  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    1/54

    KR-6RMG2-01A

    GENERAL WALL MOUNTED(60Hz/R22)

    Saudi Arabia

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    2/54

    2 GENERAL WALL MOUNTED

    GENERAL WALL MOUNTED

    Contents

    1. Models Line up .............................................................................6

    2. Nomenclature ...............................................................................7

    3. Features & Benefits......................................................................8

    4. Specifications.............................................................................10

    5. Dimensional Drawings...............................................................14

    6. Wiring Diagrams.........................................................................19

    7. Refrigerant Cycle Diagram ........................................................27

    8. Capacity Tables ..........................................................................28

    9. Capacity Coefficient factor........................................................30

    10. Operation Range ......................................................................31

    11. Air Velocity and Temperature Distribution

    (Reference Data) .......................................................................32

    12. Controller ..................................................................................33

    13. Installation ................................................................................34

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    3/54

    3

    KR-6RMG2-01A

    GENERAL WALL MOUNTED

    Test condition of international standard

    KSC ISO ARI AHAM AS SSA

    9306 5151 210/240 1861.1 385

    Indoor

    DBC(F) 27.0 27.0 26.7(80) 26.7(80) 27.0 29.0

    Cooling WBC(F) 19.5 19.0 19.4(67) 19.4(67) 19.0 19.0

    CapacityOutdoor

    DBC(F) 35.0 35.0 35.0(95) 35.0(95) 35.0 46.0

    WBC(F) 24.0 24.0 23.9(75) 23.9(75) 24.0 24.0

    Indoor

    DBC(F) 20.0 20.0 21.1(70) 21.1(70) 21.0 21.0

    Heating WBC(F) 15.0 15.0 15.6(60) 15.6(60) 15.0 15.5

    CapacityOutdoor

    DBC(F) 7.0 7.0 8.3(47) 8.3(47) 7.0 7.0

    WBC(F) 6.0 6.0 6.1(43) 6.1(43) 6.0 6.0

    Indoor

    DBC(F) 32.0 32.0 26.7(80) 32.2(90) 32.0 29.0Maximum

    WBC(F) 23.0 23.0 19.4(67) 22.8(73) 23.0 19.0Cooling

    Outdoor

    DBC(F) 43.0 43.0 46.1(115) 43.3(110) 43.0 54.0Operating

    WBC(F) 26.0 26.0 23.9(75) 25.6(78) 26.0 24.0

    Indoor

    DBC(F) 27.0 27.0 26.7(80) 26.7(80) - -Maximum

    WBC(F) 19.0 19.0 19.4(67) 22.8(73) - -Heating

    Outdoor

    DBC(F) 21.0 24.0 23.9(75) 23.9(75) - -Operating

    WBC(F) 15.0 18.0 18.3(65) 18.3(65) - -

    EnclosureIndoor

    DBC(F) 27.0 27.0 26.7(80) 26.7(80) 27.0 27.0

    Sweat / WBC(F) 24.0 24.0 23.9(75) 23.9(75) 24.0 24.0

    CondensateOutdoor

    DBC(F) 27.0 27.0 26.7(80) 26.7(80) 27.0 27.0

    Disposal WBC(F) 24.0 24.0 23.9(75) 23.9(75) 24.0 24.0

    Freeze-up/ Indoor DBC(F) 21.0 21.0 19.4(67) 21.1(70) 21.0 21.0

    Low WBC(F) 15.0 15.0 13.9(57) 15.6(60) 16.0 16.0

    Temperature

    Outdoor DBC(F) 21.0 21.0 19.4(67) 21.1(70) 21.0 21.0

    WBC(F) 15.0 15.0 13.9(57) 15.6(60) 16.0 16.0

    KS : Korea Standard AS : Australia Standard

    ISO : International Standard Organization SSA : Saudi Arabian StandardARI : Airconditioning and Refrigeration InstituteAHAM : Association of Home Appliance Manufacturers

    CLASSIFICATION

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    4/54

    4

    KR-6RMG2-01A

    GENERAL WALL MOUNTED

    General Description

    Split type of Air Conditioners are known by the category name of Wall Mounted Type of units.These units can beeasily installed in a small space and have exceptional Cooling capacity.Designed for Low-noise operation,itensures a pleasant air conditioned environment.

    LG Offers various types of units to its customers to suit for the best application and requirement.The following are

    the important categories offered by LG :1) General Wall Mounted Type Units : Units with Simplicity in design.

    2) Art Cool Units : A new concept of cooling introduced by LG in the field of Air Conditioning.

    3) New Gas Models : These models uses HCFC free refrigerant to provide a healthy environment to the world.

    Some of the Important Features of these units are listed below :

    1) Providing Health to the Customers : By having Filters such as Plasma Filter which is capable of removing MicroOrganisms up to 0.1 microns.

    2) Long Term Money Saving : By providing Features such as Gold Fin,Plasma Fin, Auto Clean etc. to maintain thesame performance for years.

    3) Best Comfort : With Features such as Sleep Mode,Timer,Auto Restart etc.

    These Units are available with many standard and optional features which gives our Customers the choice to selectthe unit of their own desire.For details refer to the Detailed specification followed after this description.

    LG Electronics Inc.

    Air Conditioning & Energy Solution Company

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    5/54

    5

    KR-6RMG2-01A

    GENERAL WALL MOUNTED

    Publication history

    PDB No. Product Name Notes Publication in

    KR-6RMG2-01A SRAC 12Models Dec. 2012

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    6/54

    6

    Models Line up KR-6RMG2-01A

    GENERAL WALL MOUNTED

    1. Models Line upGeneral Wall Mounted

    Edition Capacity Chassis Type Model

    #1

    18K SC

    C/O

    LS-C182CRU0

    LS-C182C8C0

    LS-C182CSB2

    H/P

    LS-H182CRU0

    LS-H182C8C0

    LS-H182CSB2

    24K SC

    C/O

    LS-C242CRU0

    LS-C242C8C0

    LS-C242CSB2

    H/P

    LS-H242CRU0

    LS-H242C8C0

    LS-H242CSB2

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    7/54

    7

    NomenclatureKR-6RMG2-01A

    GENERAL WALL MOUNTED

    2. Nomenclature Identification Rule

    Serial Number

    Function

    B: Basic + 4way

    C: Basic + Carbon Filter

    U: Plasma + Allergy Filter + 4Way

    Look/Color

    Chassis NameC: SC

    Electric Rating

    2: 220V, 60Hz

    Capacity

    EX) '18' 18,000Btu/h Class

    Model Type

    C: Cooling OnlyH: Heat Pump

    Product Type

    S: Split

    Refrigerant Type

    L: R22

    Supply Method Diving and Type

    -: SET

    L S C- 81 2 C R U 0

    Chassis Look Classification

    SC

    2 Libero (White+Silver Spray)

    R Libero Artcool

    S S-look

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    8/54

    3. Features & Benefits

    8

    Features & Benefits KR-6RMG2-01A

    GENERAL WALL MOUNTED

    SmokeAway GoldFin TropicalCompressor

    StylishDesign

    Quick & EasyInstallation

    Skew Fan DualProtection Filter

    Vane &Louver

    Extreme Durability

    The advanced tropical compressor withstandsextreme weather conditions, enabling theproduct to operate despite high outside tem-perature.

    By adopting gold plated fins in the exteriorunit, the heat exchanger is protected from cor-rosion and wear from external conditions.

    The combination of tropical compressor,and the gold fin in the exterior unit allcontribute in the improved durability of LG airconditioner.

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    9/54

    9

    Features & BenefitsKR-6RMG2-01A

    GENERAL WALL MOUNTED

    Power Cooling

    Perfect Health Care

    Energy Saving

    Stylish Design

    Quick & Easy Installation

    20m Windblast : Strong and cool windblastcovers the distance of 20m.

    Optimized Airflow : The interior of the com-pressor in the outdoor unit has been construct-ed to minimze the sound produced when oper-ating.

    The cool airflow reaches thedistance of 15m to all corners ofthe room, keeping the space cooland comfortable regardless ofoutside temperature.

    Smoke Away : 3 million ionsspread from diffusion charger and 3M MicroProtection filter remove smoke particle asmuch as air-purifier removes.* Test Results

    Size of Area : 30m3, CADR : 135

    Dual Protection Filter : Dual Protection Filterinitially captures dust in the air that comes into the air conditioner.

    Filter : While being easy to main-tain, the powerful plasma filtration system ofLG air conditioner protects the user from odorand any harmful substances floating in air.

    3M Multi Protection Filter : 3M MultiProtection filter captures dust, virus and aller-gen and deactivates the captured virus andallergen by unique technologies of LG and 3M.

    Various filtration system protects the userfrom all harmful substances including odor,bacteria, and allergen

    Inverter V : The advanced inverter technologyof LG enables the user of the air conditioner touse more and save more.

    State of the art heat exchanger, air outlet,compressor, and inverter technology providethe worlds highest energy efficiency

    The design of LG air conditioners are stylish ina way that is incomparable to others. Think of

    it not just as an air conditioner, but an objetthat will lighten up your living room.

    LG air conditioners are not just refreshinglyefficient, but also exceptionally elegant indesign

    Perfect finishing / Bigger tubing space / Installationplate improvement / Detachable bottom cover /Elevated service valve / Installation support clip /Compatible with inverter multi system

    Installation has never been easier as with thedelicately designed installation elements ofLG air conditioners

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    10/54

    10

    Specifications KR-6RMG2-01A

    GENERAL WALL MOUNTED

    4. SpecificationsGeneral Wall Mounted(#1)

    Note:

    O : Applied, - : No relation* For circuit breaker rating, please conform to local standards wherever nec-

    essary.

    Some of functions are slightly different depending upon models. The specification may be subject to change without notic for purpose of

    improvement.

    Cooling Capacity kWBtu/h.

    Heating Capacity kWBtu/h.

    Power Input Cooling/Heating W

    Running Current Cooling/Heating AStarting Current Cooling/Heating AEER W/W

    Btu/h.WCOP W/WPower Supply / V / HzPower Factor %Air Flow Rate Indoor,Max m3/min(CFM)

    Outdoor,Max m3/min(CFM)Moisture Removal l/h.Sound Level Indoor,H/M/L dB(A)3

    Outdoor,Max dB(A)3Refrigerant & Charge (at 7.5 m) g(oz)Additional Refrigerant charge g/m (oz/ft)Compressor Type

    ModelMotor TypeOil Type

    Oil Charge ccO.L.P. name

    Fan(Indoor) TypeMotor Output W

    Fan(Outdoor) TypeMotor TypeMotor Output W

    Circuit Breaker* APower Supply Cable No.*mm2

    Power and Transmission Cable No.*mm2 No.*mm2

    Piping Connections Liquid Side mm(in)Gas Side mm(in)

    Drain Hose O.D / I.D mm(in)Dimensions Indoor (W*H*D) mm

    inchOutdoor (W*H*D) mm

    inchNet Weight Indoor kg(lbs)

    Outdoor kg(lbs)Operation Range Cooling(Outdoor) C(F)

    Heating(Outdoor) C(F)Max. Piping Length m(ft)Max. Elevation Difference m(ft)Tool Code(Chassis) Indoor + OutdoorFunctions Temperature Control

    Plasma FilterPrefilter(washable/anti-fungus)Auto CleanCHAOS Wind(Auto Wind)Steps, Fan/Cool/HeatAirflow Direction Control(up & Down)Airflow Direction Control(left & right)Remote Controller TypeSetting Temperature Range Cooling

    HeatingTemperature IncrementAuto Operation (Micom Control)

    Auto Changeover (Micom Control)Self DiagnosisTimerSleep OperationSoft Dry OperationRestart Delay(minute)Deice Control(Defrost)Hot StartJet CoolLow Ambient OperationSpecial Function

    Models LS-C182CSB2 LS-C182C8C0 LS-C182CRU0

    5.0517,230

    --

    1,910/-

    9.0/--

    2.649.02

    -1/ 220 / 60

    96.4614.0 (494)

    42.0 (1.483)1.8

    40/38/3454

    1300 (45.9)20(0.21)Rotary

    QJ258KEAPSC

    SUNISO 4GSI

    500Internal

    SKEW FLOW FAN19

    Propeller FanAC INDUCTION

    66.320

    3*1.5(Including Earth)3*1.5(Including Earth)

    6.35(1/4)15.88((5/8)

    21.5,16(0.85,0.63)1,030*325*26040.6*12.8*10.2801*555*262

    31.5*21.9*10.317(37.5)37(81.6)

    21~54(69.8~129.2)-

    20(65.6)15(49.2)SC+UD

    Thermistor-O-O

    3/4/-OO

    Wireless LCD18 ~ 30

    -1O

    -O

    24h, On/OffOO3--O--

    5.0517,230

    --

    1,910/-

    9.0/--

    2.649.02

    -1/ 220 / 60

    96.4614.0 (494)

    42.0 (1.483)1.8

    40/38/3454

    1300 (45.9)20(0.21)Rotary

    QJ258KEAPSC

    SUNISO 4GSI

    500Internal

    SKEW FLOW FAN19

    Propeller FanAC INDUCTION

    66.320

    3*1.5(Including Earth)3*1.5(Including Earth)

    6.35(1/4)15.88((5/8)

    21.5,16(0.85,0.63)1,030*325*24540.6*12.8*9.6801*555*262

    31.5*21.9*10.317(37.5)37(81.6)

    21~54(69.8~129.2)-

    20(65.6)15(49.2)SC+UD

    ThermistorOOOO

    3/4/-OO

    Wireless LCD18 ~ 30

    -1O

    -O

    24h, On/OffOO3--O--

    5.0517,230

    --

    1,910/-

    9.0/--

    2.649.02

    -1/ 220 / 60

    96.4614.0 (494)

    42.0 (1.483)1.8

    40/38/3454

    1300 (45.9)20(0.21)Rotary

    QJ258KEAPSC

    SUNISO 4GSI

    500Internal

    SKEW FLOW FAN19

    Propeller FanAC INDUCTION

    66.320

    3*1.5(Including Earth)3*1.5(Including Earth)

    6.35(1/4)15.88((5/8)

    21.5,16(0.85,0.63)1,030*325*24540.6*12.8*9.6801*555*262

    31.5*21.9*10.317(37.5)37(81.6)

    21~54(69.8~129.2)-

    20(65.6)15(49.2)SC+UD

    ThermistorOOOO

    3/4/-OO

    Wireless LCD18 ~ 30

    -1O

    -O

    24h, On/OffOO3--O--

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    11/54

    11

    SpecificationsKR-6RMG2-01A

    GENERAL WALL MOUNTED

    Cooling Capacity kWBtu/h.

    Heating Capacity kWBtu/h.

    Power Input Cooling/Heating W

    Running Current Cooling/Heating AStarting Current Cooling/Heating AEER W/W

    Btu/h.WCOP W/WPower Supply / V / HzPower Factor %Air Flow Rate Indoor,Max m3/min(CFM)

    Outdoor,Max m3/min(CFM)Moisture Removal l/h.Sound Level Indoor,H/M/L dB(A)3Outdoor,Max dB(A)3Refrigerant & Charge (at 7.5 m) g(oz)Additional Refrigerant charge g/m(oz/ft)Compressor Type

    ModelMotor TypeOil Type

    Oil Charge ccO.L.P. name

    Fan(Indoor) TypeMotor Output W

    Fan(Outdoor) TypeMotor TypeMotor Output W

    Circuit Breaker* APower Supply Cable No.*mm2

    Power and Transmission Cable No.*mm2 No.*mm2

    Piping Connections Liquid Side mm(in)Gas Side mm(in)

    Drain Hose O.D / I.D mm(in)Dimensions Indoor (W*H*D) mm

    inchOutdoor (W*H*D) mm

    inchNet Weight Indoor kg(lbs)

    Outdoor kg(lbs)Operation Range Cooling(Outdoor) C(F)

    Heating(Outdoor) C(F)Max. Piping Length m(ft)Max. Elevation Difference m(ft)Tool Code(Chassis) Indoor + OutdoorFunctions Temperature Control

    Plasma FilterPrefilter(washable/anti-fungus)Auto CleanCHAOS Wind(Auto Wind)Steps, Fan/Cool/HeatAirflow Direction Control(up & Down)Airflow Direction Control(left & right)Remote Controller TypeSetting Temperature Range Cooling

    HeatingTemperature IncrementAuto Operation (Micom Control)

    Auto Changeover (Micom Control)Self DiagnosisTimerSleep OperationSoft Dry OperationRestart Delay(minute)Deice Control(Defrost)Hot StartJet CoolLow Ambient OperationSpecial Function

    Models LS-H182CSB2 LS-H182C8C0 LS-H182CRU0

    5.3718,320

    5.4218,500

    2,030/1,750

    9.7/8.5-

    2.659.023.1

    1/ 220 / 6095.13

    15.0 (530)42.0 (1.483)

    1.840/38/34

    541200 (42.3)

    20(0.21)Rotary

    QJ278KCFPSC

    NM56 or 4GSI

    500Internal

    SKEW FLOW FAN20.6

    Propeller FanAC INDUCTION

    76.520

    3*1.5(Including Earth)3*1.5(Including Earth)+2*0.75

    6.35(1/4)15.88((5/8)

    21.5,16(0.85,0.63)1,030 * 325 * 26040.6 * 12.8 * 10.2

    840*577*27633.1*22.7*10.9

    17 (37.5)43 (94.8)

    21~54(69.8~129.2)1~24(33.8~75.2)

    20(65.6)15(49.2)SC+UM

    Thermistor-O-O

    3/4/3OO

    Wireless LCD18 ~ 3016 ~ 30

    1-

    OO

    24h, On/OffOO3OOO--

    5.3718,320

    5.4218,500

    2,030/1,750

    9.7/8.5-

    2.659.023.1

    1/ 220 / 6095.13

    15.0 (530)42.0 (1.483)

    1.840/38/34

    541200 (42.3)

    20(0.21)Rotary

    QJ278KCFPSC

    NM56 or 4GSI

    500Internal

    SKEW FLOW FAN20.6

    Propeller FanAC INDUCTION

    76.520

    3*1.5(Including Earth)3*1.5(Including Earth)+2*0.75

    6.35(1/4)15.88((5/8)

    21.5,16(0.85,0.63)1,030 * 325 * 24540.6 * 12.8 * 10.2

    840*577*27633.1*22.7*10.9

    17(37.5)43(94.8)

    21~54(69.8~129.2)1~24(33.8~75.2)

    20(65.6)15(49.2)SC+UM

    ThermistorOOOO

    3/4/3OO

    Wireless LCD18 ~ 3016 ~ 30

    1-

    OO

    24h, On/OffOO3OOO--

    5.3718,320

    5.4218,500

    2,030/1,750

    9.7/8.5-

    2.659.023.1

    1/ 220 / 6095.13

    15.0 (530)42.0 (1.483)

    1.840/38/34

    541200 (42.3)

    20(0.21)Rotary

    QJ278KCFPSC

    NM56 or 4GSI

    500Internal

    SKEW FLOW FAN20.6

    Propeller FanAC INDUCTION

    76.520

    3*1.5(Including Earth)3*1.5(Including Earth)+2*0.75

    6.35(1/4)15.88((5/8)

    21.5,16(0.85,0.63)1,030 * 325 * 24540.6 * 12.8 * 10.2

    840*577*27633.1*22.7*10.9

    17(37.5)43(94.8)

    21~54(69.8~129.2)1~24(33.8~75.2)

    20(65.6)15(49.2)SC+UM

    ThermistorOOOO

    3/4/3OO

    Wireless LCD18 ~ 3016 ~ 30

    1-

    OO

    24h, On/OffOO3OOO--

    Note:

    O : Applied, - : No relation* For circuit breaker rating, please conform to local standards wherever nec-

    essary.

    Some of functions are slightly different depending upon models. The specification may be subject to change without notic for purpose of

    improvement.

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    12/54

    12

    Specifications KR-6RMG2-01A

    GENERAL WALL MOUNTED

    Cooling Capacity kWBtu/h

    Heating Capacity kWBtu/h

    Power Input Cooling/Heating W

    Running Current Cooling/Heating A Starting Current Cooling/Heating A EER W/W

    Btu/h.WCOP W/WPower Supply / V / Hz

    Power Factor %Air Flow Rate Indoor,Max m3/min(cfm)

    Outdoor,Max m3/min(cfm)Moisture Removal l/hSound Level Indoor,H/M/L dB(A)3

    Outdoor,Max dB(A)3Refrigerant & Charge(at 7.5m) g(oz)Additional Refrigerant Charge g/m(oz/ft)Compressor Type

    ModelMotor TypeOil Type

    Oil Charge ccO.L.P Name

    Fan(Indoor) TypeMotor Output W

    Fan(outdoor) TypeMotor TypeMotor Output W

    Circuit Breaker* APower Supply Cable No.*mm2 Power and Transmission Cable No.*mm2 No.*mm2 Piping Liquid Side mm(in)Connections Gas Side mm(in)Drain Hose O.D / I.D mm(in)Dimension Indoor(W*H*D) mm

    inchOutdoor(W*H*D) mm

    inchNet Weight Indoor kg(lbs)

    Outdoor kg(lbs)Operation Range Cooling(Outdoor) C(F)

    Heating(Outdoor) C(F)Max. Piping Length m(ft)Max. Elevation Difference m(ft)Tool Code(Chassis) Indoor + OutdoorFunctions Temperature Control

    Plasma FilterPrefilter(washable/anti-fungus)Auto CleanCHAOS Wind(Auto Wind)Steps, Fan/Cool/HeatAirflow Direction Control(up&down)Airflow Direction Control(left&right)Remote Controller Type

    Setting Temperature CoolingRange HeatingTemperature IncrementAuto Operation (Micom Control)

    Auto Changeover (Micom Control)Self DiagnosisTimerSleep OperationSoft Dry OperationRestart Delay(minute)Deice Control(Defrost)Hot StartJet CoolLow Ambient OperationSpecial Function

    Models LS-C242CSB2 LS-C242C8C0 LS-C242CRU0

    6.7423,000

    --

    2,550/-

    12.0/--

    2.649.02

    -1/ 220 / 60

    96.5919.0(671)

    42.0(1,484)2.8

    43/40/3454

    1400 (49.3)30(0.32)Rotary

    QP348KD24BPSC

    SUNISO 4GSI

    700Internal

    SKEW FLOW FAN30

    Propeller FanAC INDUCTION

    7330

    3*2.5(Including Earth)3*2.5(Including Earth)

    9.52(3/8)15.88((5/8)

    21.5,16(0.85,0.63)1,030*325*26040.6*12.8*10.2840*577*276

    33.1*22.7*10.917(37.5)

    48(105.8)21~54(69.8~129.2)

    -20(65.6)15(49.2)SC+UM

    Thermistor-O-O

    3/4/-OO

    Wireless LCD18 ~ 30

    -1O

    -O

    24h, On/OffOO3--O--

    6.7423,000

    --

    2,550/-

    12.0/--

    2.649.02

    -1/ 220 / 60

    96.5919.0(671)

    42.0(1,484)2.8

    43/40/3454

    1400 (49.3)30(0.32)Rotary

    QP348KD24BPSC

    SUNISO 4GSI

    700Internal

    SKEW FLOW FAN30

    Propeller FanAC INDUCTION

    7330

    3*2.5(Including Earth)3*2.5(Including Earth)

    9.52(3/8)15.88((5/8)

    21.5,16(0.85,0.63)1,030*325*24540.6*12.8*9.6840*577*276

    33.1*22.7*10.917(37.5)48(105.8)

    21~54(69.8~129.2)-

    20(65.6)15(49.2)SC+UM

    ThermistorOOOO

    3/4/-OO

    Wireless LCD18 ~ 30

    -1O

    -O

    24h, On/OffOO3--O--

    6.7423,000

    --

    2,550/-

    12.0/--

    2.649.02

    -1/ 220 / 60

    96.5919.0(671)

    42.0(1,484)2.8

    43/40/3454

    1400 (49.3)30(0.32)Rotary

    QP348KD24BPSC

    SUNISO 4GSI

    700Internal

    SKEW FLOW FAN30

    Propeller FanAC INDUCTION

    7330

    3*2.5(Including Earth)3*2.5(Including Earth)

    9.52(3/8)15.88((5/8)

    21.5,16(0.85,0.63)1,030*325*24540.6*12.8*9.6840*577*276

    33.1*22.7*10.917(37.5)48(105.8)

    21~54(69.8~129.2)-

    20(65.6)15(49.2)SC+UM

    ThermistorOOOO

    3/4/-OO

    Wireless LCD18 ~ 30

    -1O

    -O

    24h, On/OffOO3--O--

    Note:

    O : Applied, - : No relation

    * For circuit breaker rating, please conform to local standards wherever nec-

    essary.

    Some of functions are slightly different depending upon models.

    The specification may be subject to change without notic for purpose of

    improvement.

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    13/54

    13

    SpecificationsKR-6RMG2-01A

    GENERAL WALL MOUNTED

    Note:

    O : Applied, - : No relation

    * For circuit breaker rating, please conform to local standards wherever nec-

    essary.

    Some of functions are slightly different depending upon models.

    The specification may be subject to change without notic for purpose of

    improvement.

    Models LS-H242CSB2

    Cooling CapacitykW 6.72

    Btu/h. 22,930

    Heating CapacitykW 7.03

    Btu/h. 24,000

    Power InputCooling

    W2,690

    Heating 2,550

    Running CurrentCooling

    A12.5

    Heating 11.8Starting Current Cooling/Heating A -

    EERW/W 2.50

    Btu/h.W 8.52COP W/W 2.76Power Supply / V / Hz 1/ 220 / 60Power Factor % 96

    Air Flow RateIndoor,Max m3/min(CFM) 19.0 (671)Outdoor,Max m3/min(CFM) 42.0 (1.483)

    Moisture Removal l/h. 2.8Sound Level Indoor,H/M/L dB(A)3 43/40/34Outdoor,Max dB(A)3 54Refrigerant & Charge (at 7.5 m) g(oz) 1550 (54.7)Additional Refrigerant charge g/m(oz/ft) 30(0.32)

    Compressor

    Type RotaryModel QP362KABMotor Type PSC

    Oil Type NM56 or 4GSIOil Charge cc 700O.L.P. name Internal

    Fan(Indoor)Type SKEW FLOW FANMotor Output W 19

    Fan(Outdoor)Type Propeller FanMotor Type AC INDUCTIONMotor Output W 67.2

    Circuit Breaker* A 30Power Supply Cable No.*mm2 3*2.5(Including Earth)Power and Transmission Cable No.*mm2 3*2.5(Including Earth)+2*0.75

    Piping ConnectionsLiquid Side mm(in) 9.52(3/8)Gas Side mm(in) 15.88((5/8)

    Drain Hose O.D / I.D mm(in) 21.5,16(0.85,0.63)

    DimensionsIndoor (W*H*D)

    mm 1,030*320*245inch 40.5*12.6*9.6

    Outdoor (W*H*D)mm 870*655*320inch 34.3*25.8*12.6

    Net WeightIndoor kg(lbs) 17(37.5)Outdoor kg(lbs) 64(141.1)

    Operation RangeCooling(Outdoor) C(F) 21~54(69.8~129.2)Heating(Outdoor) C(F) 1~24(33.8~75.2)

    Max. Piping Length m(ft) 20(65.6)Max. Elevation Difference m(ft) 15(49.2)Tool Code(Chassis) Indoor + Outdoor SC+UE

    Functions

    Temperature Control ThermistorPlasma Filter -Prefilter(washable/anti-fungus) OAuto Clean -CHAOS Wind(Auto Wind) OSteps, Fan/Cool/Heat 3/4/3Airflow Direction Control(up & Down) OAirflow Direction Control(left & right) ORemote Controller Type Wireless LCDSetting TemperatureRange

    Cooling 18 ~ 30Heating 16 ~ 30

    Temperature Increment 1

    Auto Operation (Micom Control) -Auto Changeover (Micom Control) OSelf Diagnosis OTimer 24h, On/OffSleep Operation OSoft Dry Operation ORestart Delay(minute) 3Deice Control(Defrost) OHot Start OJet Cool OLow Ambient Operation -Special Function -

    6.5522,3506.90

    23,5402,690

    2,55012.511.8

    -2.438.312.71

    1/ 220 / 6096.00

    19.0 (671)42.0 (1.483)

    2.843/40/34

    541550 (54.7)

    30(0.32)Rotary

    QP362KABPSC

    NM56 or 4GSI700

    InternalSKEW FLOW FAN

    19Propeller Fan

    AC INDUCTION67.230

    3*2.5(Including Earth)3*2.5(Including Earth)+2*0.75

    9.52(3/8)15.88((5/8)

    21.5,16(0.85,0.63)1,030*320*24540.5*12.6*9.6870*655*320

    34.3*25.8*12.617(37.5)64(141.1)

    21~54(69.8~129.2)1~24(33.8~75.2)

    20(65.6)15(49.2)SC+UE

    ThermistorOOOO

    3/4/3OO

    Wireless LCD18 ~ 3016 ~ 30

    1

    -OO

    24h, On/OffOO3OOO--

    6.5522,3506.90

    23,5402,690

    2,55012.511.8

    -2.438.312.71

    1/ 220 / 6096.00

    19.0 (671)42.0 (1.483)

    2.843/40/34

    541550 (54.7)

    30(0.32)Rotary

    QP362KABPSC

    NM56 or 4GSI700

    InternalSKEW FLOW FAN

    19Propeller Fan

    AC INDUCTION67.230

    3*2.5(Including Earth)3*2.5(Including Earth)+2*0.75

    9.52(3/8)15.88((5/8)

    21.5,16(0.85,0.63)1,030*320*24540.5*12.6*9.6870*655*320

    34.3*25.8*12.617(37.5)

    64(141.1)21~54(69.8~129.2)1~24(33.8~75.2)

    20(65.6)15(49.2)SC+UE

    ThermistorOOOO

    3/4/3OO

    Wireless LCD18 ~ 3016 ~ 30

    1

    -OO

    24h, On/OffOO3OOO--

    LS-H242C8C0 LS-H242CRU0

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    14/54

    14

    Dimensional Drawings KR-6RMG2-01A

    GENERAL WALL MOUNTED

    LiberoARTC

    OOL

    CHASSISC

    ODE:SC

    3

    2

    1

    70

    70

    69

    56

    Rightrear

    piping

    Leftrear

    piping

    InstallationPlate

    MeasuringTape

    MeasuringTape

    Hanger

    Placealevelonraisedtab

    UnitOutlin

    e

    207

    105

    (Unit:mm)

    460

    570

    4

    5. Dimensional Drawings5.1 Indoor Unit

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    15/54

    15

    Dimensional DrawingsKR-6RMG2-01A

    GENERAL WALL MOUNTED

    250

    1030

    325210

    70

    70

    69

    56

    Rightrear

    pip

    ing

    Leftrear

    piping

    InstallationPlate

    MeasuringTape

    MeasuringTape

    Hanger

    Placealevelonraisedtab

    UnitOutline

    207

    105

    (Unit:mm)

    460

    570

    LiberoR/E

    CHASSISC

    ODE:SC

    4

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    16/54

    16

    Dimensional Drawings KR-6RMG2-01A

    GENERAL WALL MOUNTED

    5.2 Outdoor Unit

    71

    1

    4 2 3

    5

    840

    639.4

    321.8

    276

    336.4

    840

    299.8

    508.5

    290.3

    486

    62 70

    16.4

    276

    560.6

    GasPipeConnectionPort

    PartName

    AirDichargeGrille

    LiquidPipeConnectionPort

    ControlBox

    No.

    2 4

    EarthScrew

    531

    R

    emark

    Note

    1.Theun

    itshouldbeinstalledaccordingtoinstallationmanualwhichis

    inthep

    roductbox.

    2.Inana

    reaoraapacehavingnoproperaircirculation,anairguide

    should

    beinstalledintheoutdoorunit.

    76,Seongsan-dong,ChangwonCity,Gyeongnam,

    641-713,Korea

    www.lge.com/aircon

    ditioner

    CHASSISCOD

    E:UM

    OutdoorU

    nit

    Unit:mm

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    17/54

    17

    Dimensional DrawingsKR-6RMG2-01A

    GENERAL WALL MOUNTED

    801

    593

    303

    339

    262

    801

    257.8

    448.4

    259

    79.5

    158

    555

    25.4

    262

    57.4

    424.5

    5

    1

    2 34

    36

    GasPipeConnectionPort

    PartName

    AirDichargeGrille

    LiquidPipeConnectionPort

    ControlBox

    No.

    2 4

    EarthScrew

    531

    R

    emark

    Note

    1.Theun

    itshouldbeinstalledaccordingtoinstallationmanualwhichis

    inthep

    roductbox.

    2.Inana

    reaoraapacehavingnoproperaircirculation,anairguide

    should

    beinstalledintheoutdoorunit.

    76,Seongsan-dong,ChangwonCity,Gyeongnam,

    641-713,Korea

    www.lge.com/aircon

    ditioner

    CHASSISCOD

    E:UD

    OutdoorU

    nit

    Unit:mm

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    18/54

    18

    Dimensional Drawings KR-6RMG2-01A

    GENERAL WALL MOUNTED

    1

    GasPipeConnectionPort

    PartName

    AirDichargeGrille

    LiquidPipeConnectionPort

    ControlBox

    No.

    2 4

    EarthScrew

    531

    R

    emark

    Note

    1.Theun

    itshouldbeinstalledaccordingtoinstallationmanualwhichis

    inthep

    roductbox.

    2.Inana

    reaoraapacehavingnoproperaircirculation,anairguide

    should

    beinstalledintheoutdoorunit.

    76,Seongsan-dong,ChangwonCity,Gyeongnam,

    641-713,Korea

    www.lge.com/aircon

    ditioner

    CHASSISCOD

    E:UE

    OutdoorU

    nit

    Unit:mm

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    19/54

    19

    Wiring DiagramsKR-6RMG2-01A

    GENERAL WALL MOUNTED

    6. Wiring Diagrams6.1 Indoor Units

    CN-MOTOR

    CN-U/D

    CN-L/R

    CN-

    OPTION

    CN-DISP3

    CN-HVB

    CN-12V

    CN-TH1

    CN-

    DISP2

    CN-SUB

    Model: LS-C182CRU0, LS-C242CRU0

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    20/54

    20

    Wiring Diagrams KR-6RMG2-01A

    GENERAL WALL MOUNTED

    Model: LS-H182CRU0, LS-H242CRU0

    CN-U/D

    CN-L/R

    CN-DISP3

    CN-SUB

    CN-

    OPTION

    CN-HVB

    CN-12V

    CN-TH1

    CN-

    DISP2

    CN-4WAY

    CN-MOTOR

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    21/54

    21

    Wiring DiagramsKR-6RMG2-01A

    GENERAL WALL MOUNTED

    Model: LS-C182C8C0, LS-C242C8C0

    CN-MOTOR

    CN-U/D

    CN-L/R

    CN-

    OPTION

    CN-DISP3

    CN-HVB

    CN-12V

    CN-TH1

    CN-

    DISP2

    CN-SUB

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    22/54

    22

    Wiring Diagrams KR-6RMG2-01A

    GENERAL WALL MOUNTED

    Model: LS-H182C8C0, LS-H242C8C0

    CN-U/D

    CN-L/R

    CN-DISP3

    CN-SUB

    CN-

    OPTION

    CN-HVB

    CN-12V

    CN-TH1

    CN-

    DISP2

    CN-4WAY

    CN-MOTOR

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    23/54

    23

    Wiring DiagramsKR-6RMG2-01A

    GENERAL WALL MOUNTED

    Model: LS-C182CSB2, LS-C242CSB2

    CN-MOTOR

    CN-U/D

    CN-L/R

    CN-

    OPTION

    CN-DISP3

    CN-HVB

    CN-12V

    CN-TH1

    CN-

    DISP2

    CN-SUB

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    24/54

    24

    Wiring Diagrams KR-6RMG2-01A

    GENERAL WALL MOUNTED

    Model: LS-H182CSB2, LS-H242CSB2

    CN-U/D

    CN-L/R

    CN-DISP3

    CN-SUB

    CN-

    OPTION

    CN-HVB

    CN-12V

    CN-TH1

    CN-

    DISP2

    CN-4WAY

    CN-MOTOR

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    25/54

    25

    Wiring DiagramsKR-6RMG2-01A

    GENERAL WALL MOUNTED

    Capacitor

    Terminal Block

    Fuse

    Model: LS-C182CRU0, LS-C242CRU0, LS-C182C8C0, LS-C242C8C0, LS-C182CSB2, LS-C242CSB2

    6.2 Outdoor Unit

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    26/54

    26

    Wiring Diagrams KR-6RMG2-01A

    GENERAL WALL MOUNTED

    TerminalBlock

    Capacitor

    Model: LS-H182CRU0, LS-H242CRU0, LS-H182C8C0, LS-H242C8C0, LS-H182CSB2, LS-H242CSB2

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    27/54

    27

    Refrigerant Cycle DiagramKR-6RMG2-01A

    GENERAL WALL MOUNTED

    7. Refrigerant Cycle Diagram

    tinUroodtuOtinUroodnI

    HeatExchanger(Evaporator)

    HeatExchanger(Condenser)

    Capillary Tube

    Compressor

    Accumulator

    Gas Side

    3-Way Valve

    3-Way Valve

    Liquid Side

    Cooling

    Th1

    Th2

    rotcennoCBCPnoitpircseD.COL

    Th1 Thermistor for indoor air temperatureCN-TH1

    Th2 Thermistor for evaporating temperature

    tinUroodtuOtinUroodnI

    HeatExchanger(Evaporator)

    HeatExchanger(Condenser)

    Capillary Tube

    CompressorAccumulator

    Gas Side

    3-Way Valve

    2-Way Valve

    Liquid Side

    Cooling

    Heating

    Reversing Valve

    Th1

    Th2

    Model: LS-C182CRU0, LS-C242CRU0, LS-C182C8C0, LS-C242C8C0, LS-C182CSB2, LS-C242CSB2

    Model: LS-H182CRU0, LS-H242CRU0, LS-H182C8C0, LS-H242C8C0, LS-H182CSB2, LS-H242CSB2

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    28/54

    28

    Capacity Tables KR-6RMG2-01A

    GENERAL WALL MOUNTED

    8. Capacity Tables

    LS-C182CRU0, LS-C182C8C0, LS-C182CSB2

    Cooling capacity

    CWB CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14 20 4.40 3.41 1.30 4.30 3.37 1.55 4.10 3.28 1.80 3.98 3.21 1.90 3.83 3.14 2.02 3.74 3.10 2.09

    16 22 5.13 3.87 1.32 5.02 3.83 1.57 4.79 3.72 1.83 4.64 3.64 1.93 4.47 3.55 2.05 4.37 3.50 2.12

    18 25 5.73 4.21 1.34 5.60 4.16 1.59 5.34 4.03 1.86 5.18 3.94 1.96 4.99 3.84 2.08 4.87 3.78 2.15

    19 27 5.99 4.35 1.37 5.86 4.30 1.62 5.59 4.16 1.89 5.42 4.07 1.99 5.22 3.96 2.12 5.10 3.90 2.19

    22 30 6.58 4.61 1.38 6.44 4.55 1.64 6.13 4.40 1.91 5.95 4.29 2.02 5.73 4.18 2.14 5.60 4.10 2.21

    24 32 6.82 4.69 1.40 6.68 4.62 1.66 6.37 4.46 1.94 6.17 4.35 2.04 5.95 4.23 2.17 5.81 4.15 2.25

    Indoor Air

    Temperature

    Outdoor Air Temperature : CDB

    20 25 32 35 40 43

    CWB CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

    14 20 4.40 3.36 1.30 4.30 3.33 1.55 4.10 3.24 1.80 3.98 3.17 1.90 3.83 3.10 2.02 3.74 3.06 2.09

    16 22 5.13 3.82 1.32 5.02 3.78 1.57 4.79 3.67 1.83 4.64 3.59 1.93 4.47 3.50 2.05 4.37 3.45 2.12

    18 25 5.73 4.15 1.34 5.60 4.10 1.59 5.34 3.98 1.86 5.18 3.89 1.96 4.99 3.79 2.08 4.87 3.73 2.15

    19 27 5.99 4.29 1.37 5.86 4.24 1.62 5.59 4.11 1.89 5.42 4.01 1.99 5.22 3.91 2.12 5.10 3.85 2.19

    22 30 6.58 4.55 1.38 6.44 4.49 1.64 6.13 4.34 1.91 5.95 4.24 2.02 5.73 4.12 2.14 5.60 4.05 2.21

    24 32 6.82 4.63 1.40 6.68 4.56 1.66 6.37 4.40 1.94 6.17 4.29 2.04 5.95 4.17 2.17 5.81 4.10 2.25

    Indoor Air

    Temperature

    Outdoor Air Temperature : CDB

    20 25 32 35 40 43

    CWB CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

    14 20 5.70 4.18 1.77 5.58 4.14 2.10 5.32 4.03 2.44 5.16 3.95 2.58 4.97 3.86 2.74 4.86 3.81 2.8316 22 6.66 4.75 1.80 6.52 4.70 2.13 6.21 4.56 2.48 6.02 4.47 2.62 5.80 4.36 2.78 5.66 4.29 2.87

    18 25 7.43 5.16 1.82 7.27 5.11 2.16 6.93 4.95 2.52 6.72 4.84 2.66 6.47 4.72 2.82 6.32 4.64 2.92

    19 27 7.77 5.34 1.85 7.61 5.28 2.20 7.25 5.11 2.56 7.03 4.99 2.70 6.77 4.87 2.87 6.62 4.79 2.97

    22 30 8.53 5.66 1.88 8.35 5.59 2.23 7.96 5.40 2.60 7.72 5.27 2.73 7.43 5.13 2.91 7.26 5.04 3.00

    24 32 8.85 5.76 1.91 8.67 5.68 2.26 8.26 5.48 2.63 8.01 5.35 2.77 7.71 5.19 2.95 7.53 5.10 3.05

    Indoor Air

    Temperature

    Outdoor Air Temperature : CDB

    20 25 32 35 40 43

    SymbolDB : Dry bulb temperature [C]WB : Wet bulb temperature [C]TC : Total capacity [kW]SHC : Sensible capacity [kW]PI : Power Input [kW]

    (Comp.+ indoor fan motor+outdoor fan motor)

    Notes1. All capacites are net, evaporator fan motor heat is deducted.2. Indicates nominal capacity.3. Direct interpolation is permissible. Do not extrapolate4. Capacities are based on the following conditions:

    - Interconnecting Piping Length 7.5m- Level Difference of Zero.

    LS-H182CRU0, LS-H182C8C0, LS-H182CSB2

    LS-C242CRU0, LS-C242C8C0, LS-C242CSB2

    CWB CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

    14 20 5.70 4.24 1.87 5.58 4.20 2.21 5.32 4.09 2.58 5.16 4.00 2.72 4.97 3.92 2.89 4.86 3.86 2.99

    16 22 6.66 4.82 1.90 6.52 4.77 2.25 6.21 4.63 2.62 6.02 4.53 2.76 5.80 4.42 2.94 5.66 4.35 3.03

    18 25 7.43 5.24 1.93 7.27 5.18 2.28 6.93 5.02 2.66 6.72 4.91 2.80 6.47 4.78 2.98 6.32 4.71 3.08

    19 27 7.77 5.41 1.96 7.61 5.35 2.32 7.25 5.18 2.71 7.03 5.06 2.85 6.77 4.93 3.03 6.62 4.85 3.13

    22 30 8.53 5.74 1.98 8.35 5.67 2.35 7.96 5.48 2.74 7.72 5.35 2.89 7.43 5.20 3.07 7.26 5.11 3.17

    24 32 8.85 5.84 2.01 8.67 5.76 2.38 8.26 5.56 2.78 8.01 5.42 2.93 7.71 5.27 3.11 7.53 5.17 3.22

    Indoor Air

    Temperature

    Outdoor Air Temperature : CDB

    20 25 32 35 40 43

    LS-H242CRU0, LS-H242C8C0, LS-H242CSB2

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    29/54

    29

    Capacity TablesKR-6RMG2-01A

    GENERAL WALL MOUNTED

    LS-H182CRU0, LS-H182C8C0, LS-H182CSB2

    CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI

    16 3.86 1.34 4.55 1.47 5.26 1.60 5.52 1.65 5.79 1.70 6.12 1.72 6.62 1.82 7.31 1.94

    18 3.74 1.39 4.40 1.52 5.09 1.65 5.35 1.70 5.60 1.75 5.92 1.78 6.41 1.88 7.08 2.01

    20 3.63 1.43 4.27 1.57 4.94 1.71 5.19 1.76 5.44 1.81 5.71 1.84 6.22 1.94 6.86 2.08

    22 3.49 1.48 4.12 1.62 4.76 1.76 5.00 1.81 5.24 1.87 5.54 1.90 5.99 2.00 6.62 2.14

    24 3.37 1.52 3.98 1.67 4.60 1.81 4.83 1.87 5.06 1.93 5.35 1.96 5.79 2.06 6.39 2.21

    Indoor Air

    Temperature

    Outdoor Air Temperature : CWB

    -10 -5 0 2 4 6 10 15

    LS-H242CRU0, LS-H242C8C0, LS-H242CSB2

    CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI

    16 5.14 2.02 6.06 2.21 7.01 2.40 7.36 2.48 7.72 2.55 8.15 2.60 8.83 2.73 9.74 2.93

    18 4.98 2.09 5.87 2.28 6.79 2.49 7.13 2.56 7.47 2.64 7.90 2.68 8.55 2.83 9.43 3.03

    20 4.83 2.16 5.69 2.36 6.59 2.57 6.92 2.65 7.25 2.73 7.62 2.77 8.29 2.92 9.15 3.13

    22 4.66 2.23 5.49 2.43 6.35 2.65 6.67 2.73 6.99 2.81 7.38 2.86 7.99 3.01 8.82 3.23

    24 4.50 2.29 5.30 2.51 6.13 2.73 6.44 2.81 6.75 2.90 7.13 2.95 7.72 3.10 8.52 3.32

    Indoor Air

    Temperature

    Outdoor Air Temperature : CWB

    -10 -5 0 2 4 6 10 15

    SymbolDB : Dry bulb temperature [C]WB : Wet bulb temperature [C]

    TC : Total capacity [kW]SHC : Sensible capacity [kW]PI : Power Input [kW]

    (Comp.+ indoor fan motor+outdoor fan motor)

    Notes1. All capacites are net, evaporator fan motor heat is deducted.2. Indicates nominal capacity.

    3. Direct interpolation is permissible. Do not extrapolate4. Capacities are based on the following conditions:- Interconnecting Piping Length 7.5m- Level Difference of Zero.

    Heating capacity

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    30/54

    30

    Capacity Coefficient factor KR-6RMG2-01A

    GENERAL WALL MOUNTED

    9. Capacity Coefficient Factor

    Outdoor unit

    Indoor unit

    A

    B

    Outdoor unit

    Indoor unit

    A

    B

    Capacity

    kW (kBtu/h)

    Pipe Size[mm(in)] Standard

    Length m(ft)Max.

    Elevation m(ft)Max.

    Length m(ft)Additional Refrigerant

    g/m(oz/ft)GAS LIQUID

    5.3(18)12.7(1/2)

    6.35(1/4) 7.5(25) 15(49) 20(65) 20(0.22)15.88(5/8)

    7.0(24) 15.88(5/8) 9.52(3/8) 7.5(25) 15(49) 20(65)30(0.32)

    40(0.43)

    Model: LS-C182CRU0, LS-H182CRU0, LS-C242CRU0, LS-H242CRU0, LS-C182C8C0, LS-C182CSB2,

    LS-H182C8C0, LS-H182CSB2, LS-C242C8C0, LS-C242CSB2, LS-H242C8C0, LS-H242CSB2

    Capacity is based on standard length and maximum allowable length is on the basis of reliability.

    Additional refrigerant must be charged after 7.5m.

    CAUTION

    100

    90

    80

    70

    7.5 10 2015

    18K/24K SC Chassis

    Capacity(%)

    Total Pipe Length(m)

    100

    90

    80

    70

    7.5 10 2015

    18K/24K SC Chassis

    Capacity(%)

    Total Pipe Length(m)

    Cooling

    Heating

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    31/54

    31

    Operation RangeKR-6RMG2-01A

    GENERAL WALL MOUNTED

    10. Operation Range

    Operative: Intermittent operation due to the operationalconditions (indoor/outdoor temperature,humidity, load etc.) can cause the heatingcapacity to decrease

    46

    43

    21

    -5

    18 32

    Indoor Unit [C DB] Indoor Unit [C DB]

    Standard operation

    Operative

    Warmingup

    Operation

    OutdoorUnit[CDB]

    OutdoorUnit[CDB]

    24

    16 30

    -10

    -5

    Operative

    Continuousoperation

    Operative

    Without Low Ambient Kit

    Cooling Heating

    If outdoor temperature falls below 0C, the coolingcapacity and operating characteristics could be dif-ferent than rated.

    Operative: Intermittent operation due to the operationalconditions (indoor/outdoor temperature,humidity, load etc.) can cause the heatingcapacity to decrease

    46

    43

    21

    -5

    18 32Indoor Unit [C DB] Indoor Unit [C DB]

    Standard operation

    Operative

    Warmingup

    Operation

    OutdoorUnit[CDB]

    OutdoorUnit[CDB]

    24

    16 30

    -10

    -5

    Operative

    Continuousoperation

    With Low Ambient Kit

    Cooling Heating

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    32/54

    32

    Air Velocity and Temperature Distribution(Reference Data) KR-6RMG2-01A

    GENERAL WALL MOUNTED

    11. Air Velocity and Temperature Distribution(Reference Data)

    Model: LS-C182CRU0, LS-H182CRU0, LS-C182C8C0, LS-C182CSB2, LS-H182C8C0, LS-H182CSB2

    General Wall Mouted 18 kBtu/h

    CoolingDischarge angle:45

    HeatingDischarge angle:50

    Air velocity [m/s]

    2.7m

    2m

    1m

    0m1m2m3m4m5m6m7m8m

    Temperature [ C]

    2.7m

    2m

    1m

    0m1m2m3m4m5m6m7m8m

    0.751.25

    1.0

    1.5

    0.5

    25 24

    23

    Air velocity [m/s]

    2.7m

    2m

    1m

    0m1m2m3m4m5m6m7m8m

    Temperature [C]

    2.7m

    2m

    1m

    0m1m2m3m4m5m6m7m8m

    0.751.25

    1.0

    1.5

    0.5

    28 2930

    31

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    33/54

    33

    ControllerKR-6RMG2-01A

    GENERAL WALL MOUNTED

    12. Controller

    Type 1 (Wireless LCD)

    Display

    screen

    Controlpanel

    Controlpanel

    Displayscreen

    Description

    a F Plasma button*: Purifies the air by remov-ing particles that enter the indoor unit.

    l = Sleep mode auto button*: Sets the sleepmode auto operation.

    _ y Temperature adjustment buttons:Adjusts the room temperature when coolingand heating.

    \ - On/Off button: Turns the power on/off.

    g 7 v Indoor fan speed button: Adjusts the fanspeed.

    f A C

    D BE

    Operation mode selection button*:Selects the operation mode.Cooling operation (A) / Auto operation orauto changeover (C) / Dehumidifying oper-ation (D) / Heating operation (B) / Air circu-lation (E)

    A NJet cooling/heating button*: Warms up orcools down the indoor temperature within ashort period of time.

    H IAir flow direction button: Adjusts the airflow direction vertically or horizontally.

    k S

    Temperature display button: Displays the

    room temperature.

    z Timer button: Sets the current time andthe start / end time.

    CBD

    J

    G

    -

    Functions button*: Sets the special func-tions.

    J: Auto clean

    G: Operates energy saving cooling

    Adjusts the brightness of the indoor unitdisplay

    p - Set/clear button: Sets or cancels func-

    tions.

    r - Reset button: Initialize the air conditionersettings.

    * Some functions may not be supported, depending on themodel.

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    34/54

    34

    Installation KR-6RMG2-01A

    GENERAL WALL MOUNTED

    13. Installation

    13.1 Installation Map

    Vinyl tape (Wide) Apply after carrying out a drainage test. To carry out the drainage

    test, remove the air filters and pour water into the heat

    exchanger.

    Saddle

    Gas side pipingLiquid side piping

    Additional drain pipe

    Vinyl tape (Narrow)Drain Hose

    Base Plate

    Air Outlet

    Air Inlet

    Connecting cable

    Tubing Cover

    SleeveBushing-SleevePutty(Gum Type Sealer)

    Bend the pipe as closelyon the wall as possible,but be careful that itdoesn't break.

    Installation plate

    * The feature can be changed according to the type of model.

    () You should purchase the installation parts.

    NOTE

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    35/54

    35

    InstallationKR-6RMG2-01A

    GENERAL WALL MOUNTED

    13.2 Select the best Location

    Indoor unit

    1. There should not be any heat or steam near the unit.

    2. Select a place where there are no obstacles around the

    unit.

    3. Make sure that condensation drainage can be conveniently

    routed away.

    4. Do not install near a doorway.

    5. Ensure that the gap between a wall and the left (or right) of

    the unit is more than 100mm. The unit should be installed

    as high as possible on the wall, allowing a minimum of

    200mm from ceiling.

    6. Use a metal detector to locate studs to prevent unneces-

    sary damage to the wall.

    Outdoor unit

    1. If an awning is built over the unit to prevent direct sunlight

    or rain exposure, make sure that heat radiation from the

    condenser is not restricted.

    2. Ensure that the space around the back side and other

    sides is more than 300mm. The space in front of the unit

    should be more than 700mm.

    3. Do not place animals and plants in the path of the warmair.

    4. Take the weight of the air conditioner into account and

    select a place where noise and vibration are minimum.

    5. Select a place where the warm air and noise from the air

    conditioner do not disturb neighbors.

    More than 200

    More than100

    More than 2300

    More than100

    (Unit : mm)

    Install the indoor unit on the wall where the height from the floor is more than 2300mm.

    CAUTION

    More than300

    More than300

    Sunroof

    Fenceorobstacles

    More than700

    More than600

    (Unit : mm)

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    36/54

    36

    KR-6RMG2-01A

    GENERAL WALL MOUNTED

    Installation

    2. Measure the wall and mark the centerline. It is also important to

    use caution concerning the location of the installation plate.

    Routing of the wiring to power outlets is through the walls typical-ly. Drilling the hole through the wall for piping connections must be

    done safely.

    The wall you select should be strong and solid enough to prevent

    vibration

    1. Mount the installation plate on the wall with type "A" screws. If

    mounting the unit on a concrete wall, use anchor bolts.

    Mount the installation plate horizontally by aligning the center-

    line using Horizontal meter .

    6565

    69 56

    Rightrearpiping

    Leftrearpiping

    Installation Plate

    Measuring Tape

    Measuring TapeHanger

    Place a level on raised tabUnit Outline

    207105

    (Unit : mm)

    460 570

    Installation Plate

    ChassisHook

    Type "A" Screws

    Drill the piping hole with a 65mm hole core drill. Drill thepiping hole at either the right or the left with the hole

    slightly slanted to the outdoor side.

    5-7mm

    (3/16"~5/16")

    Indoor

    WALL

    Outdoor

    Bushing

    Sleeve

    13.3 Fixing Installation Plate

    13.4 Drill a Hole in the Wall

    Use the sleeve to prevent damage for tube assembly.

    CAUTION

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    37/54

    37

    KR-6RMG2-01A

    GENERAL WALL MOUNTED

    Installation

    13.5 Flaring Work

    Main cause for gas leakage is due to defect of flaring work. Carry out correct flaring work in the following procedure.

    Cut the pipes and the cable.

    1. Use the piping kit accessory or the pipes purchased locally.

    2. Measure the distance between the indoor and the outdoor unit.

    3. Cut the pipes a little longer than measured distance.

    4. Cut the cable 1.5m longer than the pipe length.

    Burrs removal

    1. Completely remove all burrs from the cut cross section of pipe/tube.

    2. While removing the burrs, hold the end of the pipe in

    downward direction in order to avoid dropping burrs into the tubing.

    Putting nut on

    - Remove flare nuts attached to indoor and outdoor units, then

    put them on the pipe/tube which have completed its burr removal.

    (not possible to put them on after finishing flare work)

    Flaring work1. Firmly hold copper pipe in a bar with the dimension shown

    in table below.

    2. Carry out flaring work with the flaring tool.

    Copperpipe 90 Slanted Uneven Rough

    Pipe

    Reamer

    Point down

    Flare nut

    Copper tube

    Bar

    Copper pipe

    Clamp handle

    Red arrow mark

    Cone

    Yoke

    Handle

    Bar"A"

    Outside diameter A Thickness

    mm inch mm mm

    6.35 1/4" 1.1~1.3 0.7

    9.52 3/8" 1.5~1.7 0.812.7 1/2" 1.6~1.8 0.8

    15.88 5/8" 1.6~1.8 1.0

    19.05 3/4" 1.9~2.1 1.0

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    38/54

    38

    KR-6RMG2-01A

    GENERAL WALL MOUNTED

    Installation

    Check

    1. Compare the flared work with the figures given below.

    2. If a flared section is defective, cut it off and do flaring work

    again.

    Inclined

    Inside is shiny without scratches

    Smooth all round

    Even lengthall round

    Surfacedamaged

    Cracked Uneventhickness

    = Improper flaring =

    13.6 Connecting the pipes

    1. Pull the screw caps at the bottom of the indoor unit

    2. Remove the chassis cover from the unit by loosing 3 screws

    3. Pull back the tubing holder.

    4. Remove the pipe port cover and position the piping.

    * The feature can be changed according to the type of model.

    Chassis cover

    Back side view

    Tubing holder

    Pipe Port

    Left

    Backwards

    Right

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    39/54

    39

    KR-6RMG2-01A

    GENERAL WALL MOUNTED

    Installation

    Good case

    Press the tubing cover and slowly unfold the tubing to downward. And then bend to the left side slowly.

    Bad case Following bending case from right to left directly may cause damage to the tubing.

    * The feature can be changed according to the type of model.

    Installation Information. For right piping. Follow the instruction above.

    CAUTION

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    40/54

    40

    Installation KR-6RMG2-01A

    GENERAL WALL MOUNTED

    1. Hook the indoor unit onto the upper portion of the installation plate.( engage the three hooks at the top of the indoor unit with

    the upper edge of the installation plate) Ensure that the hooks are properly seated on the installation plate by moving it left

    and right

    2. Unlock the tubing holder from the chassis and mount between the chassis and installation plate in order to separate the bot-

    tom side of the indoor unit from the wall.

    * The feature can be changed according to the type of model.

    Installation plate

    Tubing Holder

    13.7 Installation of Indoor Unit

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    41/54

    41

    InstallationKR-6RMG2-01A

    GENERAL WALL MOUNTED

    3. Insert the connecting cable through the bottom side of

    indoor unit and connect the cable

    Open the Front Grille

    Support the Front Grille with supporter

    Open the Control Cover

    Connect the connecting cable

    Control Cover

    Case 1 Case 2 Case 3

    Round pressureterminal

    Power wire

    4. Tape the tubing pipe, drain hose and the connection cable. Be sure that the drain hose is located at the lowest side of the

    bundle. Locating at the upper side can cause overflow from the drain pan through the inside of the unit.

    * The feature can be changed according to the type of model.

    Connecting pipe

    Connectingcable

    Tape

    Drain hose

    Indoor Outdoor

    Indoor UnitDrain hose

    Indoor UnitDrain hose

    Insulation(More than 100~300mm

    length and 7mm thickness)

    Extensiondrain hose

    Drain hoseConnecting pipe

    Connectingcable

    Tape

    Drain hose

    If the extension drain hose is routed inside the room,insulate the hose with an insulation material* so that drip-ping from sweating (condensation) could not damage fur-

    niture or floors.

    Foamed polyethylene or equivalent is recommended.

    CAUTION

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    42/54

    42

    KR-6RMG2-01A

    GENERAL WALL MOUNTED

    Installation

    Connecting the installation pipe and drain

    hose to the indoor unit.

    1. Align the center of the pipes and sufficiently tighten the

    flare nut by hand

    2. Tighten the flare nut with a wrench

    3. When needed to extend the drain hose of indoor unit,

    assembly the drain pipe as shown on the drawing

    Indoor unit tubing Flare nut Pipes

    Wrench

    Indoor unit tubing

    Open-end wrench (fixed)

    Connection pipe

    Flare nut

    Vinyl tape(narrow)Adhesive

    Drain pipe

    Indoor unit drain hose

    Outside diameter Torque

    mm inch kgf.m

    6.35 1/4 1.8~2.5

    9.52 3/8 3.4~4.2

    12.7 1/2 5.5~6.6

    15.88 5/8 6.3~8.2

    19.05 3/4 9.9~12.1

    Wrap the insulation material around the con-

    necting portion.

    1. Overlap the connection pipe insulation material and the

    indoor unit pipe insulation material. Bind them together with

    vinyl tape so that there may be no gap.

    2. Wrap the area which accommodates the rear piping hous-ing section with vinyl tape.

    3. Bundle the piping and drain hose together by wrapping

    them with vinyl tape sufficient enough to cover where they

    fit into the rear piping housing section.

    Insulation material

    Wrap with vinyl tape

    Drain hose

    Pipe

    Vinyl tape(wide)

    Vinyl tape(narrow)

    Connection pipe

    Connecting cable

    Vinyl tape (wide) Wrap with vinyl tape

    Indoor unit pipe

    Pipe

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    43/54

    43

    KR-6RMG2-01A

    GENERAL WALL MOUNTED

    Installation

    Finishing the indoor unit installation

    1. Mount the tubing holder in the original positon.

    2. Ensure that the hooks are properly seated on the installa-

    tion plate by moving it left and right.

    3. Press the lower left and right sides of the unit against the

    installation plate until the hooks engage into their slots(clicking sound).

    4. Finish the assembly by screwing the unit to the installation

    plate by using two pieces of type "C" screws. And assemble

    the chassis.

    5. Reconvey the chassis cover in Original place.

    Type 'C' screw

    Outdoor Unit Installation

    1. Remove the tubing cover from the unit by loosening thescrew.

    Cover control

    Tubing Cover

    2. Align the center of the pipings and sufficiently tighten the

    flare nut by hand.

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    44/54

    44

    KR-6RMG2-01A

    GENERAL WALL MOUNTED

    Installation

    3. Finally, tighten the flare nut with torque wrench until the

    wrench clicks.

    When tightening the flare nut with torque wrench, ensure

    the direction for tightening follows the arrow on the

    wrench.

    Liquid side piping(Smaller diameter)

    Torque wrench

    Gas side piping(Bigger diameter)

    Outdoor unit

    Outside diameter Torque

    mm inch kgf.m

    6.35 1/4 1.8~2.5

    9.52 3/8 3.4~4.2

    12.7 1/2 5.5~6.6

    15.88 5/8 6.3~8.2

    19.05 3/4 9.9~12.1

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    45/54

    45

    KR-6RMG2-01A

    GENERAL WALL MOUNTED

    Installation

    13.8 Connecting the Cables

    Indoor

    Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually according to the

    outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal No. are the same as those of

    the indoor unit.)

    The circuit diagram is a subject to change without notice.

    The earth wire should be longer than the common wires.

    When installing, refer to the circuit diagram on the chassis cover.

    Connect the wires firmly so that they may not be pulled out easily.

    Connect the wires according to color codes, referring to the wiring diagram.

    CAUTION

    The power cord connected to the unit should be elected according to the following specifications (Cable Type

    approved by IEC 60245 or IEC 60227).

    CAUTION

    The power connecting cable connecting the indoor and outdoor unit should be selected according to the followingspecifications (Cable type approved by IEC 60245 or IEC 60227).

    103mm

    20mm

    GN/YL

    (mm2)

    POWER CORD

    Capacity[kW (Btu/h)]

    5.3 (18) 7.0 (24)

    Nomal Cross-SectionArea

    1.5 2.5

    Unit Indoor Indoor

    Cable Type H05VV-F H05VV_F

    (mm2)

    POWER CONNECTING CABLECapacity

    [kW (Btu/h)]5.3 (18) 7.0 (24)

    Nomal Cross-SectionArea

    1.5 2.5

    Unit Indoor Indoor

    Cable Type H07RN-F H07RN-F

    103mm

    20mm

    GN/YL

    103mm

    20mm

    GN/YL

    103mm

    (mm2)

    COMMUNICATION CONNECTING CABLECapacity

    [kW (Btu/h)]5.3 (18) 7.0 (24)

    Nomal Cross-SectionArea

    0.75 0.75

    Unit Indoor Indoor

    Cable Type H05RN-F H05RN-F

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    46/54

    46

    KR-6RMG2-01A

    GENERAL WALL MOUNTED

    Installation

    Outdoor

    1. Remove the control cover from the unit by loosening the

    screw.

    Connect the wires to the terminals on the control board indi-

    vidually.

    2. Secure the cable onto the control board with the cord

    clamp.

    3. Refix the control cover to the original position with the

    screw.

    4. Use a recognized circuit breaker between the power source

    and the unit.

    A disconnecting device to adequately disconnect all supply

    lines must be fitted.

    * Round Pressure terminal and connecting requirement

    Provide the circuit breaker between power source and the

    unit as shown by

    CAUTION

    According to the confirmation of the above conditions, pre-

    pare the wiring as follows.

    1. Never fail to have an individual power circuit specifically for

    the air conditioner. As for the method of wiring, be guided

    by the circuit diagram posted on the inside of control cover.

    2. The screw which fasten the wiring in the casing of electrical

    fittings are liable to become loose from vibrations to which

    the unit is subjected during the transportation. Check them

    and make sure that They all are tightly fastened. (If they

    are loose, it could cause burn-out of the wires.)

    3. Specification of power source.

    4. Confirm that electrical capacity is sufficient.

    5. See that the starting voltage is maintained at more than 90percent of the rated voltage marked on the name plate.

    6. Confirm that the cable thickness is as specified in the

    power source specification.

    (Particularly note the relation between cable length and

    thickness.

    7. Always install an earth leakage circuit breaker in a wet or

    moist area.

    8. The following would be caused by voltage drop.

    Vibration of a magnetic switch, which will damage the

    contact point, fuse breaking, disturbance of the normal

    function of the overload.9. The means for disconnection from a power supply shall be

    incorporated in the fixed wiring and have an air gap contact

    separation of at least 3mm in each active(phase) conduc-

    tors.

    CAUTION

    Cover control

    Connecting

    cable

    The earth wire shouldhe earth wire shouldbe longer than thee longer than thecommon wires.ommon wires

    1(L) 2(N) 3 4

    CASE 1

    1(L) 2(N) 3 4

    CASE 2

    The earth wire shouldbe longer than thecommon wires.

    The earth

    wire should

    be longer than the

    common wires

    Over5mm

    Round pressureterminal

    Power wire

    AirConditioner

    Main power source

    Circuit BreakerUse a circuit breake

    or time delay fuse.

    Circuit

    Breaker (A)

    Capacity [kW (kBtu/h)]

    5.3 (18) 7.0 (24)

    20 30

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    47/54

    47

    KR-6RMG2-01A

    GENERAL WALL MOUNTED

    Installation

    To check the drainage.

    1. Pour a glass of water on the evaporator.

    2. Ensure the water flows through the drain hose of the

    indoor unit without any leakage and goes out the drain exit.

    Drain piping

    1. The drain hose should point downward for easy drain flow.

    2. Do not set the drain hose like the following.

    * The feature can be changed according to the type of model.

    Connecting areadrain hose

    Leakage

    checking

    Drain pan

    Drainhose

    Leakagechecking

    Downward slope

    Do not raiseAccumulateddrain water

    Tip of drain hosedipped in water

    Air

    WavingWaterleakage

    Waterleakage Ditch

    Less than50mm gap

    Waterleakage

    13.9 Checking the Drainage

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    48/54

    48

    KR-6RMG2-01A

    GENERAL WALL MOUNTED

    Installation

    13.10 Forming the Piping

    Form the piping by wrapping the connecting por-tion of the indoor unit with insulation material andsecure it with two kinds of vinyl tapes.

    If you want to connect an additional drain hose, the end of

    the drain outlet should be routed above the ground. Secure

    the drain hose appropriately.

    In cases, where the outdoor unit is installed belowthe Indoor unit, perform the following.

    1. Tape the piping, drain hose and connecting cable from

    down to up.

    2. Secure the tapped piping along the exterior wall using sad-dle or equivalent.

    In cases, where the outdoor unit is installed abovethe Indoor unit, perform the following.

    1. Tape the piping and connecting cable from down to up.

    2. Secure the taped piping along the exterior wall. Form a

    trap to prevent water entering the room.

    3. Fix the piping onto the wall using saddle or equivalent

    Drain hoseVinyl tape(narrow)

    Pipe

    Wrap withvinyl tape(wide)

    Taping

    Saddle

    Drain hose

    PipingsConnecting cable

    Seal small openingsaround pipings with agum type sealant.

    Trap is required to prevent water

    from entering into electrical parts.

    Seal a small openingaround the pipingswith gum type sealant.

    Trap

    Trap

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    49/54

    49

    KR-6RMG2-01A

    GENERAL WALL MOUNTED

    Installation

    13.11 Air Purging

    The air and moisture remaining in the refrigerant system have undesirable effects as indicated below.1. Pressure in the system rises.

    2. Operating current rises.

    3. Cooling(or heating) efficiency drops.

    4. Moisture in the refrigerant circuit may freeze and block capillary tubing.

    5. Water may lead to corrosion of parts in the refrigeration system.

    Therefore, after evacuating the system, take a leak test for the piping and tubing between the indoor and outdoor unit.

    Air purging with vacuum pump

    1. Preparation Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected and all

    wiring for the test run has been completed. Remove the service valve caps from both the gas and the liquid side on the outdoor unit.

    Note that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.

    2. Leak test Connect the manifold valve(with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses.

    Be sure to use a manifold valve for air purging. If it is not available, use a stop valve for this purpose. The knob of the 3-way

    valve must always be kept close.

    Pressurize the system to maximum 250 P.S.I.G. (R-22 model) or 400 P.S.I.G. (R-410A model) with dry nitrogen gas and

    close the cylinder valve when the gauge reading reaches 250 P.S.I.G. (R-22 model) or 400 P.S.I.G. (R-410A model). Next

    step is leak test with liquid soap.

    To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must be higher than its bottom when

    you pressurize the system. Usually, the cylinder is used in a vertical standing position.

    There is a risk of fire and explosion.

    Inert gas (nitrogen) should be used when you check plumbing leaks, cleaning or repairs of pipes etc.

    If you are using combustible gases including oxygen, product may have the risk of fires and explosions.

    1. Do a leak test of all joints of the tubing(both indoor and out-

    door) and both gas and liquid side service valves.

    Bubbles indicate a leak. Be sure to wipe off the soap with a

    clean cloth.

    2. After the system is found to be free of leaks, relieve the nitro-

    gen pressure by loosening the charge hose connector at the

    nitrogen cylinder. When the system pressure is reduced tonormal, disconnect the hose from the cylinder.

    *The feature can be changed according a type of model.

    CAUTION

    CAUTION

    WARNING

    Lo Hi

    Outdoor unit

    Manifold valve

    Charge hose

    Nitrogen gascylinder(in verticalstanding position)

    Pressuregauge

    Indoor unit

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    50/54

    50

    KR-6RMG2-01A

    GENERAL WALL MOUNTED

    Installation

    Soap water method

    1. Remove the caps from the 2-way and 3-way valves.

    2. Remove the service-port cap from the 3-way valve.

    3. Apply a soap water or a liquid neutral detergent on the

    indoor unit connection or outdoor unit connections by a

    soft brush to check for leakage of the connecting points of

    the piping.4. If bubbles come out, the pipes have leakage

    Evacuation

    1. Connect the charge hose end described in the preceding

    steps to the vacuum pump to evacuate the tubing and indoorunit.

    Confirm the "Lo" knob of the pressure Gauge is open. Then,

    run the vacuum pump.

    The operation time for evacuation varies with tubing length

    and capacity of the pump. The following table shows the timerequired for Evacuation.

    2. When the desired vacuum is reached, close the knob of the 3-way valve and stop the vacuum pump.

    Finishing the Job

    1. With a service valve wrench, turn the valve of liquid sidecounter-clockwise to fully open the valve

    2. Turn the valve of gas side counter clockwise to fully open the

    valve

    3. Loosen the charge hose connected to the gas side service

    port slightly to release the pressure, then remove the hose.

    4. Replace the flare nut and its bonnet on the gas side serviceport and fasten the flare nut securely with an adjustable

    wrench. This process is very important to prevent leakage

    from the system.

    5. Replace the valve caps at both gas and liquid side service

    valves and fasten them tight.This completes air purging with a vacuum pump.

    6. Replace the pipe cover to the outdoor unit by one screw

    Now the air conditioner is ready for test run.

    * The feature can be changed according to the type of model.

    Outdoor unit

    Gas side

    Liquid side

    Cap

    3-way or2-way valve

    3-way valve

    Outdoor unit

    Lo Hi

    Manifold valve

    Vacuum pump

    Pressuregauge

    Open Close

    Indoor unit

    Required time for Evacuation when 30 gal/h vacuumpump is used

    If tubing length is less than10m (33 ft)

    If tubing length is longerthan 10m (33 ft)

    10 min. or more 15 min. or more

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    51/54

    51

    KR-6RMG2-01A

    GENERAL WALL MOUNTED

    Installation

    If the actual pressure is higher than shown, the system is most likely over-charged, and charge should be removed. If the

    actual pressure are lower than shown, the system is most likely undercharged, and charge should be added.

    NOTE

    Pump downThis is performed when the unit is relocated or the refrigerant circuit is serviced.

    Pump Down means collecting all refrigerant into the outdoor unit without the loss of refrigerant.

    Be sure to perform Pump Down procedure in the cooling mode.

    Pump Down Procedure1. Connect a low-pressure gauge manifold hose to the charge port on the gas side service valve.

    2. Open the gas side service valve halfway and purge the air in the manifold hose using the refrigerant.

    3. Close the liquid side service valve(all the way).

    4. Turn on the unit's operating switch and start the cooling operation.

    5. When the low-pressure gauge reading becomes 1 to 0.5kg/cm2 G(14.2 to 7.1 P.S.I.G.), fully close the gas side valve and

    then quickly turn off the unit. Now Pump Down procedure is completed, and all refrigerant is collected into the outdoor unit.

    CAUTION

    Settlement of outdoor unit1. Fix the outdoor unit with a bolt and nut(10mm) tightly and

    horizontally on a concrete or rigid mount.

    2. When installing on the wall, roof or rooftop, anchor the

    mounting base securely with a nail or wire assuming the

    influence of wind and earthquake.

    3. If the vibration of the unit is transmitted to the pipe, securethe unit with an anti-vibration rubber.

    Evaluation of the performanceOperate the unit for 15~20 minutes, then check the system

    refrigerant charge:

    1. Measure the pressure of the gas side service valve.

    2. Measure the air temperature from inlet and outlet of air

    conditiioner.

    3. Ensure the difference between the inlet and outlet temper-

    ature is more than 8C.

    4. For reference; the gas side pressure at optimum condition

    is shown on table (cooling)

    The air conditioner is now ready to use.

    *The feature can be changed according a type of model.

    Bolt

    Tubing connection

    Dischargetemperature

    Discharge air

    Intake temperature

    Refrigerant

    Outside

    ambient

    TEMP.

    The pressure of the

    gas side service valve.

    R22 35C (95F)4~5kg/cm2G

    (56.8~71.0 P.S.I.G.)

    R410A 35C(95F)8.5~9.5kg/cm2G

    (120~135 P.S.I.G.)

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    52/54

    52

    KR-6RMG2-01A

    GENERAL WALL MOUNTED

    13.12 Installation of filters

    1. Pull out the 3M Multi protection filter from the separately packed

    plastic bag.

    2. Detach the two nitto tapes from the 3M Multi protection filter.

    3. Insert the 3M Multi protection filter into thefilter case.

    4. Detach two nitto tapes from the plasmafilter.

    * The feature can be changed according to the type of model.

    3M Multi protection filter Plasma (+HAF) Filter

    13.13 Test Running

    Check that all tubing and wiring are properly connected.

    Check that the gas and liquid side service valves are fully open.

    Prepare remote controller

    Insert batteries before using the remote control. The battery

    type used is AAA (1.5 V).

    1. Remove the battery cover.

    2. Insert the new batteries and make sure that the + and - ter-

    minals of the batteries are installed correctly.

    3. Reattach the battery cover.

    Use 2 AAA(1.5volt) batteries. Do not use rechargeable bat-teries.

    Remove the batteries from the remote controller if the sys-

    tem is not used for a long time

    NOTE

    Installation

  • 8/10/2019 PDB Korea Split + Titan Series (Art Cool+Inverter+Deluxe+Gold)

    53/54

    53

    KR-6RMG2-01A

    GENERAL WALL MOUNTED

    Installation

    13.14 Installation Guide at the Seaside

    Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced.

    Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion on the product.

    Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient performance.

    If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise it needs addition-

    al anticorrosion treatment on the heat exchanger.

    CAUTION

    Selecting the location(Outdoor Unit)

    1. If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided. Install the out-

    door unit on the opposite side of the sea wind direction.

    2. In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.

    It should be strong enough like concrete to prevent the

    sea wind from the sea.

    The height and width should be more than 150% of theoutdoor unit.

    More than 70cm(s) of space should be kept between

    outdoor unit and windbreak for easy air flow.

    Select a well-drained place.

    Sea wind Sea wind

    Sea wind

    Windbreak

    1. If you cant meet above guide line in the seaside installation, please contact LG Electronics for the additionalanticorrosion.

    2. Periodic (more than once/year) cleaning of the dust or salt particles stuck on the heat exchanger by using water