Passive Displacement Cooling (PDC)

Tay Cher SengApril 1, 2019

Page 3: Passive Displacement Cooling (PDC)

Chiller Plant

47%

Lifts

2%

Lighting

26%

others

3%

Hot Water

7%Air Side

15%

Page 4: Passive Displacement Cooling (PDC)
Page 5: Passive Displacement Cooling (PDC)

how it works

✓ nature at work

✓ hot air rise, cold air sink

• kongming lantern

• hot air balloon

5

Page 6: Passive Displacement Cooling (PDC)

No air duct– the PDC system uses no duct and therefore reduces the

provision of space above the false ceiling; in a building protected with sprinklers, there may not be a need for a

second layer of sprinkler points if the ceiling space is kept below a 800mm-height. Many end-users are also happy

with the indoor space with a high ceiling

Page 7: Passive Displacement Cooling (PDC)

No noise– the PDC system needs no silencer nor a host of acoustic treatment in

the duct and indoor space.

Page 8: Passive Displacement Cooling (PDC)

No draft – since fans are not used, occupants seated anywhere in the room

will not experience the draft effect commonly associated with AHUs / FCUs. PDC promises thermal comfort that is hard to match

Page 9: Passive Displacement Cooling (PDC)

Dust

Page 10: Passive Displacement Cooling (PDC)

condensation

Page 11: Passive Displacement Cooling (PDC)

Less maintenance with PDC

– experience has shown that little, if any, dust is found on

the cooling coils and therefore eliminating the need for regular

cleaning or chemical cleaning.

Page 13: Passive Displacement Cooling (PDC)

Computational Fluid Dynamics (CFD)

Page 14: Passive Displacement Cooling (PDC)

BEX Asia 2018

Video showing PDC integrated with cupboard; Cooled air illustrated with smoke is seen

filling up the lower part of the room until a heat source raise the temperature of the air

Page 15: Passive Displacement Cooling (PDC)

Performance

Page 16: Passive Displacement Cooling (PDC)

The Hive

@ NTU

Page 17: Passive Displacement Cooling (PDC)
Page 18: Passive Displacement Cooling (PDC)

supply air

temperature

Relative

Humidity

system

offsystem

on

18

Page 19: Passive Displacement Cooling (PDC)

ΔT= 5°

to 7°C

19

Page 20: Passive Displacement Cooling (PDC)

2.4 gpm/RT

20

Page 21: Passive Displacement Cooling (PDC)

◦ Chiller efficiency : 0.520 kW/rt

◦ Chilled water pump η : 0.035 kW/rt

◦ Condenser water pump η : 0.035 kW/rt

◦ Cooling Tower Fan η : 0.018 kW/rt

◦ Plant efficiency (water side) : 0.608 kW/rt

21

Page 22: Passive Displacement Cooling (PDC)

22

Page 23: Passive Displacement Cooling (PDC)

◦ water side efficiency : 0.608 kW/rt

◦ air side efficiency1 : 0.000 kW/rt (passive systems)

◦ air conditioning

total system efficiency : 0.608 kW/rt

23

1not including fan for fresh air intake

Page 24: Passive Displacement Cooling (PDC)

55%35%

5%5%

Chillers Fans

Cooling towers Pumps

• fans are known to consume as much as 15% of all energy used in buildings;

Page 25: Passive Displacement Cooling (PDC)

55%0%

5%5%

Chillers Fans

Cooling towers Pumps

• No fan –the PDC system uses no fan which means a potential savings of as much as 15%

Page 26: Passive Displacement Cooling (PDC)

Early Adopters

Page 27: Passive Displacement Cooling (PDC)

MOM Services Centre

Multiple Purpose Hall

Entrance Lobby

Page 28: Passive Displacement Cooling (PDC)

The Hive @ NTU

The Library

56 Classrooms

Page 29: Passive Displacement Cooling (PDC)

The Shugart

Gymnasium

Multiple Purpose Hall

Page 30: Passive Displacement Cooling (PDC)

The Wave @NTU

Page 31: Passive Displacement Cooling (PDC)

The Wave @ NTU

Stress testMore than 1,000 students attended an event over 4 hours

Achieved design conditions24° ± 1°C< 65% RH

Total AC system efficiency water side : 0.6 kW/RTair side : 0.0 kW/RT

The WaveNanyang Technological University

Page 32: Passive Displacement Cooling (PDC)

Smoke-illustrated air flow during T&C