4
PassiveAir 1 18-12-14 Airvent reserves the right to change specifications. www.airvent.eu PassiveAir Passive chilled beam Main features b Energy efficient high performance b Cooling capacity up to 455 W/m at a temperature difference of 10 °C b Silent operation b Suspended installation Description The PassiveAir passive chilled beam can be used in all types of premises where supplementary cooling is required. By absorbing heat, mainly through natural convection, PassiveAir maintains the room temperature at an even level, securing an optimal thermal comfort. The passive chilled beam works best in areas where heating and ventilation have already been installed. PassiveAir is designed for suspended installation, and due to the the low height of the product it is suitable for most type of premises. Quick selection Size (mm) ΔT Cooiling capacity (W/m) 1200-3600 10 °K 50-455 Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz

PassiveAir - Cooke Industries · PassiveAir maintains the room temperature at an even level, securing an optimal thermal comfort. The passive chilled . beam works best in areas where

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: PassiveAir - Cooke Industries · PassiveAir maintains the room temperature at an even level, securing an optimal thermal comfort. The passive chilled . beam works best in areas where

PassiveAir

118-12-14Airvent reserves the right to change specifications.

www.airvent.eu

PassiveAir

Passive chilled beam

Main features b Energy efficient high performance b Cooling capacity up to 455 W/m

at a temperature difference of 10 °C b Silent operation b Suspended installation

DescriptionThe PassiveAir passive chilled beam can be used in all types ofpremises where supplementary cooling is required. By absorbing heat, mainly through natural convection, PassiveAir maintains the room temperature at an even level, securing an optimal thermal comfort. The passive chilled beam works best in areas where heating and ventilation have already been installed. PassiveAir is designed for suspended installation, and due to the the low height of the product it is suitable for most type of premises.

Quick selectionSize

(mm)ΔT

Cooiling capacity (W/m)

1200-3600 10 °K 50-455

Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz

Page 2: PassiveAir - Cooke Industries · PassiveAir maintains the room temperature at an even level, securing an optimal thermal comfort. The passive chilled . beam works best in areas where

2 14-12-18

PassiveAir

Airvent reserves the right to change specifications.

www.airvent.eu

MaterialsThe elegant design of the aluminium side profiles and front plates makes the product blend into its environment. PassiveAir is a convector enclosed in a painted aluminium casing with a perforated front in aluminum. The coil is made of copper tubes with uniquely designed aluminium fins. The casing is powder coated in a RAL 9003 color.

Square perforation as standard option

Mounting instructionsThe unit is delivered with four factory made mounting brack-ets (one in each corner), which can be adjusted seperatley in four directions. The device can also be mounted suspended with help from a threaded rod.

www.klimatbyran.se Version A

FunctionThe operation of PassiveAir is based on the natural convection process and is self-regulating. The air velocity increases ordecreases in relation to the heat load within the room.This ensures good comfort with a minimum risk of draught. Varying sensible cooling output requirements are met by regulating the flow of chilled water through the beams heat exchanger. This is controlled by a combination of roomthermostat and water valve. The dimension of the passive beam depends on the capacity requirements.

Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz

Page 3: PassiveAir - Cooke Industries · PassiveAir maintains the room temperature at an even level, securing an optimal thermal comfort. The passive chilled . beam works best in areas where

PassiveAir

314-12-18 Airvent reserves the right to change specifications.

www.airvent.eu

50

100

150

200

250

300

350

400

450

W/m

12111098765 °C

50100150200250300

350400450500550600

W/m

5 6 87 9 10 11 12 °C

0

1000

2000

3000

4000

5000

0,03 0,05 0,07 0,09 0,11 0,13

PS(Pa)/m

qv(l/s)

Diagram 1.Cooling capacity, 157 height

Diagram 2.Cooling capacity, 266 height

Diagram 3.Pressure drop - one loop

PAS-xx-600PAS-xx-450PAS-xx-300

Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz

Page 4: PassiveAir - Cooke Industries · PassiveAir maintains the room temperature at an even level, securing an optimal thermal comfort. The passive chilled . beam works best in areas where

4 14-12-18

PassiveAir

Airvent reserves the right to change specifications.

www.airvent.eu

Dimensions

Dimensions

Size(mm)=L

Width(mm)=A

Number of water circuits

Waterconnection

Suspension bracket quantity

1200

300

450

600

1-circuit Ø 12

2

1500 2

1800 2

2100

1-circuit

2-circuits

Ø 12

Ø 15

3

2400 3

2700 4

3000 4

3300 4

3600 5

Ordering code XX -XXXX -XXX -XXX -X -XProduct acronym PASLength (mm) 1200

1500180021002400270030003600

Width (mm) 300 450 600

Height (mm) simple *) 157double *) 266

Hight of heat exchanger (mm) 50 165 2

Coil connection horizontal Hvertical V

Example: PAS-1200-300-157-1-H*) Aluminium extruded side profile

Specification

A

L

A-10

50157

127

237

266 50

A-10

24

50

78

60

L

60

Cooke Industries - Phone: +64-9-579 2185 Fax: +64-9-579 2181 Email: [email protected] Web: www.cookeindustries.co.nz