Upload
others
View
41
Download
0
Embed Size (px)
Citation preview
Power + Energy, Inc.
PE9000S Series Hydrogen Purifier
Operations Manual Version 4.1.5
Power + Energy, Inc.
February 2010 Power + Energy, Inc. 106 Railroad Drive Ivyland, PA 18974-1449 Phone: (215) 942-4600 Fax: (215) 942-9300 Sales: [email protected] Support: [email protected] Website: www.powerandenergy.com
Power + Energy, Inc.
PE9000S Control Software Documentation For use with Production Software Version 4.1.5 Safety Information.................................................................................................1
Symbols Used In this Manual ............................................................................1 General Safety Procedures and Precautions ....................................................1
Purification Process ..............................................................................................3 View of Purifier Cabinet ........................................................................................4 Gas Specifications ................................................................................................6
Hydrogen Input: .............................................................................................6 Nitrogen Input: ...............................................................................................6 Nitrogen/Clean Dry Air Input: .........................................................................6 UPH (Ultra Pure Hydrogen) Output: ..............................................................6 Bleed Output:.................................................................................................6 Helium (Leak Check) Input: ...........................................................................6
Important PE9000S Information............................................................................8 Safety features ..................................................................................................8
EMO Operation..............................................................................................8 Resetting the Unit ..........................................................................................8
Installing Filters .................................................................................................8 To begin using the PE9000S.............................................................................9 Setting the Rotometer .......................................................................................9
PE9000S Control System Overview ...................................................................10 Passwords.......................................................................................................11 Main Screen ....................................................................................................12 System Screen ................................................................................................13 Pressure Charts ..............................................................................................14 Temperature Charts ........................................................................................16 Diagnostics......................................................................................................18 Alarms .............................................................................................................19 Configure Controls ..........................................................................................20 PID Control......................................................................................................21 PID Tuning ......................................................................................................22 Configure Users ..............................................................................................23 Shut Down Mode.............................................................................................24 Hydrogen Standby Mode.................................................................................25 Operate Mode .................................................................................................26 Nitrogen Standby Mode...................................................................................27 Leak Check Mode ...........................................................................................28 Ethernet Control ..............................................................................................31 Discrete Inputs ................................................................................................31 Discrete Outputs..............................................................................................33 Alarms .............................................................................................................35
Computer error/ failure.................................................................................35 Appendix A: Electrical Schematic Drawings ......................................................38
Power + Energy, Inc.
PE9000S Operations Manual
4
Electrical Service Connection..........................................................................38 Appendix B: Chassis Dimensional Drawings .....................................................42 Appendix C : Outlet Flow Curves ........................................................................43 Appendix C : Leak Check ...................................................................................45
Power + Energy, Inc.
PE9000S Operations Manual
1
Safety Information Symbols Used In this Manual General Safety Procedures and Precautions Service by Qualified Personnel Only Operating personnel must not remove the instrument’s paneling. Component replacement, servicing or calibration must be performed by qualified individuals, preferably Power and Energy technicians. Purging the Instrument When shutting down for removal from a system or transporting the equipment it is important to purge the unit thoroughly with Nitrogen and cap all I/O Ports. Never disconnect or cut off the Nitrogen supply from the unit unless it has been fully purged and the cell is at ambient temperature. Not following this procedure may cause irreversible damage to the cell. Use Caution When Handling Flammable Gases Observe proper safety precautions and local regulations for the handling of flammable gases. External Devices All External devices that connect to this unit, including those suggested in this manual, must have fittings and usage consistent with the intended use of this product and the handling of hydrogen. Connections All connections to this unit must be made with proper gas fittings or electrical connectors. Gas connections should be leak-checked during installation.
WARNING – The Warning sign denotes a hazard. It calls attention to procedure, practice, condition, or the like, which, if not correctly performed or adhered to could result in injury to personnel or damage to the product.
NOTE – The Note sign denotes important information. It calls attention to a procedure, practice, condition, or the like, which is essential to highlight.
Power + Energy, Inc.
PE9000S Operations Manual
2
Operate at Safe Pressures Adhere to unit specifications and local safety regulations for handling pressurized gases. For safety, a suitable pressure relief valve shall be used when inlet gases are pressure regulated from a compressed source. Avoid Contamination Do not allow dust, dirt or other contamination to enter the unit before or during use. Standard industry practices should be followed to ensure clean connections to the UPH port on the unit.
Power + Energy, Inc.
PE9000S Operations Manual
3
Purification Process The hydrogen purification process has been made simple thanks to your Power + Energy ™ PE9000S Series Palladium Diffusion Hydrogen Purifier. Figure 1 is a flow diagram to illustrate the process. Hydrogen (99.95% or better H2 purity is recommended) is fed into the system via the H2 In connection. It travels through the Hydrogen purification cell, which allows only pure hydrogen to diffuse through the membranes to the Ultra-Pure (UPH) side. It then passes through the UPH out connection. Our hydrogen purification process has been constantly refined, and has been optimized to operate at 380 ºC ~ 410ºC. four heaters (3.6 kW total power) are installed around the cell to achieve this. To improve the thermal (and therefore electrical) efficiency, the UPH passes through a heat exchanger, thus saving costly electricity bills by recycling up to 70% of the heat coming off the heated UPH gas. A facility also exists for you to test your hydrogen purifier for leaks which may reduce the purity of the output. Helium may be injected into the Nitrogen stream via port F and tested on a secondary UPH output called Leak check. If the cell is in good working order, a spectrometer (or other Helium detection device) should register almost no helium in the UPH stream. Finally, it is important to maintain the nitrogen supply to the purifier. This is important, as it will ensure that during the heating up and cooling down processes, conditions are optimal for reducing thermal stress on the membranes. In the event of any electrical or other failure, flowing nitrogen ensures the safety of the purifier surroundings. This gas will pass through the bleed output, with flow control via the rotometer or via V4, the bypass valve. WARNING – Do not disconnect the N2 gas unless the
system has been properly shut down and the cell temperature has reached ambient conditions.
Power + Energy, Inc.
PE9000S Operations Manual
4
View of Purifier Cabinet
Power + Energy, Inc.
PE9000S Operations Manual
5
PE9000S P&ID Drawing
Power + Energy, Inc.
PE9000S Operations Manual
6
Gas Specifications Hydrogen Input:
Minimum pressure: 55 PSIG/ 3.8 Bar (g) Maximum pressure: 220 PSIG/ 15.2 Bar (g) Purity: ~99.95% Recommended
Nitrogen Input:
Minimum pressure: 35 PSIG/ 2.4 Bar (g) Maximum pressure: 90 PSIG/ 6.2 Bar (g) Purity: ~99.95% Recommended
Nitrogen/Clean Dry Air Input:
Instrument grade air Minimum pressure: 72 PSIG/ 5 Bar (g) Maximum pressure: 98 PSIG/ 6.7 Bar (g)
UPH (Ultra Pure Hydrogen) Output: Minimum pressure: Hard Vacuum Maximum pressure: 220PSIG/ 15.2 Bar (g) Maximum Delta P vs. Input 200 psig/ 13.79 Bar Purity: 99.9999999% H2
Rated output: See test certificate. Nominal rated output curves are given in Appendix C
Bleed Output: Flow rate: Typically 1-2% of UPH output
flow rate. See “Setting the Rotometer”, page 10.
Helium (Leak Check) Input: Minimum pressure: 10 PSI greater than N2 Input pressure Maximum pressure: 200 PSIG/ 13.79 Bar (g)
Note – You will not be able to Start up the purifier unless both the N2 input gas and the dry air are connected and are at or above minimum values.
Power + Energy, Inc.
PE9000S Operations Manual
7
Port Diagram
Power + Energy, Inc.
PE9000S Operations Manual
8
Important PE9000S Information Safety features The PE9000S has the following safety features installed:
• Emergency stop button
• Independent secondary thermal protection
• H2 detector in cabinet
• Protection against heating the cell without instrument air for valve actuation
All of these mechanisms will restrict the normal operation of the unit. Please read the following. EMO Operation Should any circumstance dictate a need to immediately cease the operation of the unit’s heaters, press the red EMO button in, located on the front panel (see front panel diagram on page 8). This will break the contactors inside the unit, and will turn off the electrical heaters. PLC and control power will remain turned on. Resetting the Unit To begin operation again:
1) Twist the EMO switch a quarter turn until it pops out. 2) Press the green “Start/Reset” button.
Installing Filters It is highly recommended that two (2) 0.5 micron High Flow Sintered Filter (Swagelok ® part #SS-4F-VCR-05 or equivalent) are installed prior to operating the purifier. These filters should be installed inline with H2 and N2 Inlets.
Power + Energy, Inc.
PE9000S Operations Manual
9
To begin using the PE9000S 1) Plumb the gas connections for input and output lines. 2) Ensure that the unit is properly connected to a 200 ~240VAC, 50/60 Hz
electrical supply. 3) Turn on the main disconnect switch located on the front panel. (see front
panel diagram on page 8). The green “Start/Reset” button should illuminate to indicate that the unit has power.
4) Press the green “Start/Reset” button on the front panel within 10 seconds of turning on the main disconnect switch. If this action is delayed, the PLC controller will display an alarm stating that the EMO has been triggered. If this alarm is triggered before the user has pressed the “Start/Reset” button, the user should press the “Start/Reset” button and clear the alarms. This will bring the system back to normal sequencing.
5) Log on as engineer2 and set and/or verify the operating voltage on screen “Operate Diagnostics” is set to your local conditions. This value may have been pre-set at the factory, but must be verified before running the heaters in the purifier.
A few seconds after power is turned on, the touch screen software will load and the “MAIN” screen will appear. From this screen, the basic modes of operation will be accessible without the need of logging in. The system will begin in shutdown mode, and will not begin to heat up or produce UPH until the user selects another mode.
Setting the Rotometer The rotometer is accessed on the front panel of the cabinet. It is used to set the flow rate on the bleed line. Turning the knob counter-clockwise will open the needle valve in the rotometer, which will increase the flow of gas through the bleed line. The flow rates for Nitrogen and Hydrogen are shown on a chart on the cabinet door, as well as in this manual (Appendix C). Be aware that when purifying hydrogen, the less pure the input gas, the greater the required bleed flow to remove the impurities. A rough guide to this is using 20 times the impurity percentage as a percentage of the UPH flow rate. Example calculation For 99.95% pure H2, the impurity percentage is 0.05%. Thus 20 x 0.05% suggests that 1% should be the percentage of UPH flow set on the rotometer. Suppose that 100 SLPM UPH is required to flow. Then 1 SLPM bleed flow is required. By reading the chart (see the panel of the PE9000S or Appendix C) you
Power + Energy, Inc.
PE9000S Operations Manual
10
will see that 1 SLPM on the red “Hydrogen” line corresponds to about 8mm on the ball. This corresponds to the reading that the center of the ball gives, when at eye level.
PE9000S Control System Overview The following sections provide a description of HMI operator panels and the functions available from each panel. Users must log on to access some machine control functions. Users should log off after changing machine settings to ensure that unauthorized access does not occur. The system does not provide any automatic log-off feature, and each user is responsible for hitting the “Log Off” button before leaving the unit’s HMI.
The Menu Panel Map shows the navigation between panels and the user password level required to access each panel.
OperateBarGSlow 500
OperateTempSlow 500
OperateDiagnostics 510
OperateAlarms 0
Log On Log Off
Operator Interface Panel Map
Operate Main 0
Operate System 500
OperateBarGFast 500
OperateTempFast 500
ConfigureControls 900
ConfigurePID
900
ConfigureUsers 900 Log Off
Edit Users
ConfigurePIDTune 900
Power + Energy, Inc.
PE9000S Operations Manual
11
Passwords The unit is preconfigured with the following ID’s and passwords: ID PASSWORD LEVEL operator 1234 100 engineer1 5678 500 engineer2 56789 510 The operator ID logon is not required to access the basic modes on this version software. The unit will initialize with the “Operate Main” screen visible to the user. The engineer1 and engineer2 ID’s will be required to access screens with levels 500 and 510, respectively.
Power + Energy, Inc.
PE9000S Operations Manual
12
Main Screen The Main screen is displayed when you Power On the PE9000S. It will provide all the functionality and information required for day to day operation. This screen will display an “Alarm Pop Disabled” warning in yellow when the alarm display pop-up function is disabled. This function should only be used when troubleshooting, and alarm pop-up should be enabled for normal operation. Leaving the alarm pop-up disabled will defeat user notification of problems. Alarm pop-up can be enabled by pressing the yellow button when it is visible on this screen.
ACTIVE CONTROLS: Log On Log Off Operate StandbyH2 ShutDown System (when logged on as engineer1 or engineer2) Alm Pop Disable button to re-enable alarm pop-ups
Cell Temp1234
Feed PSIG123.12
UPH PSIG123.12
System
Operate
ShutDown
StandbyH2
Main
Log On
Heat%DutyCycl
1234
Log Off
StandbyN2
H2 O
N2 C
UPHO
HeLC
ByPC
Valve Status
1 2 3 4 5 6 78 9 10 11 1213 14
Alm PopDisabled
Button to access SYSTEM panel. Machine state
sequence indicators
Status indicator buttons show the most recently selected machine mode in green. The normally hidden fourth light indicates Standby N2, which is normally not used.
Valve Status Display: Indicator turns green when a particular valve is open.
Buttons to access Log On and Log Off screens.
Panel name
Operational Data: Displays Heater duty cycle (% on), cell temperature in ºC and both input (feed) and UPH output pressures in psig, MPag, or Barg, factory set for each user.
Status indicator for N2 Standby Mode. Invisible when off.
Button to re-activte alarm display pop-up screen. Invisible when inactive. Should not be visible in normal operation.
Power + Energy, Inc.
PE9000S Operations Manual
13
System Screen The system screen contains access to other modes, as well as information about heater power usage and access to temperature and pressure charts.
ACTIVE CONTROLS: Main Pressure Charts Temp Charts Diagnostics (when logged on with user level of 510 or higher) Alarms Standby
Main: Press to return to the Main screen.
Main
Pressure Charts
Temp Charts
Heater
System
Alarms
Diagnostics
Cell Temp
1234
### StandbyN
Valve StatusH2 C
N2 O
UPHC
HeLC
ByPO
H2 RO
MFM
1234
Operational Data: Press to access pressure and temperature charts.
Diagnostics: Press to access information about flow rate and heater electrical current data. Also can change Standby mode
Displays Cell Temperature in °C
Heater Power: Indicator light turns on when the heater is powered.
Mass Flow Displayed (Factory Testing only)
Standby: Press to move system into Standby Mode
Power + Energy, Inc.
PE9000S Operations Manual 14
Pressure Charts The PE9000S provides pressure charts, enabling the user to see historic data about system pressures. Data may be viewed in charts spanning either a couple of minutes (Fast), or over the period of an hour (Slow). For the fast mode, a data point is taken every second, and in the slow mode, data is taken every 30 seconds.
• Each minor grid marker on the Fast chart is approximately 17 seconds
ACTIVE CONTROLS: System View Change
View change button: Press to change the time span of the chart.
System: Press to return to the System screen.
Real-Time Data: View current readings. Color corresponds to line on chart. Pressure readings are in psig.
Time axis: Measured in either MM:SS (Fast Mode) or HH:MM:SS (Slow Mode). Time is referenced to system clock.
Power + Energy, Inc.
PE9000S Operations Manual 15
• Each minor grid marker on the Slow chart is approximately 8 minutes and 30 seconds
ACTIVE CONTROLS: System View Change
Fast
--:--:-- --:--:-- --:--:-- --:--:--
1.00
0.78
0.56
0.34
0.12
-0.10
SystemPressureMPa (g) Slow
1234
1234Feed
UPH1234Cell Temp
View change button: Press to change the time span of the chart.
Real-Time Data: View current readings. Color corresponds to line on chart. Pressure readings are in psig.
Time axis: Measured in either MM:SS (Fast Mode) or HH:MM:SS (Slow Mode). Time is referenced to system
System: Press to return to the System screen.
Power + Energy, Inc.
PE9000S Operations Manual 16
Temperature Charts The PE9000S also provides temperature charts enabling the user to see historic data about the system temperature in ºC. Data may be viewed in charts spanning either a couple of minutes (Fast), or over the period of an hour (Slow).
• Each minor increment on the Fast chart is approximately 17 seconds ACTIVE CONTROLS: System View Change
Slow
--:-- --:-- --:-- --:--
500
400
300
200
100
0
SystemTempFast
Cell Temp (ºC)
1234
Time axis: Measured in either MM:SS (Fast Mode) or HH:MM:SS (Slow Mode). Time is referenced to system clock.
View change buttons: Press to change the time span of the chart.
System: Press to return to the System screen. Real-Time Data:
View current cell temperature.
Power + Energy, Inc.
PE9000S Operations Manual 17
• Each minor grid marker on the slow chart is approximately 8 minutes and 30 seconds
ACTIVE CONTROLS: System View Change
Fast
SystemTempSlow
--:--:-- --:--:-- --:--:-- --:--:--
500
400
300
200
100
0
Cell Temp (ºC)
1234
Time axis: Measured in either MM:SS (Fast Mode) or HH:MM:SS (Slow Mode). Time is referenced to system clock.
View change buttons: Press to change the time span of the chart.
Real-Time Data: View current cell temperature.
System: Press to return to the System screen.
Power + Energy, Inc.
PE9000S Operations Manual 18
Diagnostics The Diagnostics screen provides sensor displays and the button to perform a helium leak check.
Leak Check mode is provided so that membrane integrity may be examined. This is achieved by attaching a helium source to the Helium Inlet port (Port F) while attaching a helium detection device to the Leak Check port (Port E). Active Controls: System Leak Check Mode Configure Controls (logged on user must have access level 900 or higher)
SystemDiagnostics
Leak Check
Current (A)123.1
P1 (PSIA)123.12
P2 (PSIA)123.12
P3 (PSIG)123.12
T1 1234
H2 Sensor 1234
Configure Controls
T31234
H2 C
N2 C
UPHC
HeLO
ByPC
H2 RC
MFM(SLPM)
123.1
System: Press to return to the System screen.
Leak Check: Press to go to the Helium Leak check mode
Configure Controls: used to access configuration panels
Power + Energy, Inc.
PE9000S Operations Manual 19
Alarms The system constantly monitors conditions for signs of malfunction. Should anything unusual occur, the system alarms page will register an alarm as shown below. Alarms may be examined by pressing the alarms button on the System screen, and should be checked for regularly. In the case of severe alarms, the system will display the alarms screen automatically. This function will be examined in greater detail in the “Alarm Messages” section.
Note: If the independent over temperature alarm is triggered, it can only be reset by opening the front panel and pressing the reset button on the OMRON overtemp monitor. Active Controls:
Return Clear Alarms Pop-up Disable Reset OV Temp
DESCRIPTION TYPE VALUE
XxXxXxXxXxXxXxXxXxXxX YYYY 9999.XxXxXxXxXxXxXxXxXxXxX YYYY 9999.XxXxXxXxXxXxXxXxXxXxX YYYY 9999.XxXxXxXxXxXxXxXxXxXxX YYYY 9999.
ReturnAlarms Clear AlarmsPopupsDisabled
Return: reverts to previous screen Clear Alarms: Removes
displayed alarms Disable Pop-up: Disables the automatic pop-up of this alarm screen when new alarms occur.
Power + Energy, Inc.
PE9000S Operations Manual 20
Configure Controls Note: This screen is password protected for level 900.
This panel allows the user to select a set up file that is different from the factory pre-set. It is only accessible to field service engineers. Active Controls:
System Back Next Load Configuration File
System Back Next
Load Configuration File
ComboBox1
Current Configuration FileabcdefghijklmnopqrstuvwxyzABCDEF
Configure Controls
System: Returns the display to the System Screen
Back: Returns the display to the previous screen
Next: Displays the next screen in sequence
Load Configuration File: Pressing will load a new configuration file from the memory card
Power + Energy, Inc.
PE9000S Operations Manual 21
PID Control Note: This screen is password protected for level 900 access.
This panel is used by P+E Engineers for system tuning. It is only accessible to field service engineers. Values on this panel should not be modified by the user.
Dead Band (0.1 C) Output (0.01% Duty)
Gain (0.01% Duty, 0.1 C, Sec) Limit Rate
+ DeadBand1234
- DeadBand-1234
MaxOutput-12345
MinOutput-12345
Kp12345
SlewTime
12345
Ki12345
Kd
12345
Heater (%)
PID Control NextBack
OutputBias
-12345
% On
123
1234 1234Setpoint Active Temp
System
Tune
System: returns the display to the system screen
Back: Returns the display to the previous screen
Next: Displays the next screen in sequence
Power + Energy, Inc.
PE9000S Operations Manual 22
PID Tuning
This panel is used by P+E Engineers for system tuning. It is only accessible to field service engineers. Active Controls: Back
Back: Returns display to previous screen in sequence
--:-- --:-- --:-- --:--
50.0
37.5
25.0
12.5
0.0
--:-- --:-- --:-- --:--
425418410403395
BackPID Tuning 1234 1234
Power + Energy, Inc.
PE9000S Operations Manual 23
Configure Users Note: This is a password protected screen for level 900. Active Controls: Edit Users Logout System Back Next
Back NextSystemEdit Users
Logout
Edit Users: Add or remove users, authorizations and passwords
System: Return to System Screen
Back: Return to previous screen
Next: Go to next screen in sequence
Logout: Logs out of password protected screen
Power + Energy, Inc.
PE9000S Operations Manual 24
PE9000S Operational Modes
The PE9000S is designed to be as simple to use as possible. The only decision that an operator will make is to decide which mode to set the system in, after which all control is automated. The PE9000S controller has three basic operational modes, which may be accessed from the Main screen:
• Operate Mode • Hydrogen Standby Mode • Shutdown Mode
In addition, Nitrogen Standby mode may be selected via the System screen. Leak Check Mode may be accessed from the Diagnostics screen. Shut Down Mode In Shut Down mode, UPH production ceases, nitrogen flows through the system, and after the hydrogen has been purged, the cell cools to room temperature. When the system is shut down, the Main screen should match the screen below:
A Press to activate Shut Down mode. The button will glow bright green if the
system accepts the mode command. B Nitrogen gas will flow into the system. H2 production will cease, as both
the H2 input valve and the UPH output valve are closed.
A
B
C
D
Power + Energy, Inc.
PE9000S Operations Manual 25
C If the UPH pressure is above 5 PSIA, the bypass valve will open to bypass the rotometer and ensure that UPH exits the system. Ensure that the bleed line is open when shutting down.
D The system heaters will continue to work in Shut Down mode until the UPH pressure falls below 5 PSIA. Cell temperature should then fall until the system is at room temperature.
• Should the UPH pressure not fall after 50 minutes, the heaters will turn off and the bypass valve will close.
Standby Mode In standby mode, the cell will be brought up to operational temperature. This mode is configured to flow either hydrogen or nitrogen through the purifier cell. The UPH valve will never open in standby mode. When the system is in standby, the Main screen should match the screen below:
Cell Temp1234
Feed BarG123.12
UPH BarG123.12
System
Operate
ShutDown
Standby
Main
Log On
Heat%DutyCycl
1234
Log Off
StandbyN2
H2 O
N2 C
UPHO
HeLC
ByPC
Valve Status
1 2 3 4 5 6 78 9 10 11 1213 14
Alm PopDisabled
A Press to activate Standby mode. The button will glow bright green if the
system successfully enters the mode. B Nitrogen will flow through the system until the cell reaches operating
temperature. The H2 valve will open at temperature setpoint. C In H2 standby mode, the UPH pressure will rise as UPH accumulates
behind the closed UPH valve until equilibrating with the feed pressure. The UPH pressure will not exceed the feed pressure.
D The system heaters are turned on, and the cell will heat up to 395ºC. They will then turn on periodically to maintain this temperature.
A
B
C
D
Power + Energy, Inc.
PE9000S Operations Manual 26
Operate Mode In operate mode, hydrogen flows through the system and is purified. The UPH is then output through the UPH line. To put the system into operate mode, the Main screen should match the screen below:
A Press to activate Operate mode. The button will glow bright green if the system successfully accepts the request.
B N2 will flow through the system until the cell is within 1ºC of operating temperature. H2 will then flow into the system and UPH will be produced.
C The system heaters are turned on, and the cell will heat up to 395ºC. They will then turn on periodically to maintain this temperature.
.
A
B
C
Power + Energy, Inc.
PE9000S Operations Manual 27
Nitrogen/Hydrogen Standby Mode Toggle
A This button is used to toggle between Hydrogen and Nitrogen feed for the Standby mode. Nitrogen should only be used if it is not possible to maintain the system with Hydrogen. This button should only be toggled when the unit is NOT in STANDBY mode. The setting toggle will be ignored by the system if the unit is already in STANDBY mode. B In Standby mode the heaters will maintain the cell at operating temperature (395 C).
A
Power + Energy, Inc.
PE9000S Operations Manual 28
Leak Check Mode To Select the Leak Check Mode, the System screen should match the screen below:
SystemDiagnostics
Leak Check
Current (A)123.1
P1 (PSIA)123.12
P2 (PSIA)123.12
P3 (PSIG)123.12
T1 1234
H2 Sensor 1234
Configure Controls
T31234
H2 C
N2 C
UPHC
HeLO
ByPC
H2 RC
MFM(SLPM)
123.1
Heat%DutyCycl
1234Set LineVoltage
123123 When the tubing is at vacuum pressure: A Press to activate Leak Check mode. A warning will be given to ask if you
want to continue. Press [OK] to continue, or close [X] to cancel and return to the current mode.
A
B C
WARNING - IMPORTANT! Remove cap and attach a regulated helium supply to the helium inlet port. Remove cap and attach a helium detection device to the Leak Check port (port E) to test for the presence of helium on the UPH output. 1. Ensure that the tubing between the Leak Check port and the detection device is pumped down to vacuum before continuing. 2. Verify the He pressure is above N2 pressure.
E
Power + Energy, Inc.
PE9000S Operations Manual 29
. B Helium must be injected into the system via the Helium Inlet port to test for
leaks in the membranes. C A second message will inform you of the current UPH pressure. Press
[OK] to acknowledge this message.. D The user will see a message to press “OK” when finished with the test.
Exit Leak Check Mode by selecting OK on the pop-up box.
• Helium may also be sprayed inside the chassis to check for leaks in welds and seals.
E Set the local line voltage here. It should be set to the supply voltage for the unit. Values are limited between 190 and 260 volts. This setting is used to compensate the heater duty cycle based on local voltage conditions, and should only need to be set once when installing the machine.
Note: Message boxes displayed on the interface have two buttons in the top, right-hand corner: [OK] and [X]. These are the equivalent of [OK] and [Cancel], respectively, on more common operating systems.
Ensure that the Helium pressure is greater than the Nitrogen pressure, otherwise the Helium check valve will not open.
WARNING – Ensure that your detection equipment is capable and prepared to handle the UPH pressure.
Power + Energy, Inc.
PE9000S Operations Manual 30
Power + Energy, Inc.
PE9000S Operations Manual 31
External Control
Ethernet Control The system may be configured to fully replicate the operating display over an Ethernet network using GE Fanuc View Runtime software. Contact Power + Energy for more information.
Discrete Inputs The PE9000W allows the user to put the system in Shut Down, Operate or Standby modes using Dry Contacts. See Electrical Specifications. These are four (4) covered terminal connections located on top of the unit, labeled “In” with terminal numbering 1-4. To send a command to the unit a connection must be made between terminal 4 and the terminal of the desired command for duration of 2 seconds. See the table below. EXAMPLE USER CIRCUIT
The system will remain in the selected mode after contacts are reopened and until a subsequent command is given. While a contact remains closed, the command will override any command given via ethernet or touchscreen. Should
Discrete Inputs Signal Terminal
Operate Command 1 Standby Command 2 Shut Down Command 3 Common (+ 24VDC) 4
1
4
switch
Power + Energy, Inc.
PE9000S Operations Manual 32
more than one contact be closed simultaneously, Shut Down will have the lowest priority, followed by Standby, and then the Operate Command will have the highest.
To ensure proper system operation the discrete inputs shall remain isolated from external circuitry. Power and Energy recommends the use of Dry Contact Mechanical Relays, Opto-isolated Solid State Relays or Momentary Push-Button Switches for switching the discrete inputs.
Power + Energy, Inc.
PE9000S Operations Manual 33
Discrete Outputs The PE9000W controller allows the user to be notified when the system is in Shut Down, Operate or Standby mode using dry contact outputs. In addition, a number of other status signals are available .Consult the factory for additional information. These are four (4) covered terminal connections located on top of the unit, labeled “Out” with terminal numbering 1-4. When the system is in Shut Down, Standby or Operate mode, 24VDC will be present between the relevant mode connector terminal (terminal 1, 2, or 3) and the common terminal (terminal 4). See the table below. EXAMPLE USER CIRCUIT
Should the system be set by a user to be in a mode other than Shut Down, Standby or Operate, no external signal will be given. Instead, it may be inferred that the system is in Helium Leak Check Mode, Flow Test mode, or is turned off.
Discrete Outputs Signal Terminal
Operate Signal 1 Standby Signal 2 Shut Down Signal 3 Signal Ground 4
1
4
Relay coil
To ensure proper system operation, the discrete outputs shall remain isolated from external circuitry. Power and Energy recommends the use of Dry Contact Mechanical Relays or Opto-isolated Solid State Relays for switching external equipment.
Power + Energy, Inc.
PE9000S Operations Manual 34
Alarm Messages
The PE9000W will monitor its performance and display an alarm message should an alarm condition be triggered. The system will also automatically switch to the Alarms screen if an alarm is triggered. While an alarm condition is true, the condition will be highlighted in red. If the condition returns to normal, it will be shown in green. Alarms which are not based on a sensor reading may be cleared using the “Clear Alarms” button located on the Alarms page. The following columns describe the alarm condition, and may be read from left to right by scrolling across the page. Description A description of the variable causing the alarm. Type The following refer to fixed limit alarms, which are triggered when a set value is reached. Only one can be associated with a single variable at any time. LOLO: Extremely low LO : Low HI : High HIHI: Extremely high The following refers to serious system errors. BIT: A bit [Boolean variable] set to 1 when a serious error occurs Value The value of the reading which caused the alarm to be triggered. Temperature will be in ºC, pressure will be in local units. Limit The threshold above or below which an alarm is activated. Date The date when the alarm was triggered. Time The time when the alarm was triggered. Variable The PLC variable which is linked to this alarm .
Any alarm will cause the alarm page to be displayed.
Power + Energy, Inc.
PE9000S Operations Manual 35
Alarms
Computer error/ failure The PE9000S control system consists of a Programmable Logic Controller (PLC) and its touchscreen interface (HMI). Should a PLC hardware error occur, you will see an alarm of the format: PLC:[error description] BIT On or Interface:[error description] BIT On We suggest that you use the “Clear Alarms” button to reset the alarms. Should the same condition persist, the alarm will reappear within a few seconds. If the problem persists, turn the power off for at least 120 seconds and then back on again. If the problem continues to persist, or indeed if any irregular operation seems to occur, the system may need to be serviced by a Power + Energy field engineer. In this case it is safest to shut down the machine and remove electrical power to the unit. Contact Power + Energy with a detailed description of any error messages you receive, as well as information about the operating conditions under which the incident occurred. NOTE: The PLC hardware errors are built-in GE Fanuc monitoring conditions that are not listed in the ALARM TABLE shown below.
Operating at or above HIHI pressure will void warranty
Power + Energy, Inc.
PE9000S Operations Manual 36
Shutdown Table AA AB AC AD AE AF Ag AG AH
Inte
rlock
Num
ber
Revi
sion
Service Description P&ID
Inst
rum
ent T
ag
P&ID
- Sh
eet
Refe
renc
e
Proo
f Tes
t Fre
quen
cy
Trip
Set
poin
tE
nglis
h
Eng
Uni
tsE
nglis
h
Trip
Set
poin
tM
etric
Eng
Uni
tsM
etric
Inc
/ Dec
Trip
Typ
e (S
oftw
are
/ Har
dwar
e)
Tim
e De
lay
- Sec
onds
Heat
er C
onta
ctor
H2 V
alve
Sol
enoi
dPL
C O
utpu
t Q00
01
N2 V
alve
Sol
enoi
dPL
C O
utpu
t Q00
02
Lk C
hk V
alve
Sol
enoi
dPL
C O
utpu
t Q00
05
Bypa
ss V
alve
Sol
enoi
dPL
C O
utpu
t Q00
04
UPH
Valv
e So
leno
idPL
C O
utpu
t Q00
03
H2 P
ress
ure-
up V
alve
Sol
enoi
dPL
C O
utpu
t Q00
15
Heat
er S
SR D
igita
lPL
C O
utpu
t Q00
07 a
nd Q
0008
Fina
l PLC
Seq
uenc
e St
ate
CON-143 ECV-415 ECV-416 ECV-419 ECV-418 ECV-417 ECV-420 YIC-1201 1 1 1 1 1 1 1 1
2P 2P 2P 1 1 2P 2P 1 112 MO 12 MO 12 MO 12 MO 12 MO
1 2 Heater Cell Temp Hi-Hi TSHH-302 1 T1:HIHI 430 °C Inc SW 0 ON OFF OFF OFF ON OFF OFF OFF SD2 2 Heater Cell Temp High-High TSHH-146 1 T2 460 °C Inc HW 0 OFF OFF OFF OFF ON OFF OFF OFF SD3 2 Emergency Shutdown HS-001A 1 PB-128 OFF - Dec HW 0 OFF OFF OFF OFF ON OFF OFF OFF SD4 OFF - Dec HW 0 OFF OFF OFF OFF ON OFF OFF OFF SD5 - Inc SW 0 ON OFF OFF OFF ON OFF OFF OFF SD6 2 PLC Failure QY-100 1 OFF - Dec SW 0 ON OFF OFF OFF OFF OFF OFF OFF -7 Input Pressure Low PSL-403 1 P1:LO 55 PSIG Dec SW 0 ON OFF OFF OFF ON OFF OFF OFF SD8 Instrument Air Low PSL-409 1 P3:LO, P3:LOLO 70 PSIG Dec SW 0 ON OFF OFF OFF ON OFF OFF OFF SD9 Delta Pressure High PDSH-410 1 P1P2Diff:HI 200 PSI ∆ Inc SW 0 ON OFF OFF OFF ON OFF OFF OFF SD10 Heater Control Thermocouple broken wire QY-302 1 T1:LOLO -40 °C Dec SW 0 ON OFF OFF OFF ON OFF OFF OFF SD11 Instrument Air High PSH-409 1 P3:HI 98 PSIG Inc SW 0 ON OFF OFF OFF ON OFF OFF OFF SD12 Input Pressure Sensor Fail PSLL-403 1 P1:LOLO -5 PSIA Dec SW 0 ON OFF OFF OFF ON OFF OFF OFF SD13 Input Pressure High PSHH-403 1 P1:HIHI 225 PSIG Inc SW 0 ON OFF OFF OFF ON OFF OFF OFF SD14 Output Pressure Sensor Fail PSLL-406 1 P2:LOLO -5 PSIA Dec SW 0 ON OFF OFF OFF ON OFF OFF OFF SD15 Output Pressure Sensor High PSHH-406 1 P2:HIHI 225 PSIG Inc SW 0 ON OFF OFF OFF ON OFF OFF OFF SD16 Temperature Drop during OPERATE mode TSL-302 1 T1:LO 360 °C Dec SW 0 ON OFF OFF OFF ON OFF OFF OFF SD
Notes1 Final PLC Sequence State will be achieved after a progression through a shutdown sequence
Interlock Letter
P&ID Instrument TagP&ID - SheetSafety Layer
Proof Test Frequency
Power + Energy, Inc.
PE9000S Operations Manual 37
ALARM TABLE
Seq
No.
Rev
isio
n
Service Description P&ID
- Sh
eet
P&ID
Inst
rum
ent T
ags
P&ID
Ala
rm T
ags
Con
trol
Pan
el D
evic
e Ta
gs
PLC
Inpu
t Typ
e
PLC
Sig
nal T
ype
Zero
Engl
ish
Span
Engl
ish
Eng
Uni
tsEn
glis
h
Nor
mal
Ope
ratio
nEn
glis
h
Zero
Met
ric
Span
Met
ric
Eng
Uni
tsM
etric
Nor
mal
Ope
ratio
nM
etric
Inc
/ Dec
Ala
rm S
etpo
int
Engl
ish
Ala
rm S
etpo
int
Met
ric
HM
I Inp
ut L
imit
Engl
ish
HM
I Inp
ut L
imit
Met
ric
Tim
e D
elay
- Se
cond
s
Latc
h (L
) / N
on-L
atch
(NL)
Safe
ty L
ayer
/ Im
port
ance
Lev
el
Hea
ter C
onta
ctor
H2
Valv
e So
leno
idPL
C O
utpu
t Q00
01
N2
Valv
e So
leno
idPL
C O
utpu
t Q00
02
Lk C
hk V
alve
Sol
enoi
dPL
C O
utpu
t Q00
05
Byp
ass
Valv
e So
leno
idPL
C O
utpu
t Q00
04
UPH
Val
ve S
olen
oid
PLC
Out
put Q
0003
H2
Pres
sure
-up
Valv
e So
leno
idPL
C O
utpu
t Q00
15
Hea
ter S
SR D
igita
lPL
C O
utpu
t Q00
07 a
nd Q
0008
ALA
RM
OU
T PL
C O
utpu
t Q00
014
ATT
ENTI
ON
OU
TPL
C O
utpu
t Q00
013
Ala
rm S
umm
ary
- HM
I
Ala
rm H
isto
ry -
HM
I
Notes1.0 Pressure Sensors
1.1 0 Input Pressure P1 LoLo 1 PT403 AI Voltage 0 500 PSIG 200 -5 - - 0 NL ON OFF ON X X1.2 0 Input Pressure P1 Lo 1 PT403 AI Voltage 0 500 PSIG 200 55 - - 0 NL ON OFF ON X X1.3 0 Input Pressure P1 Hi 1 PT403 AI Voltage 0 500 PSIG 200 220 - - 0 NL ON ON OFF X X1.4 0 Input Pressure P1 HiHi 1 PT403 AI Voltage 0 500 PSIG 200 225 - - 0 NL ON OFF ON X X1.5 0 Output Pressure P2 LoLo 1 PT406 AI Voltage 0 500 PSIG 0-150 -5 - - 0 NL ON OFF ON X X1.6 0 Output Pressure P2 Hi 1 PT406 AI Voltage 0 500 PSIG 0-150 220 - - 0 NL ON ON OFF X X1.7 0 Output Pressure P2 HiHi 1 PT406 AI Voltage 0 500 PSIG 0-150 225 - - 0 NL ON OFF ON X X1.8 0 P1P2Diff Hi N/A N/A 0 500 PSI 180 200 - - 0 NL ON OFF ON X X
2.0 Heating System2.1 0 Heater Temp T1 LoLo 1 TE302 AI Type K T/C -270 1622 °C 0-400 -40 - - 0 NL ON OFF ON X X2.2 0 Heater Temp T1 Lo 1 TE302 AI Type K T/C -270 1622 °C 0-400 360 - - 0 NL ON OFF ON X X2.3 0 Heater Temp T1 Hi 1 TE302 AI Type K T/C -270 1622 °C 0-400 440 - - 0 NL ON ON OFF X X2.4 0 Heater Temp T1 HiHi 1 TE302 AI Type K T/C -270 1622 °C 0-400 460 - - 0 NL ON OFF ON X X2.5 0 Heater Current CT HIHI 1 IT239 AI 4-20mA DC 0 50 A 0-18 21000 - - 0 NL ON ON OFF X X2.6 0 Heater Temp T2 HiHi 1 TE147 N/A Type K T/C -270 1622 °C 0-400 460 - - 0 L OFF OFF ON X X
3.0 General State Transition Error3.1 0 GoToES fault state QY001 N/A SW register 1 - - 0 NL ON OFF OFF OFF ON OFF OFF OFF OFF ON X X
4.0 System Utilities4.1 0 PLC Failure 1 QY001 N/A SW register 1 0 NL ON OFF OFF OFF OFF OFF OFF OFF OFF OFF X X4.2 0 Cabinet Temp T3 LoLo N/A AI Type K T/C -270 1622 °C n/a 0 NL ON ON OFF X X4.3 0 Cabinet Temp T3 Lo N/A AI Type K T/C -270 1622 °C n/a 0 NL ON ON OFF X X4.4 0 Cabinet Temp T3 Hi N/A AI Type K T/C -270 1622 °C n/a 0 NL ON ON OFF X X4.5 0 Cabinet Temp T3 HiHi N/A AI Type K T/C -270 1622 °C n/a 0 NL ON OFF ON X X4.6 0 Cabinet Temp T4 LoLo N/A AI Type K T/C -270 1622 °C n/a 0 NL ON ON OFF X X4.7 0 Cabinet Temp T4 Lo N/A AI Type K T/C -270 1622 °C n/a 0 NL ON ON OFF X X4.8 Cabinet Temp T4 Hi N/A AI Type K T/C -270 1622 °C n/a 0 NL ON ON OFF X X4.9 Cabinet Temp T4 HiHi N/A AI Type K T/C -270 1622 °C n/a 0 NL ON OFF ON X X4.10 Instrument Air P3 LoLo 1 PT409 AI Voltage 0 120 psig 75 -5 -2 ON OFF ON X X4.11 Instrument Air P3 Lo 1 PT409 AI Voltage 0 120 psig 75 72.7 0 NL ON OFF ON X X4.12 Instrument Air P3 Hi 1 PT409 AI Voltage 0 120 psig 75 98 0 NL ON OFF ON X X4.13 Hydrogen Detector In 1 ASHH422 DI DI 0 1 0 1 0 L ON OFF ON X X 1
5.0 Emergency Shutdown5.1 0 Emergency Shutdown 1 HS001A YIC-108 DI On / Off 1 L OFF OFF ON X X5.2 0 Emergency Shutdown - Remote 1 HS001B YIC-108 DI On / Off 1 L OFF OFF ON X X
See interlock 3 - Shutdown TableSee interlock 4 - Shutdown Table
See interlock 8 - Shutdown TableSee interlock11 - Shutdown TableSee interlock 5 - Shutdown Table
See interlock 8 - Shutdown Table
Basis of Setpoint
See interlock 16 - Shutdown Table
See interlock 1 - Shutdown Table
See interlock 2 - Shutdown Table
Notes
See interlock 12 - Shutdown TableSee interlock 7 - Shutdown Table
See interlock 13 - Shutdown TableSee interlock 14 - Shutdown Table
See interlock 15 - Shutdown Table
See interlock 10 - Shutdown Table
The Omron K8-ABTH over-temperature monitor must be reset manually if triggered. The reset button is on the front of the unit and should be depressed with a small instrument such as a pen. The red alarm light will extinguish when the unit is reset. Do not change the dial switch settings on the unit. Doing so may disable the over-temperature protection.
Power + Energy, Inc.
PE9000S Operations Manual 38
Appendix A: Electrical Schematic Drawings
Electrical Service Connection 200 to 240 VAC, 50~60 Hz, 25 amperes service rating
Wire connection is: HOT, NEUTRAL, GROUND Unit maximum current draw is approximately 16.3 amps at 200VAC .
Power + Energy, Inc.
PE9000S Operations Manual 39
Power + Energy, Inc.
PE9000S Operations Manual 40
Power + Energy, Inc.
PE9000S Operations Manual 41
Power + Energy, Inc.
PE9000S Operations Manual 42
Appendix B: Chassis Dimensional Drawings
Power + Energy, Inc.
PE9000S Operations Manual 43
Appendix C : Outlet Flow Curves
Power + Energy, Inc.
PE9000S Operations Manual 44
Rotameter settings for controlling bleed outlet flow
ROTAMETER FLOW RATES, H2 & N2 ccpm VS BALL
02468
10121416182022
0 5 10 15 20 25 30 35 40 45 50 55 60 65Flow Tube '6G07R3' 1/4" BLACK GLASS - CENTER of BALL
SLP
M
(SLPM HYDROGEN) (SLPM NITROGEN)
Power + Energy, Inc.
PE9000S Operations Manual 45
Appendix C : Leak Check
Power + Energy, Inc.
PE9000S Operations Manual 46
Change Log
Date Description Page Initials2009Nov11 Manual revised for Version 4.1.2 software all EP
2009Nov11 Manual revised for hardware rev.6 all EP
2009Nov18 Alarm setpoints table 37 EP
2009Nov18 Schematic 40-42 EP
2009Dec17 Manual revised for Version 4.1.3 software 5-8,11, 12, 19, 30, 36, 37, 40, 43, 45
EP