Passive House Academy

Passive House Certification Guidance Document

Page 2: Passive House Academy Passive House Certification · Passive House Planning A R E A C A L C U L A T I O N Building: Heating Demand 15 kWh/(m²a) Summary Group No. Area Group Temp

Why work with Passive House Academy?

• Internationally accredited by the Passivhaus Institut to certify Passive House projects Internationally

• Leading experts in the Passive House standard, working on projects since 2002

• Currently working on over 60 Certification projects in the US

• Dedicated Certification team of 8 experienced Consultants

• Staff are very experienced in PHPP software – the essential passive house design

tool as well as with Therm calculations for thermal bridges

• PHA is a leading training provider for both designers and tradespersons in the US and has extensive experience in dealing with a broad range of construction types and climates

• Proactive and solutions-focused approach with the aim of providing a timely and

efficient service to our Clients

• Certifiers of numerous award winning Passive House projects including Julie Torres Moskovitz’s ‘Tighthouse’ in Brooklyn and Onion Flats’ ‘Belfield Homes’ project in Philadelphia.

• Certifiers of several ‘EnerPHit’ projects (the Passive House deep retrofit

standard).

Page 3: Passive House Academy Passive House Certification · Passive House Planning A R E A C A L C U L A T I O N Building: Heating Demand 15 kWh/(m²a) Summary Group No. Area Group Temp

Why Certify your Passive House Project?

• Certification process typically ensures a cost-optimal design approach delivering the best return on investment

• Quality assurance for the client;

• Proof of evidence of reaching the International standard;

• Listing on the international database of Certified projects;

• Distinction in the marketplace, record of achievement and stamp of approval;

• Access to increased marketing opportunities (Editors are more open to featuring projects that have been certified); and

• Learning opportunity for the Project Architect resulting from participation in the process.

Page 4: Passive House Academy Passive House Certification · Passive House Planning A R E A C A L C U L A T I O N Building: Heating Demand 15 kWh/(m²a) Summary Group No. Area Group Temp

Passive House PlanningA R E A C A L C U L A T I O N

Building: Heating Demand 15 kWh/(m²a)

SummaryGroup

No. Area Group Temp Zone Area Unit Comments

1 Treated Floor Area 439.44 m² Living area or useful area within the thermal envelope2 North Windows A 11.22 m² North Windows 1.0463 East Windows A 0.00 m² East Windows 4 South Windows A 51.56 m² Results are from the Windows worksheet. South Windows 0.8505 West Windows A 0.00 m² West Windows 6 Horizontal Windows A 0.00 m² Horizontal Windows 7 Exterior Door A 4.66 m² Please subtract area of door from respective building element Exterior Door 0.8008 Exterior Wall - Ambient A 685.37 m² Window areas are subtracted from the individual areas specified in the "Windows" worksheet. Exterior Wall - Ambient 0.1149 Exterior Wall - Ground B 0.00 m² Temperature Zone "A" is ambient air. Exterior Wall - Ground10 Roof/Ceiling - Ambient A 101.48 m² Temperature zone "B" is the ground. Roof/Ceiling - Ambient 0.11411 Foor slab/ basement ceiling B 166.26 m² Foor slab/ basement ceiling 0.09512 0.00 m² Temperature zones "A", "B","P" and "X" may be used. NOT "I"13 0.00 m² Temperature zones "A", "B","P" and "X" may be used. NOT "I" Factor for X14 X 0.00 m² Temperature zone "X": Please provide user-defined reduction factor ( 0 < f t < 1): 75%

Thermal Bridge Overview Ψ [W/(mK)]

15 Thermal Bridges Ambient A 0.00 m Units in m Thermal Bridges Ambient16 Perimeter Thermal Bridges P 0.00 m Units in m; temperature zone "P" is perimeter (see Ground worksheet). Perimeter Thermal Bridges 17 Thermal Bridges Floor Slab B 0.00 m Units in m Thermal Bridges Floor Slab

18 Partition Wall to Neighbour I 0.00 m² No heat losses, only considered for the heating load calculation. Partition Wall to Neighbour

Total Thermal Envelope 1020.55 m² Average Therm. Envelope 0.162

Area Input

Area no. Building element description Group no. Assigned to group

Quan-tity

x ( a[m]

xb

[m]+ User-deter-

mined [m²] -User sub-traction

[m²]-

Subtraction window areas[m²]

) = Area[m²]

Treated Floor Area 1 Treated Floor Area 1 x ( x + 439.44 - ) = 439.4North Windows 2 North Windows 11.2 From Windows sheet 1.046East Windows 3 East Windows 0.0 From Windows sheet 0.000South Windows 4 South Windows Please complete in Windows worksheet only! 51.6 From Windows sheet 0.850West Windows 5 West Windows 0.0 From Windows sheet 0.000Horizontal Windows 6 Horizontal Windows 0.0 From Windows sheet 0.000Exterior Door 7 Exterior Door 2 x ( 2.59 x 0.90 + - ) - = 4.7 U-Value Exterior Door 0.80

1 Floor Slab 11 Foor slab/ basement ceiling 1 x ( x + 166.26 - ) - 0.0 = 166.3 3 0.0952 WA-N-01 8 Exterior Wall - Ambient 1 x ( x + 233.25 - ) - 0.0 = 233.3 1 0.1143 x ( x + - ) - 0.0 =4 WA-E-01 8 Exterior Wall - Ambient 1 x ( x + 46.97 - ) - 0.0 = 47.0 1 0.1145 WA-E-02 8 Exterior Wall - Ambient 1 x ( x + 88.89 - ) - 0.0 = 88.9 1 0.1146 WA-E-03 8 Exterior Wall - Ambient 1 x ( x + 9.09 - ) - 0.0 = 9.1 1 0.1147 WA-E-04 8 Exterior Wall - Ambient 1 x ( x + 5.34 - ) - 0.0 = 5.3 1 0.1148 x ( x + - ) - 0.0 =9 WA-S-01 8 Exterior Wall - Ambient 1 x ( x + 52.75 - ) - 8.3 = 44.4 1 0.11410 WA-S-02 8 Exterior Wall - Ambient 1 x ( x + 146.92 - ) - 54.4 = 92.5 1 0.11411 WA-S-03 8 Exterior Wall - Ambient 1 x ( x + 14.66 - ) - 0.0 = 14.7 1 0.11412 x ( x + - ) - 0.0 =13 WA-W-01 8 Exterior Wall Ambient 1 x ( x + 46 97 ) 0 0 = 47 0 1 0 114

Average U-Value[W/(m²K)]Building Element Overview

U-Value[W/(m²K)]

Selection of the Corresponding Building

Element AssemblyNo.

Floor

Wall Exemplar

Wall Exemplar

Wall Exemplar

Wall Exemplar

Wall Exemplar

Wall Exemplar

Wall Exemplar

Wall Exemplar

Wall Exemplar

Passive House Planning

R E D U C T I O N F A C T O R S O L A R R A D I A T I O N , W I N D O W U - V A L U E

Building: Annual Heat Demand: 15 kWh/(m²a) Heating Degree Hours:

Climate: Morehead NYC Peak Data 75.2

Window Area Orientation

Global Radiation (Cardinal Points)

Shading Dirt

Non-Perpendicu-lar Incident Radiation

Glazing Fraction g-Value

Reduction Factor for Solar

Radiation

WindowArea

WindowU-Value

GlazingArea

Average Global

Radiation

Transmission Losses

Heat Gains Solar

RadiationMaximum: kWh/(m²a) 0.75 0.95 0.85 m2 W/(m2K) m2 kWh/(m2a) kWh/a kWh/a

North 141 0.70 0.95 0.85 0.420 0.50 0.24 11.22 1.05 4.7 141 882 187East 290 1.00 0.95 0.85 0.000 0.00 0.00 0.00 0.00 0.0 290 0 0South 507 0.64 0.95 0.85 0.695 0.50 0.36 51.56 0.85 35.9 507 3294 4666West 312 1.00 0.95 0.85 0.000 0.00 0.00 0.00 0.00 0.0 312 0 0Horizontal 503 1.00 0.95 0.85 0.000 0.00 0.00 0.00 0.00 0.0 503 0 0

Total or Average Value for All Windows. 0.50 0.34 62.78 0.89 40.6 4176 4853

Window Rough Openings Installed Glazing Frame g-Value U-Value Window Frame Dimensions Installation Ψ-Value Results

Quan-tity Description Deviation

from North

Angle of Inclination from the

Horizontal

Orientation Width HeightSelect area

from the Area worksheet

No.

Select glazing from the WinType

worksheet

No.

Select window from the WinType

worksheet

No.Perpen-dicular

RadiationGlazing Frames Width

LeftWidthRight

WidthBottom

WidthTop

Left1/0

Right1/0

Sill1/0

Head1/0 Ψ Spacer Ψ Installation

Window Area

Glazing Area

U-ValueWindow

Glazed Fraction

per Window

Degrees Degrees m m Select: Select: Select: - W/(m2K) W/(m2K) m m m m W/(mK) W/(mK) m2 m2 W/(m2K) %0 D-GF-S-01 180 90 South 0.910 2.590 9 1 8 0.50 0.66 0.72 0.12 0.06 0.13 0.12 1 0 1 1 0.028 0.040 0.0 0.000 D-GF-S-02 180 90 South 0.810 2.590 9 1 8 0.50 0.66 0.72 0.12 0.06 0.13 0.12 1 0 1 1 0.028 0.040 0.0 0.00

0 0 0

1 W-FIF-S-01 180 90 South 0.760 1.520 9 1 3 0.50 0.66 0.72 0.12 0.06 0.12 0.12 1 0 1 1 0.028 0.040 1.2 0.75 0.88 65%1 W-FIF-S-02 180 90 South 1.630 1.520 9 1 5 0.50 0.66 0.72 0.12 0.12 0.06 0.06 0 0 1 1 0.028 0.040 2.5 1.96 0.79 79%1 W-FIF-S-03 180 90 South 0.710 1.520 9 1 5 0.50 0.66 0.72 0.12 0.12 0.06 0.06 0 0 1 1 0.028 0.040 1.1 0.67 0.83 62%1 W-FIF-S-04 180 90 South 1.630 1.520 9 1 5 0.50 0.66 0.72 0.12 0.12 0.06 0.06 0 0 1 1 0.028 0.040 2.5 1.96 0.79 79%1 W-FIF-S-05 180 90 South 0.760 1.520 9 1 3 0.50 0.66 0.72 0.12 0.06 0.12 0.12 1 0 1 1 0.028 0.040 1.2 0.75 0.88 65%

0 0 0

1 W-SEF-S-01 180 90 South 0.860 1.980 10 1 3 0.50 0.66 0.72 0.12 0.06 0.12 0.12 1 0 1 1 0.028 0.040 1.7 1.20 0.85 70%1 W-SEF-S-02 180 90 South 1.270 1.500 10 1 4 0.50 0.66 0.72 0.12 0.06 0.06 0.12 1 0 1 0 0.028 0.040 1.9 1.45 0.80 76%1 W-SEF-S-02 180 90 South 1.270 0.480 10 1 4 0.50 0.66 0.72 0.12 0.06 0.06 0.12 1 0 1 0 0.028 0.040 0.6 0.33 0.93 55%1 W-SEF-S-03 180 90 South 1.070 1.520 10 1 1 0.50 0.66 0.72 0.12 0.12 0.12 0.12 1 1 1 1 0.028 0.040 1.6 1.08 0.88 66%1 W-SEF-S-04 180 90 South 0.610 1.520 10 1 1 0.50 0.66 0.72 0.12 0.12 0.12 0.12 1 1 1 1 0.028 0.040 0.9 0.48 0.97 52%1 W-SEF-S-05 180 90 South 1.270 1.500 10 1 4 0.50 0.66 0.72 0.12 0.06 0.06 0.12 1 0 1 0 0.028 0.040 1.9 1.45 0.80 76%1 W-SEF-S-05 180 90 South 1.270 0.480 10 1 4 0.50 0.66 0.72 0.12 0.06 0.06 0.12 1 0 1 0 0.028 0.040 0.6 0.33 0.93 55%1 W-SEF-S-06 180 90 South 0.860 1.980 10 1 3 0.50 0.66 0.72 0.12 0.06 0.12 0.12 1 0 1 1 0.028 0.040 1.7 1.20 0.85 70%

0 0 0

1 W-TF-S-01 180 90 South 0.810 1.520 10 1 3 0.50 0.66 0.72 0.12 0.06 0.12 0.12 1 0 1 1 0.028 0.040 1.2 0.82 0.87 66%1 W-TF-S-02 180 90 South 1.320 1.520 10 1 3 0.50 0.66 0.72 0.12 0.06 0.12 0.12 1 0 1 1 0.028 0.040 2.0 1.47 0.83 73%1 W-TF-S-03 180 90 South 1.070 1.520 10 1 1 0.50 0.66 0.72 0.12 0.12 0.12 0.12 1 1 1 1 0.028 0.040 1.6 1.08 0.88 66%1 W-TF-S-04 180 90 South 0.610 1.520 10 1 1 0.50 0.66 0.72 0.12 0.12 0.12 0.12 1 1 1 1 0.028 0.040 0.9 0.48 0.97 52%1 W-TF-S-05 180 90 South 1.320 1.520 10 1 3 0.50 0.66 0.72 0.12 0.06 0.12 0.12 1 0 1 1 0.028 0.040 2.0 1.47 0.83 73%1 W-TF-S-06 180 90 South 0.810 1.520 10 1 3 0.50 0.66 0.72 0.12 0.06 0.12 0.12 1 0 1 1 0.028 0.040 1.2 0.82 0.87 66%

0 0 0

1 W-FOF-S-01 180 90 South 0.810 1.520 10 1 3 0.50 0.66 0.72 0.12 0.06 0.12 0.12 1 0 1 1 0.028 0.040 1.2 0.82 0.87 66%1 W-FOF-S-02 180 90 South 1.320 1.520 10 1 3 0.50 0.66 0.72 0.12 0.06 0.12 0.12 1 0 1 1 0.028 0.040 2.0 1.47 0.83 73%1 W-FOF-S-03 180 90 South 1.070 1.520 10 1 1 0.50 0.66 0.72 0.12 0.12 0.12 0.12 1 1 1 1 0.028 0.040 1.6 1.08 0.88 66%1 W-FOF-S-04 180 90 South 0.610 1.520 10 1 1 0.50 0.66 0.72 0.12 0.12 0.12 0.12 1 1 1 1 0.028 0.040 0.9 0.48 0.97 52%1 W-FOF-S-05 180 90 South 1.320 1.520 10 1 3 0.50 0.66 0.72 0.12 0.06 0.12 0.12 1 0 1 1 0.028 0.040 2.0 1.47 0.83 73%1 W-FOF-S-06 180 90 South 0.810 1.520 10 1 3 0.50 0.66 0.72 0.12 0.06 0.12 0.12 1 0 1 1 0.028 0.040 1.2 0.82 0.87 66%

0 0 0

1 W-FF-S-01 180 90 South 0.810 1.520 10 1 3 0.50 0.66 0.72 0.12 0.06 0.12 0.12 1 0 1 1 0.028 0.040 1.2 0.82 0.87 66%1 W-FF-S-02 180 90 South 1.320 1.520 10 1 3 0.50 0.66 0.72 0.12 0.06 0.12 0.12 1 0 1 1 0.028 0.040 2.0 1.47 0.83 73%1 W-FF-S-03 180 90 South 1.070 1.520 10 1 1 0.50 0.66 0.72 0.12 0.12 0.12 0.12 1 1 1 1 0.028 0.040 1.6 1.08 0.88 66%1 W-FF-S-04 180 90 South 0.610 1.520 10 1 1 0.50 0.66 0.72 0.12 0.12 0.12 0.12 1 1 1 1 0.028 0.040 0.9 0.48 0.97 52%1 W-FF-S-05 180 90 South 1.320 1.520 10 1 3 0.50 0.66 0.72 0.12 0.06 0.12 0.12 1 0 1 1 0.028 0.040 2.0 1.47 0.83 73%1 W-FF-S-06 180 90 South 0.810 1.520 10 1 3 0.50 0.66 0.72 0.12 0.06 0.12 0.12 1 0 1 1 0.028 0.040 1.2 0.82 0.87 66%

0 0 0

1 D-SIF-S-01 180 90 South 1.070 2.400 10 1 8 0.50 0.66 0.72 0.12 0.06 0.13 0.12 1 0 1 1 0.028 0.040 2.6 1.92 0.81 75%1 D-SIF-S-02 180 90 South 1.070 2.400 10 1 8 0.50 0.66 0.72 0.12 0.06 0.13 0.12 1 0 1 1 0.028 0.040 2.6 1.92 0.81 75%

0 0 0

1 W-SEF-N-01 0 90 North 0.610 0.820 10 1 1 0.50 0.66 0.72 0.12 0.12 0.12 0.12 1 1 1 1 0.028 0.040 0.5 0.22 1.03 44%1 W-SEF-N-02 0 90 North 0.610 0.610 10 1 1 0.50 0.66 0.72 0.12 0.12 0.12 0.12 1 1 1 1 0.028 0.040 0.4 0.14 1.07 38%1 W-SEF-N-03 0 90 North 0.610 0.610 10 1 1 0.50 0.66 0.72 0.12 0.12 0.12 0.12 1 1 1 1 0.028 0.040 0.4 0.14 1.07 38%

WA-S-01

WA-S-01

WA-S-01

WA-S-01

WA-S-01

WA-S-01

WA-S-01

WA-S-02

WA-S-02

WA-S-02

WA-S-02

WA-S-02

WA-S-02

WA-S-02

WA-S-02

WA-S-02

WA-S-02

WA-S-02

WA-S-02

WA-S-02

WA-S-02

WA-S-02

WA-S-02

WA-S-02

WA-S-02

WA-S-02

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

Door Side

Door Side

G Side Join

G Two Sides Join

G Two Sides Join

G Two Sides Join

G Side Join

G Side Join

G Top & Side Join

G Top & Side Join

G W Pazen GmbH - F

G W Pazen GmbH - F

G Top & Side Join

G Top & Side Join

G Side Join

G Side Join

G Side Join

G W Pazen GmbH - F

G W Pazen GmbH - F

G Side Join

G Side Join

G Side Join

G Side Join

G W Pazen GmbH - F

G W Pazen GmbH - F

G Side Join

WA-S-02

WA-S-02

WA-S-02

WA-S-02

WA-S-02

WA-S-02

WA-S-02

WA-S-02

WA-S-02

WA-S-02

WA-S-02

WA-S-02

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

INTERPANE - iplus 3

G Side Join

G Side Join

G Side Join

G W Pazen GmbH - F

G W Pazen GmbH - F

G Side Join

G Side Join

Door Side

Door Side

G W Pazen GmbH - F

G W Pazen GmbH - F

G W Pazen GmbH - F

Documentation Required for a Passive House Quality Approval Certificate Please note: To submit an information package or an enquiry about Certification please email Alan at [email protected]. We only accept information on your project by digital download link. We do not accept hard copy or CD packages or live shared folders. 1) Minimum Documentation Required for Commencement of Certification 1.1) A Complete PHPP File Containing at least the following Calculations:

• Verification • Areas • R-values • Windows • WinType • Ground • Shading • Ventilation • Annual Heating Demand • Monthly Method • Heating Load • Summer, Shading-S, SummVent • DHW+Distribution • SolarDHW • Annual heat generator utilisation factor • Compact, Boiler or District Heat • Electricity demand • Electricity • Auxiliary electricity demand • Aux Electricity • Primary energy • PE Value • Climate data

Page 5: Passive House Academy Passive House Certification · Passive House Planning A R E A C A L C U L A T I O N Building: Heating Demand 15 kWh/(m²a) Summary Group No. Area Group Temp

1.2) A site plan or sketch showing the heights of immediately surrounding buildings and trees. The sketch or drawing should display the measured distance from the facade of the building to each shading object and also an approximate height from floor level to the shading object.

1.3) An auto-cad Dxf/Dwg of plans, elevations & sections for the proposed design. The edge of frame dimensions should be clearly shown for all windows (in dashed under overlap of insulation if any). If there are multiple assemblies intended for different areas of the elevations this should be clearly shown in coloured hatch or highlighting.

1.4) Photographs facing every direction, with the orientation clearly labelled and depicting all shading objects surrounding the project.

1.5) A Google Map link with the exact project location 1.6) Proposed Construction Details A detail of every junction in the thermal envelope should be submitted. If the construction build-ups of all opaque elements (walls, roofs and floors) are not clearly shown on these then a sketch/drawing should be submitted of all assemblies (PHPP calculations alone will not suffice). Both construction details and assembly sketches must show: • The thickness of all layers;

• The insulation type, including conductivities or R per inch of all materials in the assembly/detail (products technical specifications must be submitted in accordance with item 2.2);

• The centers and thicknesses of any repeating elements (ie, timber studs or steel studs); and

• The gauge of steel studs (if used).

2) Additional Documentation for Advancing Certification

2.1) Technical Information for Insulation Products • Technical Brochures for all insulation products must be provided stating thermal

conductivities (R per inch) in accordance with local government standards;

Page 6: Passive House Academy Passive House Certification · Passive House Planning A R E A C A L C U L A T I O N Building: Heating Demand 15 kWh/(m²a) Summary Group No. Area Group Temp

• This can any local government testing. The Construction Supervisor is liable for the performance of the materials so if materials are rated with dubious values caution must be taken.

• Be sure to highlight the specific insulation values that pertain to the product you have chosen.

2.2) Glass Technical Information 2.2.1) Ug or Rg according to ISO EN 673

2.2.2) Solar heat gain coefficient (SHGC) or ‘g-value’ according to ISO EN 410

2.2.3) Psi glass edge according to ISO EN 10077-2

2.3) Window Frame Glazed Door or Solid Door Technical Information 2.3.1) Uf or Rf according to ISO EN 10077-2

2.3.2) Widths of frames for top, bottom and sides

2.4) Technical Information for the Ventilation Unit • We highly recommend the use of a Passivhaus Institut (PHI) certified ERV (energy

recovery ventilator) or HRV (heat recovery ventilator as, leaks and thermal bridges in non-certified units can drastically affect their efficiency. The type (ERV or HRV?) and certification for the proposed ventilation unit is needed. If you choose not to use a PHI certified unit, we are required to reduce the manufacturers stated efficiency by 12%.

• The designed air flow rate has a significant effect on the energy balance of Passive House buildings. Air flow rates must be designed so that a minimum of 0.3 air changes per hour is achieved. In climates with cold winters, it is important not to greatly exceed the 0.3 air changes per hour in order to avoid low internal air humidity.

Page 7: Passive House Academy Passive House Certification · Passive House Planning A R E A C A L C U L A T I O N Building: Heating Demand 15 kWh/(m²a) Summary Group No. Area Group Temp

2.4.1) For certification we need a simple sketch (if drawings are already created, please send them) of the proposed supply and extract points, the position of the ERV / HRV and the intended flow rates at all registers.

2.4.2) Passive House certificate/technical Information stating both heat recovery and electrical efficiency.

2.4.3) Length of ambient air ducts (those that connect to the outside world) as well as proposed insulation type, thickness and R per inch thereon .

2.5) Subsoil Heat Exchanger In extremely cold climates a subsoil heat exchanger is a viable source of frost protection and pre-tempering. Subsoil heat exchangers can be extremely problematic if not constructed properly or if the condensate drain dries out. It is imperative that if such a system is used that a specialist contractor is used. A liquid source solution such as brine/glycol is much less problematic and can work very well with common systems. For either system a layout showing the underground piping is needed. Although useful for frost protection and some tempering of the air it will only improve the ERV / HRV efficiency by approximately 4%. With liquid systems this energy saving may be outweighed by the electrical consumption of the circulation pumps. 2.6) Primary Energy – Heating, Cooling and Hot Water Production Description We need a brief description of the proposed heating, cooling and hot water systems. The use of efficient heating, cooling and hot water systems is crucial and contributes to a large proportion of the energy use in a Passive House building. If solar thermal collectors are used in combination with an efficient heating, cooling and and hot water system then the primary energy target can usually be easily met. The use of direct electricity is not recommended and will cause the primary energy target to be exceeded in most cases (heat pumps, mini-splits are typically acceptable). For the Pre-Certification we need an outline description of how you intend to produce hot water and deal with the heating and cooling demands.

Page 8: Passive House Academy Passive House Certification · Passive House Planning A R E A C A L C U L A T I O N Building: Heating Demand 15 kWh/(m²a) Summary Group No. Area Group Temp

2.7) Technical Brochures stating Efficiencies of Mechanical Equipment (heating, cooling and domestic hot water) For heating furnaces/boilers we simply need a technical document stating the efficiency. For Heat Pumps we need the coefficiency of performance (COP) and season energy efficiency ratio (SEER), the capacity and the flow rates of each indoor cassette and wall unit for both heating and cooling modes. If you are using a heat pump hot water heater we need the COP or SEER and for the storage tank the losses in W/K or BTU/hr.F. 2.8) Hot Water and Heating Supply Pipelines Layout

For all hot water pipes we will need a dimensioned layout or sketch showing dimensions, diameter and thickness and type of insulation and details of the circulation loop (if used). The location of the tank and heat generator should also be shown. 3) Additional Documentation for Certification of Schools and Offices 3.1) A usage profile indicating the occupancy times and frequencies of absenteeism for

all spaces within the building. 3.2) A lighting layout with a legend indicating the wattage of each fixture. 3.3) An equipment and appliance schedule with the power consumption of all

electronic devices.

Additional Documentation Additional documentation will be requested depending on special circumstances and building types. Items such as external sliding doors, elevators, extract exhausts for dryers and other special items like thermal bridging of details may be sought. At the end of the review all such special information will be listed. 4 Verifications and Declarations 4.1 Verification of the airtight building envelope in accordance with EN ISO 13829* *This standard is currently under review, please check prior to commencement In addition to what is specified in EN ISO 13829*, a series of air tightness measurements for both positive and negative pressure is necessary for Passive House projects (see image below). The pressure tests are to be carried out only for the heated building

Page 9: Passive House Academy Passive House Certification · Passive House Planning A R E A C A L C U L A T I O N Building: Heating Demand 15 kWh/(m²a) Summary Group No. Area Group Temp

envelope (basements, porches and conservatories etc. that are not integrated into the thermal envelope should not be included in the test). It is recommended that the test be carried out when the airtight layer is still accessible so that improvements can still be made if necessary. The indoor air volume calculation should also be documented in the pressure test report. The pressure test is to be carried out by an institution or person independent of the contractor or building owner. Pressure tests conducted by the contractor will only be accepted if an individual who is fully responsible for checking the accuracy of the information provided in the test results signs off on them.

4.2 Documenting Flow Rate Adjustment (Balancing the Ventilation System) In Cell I67 in the PHPP “Ventilation” sheet the maximum design air flow rate is specified. However, when balancing the ventilation system, this must be done at the standard

rate (typically 77% of the maximum rate), specified in Cell I68 in the same sheet.

Page 10: Passive House Academy Passive House Certification · Passive House Planning A R E A C A L C U L A T I O N Building: Heating Demand 15 kWh/(m²a) Summary Group No. Area Group Temp

In the “Design” sheet of the “Final Protocol Worksheet Ventilation IP” excel file the supply and return flow rates planned for each space (whether supply or extract) are entered into the relevant cells making sure that the total supply rate matches the total extract rate as depicted below.

Then in the “Initial Start Up” sheet of the same Excel file mentioned above, the person responsible for balancing the system enters the real or actual flow rates measured at each register using a digital anemometer. Often it will take at least two attempts to get the actual flow rates at each register to equate to the design rate (as depicted in the screen-grab below). On completion of the system set-up, there must be less than 10% imbalance between the total extract and total supply rates (in the example below, we have achieved a disbalance of 5%).

The ventilation flow rate adjustment documentation must include at least the following:

Page 11: Passive House Academy Passive House Certification · Passive House Planning A R E A C A L C U L A T I O N Building: Heating Demand 15 kWh/(m²a) Summary Group No. Area Group Temp

• Description of the property; • Property address; • Name and address of the tester; • Date and time of adjustment; • Make and model of the ventilation unit; • Adjusted volumetric flows per register at normal operation; and • Volumetric flow balance for outdoor air and exhaust air.

4.3 Declaration of the construction supervisor

Full and complete implementation according to certified Passive House project planning must be documented and confirmed by the construction supervisor. Any variation in terms of implementation should be mentioned. For any products not mentioned in the plans, corresponding documentation must be provided. A template for this document can be provided upon request 4.4 Photographs

Photographs should be taken of the insulation being installed at every level of the build-up, on every floor, roof, wall and basement wall. Photographs of the installed duct-work to the outside air and its insulation thickness should also be taken. You should also photograph every detail which involves a thermal break (for proof of installation), of every critical detail involving steel or timber with overlapping insulation and of window fitting details with their connecting/overlapping insulation. For at least one of each proof of element a measuring tape should be placed beside each insulation installation for proof/scale of thickness. "As many photographs as possible to document the construction process".

Page 12: Passive House Academy Passive House Certification · Passive House Planning A R E A C A L C U L A T I O N Building: Heating Demand 15 kWh/(m²a) Summary Group No. Area Group Temp

5. Fee Proposal Please apply for fees for all projects. If you have already availed of Pre-Certification for your Project then a reduced fee for Full Certification is included in the original quote. All projects or multi-unit residential projects are charged according to a bespoke fee for that project. We will forward you a fee proposal for your project within 3 working days of receiving drawings and schematics from you. If you decide to go ahead, we will require the following:

• Written instruction to proceed.

• All documents and drawings required for the Passive House Quality Approval Certificate (as above). Please note all required items are to be provided by you at your cost. Should you require assistance in preparing any of the required items we would be happy to quote for that separately.

• 25% deposit payable in advance.

• 50% due on complete review.

• Final 25% prior to issue of Certificate & compiled package.

Note: If the project fails to achieve the Passive House Standard for any reason outside the control of Passive House Academy (such as failing to meet the required level of airtightness), Passive House Academy expects to be paid the full fee as quoted above. 6. Publication on the Passive House Academy Website We would like to publish your project once Certified on our website www.passivehouseacademy.com. To enable this we will need the following:

Page 13: Passive House Academy Passive House Certification · Passive House Planning A R E A C A L C U L A T I O N Building: Heating Demand 15 kWh/(m²a) Summary Group No. Area Group Temp

• Description of your project in max 100 words (an architectural overview, describing the design concept, the setting, materials and finishes, Client’s brief…).

• 2 high quality exterior images and 2 high quality interior images. • Names and web addresses of the key design team members as well as the

Contractor so that visitors to our site can get in touch. General Terms & Conditions Advice on general queries on this or other projects outside the fixed fee proposal noted above would be charged on a time basis and agreed in advance. All comments / details provided will only concern the thermal performance of the building in relation to the PHPP report. Your Architect will remain responsible for the performance of the details in terms of all Building Codes, water penetration, weathering, structural performance, aesthetics, durability, retention of guarantees and so forth. Passive House Academy will act as consultants to your Architect. Passive House Academy will require your Architect and other consultants involved in the project to carry Professional Indemnity Insurance at the appropriate level for the value of the particular project. A condition of contract is that Passive House Academy is mentioned as the Certifier in the event of any kind of publication of the building for which its service is provided.

Page 14: Passive House Academy Passive House Certification · Passive House Planning A R E A C A L C U L A T I O N Building: Heating Demand 15 kWh/(m²a) Summary Group No. Area Group Temp

Contact Us: 133 Union Street, Brooklyn, NY 11231.

Tel: 646-233-1365 Email: [email protected] Website: www.passivehouseacademy.com

Page 15: Passive House Academy Passive House Certification · Passive House Planning A R E A C A L C U L A T I O N Building: Heating Demand 15 kWh/(m²a) Summary Group No. Area Group Temp

Passive House Pre-Certification & Certification Information Checklist 1) Minimum Documentation Required for Commencement

required incomplete complete

1.1) Completed PHPP file □ □ □

1.2) Site Plan □ □ □

1.3) Plans, Elevations & Sections □ □ □

1.4) Photographs of Surroundings (labelled as to

orientation)

□ □ □

1.5) Google Map Link of Exact Location □ □ □

1.6) Proposed Construction Details showing: □ □ □

1) Thickness of each material 2) Lambda or R per Inch of each material 3) Center and thickness of steel or wood studs 4) Gauge of steel studs Note: Both printed pdf set and dwg files are needed for all Design Drawings

2) Additionally Required Documentation required incomplete complete

2.1) Technical Brochures for all insulation

products

□ □ □

(don't forget to highlight your product if there are multiple values)

Page 16: Passive House Academy Passive House Certification · Passive House Planning A R E A C A L C U L A T I O N Building: Heating Demand 15 kWh/(m²a) Summary Group No. Area Group Temp

2) Additionally Required Documentation required incomplete complete

2.2) Technical specification for windows □ □ □

1) Psi Glass Edge according to ISO EN 10077-2 □ □ □

2) Uf according to ISO EN 10077-2 □ □ □

3) Ug according to ISO EN 673 □ □ □

4) G-Value/SHGC according to ISO EN 410 □ □ □

5) Psi Install according to ISO EN 10211 □ □ □

6) Widths of frames for top, bottom and sides □ □ □

2.3) Technical specification for glazed doors □ □ □

1) Psi Glass Edge according to ISO EN 10077-2 □ □ □

2) Uf according to ISO EN 10077-2 □ □ □

3) Ug according to ISO EN 673 □ □ □

4) G-Value/SHGC according to ISO EN 410 □ □ □

5) Psi Install according to ISO EN 10211 □ □ □

6) Widths of frames for top, bottom and sides □ □ □

2.4) Technical Information for ventilation unit □ □ □

2.4.1) Ventilation Layout □ □ □

2.4.2) Efficiency and Electrical Consumption □ □ □

2.4.3) Ambient air duct; Insulation, thickness,

length and diameter

□ □ □

Page 17: Passive House Academy Passive House Certification · Passive House Planning A R E A C A L C U L A T I O N Building: Heating Demand 15 kWh/(m²a) Summary Group No. Area Group Temp

2) Additionally Required Documentation required incomplete complete

2.5) Information about the sub-soil heat exchanger

(only if used)

□ □ □

2.6) Primary Energy – Heating, Cooling and Hot

Water Production Description

□ □ □

2.7) Technical brochures stating efficiencies of

mechanical equipment

□ □ □

1) Heating Efficiency □ □ □

2) Cooling Efficiency □ □ □

3) Hot Water Production □ □ □

4) Hot Water Storage □ □ □

2.8) Hot water and heating supply pipelines □ □ □

(lengths, dimensions, thickness and level of

insulation if any, circulation loop)

□ □ □

3) Additional Documentation for Schools and

Offices

required incomplete complete

3.1) A usage profile indicating the occupancy times

and frequencies of absenteeism for all spaces

within the building

□ □ □

3.2) A lighting layout with a legend indicating the

wattage of each fixture in the building

□ □ □

3.3) An equipment and appliance schedule with the

power consumption of all electronic devices.

□ □ □

Page 18: Passive House Academy Passive House Certification · Passive House Planning A R E A C A L C U L A T I O N Building: Heating Demand 15 kWh/(m²a) Summary Group No. Area Group Temp

4) Certification Verifications and Declarations for Full Certification Only

required incomplete complete

4.1) Verification of the airtight building envelope in

accordance with EN ISO 13829 (This standard is

currently under review please check to see if

updated)

□ □ □

4.2) Documentation of the flow rate

adjustment(balancing the ventilation system)

□ □ □

4.3) Declaration of the construction supervisor □ □ □

4.4) Photographs □ □ □