AIR CONDITIONING SYSTEM
PAN HUMIDIFIER LOAD CALCULATION
S.No. DESCRIPTION UNITBUILDING
ROOM1
1 Design Room Condition
- Temperature [°C] 24
- Relative Humidity [%} 50
2
- Temperature [°C] 24
- Relative Humidity [%} 45
3 0.0109
4 0.0098
5 0.0011
6 Air Flow rate in supply air header[CFM] 30600
51989.73
7 Humidification load [kg/hr] 57.19
8 Heater capacity calculated [KW] 4.36
9 Pan Humidifier capacity selected [KW] 6
Anticipated condition for Pan humidifier sizing
Absolute humidity of air at design room condition
[Kg/m3]
Absolute humidity of air at anticipated condition
[Kg/m3]
Moisture to be added to increase the humidity to maintain the design condition.
[Kg/m3]
[m3/hr]