16.4 s (for fnom = 50 Hz) or13.7 s (for fnom = 60 Hz)

    Resolution of the Recorded Data

    SignalsTime resolution: 1 ms

    Fault valuesTime resolution: 20 sampled values per period

    Phase currentsDynamic range: 33 InomAmplitude resolution: 2 mA r.m.s. for Inom = 1 A

    10.1 mA r.m.s. for Inom = 5 A

    Voltages Dynamic range: 150 V ACAmplitude resolution: 9.2 mV r.m.s

  • 7/31/2019 P63X

    32/525

    2 Technical Data(continued)

    2-12 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    2.11 Power supply

    Power supplyNominal auxiliary voltage VA,nom:

    24 V DC or 48 to 250 V DC and 100 to 230 V AC (per order)

    Operating range for direct voltage:0.8 to 1.1 VA,nom with a residual ripple of up to 12 % VA,nom

    Operating range for alternating voltage: 0.9 to 1.1 VA,nom

    Nominal consumption where VA = 220 V DC and maximum module configuration

    For case 40 T 84 TInitial position approx.: 12.6 W 14.5 W

    Active position approx.: 34.1 W 42.3 W

    Start-up peak current: < 3 A for duration of 0.25 ms

    Stored energy time: 50 ms for interruption of VA 220 V DC

  • 7/31/2019 P63X

    33/525

    2 Technical Data(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 2-13

    2.12 Dimensioning of Current Transformers

    The following equation is used for dimensioning a current transformer to the offsetmaximum primary current:

    ( ) ( ) ' max1,iopnominomsat IkRRInRRV ++=

    where:

    satV : saturation voltage

    I1,max' : non-offset maximum primary current, converted to the secondary side

    Inom: rated secondary current

    n: rated overcurrent factor k: overdimensioning factor

    Rnom: rated burden

    :Rop actual connected operating burden

    Ri: internal burden

    The current transformer can then be dimensioned for the minimum required saturation

    voltage satV as follows:

    ( ) ' max1,iopsat IkRRV +

    Alternatively, the current transformer can also be dimensioned for the minimum requiredrated overcurrent factor n by specifying a rated power Pnom as follows:

    ( )( )

    ( )( ) nom

    'max1,

    inom

    iop

    nom

    'max1,

    inom

    iop

    I

    Ik

    PP

    PP

    I

    Ik

    RR

    RRn

    +

    +=

    +

    +

    where

    2

    nomii

    2nomopop

    2nomnomnom

    IRP

    IRP

    IRP

    =

    =

    =

    Theoretically, the current transformer could be dimensioned for lack of saturation byinserting in the place of the required overdimensioning factor k its maximum:

    k Tmax +1 1

    where:: system angular frequency

    T1: system time constant

  • 7/31/2019 P63X

    34/525

    2 Technical Data(continued)

    2-14 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    However, this is not necessary. Instead, it is sufficient to dimension the overdimensioningfactor k such that the normal behavior of the analyzed protective function is guaranteedunder the given conditions.

    The transformer differential protection device is equipped with a saturation discriminator.This function will generate a stabilizing blocking signal if a differential current occurs as aconsequence of transformer saturation with an external fault (in contrast to an internalfault). For the passing maximum fault current in the case of an external fault,overdimensioning is, therefore, obviated.

    For the maximum fault current with an internal fault, static saturation up to a maximumsaturation factor fS of 4 is permissible. This corresponds to an overdimensioning factor kof 0.25.

    The implementation of these requirements is comparitively unproblematic as transformerdifferential protection would require overdimensioning in accordance with the total faultclearing time, that is including the total circuit-breaker-open time for an external fault.

    The current transformers should comply with the fault tolerance values of class 5P.

  • 7/31/2019 P63X

    35/525

    3 Operation

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06660 EN 3-1

    3 Operation

    3.1 Modular Structure

    The P63x, a numerical protection device, is one of the units of instrumentation in theMiCOM P 30 product range. The devices that are part of this range are built fromidentical uniform hardware modules. Figure 3-1 shows the basic hardware structure ofthe P63x.

    3-1 Basic hardware structure

  • 7/31/2019 P63X

    36/525

    3 Operation(continued)

    3-2 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06660 EN

    The external analog and binary quantities electrically isolated are converted to theinternal processing levels by the peripheral modules T, Y and X. Commands and signalsgenerated by the device internally are transmitted to external destinations via floatingcontacts through the binary I/O modules X. The external auxiliary voltage is applied tothe power supply module V which supplies the auxiliary voltages that are requiredinternally.

    Analog data are always transferred from the transformer module T via the analog busmodule B to the processor module P. The processor module contains all the elementsnecessary for the conversion of measured analog variables, including multiplexers andanalog/digital converters. The analog data conditioned by the analog I/O module Y aretransferred to the processor module P via the digital bus module. Binary signals are fedto the processor module by the binary I/O modules X via the digital bus module. The

    processor handles the processing of digitized measured variables and of binary signals,generates the protective trip and signals and transfers them to the binary I/O modules Xvia the digital bus module. Moreover, the entire device communication is handled by theprocessor module. As an option, communication module A can be mounted on theprocessor module to provide serial communication with substation control systems.

    The control and display elements of the integrated local control panel and the integratedPC interface are housed on control module L.

  • 7/31/2019 P63X

    37/525

    3 Operation(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06660 EN 3-3

    3.2 Operator-Machine Communication

    The following interfaces are available for the exchange of information between operatorand device:

    Integrated local control panel

    PC interface

    Communication interface

    All setting parameters and signals as well as all measured variables and control functionsare arranged within the branches of the menu tree following a scheme that is uniformthroughout the device family. The main branches are:

    Parameters branchThis branch carries all setting parameters, including the device identification data, theconfiguration parameters for adapting the device interfaces to the system, and thefunction parameters for adapting the device functions to the process. All values in thisgroup are stored in non-volatile memory, which means that the values will be preservedeven if the power supply fails.

    Operation branchThis branch carries all information relevant for operation such as measured operatingdata and binary signal states. This information is updated periodically and consequentlyis not stored. In addition, various control parameters are grouped here, for examplethose for resetting counters, memories and displays.

    Events branchThe third branch is reserved for the recording of events. Therefore all informationcontained in this group is stored. In particular, the start/end signals during a fault, themeasured fault data, and the sampled fault records are stored here and can be read outat a later time.

    Settings and signals are displayed either in plain text or as addresses, in accordance withthe users choice. The appendix documents the settings and signals of the P63x in theform of an address list. This address list is complete and thus contains all settings,signals and measured variables used with the P63x.

    The configuration of the local control panel moreover allows the installation of MeasuredValue Panels on the LCD display. Different panels are automatically displayed for certainoperation conditions of the system. Priority increases from normal operation to operationunder overload conditions and finally to operation following a short-circuit in the system.The P63x thus provides the measured data relevant for the prevailing conditions.

  • 7/31/2019 P63X

    38/525

    3 Operation(continued)

    3-4 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06660 EN

    3.3 Configuration of the Measured Value Panels (Function Group LOC)

    The P63x offers Measured Value Panels which display the measured values relevant at agiven time.

    During normal power system operation, the Operation Panel is displayed. As an eventoccurs, the display switches to the appropriate Event Panel - provided that measuredvalues have been selected for the Event Panels. In the event of overload event, thedisplay will automatically switch to the Operation Panel at the end of the event. In theevent of a fault, the Fault Panel remains active until the LED indicators or the faultmemories are reset.

    Operation Panel

    The Operation Panel is displayed after the set return time has elapsed, provided that atleast one measured value has been configured.

    From the measured operating data, values may be selected via an 'm out of n' parameterfor display on the Operation Panel. If more measured values are selected for displaythan the LC display can accommodate, then the display will switch to the next set ofvalues at intervals defined by the setting at L O C : H o l d - t i m e f o r Pa n e l s or whenthe appropriate key on the local control panel is pressed.

    3-2 Operation Panel

  • 7/31/2019 P63X

    39/525

    3 Operation(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06660 EN 3-5

    Fault panelThe Fault Panel is displayed in place of another data panel when there is a fault, providedthat at least one measured value has been configured. The Fault Panel remains ondisplay until the LED indicators or the fault memories are reset.

    The user can select the measured fault values that will be displayed on the Fault Panel bysetting an 'm out of n' parameter. If more measured values are selected for display thanthe LC display can accommodate, then the display will switch to the next set of values atintervals defined by the setting at L O C : H o l d - t i m e f o r Pa n e l s or when theappropriate key on the local control panel is pressed.

    3-3 Fault panel

  • 7/31/2019 P63X

    40/525

    3 Operation(continued)

    3-6 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06660 EN

    Overload panelThe Overload Panel is automatically displayed in place of another data panel when thereis an overload, provided that at least one measured value has been configured. TheOverload Panel remains on display until the overload ends, unless a fault occurs. In thiscase the display switches to the Fault Panel.

    The user can select the measured values that will be displayed on the Overload Panel bysetting an 'm out of n' parameter. If more measured values are selected for display thanthe LC display can accommodate, then the display will switch to the next set of values atintervals defined by the setting at L O C : H o l d - t i m e f o r P a n e l s or when theappropriate key on the local control panel is pressed.

    3-4 Overload Panel

  • 7/31/2019 P63X

    41/525

    3 Operation(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06660 EN 3-7

    3.4 Serial Interfaces

    The P63x has a PC interface as standard component. The communication interface isoptional. Setting and readout is possible through both P63x interfaces.

    If tests are run on the P63x, the user is advised to activate the test mode so that the PCor the control system will evaluate all incoming signals accordingly (see GeneralFunctions).

    3.4.1 PC Interface (Function Group PC)

    Communication between the device P63x and a PC is through the PC interface. In orderfor data transfer between the P63x and the PC to function, several settings must be

    made in the P63x.

    The S&R-103 Operating Program is available as an accessory for P63x control (see theChapter entitled Accessories).

  • 7/31/2019 P63X

    42/525

    3 Operation(continued)

    3-8 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06660 EN

    3-5 PC interface settings

  • 7/31/2019 P63X

    43/525

    3 Operation(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06660 EN 3-9

    3.4.2 Communication Interface (Function Group COMM1)

    Communication between the P63x and the control stations computer is through thecommunication interface. Depending on the design version of the communicationmodule A (see Technical Data), several interface protocols are available. The protocolas per IEC 60870-5-103 is supported for all versions. The following user-selectedinterface protocols are available for use with the P63x:

    IEC 60870-5-103, Transmission protocols - Companion standard for the informativeinterface of protection equipment, first edition, 1997-12 (corresponds to VDEW / ZVEIRecommendation, Protection communication companion standard 1, compatibilitylevel 2, February 1995 edition) with additions covering control and monitoring

    IEC 870-5-101, Telecontrol equipment and systems - Part 5: Transmissionprotocols - Section 101 Companion standard for basic telecontrol tasks, first edition1995-11

    ILS-C, internal protocol of AREVA

    MODBUS

    DNP 3.0

    In order for data transfer to function properly, several settings must be made in the P63x.

    The communication interface can be blocked through a binary signal input. In addition, asignal or measured-data block can also be imposed through a binary signal input.

  • 7/31/2019 P63X

    44/525

    3 Operation(continued)

    3-10 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06660 EN

    3-6 Selecting the interface protocol

  • 7/31/2019 P63X

    45/525

    3 Operation(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06660 EN 3-11

    3-7 Settings for the IEC 60870-5-103 interface protocol

  • 7/31/2019 P63X

    46/525

    3 Operation(continued)

    3-12 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06660 EN

    3-8 Settings for the IEC 870-5-101 interface protocol

  • 7/31/2019 P63X

    47/525

    3 Operation(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06660 EN 3-13

    3-9 Settings for the ILS_C interface protocol

  • 7/31/2019 P63X

    48/525

    3 Operation(continued)

    3-14 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06660 EN

    3-10 Settings for the MODBUS protocol

  • 7/31/2019 P63X

    49/525

    3 Operation(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06660 EN 3-15

    3-11 Settings for the DNP 3.0 protocol

  • 7/31/2019 P63X

    50/525

    3 Operation(continued)

    3-16 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06660 EN

    3.5 Time Synchronization via the IRIG-B Interface (Function Group IRIGB)

    If, for example, a GPS receiver with IRIG-B connection is available, the internal clock ofthe P63x can be synchronized to run on GPS time using the optional IRIG-B interface. Itshould be noted that the IRIG-B signal holds information on the day only (day of thecurrent year). Using this information and the year set at the P63x, the P63x calculatesthe current date (DD.MM.YY).

    Disabling or enabling theIRIG-B interface

    The IRIG-B interface can be disabled or enabled from the local control panel.

    Ready to synchronizeIf the IRIG-B interface is enabled and receiving a signal, the P63x checks the receivedsignal for plausibility. Implausible signals are rejected by the P63x. If the P63x does notreceive a correct signal in the long run, synchronization will not be ready any longer.

    3-12 IRIG-B-interface

  • 7/31/2019 P63X

    51/525

    3 Operation(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06660 EN 3-17

    3.6 Configuration and Operating Mode of the Binary Inputs (Function Group INP)

    The P63x has optical coupler inputs for the processing of binary signals from thesubstation. The functions that will be activated by triggering these binary signal inputsare defined by the configuration of the binary signal inputs. The trigger signal mustpersist for at least 30 ms in order to be recognized by the P63x.

    Configuration of the binaryinputs

    To each binary signal input, a function can be assigned by configuration. The samefunction can be assigned to several signal inputs. Thereby, a function can be activatedfrom several control points with differing signal voltages.

    In this manual, we assume that the required functions (marked EXT in the addressdescription) have been assigned to binary signal inputs by configuration.

    Operating mode of thebinary inputs

    For each binary signal input, the operating mode can be defined by the user. The usercan specify whether the presence (active high mode) or the absence (active lowmode) of a voltage should be interpreted as the logic 1 signal. The display of the stateof a binary signal input low or high is independent of the setting for the operatingmode of the signal input.

    3-13 Configuration and operating mode of the binary signal inputs

  • 7/31/2019 P63X

    52/525

    3 Operation(continued)

    3-18 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06660 EN

    3.7 Measured Data Input (Function Group MEASI)

    The P63x has a measured data input function involving two inputs. Direct current is fedto the P63x through one of the inputs. The other input is designed for connection of aresistance thermometer.

    The input current IDC is displayed as a measured operating value. The current that isconditioned for monitoring purposes (IDClin) is also displayed as a measured operatingvalue. In addition, it is monitored by the limit value monitoring function to detect whetherit exceeds or falls below set thresholds (see Limit Value Monitoring).

    The measured temperature is also displayed as a measured operating value andmonitored by the limit value monitoring function to detect whether it exceeds or falls

    below set thresholds (see Limit Value Monitoring).

    Disabling and enablingmeasured data input

    The measured data input function can be disabled or enabled from the local controlpanel.

    3-14 Disabling and enabling the measured data input function

  • 7/31/2019 P63X

    53/525

    3 Operation(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06660 EN 3-19

    3.7.1 Direct Current Input

    External measuring transducers normally supply an output current of 0 to 20 mA that isdirectly proportional to the physical quantity being measured the temperature, forexample. If the output current of the measuring transducer is directly proportional to themeasured quantity only in certain ranges, linearization can be arranged - provided thatthe measured data input is set accordingly. Furthermore, it may be necessary for certainapplications to limit the range being monitored or to monitor certain parts of the rangethat have a higher or lower sensitivity. By setting the value pair M E A S I : I D C x andM E AS I : I D C l i n x , the user specifies which input current (IDC) will correspond to thecurrent that is monitored by the limit value monitoring function (IDC,lin). The pointsdetermined in this way, which are called interpolation points, are connected by straightlines in an IDC-IDClin diagram. In order to implement a simple characteristic, it is sufficient

    to specify two interpolation points, which are also used as limiting values (Figure 3-15).Up to 20 interpolation points are available for implementing a complex characteristic.

    When setting the characteristic the user must remember that only a monotone ascendingcurve is allowed. If the setting differs, the signal S F M O N : I n v a l i d s c a l i n g I D Cwill be generated.

    0

    0.1

    0.2

    0.3

    0.4

    0.5

    0.6

    0.7

    0.8

    0.9

    1

    1.1

    1.2

    0 0.1 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.6 IDC / IDC,nom

    IDClin / IDC,nom

    IDC1 IDC20

    IDClin1

    IDClin20

    D5Z52KDA

    3-15 Example of the conversion of 4-10 mA input current to 0-20 mA monitored current, IDClin

  • 7/31/2019 P63X

    54/525

    3 Operation(continued)

    3-20 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06660 EN

    0

    0.1

    0.2

    0.3

    0.4

    0.5

    0.6

    0.7

    0.8

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2

    IDC / IDC,nom

    IDClin / IDC,nom

    D5Z52KEA

    IDC1 IDC2 IDC3 IDC4 IDC20

    IDClin1

    IDClin2

    IDClin3

    IDClin4

    IDClin20

    Interpolation points

    Enable IDC p.u.

    3-16 Example of a characteristic having five interpolation points (characteristic with zero suppression setting of 0.1 IDC,nom is shown as abroken line)

    Zero suppressionZero suppression is defined by setting M E A S I : E n a b l e I D C p . u . If the directcurrent does not exceed the set threshold, the per-unit input current IDC p.u. and the

    current IDClin will be displayed as having a value of 0.

    Open-circuit and overloadmonitoring

    The device is equipped with an open-circuit monitoring function. If current IDC falls belowthe set threshold, the signal M E A S I : O p e n c i r c . 2 0 m A i n p . is issued.

    The input current is monitored in order to protect the 20 mA input against overloading. Ifit exceeds the fixed threshold of 24.8 mA, the signal M E A S I : O v e r l o a d 2 0 m Ai n p u t is issued.

  • 7/31/2019 P63X

    55/525

    3 Operation(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06660 EN 3-21

    3-17 Analog direct current input

  • 7/31/2019 P63X

    56/525

    3 Operation(continued)

    3-22 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06660 EN

    Beyond the linearization described above, the user has the option of scaling thelinearized values. Thereby negative values, for example, can be displayed as well andare available for further processing by protection functions.

    3-18 Scaling of the linearized measured value

    3.7.2 Input for Connection of a Resistance Thermometer

    This input is designed for connection of a PT 100 resistance thermometer. The mappingcurve R = f(T) of PT 100 resistance thermometers is defined in DIN IEC 751. If thePT 100 is connected using the 3-wire method, then no further calibration is required.

    Open-circuit monitoringIf there is an open measuring circuit due to wire breakage, the signal M E A SI : P T 1 0 0faulty is generated.

    3-19 Temperature measurement using resistance thermometer

  • 7/31/2019 P63X

    57/525

    3 Operation(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 3-23

    3.8 Configuration, Operating Mode and Blocking of the Output Relays(Function Group OUTP)

    The P63x has output relays for the output of binary signals. The binary signals to beissued are defined by configuration.

    Configuration of the outputrelays

    One binary signal can be assigned to each output relay. The same binary signal can beassigned to several output relays by configuration.

    Operating mode of theoutput relays

    The user can set an operating mode for each output relay. The operating modedetermines whether the output relay will operate in an energize-on-signal (ES) mode ornormally-energized (NE) mode and whether it will operate in latching mode.

    Depending on the I/O module under consideration, the output relays have either make

    contacts, changeover contacts or both (see the Terminal Connection Diagrams in the

    Appendix). For relays with make contacts, the energize-on-signal (ES) mode

    corresponds to normally-open operation. The normally-energized (NE) mode means that

    the polarity of the driving signal is inverted, such that a logic "0" maintains the relay

    normally-closed. For relays with changeover contacts, these more common descriptions

    are not applicable.

    Latching is disabled manually from the local control panel or through an appropriatelyconfigured binary signal input either at the onset of a new fault or at the onset of a newsystem disturbance, depending on the operating mode selected.

    Blocking the output relaysThe P63x offers the option of blocking all output relays from the local control panel or byway of an appropriately configured binary signal input. The output relays are likewiseblocked if the device is disabled via appropriately configured binary inputs.

    In these cases, the relays are treated in keeping with their set operating mode. Relays innormally-energized (NE) mode are triggered, those in energize-on-signal (ES) mode arenot.

    This does not apply to relays with the signals SF MO N: W ar ning (r el ay ) or MA IN :Blocked/fault y assigned to them. Thereby the blocking is signalled correctly.(The signal MA IN : Bl oc ked /f au lt y is coupled to the activation of the LED labeled'OUT OF SERVICE'.)

    If, on the other hand, the self-monitoring function detects a serious hardware fault (seeChapter 10 for signals leading to protection blocking), all output relays are resetirrespective of the set operating mode or signal assignment.

  • 7/31/2019 P63X

    58/525

    3 Operation(continued)

    3-24 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    3-20 Configuration, operating mode and blocking of the output relays

  • 7/31/2019 P63X

    59/525

    3 Operation(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 3-25

    Testing the output relaysFor testing purposes, the user can select an output relay and trigger it via the local controlpanel. Triggering persists while the set hold time is running.

    3-21 Testing the output relays

  • 7/31/2019 P63X

    60/525

    3 Operation(continued)

    3-26 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    3.9 Measured Data Output (Function Group MEASO)

    Output of the measured fault or ground fault data provided by the P63x can be inBCD-coded form through output relays or in analog form as direct current. Output asdirect current can only occur if the device is equipped with analog I/O module Y. BCD-coded output, however, is possible, regardless of whether the device is equipped withanalog I/O module Y or not.

    Disabling and enabling themeasured data outputfunction

    The measured data output function can be disabled or enabled from the local controlpanel.

    3-22 Disabling and enabling the measured data output function

  • 7/31/2019 P63X

    61/525

    3 Operation(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 3-27

    Enabling measured dataoutput

    Measured data output can be enabled through a binary signal input, provided that thefunction MEASO: Outp. enabled EXT has been configured. If the functionM E A S O : O u t p . e n a b l e d E X T has not been configured for a binary signal input,then measured data output is always enabled.

    3-23 Enabling measured data output

  • 7/31/2019 P63X

    62/525

    3 Operation(continued)

    3-28 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    Resetting the measureddata output function

    BCD-coded or analog output of measured data is terminated while the hold time elapsesif one of the following conditions is met:

    The measured data output function is reset from the local control panel or through anappropriately configured binary signal input.

    There is a general reset.

    The LED indicators have been reset.

    3-24 Resetting the measured data output function

  • 7/31/2019 P63X

    63/525

    3 Operation(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 3-29

    3.9.1 BCD-Coded Measured Data Output

    The user can select a measured value for output in BCD-coded form through outputrelays.

    The selected measured value is output in BCD-coded form for the duration of the set holdtime (ME A S O : H o l d t i m e o u t p u t B C D . If the selected variable was notmeasured, then there is no output of a measured value.

    Output of measured eventvalues

    If the measured event value is updated while the hold time is elapsing, the measuredvalue output memory is cleared and the hold time is re-started. This means that theupdated value is immediately output.

    Output of measuredoperating values

    The measured operating value is output for the duration of the hold time. After the holdtime has elapsed, the current value is saved and the hold time is re-started. If the holdtime has been set to blocked, the measured operating value that has been output will bestored until the measured data output function is reset.

    ScalingThe resolution for measured data output is defined by setting the scaling factor. Thescaling factor should be selected so that the value 399 is not exceeded by the maximummeasured value to be output. If this should occur, however, or if the measured value isoutside the acceptable measuring range, then the value for Overflow (all relays

    triggered) is transmitted.

    factorscaling

    MM

    max,xscal,x =

    where:

    scal,xM : scaled measured value

    Mx,max : maximum transmitted value for the selected measured value

  • 7/31/2019 P63X

    64/525

    3 Operation(continued)

    3-30 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    3-25 BCD-coded measured data output

  • 7/31/2019 P63X

    65/525

    3 Operation(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 3-31

    3.9.2 Analog Measured Data Output

    Analog output of measured data is two-channel.

    The user can select two of the measured values available in the P63x for output in theform of load-independent direct current. Three interpolation points per channel can bedefined for specific adjustments such as adjustment to the scaling of a measuringinstrument. The direct current that is output is displayed as a measured operating value.

    The selected measured value is output as direct current for the duration of the set holdtime (ME A S O : H o l d t i m e ou t pu t A - x ) . If the selected variable was notmeasured, then there is no output of a measured value.

    Output of measured eventvalues

    If the measured event value is updated while the hold time is elapsing, the measuredvalue output memory is cleared and the hold time is re-started. This means that theupdated value is immediately output.

    Output of measuredoperating values

    The measured operating value is output for the duration of the hold time. After the holdtime has elapsed, the current value is saved and the hold time is re-started. If the holdtime has been set to blocked, the measured operating value that has been output will bestored until the measured data output function is reset.

    Configuration of outputrelays assigned to theoutput channels

    The user must keep in mind that direct current output only occurs when the output relaysassigned to the output channels are configured for M E A S O : V a l u e A - x o u t pu t ,since otherwise the output channels remain short-circuited (see terminal connectiondiagrams).

  • 7/31/2019 P63X

    66/525

    3 Operation(continued)

    3-32 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    ScalingThe minimum and maximum values to be transmitted for the selected measured valueand one additional value for the knee point must be scaled to the range limit value of themeasured value. By setting the following parameters the user can obtain an analogoutput characteristic like the one shown in Figure 3-26.

    M E A S O : S c a l e d m i n . v a l . A - x

    M E A S O : S c a l e d k n e e v a l . A - x

    M E A S O : S c a l e d m a x . v a l . A - x

    M E A S O : A n O u t m i n . v a l . A - x

    M E A S O : A n O u t k n e e p o i n t A - x

    M E A S O : A n O u t m a x . v a l . A - x

    The scaled values that need to be set can be calculated using the following formulas:

    Formulas Example

    Key to the Formulas:

    RL,xM : Range limit value of

    selected measured value

    min,xM : Minimum value to be

    transmitted for selectedmeasured value

    knee,xM : Knee point value to be

    transmitted for selectedmeasured value

    max,xM : Maximum value to be

    transmitted for selectedmeasured value

    min,scal,xM : Scaled minimum value

    knee,scal,x

    M : Scaled knee point value

    max,scal,xM : Scaled maximum value

    Let voltage V12 be selected as themeasured value to be transmitted. Let themeasuring range be 0 to 1.5 Vnom.

    When Vnom = 100 V, the range limit valuein the assumed example is 150 V.

    Range to be transmitted:0.02 to 1 Vnom = 2 to 100 V

    Knee point:0.1 Vnom = 10 V

    RL,x

    min,xmin,scal,x

    M

    MM = 013.0

    V150

    V2M min,scal,x ==

    RL,x

    knee,xknee,scal,x

    M

    MM = 067.0

    V150

    V10M knee,scal,x ==

    RL,x

    max,xmax,scal,x

    M

    MM = 67.0

    V150

    V100M max,scal,x ==

  • 7/31/2019 P63X

    67/525

    3 Operation(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 3-33

    By setting M E A S O : A n O u t m i n . v a l ue A - x , the user can specify the outputcurrent that will be output when values are smaller than or equal to the set minimummeasured value to be transmitted. The setting at M E A S O : A nO u t m ax . v a l . A -x defines the output current that is output for the maximum measured value to betransmitted. By defining the knee point, the user can obtain two characteristic curvesections with different slopes. When making this setting the user must keep in mind thatonly a monotone ascending or a monotone descending curve is allowed. If the wrongsetting is entered, the signal S F MO N : I n v a l i d s c a l i n g A - x will be generated.

    Note:

    After this setting, the new characteristics will be checked and implemented after enablingat MAIN: Protection enabled.

    0

    2

    4

    6

    8

    10

    12

    14

    16

    18

    20

    0 0.02 0.1 1 1.2 1.3 1.4 1.5

    Ia / mA

    D5Z52KFA

    Min. output

    value

    Knee point

    output value

    Max.

    output value

    Mx,scal0.013 0.067 0.667

    Vnom

    3-26 Example of a characteristic curve for analog output of measured data

  • 7/31/2019 P63X

    68/525

    3 Operation(continued)

    3-34 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    3-27 Analog measured data output

  • 7/31/2019 P63X

    69/525

    3 Operation(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 3-35

    3.9.3 Output of External Measured Data

    Measured data from external devices, which must be scaled for 0-100%, can be writtento the following parameters of the P63x by way of the communications interface:

    M E A S O : O u t p u t v a l u e 1

    M E A S O : O u t p u t v a l u e 2

    M E A S O : O u t p u t v a l u e 3

    These "external" measured values are output by the P63x either in the form of BCD-coded data or as load-independent direct current, provided that the BCD-codedmeasured data output function or the channels of the analog measured data output

    function are configured accordingly.

  • 7/31/2019 P63X

    70/525

    3 Operation(continued)

    3-36 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    3.10 Configuration and Operating Mode of the LED Indicators(Function Group LED)

    The P63x has 17 LED indicators for the indication of binary signals. Five of the LEDindicators are permanently assigned to functions. The other LED indicators are freelyconfigurable. (However, LED indicator H4 has a default setting of Gen. tr ip signaland is labeled "Trip".)

    Configuration of the LEDindicators

    To each of the freely configurable LED indicators, a binary signal can be assigned. Thesame binary signal can be assigned to several LED indicators by configuration.

    Operating mode of the LEDindicators

    The user can set an operating mode for each LED indicator with the exception of thefirst one - that determines whether the LED indicator operates in an energize-on-signalarrangement (open-circuit principle) or normally-energized arrangement (closed-circuitprinciple) and whether it operates in latching mode. Latching is disabled either manuallyfrom the local control panel or by an appropriately configured binary signal input (seeMain Functions of the P63x), at the onset of a new fault or of a new system disturbance,depending on the operating mode selected.

  • 7/31/2019 P63X

    71/525

    3 Operation(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 3-37

    3-28 Configuration and operating mode of the LED indicators

  • 7/31/2019 P63X

    72/525

    3 Operation(continued)

    3-38 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    3.11 Main Functions of the P63x (Function Group MAIN)

    3.11.1 Conditioning of the Measured Variables

    The secondary phase currents of the system transformers are fed to the P63x.Furthermore, there is the option of connecting a measuring voltage. The measuredvariables are electrically isolated converted to normalized electronics levels. Theanalog quantities are digitized and are thus available for further processing. Dependingon the design version, the P63x has the following measuring inputs:

    P631:

    Current inputs (three phases) for the processing of measured variables for two ends

    of the transformer

    P632:

    Current inputs (three phases) for the processing of measured variables for two endsof the transformer

    Two current inputs for the measurement of the residual currents (see Figure 3-30)

    One voltage input

    P633 and P634:

    Current inputs (three phases) for the processing of measured variables for three

    (P633) or four (P634) ends of the transformer

    Current inputs for up to three neutral-point-to-ground connections (see Figure 3-29)or, alternatively, for looping into the ground connections of the phase currenttransformers or for connection to a Holmgreen group

    One voltage input

  • 7/31/2019 P63X

    73/525

    3 Operation(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 3-39

    3-29 Connection of the measured variables to the P63x, connection of the fourth current transformer set to the transformers of theneutral-point-to-ground connections

  • 7/31/2019 P63X

    74/525

    3 Operation(continued)

    3-40 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    3-30 a Connection of the measured variables to the P63x, looping of the fourth current transformer set into the ground connections of the phasecurrent transformers, Part 1 of 2

  • 7/31/2019 P63X

    75/525

  • 7/31/2019 P63X

    76/525

    3 Operation(continued)

    3-42 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    3.11.2 Selection of the Residual Current to be Monitored

    For protection functions of the P632, P633 and P634 monitoring the residual current, theuser can select whether the device is to use the current calculated from the three phasecurrents or the current measured at the fourth current transformer.

    Moreover, the P633 and P634 offer the option of forming the sum of the phase currentsor of the residual currents for two ends of the transformer.

  • 7/31/2019 P63X

    77/525

    3 Operation(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 3-43

    3-31 Evaluation of residual current

  • 7/31/2019 P63X

    78/525

    3 Operation(continued)

    3-44 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    3-32 Summation of the phase currents or of the residual currents

  • 7/31/2019 P63X

    79/525

    3 Operation(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 3-45

    3.11.3 Operating Data Measurement

    The P63x has an operating data measurement function for the display of currents andvoltages measured by the P63x during normal power system operation; quantitiesderived from these measured values are also displayed. For the display of measuredvalues, set lower thresholds need to be exceeded. If these lower thresholds are notexceeded, the value not measuredis displayed. The following measured variables aredisplayed:

    Phase currents of all three phases of all four ends of the transformer

    Maximum phase current of each end of the transformer

    Minimum phase current of each end of the transformer

    Delayed and stored maximum phase current of each end of the transformer

    Current IN calculated by the P63x from the sum of the phase currents for each end ofthe transformer

    Current IY measured by the P63x at transformer -Tx4 (x: 1, 2 or 3)

    Phase currents of all three phases of the virtual end of the transformer.The virtual end is formed by adding the corresponding currents of two transformerends selected by the user at MA IN : Cu rr en t su mmat io n.

    Maximum phase current of the virtual end of the transformer

    Minimum phase current of the virtual end of the transformer

    Current IN of the virtual end of the transformer Voltage

    Frequency

    Angle between the phase currents for a given end of the transformer

    Angle between the currents of the same phase between two ends of the transformer

    Angle between calculated IN and the current measured at transformer -Tx4(x: 1, 2 or 3)

    The measured data are updated at 1 s intervals. Updating is interrupted if a generalstarting state occurs or if the self-monitoring function detects a hardware fault.

  • 7/31/2019 P63X

    80/525

    3 Operation(continued)

    3-46 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    Measured current valuesThe measured values for the current are displayed both as quantities referred to thenominal current of the P63x and as primary quantities. To allow a display in primaryvalues, the primary nominal current of the transformers connected to the P63x needs tobe set.

  • 7/31/2019 P63X

    81/525

    3 Operation(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 3-47

    3-33 Measured operating data for the phase currents, ends a to d

  • 7/31/2019 P63X

    82/525

    3 Operation(continued)

    3-48 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    Delayed maximum phasecurrent display

    The P63x offers the option of delayed display of the maximum value of the three phasecurrents. The delayed maximum phase current display is an exponential function of themaximum phase current IP,max (see upper curve in Figure 3-34). A t MAIN : Se t t l . t .I P , m a x , d e l the user can set the time after which the delayed maximum phase currentdisplay will have reached 95 % of maximum phase current IP,max.

    Stored maximum phasecurrent display

    The stored maximum phase current follows the delayed maximum phase current. If thevalue of the delayed maximum phase current is declining, then the highest value of thedelayed maximum phase current remains stored. The display remains constant until theactual delayed maximum phase current exceeds the value of the stored maximum phase

    current (see middle curve in Figure 3-34). At MAIN : Res e t IP ,ma x ,s t o re d theuser can set the stored maximum phase current to the actual value of the delayedmaximum phase current (see lower curve in Figure 3-34).

  • 7/31/2019 P63X

    83/525

    3 Operation(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 3-49

    3-34 Operation of delayed and stored maximum phase current display

  • 7/31/2019 P63X

    84/525

    3 Operation(continued)

    3-50 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    3-35 Measured operating data for the residual currents, ends a to c

  • 7/31/2019 P63X

    85/525

    3 Operation(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 3-51

    3-36 Measured operating data for the residual currents, end d (P634 only)

  • 7/31/2019 P63X

    86/525

    3 Operation(continued)

    3-52 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    3-37 Measured operating data for the phase currents and the residual current for the virtual end (formed by current summation,

    P633 and P634 only, see Figure 3-32)

  • 7/31/2019 P63X

    87/525

    3 Operation(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 3-53

    Measured voltage valueThe measured voltage value is displayed both as quantity referred to the nominal voltageof the P63x and as primary quantity. To allow a display in primary values, the primarynominal voltage of the transformer connected to the P63x needs to be set.

    3-38 Measured voltage value

    FrequencyThe P63x determines the frequency from the voltage. The voltage needs to exceed aminimum threshold of 0.65 Vnom in order for the frequency to be determined.

    3-39 Frequency measurement

  • 7/31/2019 P63X

    88/525

    3 Operation(continued)

    3-54 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    Angle determinationThe P63x determines the angle between the following currents if the associated currentsexceed the lower threshold of 0.033 Inom:

    Angle between the phase currents for each end of the transformer

    Angle between the currents of the same phase between two ends of the transformer

    Angle between the calculated residual current and the current measured at thetransformer -Tx4 (x: 1, 2 or 3) for each end of the transformer

    3-40 Determination of the angle between the phase currents

  • 7/31/2019 P63X

    89/525

    3 Operation(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 3-55

    3-41 Determination of the angle between the phase currents of the transformer ends

  • 7/31/2019 P63X

    90/525

    3 Operation(continued)

    3-56 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    3-42 Determination of the angle between the calculated residual current and the current measured at transformer -Tx4

  • 7/31/2019 P63X

    91/525

    3 Operation(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 3-57

    3.11.4 Configuring and Enabling the Protection Functions

    By means of a straight-forward configuration procedure, the user can adapt the unitflexibly to the range of functions required in each particular high voltage substation. Byincluding the relevant protection functions in the device configuration and canceling allothers, the user creates an individual device appropriate to the application. Parameters,signals and measured values of canceled protection functions are not displayed on thelocal control panel. Functions of general applicability such as operating data recording(OP_RC) or main functions (MAIN) cannot be canceled.

    Canceling a protectionfunction

    The following conditions have to be met before a protection function can be canceled:

    The protection function must be disabled.

    None of the functions of the protection function to be canceled may be assigned to abinary input.

    None of the signals of the protection function may be assigned to a binary output or toan LED indicator.

    If the above conditions are met, proceed through the Configuration Parameters branch ofthe menu tree to access the setting parameter relevant for the device function to becanceled. If you wish to cancel the LIMIT function group, for example, access the settingparameter LI M IT : F u nc ti on gr ou p L I MI T and set its value to Without. Shouldyou wish to re-include the function group in the device configuration, set the value to

    With.

    The assignment of a parameter, a signal or a measured value to a protection function isdefined by a function group descriptor such as LIMIT. In the description of theprotection functions later in this manual, the protection function being described ispresumed to be included in the configuration.

    Disabling and enabling theprotection function

    Protection functions that are included in the configuration may still be disabled via afunction parameter or via binary signal inputs. Protection can only be disabled or enabledthrough binary signal inputs if the M A I N : D i s a b l e p r o t e c t . E X T andM A I N : E n a b l e p r o t e c t . E X T functions are both configured. When only one or

    neither of the two functions is configured, this is interpreted as Protection externallyenabled. If the triggering signals of the binary signal inputs are implausible, as forexample when they both have a logic value of 1, then the last plausible state remainsstored in memory.

    Note: If the protection device is disabled via the binary signal input configured toMAI N: Disa ble pr ote ct. EX T there will be no M AIN : Bloc ke d/f aul tysignal.

  • 7/31/2019 P63X

    92/525

    3 Operation(continued)

    3-58 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    3-43 Enabling or disabling protection

  • 7/31/2019 P63X

    93/525

    3 Operation(continued)

    P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN 3-59

    3.11.5 Activation of Dynamic Parameters

    For several of the protection functions, it is possible to switch the duration of the set holdtime to other settings - the "dynamic parameters" through an appropriately configuredbinary signal input. If the hold time is set to 0 s, the switching is effective while the binarysignal input is being triggered.

    3-44 Activation of dynamic parameters

    3.11.6 Multiple Blocking

    Four multiple blockings may be defined via 'm out of n' parameters. The items availablefor selection are found in the Address List. Thereby the functions defined by the selectionmay be blocked via an appropriately configured binary signal input.

  • 7/31/2019 P63X

    94/525

    3 Operation(continued)

    3-60 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    3-45 Multiple blocking

  • 7/31/2019 P63X

    95/525

  • 7/31/2019 P63X

    96/525

    3 Operation(continued)

    3-62 P631-301-401-601 // P632-301-401-601 // P633-301-401-601 // P634-301-401-601 / AFSV.12.06661 EN

    3.11.8 Starting Signals and Starting Logic

    Starting signalsThe trip signals of differential protection and ground differential protection (Br: Restrictedearth fault protection) plus the general startings of the definite-time and inverse-timeovercurrent protection are combined into one common general starting.

    3-47 General starting of the P63x

  • 7/31/20